wholesale tev
TRANSCRIPT
©2012 Sporlan Division, Parker Hannifin Corporation
©2012 Sporlan Division, Parker Hannifin Corporation
THERMOSTATIC EXPANSION
VALVES (TEV’S)
Wholesaler Training Program – Part 1
©2012 Sporlan Division, Parker Hannifin Corporation
Thermostatic Expansion Valves
General
Thermostatic expansion valves and solenoid valves
were Sporlan’s first products. Sporlan calls the
device a “thermostatic expansion valve” abbreviated
“TEV”. Among industry person- nel it may also be
referred to as a “Thermo Valve”, “TX Valve” or just
“expansion valve”.
The TEV product line has grown to include many
different body styles for use on many refrigerants for
many applications.
©2012 Sporlan Division, Parker Hannifin Corporation
Thermostatic Expansion Valves
Its principle of operation is explained in Bulletins 10-9
and 10-10 but in the simplest of terms, it is merely a
refrigerant metering device to regulate the proper
amount of refrigerant flow into the evaporator. It
accomplishes this by sensing and regulating the
amount of superheat at the outlet of the evaporator
where the bulb is fastened to the suction line.
Superheat is a term that will be heard frequently
when discussing TEV’s. In order to become more
knowledgeable on their operation a more thorough
study of “superheat” is suggested.
©2012 Sporlan Division, Parker Hannifin Corporation
The Valve Types
Basic valve types have always been identified by
letters. Unfortunately there is a limit to the number of
letters in the alphabet so as Sporlan has expanded
its line over the years it has been necessary to use
some letters a second time usually after the original
valve model has discontinued for a period of time.
For the sake of simplicity each standard cataloged
valve has certain standard specifications supplied
unless otherwise specified. Some deviations are
possible on special order but are limited and should
be avoided to eliminate delays and special handling.
The following describe the standard specifications.
©2012 Sporlan Division, Parker Hannifin Corporation
Type of Connections
Flare (also called SAE):
To connect a copper line to a valve having an SAE
connection, it is only necessary to “flare” the end of
the line and connect to the valve with the correspon-
ding size of flare nut. SAE connections are usually
1/4, 3/8 or 1/2. 5/8 is rare and larger sizes are not
available.
Valve types F, G and C have flare connec- tions as a
standard in the sizes shown in Bulletin 10-10.
©2012 Sporlan Division, Parker Hannifin Corporation
Type of Connections
Solder (also called “sweat” or ODF):
The nominal size for refrigeration tubing is measured
on the outside diameter (OD). Thus a 7/8 line size is
7/8” OD. To connect this line to the inlet of an
expansion valve, a 7/8 ODF (outside diameter -
female) inlet connection will allow the tube to slide
inside the fitting where the brazing or soldering takes
place.
Because of the never-ending combination of fitting
sizes the wholesaler normally stocks only the
standard connections. If the line size does not match
the standard connection, the use of reducing bushing
and/or couplings will allow the connection to be
made.
Standard valve types EG, S, SBF, EBS, O, SQ and
EQ are furnished with ODF connections.
©2012 Sporlan Division, Parker Hannifin Corporation
Type of Connections
ODF flange connections:
A TEV with ODF flange connections has bolt-on steel
flanges with a brass bushing. The line is soldered to
the ODF bushing. The flange fits over the bushing
and is bolted to the valve body.
Once the bushings are brazed to the line installation
and removal of this type valve only requires bolting or
unbolting of the flange.
Types H, M, V and W are furnished with ODF flange
connections.
©2012 Sporlan Division, Parker Hannifin Corporation
Type of Connections
FPT (Female pipe thread) connections:
Type D and A valves for ammonia have FPT flange
connections. Types H, M and V valves that normally
come with ODF flange connections can be adapted
to FPT with the H valve requiring special adaptors.
©2012 Sporlan Division, Parker Hannifin Corporation
Other Standard Specifications
Nominal capacity:
The nominal capacities available for every valve type
is shown in Bulletin 10-10 for each refrigerant.
Capillary tube length:
The standard length for each valve type listed can
vary from 30 inches for the type F to 10 feet for the
W, D and A valves.
Size of power element:
Each valve type is made with a particular size of
power element (example: 53, 83, 33, et cetera).
The bulb size is determined by the thermostatic
charge furnished. Information on both element and
bulb size is also shown for each valve type in Bulletin
10-10.
