what is in the obc sb-10 update? · what is in the obc sb-10 update? the ontario architects...
TRANSCRIPT
What is in the OBC SB-10 Update? The Ontario Architects Association Perspective
Ontario Gets Serious about Energy Use in New Buildings
1
Introduction
2
OBC Introduced SB-10 in 2007
Prescribed minimum energy performance
MNECB-1997 + ASHRAE 90.1-2004
Update published in July 2011, effective Jan 2012
Implementation of ASHRAE 90.1-2010 + ASHRAE
189.1-2009 envelope values
Three methods of compliance
Performance (3 baselines in performance)
Prescriptive + envelope trade-off
Prescriptive
Today will focus on prescriptive path
OBC Compliance Paths
10
OBC Compliance
90.1-2010
+ Chapter 2
90.1 + Chapter 2 Mandatories
90.1 Prescriptive + Chapter 2
Energy modeling against 90.1 +
Chapter 2 prescriptive
25% Less than MNECB
MNECB Mandatories Energy Modeling against MNECB
prescriptive
5% Less than 90.1 2010
90.1 Mandatories Energy modeling
against 90.1 prescriptive
Today’s
Focus
ASHRAE 90.1-2010 / SB-10 Prescriptive
Path
11
Outlines minimum performance parameters for:
Wall, Roofs, Windows elements etc.
Prescriptive and performance paths for insulation
Weighted U-value allowed for some trade-offs within element type
Envelope Trade-off calculations required for trade-offs across element
types
Maximum fenestration-to-wall ratio 40%
Installed lighting power density
Receptacle requirements
Labeling (insulation, fenestration)
HVAC plant minimum performance requirements (boilers, chillers)
HVAC distribution performance requirements (fans, pumps)
etc
90.1 Adoption as Building Code
Most widely adopted building energy standard in North
America
British Columbia
90.1-2004
Vancouver
90.1-2007
Ontario
90.1-2010 +
189.1-2009
envelope
12
0
100
200
300
400
500
Before 1920 1920-1959 1960-1969 1970-1979 1980-1989 1990-1999 2000-2004
Tota
l En
ergy
Inte
nsi
ty (
ekW
h/m
²)
Year building was contructed
Energy Use of All Buildings – By Age of Construction
Ref: Commercial and Institutional Building Energy Use, NRCAN 2005
Zero energy buildings by
year 3300
14
90.1-2010 Section 3
15
Definitions, Abbreviations and Acronyms OK sounds boring… BUT
How to interpret RATED R-VALUE
How to interpret SPANDREL
How to interpret METAL ROOF
How to interpret ADOPTING AUTHORITY
How to interpret BASELINE BUILDING DESIGN
How to interpret ATTIC ROOF
How to interpret SKYLIGHT
How to interpret FENESTRATION AREA
How to interpret F-FACTOR, U-FACTOR, C-FACTOR
How to interpret CONTINUOUS INSULATION!
AND LOTS OF OTHER STUFF!
Read this section! (hint spandrel, U-factor, Continuous Insulation) FYI: Spandrel sucks!
90.1-2010 Section 4
16
Administration and Enforcement
Interpretations, claims of exemption and rights of appear are
specified by the authority having jurisdiction
Conflict with other laws, codes etc, to be determined by
authority having jurisdiction
Normative Appendices are considered a part of the standard
Interpretations can be asked directly to ASHRAE
Informal or
Formal
90.1 – Air Barriers / Vestibules
5.4.3.1 Continuous Air Barrier
Clearly identified or otherwise noted on construction documents for each assembly
The joints, interconnections and penetrations shall be detailed or otherwise noted
5.4.3.1.A. Air Barrier Materials, Assemblies and Systems
(1) The air barrier materials, assemblies and systems that are in conformance with Part 5 of Division B of the Building Code shall be deemed to be in compliance with Sentence 5.4.3.1.3 and Sentence 5.4.3.2.
