Technical Manual Installation type with fire resistance class PATENTED FIRE DAMPER CIRCULAR SERIES WH45 - 500 Pa Cert. N° 1812-CPR-1007 WH45

Upload: others

Post on 09-Mar-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

Technical Manual

Installation type with fire resistance class

PATENTED FIRE DAMPERCIRCULAR SERIES WH45 - 500 Pa

Cert. N° 1812-CPR-1007

WH45

Page 2: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box
Page 3: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

3

Overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4Description � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4General characteristics � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4European Standards applied � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4Certifications and approvals � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4Components � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4Available dimensions � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4Performances � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 4Fire resistance classification according to EN 13501-3-2005 � � � � � � � � � � � � � � � � � � � � � � � �  p� 5Mechanism type � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 6

Technical data � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 8Dimension � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 8Weights � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 8

Installation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 9Intended use � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 9Prohibited uses � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 9Flexible connector use � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 9Blade rotation axis positioning � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 9Minimum distances � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 9Wall characteristics � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 11Installation within vertical rigid wall EI 120 S � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 13Installation within vertical light wall (plasterboard) EI 90 S � � � � � � � � � � � � � � � � � � � � � � � �  p� 14Installation within vertical light wall (gypsum blocks wall) EI 90 S � � � � � � � � � � � � � � � � � � � �  p� 15Installation within vertical light wall (gypsum blocks wall) EI 120 S � � � � � � � � � � � � � � � � � � � �  p� 16Installation within floor EI 90 S � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 17Installation within floor EI 120 S � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 18Installation within floor EI 180 S � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 19

Electrical connections � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 20Electrical wiring � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 20Electrical specifications � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 21

Maintenance and inspections � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 22Periodic inspection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 22

Selection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 23Air flow rates in relation to the diameter � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 23Air flow rates as a function of the pressure drop � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 23Air flow rates as a function of generated sound levels � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 23Pressure drop and sound level graph Ø 200-560 � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 24Pressure drop and sound level graph Ø 450-800 � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 25Sound spectrum table � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 25

Accessories and spare parts � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 26

How to order � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 29Motorized fire dampers � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 29Fire damper with manual control � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 29Electric motor driven actuators � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 30

Specification Text � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 31Series WH45 circular fire damper � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 31

Revision Index � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �  p� 32

TAbLE oF CoNTENTS WH45

3

Page 4: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

4

ovERvIEW � Description

The WH45 fire dampers were designed for air duct installa-tion when the air duct crosses fire resistance walls or floors. They stop fire and smoke from spreading through air ducts.Tested and classed in accordance with EN 1366-2 and EN 13501-3 regulations with 500 Pa depression.Studied and optimized for medium and big diameter ducts focusing on aeraulic and acoustical performance.Equipped with various different mechanisms completely outside the wall, easily interchangeble even after installa-tion.

� General characteristicsCasing made from galvanized carbon steel.Air duct connection gasket.Intumescent sealing gasket.opening/closing mechanism with IP42 protection box (IP54 for motorized version).40 mm thick closing blade made with refractory material.Lip seal on blade border for cold smoke seal.Internal intumescent gasket for hot smoke seal.

� European Standards appliedCE certification EN 15650Test EN 1366-2Classification EN 13501-3Thermal fuse reliability ISO 10294-4Air tightness EN 1751Resistance to corrosive environments EN 60068-2-52

� Certifications and approvalsCE Certificate of Constancy of Performance n° 1812-CPR-1007 EfectisGerman approval n° Z-56.4212-987 DIBtNF certification n° 09/02.03 AFNORSwiss approval n° 23221 VKF-AEAI

� Components

1. Casing made from 2 galvanized carbon steel ducts.2. Mineral fiber gasket between the 2 fire damper casings.3. Intumescent graphite gasket on inside of casing for the hot seal

of the blade once closed4. Damper blade made from refractoring material5. Gasket to prevent air losses on the mechanism plate.

6. Blade rotation axis, pivots housing.7. Blade drive with crank and slotted link mechanism8. Protection box9. Manual closing device (Test button)10. Temperature controlled closing device (thermal fuse)

� Available dimensionsØ mm 200 250 300 315 355 400 450 500 560 600 630 710 800

� PerformancesPerformance Reference standard ClassThermal fuse testing ISO 10294-4 Compliant

ovERvIEW WH45

4

Page 5: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

5

Performance Reference standard ClassOpen and Close cycle reliability EN 15650 CompliantResistance to corrosion in humid and saline environments EN 60068-2-52 Degree of severity 2Air tightness of casing EN 1751 Class C (1)Blade seal EN 1751 Class 2 minimum

(1) Casing leakage class C for diameter bigger than 315 mm as per EN 1751. Casing leakage class B minimum for diameter less than or equal to 315 mm as per EN 1751 (class C on request).

� Fire resistance classification according to EN 13501-3-2005

EI 180 S(500 Pa)

EI 120 S(500 Pa)

EI 90 S(500 Pa)

EI 60 S(500 Pa)

Rigid

wall

Installation within vertical rigid wall EI 120 S  p. 13Wall minimum thickness 100 mmWall minimum density 500 kg/m³Mortar sealingve (i o)

W -Ø

min 200max 800

Ømin 200max 800

Ømin 200max 800

Flexib

le wa

ll

Installation within vertical light wall (plasterboard) EI 90 S  p. 14Wall minimum thickness 100 mmWall rock wool minimum density 100 kg/m³Plasterboard and rock wool 100 kg/m³ sealingve (i o)

D - -Ø

min 200max 800

Ømin 200max 800

Installation within vertical light wall (gypsum blocks wall) EI 90 S  p. 15Wall minimum thickness 70 mmWall minimum density 995 kg/m³Plaster putty sealingve (i o)

W - -Ø

min 200max 800

Ømin 200max 800

Installation within vertical light wall (gypsum blocks wall) EI 120 S  p. 16Wall minimum thickness 100 mmWall minimum density 995 kg/m³Plaster putty sealingve (i o)

