Title 24, Part 6:
Where We're Headed with the 2019 Standards
Martyn C. Dodd
EnergySoft
www.energysoft.com
August, 2019
Energy Code Ace
A new website developed by the Statewide Codes & Standards Program to help you meet the requirements of Title 24, Part 6, and Title 20
We offer FREE
A variety of tools to
help you identify the
forms, installation
techniques, and
building energy
standards relevant to
building projects in
California
Training opportunities for Title 24, Part 6:
Traditional classroom
V-class
Vorkshop
Online self-study
Decoding Talks
Code & Coffee (YouTube)
Request a class
Fact Sheets, Trigger
Sheets, Checklists,
and FAQs to help
you understand when
Title 24, Part 6 is
“triggered” and how
to correctly comply
when it is
visit us at
www.EnergyCodeAce.comWhere We're Headed with the 2019 Standards 2
Key word and full-phrase
search capabilities
Hyperlinked tables
Links to related Sections and
to Compliance Manuals
Glossary function
Navigate the Standards with ease
Fast & Easy Access to the Standards
Use the link on the “Downloads” panel…
Give it a try during the break
Where We're Headed with the 2019 Standards 3
Identify the major areas of change in the 2019
Title 24 Building Energy Efficiency Standards
including:
Overall changes in scope and application
Envelope Requirements
Mechanical Requirements
Indoor Lighting Requirements
Outdoor Lighting Requirements
Learning Objectives
Where We're Headed with the 2019 Standards 4
Required when using the Prescriptive compliance approach
Optional feature accounted for when doing Performance-based computer modeling
Always required regardless of compliance approach used
Course Conventions
Mandatory
Prescriptive
Performance
Where We're Headed with the 2019 Standards 5
Overview of What’s New
Where We're Headed with the 2019 Standards 6
May 9, 2018 Business Meeting –
Language Adoption
Jan 1, 2020 Implementation Date
Any projects that apply for permit
on or after Jan 1, 2020 will be
subject to the 2019 Standards
Information and documents
available at:
http://www.energy.ca.gov/
title24/2019standards/
Update Schedule
Where We're Headed with the 2019 Standards 7
Institutional Facilities added (Occupancy I-1 & I-2)
Healthcare Facilities 100.0(a)
Definitions section
Buildings and structures used for medical care on a 24-hour basis for more than five persons who are incapable of self-preservation or classified as nonamblulatory or bedridden.
Important exemptions are listed in many sections of the code
I-1 Covers
I-2 Covers
Where We're Headed with the 2019 Standards 8
Prisons
Jails Reformatories
Detention Centers
Correctional Centers
Prerelease centers
Daycare facilities
Other Institutional Facilities 100.0(a)
I-3 Exempt
I-4 Exempt
Where We're Headed with the 2019 Standards 9
New code section that consolidates all
Demand Response items
References OpenADR 2.0 protocols
HVAC controls
Lighting controls
Electric message centers
Demand Management 110.12
Where We're Headed with the 2019 Standards 10
Allows a common shared system to be used to
offset solar and/or battery requirements
Must be operational before final permit signed
off on building
Must provide equivalent or better performance
than what is specified for building
Must directly feed the building
Must provide benefit to the building for 20
years minimum
Cannot transfer benefit to another building
Requires approval from the CEC
Community Shared Solar or Battery Systems 10-115
Where We're Headed with the 2019 Standards 11
1. The implementation date for enforcement of the new
2019 Standards will be:
a. January 1, 2019
b. January 1, 2020
c. Immediately after the CEC officially adopts the
language
Check Your Understanding
The CEC gives us 18 months to get prepared.
Where We're Headed with the 2019 Standards 12
Nonresidential Envelope
Where We're Headed with the 2019 Standards 13
Required to meet the U-Factor
specified for exterior fenestration
No SHGC or VT requirement
140.3(a)3Windows in Demising Walls
Where We're Headed with the 2019 Standards
CONTINUED: Table 140.3-B: Prescriptive Envelope Criteria for Nonresidential Buildings (Including Relocatable Public School Buildings Where Manufacturer Certifies Use Only in Specific Climate Zone; Not Including High-Rise Residential Buildings and Guest Rooms Of Hotel/Motel Buildings)
En
velo
pe
Fe
ne
str
ati
on
All Climate Zones
Fixed WindowOperableWindow
Curtainwall or Storefront
Glazed Doors2
Ve
rtic
al
Area-Weighted Performance Rating Max U-factor 0.36 0.46 0.41 0.45
Sk
yli
gh
ts Glass, Curb Mounted
Glass, Deck Mounted
Plastic, Curb Mounted
Area-Weighted Performance Rating Max U-factor 0.58 0.46 0.88
14
New requirements for Tubular Skylights
Includes U-Factor, SHGC and VT ratings
140.3(a)5Tubular Skylights
Where We're Headed with the 2019 Standards
CONTINUED: Table 140.3-B: Prescriptive Envelope Criteria for Nonresidential Buildings (Including Relocatable Public School Buildings Where Manufacturer Certifies Use Only in Specific Climate Zone; Not Including High-Rise Residential Buildings and Guest Rooms Of Hotel/Motel Buildings)
En
ve
lop
e
Fe
ne
str
ati
on
All Climate Zones
Fixed WindowOperable Window
Curtainwall or Storefront
Glazed Doors2
Ve
rtic
al
Area-Weighted Performance Rating
MaxU-factor 0.36 0.46 0.41 0.45
Max RSHGC 0.25 0.22 0.26 0.23
Area-Weighted Performance Rating
Min VT 0.42 0.32 0.46 0.17
Maximum WWR% 40%
Sk
yli
gh
ts
Glass, Curb Mounted
Glass, Deck Mounted
Plastic, Curb Mounted
Tubular Daylighting Devices (TDDs)2016 2019
Area-Weighted Performance Rating
MaxU-factor 0.58 0.46 0.88 N/A 0.88
Max SHGC 0.25 0.25 NR N/A NR
Area-Weighted Performance Rating
Min VT0.49 0.49 0.64 N/A 0.38
(Min VTannual for TDDs)
Maximum SRR% 5%
15
Nonresidential Mechanical
Where We're Headed with the 2019 Standards 16
SPVAC & SPVHP minimum EER = 11
Propeller or Axial fan closed-circuit
Cooling Towers >= 16.1 gpm/hp
Variable Refrigerant Flow (VRF) Air Cooled
65,000 – 135,000 14.6 IEER
135,000 – 240,000 13.9 IEER
>= 240,000 12.7 IEER
Variable Refrigerant Flow (VRF) Water Cooled
65,000 – 135,000 15.8 IEER
135,000 – 240,000 13.8 IEER
>= 240,000 12.0 IEER
HVAC Efficiencies 110.2
Where We're Headed with the 2019 Standards 17
Applicable to Highrise
Residential occupancies
Establishes minimum air filter
requirements
Applicable to ducted systems
Systems that provide outside air or
recirculate air
Minimum 2” Filter (larger face area
formula will allow for 1”)
Minimum MERV 13 filtration
Air Filtration 120.1(b)
Where We're Headed with the 2019 Standards 18
Applicable to Nonresidential
and Hotel/Motel occupancies
Minimum MERV 13 filtration
for outdoor air supply
Minimum 2” Filter (larger face area
formula will allow for 1”)
Air Filtration 120.1(c)
Where We're Headed with the 2019 Standards 19
High-rise multi-family dwelling
units must include either:
A balanced ventilation system
A continuously operating supply
ventilation system
A continuously operating exhaust
ventilation system
If using a continuous system, it requires HERS
blower door testing to show no more than 0.3
cfm/sf leakage based upon the envelope surface
area
ASHRAE 62.2 is the basis for required ventilation
rates
Operable windows not permitted as a source of
ventilation
Continuous operation of the forced air system
not a permitted as a source of ventilation
Ventilation 120.1(b)
Where We're Headed with the 2019 Standards 20
Applicable to Highrise
Residential occupancies
Range hoods must be HERS or ATT
inspected in the field to verify:
Minimum airflow per ASHRAE 62.2
(100 cfm)
Maximum sound ratings per ASHRAE
62.2 (3.0 sones)
Other airflow options are provided in
ASHRAE 62.2 for continuous ventilation.
