voltage dips characterization at wind projects

Upload: supernaenergy

Post on 14-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Voltage Dips Characterization at Wind projects

    1/6

    Characterization of Measured Voltage Dips in Wind

    Farms in the Light of the New Grid Codes

    Emilio Gomez-Lazaro and Miguel CanasRenewable Energy Research Institute

    Dept. of Electrical, Electronic

    and Control Eng. EPSA

    Universidad de Castilla-La Mancha

    02071 Albacete (SPAIN)

    Email: [email protected], [email protected]

    Juan Alvaro Fuentes and Angel Molina-GarcaDept. of Electrical Eng.

    Universidad Politecnica de Cartagena

    30202 Cartagena (SPAIN)

    Email: [email protected], [email protected]

    Abstract Voltage dips are a major concern for some transmis-sion system operators. With increasing wind farm penetration inpower systems, many national grid codes are imposing require-ments for uninterrupted generation throughout power systemdisturbances.

    The aim of this paper is to present the results of measuredvoltage dips using two power quality analyzers installed formonths in a Spanish wind farm. From the measured voltagewaveforms, voltage dips are characterized by extracting dip typeand characteristics.

    I. INTRODUCTION

    Voltage dips are short duration reductions in rms voltage

    (between 10% and 90%) of the voltage at a point in the

    electrical system, which lasts for half a cycle to 1 min, [1]. The

    duration of voltage dips is described as the total time interval

    between the point on wave of sag initiation and recovery,

    [2]. They are caused by faults in the electric supply system

    and the starting of large loads, such as motors. Voltage dipsare generally considered a power quality problem of equal

    importance as long and short interruptions in the supply. The

    interests in voltage dips are increasing because they cause

    the detrimental effects on several sensitive equipments such

    as adjustable-speed drives, process-control equipments, and

    computers. Such equipments can be tripped when the voltage

    drops below 90% of the rated voltage for longer than a

    few cycles, [3], [4]. In accordance with the practice in wind

    farms, wind turbines are disconnected from the grid when the

    terminal voltage fell below 80-90%, [5], [6]. Even relays and

    contactors in motor starters can be sensitive to voltage dips,

    resulting in shutdown of a process when they drop out, [7].

    Voltage dips are mainly due to short-circuits and earthfaults in the grid, [8]. These faults in the power system, even

    far away from the location of the wind farm, or any other

    power installation, can generate a voltage dip at the connection

    point of the wind turbines. Factors governing the magnitude

    and duration of voltage dips include the fault impedance and

    location, the configuration of the power network, and the

    system protective relay design and operation, [7]. This last

    aspect is important since voltage dip condition lasts until the

    fault is cleared by a protective device. Solutions to the voltage

    dip effects must be implemented in the customer facility, since

    although it is possible for the utility to reduce the number of

    faults through design practices and specific equipment, it is

    impossible to avoid faults on the power system, [7]. Therefore,

    in wind farms, the solution must be installed at the wind farminterconnection point with the electrical grid or at the wind

    turbine level.

    The installed capacity of wind power generation has grown

    very fast in the past years, increasing dramatically the level of

    wind power generation into existing utilities network. On the

    other hand, the rating of large wind farms reaches rating of

    conventional generating units and this development has carried

    out to requirements of how to connect wind farms to the grid.

    Until now, these grid codes specified by the transmission

    system operators mainly dealed with how a wind farm

    should operate in steady state while requirements recently

    imposed in some countries dealed with how a wind installation

    response to grid faults must be addressed, [9]. These arecommonly referred to as the fault ride-through specifications.

    Specifically, national grid codes are requiring uninterrupted

    generation throughout power system disturbances supporting

    the network voltage and frequency, and therefore, extending

    characteristics such as low voltage ride through, or reactive and

    active power capabilities, [9], [10]. In [9][13] grid connection

    requirements in Spain, Denmark, Germany, Ireland, Sweden

    and Scotland are studied. When the wind power penetration

    level is high, the protective disconnection of a large amount of

    wind power is an unacceptable consequence that may threaten

    the power system stability. This is due to conventional power

    plants will be not be able to support the voltage and the

    frequency of the grid during and immediately following thegrid failure.