W -Ø

min 200max 800

Ømin 200max 800

Ømin 200max 800

Floor

Installation within floor EI 90 S  p. 17Floor minimum thickness 100 mm Floor minimum density 650 kg/m³Mortar sealingho (i o)

W - -Ø

min 200max 800

Ømin 200max 800

Installation within floor EI 120 S  p. 18Floor minimum thickness 150 mm Floor minimum density 650 kg/m³Mortar sealingho (i o)

W -Ø

min 200max 800

Ømin 200max 800

Ømin 200max 800

Installation within floor EI 180 S  p. 19Floor minimum thickness 150 mm Floor minimum density 2200 kg/m³Mortar sealingho (i o)

min 200max 800

Ømin 200max 800

Ømin 200max 800

Ømin 200max 800

Ø is the minimum and maximum nominal diameter of fire dampers in mmve Vertical installationho Horizontal installation(i o) Origin of fire irrelevantPa Pascal of depressionE IntegrityI Thermal insulationS Smoke sealW Wet method sealingD Dry method sealingCert. N° 1812-CPR-1007

ovERvIEW WH45

5

Page 6: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

6

�Mechanism type

� WH45B - Manual and WH45M - Manual with magnet

1. Manual opening lever2. Protection box3. Lever position when the blade is open4. Lever position when the blade is closed5. Magnet knob (for magnetic version)6. Closed blade indicator7. Open blade indicator8. Manual closing button

Blade closing modeAutomatic closing with thermal fuse.The WH45b control mechanism has a thermosensitive element that automatically closes the blade when the temperature in the duct exceeds 70°C (or 95°C for the fire damper with 95°C thermal fuse).It is possible to close the damper by pressing the indicated button.If the manual mechanism is equipped with electromagnet (WH45M version) it is possible to remotely close the fire damper.The manual command mechanism with magnet is equipped with an electromagnet which, in case power is interrupted (interuption magnet version) or when power is supplied (input magnet version), comands the closing of the damper.

Blade opening modeIn case of closed damper by pressing the closing button or remotely by electromagnet (magnetic version), it is possi-ble to manually open the fire damper blade by rotating the lever antyclockwise.For power supply interruption electromagnet, provide power supply and pull the magnet knob before opening the fire damper.In case of closed damper as a result of the action of the thermosensitive element, it is possible to manually reopen the damper by rotating the lever counterclockwise once the element has been replaced.

Position indication microswitcheson request, the fire damper can be supplied with posi-tion microswitches (SA/SC/S2 optional) that signal the

blade position (open or closed). Refer to Electrical connec-tions  p. 20 paragraph for more details.

Closing by remote controlWith power supply input or interruption magnet (WH45M version only).

Temperature calibration of thermosensitive element for automatic damper closing70 °C±7 °C (Standard)95 °C±9 °C (on request).

� WH45VPB/DPB/VGB/DGB - Belimo motorized version

1. Manual closing switch2. Manual opening lever3. Position indicator

Blade closing modeAutomatic closing with thermal fuse.The WH45vPb/DPb/vGb/DGb control mechanism has a thermosensitive element that automatically closes the blade when the temperature in the duct or in the room exceeds 72°C (or 95°C for the 95°C version).To close the damper when the motor is connected, press the switch on the temperature sensor or cut off the power supply.

Blade opening modeTo open the damper with the electric motor driven actua-tor, provide power supply to the motor. Refer to the section Electrical connections  p. 20 for further information.To manually open the damper, use the handle supplied and carefully rotate counterclockwise to the 90° indicator. To hold the damper in open position, carefully rotate the handle clockwise.For the vGb/DGb version the rotation is opposite to that indicated aboveDuring the manual opening of the damper, power must not be supplied to the motor.

Position indication microswitchesThe motorized versions are supplied with two microswitch-es to show the blade’s position (open or closed). Refer to the section Electrical connections   p.  20 for further in-formation.

ovERvIEW WH45

6

Page 7: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

7

Closing by remote controlIf power to the motor is cut off, the blade will close.

Temperature calibration of thermosensitive element for automatic damper closing72 °C±7 °C (Standard)95 °C±9 °C (on request).

� WH45VPS/DPS/VGS/DGS - Siemens motorized version

1. Manual closing switch2. Manual opening lever3. Screwdriver4. Position indicator

Blade closing modeAutomatic closing with thermal fuse.The WH45vPS/DPS/vGS/DGS control mechanism has a thermosensitive element that automatically closes the blade when the temperature in the duct or in the room exceeds 72°C (or 95°C for the 95°C version).To close the damper when the motor is connected, press the switch on the temperature sensor or cut off the power supply.

Blade opening modeTo open the damper with the electric motor driven actua-tor, provide power supply to the motor. Refer to the section Electrical connections  p. 20 for further information.To manually open the damper, use the handle supplied and carefully rotate counterclockwise to the 90 °C indica-tor. To hold the damper in open position, rotate the screw anticlockwise as shown in the picture.During the manual opening of the damper, power must not be supplied to the motor.

Position indication microswitchesThe motorized versions are supplied with two microswitch-es to show the blade’s position (open or closed). Refer to the section Electrical connections   p.  20 for further in-formation.

Closing by remote controlIf power to the motor is cut off, the blade will close.

Temperature calibration of thermosensitive element for automatic damper closing72 °C±7 °C (Standard)95 °C±9 °C (on request).

ovERvIEW WH45

7

Page 8: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

8

TECHNICAL DATAThe sizes shown are in mm.

� Dimension

Ø mm 200 250 300 315 355 400 450 500 560 600 630 710 800S blade exposition mm - - - - - - - - - - - 35 40

� Dimension WH45B

� Dimension WH45M

� Dimension SIEMENS WH45VGS/DGS

� Dimension BELIMO WH45VGB/DGB

�WeightsØ mm 200 250 300 315 355 400 450 500 560 600 630 710 800Weight kg 7 8 9 10 11 12 14 15 18 20 22 26 31

Manual version. Motorized version: +1 kg

TECHNICAL DATA WH45

8

Page 9: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

9

INSTALLATIoNThe sizes shown are in mm.