5.4.3.4 Shall have vestibules, exceptions:
Building entrances with revolving doors
Doors not intended to be a building entrance
Doors opening directly from a dwelling unit
Building is less than 90 m²
Doors separate from the building entrance that open unto a space under 280 m²
18
Division 3 Chapter 2 Revision
19
Mandatories insulation details introduced from MNECB
1997
5.5.3.5.1 Slabs 5.5.3.5.2 Continuity
of Insulation
Div 3 Ch 2 Revision to 90.1 – Thermal
Bridging Can be Ignored for….
5.5.3.7/8 For the purposes of Section 5, the effects of thermal bridging are waived for: continuous steel shelf angles (or
similar structural element) used to support the building facade provided there is a thermal break
structural connections of load bearing elements where a thermal break cannot be achieved
exposed structural projections of buildings where the total cross-sectional area of the exposed element does not exceed 2%
ties in masonry construction,
flashing, and
top exposed portion of foundation walls provided the exposure does not exceed 200 mm
20
90.1 Section 5 Building Envelope
Climate Definitions
21
Climate Zone Definitions for Ontario
Zone Number Thermal Criteria
Zone 5 HDD18 < 4000
Zone 6 4000 < HDD18 < 5000
Zone 7 HDD18 > 5000
If space is electrically heated, then
ALWAYS use Zone 7
90.1 Chapter 5
Space Conditioning Categories
90.1 Section 5.5
Comply with Tables
(SB5.5-5 thru -7)
Minimum RATED R-values
of insulation
Maximum U-Factor, C-
Factor or F-Factor
Appendix A tables
Appendix A9 calculations
2-D calculations (e.g. Therm)
22
90.1 Chapter 5 How to Use Envelope Tables
Determine Climate Zone 5, 6 or 7
Determine envelope category Roof
Insulation above deck
Metal Building
Attic & other
Walls above grade Mass
Metal Building
Steel-framed
Wood-framed & other
Etc.
Determine space conditioning category Non-Residential
Residential
Semi-heated
Today’s examples will be: Climate Zone 6
Non-Residential
23
90.1 Section 5 – Above Grade Wall
Requirements (SB-10 revisions)
25
Steel Framed Wall: Includes curtain-wall / window-wall
spandrel panel
ASHRAE Appendix A Assembly
U/C/F-Factor Look-up Tables
28
Roofs
A2.2 Roofs with Insulation Entirely Above Deck
A2.3 Metal Building Roofs
A2.4 Attic Roofs with Wood Joists
A2.4.2 Single Rafter Roofs
A2.5 Attic Roofs with Steel Joists
Walls
A3.1A Above-Grade Concrete Walls and Masonry Walls
A3.1B U-Factors, C-Factors, Ru, Rc and HC for Concrete
A3.1C U-Factors, C-Factors, Ru, Rc and HC for Concrete Block Walls
A3.1D Effective R-Values for Insulation/Framing Layers Added to Above/Below Grade Mass Wall
A3.2 Metal Building Walls
A3.3 Steel-Frame Walls
A3.4 Wood-Frame Walls
A4.2 Below Grade Walls
Exposed Floors
A5.2 Mass Floors
A5.3 Steel Joist Floors
A5.4 Wood Joist Floors
Slab on Grade Floors
A6.3 Slab on Grade Floors
13 mm drywall
102 mm steel stud @ 400
mm oc
13 mm exterior sheathing
102 mm z-girt @
600 mm oc with semi-
rigid
Metal siding
Metal Cladding with Z-Girts
29
Metal Cladding with Z-Girts
Nominal R-15 OBC Requirement: U-0.055 BTU/hr-ft²-°F
Actual R-8.6 Assembly: U-0.116 BTU/hr-ft²-°F
30
13 mm drywall
102 mm steel stud @ 400
mm oc
13 mm exterior sheathing
51 mm z-girt @
600 mm oc with spray
foam
51 mm z-girt @
600 mm oc with spray
foam
Metal siding
Metal Cladding with Orthogonal Z-Girts and
Spray Foam
31
Metal Cladding with X Z-Girts and Spray
Foam
32
Nominal R-24 OBC Requirement: U-0.055 BTU/hr-ft²-°F
Actual R-21 Assembly: U-0.048 BTU/hr-ft²-°F
Spandrel ??