Range Hoods 120.1(b)
Where We're Headed with the 2019 Standards 21
Nonresidential and Hotel/Motel
occupancies will be the larger of:
CFM/sq. ft. from the expanded Table
120.1-A
The actual number of occupants
Ventilation 120.1
Where We're Headed with the 2019 Standards 22
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-A – Minimum Ventilation Rates — p. 1 of 6
23
Occupancy Category Area Outdoor Air Rate1 Racfm/ft2
Min Air Rate for DCV2
cfm/ft2Air
Class Notes
Educational Facilities
Daycare (through age 4) 0.21 0.15 2
Daycare sickroom 0.15 3
Classrooms (ages 5-8) 0.38 0.15 1
Classrooms (age 9 -18) 0.38 0.15 1
Lecture/postsecondary classroom 0.38 0.15 1 F
Lecture hall (fixed seats) - 0.15 1 F
Art classroom 0.15 2
Science laboratories 0.15 2
University/college laboratories 0.15 2
Wood/metal shop 0.15 2
Computer lab 0.15 1
Media center 0.15 1 A
Music/theater/dance 1.07 0.15 1 F
Multiuse assembly 0.50 0.15 1 F
Food and Beverage Service
Restaurant dining rooms 0.50 0.15 2
Cafeteria/fast-food dining 0.50 0.15 2
Bars, cocktail lounges 0.50 0.20 2
Kitchen (cooking) 0.15 2
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-A – Minimum Ventilation Rates — p. 2 of 6
24
Occupancy Category Area Outdoor Air Rate1 Racfm/ft2
Min Air Rate for DCV2
cfm/ft2Air
Class Notes
General
Break rooms 0.50 0.15 1 F
Coffee Stations 0.50 0.15 1 F
Conference/meeting 0.50 0.15 1 F
Corridors 0.15 1 F
Occupiable storage rooms for liquids or gels 0.15 2 B
Hotels, Motels, Resorts, Dormitories
Bedroom/living room 0.15 1 F
Barracks sleeping areas 0.15 1 F
Laundry rooms, central 0.15 2
Laundry rooms within dwelling units 0.15 1
Lobbies/pre-function 0.50 0.15 1 F
Multipurpose assembly 0.50 1 F
Office Buildings
Breakrooms 0.50 0.15 1
Main entry lobbies 0.50 0.15 1 F
Occupiable storage rooms for dry materials 0.15 1
Office space 0.15 1 F
Reception areas 0.15 1 F
Telephone/data entry 0.15 1 F
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-A – Minimum Ventilation Rates — p. 3 of 6
25
Occupancy Category Area Outdoor Air Rate1 Racfm/ft2
Min Air Rate for DCV2
cfm/ft2Air
Class Notes
Miscellaneous Spaces
Bank vaults/safe deposit 0.15 2 F
Banks or bank lobbies 0.15 1 F
Computer (not printing) 0.15 1 F
Freezer and refrigerated spaces (<50ºF) – 2 E
General manufacturing (excludes heavy industrial and process using chemicals)
0.15 3
Pharmacy (prep. Area) 0.15 2
Photo studios 0.15 1
Shipping/receiving 0.15 2 B
Sorting, packing, light assembly 0.15 2
Telephone closets 0.15 1
Transportation waiting 0.50 0.15 1 F
Warehouses 0.15 2 B
All others 0.15 2
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-A – Minimum Ventilation Rates — p. 4 of 6
26
Occupancy Category Area Outdoor Air Rate1 Racfm/ft2
Min Air Rate for DCV2
cfm/ft2Air
Class Notes
Public Assembly Spaces
Auditorium seating area 1.07 0.15 1 F
Places of religious worship 1.07 0.15 1 F
Courtrooms 0.19 0.15 1 F
Legislative chambers 0.19 0.15 1 F
Libraries (reading rooms and stack areas) 0.15 1
Lobbies 0.50 0.15 1 F
Museums (children’s) 0.25 0.15 1
Museums/galleries 0.25 0.15 1 F
Residential
Common corridors 0.15 1 F
Retail
Sales (except as below) 0.25 0.20 2
Mall common areas 0.25 0.15 1 F
Barbershop 0.40 2 F
Beauty and nail salons 0.40 2
Pet shops (animal areas) 0.25 0.15 2
Supermarket 0.25 0.20 1 F
Coin-operated laundries 0.30 2
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-A – Minimum Ventilation Rates — p. 5 of 6
27
Occupancy Category Area Outdoor Air Rate1 Racfm/ft2
Min Air Rate for DCV2
cfm/ft2Air
Class Notes
Sports and Entertainment
Gym, sports arena (play area) 0.50 0.15 2 E
Spectator areas 0.50 0.15 1 F
Swimming (pool) 0.15 2 C
Swimming (deck) 0.50 0.15 2 C
Disco/dance floors 1.50 0.15 2 F
Health club/aerobics room 0.15 2
Health club/weight rooms 0.15 2
Bowling alley (seating) 1.07 0.15 1
Gambling casinos 0.68 0.15 1
Game arcades 0.68 0.15 1
Stages, studios 0.50 0.15 1 D, F
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-A – Minimum Ventilation Rates — p. 6 of 6
28
Occupancy Category Area Outdoor Air Rate1 Racfm/ft2
Min Air Rate for DCV2
cfm/ft2Air
Class Notes
General:
1 Ra was determined This value assumes as being the larger of the area method and the default per person
method. The occupant density used in the per person method was assumed to be one half of the maximum
occupant load assumed for egress purposes in the CBC. non-fixed seating and uses the occupant density
assumption in accordance with Section 120.1(c)3.
