voltage stress in power systems -
TRANSCRIPT
-
7/30/2019 Voltage Stress in Power Systems -
1/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 1 -
Voltage Stress in Power Systems - Classification
IEC 60071-1
-
7/30/2019 Voltage Stress in Power Systems -
2/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 2 -
Classification of real stress
Classification of real stress
Voltage Stress in Power Systems
"Continuous (power-frequency) voltage"
Power-frequency voltage, considered having constant r.m.s. value, continuously applied to any pair of
terminals of an insulation configuration
f= 50 Hz or 60 Hz
T1 3 600 s
Any power-frequency voltage lasting for 1 h or more is considered a continuous voltage!
Standard voltage
Standard voltage "Standard power-frequency voltage"
A sinusoidal voltage with frequency of 50 Hz or 60 Hz
T1 to be specified by the apparatus committees T1 up to 2 years! see next slides
Conversioninto
Voltage Stress in Power Systems - Classification
-
7/30/2019 Voltage Stress in Power Systems -
3/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 3 -
Example: Cable tests at power-frequency voltage
Example: Cable tests at power-frequency voltage
Voltage Stress in Power SystemsVoltage Stress in Power Systems - Classification
Lifetime characteristic:
-
7/30/2019 Voltage Stress in Power Systems -
4/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 4 -
Example: Cable tests at power-frequency voltageExample: Cable tests at power-frequency voltage
Voltage Stress in Power SystemsVoltage Stress in Power Systems - Classification
Source: Brugg Cables
11.4 years
-
7/30/2019 Voltage Stress in Power Systems -
5/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 5 -
Voltage Stress in Power Systems
"Temporary overvoltage"
Power-frequency overvoltage of relatively long duration. The overvoltage may be damped or
undamped. In some cases its frequency may be several times smaller or higher than power
frequency.
10 Hz < f< 500 Hz
3 600 s T1 0.02 s
Highest values by following main reasons:
phase-to-earth earth faults and load rejection
phase-to-phase load rejection
longitudinal phase opposition during synchronization of two grids
Standard voltageStandard voltage "Standard short-duration power-frequency voltage"
A sinusoidal voltage with frequency between 48 Hz and 62 Hz
T1 = 60 s
Conversioninto
Classification of real stressClassification of real stress
Example [THI-01]
Voltage Stress in Power Systems - Classification
-
7/30/2019 Voltage Stress in Power Systems -
6/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 6 -
Voltage Stress in Power Systems
"Transient overvoltage"
Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly
damped. May be followed by temporary overvoltages. In this case, both events are considered as
separate events.
Standard voltageStandard voltage "Standard switching impulse"
An impulse voltage of
Tp = 250 s
T2 = 2 500 s
Conversioninto
Classification of real stressClassification of real stress
"Slow-front overvoltage"
Transient overvoltage, usually unidirectional
5000 s Tp > 20 s
T2 20 ms
Main reasons: line faults, switching
Example [THI-01]
Voltage Stress in Power Systems - Classification
-
7/30/2019 Voltage Stress in Power Systems -
7/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 7 -
Voltage Stress in Power Systems
"Transient overvoltage"
Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly
damped. May be followed by temporary overvoltages. In this case, both events are considered as
separate events.
Standard voltageStandard voltage "Standard lightning impulse"
An impulse voltage of
T1 = 1.2 s
T2 = 50 s
Conversioninto
Classification of real stressClassification of real stress
"Fast-front overvoltage"
Transient overvoltage, usually unidirectional
20 s T1 > 0.1 s
T2 300 s
Main reasons: lightning strokes, switching
Example [THI-01]
Voltage Stress in Power Systems - Classification
-
7/30/2019 Voltage Stress in Power Systems -
8/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 8 -
Voltage Stress in Power Systems
"Transient overvoltage"
Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly
damped. May be followed by temporary overvoltages. In this case, both events are considered as
separate events.