33
Nominal R-14 OBC Requirement: U-0.055 BTU/hr-ft²-°F
Actual R-4.0 Assembly: U-0.250 BTU/hr-ft²-°F
Spandrel will be challenging (condensation?)
34
With 1” XPS interior insulation
Nominal R-19
Actual R-9.1
OBC Requirement: U-0.055 BTU/hr-ft²-°F
Assembly: U-0.11 BTU/hr-ft²-°F
With 2” XPS interior insulation
Nominal R-24
Actual R-14.2
OBC Requirement: U-0.055 BTU/hr-ft²-°F
Assembly: U-0.070 BTU/hr-ft²-°F
90.1 Section 5 – Maximum Fenestration
Area
35
5.5.4.2.1 Vertical
Fenestration Area
The total vertical
fenestration area shall be
less than 40% of the gross
wall area
90.1 Section 5 Fenestration Orientation
38
5.5.4.5 Fenestration Orientation
“South” Fenestration Area must greater or equal to “west” and
“east”
As ≥ Aw and As ≥ Ae
Exceptions for nearly any site restrictions
Topography, adjacent structures within 6 meters
Exceptions for 5.5.4.4.1 (street side fenestration)
Window heat loss
Flanking (and
installation)
Frame
Edge of Glass
Centre of Glass
glazing
system
U-value
Curtain Wall Plan View
40
90.1 Section 5 – Determining Fenestration
Performance
41
5.8.2 Vertical Fenestration U-Factors & SHGC shall be
determined in accordance with:
Standard NRFC 100 or
CSA-A440.2 or
90.1-2010 Table A8.2 – not recommended!
90.1 Section 5 – Determining Fenestration
Performance
FramePlus Online
Can be used for estimating
whole window
performance
Not for compliance!
http://tools.enermodal.com
/webframeplus
42
FramePlus Online Curtain-Wall
Performance
43
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0 2 4 6 8 10 12 14 16 18 20
Fen
est
rati
on
Syst
em
U-v
alu
e
Curtain Wall Frame Thermal Break Size in mm
Curtain Wall System U-values [BTU/ft²-hr-°F]
Dbl SB60 Argon
Tpl SB60 Argon
Climate Zone 5 & 6
Climate Zone 7
FramePlus Online Punched Alum Window
Performance
44
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0 2 4 6 8 10 12 14 16 18 20
Fen
est
rati
on
Syst
em
U-v
alu
e
Aluminum Frame Thermal Break Size in mm
Punched Aluminum Window U-values [BTU/ft²-hr-°F]
Dbl SB60 Argon
Tpl SB60 Argon
Climate Zone 5 & 6
Climate Zone 7
FramePlus Online Casement/Awning Alum
Window Performance
45
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0 1 2 3 4 5 6 7 8 9 10
Fen
est
rati
on
Syst
em
U-v
alu
e
Aluminum Frame Thermal Break Size in mm
Casement/Awning Aluminum Window U-values [BTU/ft²-hr-°F]
Dbl SB60 Argon
Tpl SB60 Argon
Climate Zone 5 & 6
Climate Zone 7
90.1 Section 5 Envelope Trade-Offs within
Prescriptive Path – Area Weighted
46
Area weighted U / C / F factors within
Class of construction and
Space conditioning category
Can trade off:
Steel Framed / Non-Residential Walls with
Steel Framed / Non-Residential Walls
Attic / Non-Residential Roof with
Attic / Non-Residential Roof
Metal Framing Vertical Fenestration Residential with
Metal Framing Vertical Fenestration Residential
Complying with Prescriptive Envelope: Area
Weighted U-Factor
Gross Walls
160,800 U-Factor Reff
W1 Spandrel 50,700 31.5% 0.154 6.5
W2 Steel Frame 50,700 31.5% 0.055 18.2
Window 59,400 37.0%
Uavg 0.104
Ravg 9.576
Gross Walls 160,800 U-Factor Reff
W1 Spandrel 50,700 31.5% 0.154 6.5
W2 Steel Frame 50,700 31.5% 0 Infinite!
