€¦ · web viewgalvanized steel sheet metal extra strength vitrified clay galvanized malleable...
TRANSCRIPT
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
Quiz 11. UPC Chapter 11 Storm Drainage governs
the materials, design and _______ of stormwater drainage systems.
inspection manufacturing installation overview utilization
2. A _____ is an exterior vertical drainage pipe for conveying stormwater from the roof or gutter drains.
soil stack catch basin sanitary drain leader storm drain
3. _______ system is designed to collect rainwater runoff, domestic sewage and industrial wastewater.
A combined sewer A free-for-all An unrestricted water A stormwater drainage An archaic piping
4. It is permissible for the rainwater drainage from a rooftop to drain into a location other than a separate or combined storm sewer system.
No, this is not permitted. Yes, this is permitted only if
neither type of storm sewer system is available.
1
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
No, this is not permitted unless the drainage system was installed prior to 1990.
Yes, it is possible to drain to some other place of disposal satisfactory to the AHJ.
Yes, this is permitted only for upgrades to existing drainage systems.
5. In the case of a single-family dwelling, it is permissible to drain stormwater onto a lawn.
Yes, provided the water flows away from the building and does not create a nuisance.
No, this is not permitted. Yes, this is recommended,
provided that both properties have the same owner.
No, this is not permitted without pre-approval from the AHJ.
Yes, this is permitted if there is nowhere on the property for the water to drain.
6. It is permissible for stormwater to be drained into sanitary sewers.
No, this is not permitted. Yes, it is permitted only if there
is no other suitable drainage location for the stormwater.
No, this is not permitted unless a licensed professional engineer has deemed it necessary.
Yes, it is permitted if the sanitary sewer is designed for double the capacity.
Yes, it is permitted, but only if the stormwater drainage system has reached capacity.
7. The material and design of pipes selected for conveying rainwater must _______ to the satisfaction of the AHJ.
be cost effective have extremely high durability
ratings
blend into their surroundings be versatile perform their intended function
8. Stormwater conductors _______ shall be made of cast iron, copper, lead, wrought iron, Schedule 40 ABS DWV or other approved materials.
installed above ground within a shaft below ground entering a detention pond adjacent to a vent
9. Stormwater drainage pipe changes of direction must be _______.
no closer than 12 inches from another change of direction
in accordance with Chapter 14 Firestop Protection
installed in such a way as to slow the flow rate of the water
in accordance with the requirements of UPC Section 706.0
avoided unless absolutely necessary
10. Materials exposed within ducts or plenums in other than single-family dwelling units must have a flame-spread index _______.
of 25 or less that is lower than their smoke-
developed index of not more than 50 that is suitable for
environmental air spaces of at least 25
11. _______ copper and copper alloy pipe and tube shall be installed in accordance with Section 705.3.
Changes of direction in Caps and fittings for Changes in elevation of Joints and connections in Underground systems of
2
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
12. Storm drainage conductors installed aboveground in buildings shall be in accordance with the standards referenced in Table 701.2 for _______.
building sewer applications aboveground drain, waste and
vent pipe copper and copper alloys (Type
DVW) underground installations PVC Schedule 40
13. Co-extruded PVC storm drainage pipes installed along the ceiling in a building must be in accordance with _______.
ASME B16.23 ASTM D2665 ASTM F628 CISPI 301 ASTM F891
14. Stormwater drainage conductors installed aboveground shall be of Type DWV copper drainage tube.
Yes, this is correct. No, this is not permissible. Yes, Type DWV copper is
permissible, but there are also other permissible conductors.
Yes, provided the copper tube is compliant with ASTM B43.
No, Type DWV copper drainage tube is preferred for underground installations.
15. Leaders installed outside may be fabricated from _______.
machined cast iron galvanized steel sheet metal extra strength vitrified clay galvanized malleable iron copper or copper alloy tubing
16. Underground building storm drains shall comply with _______ for underground drain, waste and vent pipe.
the applicable standards in Table 701.2
the manufacturer’s installation recommendations
the design engineer’s requirements
all requirements the building owner’s
preferences
17. It is permissible for a building storm sewer to convey liquid wastes other than rainwater.
No, this is not permitted. Yes, this is allowable, provided
the other wastes are not sewage.
No, this is not permitted without pre-approval from the AHJ.
Yes, this is acceptable. Yes, this is permitted, provided
the other wastes are not toxic.