2 If this column specifies a minimum cfm/ft2 then it shall be used to comply with Section 120.1(d)4E.
Specific Notes:
A – For high-school and college libraries, the values shown for “Public Assembly Spaces – Libraries” shall be
used. B – Rate may not be sufficient where stored materials include those having potentially harmful
emissions.
C – Rate does not allow for humidity control. “Deck area” refers to the area surrounding the pool that is
capable of being wetted during pool use or when the pool is occupied. Deck area that is not expected to
be wetted shall be designated as an occupancy category.
D – Rate does not include special exhaust for stage effects such as dry ice vapors and smoke.
E – Where combustion equipment is intended to be used on the playing surface or in the space, additional
dilution ventilation, source control, or both shall be provided.
F – Ventilation air for this occupancy category shall be permitted to be reduced to zero when the space is in
occupied-standby mode
Typically a CO2 sensor
High density spaces (40 sqft/person or less)
System has an outside air economizer or;
System has Outside Air > 3,000 cfm
Classroom exemption is removed
Additional spaces exempted
Daycare Sickrooms
Science Labs
Barber Shops
Beauty and nail salons
Demand Control Ventilation 120.1(d)3
Where We're Headed with the 2019 Standards 29
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-B – Minimum Exhaust Rates [ASHRAE 62.1: TABLE 6.5] — p. 1 of 2
30
Occupancy CategoryExhaust Rate,
cfm/unitExhaust Rate,
cfm/ft2Air Class Notes
Arenas - 0.50 1 B
Art classrooms - 0.70 2
Auto repair rooms - 1.5 2 A
Barber shops - 0.50 2
Beauty and nail salons - 0.60 2
Cells with toilet - 1.00 2
Copy, printing rooms - 0.50 2
Darkrooms - 1.00 2
Educational science laboratories - 1.00 2
Janitor closets, trash rooms, recycling - 1.00 3
Kitchenettes - 0.30 2
Kitchens – commercial - 0.70 2
Locker rooms for athletic or industrial facilities - 0.50 2
All other locker rooms - 0.25 2
Shower rooms 20/50 - 2 G,H
Paint spray booths - - 4 F
Parking garages - 0.75 2 C
Pet shops (animal areas) - 0.90 2
120.1Ventilation
Where We're Headed with the 2019 Standards
Table 120.1-B – Minimum Exhaust Rates [ASHRAE 62.1: TABLE 6.5] — p. 2 of 2
31
Occupancy CategoryExhaust Rate,
cfm/unitExhaust Rate,
cfm/ft2Air Class Notes
Refrigerating machinery rooms - - 3 F
Soiled laundry storage rooms - 1.00 3 F
Storage rooms, chemical - 1.50 4 F
Toilets – private 25/50 - 2 E
Toilets – public 50/70 - 2 D
Woodwork shop/classrooms - 0.50 2
Notes:
A – Stands where engines are run shall have exhaust systems that directly connect to the engine exhaust and prevent escape of fumes.
B – Where combustion equipment is intended to be used on the playing surface, additional dilution ventilation, source control, or both shall be provided.
C – Exhaust shall not be required where two or more sides comprise walls that are at least 50% open to the outside.
D – Rate is per water closet, urinal, or both. Provide the higher rate where periods of heavy use are expected to occur. The lower rate shall be permitted to be used otherwise.
E – Rate is for a toilet room intended to be occupied by one person at a time. For continuous systems operation during hours of use, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used.
F – See other applicable standards for exhaust rate.
G –For continuous system operation, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used.
H – Rate is per showerhead
Language change now means
it applies to ALL systems
Cooling is > 54,000 Btuh
Detect free cooling available
Detect economizer enabled
Detect compressor enabled (DX
systems)
Detect heating enabled
Determine mixed air low limit cycle
Fault Detection & Diagnostics (FDD) 120.2(i)
Where We're Headed with the 2019 Standards 32
Nameplate rating > 5 horsepower
Option 1 – Nameplate HP:
Constant Volume Fan hp< cfm X 0.0011
Variable Volume Fan hp< cfm X 0.0015
Option 2 – Brake HP:
Constant Volume Fan hp< cfm X 0.00094 + A
Variable Volume Fan hpcfm X 0.0013 + A
A = Sum of pressure drop adjustments
Example: A 10,000 cfm VAV fan would be allowed a 13 bhp motor
140.4(c)Fan Power
Where We're Headed with the 2019 Standards
Device Adjustment Credits
Return or exhaust systems required by code or accreditation standards to be fully ducted, or systems required to maintain air pressure differentials between adjacent rooms
0.5 in. of water
Return and/or exhaust airflow control devices
0.5 in. of water
Exhaust filters, scrubbers, or other exhaust treatment
The pressure drop of device calculated at fan system design condition
Particulate Filtration Credit: MERV 16 and greater and electronically enhanced filters
Pressure drop calculated at 2 x clean filter pressure drop at fan system design condition
Carbon and other gas-phase air cleaners
Clean filter pressure drop at fan system design condition
Biosafety cabinet Pressure drop of device at fan system design condition
Energy recovery device, other than coil runaround loop1
For each airstream [(2.2 x Energy Recovery Effectiveness) – 0.5] in. of water
Coil runaround loop1 0.6 in. of water for each airstream
Exhaust systems serving fume hoods
0.35 in. of water
1 Credit to be taken only when required by code
Table 140.4-B Fan Power Limitation Pressure Drop Adjustment
33
Fan Power regulated on
fans > 10,000 cfm by either:
0.85 watts/cfm limitation for systems
with filtration, scrubbers or air
treatment
0.65 watts/cfm limitation for others
Variable flow rate based upon
wind speed and direction
Variable flow rate based upon
contaminant concentration
Requires field verification of fan system
via Acceptance Testing
Process Exhaust 140.9(c)1
Where We're Headed with the 2019 Standards 34
Vertical only Sashes required to have Automatic Sash Closures if it is fume hood intense
Table 140.9-B describes trigger based upon ACH and hood density
Occupancy sensor based
Closes in 5 minutes after detecting no motion
Must have obstruction detecting capability
Requires field verification of sash system via Acceptance Testing
Variable Volume Fume Hoods
Where We're Headed with the 2019 Standards
140.9(c)4
Table 140.9-B Fume Hood Intensive Laboratories
Occupied Minimum Ventilation ACH ≤ 4 > 4 and≤ 6
> 6 and≤ 8
> 8 and≤ 10
> 10 and≤ 12
> 12 and≤ 14
Hood Density (linear feet per 10,000 ft3 of laboratory space)
≥ 6 ≥ 8 ≥ 10 ≥ 12 ≥ 14 ≥ 16
35
1. Demand Control ventilation is required on high density
spaces with outside air:
a. Less than 2,000 cfm
b. Less than 3,000 cfm
c. Greater than 3,000 cfm
Check Your Understanding
Where We're Headed with the 2019 Standards 36
Nonresidential Indoor Lighting
Where We're Headed with the 2019 Standards 37
Luminaries having replaceable
lamps (screw-in, etc.) shall use the
maximum rated lamp wattage for fixture
Line voltage recessed luminaries shall be
the larger of:
50 watts
Rated JA8 lamp wattage installed
Luminaire Wattage 130.0(c)2
Where We're Headed with the 2019 Standards 38
With no Current Limiter installed, greater of:
30 watts/ft of track or plug-in busway
Actual luminaires shown on plans
With a Current Limiter installed:
Maximum wattage of current limiter
With an Overcurrent Protection Panel:
Maximum wattage for the panel
Current limiting component such as a transformer:
Maximum wattage of transformer
*Note 12.5 w/ft rule for current limiters is gone
Track Lighting 130.0(c)6
Where We're Headed with the 2019 Standards 39
Manual area controls: New language related to Healthcare for switching location
Multi-level controls: Removed classroom exception but adds a new exception for bathrooms and Healthcare
Shut-off controls: New occupant sensors requirement to restrooms and newexceptions for Healthcare
Automatic daylighting controls:
New specifications regarding stable level of light and requirements that at least one sensor in daylit zone not be readily accessible to public
New exceptions regarding spaces blocked from direct sunlight (skylights and vertical fenestration)
New exception for retail sidelit zones
40
Controls §130.1
For general lighting, the manual area control shall permit the level
or amount of light provided while the lighting is on to be set or
adjusted by the controls specified in Section 130.1(b), (c), (d) & (e).
