water source hp loop_controls
TRANSCRIPT
Approved by:M.E. Warren
SHEET NAME:
TITLE PAGE & DRAWING INDEX
Drawn by: E.A. Datu
ISSUE DATES & REVISIONS:
DWG NO:
1.00
07/15/15 AS-BUILT
WATER SOURCE HEAT PUMP LOOP CONTROL
DWG# DESCRIPTION DATE REMARKS
1.00 TITLE PAGE & DRAWING INDEX 07/15/15
2.00 LEGEND, NOTES, SEQUENCE OF OPERATIONS 07/15/15
3.00 BLDG-A (SOUTH) VFD NETWORK 07/15/15
DRAWING INDEX
4.00 CONDENSER WATER SYSTEM LOOP - BLDG-A (SOUTH) 07/15/15
5.00 BLDG-A SOUTH TOWER DDC-32X-1 CONTROLLER WIRING DETAILS 07/15/15
AS-BUILT
Water Source Heat Pump
Main Loop
COOLING WATER LOOP CONTROL AND
AUTOMATION SYSTEM
Approved by:M.E. Warren
SHEET NAME:
LEGEND/NOTES/SEQUENCE
Drawn by: E.A. Datu
ISSUE DATES & REVISIONS:
DWG NO:
2.00
07/15/15 AS-BUILT
SEQUENCE OF OPERATIONS
BULB TYPE TEMPERATURESENSING ELEMENT
AVERAGING TYPETEMPERATURE SENSING
VAPOR TENSIONTEMPERATURE SENSING
BULB TYPE TEMPERATURE
UNDER SHIELD IN
INSIDE SEPARABLE
AIR PRESSURE GAGE
DRAWING REVISION SYMBOLWITH APPROPRIATE NUMBERUSE NUMBERS 1,2,3-ETC.
CONTINUATION SYMBOLFROM ONE SHEET TOANOTHER USE LETTERS
BULB TYPE TEMPERATURESENSING ELEMENT LOCATED
SENSING ELEMENT LOCATED
BUILDING'SSTRUCTURE HAS TO BE ROMOVED TO GAIN ACCESS TO THE JUNCTION BOX.
INSTRUMENT IDENTIFICATIONNUMBER IN-LINE RESTRICTOR .005" A,B,C,-ETC.
A
DEVICE LEGEND
DRAWING)
PNEUMATIC TUBE TERMINALWITH APPROPRIATE NUMBER
ELECTRICAL WIRETERMINAL WITH APPROPRIATE NUMBER
SPECIAL TERMINALS WITHAPPROPRIATE NUMBER(MUST BE IDENTIFIED ON
ITEM LOCATED INCONTROL PANEL
ITEM LOCATED INMOTOR STARTER
ITEM LOCATED AT AC UNIT
ITEM LOCATED ONPANEL FACE
OPTIONAL LOCATION
IN-LINE RESTRICTOR .007"
1280
TUBE AT 80 PSIG
ELECTRICAL WIRE
CONNECTED LINES OR
CROSSING LINES OR WIRES,NOT CONNECTED
ELECTRIC WIRE IN CONDUIT(STROKES INDICATE NO. OF WIRES)
WIRES
AIR LINE OR
MAIN AIR SUPPLY TUBE
DUAL AI R SUPPLY TUBEAT 15/20 PSIG
HIGH PRESSURE AIR SUPPLY
AT 20 PSIGS20
S15-20
S
7
17
ELEMENT
SOCKET/WELL
I
OUTSIDE AIR
ELEMENT
GENERAL DDC SYSTEM CONTROLS NOTES
DAMPER ANALOG
OUTPUT
STAGED
BINARY OUTPUTS
FAN VOLUME CONTROL
ANALOG OUTPUT
HIGH HUMIDITY
CONTROLLER
PRESSURE INPUTS
OUTDOOR PRESSURE
REFERENCE TIP
SUPPLY AIR STATIC
PRESSURE TIP
ROOM PRESSURE
REFERENCE TIP
AIR FLOW
MEASURING STATION
SUPPLY AIR LOW
STATIC PRESSURE TIP
TS-1M.A.L.L. PS-1
S.P.-H.L.
