Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Lid ScrewsUse Allen key to remove lid screws and access the interior of the PowerSyncTM enclosure.
PlugRemove one plug for each required cable entry and replace with suitable cable gland or conduit adaptor.
Mounting HolesUse suitable screws (6 mm or 1/4” diameter) and flat washers to attach enclosure to suitable mounting surface.
Observe orientation diagram in back of enclosure for correct orientation. Enclosure should be mounted in a vertical orientation so that the cable entries do not face upwards.
PlugLeave plug in place if not required for cable entry.
SealIf required, retain and use seal provided to ensure a water tight seal between cable, gland and enclosure
Electronic Equipment inside; failing to seal enclosure properly will void warranty.
LS6540MODEL: LS6540
INPUT VOLTAGE: 120-277 VCONNECTED CURRENT: 16A MAX
CONTROL & SUPPLY
INSTALLATION INSTRUCTIONSLUMASCAPE INC1300 Industrial Rd, Unit #19 San Carlos, CA 94070, USAT (650) 595-5862W www.lumascape.comFree Call : (866) 695-5862
FORM IN0172US 180328
Warranty void if not installed per instructions and local electrical code
Install in accordance with National Electric Code, ANSI/NFPA 70 or the Canadian Elec-
trical Code, Part I (CEC), CSA C22.1
WARNING
Power In/PowerSyncTM OutWire terminal clamps are opened by means of lever opening using fixed screwdriver. Terminals suit up to 8AWG copper wire, solid or stranded. Recommmended wire strip length is 0.6”(15mm).
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Overview
USB comissioning portStatus indicators
PWM / 0-10 V in
LabelDesignation
Use with 0-10 V Sinking Dimmers Use with 0-10 V Sourcing Dimmers PWM
10 V 10 V source (Purple wire) Not connected Not connected
+1 Channel 1 return (Grey wire) Channel 1 + Channel 1 +
+2 Channel 2 return (Reserved for future use) Channel 2 + Channel 2 +
GND Not connected Common − Common −
Wireless DMX system (optional)Label Designation
+ Power + (48 V DC)
− Power −For use with Lumascape wireless DMX system only.
Mode switchLabel Designation
0 DMX / RDM
1 DMX / RDM with SIP
2 Phase Dimming
3 0-10V Dimming (for Sinking Dimmers)
4 PWM Dimming
5 0-10V Dimming (for Sourcing Dimmers)
6 Reserved
7 4 Channel Cycle (Test Mode)
8 All Channels On (Test Mode)
9 All Channels Off (Test Mode)
Power inLabel Designation
L Line (120 - 277 V)
Earth
N Neutral
Phase controlLabel Designation
Phase active
PowerSyncTM out
LabelLuminaire
Wire ColourDesignation
Data Grey* PowerSync Data
L Black Line
Green / Yellow Earth
N White Neutral*Connecting high voltage to data terminal will cause permanent damage and void warranty.
DMX in / DMX out
Label DesignationPin out Cat 5 wire colour
3-pin XLR
5-pin XLR
RJ45 T568A T568B
+ Data + 3 3 1 White / Green White / Orange
− Data − 2 2 2 Green Orange
GND Ground 1 1 7 White / Brown White / BrownRefer to next page for correct installation of DMX wires.
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Installation of DMX wires
Wire clamp
Gently lift wire clamp to the open position. Do not force beyond this point.
Insertion points
Each wire clamp has two insertion points. Insert each wire as per appropriate wiring diagram.
Insert wire
Push the wire all the way into the insertion point. If done correctly, the end of the wire will be visible through the opening in the wire clamp.
The wire insulation should not be removed before wire insertion.
Close wire clamp
Firmly press the wire clamp back into its closed position; clamping the wires in place.
The wire clamp will cut the insulation and make contact.
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Wiring for DMX Controllers
Power inColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
DMX inColour Label Designation
White / Brown GND Ground
Green − Data −
White / Green + Data +
PowerSyncTM out to LuminairesColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Grey Data PowerSync Data
Refer to third party installation instructions for details on dimmer installation.