The manual area control shall permit the shutoff control to turn the
lighting down or off.
The multi-level lighting control shall permit the automatic daylighting control
to adjust the electric lighting level in response to changes in the amount of
daylight in the daylit zone.
The multi-level lighting control shall permit the demand responsive control to
adjust the lighting during a demand response event and to return it to the
level set by the multilevel control after the event.
The shutoff control shall permit the manual area control to turn the lighting
on. If the on request occurs while an automatic time switch control would turn
the lighting off, then the on request shall be treated as an override request.
The automatic daylighting control shall permit the multi-level lighting control
to adjust the level of lighting.
For lighting controlled by multi-level lighting controls and by occupant
sensing controls that provide an automatic-on function, the controls shall
provide a partial-on function that is capable of automatically activating
between 50-70 percent of controlled lighting power.
Control Interactions 130.1(f)
Where We're Headed with the 2019 Standards 41
Section 130.1(f)
New section dictating lighting control interactions
New daylighting adjustments for architectural
elements on a building.
Section 140.3 dictates the geometry of the element
to qualify for credit
Maybe added to other PAFs in table
Power Adjustment Factors 140.6-A
5. Clerestories Luminaires in daylit areas adjacent to clerestories.
Luminaires that qualify for daylight dimming plus OFF control may also
qualify for this PAF.
0.05
6. Horizontal Slats Luminaires in daylit areas adjacent to vertical fenestration with interior or
exterior horizontal slats.
Luminaires that qualify for daylight dimming plus OFF control may also
qualify for this PAF.
0.05
7. Light Shelves Luminaires in daylit areas adjacent to clerestories with interior or exterior light
shelves. This PAF may be combined with the PAF for clerestories.
Luminaires that qualify for daylight dimming plus OFF control may also
qualify for this PAF
0.10
Excerpt from 2019 Table 140.6-A: Lighting Power Adjustment Factors (Paf)
Where We're Headed with the 2019 Standards 42
140.6Complete Building Lighting Allowances
Where We're Headed with the 2019 Standards
Type of BuildingAllowed Lighting Power Density
(Watts per Square Foot)
2016 2019
Auditorium Assembly Building 1.40 0.70
Classroom Building 1.10 [N/A]
Commercial and Industrial Storage Building 0.60 0.45
Convention Center Building 1.00 [N/A]
Financial Institution Building 1.00 0.65
Industrial/Manufacturing Facility Building
[2016: General Commercial Building/Industrial Work Building]1.00 0.60
Grocery Store Building 1.50 0.95
Gymnasium Building [N/A] 0.65
Library Building 1.20 0.70
Healthcare Facility [N/A] 0.90
Medical Building/Clinic Building 1.00 [N/A]
Office Building 0.80 0.65
Parking Garage Building 0.20 0.13
Religious Facility Building 1.50 0.70
Restaurant Building 1.10 0.70
Retail Store Building [N/A] 0.90
School Building 0.95 0.65
Sports Arena Building [N/A] 0.75
Motion Picture Theater Building 1.30 0.70
Performing Arts Theater Building [N/A] 0.80
All others buildings 0.50 0.40
Table 140.6-B Complete Building Method Lighting Power Density Values
43
140.6-cArea Category Lighting Allowances
Where We're Headed with the 2019 Standards
Table 140.6-C Area Category Method — Lighting Power Density Values (Watts/Ft²) — p. 1 of 6
Primary Function Area
Allowed Lighting Power Density
(W/ft2)
Additional Lighting Power1
Qualified Lighting Systems
Additional Allowance (W/ft2
unless noted)2016 2019 2016 2019
Auditorium Area 1.40 3 0.70Ornamental 0.50 0.30
Accent, display and feature3 N/A 0.20
Auto Repair / Maintenance Area 0.90 2 0.55 Detailed Task Work7 0.50 0.20
Audience Seating Area [2016: N/A] N/A 0.60 Ornamental N/A 0.30
Beauty Salon Area 1.70 0.80Detailed Task Work7 – 0.20
Ornamental – 0.30
Civic Meeting Place Area 1.30 3 1.00 Ornamental 0.50 0.30
Classroom, Lecture, Training, Vocational Areas 1.20 5 0.70 White or Chalk Board1 5.50W/ft
4.50 W/ft
Commercial/ Industrial Storage
Warehouse N/A 0.45 – N/A –
Shipping & Handling N/A 0.60 – N/A –
[2016: Commercial and Industrial Storage Areas (conditioned and unconditioned)]
0.60 N/A N/A – N/A
[2016: Commercial and Industrial Storage Areas (refrigerated)]
0.70 N/A N/A – N/A
Convention, Conference, Multipurpose and Meeting Center