� Intended useThe MP3 fire dampers are “ventilation duct fire dampers. According to the installation and operation instructions in-dicated by MP3, they maintain fire compartments accord-ing to the 3.5 paragraph of EN 15650:10 standard.”It is compulsory to install the fire damper according to the instructions indicated in the technical data sheet and man-ual to maintain the declared performances and, in particu-lar, the fire classes.Use permitted in any civil and industrial building.Use permitted in saline atmosphere, for example:

maritime and port enviroments;fish markets;slaughterhouses;cheese makers.

� Prohibited usesUse with installations different to those described in the technical data sheet and manual;use as smoke control damper;use as shut off damper according to DIN 1946-4;use in external environments without adequate protec-tion from atmospheric conditions;use in explosive environments;use on board of ships;use in cooker extraction hoods;use in pneumatic conveying systems of dust or corn;use in ventilation systems within locations subject to chemical contamination;use in non inspectable enviroments.

� Flexible connector useIt is suggested to install flexible connectors to compensate any duct thermal expansion and wall bending in case of fire.

1. Fire damper2. Flexible connector

1. Fire damper2. Flexible connector3. Extension junction

Refer to the section Technical data   p.  8 for blade expo-sition values.

� Blade rotation axis positioningThe fire damper can be installed both with the blade axis positioned vertically, horizontally or tilted in any angle.

�Minimum distancesIt is recommended to keep enough space for using the control mechanism or for maintenance.Standard (EN 1366-2 art. 13.5) states that:

INSTALLATIoN WH45

9

Page 10: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

10

between 2 or more fire dampers installed on the same construction support the minimum distance is 200 mmbetween each fire damper and floor, ceiling or wall, the minimum distance is 75 mm

if no specific tests were performed by the manufacturer (EN 1366-2 art. 7.3).

1. Floor2. Vertical lateral wall

INSTALLATIoN WH45

10

Page 11: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

11

�Wall characteristicsThe European standard for fire dampers foresees a precise correlation between the wall/floor characteristics and the fire resistance class obtained, as well as the correlation be-tween wall/floor used for the test and wall/floor used for the actual installation.The test results obtained on a type of wall/floor are valid also for walls/floor of the same type but with greater thick-ness and/or density than those used in the test.For plasterboard walls, the test results are also valid for walls with a greater number of plasterboard layers on each side.As a result, the indicated thickness and density characteris-tics are to be considered as minimum values.The wall/floor in which the fire dampers are installed must be fire class certified according to the standards foreseen for the structure.If the fire resistance class of the wall/floor is different from that of the fire damper in the specific installation condi-tions, the fire class to be used as reference will be the lesser of the two.

� Rigid wallsCan be made with aerated concrete blocks, poured con-crete, concrete panels, perforated cell elements in concrete or brick in accordance with the following characteristics:

minimum thickness 100 mm;minimum density 500 kg/m³.

The use of a reinforcing beam above the opening is recom-mended for walls made from concrete blocks, bricks or in concrete cell elements.

1. Reinforcing beam

� Light plasterboard vertical wallsDuring testing, light plasterboard walls have been used with the following characteristics:

U-shaped horizontal metal frame (50 mm) and C-shaped vertical frame (49 mm) made from 0,6 mm thick sheet metal;vertical profiles placed with a maximum spacing of 625 mm between each other;Rock wool filling which has density 100 kg/m³;Each side is made from two plasterboard layers 12,5 mm thick, unalinged to avoid alignment between the joints of the layer above and below.

The following indications are given for the installation walls:metal profiles minimum width: 49 mm;metal profiles minimum thickness: 0,6 mm;

vertical profiles placed with a maximum spacing of 625 mm between each other;vertical profile fixing with selfthreading screws or by clinching to the bottom horizontal profile and insertion in the top horizontal profile;profiles fixed using self-threading screws or by clinching on every intersection.installation of a frame around the damper with base and height as shown in the installation instructions;rock wool filling which has minimum density 100 kg/m³:each side is made from two plasterboard layers 12,5 mm minumum thick, unalinged to avoid alignment between the joints of the layer above and below.the front plasterboards layers are fixed using long enough screws to pass through the lower plasterboard and attach to the steel profile underneath.

1. Plasterboard thickness 12,5 mm2. Rock wool, 100 kg/m³3. Horizontal U-shaped profile4. Vertical C-shaped profile

INSTALLATIoN WH45

11

Page 12: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

12

� Gypsum blocks light wallsGypsum blocks wall can be built with special solid gypsum blocks with interlocking shaped edges as indicated in the supplier’s instructions and according to the following char-acteristics:

minimum thickness 70 or 100 mm according to the type and resistance class required;minimum density 995 kg/m³.

It is generally advisable to first build the wall and then pro-vide the opening for the fire damper.

� Aerated concrete floorsAerated concrete floors can be built during installation or with preformed slabs with interlocking shaped edges ac-cording to the following characteristics:

minimum thickness 100 or 150 mm according to the type and resistance class required;

minimum density 650 kg/m³

� Poured concrete floorsPoured concrete floors can be built during installation or with preformed slabs with interlocking shaped edges ac-cording to the following characteristics:

minimum thickness 100 or 150 mm according to the re-sistance class required;minimum density 2200 kg/m³.

� Fire damper installation in wall/floor with greater thickness than those tested

The extension from the wall/floor of the fire damper, mech-anism side, remains that of the test.Refer to the following example drawing.