OUTPUT DEVICES
MOTOR STARTER
BINARY OUTPUT
CONTROL VALVE ANALOG
OUTPUT
HUMIDIFIER CONTROL
VALVE ANALOG OUTPUT
S.F.-C
V-2CHWVLV
NC
H-1HFRVLV
NC
HUMIDITY INPUTS
HE-2R.A.H.
HE-1RM-H
DUCT HUMIDITY
TRANSDUCER
ROOM HUMIDITY
TRANSDUCER
DA-4S.F.-INV
DA-1,3 D-1,3M.A.-DPR
DXC
HC-1H.D.-H.
INPUT DEVICES
ROOM TEMPERATURE
SENSOR
TEMPERATURE SENSOR
WITH SUNSHIELD
B BULB TEMPERATURE
SENSOR
LOW TEMPERATURE
SWITCH
TEMPERATURE SENSOR
WITH WELL
AVERAGING TEMPERATURE
SENSOR
TE-1O.A.T.
TE-4M.A.T.
TE-2HWS-T
TE-2R.A.T.
TEMPERATURE INPUTS
TE-1RM.-T
PT-1O.A.-A.P.
PT-2RM.-S.P.
PS-2S.P.-L.L.
F-2R-F
S.A.-S.P.
SUPPLY AIR HIGH
STATIC PRESSURE TIP
9. THE INSTALLATION OF ANY FIRE ALARM DEVICES AND RELATED EQUIPMENT SHALL BE IN
ACCORDANCEWITH NFPA 72,NFPA 90A, NFPA 101, SBCCI, AND ANY APPLICABLE ANSI STANDARDS.
3. WIRE TYPE FOR ANY 24VDC/AC CIRCUIT SHALL BE 2C/#16/TW/STRANDED/PLENUM.
2. WIRE TYPE FOR ANY 120VAC CIRCUITS SHALL BE #12/THHN.
1. WIRE TYPE FOR THE RS-485 TRANSMISSION. TRUNK SHALL BE 2C/#18/TW/SHD/STRANDED/PLENUM.
7. ALL JUNCTION BOXES SHALL BE MOUNTED IN SUCH A WAY THAT NO PERMANENT PART OF THE
5. ALL WIRE SPLICES NOT CONNECTED TO A DEVICE SHALL BE HOUSED WITHIN A
4. WIRE TYPE FOR CONNECTION TO 10K OHM THERMISTOR TEMPERATURE SENSORS SHALL
8. THE ELECTRICAL INSTALLATION OF EQUIPMENT, CONDUCTORS, AND ALL OTHER RELATED ITEMS
SHALL BE IN ACCORDANCE WITH NFPA 70.
BE 2C/#18/TW/STRANDED/PLENUM.
4"X4"X2-1/8" JUNCTION BOX.