    In Spanish case, REE the transmission system operator

    Red Electrica de Espana grid code, recently approved, spec-

    ifies that the wind farm must support voltage dips, at the point

    of interconnection with the transmission network, without

    tripping. The voltage-time curve that limits the magnitude

    and duration of the voltage dips, produced by single-phase-to-

    ground, two-phase-to-ground and three-phase short-circuits, is

    shown in figure 1. For non-earthed two-phase short-circuits,

  • 7/29/2019 Voltage Dips Characterization at Wind projects

    2/6

    Voltage(pu)

    1

    0.2

    0.5 1 Time (sec.)

    Beginning of

    perturbation

    0.8 0.95 pu

    0 15

    Fault clearance

    Duration

    of fault

    Fig. 1. Voltage-time curve that the generation facility must support

    the voltage limit is chosen at 0.6 p.u. instead of 0.2 p.u.

    I I . VOLTAGE DIP CHARACTERIZATION

    Voltage-dip characterization concerns the quantification of

    voltage-dip events through a limited number of parameters,

    [14]. Most methods for voltage dip characterization use two

    parameters to quantify the severity of a voltage dip

    magnitude (or remaining voltage) and duration, [3], [15]

    [17]. However, voltage dips can be far more complicated than

    this type of characterization can show:

    Usually, methods are based on the lowest remaining

    voltage and the longest duration of all the three voltages.

    This causes some problems. For example, a voltage drop

    in one phase is not distinguished from other in three

    phases, or voltage dips due to an earth fault in a high-

    impedance grounded network will be seen as equallysevere or even more severe than the dip due to a

    short-circuit fault, [15]. Therefore, it is an appropriate

    approximation for balanced dips, whereas the majority

    of dips are unbalanced, [16].

    Dip depth and phase-angle jump information can be

    required along with start and end times, [15].

    Therefore, some authors are researching other methods

    to characterize unbalanced dips, being based on measure-

    ments or applying the basic circuit theory in the faults,

    [14].

    It is usually assumed that the voltage profile during

    voltage dip is rectangular, failing in the characterization

    of non-rectangular dip, overestimating it, [3], [14]. Thiscan be important to many industrial customers with large

    induction motor loads or in the case or wind farms.

    This methodology is not adequate to multistage voltage

    dips events, in which the fault can evolve to a different

    type.

    Basically, the input data to the characterization methods can

    be fitted in:

    Monitoring the lowest remaining voltage and the longest

    duration of all the three voltages.

    Monitoring all the voltages waveforms with an adequate

    sample rate.

    Monitoring of

    V2d + V2q in a vector controller, [4].

    This method is derived from space vector control usually

    employed in the control of induction machinery. The

    three-phase voltages are converted into one phasor with

    two orthogonal components and synchronous reference

    frame, which is locked via a phase-locked loop PLLIn [15] two methods to obtain three-phase voltage dip char-

    acterization ABC classification and symmetrical com-

    ponents classification were exposed and compared. It is

    concluded that ABC classification due to its simplicity is

    more used than the symmetrical components, being also more

    intuitive and giving a good approximation about the evolution

    of the dips along the different voltage levels of the network.

    The ABC classification should not be viewed as a different

    classification, since it can be considered as a special case

    of the symmetrical components classification. However, this

    classification is based on a simplified model of the network,

    being not recommended in [15] for the classification of voltage

    dips obtained from measured instantaneous voltages. ABCclassification considers seven types of voltage dips, by defining

    complex voltages and phasor diagrams.

    In [18], theoretical relations between the minimum phase-

    to-neutral voltage VPN and the minimum phase-to-phase

    voltage VPP are presented for the seven types of dips,

    defined in [15]:

    Type A: all phases experience the same retained voltage

    and phase-angle jump.

    VPP = VPN (1)

    Type B: It is not common because it is seen only when

    a line to ground fault occurs at the same voltage level orat a location connected by star-star transformer grounded

    at both sides.

    VPP =

    1

    2+ VPN

    2+ 3

    43

    (2)

    Type C: It is a reduction of the voltage in two phases. It

    is caused by a line to line fault or by a propagation of

    dip type B through a delta-star connected transformer.