1. Gypsum blocks light walls2. Aerated concrete floors, poured concrete floors3. Walls/floors with thickness greater than those used during the test

INSTALLATIoN WH45

12

Page 13: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

13

� Installation within vertical rigid wall EI 120 SThe WH45 fire dampers classified EI 120 S within vertical rigid walls, guarantee fire and heat sealing for 120 minutes only if installed inside walls with a minimum fire resistance class of REI 120, minimum thickness of 100 mm and mini-mum density of 500 kg/m³.This said, the fire resistance rate will be that of the wall, be-ing the weaker of the two.In accordance with standard EN 1366-2 (Article 13.6) the results of the tests are extended to thicker or higer density walls.WH45 series fire dampers can therefore also be installed within walls made of brick or concrete with a minimum thickness of 100 mm.Comply with the minimum distances indicated on section Minimum distances  p. 9

� Wall openingA circular opening must be provided in the wall 25 mm greater than the nominal diameter of the fire damper. It is advisable not to exceed by more than 10 mm from the in-dicated sizes so as not to compromise the correct thermal insulation.

The use of a reinforcing beam above the opening is recom-mended for walls made from concrete blocks, bricks or in concrete cell elements.For walls built with perforated elements, it is also recom-mended that the area of the opening be made from full elements (for example aerated concrete blocks) to guaran-tee the correct adhesion of the mortar.

� Damper positioningPosition the damper in the opening so that the side of the closing mechanism extends from the wall by 260 mm.The double test (with the mechanism inside and outside the fire area) demonstrated that there is no preferred direc-tion for the position of the damper, both in relation to air flow and the side with the higher probability of exposure to fire, as indicated in standard EN1366-2 (paragraph 6.2).

� FillingFill the space between the wall and the damper using mor-tar suitable for use in fire resistant constructions, M10 class or higher.

1. Mortar M-10, EN998-2

INSTALLATIoN WH45

13

Page 14: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

14

� Installation within vertical light wall (plasterboard) EI 90 SThe WH45 fire dampers classified EI 90 S within light (plas-terboard) walls guarantee fire and heat sealing for 90 min-utes only if installed inside walls with a minimum fire re-sistance class of EI 90 and minimum thickness of 100 mm.This said, the fire resistance rate will be that of the wall, be-ing the weaker of the two.Laboratory test were carried out using 100 mm thick wall with two plasterboard layers 12,5 mm thick for side and in-sulated with rock wool 100 kg/m³ density.In accordance with standard EN 1366-2 (Article 13.6) the results of the tests are extended to thicker or higer density walls.Comply with the minimum distances indicated on section Minimum distances  p. 9

� Wall openingA rectangular opening must be provided in the wall with a frame made by metal profiles ideal for use with plaster-board (min. thickness 0,6 mm) with a side 35 mm greater than the nominal diameter of the damper. It is advisable not to exceed by more than 10 mm from the indicated siz-es so as not to compromise the correct thermal insulation.

� Damper positioningPosition the damper in the opening so that the side of the closing mechanism extends from the wall by 260 mm.The double test (with the mechanism inside and outside the fire area) demonstrated that there is no preferred direc-tion for the position of the damper, both in relation to air flow and the side with the higher probability of exposure to fire, as indicated in standard EN1366-2 (paragraph 6.2).

� FillingFill the space between the wall and the fire damper using rock wool which has density of 100 kg/m³, or using mortar suitable for use in fire resistant constructions, M10 class or higher or plaster putty.Cover the rock wool (or mortar, or plaster putty) by apply-ing on both faces of the wall a layer of plasterboard, to a total minimum thickness of 12,5 mm per side, to make a frame with a side 200 mm greater than the nominal diam-eter of the damper.

1. Rock wool, 100 kg/m³2. Plasterboard arch infill, thickness 12,5 mm3. Plasterboard thickness 12,5 mm4. Rock wool, 100 kg/m³, or mortar M-10, EN998-2 or plaster putty

INSTALLATIoN WH45

14

Page 15: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

15

� Installation within vertical light wall (gypsum blocks wall) EI 90 SThe WH45 fire dampers classified EI 90 S within vertical light walls built with gypsum blocks “carreaux de plâtre”, guarantee fire and heat sealing for 90 minutes only if in-stalled inside walls with a minimum fire resistance class of EI 90, minimum thickness of 70 mm and minimum density of 995 kg/m³.This said, the fire resistance rate will be that of the wall, be-ing the weaker of the two.In accordance with standard EN 1366-2 (Article 13.6) the results of the tests are extended to thicker or higer density walls.Comply with the minimum distances indicated on section Minimum distances  p. 9

� Wall openingA circular opening must be provided in the wall 25 mm greater than the nominal diameter of the fire damper. It is

advisable not to exceed by more than 10 mm from the in-dicated sizes so as not to compromise the correct thermal insulation.

� Damper positioningPosition the damper in the opening so that the side of the closing mechanism extends from the wall by 275 mm.The double test (with the mechanism inside and outside the fire area) demonstrated that there is no preferred direc-tion for the position of the damper, both in relation to air flow and the side with the higher probability of exposure to fire, as indicated in standard EN1366-2 (paragraph 6.2).

� FillingFill the space between the wall and the damper using plas-ter putty.

1. Plaster putty

INSTALLATIoN WH45

15

Page 16: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

16

� Installation within vertical light wall (gypsum blocks wall) EI 120 SThe WH45 fire dampers classified EI 120 S within vertical light walls built with gypsum blocks “carreaux de plâtre”, guarantee fire and heat sealing for 120 minutes only if in-stalled inside walls with a minimum fire resistance class of EI 120, minimum thickness of 100 mm and minimum den-sity of 995 kg/m³.This said, the fire resistance rate will be that of the wall, be-ing the weaker of the two.In accordance with standard EN 1366-2 (Article 13.6) the results of the tests are extended to thicker or higer density walls.Comply with the minimum distances indicated on section Minimum distances  p. 9

� Wall openingA circular opening must be provided in the wall 25 mm greater than the nominal diameter of the fire damper. It is

advisable not to exceed by more than 10 mm from the in-dicated sizes so as not to compromise the correct thermal insulation.

