why we need to calculate heating load ? a)to find how much energy we are going to use? b)to size the...
TRANSCRIPT
Why we need to calculate heating load ?
A) To find how much energy we are going to use?
B) To size the HVAC equipment?
C) To estimate the cost of the building?
D) A and C
E) B and C
F) A, B and C
Objectives
• Finish the heating Load Calculation
• Learn and Practice the calculation of cooling load of buildings
Heat transfer in the building Not only conduction and convection !
Infiltration
• Air transport Sensible energy
Previously defined
• Q = m × cp × ΔT [BTU/hr, W]
• ΔT= T indoor – T outdoor
• or Q = 1.1 BTU/(hr CFM °F) × V × ΔT [BTU/hr]
Latent Infiltration and Ventilation
• Can either track enthalpy and temperature and separate latent and sensible later:• Q total = m × Δh [BTU/hr, W]
• Q latent = Q total - Q sensible = m × Δh - m × cp × ΔT
• Or, track humidity ratio:• Q latent = m × Δw × hfg
Ventilation Example
• Supply 500 CFM of outside air to our classroom• Outside 90 °F 61% RH
• Inside 75 °F 40% RH
• What is the latent load from ventilation?• Q latent = m × hfg × Δw
• Q = ρ × V × hfg × Δw
• Q = 0.076 lbair/ft3 × 500 ft3/min × 1076 BTU/lb × (0.01867 lbH2O/lbair - .00759 lbH2O/lbair) × 60 min/hr
• Q = 26.3 kBTU/hr
What is the difference between ventilation and infiltration?
A) Ventilation refers to the total amount of air entering a space, and infiltration refers only to air that unintentionally enters.
B) Ventilation is intended air entry into a space. Infiltration is unintended air entry.
C) Infiltration is uncontrolled ventilation.
Ground Contact
• Receives less attention:• 3-D conduction problem• Ground temperature is often much closer to indoor air
temperature
• Use F- value for slab floor [BTU/(hr °F ft)] • Note different units from U-value• Multiply by slab edge length• Add to ΣUA• Still need to include basement wall area• Tao and Janis Tables 2.10 and 2.11
More details in ASHRAE handbook -Chapter 29
Ground Contact• 3-D conduction problem
• Ground temperature is often much closer to indoor air temperature
• Use F- value for slab floorMultiply by slab edge length
and Add to ΣUA
Where do you get information about amount of ventilation required?
• ASHRAE Standard 62• Table 2
• Tao and Janis Table 2.9A
Weather Data
• Table 2-2A (Tao and Janis) or• Chapter 28 of ASHRAE Fundamentals
• For heating use the 99% design DB value• 99% of hours during the winter it will be warmer
than this Design Temperature• Elevation, latitude, longitude
• For cooling use the 1% DB and
coincident WB for load calculations
• 1% of hours during the summer will be warmer than this Design Temperature
• Use the 1% design WB for specification of equipment
Weather Data
Cooling Load Calculation
Solar Gain• Affects conductive heat gains because outside surfaces
get hot• Use Q = U·A·ΔT
Replace ΔT with TETD – total equivalent temperature differential
Q = U·A· TETD
• Tables 2-12 – 2-14 in Tao and Janis
Replace ΔT with CLTD (Tables 1 and 2 Chapter 29 of ASHRAE Fundamentals)
Solar Gain
TETD depends on:
- orientation,
- time of day,
- wall properties - surface color- thermal capacity
Glazing
• Q = U·A·ΔT+A×SC×SHGF• Calculate conduction normally Q = U·A·ΔT
• Use U-values from NFRC National Fenestration Rating Council
• ALREADY INCLUDES AIRFILMS• http://cpd.nfrc.org/pubsearch/psMain.asp
• Use the U-value for the actual window that you are going to use
• Only use default values if absolutely necessary• Tao and Janis - no data • Tables 4 and 15, Chapter 31 ASHRAE Fundamentals
Shading Coefficient - SC
• Ratio of how much sunlight passes through relative to a clean 1/8” thick piece of glass
• Depends on• Window coatings• Actually a spectral property• Frame shading, dirt, etc.• Use the SHGC value from NFRC for a particular window
SC=SHGC/0.87• Lower it further for blinds, awnings, shading, dirt
•http://cpd.nfrc.org/pubsearch/psMain.asp
More about Windows
• Spectral coatings (low-e)• Allows visible energy to pass, but limits infrared
radiation• Particularly short wave
• Tints
• Polyester films
• Gas fills
• All improve (lower) the U-value
Low- coatings
Internal gains
• What contributes to internal gains?