Window 59,400 37.0%
Uavg 0.077
Ravg 13.000
Gross Walls 160,800 U-Factor Reff
W1 Spandrel 25,300 15.7% 0.154 6.5
W2 Steel Frame 76,100 47.3% 0.022 45.5
Window 59,400 37.0%
Uavg 0.055
Ravg 18.195
U-Factor Target for Steel Frames Walls: 0.055
47
Envelope Trade-Offs within Prescriptive
Path – Building Envelope Trade-off
90.1 Section 5.6
comply with:
5.1General
5.4 Mandatories
5.7 Submittals
5.8 Product information and
installation requirements
the envelope performance factor
is less than or equal to budget
building
Appendix C calculations
Do not try this at home!
Software Tool: ComCheck
OBC version being developed
48
ComCheck Software (Version 3.9.1 Shown)
49
OBC Version being developed
Exceeding 60% fenestration will still be a challenge with
only envelope trade-offs
Complying with Prescriptive Envelope:
Building Envelope Trade-Off: Wall Insulation
Gross Walls 160,800 U-Factor Reff
W1 Spandrel 50,700 31.5% 0.154 6.5
W2 Steel Frame 50,700 31.5% 0.055 18.2
Window 59,400 37.0%
-7% below code
Gross Walls 160,800 U-Factor Reff
W1 Spandrel 50,700 31.5% 0.154 6.5
W2 Steel Frame 50,700 31.5% 0 Infinite!
Window 59,400 37.0%
-2% below code
Gross Walls 160,800 U-Factor Reff
W1 Spandrel 25,350 15.7% 0.154 6.5
W2 Steel Frame 76,050 47.3% 0.036 28
Window 59,400 37.0%
+0.1% above code
Gross Walls 160,800 U-Factor Reff
W1 Spandrel 33,800 21.0% 0.154 6.5
W2 Steel Frame 67,600 42% 0.022 45.5
Window 59,400 37.0%
+0.1% above code
50
Complying with Prescriptive Envelope: Building
Envelope Trade-Off: Walls and Punched Window
Envelope 160,800 U-Factor Reff
W1 Steel Frame 80,400 50% 0.055 18.2
Code Punched Window 80,400 50% 0.45
-5% below code
Envelope 160,800 U-Factor Reff
W1 Steel Frame 80,400 50% 0.011 91
Code Punched Window 80,400 50% 0.45
+0.1% above code
Envelope 160,800 U-Factor Reff
W1 Steel Frame 56,250 35% 0.055 18.2
Hi-Perf Double Punched
Window 104,550 65% 0.32
+0.1% above code
Envelope 160,800 U-Factor Reff
W1 Spandrel 8,000 5% 0.154 6.5
Super Windows (3pl) 153,000 95% 0.22
+2% above code
51
Building Envelope Compliance Summary
52
Prescriptive Weighted
U-Value /
SHGC
Envelope
Trade-Off
Whole
Building
Energy Model
FWR ≤40% ≤40% ≤40% in baseline ≤40% in baseline
Fenestration
Tables SB5.5-5
thru -7
Tables SB5.5-5
thru -7
and within same
assembly type
and
conditioned
space
Compared to
Tables SB5.5-5
thru -7
Compared to
Tables SB5.5-5
thru -7 and
HVAC / Electrical
prescriptive
targets
Walls
Roof
HVAC Section 6 Heating/Cooling
Peformance
Mandatory
Minimum
Equipment
Efficiencies Tables
6.8.1 A-K
Equipment not
regulated by
NAECA shall have
permanent label
stating compliance
with 90.1
Equipment Minimum Efficiency
Air Conditioners COP 3.2 – 3.8
Heat Pumps COPc >3.2
COPh > 2.2
Chillers Air Cooled COP IPLV > 3.6
Reciprocating COP IPLV > 5.6
Centrifugal COP IPLV > 5.9
Furnaces > 78% AFUE or
> 80% thermal efficiency
Boilers under 88 kW / 300 MBH 80%
Over 733 kW / 2500 MBH 82%
Heat Rejection Axial Fan Open-circuit >3.23 L/(s-kW)
Centrifugal Fan Open-circuit >1.7 L/(s-kW)
Axial Fan Closed-circuit >1.7 L/(s-kW)
Centrifugal Fan Closed-circuit 0.59 L/(s-kW)
54
90.1 Section 6 – Variable Fan/Pump
Control
55