� Damper positioningPosition the damper in the opening so that the side of the closing mechanism extends from the wall by 260 mm.The double test (with the mechanism inside and outside the fire area) demonstrated that there is no preferred direc-tion for the position of the damper, both in relation to air flow and the side with the higher probability of exposure to fire, as indicated in standard EN1366-2 (paragraph 6.2).

� FillingFill the space between the wall and the damper using plas-ter putty.

1. Plaster putty

INSTALLATIoN WH45

16

Page 17: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

17

� Installation within floor EI 90 SThe WH45 fire dampers classified EI 90 S within concrete floors, can guarantee fire and heat sealing for 90 minutes only if installed inside floors with a minimum fire resistance class of REI 90, minimum thickness of 100 mm and mini-mum density of 650 kg/m³.This said, the fire resistance rate will be that of the floor be-ing the weaker of the two elements.In accordance with standard EN 1366-2 (Article 13.6) the results of the tests are extended to thicker or higer density floors.Comply with the minimum distances indicated on section Minimum distances  p. 9

� Floor openingA circular opening must be provided in the floor 40 mm greater than the nominal diameter size of the damper. It is advisable not to exceed by more than 10 mm from the in-

dicated sizes so as not to compromise the correct thermal insulation.

� Damper positioningPosition the damper in the opening so that the side of the closing mechanism extends from the floor by 260 mm.The mechanism can be located both above and below the floor.The double test (with the mechanism inside and outside the fire area) demonstrated that there is no preferred direc-tion for the position of the damper, both in relation to air flow and the side with the higher probability of exposure to fire, as indicated in standard EN1366-2 (paragraph 6.2).

� FillingFill the space between the floor and the damper using mortar suitable for use in fire resistant constructions, M10 class or higher.

1. Mortar M-10, EN998-2

INSTALLATIoN WH45

17

Page 18: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

18

� Installation within floor EI 120 SThe WH45 fire dampers classified EI 120 S within concrete floors, can guarantee fire and heat sealing for 120 minutes only if installed inside floors with a minimum fire resistance class of REI 120, minimum thickness of 150 mm and mini-mum density of 650 kg/m³.This said, the fire resistance rate will be that of the floor be-ing the weaker of the two elements.In accordance with standard EN 1366-2 (Article 13.6) the results of the tests are extended to thicker or higer density floors.Comply with the minimum distances indicated on section Minimum distances  p. 9

� Floor openingA circular opening must be provided in the floor 40 mm greater than the nominal diameter size of the damper. It is advisable not to exceed by more than 10 mm from the in-

dicated sizes so as not to compromise the correct thermal insulation.

� Damper positioningPosition the damper in the opening so that the side of the closing mechanism extends from the floor by 235 mm.The mechanism can be located both above and below the floor.The double test (with the mechanism inside and outside the fire area) demonstrated that there is no preferred direc-tion for the position of the damper, both in relation to air flow and the side with the higher probability of exposure to fire, as indicated in standard EN1366-2 (paragraph 6.2).

� FillingFill the space between the floor and the damper using mortar suitable for use in fire resistant constructions, M10 class or higher.

1. Mortar M-10, EN998-2

INSTALLATIoN WH45

18

Page 19: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

19

� Installation within floor EI 180 SThe WH45 fire dampers classified EI 180 S within concrete floors, can guarantee fire and heat sealing for 180 minutes only if installed inside floors with a minimum fire resistance class of REI 180, minimum thickness of 150 mm and mini-mum density of 2200 kg/m³.This said, the fire resistance rate will be that of the floor be-ing the weaker of the two elements.In accordance with standard EN 1366-2 (Article 13.6) the results of the tests are extended to thicker or higer density floors.Comply with the minimum distances indicated on section Minimum distances  p. 9

� Floor openingA circular opening must be provided in the floor 40 mm greater than the nominal diameter size of the damper. It is advisable not to exceed by more than 10 mm from the in-

dicated sizes so as not to compromise the correct thermal insulation.

� Damper positioningPosition the damper in the opening so that the side of the closing mechanism extends from the floor by 235 mm.The mechanism can be located both above and below the floor.The double test (with the mechanism inside and outside the fire area) demonstrated that there is no preferred direc-tion for the position of the damper, both in relation to air flow and the side with the higher probability of exposure to fire, as indicated in standard EN1366-2 (paragraph 6.2).

� FillingFill the space between the floor and the damper using mortar suitable for use in fire resistant constructions, M10 class or higher.

1. Mortar M-10, EN998-2

INSTALLATIoN WH45

19

Page 20: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

20

ELEC TRICAL CoNNEC TIoNS � Electrical wiring

Electrical connections must be done by qualified and trained people.Switch off the power supply before starting any work on the electric elements. Never switch on the power supply during electrical connections.

1. SC (closed damper) microswitch - on request2. SA (open damper) microswitch - on request3. Magnet - on request4. Magnet cables for wiring

� SC/SA microswitches position

1. “NC” contact of SC microswitch. When the fire blade is closed the circuit is open.

2. “NO” contact of SC microswitch. When the fire blade is closed the circuit is closed.

3. “NC” contact of SA microswitch. When the fire blade is open the circuit is open.

4. “NO” contact of SA microswitch. When the fire blade is open the circuit is closed.

� 230 V AC magnet wiring

1. 230 V AC power supply2. Magnet3. Rectifier

� 24 V DC magnet wiring

1. 24 V DC power supply2. Magnet

� WH45 - Motorized version

Belimo servomotor:bLF24T, bF24T, bLF230T, bF230T.

ELEC TRICAL CoNNEC TIoNS WH45

20

Page 21: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

21

Siemens servomotor:GNA126, GGA126.

Siemens servomotor:GNA326, GGA326.

Motorized fire dampers electical wiringTo connect the dampers to the power supply, proceed as follows:

Check that the voltage and electrical frequency are equivalent to those of the motor of the servomotor (check the motor’s information label);Make the connections as shown in the below diagram.