18. Subsurface water may be collected and conveyed to a disposal location by a _______.
seepage collection vessel rainwater leader subsoil drain stormwater sponge subsurface drain
19. A vitrified clay subsoil drain must be _______.
open jointed installed in accordance with
ASTM D2729 buried beneath no less than 14
inches of earth perforated open jointed, perforated or
both
20. Stormwater drainage expansion joints or sleeves must be provided where _______.
conductors are installed under roadways
3
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
subsoil drains cross the frost layer
sewers are made of rigid pipe and fittings
necessary due to temperature variations or physical conditions
conductors cross from inside of buildings to outside
Quiz 21. Subsoil drains must be installed around
the perimeter of buildings having basements, cellars, crawl spaces or floors _______.
below grade that are likely to flood under construction in wet
locations located within 50 feet of a body
of water where the soil is not sufficiently
porous to drain well on its own
2. Perforated subsoil drain piping laid in crushed rock must have no less than _______ of the crushed rock surrounding the pipe.
2 inches 4 inches 12 inches 6 inches 14 inches
3. Subsoil drainage shall be piped to _________.
a storm drain an approved water course a street curb an alley any of the above
4. It is permissible to use a concrete gutter to route the discharge from a subsoil drain to an alley.
No, it is not acceptable to discharge stormwater into an alley.
Yes, this is permitted, provided the concrete gutter is no less than 4 inches in diameter.
Yes, this is permitted, provided the discharge runs to open-jointed rain tiles in the alley.
Yes, this is acceptable. Yes, this is allowed for alleys
with existing storm drains.
5. What is required if one encounters continuously flowing groundwater during the installation of subsoil drain pipe?
Continue with the installation, adding extra perforations to the pipe in this area.
Direct the subsoil drain pipe to a storm drain or approved water course.
Terminate the piping at this location.
Run a concrete gutter through this location, then proceed with the installation.
Increase the 4 inches of porous rock surrounding the pipe to 12 inches or more.
6. Where it is not possible to convey the discharge by gravity, subsoil drains must discharge to _______ provided with an approved automatic electric pump.
an approved underground water course
a below-grade sanitary sewer system
a tank or pit a French drain an accessible sump
7. The minimum required dimensions of a subsoil drain sump are _______.
10 inches diameter and 18 inches deep
4
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
12 inches diameter and 20 inches deep
15 inches diameter and 22 inches deep
15 inches diameter and 18 inches deep
18 inches diameter and 15 inches deep
8. The discharge piping from a sump pump must be _______.
at least 1-1/2 inches in diameter
no more than 18 inches below grade
at least 2 inches in diameter readily accessible extended to an above-grade
level
9. The concrete splash block for the drainage from a sump discharge pipe must be at least _______ inches in length.
8 16 24 32 36
10. It is mandatory to install _______ in a subsoil drain line that discharges into a storm drain if the drain line is subject to backflow.
a backwater valve a quick-disconnect device a shutoff valve an expansion joint a gate valve
11. Drains that serve subsoil drains or areaways of detached building may discharge to a properly graded open area unless _______.
the neighbor doesn’t approve it the plumber doesn’t approve it they’re serving a flowing spring the flow is blocked by large tree
or shrub none of the answers provided
12. A detached building areaway drain must discharge _______ or to a properly graded open area.
adjacent to a fence at least 10 feet from a property
line to a drainage easement through the perforations in the
pipe parallel to the nearest property
line
13. If it is impracticable for a subsoil drain to discharge to a storm drain, approved water course, front street curb or gutter, or to an alley, _______.
the property owner must request an exemption
the local soil must be amended to handle the discharge flow
it may discharge to a properly graded open area
it must discharge to a sump tank or pit
the property owner must obtain a drainage easement
14. Building subdrains below the public sewer level shall discharge _______.
onto a properly graded open area
into a subsurface water course up onto grade level into the nearest sanitary sewer into a sump or receiving tank
15. The subsurface space of a stairwell for a building’s basement entrance must have _______.
crushed rock around the drain area
a grade leading away from the stairs
a semi-porous surface material a drain or drains any of the answers provided
5
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
16. Cellar entrance areaways measuring less than 100 square feet must have a drain of at least _______.
2 inches radius 2% of the subsurface area 2 inches in diameter 2 inches by 2 inches 2 square inches
17. The drain for a subsurface areaway measuring 10 feet by 20 feet is permitted to drain into a subsoil drain.
No, this is not permitted. Yes, this is permitted because
the areaway does not exceed 200 square feet.