1.20 3 0.85 Ornamental 0.50 0.30
Copy Room [2016: N/A] N/A 0.50 – N/A –
NOTE: Under Additional Lighting Power, “Detailed Task Work” in the 2019 Standards is referred to as “Specialized Task Area” in the 2016 Standards 44
Area Category Lighting Allowances
Where We're Headed with the 2019 Standards
Table 140.6-C Area Category Method — Lighting Power Density Values (Watts/Ft²) — p. 1 of 6
Primary Function Area
Allowed Lighting Power Density
(W/ft2)
Additional Lighting Power1
Qualified Lighting Systems
Additional Allowance (W/ft2
unless noted)2016 2019 2016 2019
Auditorium Area 1.40 3 0.70Ornamental 0.50 0.30
Accent, display and feature3 N/A 0.20
Auto Repair / Maintenance Area 0.90 2 0.55 Detailed Task Work7 0.50 0.20
Audience Seating Area [2016: N/A] N/A 0.60 Ornamental N/A 0.30
Beauty Salon Area 1.70 0.80Detailed Task Work7 – 0.20
Ornamental – 0.30
Civic Meeting Place Area 1.30 3 1.00 Ornamental 0.50 0.30
Classroom, Lecture, Training, Vocational Areas 1.20 5 0.70 White or Chalk Board1 5.50W/ft
4.50 W/ft
Commercial/ Industrial Storage
Warehouse N/A 0.45 – N/A –
Shipping & Handling N/A 0.60 – N/A –
[2016: Commercial and Industrial Storage Areas (conditioned and unconditioned)]
0.60 N/A N/A – N/A
[2016: Commercial and Industrial Storage Areas (refrigerated)]
0.70 N/A N/A – N/A
Convention, Conference, Multipurpose and Meeting Center
1.20 3 0.85 Ornamental 0.50 0.30
Copy Room [2016: N/A] N/A 0.50 – N/A –
NOTE: Under Additional Lighting Power, “Detailed Task Work” in the 2019 Standards is referred to as “Specialized Task Area” in the 2016 Standards 45
Area Category Lighting Allowances
Where We're Headed with the 2019 Standards
Table 140.6-C Area Category Method — Lighting Power Density Values (Watts/Ft²) — p. 2 of 6
Primary Function Area
Allowed Lighting Power Density
(W/ft2)
Additional Lighting Power1
Qualified Lighting Systems
Additional Allowance (W/ft2
unless noted)2016 2019 2016 2019
Corridor Area[2016: Corridor, Restroom, Stair, and Support Areas]
0.60 0.60 – – –
Dining Area
Bar/Lounge and Fine Dining
1.00 3
0.55
Ornamental 0.50 0.30Cafeteria/Fast Food 0.40
Family and Leisure 0.50
Electrical, Mechanical, Telephone Rooms 0.55 2 0.40 Detailed Task Work7 0.50 0.20
Exercise/Fitness Center and Gymnasium Areas 1.00 0.50 – – –
Hotel Function Area 1.43 0.85 Ornamental – 0.30
Museum AreaExhibition/Display 1.80 0.60 – – –
Restoration Room [2016: N/A] N/A 0.75 Detailed Task Work7 N/A 0.20
Financial Transaction Area 1.00 3 0.80 Ornamental 0.50 0.30
General/Commercial & Industrial Work Areas
Low Bay 0.90 2 0.60 Detailed Task Work7 0.50 0.20
High Bay 1.00 2 0.65 Detailed Task Work7 0.50 0.20
Precision 1.20 4 0.85 Precision Work9 1.00 0.70
Library AreaReading Area 1.10 3 0.80 Ornamental 0.50 0.30
Stacks Area 1.50 3 1.10 Ornamental 0.50 –
46
Area Category Lighting AllowancesTable 140.6-C Area Category Method — Lighting Power Density Values (Watts/Ft²) — p. 3 of 6
Primary Function Area
Allowed Lighting Power Density
(W/ft2)
Additional Lighting Power1
Qualified Lighting Systems
Additional Allowance (W/ft2
unless noted)2016 2019 2016 2019
Main Entry Lobby [2016: Lobby Area: Hotel lobby | Main entry lobby]
0.95 3 0.85 Ornamental 0.50 0.30
Locker Room [2016: Locker/Dressing Room]
0.70 0.45 – – –
Lounge, Breakroom, or Waiting Areas [2016: Lounge Area]
0.90 3 0.65 Ornamental 0.50 0.30
Concourse and Atria Area[2016: Malls and Atria]
0.95 3 0.90 Ornamental 0.50 0.30
Office Area
> 250 square feet 0.75 0.65
Portable lighting for office areas6 – 0.20
≤ 250 square feet 1.00 0.70
Open plan office [2016: N/A]
N/A 0.60
Parking Garage Area
Parking Zone[2016: Parking Area]
0.14 0.10First ATM N/A 100 W
Additional ATM N/A 50 W each
Dedicated Ramps 0.30 0.25 – – –
Daylight Adaptation Zones2 0.60 0.50 – – –
Pharmacy Area [2016: N/A] N/A 1.10 Specialized Task Work8 N/A 0.35Where We're Headed with the 2019 Standards 47
Area Category Lighting Allowances
Where We're Headed with the 2019 Standards
Table 140.6-C Area Category Method — Lighting Power Density Values (Watts/Ft²) — p. 4 of 6
Primary Function Area
Allowed Lighting Power Density
(W/ft2)
Additional Lighting Power1
Qualified Lighting Systems
Additional Allowance (W/ft2
unless noted)2016 2019 2016 2019
Retail Sales Area
Grocery Sales 1.206 & 7 1.00Accent, display and feature3 0.30 0.20
Decorative 0.20 0.15
Retail Merchandise Sales 1.206 & 7 0.95Accent, display and feature3 0.30 0.20
Decorative 0.20 0.15
Fitting Room [2016: N/A] N/A 0.60 Illuminated Mirror5 N/A ??