©2012 Sporlan Division, Parker Hannifin Corporation
Other Standard Specifications
Size and type of external equalizer connection:
All standard cataloged valves with SAE (Flare) and
flange connections have 1/4 SAE equalizer fittings as
standard. Those with ODF (Solder) connections are
furnished with 1/4 ODF external equalizer fittings.
The flanged H, M, V and W valves have 1/4 SAE
equalizer fittings. The D and A valves have 1/8 FPT
equalizer fittings.
©2012 Sporlan Division, Parker Hannifin Corporation
More About Refrigerants and
Thermostatic Charges
Refrigerants
The material used in most valve types are compatible
with all common refrigerants. The principle exception
is the D and A valves which are used on ammonia
only.
The code letter for the refrigerant is always found in
the valve’s designation (GV is a type G valve for “22”
and GJ is for 134A). A complete list of refrigerants
and their letter code is in Bulletin 10-10.
©2012 Sporlan Division, Parker Hannifin Corporation
More About Refrigerants and
Thermostatic ChargesThermostatic Charges
Like body types and refrigerants, thermostatic charges are also identified by a letter. Generally, each charge covers an evaporator temperature range but some other application considerations can be involved particularly on the pressure-limit or maximum operating pressure (MOP) charges designated by the addition of the letter “P” and sometimes a number (example CP100).
Many of the thermostatic charges used with the newer refrigerants are interchangeable with the older refrigerants being replaced. As an example, the following refrigerants use the same thermostatic charge: R-12, R-134a, R-401A, and R-409A. This is further illustrated here for thermo- static charges use for commercial temperature ranges of -10°F to 50°F.
The pressure limit charges (MOP) will limit the amount a TEV opens so that the evaporator pressure will not exceed the “Nominal System” values shown. This can be an important feature at pull-down or after a defrost.
©2012 Sporlan Division, Parker Hannifin Corporation
More About Refrigerants and
Thermostatic ChargesInternal or external equalizer
The purpose of the external equalizer (designated by the letter “E”) is to compensate for pressure drop through the evaporator and/or refrigerant distributor. It is generally known if a refrigerant distributor will be used on the evaporator. However, it is rare that wholesaler customers will know evaporator pressure drop. Therefore, the following rule-of-thumb is suggested:
A. Use the externally equalized valve on any evaporator equipped with a refrigerant distributor.
B. Use the externally equalized valve when there is any doubt and particularly on valves with nominal capacities above 1 ton. There is no disadvantage to using it even if it is not required.
C. Use the internally equalized valve on small tonnage TEV’s (below 1 ton) when it is known that the evaporator is single-circuit with no refrigerant distributor.
©2012 Sporlan Division, Parker Hannifin Corporation
Balanced Port Thermostatic
Expansion Valves
The port construction of standard thermo- static
expansion valves is such that the pressure drop
across it (difference between inlet and outlet) tends
to open the valve. This pressure imbalance has little
effect on the TEV’s operation under most normal
operating conditions, particularly on small valves.
©2012 Sporlan Division, Parker Hannifin Corporation
Balanced Port Thermostatic
Expansion Valves
On larger valves with greater port areas it becomes
more of a factor and our type V and W valves have
always been made with semi balanced ports. The
type “O” valve was later introduced which has a
completely balanced port.
©2012 Sporlan Division, Parker Hannifin Corporation
Balanced Port Thermostatic
Expansion Valves
The type “O” valve with its balanced port construction
has been widely accepted for its ability to maintain
close control under conditions of varying inlet
pressure and fluctuating loads. With its large capacity
ratings the O valve is ideally suited for chillers or
other applications where head pressure can fall and
loads can change.
©2012 Sporlan Division, Parker Hannifin Corporation
Balanced Port Thermostatic
Expansion Valves
The balanced port version of the F valve is the Type
BF, EBF and SBF. The balanced port S valve is type
EBS.
Bulletin 10-10 provides further information on the BF
valve.
©2012 Sporlan Division, Parker Hannifin Corporation
Power Elements
The power elements are replaceable on most standard TEV’s.