No, this is not allowed unless it is impracticable to drain to another approved location.
Yes, this is allowed provided the subsoil drain discharges to a graded open area.
No, this is only allowed for areaways with more than one drain.
18. A subsurface areaway basement entrance measuring 1500 square feet with 1/8-inch-per-foot slope in a location receiving up to 5 inches per hour of rainfall must have a drainpipe size of _______ diameter.
at least 3 inches at least 4 inches no more than 4 inches at least 5 inches no more than 5 inches
19. A subsurface areaway of 110 square feet with ¼-inch-per-foot slope in a location that receives rain at a rate of less than 1 inch per hour must have a drainpipe size of _______ diameter.
at least 2 inches 3 inches maximum 3 inches minimum no more than 2.5 inches at least 2.5 inches
20. A window areaway up to _______ shall be permitted to discharge into a 2-inch subsoil drain.
8 square feet in area 5 feet by 5 feet 2 feet by 2 feet 10 square feet in area 12 square feet in area
21. A subsurface window areaway of 22 square feet with 1/8-inch-per-foot slope in a location that receives rain at a rate of up to 2 inches per hour must have a drainpipe size of _______ diameter.
3 inches maximum at least 2 inches at least 4 inches 3 inches minimum no more than 2.5 inches
Quiz 31. The paved areas at a public filling
station _______. are required to drain to an
approved water course must be sloped toward sumps
or gratings within the property lines
larger than 400 square feet must have a drain installed
smaller than 1000 square feet may drain to an unpaved area filled with crushed rocks
do not require a drain provided they slope toward a curb or gutter storm drain
2. Where the drainage at a motor vehicle washing establishment needs to be directed to a sump, the UPC may require the establishment to _______.
reduce the amount of waste water they produce
first discharge the water to a properly graded open area
6
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
install curb and gutter drains install 6-inch or taller curbs to
direct the water replace some paved areas with
crushed rocks
3. If a newly constructed building and parking area create surface water drainage, the sumps and drains must be piped _______.
to a storm drain or approved water course
around the edges of the parking area
onto a properly graded open area
to a subsoil drain to the nearest sanitary sewer
4. Vertical rainwater piping must be_______.
round rectangular square any of the answers provided none of the answers provided
5. The location and sizing of roof drains and gutters _______.
must be coordinated with the aesthetic style of the roof
is determined by Table D 101.1 is dependent solely on the size
and pitch of the roof must be coordinated with the
pitch and design of the roof depends on the porosity of the
roof covering
6. Roof drains, gutters, vertical conductors and leaders, and horizontal storm drains for primary drainage must be sized based on a storm of 60 minutes duration and 100-year return period.
Yes, this is correct. Yes, this is how to find the
minimum size, but it’s always better to size larger.
Yes, unless the AHJ has other requirements.
Yes, unless the location in question is below sea level.
No, this is not correct.
7. Secondary roof drainage shall be provided by an open-sided roof or scupper(s) where the roof perimeter construction _______.
allows the water to drain off freely to prevent ponding
extends above the roof in such a manner that water will be entrapped
is completely surrounded by gutters so that no water can overflow the roof edges
extends beyond the roof such that water will drain down without touching the building
is sloped toward the scupper
8. If we determine from Table 1101.12 that our rooftop requires a 3-inch-diameter vertical rainwater pipe, which size rectangular drainage pipe we may use?
2 inches x 5 inches 3 inches x 3.5 inches 1.5 inches x 4 inches 2.5 inches x 3 inches 2.5 inches x 5 inches
9. If we determine from Table 1101.12 that our rooftop requires a 4-inch-diameter vertical rainwater pipe, what is the minimum size square drainage pipe we are permitted to use?
2 inches x 2 inches 3 inches x 3 inches 3-1/2 inches x 3-1/2 inches 4 inches x 4 inches 5 inches x 5 inches
10. What is the minimum height of a scupper opening?
2 inches
7
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
3 inches 1.5 inches 4 inches 5 inches
11. What size scupper opening is required for a 1000-square-foot roof in an area that receives rain at a rate of 3 inches per hour?
4 inches wide by 3 inches tall 2 inches wide by 3.5 inches tall 5 inches wide by 4 inches tall 3 inches wide by 4 inches tall 5 inches wide by 3 inches tall
12. What is the minimum width scupper opening required for an 8700-square-foot roof in a location that receives rain at a rate of 1 inch per hour?