1 Negative (DC) or neutral (AC)2 Positive (DC) or phase (AC)3 Phase4 NeutralS1 Common closed damper microswitchS2 Normally closed, closed damper microswitchS3 Normally opened, closed damper microswitchS4 Common open damper microswitchS5 Normally closed, open damper microswitchS6 Normally opened, open damper microswitch

� Electrical specifications

WH45B WH45M, WH45VPS/DPS/VGS/DGS and WH45VPB/DPB/VGB/DGB

Voltage and power consumption -

Power interrruption magnet:P=4,5 W (24V DC or 230 V AC version)

Power input magnet:P=4,5 W (24V DC or 230 V AC version)

Motor 24V AC/DC (WH45VPB):Belimo BLF24TOpening: 5 WIn stand-by: 2,5 W

Motor 230V AC (WH45DPB):Belimo BLF230TOpening: 6 WIn stand-by: 3 W

24V AC/DC (WH45VGB) motor:Belimo BF24TOpening: 7 WIn stand-by: 2 W

230V AC (WH45DGB) Motor:Belimo BF230TOpening: 8 WIn stand-by: 3 W

Motor 24V AC/DC (WH45VPS):Siemens GNA126Opening: 3,5 WIn stand-by: 2 W

Motor 230V AC (WH45DPS):Siemens GNA326Opening: 4,5 WIn stand-by: 3,5 W

24V AC/DC motor (WH45VGS):Siemens GGA126Opening: 6 WIn stand-by: 1,5 W

230V AC motor (WH45DGS):Siemens GGA326Opening: 6 WIn stand-by: 2,5 W

Microswitches position contactsManual control version:15 - 400V1,8 A

Motorized version:Siemens: AC 24V…230V / 6 (2) ABelimo: DC 5V…AC 250V / 1mA…3A (0,5A)

Blade closing time Spring: 1 s motor: < 30 s

Protection degree IP42 IP42 MAGNETIC VERSION (WH45M) –IP54 MOTORIZED VERSION (WH45VPS/DPS/VGS/DGS, WH45VPB/DPB/VGB/DGB)

ELEC TRICAL CoNNEC TIoNS WH45

21

Page 22: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

22

MAINTENANCE AND INSPEC TIoNSThe MP3 fire dampers don’t need maintenance.

� Periodic inspectionThe damper inspection must be done according to nation-al law.The periodic inspection must be according to EN 15423 annex C and EN 15650 annex D.

MAINTENANCE AND INSPEC TIoNS WH45

22

Page 23: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

23

SELEC TIoN � Air flow rates in relation to the diameter

Ø Front section Net section Maximum air flowmm m² m² m³/h200 0,031 0,023 1696250 0,049 0,039 2649300 0,071 0,059 3815315 0,078 0,065 4206355 0,099 0,085 5342400 0,126 0,110 6782450 0,159 0,141 8584500 0,196 0,176 10598560 0,246 0,224 13294600 0,283 0,259 15260630 0,312 0,286 16825710 0,396 0,367 21369800 0,502 0,470 27130

� Air flow rates as a function of the pressure drop

ØΔP 20 Pa ΔP 30 Pa ΔP 40 Pa

Q Lw Q Lw Q Lwmm m³/h dB(A) m³/h dB(A) m³/h dB(A)200 618 43,8 757 49,9 874 54,3250 1149 45,8 1408 52,0 1625 56,3300 1908 47,5 2336 53,7 2698 58,0315 2185 48,0 2676 54,1 3090 58,5355 3046 49,1 3730 55,2 4307 59,6400 4244 50,2 5198 56,3 6002 60,7450 5888 51,3 7211 57,4 8326 61,8500 7891 52,2 9664 58,4 >Qmax --560 10812 53,3 13242 59,4 >Qmax --600 13098 53,9 >Qmax -- >Qmax --630 15000 54,4 >Qmax -- >Qmax --710 20912 55,5 >Qmax -- >Qmax --800 >Qmax -- >Qmax -- >Qmax --

� Air flow rates as a function of generated sound levels

ØLw 35 db(A) Lw 40 db(A) Lw 45 db(A)

Q ΔP Q ΔP Q ΔPmm m³/h Pa m³/h Pa m³/h Pa200 463 11,2 546 15,6 644 21,7250 804 9,8 948 13,6 1118 18,9300 1262 8,8 1489 12,2 1755 16,9315 1424 8,5 1680 11,8 1981 16,4355 1915 7,9 2258 11 2663 15,3400 2572 7,3 3034 10,2 3577 14,2450 3443 6,8 4060 9,5 4788 13,2500 4469 6,4 5270 8,9 6215 12,4560 5915 6 6976 8,3 8227 11,6600 7017 5,7 8275 8 9758 11,1630 7917 5,6 9337 7,7 11011 10,8710 10643 5,2 12551 7,2 14801 10800 14300 4,8 16864 6,7 19887 9,3

SELEC TIoN WH45

23

Page 24: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

24

� Pressure drop and sound level graph Ø 200-560

ExampleØ = Diameter [mm] Ø = 315 mmQ = Air flow [m³/h] Q = 3000 m³/hV1 = Frontal air speed [m/s] V1 = 10,7 m/sΔP = Pressure drop [Pa] From graph: ΔP = 37,7 PaLw = Sound level [dBa] From graph: Lw = 56 dBa

SELEC TIoN WH45

24

Page 25: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

25

� Pressure drop and sound level graph Ø 450-800

ExampleØ = Diameter [mm] Ø = 630 mmQ = Air flow [m³/h] Q = 20000 m³/hV1 = Frontal air speed [m/s] V1 = 17,8 m/sΔP = Pressure drop [Pa] From graph: ΔP = 36 PaLw = Sound level [dBa] From graph: Lw = 59 dBa

� Sound spectrum table

Correction used to estimate the octave band spectrum (Values to be added to the noise levels in dBa)Frontal speed Frequency Hz

m/s 63 125 250 500 1000 2000 4000 80006 15 7 4 -4 -9 -10 -15 -229 17 8 5 -4 -9 -10 -19 -20

