1700IB0301R11/12 © 2003–2012 Schneider Electric. All rights reserved. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. Schneider Electric 1010 Airpark Center Drive Nashville, TN 37217 1-888-778-2733 1700IB0301R11/12 Dec 2012 Device Web Pages EGX300 Quick Start Guide

Upload: amadeoam

Post on 23-Oct-2015

39 views

Category:

Documents


2 download

DESCRIPTION

WEB EGX

TRANSCRIPT

Page 1: Web Egx300

1700IB0301R

11/12 © 2003–2012 Schneider Electric. A

ll rights reserved.

Electrical equipment should be installed, operated, serviced, andmaintained only by qualified personnel. No responsibility isassumed by Schneider Electric for any consequences arising outof the use of this material.

Schneider Electric

1010 Airpark Center DriveNashville, TN 372171-888-778-2733

1700IB0301R11/12Dec 2012

Device Web PagesEGX300 Quick Start Guide

Page 2: Web Egx300

Before following these quick-start instructions, please ensure your equipment with EGX300 is already installed and connected to your local area network (LAN). Follow the steps below for final commissioning and to gain instant access to power system information.

Please take this quick-start guide to your Network Administrator to obtain the necessary network information, and enter it in the spaces below for future reference.

NOTE: Equipment with EGX300 is designed for standard 100BaseTX (100 Mbps) twisted-pair Ethernet LANs. To ensure compatibility with slower (10 Mbps) networks or fiber-optic LANs (Media Type “Other” above), please contact your local Schneider Electric sales office.

1. Connect a standard Ethernet cable from your PC to the equipment’s front-accessible Ethernet port.NOTE: Record the current IP address and subnet mask of your PC before proceeding.

2. On your PC, for the EGX300, set a static IP address of 169.254.0.11 and a subnet mask of 255.255.0.0.NOTE: If you are unsure how to do this, search Windows® Help for keywords “assign a static IP address“, “IPConfig“, and “WinIPcfg“, or contact your Network Administrator for assistance.

3. Reboot your PC, if necessary.4. Start your Internet browser.

NOTE: Microsoft® Internet ExplorerTM version 6.0 or higher is recommended.

5. In the URL Address field, type the equipment’s IP Address, and press Enter. The Login Page will display.NOTE: For the EGX300, the default IP address is 169.254.0.10.

6. Enter your Password, and click Log In. The Home page will appear.NOTE: For the EGX300, the default ID and password are Administrator and Gateway, respectively (both case sensitive).

7. To set the network communication parameters, click Setup for the EGX300. Set the COM1 or Serial Port parameters to Physical Interface to RS485 2-wire, Transmission Mode to Automatic, Baud Rate to 19200, and Parity to Even.

8. Enter the IP Address, Subnet Mask, and Default Gateway (router) information gathered in Step 1 into the appropriate fields (leave Media Type set to 10T/100TX Auto), and click Update or Apply.

9. Reset your PC back to its original network configuration.

1. Start your Internet browser.2. Type your equipment’s IP Address into the URL Address field, and press Enter.3. Type your Password into the Password field, and press Enter.

NOTE: For the EGX300, the default ID and password are Administrator and Gateway, respectively (both case sensitive).

4. Welcome to your new Web pages. You can now access real-time power system data at any time from any computer on your network!

Before You Begin

Step1IP Address:

. .

. .

. ...

.Default Gateway:

Subnet Mask:

Media/Port Type: 10/100 Auto (Auto-detects 10BaseT or 100BaseTX)100BaseTX (Half-duplex)100BaseTX (Full-duplex)Other

(Check one)

Network Address Setup

EGXStep2

EGX300

1EGX

Log In to Your Web Page

Step3

Device Web Pages Quick-Start Guide—EGX300 1700IB0301R11/1212/2012

© 2003–2012 Schneider Electric All Rights Reserved