Standard voltageStandard voltage not standardized
Conversioninto
Classification of real stressClassification of real stress
"Very-fast-front overvoltage"
Transient overvoltage, usually unidirectional
Tf< 100 ns
(Tt 3 ms)
basic oscillation (1st harmonics) 30 kHz < f< 300 kHzsuperimposed oscillations 300 kHz < f< 100 MHz
Main reasons: switching of disconnectors in GIS
Example [THI-01]
Voltage Stress in Power Systems - Classification
-
7/30/2019 Voltage Stress in Power Systems -
9/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 9 -
Voltage Stress in Power Systems
"Combined (temporary, slow-front, fast-front,very-fast-front) overvoltage"
Consisting of two voltage components simultaneously applied between each of the two phase
terminals of a phase-to-phase (or longitudinal) insulation and earth. It is classified by the component
of the higher peak value.
Standard voltageStandard voltage "Standard combined switching impulse"
Conversioninto
Classification of real stressClassification of real stress
Combined impulse voltage having two components of equal peak value and opposite polarity. The
positive component is a standard switching impulse and the negative one is a switching impulse
whose times to peak and half value should not be less than those of the positive impulse. Bothimpulses should reach their peak values at the same instant. The peak value of the combined voltage
is, therefore, the sum of the peak values of the components.
Voltage Stress in Power Systems - Classification
-
7/30/2019 Voltage Stress in Power Systems -
10/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 10 -
Temporary Overvoltages Earth Faults
Reasons for temporary overvoltages: earth faults
load rejection
resonance phenomena
In case of earth faults the overvoltage amplitudes depend on
neutral earthing
fault location.
Important parameter: Earth fault factor kImportant parameter: Earth fault factor k
LE
b/ 3
Uk
U=... in other "words": ULE ... phase-to-earth voltage of sound phase during fault
Ub ... phase-to-phase voltage at same location before fault
IEC 60071-1
-
7/30/2019 Voltage Stress in Power Systems -
11/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 11 -
Temporary Overvoltages Earth Faults
The earth fault factor depends on the ratio of the complex impedances Z1 andZ0 of the positive and zero sequence systems (German: "Mitsystem",
"Nullsystem"). In case of neglecting the resistances (possible in high-voltage
systems) it depends on the ratio of the reactances X0 and X1:
( )2
0 1 0 1
0 1
1 / /3
2 /
X X X Xk
X X
+ +=
+
a ratio ofX0/X1 = -2 must be avoided!solidlyearth
edneutral
resonant earthedneutral,isolated neutral
resonant earthedneutral,isolated neutral
not forpractical use!
according to [BAL-04]
-
7/30/2019 Voltage Stress in Power Systems -
12/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 12 -
Temporary Overvoltages Earth Faults
Treatment of neutral in Germany (VDEW, 1998):
according to [BAL-04]
treatment of neutral 10 kV 20 kV 110 kV 380 kV
isolated 8.6% < 0.1% 0.0% 0.0%
resonant earthed 77.8% 92.8% 80.9% 0.7%
solidly earthed 13.6% 2.2% 19.1% 99.3%
Earthing reactor (Petersen coil):
fixed or switchable type
Earthing reactor (Petersen coil):
variable core type
Pictures: VATech
Caused by several recent blackouts it
has been considered internationally to
increasingly operate sub-transmission
systems (Us
170 kV) in the resonantearthed mode in order to increase
reliability of power supply. [Information
from a Cigr meeting in Frankfurt,
October 2005]
Caused by several recent blackouts it
has been considered internationally to
increasingly operate sub-transmission
systems (Us 170 kV) in the resonant
earthed mode in order to increase
reliability of power supply. [Information
from a Cigr meeting in Frankfurt,
October 2005]
-
7/30/2019 Voltage Stress in Power Systems -
13/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 13 -
Temporary Overvoltages Earth Faults
Active part of a high-voltage reactor with variable core
Fixed part of the core
Drive
Lead screw (the core is actually in 100% position)
coremove
ment
-
7/30/2019 Voltage Stress in Power Systems -
14/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 14 -