Theater AreaMotion picture 0.90 3 0.60
Ornamental 0.50 0.30Performance 1.40 3 1.00
Kitchen/Food Preparation Area 1.20 0.95 – – –
Scientific Laboratory Area 1.41 1.00 Specialized Task Work8 N/A 0.35
Healthcare Facility and Hospitals [2016: Medical and Clinical Care Area]
Exam/Treatment Room 1.15 – –
Imaging Room 1.00 – –
Medical Supply Room 0.55 – –
Nursery 0.95 Tunable white or dim-to-warm10 0.10
Nurse’s Station 1.2 0.75 Tunable white or dim-to-warm10N/A
0.10
Operating Room 1.90 – –
Patient Room 0.55Decorative 0.15
Tunable white or dim-to-warm10 0.10
Physical Therapy Room 0.85 Tunable white or dim-to-warm10 0.10
Recovery Room 0.90 Tunable white or dim-to-warm10 0.10
48
Area Category Lighting Allowances
Where We're Headed with the 2019 Standards
Table 140.6-C Area Category Method — Lighting Power Density Values (Watts/Ft²) — p. 5 of 6
Primary Function Area
Allowed Lighting Power Density
(W/ft2)
Additional Lighting Power1
Qualified Lighting Systems
Additional Allowance (W/ft2
unless noted)
2016 2019 2016 2019
Laundry Area 0.70 0.45 – – –
Religious Worship Area 1.50 3 0.95 Ornamental 0.50 0.30
Restrooms[2016: Corridor, Restroom, Stair, and Support Areas]
0.60 0.65 – – –
Transportation Function AreaBaggage Area 0.50 0.40 – – –
Ticketing Area 1.00 0.45 Accent, display and feature3 – 0.20
Sports Arena – Playing Area[2016: N/A]
Class I Facility
N/A
2.25 –
N/A
–
Class II Facility 1.45 – –
Class III Facility 1.10 – –
Class IV Facility 0.75 – –
Stairwell[2016: Corridor, Restroom, Stair, and Support Areas]
0.60 0.50Accent, display and feature3 – 0.20
Decorative4 – 0.15
Videoconferencing Studio 1.20 8 0.90 Videoconferencing 1.5 1.00
All other 0.50 0.40 – – –
49
Area Category Lighting Allowances
Where We're Headed with the 2019 Standards
Table 140.6-C Area Category Method — Lighting Power Density Values (Watts/Ft²) — p. 6 of 6
Primary Function Area
Allowed Lighting Power Density
(W/ft2)
Additional Lighting Power1
Qualified Lighting Systems
Additional Allowance (W/ft2
unless noted)
2016 2019 2016 2019
Aging Eye / Low-vision11
Main Entry Lobby
ANSI / IES
RP-28
0.85
Ornamental – 0.30
Transition Lighting OFF at night12
– 0.95
Stairwell 0.80 – – –
Corridor Area 0.80 Decorative4 – 0.15
Lounge Waiting Area 0.75 Ornamental – 0.30
Multipurpose Room 0.95 Ornamental – 0.30
Religious Worship Area 1.00 Ornamental – 0.30
Dining 0.80 Ornamental – 0.30
Restroom 0.80 Accent, display and feature3 – 0.20
50
Tailored Lighting Allowances
Where We're Headed with the 2019 Standards
1 2 3 4 5
Primary Function Area
General Illumination Level (Lux)
Wall Display Lighting Power Density (W/ft)
Allowed Combined Floor Display Power
and Task Lighting Power Density (W/ft²)
Allowed Ornamental/ Special Effect Lighting Power Density (W/ft²)
2016 2019 2016 2019 2016 2019 2016 2019
Auditorium Area 300 300 2.25 3.00 0.3 0.20 0.5 0.40
2019: N/A [2016: Civic Meeting Place] 300 N/A 3.15 N/A 0.2 N/A 0.5 N/A
Convention, Conference, Multipurpose, and Meeting Center Areas 300 300 2.50 2.00 0.4 0.35 0.5 0.40
Dining Areas 200 200 1.50 1.25 0.6 0.50 0.5 0.40
Exhibit, Museum Areas 150 150 15.0 11.50 1.2 0.80 0.5 0.40
2019: N/A [2016: Financial Transaction Area] 300 N/A 3.15 N/A 0.2 N/A 0.5 N/A
2019: N/A [2016: Grocery Store Area] 500 N/A 8.00 N/A 0.9 N/A 0.5 N/A
Hotel Area: [2016: “Headline” Grouping N/A]
Ballroom/Events [2016: Hotel Function Area] 400 400 2.25 1.80 0.2 0.12 0.5 0.40
2016: “Headline/Grouping” N/A [2016: Lobby Area:]
Lobby [2016: Hotel lobby] 200 200 3.15 3.50 0.2 0.20 0.5 0.40
Main entry lobby 200 200 0 3.50 0.2 0.20 0 0.40
2019: N/A [2016: Lounge Area] 200 N/A 7.00 N/A 0 N/A 0.5 N/A
2019: N/A [2016: Malls and Atria] 300 N/A 3.50 N/A 0.5 N/A 0.5 N/A
Religious Worship Area 300 300 1.50 1.30 0.5 0.40 0.5 0.40
Retail Sales [2016: “Headline/Grouping’ N/A]
Grocery [2016: N/A] N/A 600 N/A 6.80 N/A 0.70 N/A 0.40
Merchandise Sales, and Showroom Areas [2016: Retail Merchandise Sales, and Showroom Areas] 400 500 14.00 11.80 1.0 0.80 0.5 0.40
Theater Area:
Motion picture 200 200 3.00 2.00 0 0.20 0.5 0.40
Performance Arts [2016: Performance] 200 200 6.00 7.50 0 0.20 0.5 0.40
2019: N/A [2016:Transportation Function Area] 300 N/A 3.15 N/A 0.3 N/A 0.5 N/A
2019: N/A [2016: Waiting Area] 300 N/A 3.15 N/A 0.2 N/A 0.5 N/A
Table 140.6-D: Tailored Method Lighting Power Allowances
51
Tailored Lighting Display Height 140.6-E
Where We're Headed with the 2019 Standards
Table 140.6-E: Wall and Floor Display Mounting Height Adjustment Factor
[2016: Table 140.6-E: Adjustments for Mounting Height Above Floor]
2016 2019
Height in feet above finished floor and
bottom of luminaire(s)
Floor Display or Wall Display – Multiply by
Height in feet above finished floor and
bottom of luminaire(s)
Floor Display or Wall Display – Multiply by
< 12' 1.00 10’-7” 1.00
12' to 16' 0.87 10’-7” to 14’-0” 0.85
>14’-0” to 18’-0” 0.75
> 16’ 0.77 > 18’-0” 0.70
52
140.6Tailored Lighting General Illumination
Where We're Headed with the 2019 Standards
General Illuminance Level (lux)a
General Lighting Power Density (W/ft²) for the following RCR valuesb
RCR ≤ 2.0
RCR> 2.0 and ≤ 3.5
RCR > 3.5 and ≤ 7.0
RCR > 7.0
2016 2019 2016 2019 2016 2019 2016 2019
2019: N/A [2016: 50] 0.18 N/A 0.22 N/A 0.32 N/A 0.46 N/A
2019: N/A [2016: 100] 0.30 N/A 0.38 N/A 0.56 N/A 0.84 N/A
150 0.5 0.40 0.7 0.45 1.05 0.60 1.55 0.75
200 0.48 0.45 0.64 0.55 0.88 0.75 1.34 1.00
300 0.64 0.65 0.82 0.80 1.12 1.00 1.76 1.40
400 0.78 0.75 0.98 0.95 1.34 1.25 2.08 1.50
500 0.90 0.90 1.10 1.05 1.52 1.45 2.32 1.85
600 1.06 1.08 1.26 1.24 1.74 1.64 2.60 2.38
2019: N/A [2016: 700] 1.24 N/A 1.46 N/A 1.82 N/A 2.96 N/A
2019: N/A [2016: 800] 1.44 N/A 1.70 N/A 2.28 N/A 3.30 N/A
2019: N/A [2016: 900] 1.66 N/A 2.00 N/A 2.64 N/A 3.74 N/A
2019: N/A [2016: 1000] 1.84 N/A 2.20 N/A 2.90 N/A 4.06 N/A
a Illuminance values from Column 2 of TABLE 140.6-D.b RCR values are calculated using applicable equations in TABLE 140.6-F.
