A New Standard of Excellence

Page 2: WDG-V Thermox Combustion Analyzer

PREVENTION IS SO EASY...LIVING THROUGH A DISASTER IS NOT

The reliable identification of low combustion oxygen in a fired heater or boiler has always been critical to the effectiveness of the Burner Management System for proper control and safety.

Low emission burners and aggressive firing control points to achieve increased efficiency and emission reductions have driven the industry to tighter control measures. But tighter control measures also hold a greater potential for combustion damage. Reducing the risk of a combustion event has become a priority and has led to the implementation of Safety Instrumented Systems (SIS). This additional layer of safety is added to the Basic Process Control System.

The WDG-V has been designed to provide an additional layer of safety with the measurement of excess O2, Combustibles and Methane. These measurements are used to ensure the safe operation of the Burner Management System.

The WDG-V Combustion Analyzer is designed to provide the complete solution for combustion process control and process control safety applications. The WDG-V Combustion Analyzer has built-in redundancy and diagnostics to monitor performance and health as well as provide the statistical data needed to implement predictive and proactive maintenance programs. In control and safety applications, it is critical that the analyzer is always operational.

Precise control of low O2 setpoints with confidence

CO detection for control interlocks and safety shutdown

Predictive diagnostics

SIL 2 capable for SIS implementation of IEC 61508/61511 into

the burner management system

Page 3: WDG-V Thermox Combustion Analyzer

WDG-V COMBUSTION ANALYZER SENSORRANGES: O2 0-1% to 0-100% COMBUSTIBLES 0-1000ppm with overrange 0-2000ppm to 0-5% HYDROCARBONS 0-1% to 0-5%RESPONSE: O2 90% < 11sec with Flame ArrestorsANALOG OUTPUT: (3) 4-20 mAALARM OUTPUT: (5) Dry ContactPROCESS CONNECTION: 2”, 3” or 4” FlangeAMBIENT TEMPERATURE: -25°C to 65°CDIGITAL INTERFACE: MODBUS RTU, Configuration SoftwareENCLOSURE: Class I, Div II, Gp B, C, D / ATEX Zone 2, T3, IP65POWER REQUIREMENT: 115 VAC, ±10%, 47-63 Hz, 740 VA 230 VAC, ±10%, 47-63 HzDIMENSIONS (LxWxD): 44.45 x 31.75 x 19.8 cm (17.5” x 12.5” x 7.8”)WEIGHT: 20 kg (44 lbs.)

AMEVISION HMICOMMUNICATION: 2 Wire MODBUSDISPLAY: 4.2” Color 1/4W VGA with GUIKEYPAD: Alpha Numeric MembraneENCLOSURE: Div 2, Zone 2, IP65 (NEMA 4X)POWER REQUIREMENT: 115 VAC or 230 VACOUTPUTS: 2 or 4 Wire MODBUS RTU- Configurable, Ethernet-RJ45 connection with Web ServerDIMENSIONS (LxWxD): 22.9 x 22.9 x 13.3 cm (9” x 9” x 5.25”)

WDG-V COMBUSTION ANALYZER SYSTEM

REMOTE CALIBRATION UNIT (RCU)GAS CAPABLE: Aspirator Air (Span) Optional Span O2

Zero O2

Combustible Span Hydrocarbon SpanENCLOSURE: IP65, NEMA 4X Class I, Div 2; ATEX Zone 2POWER REQUIREMENT: None (Supplied from Analyzer)CONSTRUCTION: 316SS, Hard PipedDIMENSIONS (LxWxD): 26 x 31.2 x 13.3 cm (10.25” x 12.28” x 5.25”)

Page 4: WDG-V Thermox Combustion Analyzer

# COMPONENT SENSOR ENHANCEMENTS1 Enclosure The Sensor enclosure size and weight has been reduced by over 30% and features a

hinged door IP65 enclosure as standard. Lightweight, high “R” value blanket insulation inside the enclosure insures sensor temperature stability throughout wide ambient temperature cycles.

2 Sensor Heater Block High output single cartridge heater with improved thermal transfer radiant block maintains internal sensor and enclosure temperature to 235°C with only a 30% duty cycle leaving added capacity for extreme temperature environments.

3 Aspirator Block New Aspirator block design with increased orifice sizes reduce chances of particulate interference. Instrument Air or Nitrogen drive gas consumption is reduced by over 20% while directing more process convective flow to the sensors. Analyzer response time with sensor flame arresters is improved to levels of analyzers without flame arresters installed.

4 Combustible Sensor Combustible and Hydrocarbon detectors are installed in a thermally controlled flow block of substantial mass, independent of enclosure temperature, insuring precise temperature stability of detectors, reducing the effects of thermal drift.

5 Flame Arrestors Flame arrestors are incorporated into the convection flow loop so that they may be inspected or replaced in minutes. An upstream arrestor “cartridge” installed in the combustible flow sensor block can be inspected or replaced in minutes without disassembly of sensor piping.

6 Flow Sensor A flow sensor is incorporated into the sensor piping to detect and alarm when sensor flow is reduced or stopped to insure the sample transport integrity to the measurement sensors from inlet probe tip to exhaust port.

7 Zirconia Cell Furnace New cell furnace design reduces the size and susceptibility to vibration and environmental effects. Redundant thermocouples for cell temperature measurement improves reliability of the measurement. The re-orientation of the cell furnace parallel to the combustible sensor block efficiently utilizes cell furnace heat for maintaining combustible detector temperature stability.

8 Sensor Terminal Enclosure

Modular snap in terminal strips with laser etched labels simplify wire connections. Recessed electronics and bottom conduit connections eliminate problems due to conduit stress, moisture egress, and improve the reliability and integrity of the sensor connection in high radiant heat areas.

Page 5: WDG-V Thermox Combustion Analyzer

• Sample Flow Verification

• Calibration History

• Cell & Detector Trending

• ‘End of Life’ Prediction of Zirconium Oxide cell & combustible detector with Warning

• Stability Indicator during the Calibration Process

• Analog Output Verification

• Individual Controls of Analog Outputs, Relays

• Time Stamped Alarm/Event Log

• Trend Data Logging & Access by USB Port

• Redundant Cell, Enclosure & Electronics Temperature Monitoring

Enables the convenience of site calibration and communication

with the analyzer

• MODBUS RS485• TCP/IP Ethernet• USB Port• 4.2” color VGA display

AMEVISIONDisplay Unit Interface

DIAGNOSTICS & AMEVISION HMI

Page 6: WDG-V Thermox Combustion Analyzer

© 2013, by AMETEK, Inc. All rights reserved. Printed in the U.S.A. F-0409 Rev. 3 (1013)

150 Freeport Road, Pittsburgh, PA 15238Ph. +1-412-828-9040, Fax +1-412-826-0399www.ametekpi.com

CONFIGURATION 2: STAND ALONE SENSOR WITH AMEVISION HMI

CONFIGURATION 1: SENSOR - STAND ALONE, BPCS OR LOGIC SOLVER COMMUNICATION

CONFIGURATION 3: MULTI-SENSOR with AMEVISION HMI