voltage dips characterization at wind projects
TRANSCRIPT
-
7/29/2019 Voltage Dips Characterization at Wind projects
1/6
Characterization of Measured Voltage Dips in Wind
Farms in the Light of the New Grid Codes
Emilio Gomez-Lazaro and Miguel CanasRenewable Energy Research Institute
Dept. of Electrical, Electronic
and Control Eng. EPSA
Universidad de Castilla-La Mancha
02071 Albacete (SPAIN)
Email: [email protected], [email protected]
Juan Alvaro Fuentes and Angel Molina-GarcaDept. of Electrical Eng.
Universidad Politecnica de Cartagena
30202 Cartagena (SPAIN)
Email: [email protected], [email protected]
Abstract Voltage dips are a major concern for some transmis-sion system operators. With increasing wind farm penetration inpower systems, many national grid codes are imposing require-ments for uninterrupted generation throughout power systemdisturbances.
The aim of this paper is to present the results of measuredvoltage dips using two power quality analyzers installed formonths in a Spanish wind farm. From the measured voltagewaveforms, voltage dips are characterized by extracting dip typeand characteristics.
I. INTRODUCTION
Voltage dips are short duration reductions in rms voltage
(between 10% and 90%) of the voltage at a point in the
electrical system, which lasts for half a cycle to 1 min, [1]. The
duration of voltage dips is described as the total time interval
between the point on wave of sag initiation and recovery,
[2]. They are caused by faults in the electric supply system
and the starting of large loads, such as motors. Voltage dipsare generally considered a power quality problem of equal
importance as long and short interruptions in the supply. The
interests in voltage dips are increasing because they cause
the detrimental effects on several sensitive equipments such
as adjustable-speed drives, process-control equipments, and
computers. Such equipments can be tripped when the voltage
drops below 90% of the rated voltage for longer than a
few cycles, [3], [4]. In accordance with the practice in wind
farms, wind turbines are disconnected from the grid when the
terminal voltage fell below 80-90%, [5], [6]. Even relays and
contactors in motor starters can be sensitive to voltage dips,
resulting in shutdown of a process when they drop out, [7].
Voltage dips are mainly due to short-circuits and earthfaults in the grid, [8]. These faults in the power system, even
far away from the location of the wind farm, or any other
power installation, can generate a voltage dip at the connection
point of the wind turbines. Factors governing the magnitude
and duration of voltage dips include the fault impedance and
location, the configuration of the power network, and the
system protective relay design and operation, [7]. This last
aspect is important since voltage dip condition lasts until the
fault is cleared by a protective device. Solutions to the voltage
dip effects must be implemented in the customer facility, since
although it is possible for the utility to reduce the number of
faults through design practices and specific equipment, it is
impossible to avoid faults on the power system, [7]. Therefore,
in wind farms, the solution must be installed at the wind farminterconnection point with the electrical grid or at the wind
turbine level.
The installed capacity of wind power generation has grown
very fast in the past years, increasing dramatically the level of
wind power generation into existing utilities network. On the
other hand, the rating of large wind farms reaches rating of
conventional generating units and this development has carried
out to requirements of how to connect wind farms to the grid.
Until now, these grid codes specified by the transmission
system operators mainly dealed with how a wind farm
should operate in steady state while requirements recently
imposed in some countries dealed with how a wind installation
response to grid faults must be addressed, [9]. These arecommonly referred to as the fault ride-through specifications.
Specifically, national grid codes are requiring uninterrupted
generation throughout power system disturbances supporting
the network voltage and frequency, and therefore, extending
characteristics such as low voltage ride through, or reactive and
active power capabilities, [9], [10]. In [9][13] grid connection
requirements in Spain, Denmark, Germany, Ireland, Sweden
and Scotland are studied. When the wind power penetration
level is high, the protective disconnection of a large amount of
wind power is an unacceptable consequence that may threaten
the power system stability. This is due to conventional power
plants will be not be able to support the voltage and the
frequency of the grid during and immediately following thegrid failure.
