1. Read this manual thoroughly before using the VT210S, and store ina safe place for reference.
2. Make sure that this manual is delivered to the final user.
MEIDENSHA CORPORATION
MEIDEN
AC SPEED CONTROL EQUIPMENT
THYFREC-VT210S400V System 37 to 315kW (C/T)400V System 45 to 370kW (V/T)
QUICK START GUIDE
Feb 2000QS210S Rev1
-
8/12/2019 VT210S
2/8
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 1
Warning
This Quick Start Instruction Guide is intended as a guide only.
Read the Instruction Manual thoroughly before using the VT210S.
Use extreme caution during installation.
Do not open the front cover while power is applied.
Always ground the Inverter heatsink.
If in doubt, refer to your supplier or
MEIDEN DRIVELINE Tel: 01908 276000
The information contained in this publication, including numerical data, hasbeen prepared as a general guide to the product. No responsibility is assumedfor errors herein. Meiden Europe Ltd reserve the right to make changes to thisdocument and Instruction Manual at any time.
E&OE
-
8/12/2019 VT210S
3/8
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 2
Installation
Install the Inverter vertically, so that the cable glands face downwards.Allow for the correct spacing around the Inverter for ventilation
(X +>50mm, Y +>200mm). Fig. 1.
Always ensure that the Inverter is switched off before wiring.
Please note that TBA must be set in position shown (Fig. 2.)for 380-400V operation, and in position 1-2 for 415-460Voperation.
Connect wiring as shown in Fig. 2. Make sure that correctshort circuit protection devices are fitted and best wiringpractises are observed (see page 2-3 in the suppliedmanual).
A Ferrite is supplied with the filter, which must be fitted to
meet EMC compliance. The motor phase cables must beinserted through the output ferrite as per EMC Filter KitsGuide to Installation and Use.
Voltage Surge
For long motor cable lengths (>30m), a motor choke can be ordered whichmust be fitted between the Inverter and the motor. Motor cables must bescreened at both ends.
Connect inputs as shown in Fig. 3. or to suit your application. If using a
potentiometer, connect the wiper to FSV terminal. Analogue signalcables MUSTbe screened. Connect one end of the screen to COM.The COMterminals are linked internally.RY0is isolated and must NOTbe connected to COM.
Test Running the Drive
Please note that VT210S drives are supplied either as Constant Torque or Variable Torque and cannot be changedby the user. Operating the drive type is identical in all other ways although maximum and minimum values of someparameters may vary.
Default settings allow the basic running of the motor to prove the system, but first set:
B00-1 set 31 assuming 415V, 50Hz B00-5 set motor rated current (A)supply, and max freq B00-4 Output Voltage may haverequirement of 50Hz. to be set for non-standard
motors.
On power up, the Inverter display will cycle through a self-diagnostics check, and then show confirming thedrive is in a ready state.
Press FWD on the keypad and the motor will ramp up to 10Hz in a forward direction. The display will changefrom to ( local frequency setting A00-0).Press REVand check that the motor changes direction. Now press STOP, the motor will stop.
Acceleration and Deceleration will be default values at this stage.
(R RUN)
(F JOG)
(R JOG)
N.B. Terminal/Busbararrangements differ onlarger drives.(Refer to page 2-8 in thesupplied manual).
Fig.2.
-
8/12/2019 VT210S
4/8
-
8/12/2019 VT210S
5/8
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 4
Other Useful Features
LCD Operator Panel - Upload/Download parameters, save 10 programsContact you Supplier or Meiden Europe Ltd for more information.
Parameter (password) protection - B06-0 Pages 6-11/6-19Programmable outputs - B05-0/2 Pages 6-11/6-18Dynamic Braking - B80-1 Pages 7-3/7-4Pattern Run - B5x-x Pages 6-38/6-39PID Control - B43-x Pages 6-37/6-434-20mA input - B04-1 Page 6-11
Auxiliary Input - B24-0 Pages 6-22/6-29Arbitary Scale - B05-2 Pages 6-11/6-18
Setting Pre-set Speeds
As well as running from 0-10V analogue reference, it is possible to set up to 8 pre-set speeds (plus Jog). Digitalinputs PSI1-PSI5 can be programmed in a number of ways to suit the application.