2 inches 3 inches 4 inches 5 inches 6 inches
13. Secondary roof drains are required. Yes, this is correct. Yes, but only in locations that
receive rainfall at a rate of at least 2 inches per hour.
Yes, but only in locations where the rooftop water might pond deeper than 2 inches.
Yes, provided they have a diameter of at least 2 inches.
No, secondary roof drains are not always required.
14. The overflow level of the secondary drain inlet above the primary drain inlet shall not be less than _________ inch(es) above the roof.
1 2 3 4
15. The maximum height of a secondary roof drain is determined by _______.
the AHJ the rainfall rate of the location the number of primary drains
on the rooftop the area and pitch of the
rooftop the maximum possible depth of
ponding water and the roof design
16. A secondary roof drainage system may discharge into the same location as the primary system.
No, this is not permitted. Yes, provided the two drainage
systems are mostly independent.
Yes, provided the discharge is above grade and observable.
Yes, provided the primary system isn’t likely to be exceeded.
Yes, provided the primary system is sized for double the local rainfall rate.
17. Secondary roof drains may connect to the vertical piping of the primary storm drainage conductor _______.
downstream of the last horizontal offset located below the roof
provided the AHJ has approved it
only if it is impracticable to have two completely independent systems
if they are intended to discharge to the same location
provided the discharge is above grade and observable
18. A building’s primary storm drainage system must connect to the building storm sewer that connects to _______.
a public sanitary sewer
8
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
an approved waterway an underground public storm
sewer the primary roof drainage
system a public sewer system
19. The sizing of the combined primary and secondary roof drain systems is based on _______.
the size of the underground public sewer into which it discharges
the pitch of the rooftop the 1000-year storm rainfall
rate 1.5 times the rainfall rate for
the local area double the rainfall rate for the
location
20. A rain leader connected to a building storm sewer shall have a cleanout installed at the base of the outside leader _______.
no closer than 6 feet from the discharge into the underground public sewer
with an opening at least double the diameter of the leader
but at least 6 inches above grade level
before it connects to the horizontal drain
immediately after it connects to the horizontal drain
21. Rainwater sumps serving _______ shall be provided with dual pumps arranged to function alternately in case of overload or mechanical failure.
drainage from large, flat rooftops
public use occupancy buildings industrial manufacturing
facilities any building with a roof subject
to ponding
hospitals, nursing homes and similar facilities
Quiz 41. Leaders and storm drains must be
trapped. Yes, this is always required. No, this is not a requirement. Yes, this is required at the
location where they connect to a combined sewer.
No, this is not required unless the location is one that has a lot of debris.
Yes, this is required within 2 feet of a junction or connection.
2. Traps shall not be required where roof drains, rain leaders, and other inlets are at locations allowed under _______.
Section 719.0, Cleanouts Section 908.0, Wet Venting Section 1101.7, Building
Subdrains Section 720.0, Sewer and Water
Pipes Section 906.0, Vent
Termination
3. Traps are not required for leaders or conductors that are connected to a sewer _______.
with a sufficiently large diameter to handle the debris
that connects to a combined sewer
that discharges to a building sub-drain
carrying stormwater exclusively within 10 feet of the property
line
4. Traps for individual conductors must be _______ the horizontal drain to which they are connected.
the same size as or larger than the same size as smaller than the same size as or smaller than
9
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
larger than
5. In lieu of individual traps for the drain branch serving each stormwater inlet, it is permissible to install a single trap in the main storm drain just before its connection with the _______.
combined building sewer next horizontal branch underground public sewer building sump pit public sewer main
6. Stormwater traps must be provided with _______ located on the outlet side of the trap.
an expansion joint a quick-disconnect device an accessible cleanout a water shutoff valve a pressure-balancing valve
7. It is permissible to use a waste pipe as a rain leader in a building with a combined building sewer.
True False
8. Leaders installed in locations where they are exposed to potential damage must be protected by metal guards.
Yes, this is correct. Yes, provided the guard is made
from ferrous pipe. No, this is only required in
certain specific locations. No, this is not required for
leaders constructed from ferrous pipe.
Yes, and the guard must completely cover the leader.
9. The sanitary and storm drainage systems of a building shall be entirely separate.
Yes, except where a combined sewer is used.
Yes, this is correct.
Yes, this is correct, unless it is impracticable to do so.
No, this is not required. No, not unless the local
jurisdiction requires it.
