vulnerability of electricity grid systems to climate...
TRANSCRIPT
2138-10
Joint ICTP-IAEA Workshop on Vulnerability of Energy Systems to Climate Change and Extreme Events
David M. Ward
19 - 23 April 2010
Magnox North, Ltd. Thornbury
UK
Vulnerability of Electricity Grid Systems to Climate Change & Extreme Weather Events
ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010 11
David WardDavid WardMagnox North Ltd, UKMagnox North Ltd, UK
International Workshop on ‘Vulnerability of Energy Systems to Climate Change and Extreme Events’
Vulnerability of Electricity Grid Vulnerability of Electricity Grid Systems to Climate Change & Systems to Climate Change &
Extreme Weather EventsExtreme Weather Events
22ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Electricity Grid SystemElectricity Grid System
Source: Wikipedia Commons / US DOE / Final Report of the US-Canada Task Force, 2004
33ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Reliable grid?Reliable grid?
� Loss of supply to customers is rare� System collapse/blackout very rare� Voltage well controlled (+/- 5%)� Frequency well controlled (+/- 1%)� Abnormal voltage or frequency is rare
44ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Components of a Grid SystemComponents of a Grid System� Overhead lines� Underground cables� Substations (switchyards)� Transformers� Control centres� Communications systems� People to operate and maintain it
55ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Transmission Transmission NetworkNetwork
� Very high voltages (>100kV)� Transmits high power long distances
� One circuit supplies many customers
� >95% Overhead lines� Uses tall steel towers
Source: Author’s own photo - 400kV line near Bristol, UK
66ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Transmission SubstationTransmission Substation
Source: British Energy photo - Heysham 400kV substation
77ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Distribution NetworkDistribution Network� Operates at medium/low voltage (<<100kV)
� Transmits medium/low power short distances
� Each circuit supplies a few customers
� 25%-95% overhead lines� Typically uses wooden poles
Source: Author’s own photo - 11kV/400V transformer and lines
88ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Distribution SubstationDistribution Substation
Source: Author’s own photo - Almondsbury 33kV/11kV substation
99ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Reliability StandardsReliability Standards� UCTE / ENTSO-E (Western Europe)
http://www.entsoe.eu/� NERC (USA & Canada)
http://www.nerc.com/� National Grid (Great Britain)
http://www.nationalgrid.com/� Nordel (Scandinavia)
http://www.entsoe.eu/
1010ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
UnplannedUnplanned trip of:trip of:� Generating unit� Overhead line� Underground cable
� Transformer� Busbar in substation
Should not cause:Should not cause:� Disconnection of customers
� Unacceptable voltages
� Unacceptable frequency
� Circuit overload� Loss of synchronism (pole slip)
� Cascade tripping
X
1111ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Transmission NetworkTransmission Network“Meshed”
Source: National Grid Seven Year Statement
1212ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Distribution NetworkDistribution NetworkSupply from transmission network
Supply to customers
Medium Voltage
“Radial”
Low Voltage
High Voltage
Source: Author’s own drawing
1313ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Grid System FaultsGrid System Faults� Weather-related
• Lightning, wind, rain, snow� Environmental
• Trees, birds, vermin, air pollution, earthquakes, geomagnetic storms
� Equipment failure� Human error� Malicious damage
1414ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Weather and Grid SystemsWeather and Grid Systems� Normal Weather
• Occasional grid faults� Adverse Weather
• Multiple grid faults, but little damage� Extreme Weather
• Multiple grid faults• Widespread damage
1515ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Transmission Faults Transmission Faults
0
20
40
60
80
10019
81-82
1984
-85
1987
-88
1990
-91
1993
-94
1996
-97
1999
-00
2002
-03
2005
-06
2008
-09
Fault
s per
year
Weather-relatedNon-Weather
Source: Prepared by author from National Grid data
(One region of GB - 741 circuit km of overhead lines)
1616ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Energy Not SuppliedEnergy Not Supplied
0
500
1000
1500
2000
2500
3000
350019
90/91
1993
/94
1996
/97
1999
/00
2002
/03
2005
/06
2008
/09
MW-H
ours
Weather-relatedNon-Weather
Source: Prepared by author from published National Grid data
(All of England and Wales - transmission faults only)
1717ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Blackouts in 2003Blackouts in 2003� Flashover to trees; poor control &
communications• USA/Canada (14 August)• Italy (28 September)
� Unusual equipment faults• Sweden/Denmark (23 September)
� Human error (incorrect protection)• London (28 August)
Source: Various published reports
1818ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Causes of Major US EventsCauses of Major US Events
Source: Prepared by author from data in Hines et al (2009)
Equipment failure
Operator error
FireWind/Rain
Ice stormHurricane Tornado
Other cold weather Lightning
Othernon-weather
1984 - 2006>300MW
1919ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
High windsHigh winds� Most customer interruptions due to