6. ALL JUNCTION BOX COVERS SHALL BE LABELED WITH "DDC CONTROLS SYSTEM".
AS-BUILT
Water Source Heat Pump
Main Loop
COOLING WATER LOOP CONTROL AND
AUTOMATION SYSTEM
Approved by:M.E. Warren
SHEET NAME:
BLDG-X (SOUTH)VFD NETWORK
Drawn by: E.A. Datu
ISSUE DATES & REVISIONS:
DWG NO:
3.00
07/15/15 AS-BUILT
(NEW NEMA-4 ENCLOSURE)
HOT WATER BOILER
120VAC
TO PACIFIC BEACON LAN/WAN
(COORDINATED)
RS485 (PORT-2)
ROOF
LAN/WAN
(BY OTHERS)
SW-1
CAT5e
EXISTING SIEMENS CONTROL
PANEL
VFD CTP-3
VFD CTP-4
VFD CTF-1
VFD CTF-2
VFD CW-5
VFD CWP-6
TOWER FAN-1
TOWER FAN-2
RECIRC. PUMP-P3
RECIRC. PUMP-P4
SEC. PUMP-P5
SEC. PUMP-P6
E-FLEX
E-FLEX
E-FLEX
E-FLEX
S-FLEX
S-FLEX
BACnet
BACnet
BACnet
BA
Cne
t
BACnet
BA
Cne
t
BACnet
BACnet
BACnet
BACnet
BACnet
BA
Cne
t
B-1
32X - 1
BUILDING – X (SOUTH) VFD NETWORK
BUILDING – A (SOUTH)
TCP/IP
BUILDING-A (SOUTH)
NEW COMPUTROLSDDC CONTROLLER
(MOUNT INSIDE DDC-32X NEMA-4
ENCLOSURE)
AEGIS
(EXISTING)
CAT5e CAT5e CAT5e(BY OTHERS) (BY OTHERS)(BY OTHERS)
COOLING TOWER
CHEMICAL
TREATMENT
CONTROLLER
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE)
(FUTURE) AS-BUILT
OPEN LOOP COOLING TOWER SIDE WSHP & BOILER CLOSED LOOP SIDE
Water Source Heat Pump
Main Loop
COOLING WATER LOOP CONTROL AND
AUTOMATION SYSTEM
Approved by:M.E. Warren
SHEET NAME:
BLDG-X (SOUTH)CONDENSER WATER
SYSTEM LOOP
Drawn by: E.A. Datu
ISSUE DATES & REVISIONS:
DWG NO:
4.00
07/15/15 AS-BUILT
BUILDING - X CONDENSER WATER SYSTEM LOOP (SOUTH TOWER)
Water Source Heat Pump
Main Loop
BLDG-A (North)
SITE LINKS
BUILDING-B
BUILDING-C
PALMER HALL
COOLING WATER LOOP CONTROL AND
AUTOMATION SYSTEM
CTP-1
CTP-2
CWP-5
CWP-6
HX-1
B-1
VFD CTP-3
VFD CTP-4
psi
Hz SPEED
STATUS
START/STOP
Hz SPEED
STATUS
START/STOP
VFD CTF-1
VFD CTF-2
Hz SPEED
STATUS
START/STOP
Hz SPEED
STATUS
START/STOP
VFD CWP-5
VFD CWP-6
Hz SPEED
STATUS
START/STOP
Hz SPEED
STATUS
START/STOP
STATUS
START/STOP
TS-2
TS-3
TS-4DPT-1
TS-1
TS-HWS
OSA-1
oF
CTF-1 CTF-2
Delta-T
Delta-T
AS-BUILT
Approved by:M.E. Warren
SHEET NAME:
BLDG-X South DDC-32X-1 CONTROLLER
WIRING DETAILS
Drawn by: E.A. Datu
ISSUE DATES & REVISIONS:
DWG NO:
5.00
AS-BUILT07/15/15
DDC-32X LOOP CONTROLLER WIRING DETAIL (BLDG-A South)
+
+
+
(24VAC) COM
(24VAC) HOT
TO ETHERNET SWITCH
SW-1
9
TR1
BLK
WHT120VAC
BR
-1
5 13C
RJ-45
DPT-1
VFD CT-1 SPEED
VFD CT-1 START/STOP, R-1 (14)
VFD CT-1 START/STOP, R-1 (13)
CT-1 FAN, CS-1 STATUS
CT-1 FAN, CS-1 STATUS
VFD CT-2 START/STOP, R-2 (13)
VFD CT-2 SPEED