A worked example of using 10Hz, 13.20Hz, 25Hz, 40.32Hz and 50Hz pre-set speeds is shown below:
Set B03-1to 0 turns off F Jog Set B04-6to 5 uses PSI5 as S2Set B03-2to 0 turns off R Jog Set B20-0to 10.00 Prog Freq 0 - 10HzSet B04-2to 2 uses PSI2 as PROG Set B20-1to 13.00 Prog Freq 1 - 13.20Hz
to enable pre-set speeds Set B20-2to 25.00 Prog Freq 2 - 25HzSet B04-4to 3 uses PSI3 as S0 Set B20-3to 40.32 Prog Freq 3 - 40.32HzSet B04-5to 4 uses PSI4 as S1 Set B20-4to 50 Prog Freq 4 - 50Hz
Using inputs PSI3-PSI5 as binary inputs (see Fig. 5) it is possible to set any of the speeds. Please note that it is alsopossible to set independent accel/decel ramps to each pre-set speed. (Refer to B40-0, B41-xand B42-xon pages6-37/6-40).
Sequence Command Selected Frequency
Prog S2 S1 S0
ON OFF OFF OFF Prog Freq 0 - 10Hz
ON OFF OFF ON Prog Freq 1 - 13.2Hz
ON OFF ON OFF Prog Freq 2 - 25Hz
ON OFF ON ON Prog Freq 3 - 40.32Hz
ON ON OFF OFF Prog Freq 4 - 50Hz
ON ON OFF ON Prog Freq 5 - Unset
ON ON ON OFF Prog Freq 6 - Unset
ON ON ON ON Prog Freq 7 - Unset
OFF ANY ANY ANY Analogue I/P
Fig.5.
-
8/12/2019 VT210S
6/8
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 5
Param Description
Monitor/(Display) ParametersOutput frequency
D00-0 O/P frequency (Hz)D00-1 O/P frequency (%)D00-2 O/P frequency (AS)Frequency Setting
D01-0 Set frequency (Hz)
D01-1 Set frequency (%)D01-2 Set frequency (AS)Output (O/P) current
D02-0 O/P current (A)
D02-1 O/P current (%)
D02-2 OLT monitor (%)
D02-3 Heatsink temperature (C)Voltage
D03-0 DC voltage (V)D03-1 O/P voltage command (V)Sequence status
D04-0 I/PD04-1 O/PExtended monitor
D05-0 Fault historyD05-1 Trace data entryD05-2 Non-default parameter listD05-3 Cumulative cond time (Hrs)D05-4 Cumulative run time (Hrs)
D05-5 CPU version
D05-6 ROM versionPattern run monitor
D06-0 Step No.
D06-1 Remaining time (s)Speed detection monitor (ASR)
D07-0 Detection speed (Hz)D07-1 Detection speed (%)D07-2 Detection speed (AS)
A ParametersFrequency setting
A00-0 Set local frequency (Hz)A00-1 Set jog frequency (Hz)
Acceleration/Deceleration times
A01-0 Acceleration time - 1 (s)A01-1 Deceleration time - 1 (s)Torque boost
A02-0 Torque boost voltage (%)A02-1 Reduced volt squ law trq (%)
A02-2 Auto torque boost gain
A02-3 Slip compensation gain (%)DC brake
A03-0 DC braking voltage (%)A03-1 DC braking time (s)Custom parameters
A04-0 Custom - 0 (Ref B07-0)A04-1 Custom - 1 (Ref B07-1)A04-2 Custom - 2 (Ref B07-2)A04-3 Custom - 3 (Ref B07-3)A04-4 Custom - 4 (Ref B07-4)A04-5 Custom - 5 (Ref B07-5)A04-6 Custom - 6 (Ref B07-6)A04-7 Custom - 7 (Ref B07-7)Block B skip parameters
A05-0 Skip selector (1111-2221)
B Parameters - Basic FunctionsOutput ratings
B00-1 Preset V/F patternB00-2 Max O/P freq (Fmax) (Hz)B00-3 Base freq (Hz)B00-4 O/P voltage (V)B00-5 Motor rated current (A)B00-6 Carrier frequency (kHz)Control methods
B01-0 Run/stopB01-1 Inhibit (EMS)B01-2 Control sourceStart/stop frequencyB02-0 Start freq (Hz)B02-1 Stop freq (DC brake start) (Hz)
Min - Max
0.10 - Fmax0.10 - Fmax
0.1 - 60000.1 - 6000
0.0 - 10.00.0 - 25.0
0.00 - 10.000.0 - 5.0
0.1 - 10.00.0 - 20.0
1111 - 2221
10 - 593.0 - 440.00.0 - 440.0
0 - 460Icrx0.3 - Irc