The power element consists of the bulb, capil- larytube, diaphragm case assembly and the thermostatic charge it contains. Replacement power elements are supplied in kit form with a prefix KT (for Kit, Thermostatic) to the designation followed by a number indicating the lock ring size, as well as the refrigerant letter designation. The length of the cap tube should also be specified when ordering. This KT-83-VCP100 indicates the following:
1. KT - 83 Element size 83
2. V Refrigerant 22
3. CP100 Thermostatic charge CP100
©2012 Sporlan Division, Parker Hannifin Corporation
About Changing Power Elements
The type “Q” Valve is designed to provide the
flexibility for changing power elements and nominal
capacities. For more information about the Type Q
Valve, there is a separate program available covering
its features. When other standard valves are involved
in power element changes, other considerations are
involved:
©2012 Sporlan Division, Parker Hannifin Corporation
About Changing Power Elements
When changing from one thermostatic charge to another using the same refrigerant, the nominal capacity remains the same and the stamping on the valve body will still reflect the correction identification. However, the customer should be advised that a super-heat adjustment might be required.
When changing from one refrigerant to another, the nominal capacity will probably change. As an example, the same port size is rated for nominal 5 tons on R-22 and 3 tons on R-12 and R-134a. Also, it is very likely that a superheat adjustment will be required because of variations in the superheat spring sizes. One other point to remember is that the identification stamped on the valve body, showing the original refrigerant and nominal capacity, will no longer correctly identify the valve. The Q valve design is such that these problems are eliminated.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEV
Wholesalers are often confronted with the problem of
supplying their customers with the correct TEV based
on information that is incomplete, or inaccurate.
When this occurs, asking the right questions can
often lead to a solution. Generally, one of the
following situations is involved:
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVSelection of a TEV for a new application
This can become a case of how precise the customer may be in his requirements. One extreme is the engineer who supplies every detail on the system characteristics. On the other end of the scale is the service mechanic who may say, “give me a 5 ton valve!”
Finding the correct valve capacity
The nominal capacity rating (except for ammonia) is based on:
a. 40 degrees F evaporator temperature
b. 100 PSI pressure drop across TEV (60 PSI for R-134a)
c. 100 degrees F vapor-free liquid entering TEV.
TEV’s for air conditioning applications including water chillers will usually fall roughly into the conditions shown above. This means that a nominal 5 ton valve will be selected for a 5 ton or 5 horsepower system. This situation calls for an SVE-5- CP100 or SVE-5-GA.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVFor refrigeration applications the selection can become a little more involved, particularly when operating conditions become more variable.
TEV capacity tables assume that the pressure drop across it will be in accordance with the evaporator pressure that is expected at the particular evaporator temperature. In other words, with a constant discharge pressure (TEV inlet) the pressure drop increases as the evaporator pressure (temperature) is reduced. Therefore, for R-22 and equivalent refrigerants, the pressure drop is assumed to be 100 psi at a 40°F evaporator, 125 psi at 0°F to 10°F evaporator, 150 psi at -10°F to -20°F, and 175 psi drop at -40°F. The entering liquid temperature is based on 100°F at all evaporator temperatures.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEV
In the example shown, valve types NI, F, EF, G, &
EG all have rated capacities of 1.09 tons at a 20°F
evaporator and standard conditions of 125 psi
pressure drop and 100°F entering liquid
temperature.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEV
When the entering liquid temperature and/or
pressure drop across the TEV is significantly
different from stated standard
conditions, correction factors are applied to the
TEV’s rated capacity as shown in the capacity
tables.
In this example, an adjusted capacity is
calculated for the valve selected from the
capacity table based on standard conditions at a
20°F evaporator.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEV
The correction factor for 70°F liquid is found from
the table to be 1.17 and the factor for 100 psi is
shown as 0.89. The two correction factors
multiplied by each other and then times the rated
capacity of 1.09 results in new capacity of 1.13
tons and the type EGVE-1 is chosen for a one ton
load.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVAssuming that a refrigerant distributor is used, a TEV with an external equalizer will be required. When determining the pressure drop through the evaporator, the drop across the distributor must be included. In this typical example, the suction pressure at the compressor is 43 psig, but the pressure at the outlet of the TEV is only 78 psig.
Therefore, an external equalizer is required designated by the letter “E”. Again, the purpose of the external equalizer is to compensate for the pressure drop through the evaporator and /or refrigerant distributor.
The final consideration is the thermostatic charge. Since the specified evaporator temperature is 20°F, a “C” charge is selected.
The complete designation for the selection is EGVE-1-C, 3/8 X 1/2 ODF-5”
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVSelecting a Replacement TEV For Another Sporlan Valve
• Standard Cataloged Valves
A. This is a case of getting the required information from the old valve not always an easy task!
B. Bulletin 210-60 will serve as a guide to directing the customer to the location of the identifying numbers and letters on the valve.