6.5.3.2.1 All Fan motors > 7.4 kW / 10 hp shall have one
of:
Variable speed drive
Variable pitch blades (axial fans)
Other controls capable of achieving 30% energy consumption
at 50% design flow
6.5.4.1 Systems having a total pump system power greater
than 7.5 kW / 10 hp shall be variable speed
Differential pressure transducer located where greatest
pressure difference will occur
90.1 Section 6 – Exhaust Air Heat Recovery
56
50% energy recovery
required for most multi-
zone systems
Exempt if
the largest single source of
exhaust is less than 75% of
O/A rate
More than 60% of outdoor
air heating from site solar
or site recovered energy
Operates less than
20 hr/week
% Outdoor Air at
Full Design
Airflow Rate
Design Supply Air
Flow Rate
≥ 30% and < 40% > 2596 L/s > 5500
CFM
≥ 40% and < 50% > 2124 L/s > 4500
CFM
≥ 50% and < 60% > 1652 L/s > 3500
CFM
≥ 60% and < 70% > 944 L/s > 2000
CFM
≥ 70% and < 80% > 472 L/s > 1000
CFM
> 80% > 0 > 0
90.1 Section 7
90.1 Requirements
SB-10 Revisions
Canadian Standards
7.4.5.2 Heated exterior
public pools and public spas
shall be equipped with a
pool cover
Unless 60% of their annual
heating from site-recovered
or solar sources
57
90.1 Section 8
8.4.2 Automatic Receptacle Control For private offices, open office
and computer classrooms
50% of receptacles shall have either Occupancy sensors
On a schedule to turn off during unoccupied hours
Any other means to ensure power is turned off during unoccupied hours
Exceptions where it can be shown that equipment needs to be on continuously
58
90.1 Section 9 Occupant sensor or timer switch
shall be used in:
Classrooms and lecture halls
Conference, meeting and training rooms
Employee lunch and break rooms
Storage and supply rooms (15 to 305 m²)
Rooms used for document copying and printing
Office spaces up to 76 m²
Restrooms
Dressing, locker and fitting rooms
Exception for space
With multi-scene control
Shop and laboratory classrooms
where automatic lights would endanger safety or security
24-hour operation spaces
59
90.1 Section 9 Lighting Power Density
60
Table 9.5.1 ASHRAE 90.1 LPD using Building Area Method 2007 2010 Reduction
Building Area Type W/m2 W/m2 Automotive facility 10 8.8 12% Convention centre 13 11.6 11% Courthouse 13 11.3 13% Dining: bar lounge/leisure 14 10.7 24% Dining: cafeteria/fast food 15 9.7 35% Dining: family 17 9.6 44% Dormitory 11 6.6 40% Exercise centre 11 9.5 14% Fire station N/A 7.6 N/A Gymnasium 12 10.8 10% Health-care clinic 11 9.4 15% Hospital 13 13 0% Hotel 11 10.8 2% Library 14 12.7 9% Manufacturing facility 14 11.9 15% Motel 11 9.5 14%
61
Table 9.5.1 ASHRAE 90.1 LPD using Building Area
Method 2007 2010 Reduction Building Area Type W/m2 W/m2 Motion picture theatre 13 8.9 32% Multifamily 8 6.5 19% Museum 12 11.4 5% Office 11 9.7 12% Parking garage 3 2.7 10% Penitentiary 11 10.4 5% Performing arts theatre 17 15 12% Police/fire station 11 10.3 6% Post office 12 9.4 22% Religious builidng 14 11.3 19% Retail 16 15.1 6% School/university 13 10.7 18% Sports arena 12 8.4 30% Town hall 12 9.9 18% Transportation 11 8.3 25% Warehouse 9 7.1 21% Workshop 15 2.9 81%
Average
reduction
in LPD 19%
What about Division 4?