Mode SwitchSet to Mode 0
DMX out to next PowerSyncTM Data Injector (optional)Colour Label Designation
Green − Data −
White / Green + Data +
White / Brown GND GroundConnect to DMX in terminals of next PowerSyncTM Data Injector for DMX loop-through functionality.
Set mode switch on next PowerSyncTM Data Injector to Mode 0.
NOTE: If the output is not used a 120 Ω, 0.125 W resistor must be inserted between Data + and Data − of the DMX out terminals.
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Wiring for Lumascape Wireless DMX System
Power inColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Power to wireless moduleColour Label Designation
White + Power + (48 V DC)
White / White − Power −
DMX in from wireless moduleColour Label Designation
White / Brown GND Ground
Green − Data −
White / Green + Data +
PowerSyncTM out to LuminairesColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Grey Data PowerSync Data
Mode SwitchSet to Mode 0
DMX out to next PowerSyncTM Data Injector (optional)Colour Label Designation
Green − Data −
White / Green + Data +
White / Brown GND GroundConnect to DMX in terminals of next PowerSyncTM Data Injector for DMX loop-through functionality.
Set mode switch on next PowerSyncTM Data Injector to Mode 0.
NOTE: If the output is not used a 120 Ω, 0.125 W resistor must be inserted between Data + and Data − of the DMX out terminals.
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Wiring for 0-10 V Sinking Dimmers
Power inColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
0-10 V in from sinking dimmerColour Label Designation
Grey +2 Channel (2 V –) (optional)
Grey +1 Channel 1 (V +)
Purple 10 V 10 V source (V+)
PowerSyncTM out to LuminairesColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Grey Data PowerSync Data
Refer to third party installation instructions for details on dimmer installation.
Mode SwitchSet to Mode 3
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Wiring for 0-10 V Sourcing Dimmers
Power inColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
0-10 V in from sourcing dimmerLabel Designation
GND Common (V −)
+2 Channel 2 (V+) (optional)
+1 Channel 1 (V+)
PowerSyncTM out to LuminairesColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Grey Data PowerSync Data
Refer to third party installation instructions for details on dimmer installation.
Mode SwitchSet to Mode 5
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Wiring for PWM Dimmers
Power inColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (112 - 277 V)
PWM in from dimmerLabel Designation
GND Common (V−)
+2 Channel 2 (V+) (optional)
+1 Channel 1 (V+)
PowerSyncTM out to LuminairesColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Grey Data PowerSync Data
Refer to third party installation instructions for details on dimmer installation.
Mode SwitchSet to Mode 4
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
Wiring for Trailing Edge Phase Dimmers
Power inColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Signal in from trailing edge phase dimmerLabel Designation
Line input
Signal output
PowerSyncTM out to LuminairesColour Label Designation
White N Neutral
Green / Yellow Earth
Black L Line (120 - 277 V)
Grey Data PowerSync Data
Refer to third party installation instructions for details on dimmer installation.
PWM out to next PowerSyncTM Data Injector (optional)Label Designation
+1 Channel 1+
+2 Channel 2+ (optional)
GND Common −Connect to PWM in terminals of next PowerSyncTM Data Injector for PWM repeater functionality.
Set mode switch on next PowerSyncTM Data Injector to Mode 4.
Mode SwitchSet to Mode 2
Check compatibility with dimmers before implementation.