3 - 8
1111 - 322311 - 3211 - 22
0.1 - 60.00.1 - 60.0
Param Description
B Parameters - Basic FunctionsProg I/P config 1 - operating commands
B03-0 R RUNB03-1 F JOGB03-2 R JOGB03-3 HOLDB03-4 BRAKE
B03-5 PICKB03-6 COP
B03-7 CSEL
B03-8 IPASSProg I/P config 2 - select commands
B04-0 VFS
B04-1 IFSB04-2 PROGB04-3 CFSB04-4 S0B04-5 S1B04-6 S2B04-7 FUPB04-8 FDWB04-9 FUP/FDW step (Hz)Meter O/P gain/scale multiplier
B05-0 O/P gain (FM)B05-1 O/P gain (AM)B05-2 AS display coeff (AS)Protection/operation (PP/O) locks
B06-0 PP/O locks
B06-1 Reverse lock
B06-2 Fault history buffer clear
B06-3 Default value loadCustom parameter registerB07-0 Custom - 0 (Ref A04-0)B07-1 Custom - 1 (Ref A04-1)B07-2 Custom - 2 (Ref A04-2)B07-3 Custom - 3 (Ref A04-3)B07-4 Custom - 4 (Ref A04-4)B07-5 Custom - 5 (Ref A04-5)B07-6 Custom - 6 (Ref A04-6)B07-7 Custom - 7 (Ref A04-7)Operation panel initial mode
B08-0 Initial modeB08-1 Operation monitorB08-2 LCD OPU monitor
B08-3 LCD OPU bar graph
B Parameters - Extended FunctionsProgram frequency setting
B20-0 Program frequency - 0 (Hz)B20-1 Program frequency - 1 (Hz)B20-2 Program frequency - 2 (Hz)B20-3 Program frequency - 3 (Hz)B20-4 Program frequency - 4 (Hz)B20-5 Program frequency - 5 (Hz)B20-6 Program frequency - 6 (Hz)B20-7 Program frequency - 7 (Hz)
Acceleration/deceleration times
B21-0 Acceleration time 2 (s)B21-1 Deceleration time 2 (s)B21-2 Jog acceleration (s)B21-3 Jog deceleration (s)
B21-4 S curve characteristics (s)
B21-5 Time unit multiplierFrequency skip
B22-0 Skip frequency 1 (Hz)
B22-1 Skip band 1 (Hz)B22-2 Skip frequency 2 (Hz)B22-3 Skip band 2 (Hz)B22-4 Skip frequency 3 (Hz)B22-5 Skip band 3 (Hz)Ratio Interlock setting
B23-0 Polarity setting (A&B)B23-1 Coefficient A valueB23-2 Bias B value (Hz)B23-3 Upper limit (Hz)B23-4 Lower limit (Hz)I/P terminal function
B24-0 I/P terminal modeB24-1 AUX I/P gain settingO/P terminal function
B25-0 FM/AM O/P parameters
B25-1 RUN terminal parametersB25-2 ATN terminal parameter
Min - Max
0 - 160 - 160 - 160 - 160 - 16
0 - 160 - 160 - 160 - 16
0 - 160 - 160 - 160 - 160 - 160 - 160 - 160 - 160 - 16
0.01 - 2.00
0.20 - 2.000.20 - 2.00
0.01 - 100.0
1111 - 123911 - 220 - 99990 - 9999
0.00 - 99.90.00 - 99.90.00 - 99.90.00 - 99.90.00 - 99.90.00 - 99.90.00 - 99.90.00 - 99.9
11 - 320.0 - 9.90.0 - 9.9
0.0 - 9.9
0.10 - Fmax0.10 - Fmax0.10 - Fmax0.10 - Fmax0.10 - Fmax0.10 - Fmax0.10 - Fmax0.10 - Fmax
0.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.0
0.0 - 5.01 - 3
0.10 - 440.000.0 - 10.0
0.10 - 440.000.0 - 10.0
0.10 - 440.000.0 - 10.0
11 - 220.000 - 10.0000.00 - 440.000.10 - 440.000.10 - 440.00
1111 - 12320.000 - 5.000
00 - 88
0 - 150 - 15
Parameter Listing
-
8/12/2019 VT210S
7/8
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 6
Param Description
B Parameters - Extended FunctionsDetect levelssequence O/P
B26-0 ATN detect band (%)B26-1 Current det level (IDET) (%)B26-2 Speed det level 1 (SPD1) (%)B26-3 Speed det level 2 (SPD2) (%)Retry/Pick up
B28-0 No. of retriesB28-1 Retry wait time (s)
B28-2 Pick-up wait time (s)
B28-3 Pick-up voltage time (s)Overcurrent limit
B29-0 Drive current limit (%)
B29-1 Regen torque limit (%)Overload