All Sporlan TEV’s have permanent identifying marks and most have an identifying label on the power element showing sufficient information to select a replacement. Unfortunately this label can become obliterated with age and it then becomes necessary to seek out the permanent markings as shown in Bulletin 210-60.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEV
Replacement of Special Non-Cataloged Valves
Sporlan manufactures many special TEV’s for OEM’s
- usually modifications of standard valves to meet the
particular requirements of their unit.
Identifying and selecting a replacement can often be
handled with the assistance of bulletins in the “210”
section of your wholesaler’s manual.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVThe special designations will usually be one of the following:
• Type I or BI valve (example - IVE-2-GA, BIVE-2-GA and BBIVE-2-GA): Sporlan type Q or RCVE valves can often be matched to the specifications of these models. The BBI valve having a balanced port might be replaced by a type SBF. The above original valves will most likely be non-adjustable. The standard replacements will have adjustable superheat to allow for an adjustment to match any special setting that was originally furnished to the OEM.
• Type X Valve (example - XVE-7 1/2-CP100): This valve is usually field replaced with a standard type S, G, C, RCVE, or Q valve.
• Valves Identified with a “Y” Number (example - Y362GR-1-Z): These are the most difficult to identify since the “Y” numbers that Sporlan have used over the years is now in excess of 1,000 and each number signifies some special feature known only to Sporlan and perhaps the OEM. This then becomes a case of contacting Sporlan or directing the customer to the OEM involved. Delivery is usually long.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVSelecting A Replacement For A Competitive TEV
This is another case where there can be no easy guide to making a proper selection because of the wide number of manufacturers and model numbers involved. Sporlan does publish a cross-reference table with competitive valves.
The cross references are based on nominal capacity matches. Valve performance, and thus system performance, cannot be guaranteed when replacing a valve using these cross references because of unique valve flow characteristics and potentially differing test and rating procedures by the valve manufacturers. There is also no assurance that the valve being replaced has been properly sized for the systemrequirements. Therefore it is always recommended to properly confirm the valve selection as outlined in Bulletin 10-10.
Note: This is a nominal capacity cross reference only. Physical attributes, such as connection sizes, body configuration, lay in dimensions, and capillary tube length may not be identical. Due to some of the differ- ing valve physical attributes, some system modifications may be required.
Most wholesalers have competitive catalogs for reference.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVIdentification of Numbers and/or Letters Not Commonly Encountered
Customers may occasionally provide unrecognizable designations other than “Y” numbers or OEM specials such as I, BI and X valves. The following are some of these cases:
• Suffix numbers to “P” charges (example GRE-2-ZP35): These numbers indicate a pressure limit other than standard. Bulletin 10-10 shows the standard pressure limit values for all standard charges. As an example the RZP standard factory air test settings is 45 PSI.
Therefore, an RZP35 charge has a pressure limit setting to 10 PSI below the standard RZP.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEV• BP and RPB: TEV’s with either of these features
are designed for use on systems having a “low starting torque” compressor motor (such as permanent split capacitor or PC motor). This type of compressor will start only if there is a negligible difference in high and low side pressures.
Both the BP and the RPB features allow the TEV to equalize the high and low side pressures when the compressor is stopped. When restarting there is virtually no pressure difference and the compressor is stopped.
• The letters BP stand for “bleed port” and will be followed by a number to indicate the percent of bleed. Thus BP/30 means a 30% bleed.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEV
The letters RPB stand for “rapid pressure balance”
and does not include a number as in the case of
straight bleed-port valves (BP).
Replacement of a TEV on a system with a PSC
motor (low starting torque) must have a bleed port or
RPB feature. A standard TEV without the BP or RPB
can only be used by adding a “hard-start kit” to the
compressor motor. Also 3-phase compressor motors
do not require the BP or RPB feature.
Non-adjustable TEV’s: Some standard models of
TEV’s are made non-adjustable for OEM’s. The
designation for these use the “N” prefix such as
NSVE-8 which is replaced in the field by a standard
SVE-8.
©2012 Sporlan Division, Parker Hannifin Corporation
Supplying the Customer with the
Correct TEVReplacement Parts for TEV’s
Sporlan TEV’s are very trouble-free and service or necessity for replacement parts is extremely rare. Most complaints involving the operation of TEV’s can usually be traced to contaminants in the refrigerant. It is a well established fact that because of the valve’s location in the system, even the smallest trace of circulating contaminants will eventually be trapped by the TEV. Of course the Sporlan Catch-All is the best insurance against this happening and will be discussed later.