Table 140.6-G: Tailored Method General Lighting Power Allowed by Illuminance and Room Cavity Ratio
[2016: Illuminance Level (Lux) Power Density Values (Watts/ft²)]
53
Triggered if 10% or
more of the luminaires
in a space are altered
Controls depend upon
path to compliance
chosen
Path I – Meets current
Title 24 LPD
Path II – Beats Title 24
by 20%
Path III – 40% reduction
from existing lighting
(Path III only allowed if
5,000 ft2 or less)
141.0(b)2ILighting Alterations
Control Specifications
Projects complying
with Section 141.02(b)Ii
Projects complying
with Section 141.02(b)Iii
Projects complying
with Section 141.02(b)Iii
ManualArea Controls
130.1(a)1 Required
130.1(a)2 Required
130.1(a)3Only required for new or
completely replaced circuits
Multi-Level Controls 130.1(b) Required Not Required
Automatic Shut Off Controls
130.1(c)1Required; 130.0(c)1D only
required for new or completely replaced circuits
130.1(c)2 Required
130.1(c)3 Required
130.1(c)4 Required
130.1(c)5 Required
130.1(c)6 Required
130.1(c)7 Required
130.1(c)8 Required
Daylighting Controls 130.1(d) Required Not Required
Demand Responsive Controls
130.1(e) Required Not Required
Where We're Headed with the 2019 Standards 54
EXCEPTION 1 to Section 141.0(b)2I. Alteration of portable
luminaires, luminaires affixed to moveable partitions,
or lighting excluded as specified in Section 140.6(a)3.
EXCEPTION 2 to Section 141.0(b)2I. Any enclosed space with only
one luminaire.
EXCEPTION 3 to Section 141.0(b)2I. Any alteration that would directly
cause the disturbance of asbestos, unless the alteration is made in
conjunction with asbestos abatement.
EXCEPTION 4 to Section 141.0(b)2I. Acceptance testing requirements of
Section 130.4 are not required for alterations where lighting controls are
added to control 20 or fewer luminaires.
EXCEPTION 5 to Section 141.0(b)2I. Any alteration limited to
adding lighting controls or replacing lamps, ballasts, or drivers.
EXCEPTION 6 to Section 141.0(b)2I. For each building or tenant space,
alteration of up to 50 luminaires per floor of the space, per annum.
Lighting Alterations(cont) 141.0(b)2I
Where We're Headed with the 2019 Standards 55
1. The wattage of a luminaire with a replaceable lamp is:
a. The higher of the lamp wattage or the fixture rating
b. The lower of the lamp wattage or the fixture rating
c. The fixture rating
Check Your Understanding
Where We're Headed with the 2019 Standards 56
Recessed luminaires shall be the greater of
50 watts
Rated JA8 lamp wattage installed
2. Options for lighting compliance include:
a. The Area category allowances
b. The Complete Building allowances
c. The Tailored allowances
d. All of the above
Where We're Headed with the 2019 Standards 57
Outdoor Lighting
Where We're Headed with the 2019 Standards 58
Cutoff fixture requirement triggered
at 6,200 lumens
Backlight, Uplight and Glare triggered
per Title 24 Part 11 (CalGreen) table
Adds the Backlight component to the
regulation (previous code had no
Backlight regulation)
Luminaires 130.2(b)
Where We're Headed with the 2019 Standards 59
Automatic Scheduling: all lighting must be controlled to allow
At least 50% of lighting off at night (no more than 90% new) AND
At least two nighttime periods to be programmed (new)
Motion Sensing: all lighting within 24 ft above grade must be controlled to allow
At least 50% (was 40%) of lighting off at night (but no more than 90%) AND
Turn light off/reduce 15 minute or less timeout (new)
Single sensor limited to 1500 watts of lighting, or less
Including wall packs used for Building Façade, Ornamental Hardscape, or Outdoor Dining that have bilaterally symmetric distribution (up & down) (new)
60
Auto Shut-off Controls
Exceptions to motion sensor:
Luminaries 40 Watts or less (was pole=75W, wall=30W, linear=4W/ft)
Exempt lighting per §140.7(a)
Dimming can be above 50%, or turn down/off longer than 15 minutes, if health / safety take precedence. (new)
§130.2(c)2-3
New General Hardscape Allowances 140.7
Where We're Headed with the 2019 Standards
Type of Power Allowance
Lighting Zone
0
Lighting Zone
1 3
Lighting Zone
2 3
Lighting Zone
3
Lighting Zone
4
20162019
20162019
20162019
20162019
20162019
Asphalt / Concrete
Asphalt / Concrete
Asphalt Concrete2 Asphalt Concrete2 Asphalt / Concrete
Area Wattage Allowance (AWA)
No allow-ance1
No allow-ance1
0.020 W/ft²
0.018 W/ft²
0.030 W/ft²
0.023 W/ft²
0.025 W/ft²
0.040 W/ft²
0.025 W/ft²
0.03 W/ft²
0.050 W/ft²
0.03 W/ft²
Linear Wattage Allowance (LWA)
0.15 W/lf
0.15 W/lf0.25 W/lf
0.17 W/lf
0.4W/lf
0.35 W/lf
0.25 W/lf
0.4 W/lf0.45 W/lf
0.35 W/lf
Initial Wattage Allowance (IWA)
340W
180W
450W
250W
250W
520W
350W
350W
640W
400W
Table 140.7-A: General Hardscape Lighting Power Allowance
61
140.7Specific Lighting Applications
Where We're Headed with the 2019 Standards
Lighting ApplicationLighting Zone
0Lighting Zone
1Lighting Zone
2Lighting Zone
3Lighting Zone
42016 2019 2016 2019 2016 2019 2016 2019 2016 2019
WATTAGE ALLOWANCE PER APPLICATION. Use all that apply as appropriate.
Building Entrances or Exits. Allowance per door. Luminaires qualifying for this allowance shall be within 20 feet of the door.