damage to distribution network� >50% damage due to trees� Damage related to square of maximum
(gust) wind speed� Only in most severe storms is
transmission network damaged
Source: Davidson et al (2003), Winkler et al (2010), Reed (2008)
2020ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
England England -- October 2002October 2002� Wind speed up to 45m/s� 2 million customers lost supplies for 18
hours up to 10 days� Damage to distribution networks� “Nearly all damage caused by falling
trees”� One very minor interruption do to fault
on transmission networkSource: House of Commons report (2004)
2121ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
England England -- October 1987October 1987� Worst storm in UK
for 300 years.� Wind speed 50 m/s� 15,000,000 trees
blown over� 17,000 houses
damaged
Source: House of Commons (2004). Photos: BBC Website
2222ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
England October 1987England October 1987� 1.5 million customers lost supply, some
for up to 3 weeks� Distribution network severely damaged,
mostly by falling trees� Parts of transmission network out of
service for up to 12 hours • Wind blown debris, salt pollution• No structural failure
Source: Various published reports
2323ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
France France -- December 1999December 1999Storms “Lothar” and “Martin”� Most severe storm ever in France� Wind speed up to 60m/s� 3.5million customers lost supply� 90% of damage to distribution network
due to falling trees� Severe damage to transmission network
- 120 towers collapsed.Source: Various published reports
2424ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Wind Wind -- Remedial MeasuresRemedial Measures� Higher design standards for poles and
towers� Change routes of overhead lines
• Along roads, away from trees� Rigorous management of trees� Use covered/insulated conductors � Use more underground cables
• Particularly in wooded areas
2525ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Snow and IceSnow and Ice� Weight of snow & ice, plus wind may
cause failures• Direct failure of overhead lines• Failure due to falling trees• Conductor “galloping”
� Extreme form is the “ice storm”• Super-cooled rain causes rapid build-up of ice
2626ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010 Source: Ontario Hydro centenary booklet & IAEA report
Ice Storm Ice Storm -- January 1998January 1998
2727ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Lightning StrikesLightning Strikes� Common on transmission network• Protected by earth wires, spark gaps etc.
� Less common on distribution networks• Not usually protected by earth wires, spark gaps etc.
Source: Photo from Wikipedia commons - Lyoha123
2828ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Lightning RiskLightning RiskIf lightning gets worse…
� More damage to equipment
� Justifies more money for lightning protection
Source: Photos from public domain EPRI reports
2929ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
RainRain� Heavy rain by itself not usually a major problem
� Sometimes causes flashover faults
� Sometimes leaks into equipment
Source: Photo from public domain EPRI report
3030ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Water Ingress Water Ingress -- Failure Failure
Source: Magnox photo
3131ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Climate and FloodsClimate and Floods� Very heavy rain, so rivers flood
surrounding area� Very high winds damage flood defences
(e.g. Hurricane Katrina)� Sea level rise from global warming
3232ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
FloodFlood� Not an issue for transmission circuits
� Not an issue for distribution circuits, unless very deep
� Serious issue for equipment mounted at ground level in substations
Source: Author’s own photos
3333ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010 Source: Photo courtesy of British Energy
FloodFlood
3434ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
High TemperatureHigh TemperatureLimits the power rating of � Overhead lines� Underground cables� TransformersDoes not cause immediate faults of� Underground cables� Transformers
3535ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
High temperature flashoverHigh temperature flashoverFlashover to trees
Source: US DOE / Final Report of the US-Canada Task Force, 2004
3636ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
DroughtDrought� Not major problem for grid systems
(water not used for cooling)� If soil dries out - can reduce thermal
rating of underground cables� Main problem is increased risk from
brush fires or forest fires.
3737ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Fires after droughtFires after drought
Source: Internet photo and US Bureau of Land Management
3838ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
Avalanches and LandslidesAvalanches and Landslides� Result of very heavy rain or snow
� May damage a few towers or poles
� Limited effect on transmission or distribution
� Could damage substations
Source: Photos from Wikipedia Commons (US Federal Government)
3939ICTP, Trieste, ItalyICTP, Trieste, Italy1919--23 April 201023 April 2010
DiscussionDiscussion� Grid equipment has a life of 30 to 50
years.� It can gradually be replaced with
equipment of higher standard� Transmission and Distribution networks
are different� Control of trees is a major issue.