B30-0 Overload setting (%)B30-1 0Hz overload (%)B30-2 0.7 Ftrq overload (%)V/F middle point
B31-0 Frequency 2 (GF2) (Hz)B31-1 Voltage 2 (GV2) (%)B31-2 Frequency 1 (GF1) (Hz)B31-3 Voltage 1 (GV1) (%)Start interlock
B32-0 Start/stop frequency (Hz)B32-1 Start/stop freq hysterises (Hz)
B32-2 Interlock frequency (Hz)
B32-3 RUN delay timer (s)High-efficiency operation
B33-0 High-efficiency time constant (s)
B33-1 Voltage lower limit (%)S/W option configuration
B40-0 S/W operation selectProgram ramp - acceleration
B41-0 Acceleration time - 0 (s)B41-1 Acceleration time - 1 (s)B41-2 Acceleration time - 2 (s)B41-3 Acceleration time - 3 (s)B41-4 Acceleration time - 4 (s)B41-5 Acceleration time - 5 (s)B41-6 Acceleration time - 6 (s)B41-7 Acceleration time - 7 (s)Program ramp - deceleration
B42-0 Deceleration time - 0 (s)
B42-1 Deceleration time - 1 (s)B42-2 Deceleration time - 2 (s)
B42-3 Deceleration time - 3 (s)
B42-4 Deceleration time - 4 (s)
B42-5 Deceleration time - 5 (s)B42-6 Deceleration time - 6 (s)B42-7 Deceleration time - 7 (s)
B Parameters - Software FunctionsPID control
B43-0 Proportional gainB43-1 Integral time constant (s)B43-2 Differential time constant (s)B43-3 Upper limit (%)B43-4 Lower limit (%)Traverse option
B44-0 Centre freq (FH) (Hz)
B44-1 Amplitude - A (%)
B44-2 Drop - D (%)
B44-3 Acceleration time - B (s)
B44-4 Acceleration time - C (s)
B44-5 Deviated traverse - X (%)B44-6 Deviated traverse - Y (%)Pattern run step - 0B50-0 ModeB50-1 Frequency (Hz)B50-2 Time (s)Pattern run step - 1
B51-0 ModeB51-1 Frequency (Hz)B51-2 Time (s)Pattern run step - 2
B52-0 ModeB52-1 Frequency (Hz)B52-2 Time (s)Pattern run step - 3
B53-0 Mode
B53-1 Frequency (Hz)B53-2 Time (s)
Min - Max
0.0 - 20.05 - 300.0
1.0 - 105.01.0 - 105.0
0 - 101 - 301 - 10
1 - 300
50 - 3005 - 300
50 - 10520 - 10550 - 105
0.0 - Fmax0.0 - 100.00.0 - Fmax0.0 - 100.0
0.0 - 20.00.0 - 20.00.0 - 20.0
0.00 - 10.00
10 - 30155 - 100
11 - 24
0.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.0
0.1 - 6000.0
0.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.00.1 - 6000.0
0.01 - 10.00.0 - 30.0
0.000 - 1.00050 - 100
50 - 0
0.1 - Fmax0.1 - 20.0
0.0 - 50.00.5 - 60.00.5 - 60.00.0 - 20.00.0 - 20.0
0 - 20.10 - Fmax0.1 - 6000.0
0 - 20.10 - Fmax0.1 - 6000.0
0 - 130.10 - Fmax0.1 - 6000.0
0 - 23
0.10 - Fmax0.1 - 6000.0
Param Description
B Parameters - Software FunctionsPattern run step - 4
B54-0 ModeB54-1 Frequency (Hz)B54-2 Time (s)Pattern run step - 5
B55-0 Mode
B55-1 Frequency (Hz)B55-2 Time (s)Pattern run step - 6
B56-0 Mode
B56-1 Frequency (Hz)
B56-2 Time (s)Pattern run step - 7B57-0 ModeB57-1 Frequency (Hz)B57-2 Time (s)Pattern run step - 8B58-0 ModeB58-1 Frequency (Hz)B58-2 Time (s)Pattern run step - 9
B59-0 ModeB59-1 Frequency (Hz)B59-2 Time (s)
Min - Max
0 - 330.10 - Fmax0.1 - 6000.0
0 - 43
0.10 - Fmax0.1 - 6000.0
0 - 530.10 - Fmax0.1 - 6000.0
0 - 630.10 - Fmax0.1 - 6000.0
0 - 730.10 - Fmax0.1 - 6000.0
0 - 830.10 - Fmax0.1 - 6000.0
Parameter Listing
-
8/12/2019 VT210S
8/8
Quick Start Guide Meiden Europe Ltd
QS210S Rev 1 Page 7
Non-default Parameters
Inverter.. Job No..
Reference..
Parameter Set To.. Notes Parameter Set To.. Notes