Not applic-able
Not applic-able
15 watts
9 watts
25 watts
15 watts
35 watts
19 watts
45 watts
21 watts
Primary Entrances to Senior Care Facilities, Police Stations, Hospitals, Fire Stations, and Emergency Vehicle Facilities. Allowance per primary entrance(s) only. Primary entrances shall provide access for the general public and shall not be used exclusively for staff or service personnel. This allowance shall be in addition to the building entrance or exit allowance above. Luminaires qualifying for this allowance shall be within 100 feet of the primary entrance.
Not applic-able
Not applic-able
45 watts
20 watts
80 watts
40 watts
120 watts
70 watts
130 watts
60 watts
Drive Up Windows. Allowance per customer service location. Luminaires qualifying for this allowance shall be within 2 mounting heights of the sill of the window.
Not applic-able
Not applic-able
40 watts
16 watts
75 watts
30 watts
125 watts
50 watts
200 watts
75 watts
Vehicle Service Station Uncovered Fuel Dispenser. Allowance per fueling dispenser. Luminaires qualifying for this allowance shall be within 2 mounting heights of the dispenser.
Not applic-able
Not applic-able
120 watts
55 watts
175 watts
77 watts
185 watts
81 watts
330 watts
135 watts
ATM Machine Lighting. Allowance per ATM machine. Luminaires qualifying for this allowance shall be within 50 feet of the dispenser.
Not applic-able
Not applic-able
[2016] 250 watts for first ATM machine, 70 watts for each additional ATM machine.
[2019] 100 watts for first ATM machine, 35 watts for each additional ATM machine.
Table 140.7-B: Additional Lighting Power Allowance for Specific Applications — p. 1 of 4All area and distance measurements in plan view unless otherwise noted.
62
What's New: 2019 Title 24, Part 6 63
140.7Specific Lighting Applications
Lighting ApplicationLighting Zone
0Lighting Zone
1Lighting Zone
2Lighting Zone
3Lighting Zone
4
2016 2019 2016 2019 2016 2019 2016 2019 2016 2019
WATTAGE ALLOWANCE PER UNIT LENGTH ( W/ linear ft). May be used for one or two frontage side(s) per site.
Outdoor Sales Frontage. Allowance for frontage immediately adjacent to the principal viewing location(s) and unobstructed for its viewing length. A corner sales lot may include two adjacent sides provided that a different principal viewing location exists for each side. Luminaires qualifying for this allowance shall be located between the principal viewing location and the frontage outdoor sales area.
Not applic-able
Not applic-able
No Allow-ance
No Allow-ance
22.5 W/
linear ft
11 W/
linear ft
36W/
linear ft
19 W/
linear ft
45 W/
linear ft
25 W/
linear ft
WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft²). May be used for any illuminated hardscape area on the site.
Hardscape Ornamental Lighting. Allowance for the total site illuminated hardscape area. Luminaires qualifying for this allowance shall be rated for 100 watts or less as determined in accordance with Section 130.0(d), and shall be post-top luminaires, lanterns, pendant luminaires, or chandeliers.
Not applic-able
Not applic-able
No Allow-ance
No Allow-ance
0.02 W/ft²
0.007 W/ft²
0.04 W/ft²
0.013 W/ft²
0.06 W/ft²
0.019 W/ft²
Table 140.7-B: Additional Lighting Power Allowance for Specific Applications — p. 2 of 4All area and distance measurements in plan view unless otherwise noted.
What's New: 2019 Title 24, Part 6 64
140.7Specific Lighting Applications
Lighting ApplicationLighting Zone
0Lighting Zone
1Lighting Zone
2Lighting Zone
3Lighting Zone
42016 2019 2016 2019 2016 2019 2016 2019 2016 2019
WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft²). Use as appropriate provided that none of the following specific applications shall be used for the same area.
Building Facades. Only areas of building façade that are illuminated shall qualify for this allowance. Luminaires qualifying for this allowance shall be aimed at the façade and shall be capable of illuminating it without obstruction or interference by permanent building features or other objects.
Not applic-able
Not applic-able
No Allow-ance
No Allow-ance
0.18 W/ft²
0.100 W/ft²
0.35 W/ft²
0.170 W/ft²
0.50 W/ft²
0.225 W/ft²
Outdoor Sales Lots. Allowance for uncovered sales lots used exclusively for the display of vehicles or other merchandise for sale. Driveways, parking lots or other non sales areas shall be considered hardscape areas even if these areas are completely surrounded by sales lot on all sides. Luminaires qualifying for this allowance shall be within 5 mounting heights of the sales lot area.
Not applic-able
Not applic-able
0.164 W/ft²
0.060 W/ft²
0.555 W/ft²
0.210 W/ft²
0.758 W/ft²
0.280 W/ft²
1.285 W/ft²
0.485 W/ft²
Vehicle Service Station Hardscape. Allowance for the total illuminated hardscape area less area of buildings, under canopies, off property, or obstructed by signs or structures. Luminaires qualifying for this allowance shall be illuminating the hardscape area and shall not be within a building, below a canopy, beyond property lines, or obstructed by a sign or other structure.
Not applic-able
Not applic-able
0.014 W/ft²
0.006 W/ft²
0.155 W/ft²
0.068 W/ft²
0.308 W/ft²
0.138 W/ft²
0.485 W/ft²
0.200 W/ft²
Table 140.7-B: Additional Lighting Power Allowance for Specific Applications — p. 3 of 4All area and distance measurements in plan view unless otherwise noted.
What's New: 2019 Title 24, Part 6 65
140.7Specific Lighting Applications
Lighting ApplicationLighting Zone
0Lighting Zone
1Lighting Zone
2Lighting Zone
3Lighting Zone
4
2016 2019 2016 2019 2016 2019 2016 2019 2016 2019
[Contin.] WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft²). Use as appropriate provided that none of the following specific applications shall be used for the same area.
Vehicle Service Station Canopies. Allowance for the total area within the drip line of the canopy. Luminaires qualifying for this allowance shall be located under the canopy.
Not applic-able
Not applic-able
0.514 W/ft²
0.220 W/ft²
1.005 W/ft²
0.430 W/ft²
1.300 W/ft²
0.580 W/ft²
2.200 W/ft²
1.010 W/ft²
Sales Canopies. Allowance for the total area within the drip line of the canopy. Luminaires qualifying for this allowance shall be located under the canopy.
Not applic-able
Not applic-able
No Allow-ance
No Allow-ance
0.655 W/ft²
0.470 W/ft²
0.908 W/ft²
0.622 W/ft²
1.135 W/ft²
0.740 W/ft²
Table 140.7-B: Additional Lighting Power Allowance for Specific Applications — p. 4 of 4All area and distance measurements in plan view unless otherwise noted.
Questions?
This concludes the Title 24 Standards Training.