In Spanish case, REE the transmission system operator
Red Electrica de Espana grid code, recently approved, spec-
ifies that the wind farm must support voltage dips, at the point
of interconnection with the transmission network, without
tripping. The voltage-time curve that limits the magnitude
and duration of the voltage dips, produced by single-phase-to-
ground, two-phase-to-ground and three-phase short-circuits, is
shown in figure 1. For non-earthed two-phase short-circuits,
-
7/29/2019 Voltage Dips Characterization at Wind projects
2/6
Voltage(pu)
1
0.2
0.5 1 Time (sec.)
Beginning of
perturbation
0.8 0.95 pu
0 15
Fault clearance
Duration
of fault
Fig. 1. Voltage-time curve that the generation facility must support
the voltage limit is chosen at 0.6 p.u. instead of 0.2 p.u.
I I . VOLTAGE DIP CHARACTERIZATION
Voltage-dip characterization concerns the quantification of
voltage-dip events through a limited number of parameters,
[14]. Most methods for voltage dip characterization use two
parameters to quantify the severity of a voltage dip
magnitude (or remaining voltage) and duration, [3], [15]
[17]. However, voltage dips can be far more complicated than
this type of characterization can show:
Usually, methods are based on the lowest remaining
voltage and the longest duration of all the three voltages.
This causes some problems. For example, a voltage drop
in one phase is not distinguished from other in three
phases, or voltage dips due to an earth fault in a high-
impedance grounded network will be seen as equallysevere or even more severe than the dip due to a
short-circuit fault, [15]. Therefore, it is an appropriate
approximation for balanced dips, whereas the majority
of dips are unbalanced, [16].
Dip depth and phase-angle jump information can be
required along with start and end times, [15].
Therefore, some authors are researching other methods
to characterize unbalanced dips, being based on measure-
ments or applying the basic circuit theory in the faults,
[14].
It is usually assumed that the voltage profile during
voltage dip is rectangular, failing in the characterization
of non-rectangular dip, overestimating it, [3], [14]. Thiscan be important to many industrial customers with large
induction motor loads or in the case or wind farms.
This methodology is not adequate to multistage voltage
dips events, in which the fault can evolve to a different
type.
Basically, the input data to the characterization methods can
be fitted in:
Monitoring the lowest remaining voltage and the longest
duration of all the three voltages.
Monitoring all the voltages waveforms with an adequate
sample rate.
Monitoring of
V2d + V2q in a vector controller, [4].
This method is derived from space vector control usually
employed in the control of induction machinery. The
three-phase voltages are converted into one phasor with
two orthogonal components and synchronous reference
frame, which is locked via a phase-locked loop PLLIn [15] two methods to obtain three-phase voltage dip char-
acterization ABC classification and symmetrical com-
ponents classification were exposed and compared. It is
concluded that ABC classification due to its simplicity is
more used than the symmetrical components, being also more
intuitive and giving a good approximation about the evolution
of the dips along the different voltage levels of the network.
The ABC classification should not be viewed as a different
classification, since it can be considered as a special case
of the symmetrical components classification. However, this
classification is based on a simplified model of the network,
being not recommended in [15] for the classification of voltage
dips obtained from measured instantaneous voltages. ABCclassification considers seven types of voltage dips, by defining
complex voltages and phasor diagrams.
In [18], theoretical relations between the minimum phase-
to-neutral voltage VPN and the minimum phase-to-phase
voltage VPP are presented for the seven types of dips,
defined in [15]:
Type A: all phases experience the same retained voltage
and phase-angle jump.
VPP = VPN (1)
Type B: It is not common because it is seen only when
a line to ground fault occurs at the same voltage level orat a location connected by star-star transformer grounded
at both sides.