Wear to any of the TEV parts is practically nonexistent which leaves only the loss of the thermostatic charge as a possible source of TEV failure. Replacement power element kits are available for this purpose.
In general, even though replacement internal parts kits are available for some valves, repairing of TEV’s is considered impractical because of the cost of labor compared to the cost of a new valve.
©2012 Sporlan Division, Parker Hannifin Corporation
REFRIGERANT
DISTRIBUTORS
Wholesaler Training Program – Part 1
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
General
The refrigerant distributor is a device not often sold
by a wholesaler since it is usually included with the
evaporator coil by the OEM. Nevertheless, the
wholesaler is frequently called on to supply parts to
modify it to accommodate some design change such
as a change in refrigerants, capacity or addition of
hot gas defrost or hot gas bypass.
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
Basic Distributor Construction
Standard refrigerant distributors consist of 3 parts:
A. Body (designated by 4 digit number, i.e.: 1113)
B. Nozzle (designated by a letter and a number, i.e.:
G-6)
C. Retainer Ring (designated by same letter as
nozzle)
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
Basic Distributor Construction
Bulletin 20-10 is the guide to finding:
A. Number and size of circuits available for each
distributor body.
B. Nozzle type (L, J, G, E, C, or A) that fit a particular
distributor model.
C. Nozzle orifice size and corresponding capacity for
each (numbered 1/9 to 50).
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
Basic Distributor Construction
Refrigerant distributors for hot gas defrost, heat pump, or reverse flow (distributors with auxiliary side connectors)
A. The 1650 series (1650, 1, 2, 3, 4, 5, 6, 7, 9) are constructed with a connection on the side to receive hot gas for defrost purposes or to collect liquid from the evaporator on reverse flow such as a heat pump.
B. Models 1651, 3, 5, 7 and 9 use standard nozzles J, G, E, C, and A respectively. Models 1650, 2, 4 and 6 have nozzles that cannot be removed.
C. The purpose for using all the above models instead of a “Tee” between the TEV and distributor is to allow the hot gas or reverse flow to pass through the distributor without going through the restriction of the nozzle.
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
Basic Distributor Construction
Refrigerant distributors for hot gas bypass:
A. Refrigerant distributors for hot gas bypass
applications have the same basic construction
except for the inter- nal machining of the
distributor body and the use of a “extended tube”
nozzle. Both are designated by the letter “R”
added to the number of the distributor and/or
nozzle. Example: 1653R for the distributor and
GR for the nozzle.
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
Basic Distributor Construction
Refrigerant distributors for hot gas bypass:
B. The “R” models use special distributor body
machining and special nozzles to permit the
mixing of the hot gas from the bypass valve and
the refrigerant feed from the TEV. This is
accomplished without upsetting the proper
refrigerant distribution into each circuit of the
distributor.
C. “R” models can be used on both hot gas bypass
and hot gas defrost and reverse flow systems.
However, the standard 1650 series (without “R”)
should not be used on hot gas bypass systems.
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
Basic Distributor Construction
Converting standard distributors to side outlet models:
Customers will occasionally want to add hot gas bypass or hot gas defrost to an evaporator that was originally furnished with a standard distributor.
This can be accomplished with the use of an auxiliary side connector (ASC).
A. ASC models that fit standard model distributors are listed in bulletin 20-10.
B. Customers should follow the instructions for locating the ASC and relocating the nozzle from the distributor to the ASC.
©2012 Sporlan Division, Parker Hannifin Corporation
Refrigerant Distributors
Basic Distributor Construction
C. The ASC adapter provides a second option for
supplying a customer with a distributor with an
auxiliary side connection. In this example, a
1651R-3-1/4-4 with a 1/2 OD side connection
serves the same purpose as a 1620-3-1/4 in
combination with an ASC-5-4 using a J-4 nozzle.
©2012 Sporlan Division, Parker Hannifin Corporation
LEVEL-MASTER CONTROL
Wholesaler Training Program – Part 1
©2012 Sporlan Division, Parker Hannifin Corporation
Sporlan Level-Master Control
The Sporlan Level Master control is a modified TEV designed for application to flooded systems only. The basic difference between the Level-Master and a TEV is in the construction of the power element. This LMC element has an insert type bulb and contains a small heating element. The complete power element including the heater is available as a separate part. The heater only is also avail- able as a replacement part.
The Level-Master has limited application because of the relatively small number of flooded refrigeration systems in existence or being built. Most flooded systems use ammonia and are usually found in industrial applications.
Bulletin 60-15 gives details of construction, operation and application.