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328
PowerSyncTM Network Installation
Network Topology - PowerSync™ Dimmable
Control Signal
120-277V50/60Hz
120-277V50/60Hz
Loop to next PowerSync™Data Injector
150m (492') max
Combined length of both trunk cables can not exceed 150m (492')
PowerSync™ Topology 1 - Single Trunk Cable
10m (33')max
PowerSync™ Topology 2 - Split Trunk Cable
LS6540PowerSync™Data Injector
LS6540PowerSync™Data Injector
I
I
T
1.8
m (6
’) m
ax
T
1.8
m (6
’) m
ax
T
1.8
m (6
’) m
ax
PowerSync™ Luminaire
PowerSync™ Luminaire
PowerSync™ Luminaire
PowerSync™ Luminaire
PowerSync™ Luminaire
PowerSync™ Luminaire
PowerSync™ Luminaire
PowerSync™ Luminaire
PowerSync™ Luminaire
Up to 45 luminaires per run under the following conditions: Max total cable run length 150m (492') in up to two trunk cables
Refer to 'Maximum Circuit Load' table for circuit limitations
Always observe local electrical codes for branch circuit current limitations
For run length in excess of 30m (100') use a wire size not lower than 14 AWG
Terminator
Use PowerSync™ terminator, supplied with leader cable to terminate last luminaire in chain.
T
Maximum Current
≤16.0A through LS6540 Data Injector.
I
Connection Type
Circuits can be configured as either connectorised or hardwired. For details consult installation instructions and comply with local electrical codes.
NOTE: The above diagrams are intended to show electrical pathways between luminaires and ancillary device. These diagrams are not intended to show typeor colour of cord / wire, luminaire input voltage rating, wire gauge or approved use of the cord / wire supplied with luminaires.
Copyright ©2018 LUMASCAPE
www.lumascape.com
Should you experience any difficulty, please contact Lumascape directly: phone (866) 695-5862 or email [email protected]
IF IN DOUBT, PLEASE CALLIN0172US 180328 - 28 March 2018
Maximum trunk cable length 150 m/490ft*
Maximum fixture count per PowerSyncTM Injector 45*
Maximum branch circuits fed from 1 PowerSyncTM Injector 2
Maximum cable length for a 2-branch circuit 75 m/245ft*
Maximum circuit current 16A (Linear luminaires, connectorized, limited to 12.8A)
Maximum and Minimum System Voltage 120-277 V AC
Maximum leader cable length No limit (within trunk cable limits)
Circuits must be terminated at the furthest point from the PowerSyncTM Injector.
*Dependant on circuit load and voltage drop
PowerSyncTM System Limitations
3.3m�
/2a
bgv nrecvlrp tcvgf yltgpwvu owuv dg wugf
yjgp m-drzgu ctg lp 'ygv nrecvlrpu'.
120-288a 50/60 j�Dtcpej Eltewlv
Vjtrwij bltgf Mwpevlrp Drz
Vr Nwolpcltg
bgv nrecvlrp tcvgf yltgpwvu owuv dg wugf yjgp m-drzgu
ctg lp 'ygv nrecvlrpu'. D� rvjgtu.
'Hpf rh Twp' Mwpevlrp Drz & Vgtolpcvlrp
Vr Nwolpcltg
Lpuvcnn NU6408 Vgtolpcvrt cv cnn 'gpf rh twp' nrecvlrpu
120-288a 50/60 j�Dtcpej Eltewlv
120-288a 50/60 j�Dtcpej Eltewlv
3.3m�
/2a
bgv nrecvlrp tcvgf yltgpwvu owuv dg wugf
yjgp m-drzgu ctg lp 'ygv nrecvlrpu'.
120-288a 50/60 j�Dtcpej Eltewlv
Vjtrwij bltgf Mwpevlrp Drz
Vr Nwolpcltg
bgv nrecvlrp tcvgf yltgpwvu owuv dg wugf yjgp m-drzgu
ctg lp 'ygv nrecvlrpu'. D� rvjgtu.
'Hpf rh Twp' Mwpevlrp Drz & Vgtolpcvlrp
Vr Nwolpcltg
Lpuvcnn NU6408 Vgtolpcvrt cv cnn 'gpf rh twp' nrecvlrpu
120-288a 50/60 j�Dtcpej Eltewlv
120-288a 50/60 j�Dtcpej Eltewlv