Page 1: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Western Area Power Administration

SF6 Program Presentation for

DOE - Fugitive Emissions Working Group

January 13, 2011

Page 2: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Gene Iley, Jr. – P2 CoordinatorWestern Area Power Administration

Loveland, Colorado

Page 3: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

• Western markets and transmits hydropower generated by 57 powerplants operated by the US Bureau of Reclamation and US Army Corps of Engineers.

• Western has 687 wholesale power customers that provide service to millions of consumers in 15 western states

Page 4: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

• Western owns and maintains 17,107 miles of transmission lines and 306 substations split up between 4 Regions.

Page 5: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are
Page 6: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

• The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages)

• There are numerous manufacturers and models of SF6 breakers in place throughout Western.

• Rocky Mountain Region alone has 53 different models of SF6 breaker, ranging from 2 to 1,840 lbs SF6.

• WAPA total nameplate capacity is 173,362 lbs (2009)

Page 7: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

WAPA SF6 Breakers

0

200

400

600

800

1000

14,4

00.0

0

20,0

00.0

0

34,5

00.0

0

41,8

00.0

0

115,

000.

00

138,

000.

00

161,

000.

00

230,

000.

00

345,

000.

00

500,

000.

00

525,

000.

00

23 2 143 36

866

40113

922

106 8 108

14,400.0020,000.0034,500.0041,800.00115,000.00138,000.00161,000.00230,000.00345,000.00500,000.00525,000.00

Voltage

# O

f B

rea

ke

rs

# Of Gas Breakers Per Voltage Class

Page 8: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

HISTORY - Oil breakers are being replaced by modern gas (SF6) breakers.

Page 9: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

SF6 Breaker Leakage

Page 10: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

345 kV SF6 Breaker – ABB ELF

(48 lbs total SF6 with Nitrogen – Almost Never Leaks)

Page 11: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

230 kV SF6 Breaker – Mitsubishi

(85 lbs total SF6 – Rarely Leaks)

Page 12: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are
Page 13: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

345 kV SF6 Breaker – ITE Gould

(1,840 lbs SF6 - Always Leaks)

Page 14: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are
Page 15: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

HISTORY – SF6 Program

• EPA asked us to join a voluntary partnership that prescribed a very specific methodology for SF6 management through a formal MOU.

• In the spirit of the MOU with EPA, Western developed its own system of SF6 management and reports to EPA annually.

• Rational was cost and what made best sense for us while still complying with the intent of the EPA MOU.

Page 16: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

SF6 Emissions Reduction

- Leak detection using cameras (EPRI)

- Leak repair by Electrician crews

- BMPs by Electrician crews

Page 17: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Leak Detection

• EPRI SF6 Leak inspection results using a GasVue laser camera

Page 18: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Figure 42Breaker #1292 Merlin Gerin 345kV –no leaks.

Page 19: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Figure 43Breaker #1982 HVB 230kV is leaking sf6 from the fill valve on pole 3.

Page 20: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Leak Repair

• Electricians used multiple common plumbing techniques in repairing the leaks

Page 21: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

BMPs - Different methods used by different

crews (For example, use of good fittings and proper maintenance of those fittings).

DILO fitting doesn’t leak

Note cap to

protect fitting

Page 22: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Tracking SF6 Emissions

1. Each Electrician crew reports their SF6 use for the CY.

2. Each crew has a scale for weighing bottles.

3. Warehouse crews supply SF6 bottles and crews sometimes buy there own, but the crews actually measure the amount added to breakers (essentially the amount leaked).

Page 23: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Scales used for weighing bottles.

SF6 Gas Cart - Used for recovery, service,

and maintenance of SF6 Breakers

Page 24: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are
Page 25: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are
Page 26: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are
Page 27: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Western’s CY2009 Leakage Rate was 1.1 %(1,845 lbs emissions / 173,362 lbs nameplate capacity)

Page 28: Western Area Power Administration · •The 306 substations contain 2,367 individual SF6 breakers ranging from 14.4 to 525 kV (most are in the 115 and 230 kV voltages) •There are

Leakage Rate History

CY2000 = scanned 200 known leakers and made repairs

CY2001 = scanned 100 known leakers and made repairs

CY2002 = scanned 7 known leakers and made repairs

CY2003 = continued leak detection/repair and refined tracking program

CY2004 = 3.2 %

CY2005 = 2.8 %

CY2006 = 2.0 %

CY2007 = 1.2 %

CY2008 = 1.2 %

CY2009 = 1.1 %