10. In the case of a combined building sewer, the storm drain must be connected to the combined system through a single wye fitting _______ a soil stack.
immediately upstream from at least 10 feet downstream
from no more than 10 feet
downstream from at least 10 feet upstream from adjacent to
11. A building storm drain tying into a combined building sewer must be connected _______.
in the same horizontal plane as the sewer
with a tee fitting immediately downstream from
a trap cleanout through a series of elbows in the same vertical plane as
the soil stack
12. Roof drains may be constructed of any material as long as they comply with ASME A112.3.1 or ASME A112.6.4.
True False
13. Roof drains shall have _______. a diameter of no less than 3
inches domed strainers perforated side walls accessible cleanouts their installed height flush with
the rooftop
14. Roof drains on parking decks are permitted to be _______.
10
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
domed no higher than 1 inch above the parking surface
connected directly to the public sanitary sewer
sized by the building owner’s requirements
of the flat surface type constructed only of ferrous
metal15. Flat-surface-type roof drain strainers
may be installed on _______. any roof roofs above food storage commercial building roofs sun deck roofs any flat roof
16. The interface of _______ with the roof must be made watertight with the use of flashing material.
all roof drains metal roof drains roof drains that pass through
the roof to the building interior roof drains that pass through
the roof to the building exterior high-volume roof drains
17. Roof drain lead flashing must be _______ 4 pounds per square foot.
no less than approximately equal to less than no more than
18. Where copper flashing is used for a roof drain, it must be at least _______.
4 ounces per square foot 6 ounces per square foot 8 ounces per square foot 10 ounces per square foot 12 ounces per square foot
Quiz 51. The sizing of vertical rainwater piping is
based on _______ and Table 1101.12. the minimum projected roof
area
the size of the drain serving the pipe
the maximum projected roof area
the pitch and design of the roof whether or not it is part of a
combined sewer system
2. What is the maximum roof area that can be served by a 3-inch vertical rainwater pipe in a location that receives rain at a rate of up to 3 inches per hour?
960 square feet 2930 square feet 9200 square feet 6130 square feet 2200 square feet
3. What is the minimum size vertical rain pipe permitted for a rooftop of 3000 square feet in an area that receives rain at a rate of 1 inch per hour?
1 inch diameter 2 inches diameter 3 inches diameter 4 inches diameter 5 inches diameter
4. The sizing of a horizontal branch of a building storm drain is based upon _______ and Table 1101.8.
the area of the rooftop plus the area of the parking lot
the size of the vertical pipes serving the branch
the slope of the rooftop the porosity of the rooftop or
parking lot materials the maximum projected roof or
paved area being served
5. What is the maximum size 1/4-inch-per-foot slope parking area that can be served by a 6-inch diameter horizontal storm sewer in a location that receives rain at a rate of 5 inches per hour?
6040 square feet
11
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
4280 square feet 7670 square feet 46,000 square feet 13,040 square feet
6. What is the minimum size horizontal rain pipe permitted for a 3200-square-foot rooftop built with 1/8-inch-per-foot slope in a location that receives rain at a rate of 1 inch per hour?
6 inches diameter 5 inches diameter 4 inches diameter 3 inches diameter 2 inches diameter
7. Semi-circular rain gutters are sized by _______ and Table 1103.3.
minimum projected roof area local area requirements rooftop surface material the diameter of the vertical
pipes they serve maximum projected roof area
8. A 1/8-inch-per-foot-slope rooftop measuring 588 square feet in a location that receives rain at a rate of 6 inches per hour requires a _______ diameter semi-circular rain gutter.
2-inch 4-inch 6-inch 5-inch 3-inch
9. What is the maximum 1/16-inch-per-foot-slope roof area that can be served by a 3-inch diameter semi-circular rain gutter in a location that receives rainfall at a rate of 3 inches per hour?
320 square feet 454 square feet 226 square feet 170 square feet 480 square feet
10. What is the effective drainage area of a 100 foot by 200 foot rooftop with a 2-foot-tall wall down the long edge of the roof?
20,000 square feet 20,200 square feet 22,000 square feet 20,400 square feet 10,200 square feet
11. What is the minimum permissible size rain leader to serve a 13,000-square-foot rooftop with a pair of adjacent vertical walls with total area of 1440 square feet in a location that receives as much as 4 inches of rain per hour?
8 inches diameter 6 inches diameter 5 inches diameter 4 inches diameter 3 inches diameter
12. To determine the effective drainage area of a rooftop with two adjacent walls _______, add 35% of the total common height area and 50% of the remaining height area of the highest wall to the roof area.
with rain gutters installed on them
constructed with non-porous surfaces
of unequal height taller than 1 foot and one opposite wall
13. What is the effective drainage area of a 10-foot by 10-foot roof with two adjacent walls measuring 1 foot high and 2 feet high?