12 20 9 5 -4 -9 -15 -16 -12

SELEC TIoN WH45

25

Page 26: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

26

ACCESSoRIES AND SPARE PARTSArch infill panels for plasterboard installation from Ø 200 to Ø 800 TAMP-WH45-Ø

Open blade microswitch WHKICKITClosed blade microswitch (necessary according to UNI 10365, art. 4.9) WHKFCKIT

Remote control magnet, optional for manual command fire dampers. Power supply input version: the fire damper blade closes when power is supplied. Power supply 24 V DC - 4,5 W

WHKMA024KIT

Remote control magnet, optional for manual command fire dampers. Power supply input version: the fire damper blade closes when power is supplied. Power supply 230 V DC - 4,5 W - rectifier included

WHKMA230KIT

Remote control magnet, optional for manual command fire dampers. Power supply interruption version: the fire damper blade closes when power is not supplied. Power supply 24 V DC - 4,5 W

WHKMG024KIT

Remote control magnet, optional for manual command fire dampers. Power supply interruption version: the fire damper blade closes when power is not supplied. Power supply 230 V DC - 4,5 W - rectifier included

WHKMG230KIT

WH45 manual mechanism with fuseholder group, cam, lever, protection box and 4 fixing nuts for Ø ≤ 315

WH45MAN3

WH45 manual mechanism with fuseholder group, cam, lever, protection box and 4 fixing nuts for Ø ≤ 315

WH45MAN4

WH45 manual mechanism with fuseholder group, cam, lever, protection box 4 fixing nuts and 1 microswitch closed damper for Ø ≤ 315

WH45MAN3CM

WH45 manual mechanism with fuseholder group, cam, lever, protection box 4 fixing nuts and 1 microswitch closed damper for Ø > 315

WH45MAN4CM

Motorized plate WH45/43 for Siemens GNA + fixing screws (motor not included) WH45MTSPMotorized plate WH45/43 for Siemens GGA + fixing screws (motor not included) WH45MTSGMotorized plate WH45/43 for Belimo BLF and BF + fixing screws (motor not included) WH45MTB

ACCESSoRIES AND SPARE PARTS WH45

26

Page 27: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

27

Belimo motor for dampers predisposed for use with BF24T / BLF24T, 24 V AC/DC power supply, thermofuse 72 °C

BF24T / BLF24T

Belimo motor for dampers predisposed for use with BLF24T-ST / BLF24T-ST, 24 V AC/DC power supply, thermofuse 72 °C with connection plugs for control and monitoring systems

BF24T-ST / BLF24T-ST

Belimo motor Top Line series for dampers predisposed for use with BF24TLT-ST, 24 V AC/DC power supply, thermofuse 72 °C with connection plugs for control and monitoring systems

BF24TLT-ST

Belimo motor for dampers predisposed for use with BF230T / BLF230T, 230 V AC power supply, thermofuse 72 °C

BF230T / BLF230T

Thermofuse 72 °C (spare part) WWEZBAE72Thermofuse 95 °C (accessory) WWEZBAE95Siemens motor for dampers predisposed for use with GGA126 / GNA126, 24 V AC/DC power supply, thermofuse 72 °C

GGA126 / GNA126

Siemens motor for dampers predisposed for use with GGA326 / GNA326, 230 V AC power supply, thermofuse 72 °C

GGA326 / GNA326

Thermofuse 72 °C (spare part) MT-FUSASK79.4Thermofuse 95 °C (accessory) MT-FUSASK79.5

Copper mechanical thermofuse 70 °C WK70Copper mechanical thermofuse 95 °C WK95

Matt black epoxy powder painting for WH45 fire damper casing WH45PAINT[Ø]

Communication and control unit BKS24-1B to control and monitor 1 fire damper with Belimo motor

WHBKS241B

Communication and control unit BKS24-9A to control and monitor up to 9 fire dampers with Belimo motor

WHBKS249A

Communication and power supply unit: BKN230-24 for Belimo motors BLF24T-ST e BF24T-ST WHBKN23024LON Communication and power supply unit: BKN230-24LON for Belimo motors BF24TL-T-ST WHKBKN230-24LONModbus Communication and power supply unit: BKN230-24MOD for Belimo motors BLF24T-ST and BF24T-ST

WHKBKN230-24MOD

Communication and power supply unit MPBUS for BKS24-9A or gateways Belimo UK24MOD and UK24BAC: BKN230-24-C-MP for Belimo motors BLF24T-ST and BF24T-ST

WHKBKN230-24-C-MP

Modbus Communication and power supply unit: BKN230MOD for Belimo motors BLF230T and BF230T

WHKBKN230MOD

ACCESSoRIES AND SPARE PARTS WH45

27

Page 28: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

28

Gateway UK24BAC Belimo for BACnet communication WHKUK24BAC

(1) Is recommended to install the position microswitches for the manual fire dampers with magnet.

ACCESSoRIES AND SPARE PARTS WH45

28

Page 29: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

29

HoW To oRDER �Motorized fire dampers

CodeType WH Circular fire damper

Series 45 Blade thickness 40 mm - 500 Pa air sealing

Motor type

VPS Siemens motor GNA126 (24V)DPS Siemens motor GNA326 (230V)VPB Belimo motor BLF24T (24V)DPB Belimo motor BLF230T (230V)

TPB Belimo motor BLF24T-ST (24V) with connection plugs for integration in control and monitoring systems

VGS Siemens motor GGA126 (24V)DGS Siemens motor GGA326 (230V)VGB Belimo motor BF24T (24V)DGB Belimo motor BF230T (230V)

TGB Belimo motor BF24T-ST (24V) with connection plugs for integration in control and monitoring systems

Dimension XYZ Nominal diameter (mm)

� Fire damper with manual control

CodeType WH Circular fire damper

Series 45 Blade thickness 40 mm - 500 Pa air sealing

Command typeB Manual commandM Manual command with magnet

Position indication microswitches

S0 Without position microswitches (not recommended)SA With open blade microswitchSC With closed blade microswitchS2 With two microswitches