VFD CT-2 SPEED
CT-2 FAN, CS-2 STATUS
CT-2 FAN, CS-2 STATUS
BOILER B-1 START/STOP
BOILER B-1 ALARM
BOILER B-1 ALARM
SUPPLY TEMPSH LD
TAPE S HLD
PRIMARY LOOP
TS-1
RETURN TEMPSH LD
TAPE S HLD
PRIMARY LOOP
TS-2
SUPPLY TEMPSH LD
TAPE S HLD
SEC. LOOP
TS-3
14
BOILER, B-1CONTROL PANEL
BOILER
ALARM
BOILER
ENABLE/DISABLE
RH2B-ULDC24V
TB4-8 COM
TB5-7 SIG
TB4-7 COM
TS-1
TS-2
TB5-15 SIG(-)
(+)
4~20mA (TBD)
(24VDC) TB9(+)
CW D/P SENSOR
OSA-1
VFD-P1 SPEED
VFD-P2 START/STOP, R-P2 (13)VFD-P1, CS-3 STATUS
VFD-P2 SPEED
VFD-P2, CS-4 STATUS
START/STOPSPEED
(0~10VDC)(+)
(-)
Tower FanVFD CTF-2
R-2
ENABLE/
DISABLE
VFD
MOTOR
~ ~ ~
Tower FanCS-2 Status
CS-2
~ ~ ~
TB5-6 SIGCT
START/STOPSPEED
(0~10VDC)(+)
(-)
Tower FanVFD CTF-1
R-1
ENABLE/
DISABLE
VFD
MOTOR
~ ~ ~
Tower FanCS-1 Status
CS-1
~ ~ ~
TB5-3 SIGCT
RETURN TEMPSH LD
TAPE S HLD
SEC. LOOP
TS-4
SUPPLY TEMP
100-Ω Pt RTDSH LD
TAPE S HLD
B-1 HOT WATER
531-431A TS-HWS
TS-3
TS-4
TS-HWS
(24VDC) TB9(+)
OUTSIDE AIR SENSOR
DPT-1
OSA-1
START/STOPSPEED
(0~10VDC)(+)
(-)
R-P2
ENABLE/
DISABLE
VFD
MOTOR
~ ~ ~
Circ. PumpCS-4 Status
CS-4
~ ~ ~
TB5-21 SIGCT
START/STOPSPEED
(0~10VDC)(+)
(-)
R-P1
ENABLE/
DISABLE
VFD
MOTOR
~ ~ ~
Circ. PumpCS-3 Status
CS-3
~ ~ ~
TB5-18 SIGCT
Circ. PumpVFD CTP-3
Circ. PumpVFD CTP-4
VFD-P1 START/STOP, R-P1 (13)
START/STOPSPEED
(0~10VDC)(+)
(-)
R-P6
ENABLE/
DISABLE
VFD
MOTOR
~ ~ ~
Sec. PumpCS-6 Status
CS-6
~ ~ ~
TB5-27 SIGCT
START/STOPSPEED
(0~10VDC)(+)
(-)
TB4-22 COM
R-P5
ENABLE/
DISABLE
VFD
MOTOR
~ ~ ~
Sec. PumpCS-5 Status
CS-5
~ ~ ~
TB5-24 SIGCT
Circ. PumpVFD CWP-5
Circ. PumpVFD CWP-6
SPARESPARESPARESPARESPARE
REFER TO VFD NETWORK FOR RESPECTIVE
(BACnet) VFD-COMM CONNECTIONS
8
4
5
1
14
12
13
9
(-)(+)
TB5-22 SIG
TB4-25 COM
8
4
5
1
14
12
13
9
(-)(+)
TB5-25 SIGTB4-19 COM
8
4
5
1
14
12
13
9
(-)(+)
TB5-19 SIG
TB4-16 COM
8
4
5
1
14
12
13
9
(-)(+)
TB5-16 SIG
TB4-4 COM
8
4
5
1
14
12
13
9
(-)(+)
TB5-4 SIG
TB4-1 COM
8
4
5
1
14
12
13
9
(-)(+)
TB5-1 SIG
499Ω
P/N: T-PB-202-0
TS-COM
499Ω
499Ω
499Ω
499Ω
499Ω
100-Ω Pt RTD531-431A
100-Ω Pt RTD531-431A
100-Ω Pt RTD531-431A
100-Ω Pt RTD531-431A
SCREW TO
PANEL FOR GROUND
SH
2B
-05
SO
CK
ET
RH
2B
-ULD
C24
VS
H2
B-0
5 S
OC
KE
TR
H2
B-U
LD
C24
VS
H2B
-05
SO
CK
ET
RH
2B
-ULD
C24
V
SH
2B
-05
SO
CK
ET
RH
2B
-ULD
C24
V
SH
2B
-05
SO
CK
ET
RH
2B
-ULD
C24
V
SH
2B
-05
SO
CK
ET
RH
2B
-ULD
C24
V
100-Ω Pt RTD
499Ω
AS-BUILT
Water Source Heat Pump
Main Loop
COOLING WATER LOOP CONTROL AND
AUTOMATION SYSTEM