• How much?
• What about latent internal gains?
Internal gains
• ASHRAE Fundamentals ch. 29 or handouts• Table 1 – people
• Table 2 – lighting, Table 3 – motors
• Table 5 – cooking appliances
• Table 6 -10 Medical, laboratory, office
• Tao and Janis - People only - Table 2.17
The latent load of a building is needed to calculate __________.
A) Heating only
B) Cooling only
C) Heating and cooling
Summary:Heating and cooling loads
• Heating - Everything gets converted to a UA, UF, mcp • Sum and multiply it by the design temperature difference
• Cooling loads have additional components• Internal gains
• Solar gain
• Increased gain through opaque surfaces
• Also need to calculate latent cooling load
Heating and Cooling Load Procedures
• Handout• Calculate heating load• Calculate cooling load• Need to also calculate latent cooling load
Conclusions
• Conduction and convection principles can be used to calculate heat loss for individual components
• Air transport principles used to account for infiltration and ventilation
• Radiation for solar gain and increased conduction
• Include sensible and internal gains
Reading Assignment
• Readings: Tao and Janis
Chapter 2
Example problem• Calculate the cooling load for the building in Pittsburgh PA with the geometry shown on
figure. On east north and west sides are buildings which create shade on the whole wall.
• Windows: Horizontal slider, Manufacturer: American Window Alliance, Inc, CDP number AMW-K-3-00028 ttp://cpd.nfrc.org/pubsearch/psMain.asp• Walls: 4” face brick + 2” insulation + 4” concrete block, Uvalue = 0.1, Dark color• Roof: 2” internal insulation + 4” concrete , Uvalue = 0.120 , Dark color• Below the building is basement wit temperature of 75 F.
• Internal design parameters:• air temperature 75 F• Relative humidity 50%
• Find the amount of fresh air that needs to be supplied by ventilation system.
Example problem• Internal loads:
• 10 occupants, who are there from 8:00 A.M. to 5:00 P.M.doing moderately active office work
• 1 W/ft2 heat gain from computers and other office equipment from 8:00 A.M. to 5:00 P.M.
• 0.2 W/ft2 heat gain from computers and other office equipment from 5:00 P.M. to 8:00 A.M.
• 1.5 W/ft2 heat gain from suspended fluorescent lights from 8:00 A.M. to 5:00 P.M.
• 0.3 W/ft2 heat gain from suspended fluorescent lights from 5:00 P.M. to 8:00 A.M.
• Infiltration:• 0.5 ACH per hour
Example solution
• SOLUTION steps (see handouts):
• 1. Calculate cooling load from conduction through opaque surfaces using TETD.
• 2. Calculate conduction and solar transmission through windows.
• 3. Add sensible internal gains and infiltration. • 4. The result is your raw sensible cooling load. • 5. Calculate latent internal gains. • 6. Calculate latent gains due to infiltration. • 7. The sum of 5 and 6 is your raw latent cooling load.
Example solution
• SOLUTION:
• For which hour to do the calculation ?
• With computer calculation for all and select the largest.
Example solutionFor which hour to do the calculation when you do manual calculation?
• Identify the major single contributor to the cooling load and do the calculation for the hour when the maximum cooling load for this contributor appear.
• For example problem major heat gains are through the roof or solar through windows!
Roof: maximum TETD=61F at 6 pm (Table 2.12)South windows: max. SHGF=109 Btu/hft2 at 12 am (July 21st Table 2.15 A)
If you are not sure, do the calculation for both hours: at 6 pm
Roof gains = A x U x TETD = 900 ft2 x 0.12 Btu/hFft2 x 61 F = 6.6 kBtu/hWindow solar gains = A x SC x SHGF =80 ft2 x 0.71 x 10 Btu/hft2 = 0.6 kBtu/h total = 7.2 kBtu/h
at 12 am Roof gains = A x U x TETD = 900 ft2 x 0.12 Btu/hFft2 x 30 F = 3.2 kBtu/hWindow solar gains = A x SC x SHGF =80 ft2 x 0.71 x 109 Btu/hft2 = 6.2 kBtu/h total= 9.4 kBtu/h
For the example critical hour is July 12 AM.
Solution
• On the board
Example 2 How to calculate Cooling Load for
HVAC design
• If the room with no outdoor influence has 4 lighting fixtures with 100 W each and 10 students,
what is the needed relative humidity and temperature of supply air if only required amount of fresh air is supplied
and room temperature is 75 F and RH 50%?