    V2

    PP =4

    3V

    2

    PN1

    3(3)

    Type D: It is caused by a propagation of a type C dip

    through a delta-star windings connected transformer. It is

    a voltage drop in one phase.

    V2

    PP =1

    4+

    3

    4V

    2

    PN (4)

    Type E: It shows a symmetrical relation between PP and

    PN voltage like type A. This dip is rare as type B by the

    same reasons.

    Type F: It is a reduction of the voltage in one phase,

    caused by the propagation of a line to line to ground

  • 7/29/2019 Voltage Dips Characterization at Wind projects

    3/6

    Transformer

    690/20 kV

    Power converter

    Crowbar

    Dfig

    Transformer

    20kV/66 kV

    Power quality analyzer Power quality analyzer

    Wifi RouterWifi Router

    GPRS Ethernet

    Modem

    GPRS Network

    Internet

    GPS Time

    Synchronization

    Fig. 2. Power quality analyzer installation scheme

    fault through a delta-star connected transformer.

    3V2

    PP = (2 +1

    3 )V2

    PN +1

    3VPN +

    1

    3 (5)

    Type G: These dips are obtained from the propagation of

    a dip type F through a delta-star connected transformer.

    VPP = 0.0707 +

    3.112 V2PN 0.3271.556

    (6)

    In this classification, voltage dip types D and F C and

    G, are similar, making difficult their distinction from the

    measurements without knowing the fault types that caused

    them, [19].

    III. RESULTS

    Two power quality analyzers fulfilling IEC 61000-4-30class A accuracy, frequency synchronization, and absolute time

    requirements have been installed in a Spanish wind farm.

    These analyzers, with a 10MHz sample rate, are useful to

    capture detailed voltage and current waveforms during the

    voltage dip and the clearance of the fault, together with

    powerful trigger options to obtain the entire transient. Figure

    2 presents the power quality analyzer installation scheme,

    showing a power quality analyzer connected in the nacelle

    Gamesa G90 2,0 MW between the doubly fed induction

  • 7/29/2019 Voltage Dips Characterization at Wind projects

    4/6

    generator and the 690/20.000V power transformer. This power

    quality analyzer measures three stator voltages and currents,

    together with a rotor line current and the DC bus voltage in

    the rotor power converter. The other power quality analyzer

    measures line voltages and currents at the wind farm electrical

    substation.

    Both power quality analyzers are linked via wifi to a

    UMTS/GPRS modem, allowing the remote accessing to the

    power quality analyzer configuration and their recorded data.

    Figures 3 and 4 show the three-phase voltage waveforms,

    the amplitude and the angle of the voltage space vector,

    [9], of two measured voltage dips. The voltage space vector

    is a complex magnitude obtained by combining the three-

    phase instantaneous voltages va, vb and vc, representing

    therefore the voltage dip uniquely through an instantaneous

    complex vector, V(t). Once this complex voltage is given,the three instantaneous phase voltages can be obtained by the

    projection of V(t) along the three axis: ej0, ej2

    3 and ej2

    3 .

    These two voltage dips together with others measured for

    months in a Spanish wind farm have been characterized

    according to the methodology explained in section II, [18].The characteristics of voltage dips at these equipment ter-

    minals vary according to the transformer winding connections

    where they are located. So, in general, the difference in voltage

    dips performance magnitude and phase angle is a result

    of the propagation of voltage dips from the fault location

    to the terminals of wind farms and wind turbines, taking

    into account the transformers and the lines located between

    these two electrical points, [19]. In [2] the importance of the

    winding transformer connections have been deeply studied,

    summarizing that the Yd transformer winding connection has

    the strongest influence, reducing the number of severe voltage

    sags and increasing the number of medium voltage sags. On

    the other hand, the Yd1, Yd11, or Yd5 transformers maintainthe voltage dip magnitude, but the associated phase shifts are

    completely different from each other.

    Therefore, transformer winding connections in the substa-

    tion and wind turbines must be taken into account, being usual

    a Dy11 transformer in the wind turbine 690/20000 V

    and Yd11 transformer in the wind farm electrical substation

    20/66 kV, as it is shown in the figure 2.