100 square feet + 35% of 10 square feet + 50% of 10 square feet
10 square feet + 50% of 10 square feet
110 square feet – 35% of 20 square feet
12
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
1000 square feet + 35% of 10 square feet + 50% of 20 square feet
100 square feet + 10 square feet + 20 square feet
14. In the case where a pair of opposite vertical walls project above a roof, it is not necessary to add additional drainage area to the rooftop area in order to size the rain leader.
Yes, this is correct. Yes, provided the walls are of
equal height. Yes, this is correct for locations
with a rainfall rate not exceeding 2 inches per hour.
Yes, provided the walls are no higher than 2 feet.
Yes, unless the AHJ has other requirements.
15. To determine the size of a vertical rain pipe serving a 10,000-square-foot rooftop with two opposite 100-foot-long walls measuring 8 feet tall and 3 feet tall, we calculate the effective drainage area as _______ plus 10,000 square feet.
50% of 500 square feet 35% of 800 square feet 500 square feet 50% of 300 square feet plus
35% of 500 square feet 1100 square feet
16. To calculate the effective drainage area of a rooftop with walls on 3 sides, it is necessary to take into consideration the fact that there are both opposite and adjacent walls.
True False
17. In the case of a square rooftop measuring 100 feet by 100 feet with walls on three sides measuring 3 feet high and a wall on the fourth side
measuring 5 feet high, how can we calculate the drainage area of the walls?
50% of (300 feet x 2 feet) 50% of (200 feet x 3 feet) 50% of (100 feet x 2 feet) 35% of (100 feet x 3 feet) 35% of (400 feet x 3 feet)
18. If a pump produces a semi-continuous discharge that feeds into the building storm sewer, how much of its discharge is equivalent to 24 square feet of rooftop based upon a 4-inches-per-hour rainfall rate?
1 cubic inch 1 gallon per minute 1 hour 1 quart 1 gallon per hour
19. If a pump produces a semi-continuous discharge that feeds into the building storm sewer at a rate of 2 gallons per minute, what is its equivalent roof area based upon a 4-inches-per-hour rainfall rate?
48 inches 24 square feet 36 square feet 48 square feet 8 gallons per hour
Quiz 61. Existing storm drainage systems that An
engineered storm drainage system must be designed ______.
by the manufacturers of the materials to be used
with the assumption that setback roofs are to be included
to be as easy as possible to test by a registered design
professional by the AHJ
2. Siphonic roof drainage systems are _______.
13
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
exactly the same as conventional roof drainage systems
not approved by the 2018 Uniform Plumbing Code
required to comply with ASPE 144.6.6.2.5.1
not required to be tested none of the answers provided
3. Existing storm drainage systems that have been extended are required to be tested for leaks and defects.
Yes, this is correct. No, this is only required for new
storm drainage systems. No, this is not required if the
existing system does not have any known leaks.
Yes, this is required, but only for existing systems that have needed repair.
No, this is not required unless specifically requested by the AHJ.
4. Storm drainage piping that is to be checked for leaks by the water test may be tested in sections or as a whole system.
True False
5. A storm drainage system subjected to an air test must maintain pressure without the introduction of additional air _______.
until a column of mercury reaches 10 inches in height
for at least 30 minutes unless the pressure falls within
the first minute for no more than 15 minutes for at least 15 minutes
6. A storm drainage system subjected to an air test must maintain pressure without the introduction of additional air _______.
until a column of mercury reaches 10 inches in height
for at least 30 minutes unless the pressure falls within
the first minute for no more than 15 minutes for at least 15 minutes
7. Schedule 40 Plastic DWV storm drain systems shall not be tested by _______.
water air 10-foot-head foot of water plumbers none of the answers provided
8. If circumstances exist that make the required storm drainage system air and water tests impractical, it is possible for the AHJ to determine an alternate means of inspection.
No, all systems must pass the required air and water tests.
Yes, provided the AHJ’s alternative ensures that the work adheres to the UPC.
No, only the AHJ’s representative can authorize this.
Yes, the AHJ can completely waive all inspections if the system is really large.
No, not unless the system is built entirely above ground for easy visual inspection.
14
Rev 1.3.21 UPC Chapter 11 Storm Drainage Quiz Student Copy
15