Temporary Overvoltages Earth Faults
Earth fault in case of isolated neutral system:
according to [BAL-04]
-
7/30/2019 Voltage Stress in Power Systems -
15/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 15 -
Temporary Overvoltages Earth Faults
Earth fault in case of isolated neutral system:
faultaccording to [BAL-04]
-
7/30/2019 Voltage Stress in Power Systems -
16/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 16 -
Temporary Overvoltages Earth Faults
Earth fault in case of isolated neutral system:
fault clearing
k= 2 due to capacitances of zero sequence system, charged to a direct voltage
according to [BAL-04]
-
7/30/2019 Voltage Stress in Power Systems -
17/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 17 -
Temporary Overvoltages Earth Faults
Intermitting earth fault in case of isolated neutral system:new fault after initial fault clearing
voltage offaulty phaseaccording to [BAL-04]
-
7/30/2019 Voltage Stress in Power Systems -
18/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 18 -
Temporary Overvoltages Earth Faults
Intermitting earth fault in case of isolated neutral system:new fault after initial fault clearing
voltage ofsound phaseaccording to [BAL-04]
-
7/30/2019 Voltage Stress in Power Systems -
19/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 19 -
Temporary Overvoltages Earth Faults
Intermitting earth fault in case of isolated neutral system:
voltage of the zero sequence systemaccording to [BAL-04]
-
7/30/2019 Voltage Stress in Power Systems -
20/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 20 -
Temporary Overvoltages Earth Faults
3 ... 2k
1.4k
1.4 1.8k<
-
7/30/2019 Voltage Stress in Power Systems -
21/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 21 -
Temporary Overvoltages Load Rejection (Example 1)
Example according to [ETG-93]
Increase in generator
voltage of 120%
voltage increase on high-
voltage side of generator
transformer:from 380 kV 460 kV
for 1.4 s duration!
Increase in generator
voltage of 120%
voltage increase on high-
voltage side of generator
transformer:from 380 kV 460 kV
for 1.4 s duration!
Increase in frequency
leads to repeated phase
oppositions at the open
circuit breaker for several
minutes, see next slide
Increase in frequency
leads to repeated phase
oppositions at the open
circuit breaker for several
minutes, see next slide
-
7/30/2019 Voltage Stress in Power Systems -
22/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 22 -
Temporary Overvoltages Load Rejection (Example 1)
Example according to [ETG-93]
Phase opposition between open circuit breaker terminals stress of longitudinal insulationPhase opposition between open circuit breaker terminals stress of longitudinal insulation
-
7/30/2019 Voltage Stress in Power Systems -
23/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 23 -
Temporary Overvoltages Load Rejection (Example 2)
Example according to [DOR-81]
1: Excitation by rotating rectifiers
2: Constant excitation (manual regulation)
Voltage increase by factor of 1.35;
decrease to factor of 1.2 after 2 s.
Voltage increase by factor of 1.35;
decrease to factor of 1.2 after 2 s.
-
7/30/2019 Voltage Stress in Power Systems -
24/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 24 -
Temporary Overvoltages Load Rejection (Example 3)
TOV at the end of a long transmission lineTOV at the end of a long transmission line
caused by capacitive currents
can be controlled by parallel compensation
e
1cos
aU
U
=
Ue ... voltage at end of lineUa ... voltage at line entrance
1
1
av
=1 ... phase angle of the positive system
1
1 1
1v
L C
=
v1 ... phase velocity of the positive system
[DOR-81]
Not an issue for "normal"
length transmission lines
Not an issue for "normal"
length transmission lines
-
7/30/2019 Voltage Stress in Power Systems -
25/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 25 -
Temporary Overvoltages Load Rejection (Summary)
Voltage increase factors due to load rejection:
moderately extended systems: < 1.2 p.u. for up to several minutes
widely extended systems: 1.5 p.u. for some seconds
close to turbo generator: 1.3 p.u.
close to salient pole (German: "Schenkelpol") generator: 1.5 p.u.