    Figure 5 shows the classification of measured voltage dip

    according to the characterization established in [18]. It can

    be seen that voltage dips are undoubtedly classified. More-

    over, real data measured results are not over the theoretical

    curves on the contrary of simulation based results but

    in any way very near to them. This is due to factors suchas fault impedance neglected in the theoretical curves and

    simulations and load effects.

    On the other hand, this characterization and classification

    method presents some disadvantages such as, obviously it is

    not adequate to multistage voltage dips, in which the fault

    and therefore, the voltage dip itself evolves to a different

    type. Moreover, during the evolution in time of the fault, the

    voltage dip can not be correctly characterized, since it is based

    on the theoretical relationship between the minimum phase-to-

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

    1.5

    1

    0.5

    0

    0.5

    1

    1.5

    Time (s)

    Vo

    ltage(pu)

    (a) Voltage waveforms

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

    0.75

    0.8

    0.85

    0.9

    0.95

    1

    1.05

    1.1

    Time (s)

    Voltage(pu)

    (b) Space vector voltage (amplitude)

    0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5200

    150

    100

    50

    0

    50

    100

    150

    200Voltage space vector angle

    Time [s]

    Angle[Deg]

    (c) Space vector voltage (angle)

    Fig. 3. Example of voltage dip measured

  • 7/29/2019 Voltage Dips Characterization at Wind projects

    5/6

    0 0.5 1 1.5

    1.5

    1

    0.5

    0

    0.5

    1

    1.5

    Time (s)

    Voltage[(pu)

    (a) Voltage waveforms

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

    0.88

    0.9

    0.92

    0.94

    0.96

    0.98

    1

    1.02

    1.04

    1.06

    Time (s)

    Voltage(pu)

    (b) Space vector voltage (amplitude)

    0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3

    200

    150

    100

    50

    0

    50

    100

    150

    200

    Time (s)

    Angle(deg)

    (c) Space vector voltage (angle)

    Fig. 4. Example of voltage dip

    neutral voltage and the minimum phase-to-phase voltage. In

    the application of this method to measured voltage dips, as

    the presented here, other considerations must be taken into

    account, as the selected point reflects the voltage dip type.

    So, minimum density of measured data around zones must be

    established, and only these zones accessed for consideration in

    the classification of dips. Finally, as it was commented above,

    it is usually assumed that the voltage profile during voltage dip

    is rectangular, failing in the characterization of non-rectangular

    dip, overestimating it.

    IV. CONCLUSIONS

    Voltage dips are a major concern in wind energy indus-

    try, due to the imposition by some national grid codes of

    requiring uninterrupted generation throughout power system

    disturbances, such as the voltage dips.

    Two power quality analyzers have been installed in a wind

    farm, being the first one located inside a multi-megawatt wind

    turbine, and the second one in the wind farm substation.

    Voltage dip records from instantaneous voltages measured

    using the power quality trigger abilities have been char-acterized taking into account their waveforms along the dip.

    Basically, the presented method previously applied by its

    authors to simulated voltage dips obtains a value for each

    voltage dip according to the relationship between the minimum

    phase-to-neutral and the minimum phase-to-phase voltages,

    being classified according to the distance of that point to six

    theoretical curves.

    Disadvantages of the used method have also been high-

    lighted, such as being this point representative of the voltage

    dip without taking into account measurement errors, for

    example or the errors in the characterization of multistage

    voltage dips.

    ACKNOWLEDGMENT

    The financial support provided by the Ministerio de

    Educacion y Ciencia ENE2006-15422-C02-01/ALT and

    ENE2006-15422-C02-02/ALT is gratefully acknowledged.

    The authors also would like to thank to Mr. Juan Manuel

    Abellan from Dea y Energas Renovables, the Moralejo

    wind farm people located in Alpera, Albacete (Spain) and

    Gamesa technicians for their support in the measurements.

    REFERENCES

    [1] Recommended practices and requirements for harmonic control inelectrical power systems, IEEE Standard 519-1992.