62
Division 4 of SB 10:
if the building is within the scope of Part 9 Div B of the OBC
and,
does not contain a residential occupancy, and
does not use electric space heating, and,
is intended for occupancy on a continuing basis during the
winter months
i.e. most Non-Residential Part 9 buildings
Division 4 Building Envelope
63
Largely the same as the SB5-5 Tables of Division 3
Fewer climate zone, space categories, envelope types
If Vertical fenestration gross area exceeds 40% or
Skylights exceed 5%
Use Division 3 paths (including trade-offs and energy modeling)
SB-10 Division 4 – HVAC Requirements
65
Multi-zone systems
Revert to Division 3 (90.1-2010 + SB10 Revisions)
Single-zone systems
Use Division 3 90.1-2010 equipment performance values
Plus details on next slide…. (largely reminiscent of 90.1-2010)
SB-10 Division 4 Single Zone HVAC Details
66
(4) An air-conditioning system with a cooling capacity of 40 kW or more shall have an economizer,
(a) controlled by appropriate high limit shut-off control, and
(b) equipped with either barometric or powered relief sized to prevent excess pressurization of the building.
(5) Outdoor air dampers for economizer use shall be provided with blade and jamb seals.
(6) A heat recovery ventilator with a recovery effectiveness of 50% or more at the outside winter design temperature shall be provided where the quantity of the outdoor air supplied to the air duct distribution system is,
(a) more than 1 400 L/s, and
(b) more than 70% of the supply air quantity of the system.
(7) Where a heat recovery ventilator is installed, the system shall have provisions to bypass or control the heat recovery ventilator to permit operation of the air economizer.
(8) A heating, ventilating and air-conditioning system shall be controlled by a manual changeover or dual setpoint thermostat.
(9) Except for a system requiring continuous operation, a heating, ventilating and air-conditioning system that has a cooling or heating capacity greater than 4.4 kW and a supply fan motor rated for more than 0.5 kW shall be provided with a time clock that,
(a) is capable of starting and stopping the system under different schedules for seven different day-types per week,
(b) is capable of retaining programming and time setting during a loss of power for a period of 10 hours or more,
(c) includes an accessible manual override that allows temporary operation of the system for up to two hours,
(d) is capable of temperature setback down to 13°C during off-hours, and
(e) is capable of temperature setup to 32°C during off-hours.
(10) Where separate heating and cooling equipment serves the same temperature zone, thermostats shall be interlocked to prevent simultaneous heating and cooling.
(11) A heating, ventilating and air-conditioning system with a design supply air capacity greater than 5000 L/s shall have optimum start controls.
When should I expect an Energy Model to
Demonstrate Compliance?
68
Opaque wall assembly has lots of thermal bridging
standard spandrel panel has very low insulating value
z-girt walls
steel frames walls without exterior insulation
High amounts of glazing (>40%)
Up to 65% with very best double glazed
Up to 95% with triple glazed (super windows)
Curtain wall and window wall buildings
Likely Building Types
Condominiums
Offices
Performance Compliance Paths
69
25% less than MNECB
5% less than 90.1-2010 (without SB-10 revisions)
Less than or equal to SB-10 (90.1-2010 + SB-10 revisions)
Design must comply with mandatory requirements
Reference complies with prescriptive requirements of:
MNECB,
90.1-2010 or
SB-10
Overall building energy consumption
proposed design vs. reference design
regulated loads only
www.enermodal.com
Closing Quotes
71
Ludwig Wittgenstein (engineer, mathematician, philosopher)
“I don't know why we are here, but I'm pretty sure that it is not in order to enjoy ourselves.”
W.H. Auden (poet)
“We are all here on earth to help others; what on earth the others are here for I don't know.”
Kurt Vonnegut (writer)
"We are put on earth to fart around....don't let any one tell you any different."