Winterwarm HR-seriesThe condensing unit air heater which combines efficient heating with
energy savings and high comfort.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. .
Characteristics Winterwarm HR:
• High efficiency (on ECA list)• Energysaving (up to 25% compared to conventional heaters)
• Stainless steel heatexchanger as standard
• Modulating burner• OpenTherm Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
For many years now, suspendedunit air heaters have beenemployed worldwide to heatindustrial buildings. Researchfrom the ‘Gasunie’ (NL) regardingvarious industrial heatingsystems has confirmed thatdirect heated gas-fired air heating is one of the most efficient heating methods.
In general
The Winterwarm HR series (high
system efficiency) combines efficien-
cy, energy savings and total comfort
control through several unique design
characteristics. The OpenTherm con-
trol makes it easy to operate the
heater and realise a comfortable
environment in the room.
Technical features
The HR is a condensing unit air
heater with axial fan. The efficiency
of the heaters is more than 106%.
The premix burner allows the heater
to modulate back to 20% of its
maximum capacity. This implicates
that the heater can very precisely
adjust its heat output to the demand
received through the room thermostat.
Therefore the energy consumption is
as low as possible. As the range of the
HR-series goes up to 150 kW, a lot of
energy can be saved by applying an
HR-heater instead of a conventional
unit air heater. Measurements by the
dutch national gas institute have
proven that these savings can add up
to 25%!
The heat exchanger is made from high
grade stainless steel and has a
guarantee period of 5 years.
Condensation discharge
The HR heaters can realize an output
of 106 %. This high efficiency requi-
res a condensation discharge system
which is located at the bottom of the
heater. For the installation on the
heater unit a siphon is supplied. Any
further required drain pipes are not
supplied. This means that an extra
siphon or gooseneck is required to be
fitted before the sewage.
Suspension
The HR is provided with 4 suspension
points M10 on top of the heater. A set
of solid cantilever brackets can be
ordered along to suspend the heater
from the wall. The heater can be
either suspended from these brackets,
or be placed on top of them. This sus-
pension set consists of 2 U-sections
with 2 supports. For suspension from
the ceiling threaded bar M10 can be
used.
F
CD
H
J
K
øM
Gas
F
P
N
R
S
4xM10
T
U
Measurements
A B C D F G Gas H J K M N P R S T U
40 910 825 770 150 180 110 3/4” 560 470 120 80 137 250 115 190 100 295
60 1155 825 770 150 180 110 3/4” 560 715 140 100 137 240 115 190 100 295
80 1340 825 770 150 180 110 1” 560 890 140 100 137 240 115 190 100 295
100 1630 825 770 150 180 110 1” 560 1180 140 100 137 240 115 190 100 295
150 1890 1000 1000 180 190 175 1” 850 1425 225 130 165 235 140 170 75 295
A
B
G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flue terminal
The installation of the combustion air
supply and the combustion gas
discharge must meet the general
prescriptions for high efficiency flue
terminals. Winterwarm has a complete
range of stainless steel flue terminals
and extra lenghts/bends available.
As the HR is provided with a flue
booster one can apply either a
horizontal (wall) or a vertical (roof)
flue terminal. The length of the flue
should not exceed 10 m taking into
account that each 45˚ elbow counts as
1 m length and each 90˚ elbow counts
as 2 m length. The dimensions of the
flue is 80, 100 or 130 depending on
the type of heater.
Controls
The HR heaters are provided with a
OpenTherm protocol, controled by an
OpenTherm clock thermostat. This is
a low voltage clock thermostat which
is programmable per day and can con-
trol 1 heater. Also it is provided with
frost protection, summer ventilation
position and a reset function.
If desired, a remote sensor can be
attached so that the control can
be placed elsewhere.
Open Therm Thermostat
A B d D HOH
40 1290 660 80 125 120
60 1170 590 100 150 140
80 1170 590 100 150 140
100 1170 590 100 150 140
150 1345 928 130 200 230
A B d D HOH
40 560 250 80 125 120
60 900 400 100 150 140
80 900 400 100 150 140
100 900 400 100 150 140
150 930 400 130 180 265
Roof terminal Wall terminal
Winterwarm: leadingWinterwarm has been engaged in the development, production and sales of industrial heating in Europe since 1936.
The company not only specialises in indirect fired unit air heaters, but also sells radiant tubes, rooftops,
water heaters, destratification fans and direct fired heaters for the agricultural and horticultural industry.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Famous Winterwarm quality
• 70 years of experience• ISO 9001-2000 certified• Quick delivery• Reliable
Winterwarm BVIndustrieweg 8 Winterswijk The NetherlandsP.O.Box 36 NL-7100 AA Winterswijk The NetherlandsTel. +31 (0)543 54 63 00 Fax +31 (0)543 54 63 10www.winterwarm.nl [email protected]
Winterwarm UK Ltd. Unit H3, Taylor Business Park, Warrington Road, Risley, Warrington, Cheshire WA3 6BLTel. +44 (0)870 90 89 906 Fax +44 (0)192 57 62 996 www.winterwarmuk.com [email protected]
Technical data
Type Unit HR 40 HR 60 HR 80 HR 100 HR 150
Nominal heat input (Hs.) kW 44.4 66.7 88.8 114.4 166.7
Nominal heat input (Hi.) kW 40 60 80 103 150
Efficiency max. heat input 100% % 94.8 94.2 94.3 94.2 94.8
Efficiency partial heat output 30% % 105.7 105.8 105.8 105.6 104.9
Nominal heat output kW 37.9 56.5 75.4 97 142.2
Gas consumption G20 (hi/low) m3/h 4.18-0.88 6.22-1.34 8.16-2.25 10.67-2.94 15.3-3.37
Nominal gas supply pressure mbar 20 20 20 20 20
Gas consumption G31 kg/h 3.17-0.64 4.72-1.04 6.22-1.72 8.03-2.29 11.69-2.57
Nominal gas supply pressure mbar 37/50 37/50 37/50 37/50 37/50
Gas connection G” 3/4” 3/4” 3/4” 3/4” 3/4”
Dimensions flue terminal ø 80 100 100 100 100
Electrical connection V/Hz 230/50 230/50 230/50 230/50 230/50
Electrical consumption W 300 400 650 750 1400
Air flow rate m3/h 5000 6500 10000 12500 18500
Temperature increase T 22.8 26.3 22.8 23.5 23.1
Throw horizontal (max.-min.) m 26-36 26-36 32-46 36-50 48-68
Sound level* dB(A) 48 51 52 52 58
Minimum suspension height m 1.7 1.7 1.7 1.7 1.7
Weight kg 95 111 136 155 230
* measured 5m. in front of heater