    [2] M. T. Aung and J. V. Milanovic, The influence of transformer winding

    connections on the propagation of voltage sags, IEEE Transactions onPower Delivery, vol. 21, no. 1, pp. 262269, January 2006.

    [3] D. J. Won, S. J. Ahn, and S. I. Moon, A modified sag characteriza-tion using voltage tolerance curve for power quality diagnosis, IEEETransactions on Power Delivery, vol. 20, no. 4, pp. 26382643, October2005.

    [4] C. Fitzer, M. Barnes, and P. Green, Voltage sag detection technique for adynamic voltage restorer, IEEE Transactions on Industry Applications,vol. 40, no. 1, pp. 203212, January/February 2004.

    [5] I. Erlich and U. Bachmann, Grid code requirements concerning con-nection and operation of wind turbines in germany, in IEEE Power

    Engineering Society General Meeting, San Francisco, California, June2005.

  • 7/29/2019 Voltage Dips Characterization at Wind projects

    6/6

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.90

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    PN voltage (pu)

    PP

    voltage(pu)

    A,E

    B

    C

    D

    F

    G

    Fig. 5. Relation between phase-to-phase and phase-to-neutral measured dip magnitudes

    [6] A. Dahlgren, C. Klippel, and A. Juntti, Recorded fault ride through

    capability for two types of wind turbine generators, in Nordic windpower conference, Espoo, Finland, May 2006.

    [7] M. F. McGranaghan, D. R. Mueller, and M. J. Samotyj, Voltage sags inindustrial systems, IEEE Transactions on Industry Applications, vol. 29,no. 2, pp. 391403, 1993.

    [8] M. H. J. Bollen, G. Olguin, and M. Martins, Voltage dips at theterminals of wind power installations, Wind Energy, vol. 8, pp. 307318, 2005.

    [9] E. Gomez, J. A. Fuentes, A. Molina, F. Ruz, and F. Jimenez, Resultsusing different reactive power definitions for wind turbines submittedto voltage dips: Application to the spanish grid code, in 2006 IEEEPower Systems Conference and Expo, October-November 2006.

    [10] E. Gomez, J. Fuentes, A. Molina, F. Ruz, and F. Jimenez, Field testsof wind turbines submitted to real voltage dips under the new spanishgrid code requirements, Wind Energy, 2007, accepted for publication.

    [11] C. Jauch, J. Matevosyan, T. Ackermann, and S. Bolik, Internationalcomparison of requirements for connection of wind turbines to power

    systems, Wind Energy, vol. 8, pp. 295306, 2005.[12] C. Jauch, P. Sorensen, and B. Bak-Jensen, International review of

    grid connection requirements for wind turbines, in Nordic wind powerconference, Goteborg, March 2004.

    [13] J. Matevosyan, T. Ackermann, S. Bolik, and L. Sder, Comparison ofinternational regulations for connection of wind turbines to the network,in Nordic wind power conference, Goteborg, March 2004.

    [14] M. H. J. Bollen, Algorithms for characterizing measured three-phaseunbalanced voltage dips, IEEE Transactions on Power Delivery, vol. 18,no. 3, pp. 937944, July 2003.

    [15] M. H. J. Bollen and L. D. Zhang, Different methods for classificationof three-phase unbalanced voltage dips due to faults, Electric PowerSystems Research, vol. 66, pp. 5969, 2003.

    [16] L. Zhang and M. H. J. Bollen, Characteristic of voltage dips (sags) in

    power systems, IEEE Transactions on Power Delivery, vol. 15, no. 2,pp. 827832, April 2000.

    [17] R. Leborgne and D. Karlsson, Phasor based voltagge sag monitoringand characterisation, in International Conference on Electricity Distri-bution, June 2005.

    [18] R. Leborgne, G. Olguin, and M. H. J. Bollen, The influence of pq-monitor connection on voltage dip measurements, in IEE MedPowerConference, 2004.

    [19] S. Z. Djokic, J. V. Milanovic, D. J. Chapman, and M. F. McGranaghan,Shortfalls of existing methods for classification and presentation of volt-age reduction events, IEEE Transactions on Power Delivery, vol. 20,no. 2, April 2005.