Magnet

M0 Without magnet (only for command type “B”)MR With power supply interruption magnet, 24 V DCMI With power supply input magnet, 24 V DCMY With power supply interruption magnet, 230 V ACMZ With power supply input magnet, 230 V AC

Dimension XYZ Nominal diameter (mm)

Examples CodeWH45 fire damper with manual control, Ø 200 WH45B-S0-M0-200WH45 fire damper with manual control and two microswitches, Ø 500 WH45B-S2-M0-500WH45 fire damper with manual control, 24 V DC power interruption magnet, with closed blade microswitch, Ø 315 WH45M-SC-MR-315WH45 fire damper with manual control, 24 V DC power input magnet, with two microswitches, Ø 800 WH45M-S2-MI-800WH45 Siemens motorized 230V fire damper, Ø 250 WH45DPS-250

HoW To oRDER WH45

29

Page 30: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

30

� Electric motor driven actuators

Motor typeDiameters

200 250 300 315 355 400 450 500 560 600 630 700 800

Belimo

P P P P P P P G G G G G G

Siemens

P P P P P P P P P P P G G

Belimo Siemens24 V 230V 24 V 230V

P BLF24T BLF230T GNA126 GNA326

G BF24T BF230T GGA126 GGA326

HoW To oRDER WH45

30

Page 31: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

31

SPECIFICATIoN TExT � Series WH45 circular fire damper

DescriptionWH45 circular symmetric fire damper tested for fire resist-ance and smoke seal with 500 Pa depression as per EN 1366-2, classified according to EN 13501-3 and CE marked according to European Regulation UE 305/2011 and EN 15650 standard.It provides maximum safety by preventing the spread of fires within buildings guaranteeing a perfect isolation from heat and a complete air seal from hot and cold smoke. It can be connected to fire or smoke alarm systems to close the damper’s blade before the fire reaches the damper. This helps to prevent indirect damages caused by the spread of smoke and harmful combustion gasses.

Technical characteristicsAvailable diameters from 200 to 800 mmCase made from galvanized sheet steel, with a total length of 620 mm in 2 parts joined with bolts and min-eral fiber sealingClosing mechanism built according to UNI 10365, with thermal fuse certified to ISo 10294-4, a test button to check the correct working of the damper, a release sys-tem to block the damper in closed position and a visual signal “open/closed. The closing mechanism can be easi-ly interchanged and substituted:– with mechanical release and manual rearming– with mechanical release and manual rearming, can be

released remotely via a magnet and electric and signal– with electric release and rearming, via and integrat-

ed Siemens or belimo system tested according to EN 15650, composed by an electric thermal fuse and re-mote controlled servomotor via an electrical signal

blade damper made from calcium silicate material, com-plete with elastomer lip gasket for the air seal of cold smoke, as per EN 1366-2damper blade steel axis joined to casing with patented method, complete with low friction bearings, for maxi-mum performance in case of fireThermal, expanding graphite gasketThermal fuse with melting point certified ISo 10294-4 at 70 °C or 95 °C (version with mechanical release) or at 72 °C (version with servo motor)Absence of thermal bridge between the wall of installa-tion and the ducts before and afterResistance to salt spray, tested with severity 2, according to EN 60068-2-52Casing leakage class C for diameter bigger than 315 mm as per EN 1751.Casing leakage class b minimum for diameter less than or equal to 315 mm as per EN 1751 (class C on request).

InstallationInstallation within vertical rigid walls made from aerated concrete blocks, standard concrete or masonry with a minimum thickness of 100 mm and minimum density of 500 kg/m³ (EI 120 S)Installation within light plasterboard walls with mini-mum thickness of 100 mm (EI 90 S)

Installation within light walls made with gypsum blocks 100 mm thick and minimum density 995 kg/m³ (EI 120 S) or minimum thickness of 70 mm and minimum density 995 kg/m³ (EI 90 S)Installation within concrete floors with a minimum thick-ness of 150 mm and minimum denisty of 2200 kg/m³ (EI 180 S) or aerated concrete with minimum thickness 150 mm and minimum density 650 kg/m³ (EI 120 S) or aerated concrete with minimum thickness 100 mm and minimum density 650 kg/m³ (EI 90 S)Fire resistance characteristics independent from direc-tion of the source of the fire according to EN 1366-2 ar-ticle 6.2Installation possible with damper blade placed horizon-tally or vertically, with the mechanism placed in left/right or above/below

AccessoriesMotorised version with 24 v or 230 v servomotor in-stalled on the damperSet of microswitches with four No/NC position detect-ing connectors for open and closed damper, as per standard UNI 10365Immission and interruption magnet 24 v DC or 230 v AC with rectifierPower supply and communication unit LonWorks, MP-bus, Modbus, bacnet

SPECIFICATIoN TExT WH45

31

Page 32: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

WH45

32

REvISIoN INDExRevision n° Date of issue Description14/00 11/2014 First issue

15/07 07/2015

Added section:• Flexible connector use  p. 9• Blade rotation axis positioning  p. 9Added table:Revision Index  p. 32Updated drawing:• Installation within vertical light wall (plasterboard) EI 90 S  p. 14Updated section:• WH45VPB/DPB/VGB/DGB - Belimo motorized version  p. 6• Specification Text  p. 31Updated table:• Fire resistance classification according to EN 13501-3-2005  p. 5• Performances  p. 4• Accessories and spare parts  p. 26• Motorized fire dampers  p. 29General improvements

REvISIoN INDEx WH45

32

Page 33: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box

As the manufacturer is constantly improving its products, the aesthetic or dimensional features, the technical data, the equipment and accessories indicated could be subject to variations.

Page 34: WH45 - Lindab...5. Gasket to prevent air losses on the mechanism plate. 6. Blade rotation axis, pivots housing. 7. Blade drive with crank and slotted link mechanism 8. otPrection box