Voltage increase factors due to load rejection:
moderately extended systems: < 1.2 p.u. for up to several minutes
widely extended systems: 1.5 p.u. for some seconds
close to turbo generator: 1.3 p.u.
close to salient pole (German: "Schenkelpol") generator: 1.5 p.u.
Temporary overvoltages caused by load rejection depend on the rejected load
the system layout after disconnection
the characteristics of the sources (short-circuit power, generator type and regulation)
Extremes:
Low values of temporary overvoltages in systems with relatively short lines and highvalues of the short-circuit power at the terminal stations.
High values of temporary overvoltages in systems with long lines and low values of short-circuit power at the generating side (= typical situation of extra-high voltage systems intheir initial stage).
-
7/30/2019 Voltage Stress in Power Systems -
26/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 26 -
Temporary Overvoltages Resonance Phenomena
Temporary overvoltages caused by resonance phenomena generally arise when circuitswith large capacitive elements, such as
lines
cables
series compensated linesand inductive elements having non-linear magnetizing characteristics, such as
transformers
shunt reactors
are energized, or as result of load rejections.
Can easily be avoided by de-tuning the system from the resonance frequency!Can easily be avoided by de-tuning the system from the resonance frequency!
-
7/30/2019 Voltage Stress in Power Systems -
27/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 27 -
Temporary Overvoltages Resonance Phenomena (Example 1)
Energizing a transformer in a grid tuned to resonance at 3rd harmonics (150 Hz)Energizing a transformer in a grid tuned to resonance at 3rd harmonics (150 Hz)
Grid tuned to 150 Hz TOV of 1.9 p.u. Grid tuned to (150 Hz 7%) TOV of 1.2 p.u.
[DOR-81]
-
7/30/2019 Voltage Stress in Power Systems -
28/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 28 -
Temporary Overvoltages Resonance Phenomena (Example 2)
Load rejection with transformer in a grid tuned to resonance at 5th harmonics (250 Hz)Load rejection with transformer in a grid tuned to resonance at 5th harmonics (250 Hz) [DOR-81]
length of line: a
Length of line: 174 km fr= 250 Hz5th harmonics 33% TOV = 1.7 p.u.
Length of line: 116 km fr= 300 Hz5th harmonics 10% TOV = 1. p.u.
-
7/30/2019 Voltage Stress in Power Systems -
29/29
Fachgebiet
HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 29 -
Temporary Overvoltages and Surge Arresters
Surge arresters cannot limit TOV!Exception: resonance effects may be suppressed or even avoided by MO arresters.
Care has then to be taken not to thermally overload the arresters!
Surge arresters cannot limit TOV!Exception: resonance effects may be suppressed or even avoided by MO arresters.
Care has then to be taken not to thermally overload the arresters!
0,8
0,85
0,9
0,95
1
1,05
1,1
1,15
1,2
1,25
1,3
0,1 1 10 100 1000
t / s
ktov=
U/Ur
Time duration of (over-)voltage
Possible voltages without arresters
Voltages limited by arresters
Withstand voltage of equipment
Lightning overvoltages
(Microseconds)
Switching overvoltages
(Milliseconds)
Temporary overvoltages
(Seconds)
Highest voltage of equipment
(Continuously)
Magnitudeo
f(over-)voltage
/p.u.
1
2
3
4
0
5
Time duration of (over-)voltage
Possible voltages without arresters
Voltages limited by arresters
Withstand voltage of equipment
Lightning overvoltages
(Microseconds)
Switching overvoltages
(Milliseconds)
Temporary overvoltages
(Seconds)
Highest voltage of equipment
(Continuously)
Magnitudeo
f(over-)voltage
/p.u.
1
2
3
4
0
5
region of impressed voltage current develops according to
U-I-characteristics
region of impressed voltage current develops according toU-I-characteristics
region of impressed current
voltage develops according toU-I-characteristics
region of impressed current
voltage develops according toU-I-characteristics