VPP =
1
2+ VPN
2+ 3
43
(2)
Type C: It is a reduction of the voltage in two phases. It
is caused by a line to line fault or by a propagation of
dip type B through a delta-star connected transformer.
V2
PP =4
3V
2
PN1
3(3)
Type D: It is caused by a propagation of a type C dip
through a delta-star windings connected transformer. It is
a voltage drop in one phase.
V2
PP =1
4+
3
4V
2
PN (4)
Type E: It shows a symmetrical relation between PP and
PN voltage like type A. This dip is rare as type B by the
same reasons.
Type F: It is a reduction of the voltage in one phase,
caused by the propagation of a line to line to ground
-
7/29/2019 Voltage Dips Characterization at Wind projects
3/6
Transformer
690/20 kV
Power converter
Crowbar
Dfig
Transformer
20kV/66 kV
Power quality analyzer Power quality analyzer
Wifi RouterWifi Router
GPRS Ethernet
Modem
GPRS Network
Internet
GPS Time
Synchronization
Fig. 2. Power quality analyzer installation scheme
fault through a delta-star connected transformer.
3V2
PP = (2 +1
3 )V2
PN +1
3VPN +
1
3 (5)
Type G: These dips are obtained from the propagation of
a dip type F through a delta-star connected transformer.
VPP = 0.0707 +
3.112 V2PN 0.3271.556
(6)
In this classification, voltage dip types D and F C and
G, are similar, making difficult their distinction from the
measurements without knowing the fault types that caused
them, [19].
III. RESULTS
Two power quality analyzers fulfilling IEC 61000-4-30class A accuracy, frequency synchronization, and absolute time
requirements have been installed in a Spanish wind farm.
These analyzers, with a 10MHz sample rate, are useful to
capture detailed voltage and current waveforms during the
voltage dip and the clearance of the fault, together with
powerful trigger options to obtain the entire transient. Figure
2 presents the power quality analyzer installation scheme,
showing a power quality analyzer connected in the nacelle
Gamesa G90 2,0 MW between the doubly fed induction
-
7/29/2019 Voltage Dips Characterization at Wind projects
4/6
generator and the 690/20.000V power transformer. This power
quality analyzer measures three stator voltages and currents,
together with a rotor line current and the DC bus voltage in
the rotor power converter. The other power quality analyzer
measures line voltages and currents at the wind farm electrical
substation.
Both power quality analyzers are linked via wifi to a
UMTS/GPRS modem, allowing the remote accessing to the
power quality analyzer configuration and their recorded data.
Figures 3 and 4 show the three-phase voltage waveforms,
the amplitude and the angle of the voltage space vector,
[9], of two measured voltage dips. The voltage space vector
is a complex magnitude obtained by combining the three-
phase instantaneous voltages va, vb and vc, representing
therefore the voltage dip uniquely through an instantaneous
complex vector, V(t). Once this complex voltage is given,the three instantaneous phase voltages can be obtained by the
projection of V(t) along the three axis: ej0, ej2
3 and ej2
3 .
These two voltage dips together with others measured for
months in a Spanish wind farm have been characterized
according to the methodology explained in section II, [18].The characteristics of voltage dips at these equipment ter-
minals vary according to the transformer winding connections
where they are located. So, in general, the difference in voltage
dips performance magnitude and phase angle is a result
of the propagation of voltage dips from the fault location
to the terminals of wind farms and wind turbines, taking
into account the transformers and the lines located between
these two electrical points, [19]. In [2] the importance of the
winding transformer connections have been deeply studied,
summarizing that the Yd transformer winding connection has
the strongest influence, reducing the number of severe voltage
sags and increasing the number of medium voltage sags. On
the other hand, the Yd1, Yd11, or Yd5 transformers maintainthe voltage dip magnitude, but the associated phase shifts are
completely different from each other.
Therefore, transformer winding connections in the substa-
tion and wind turbines must be taken into account, being usual
a Dy11 transformer in the wind turbine 690/20000 V
and Yd11 transformer in the wind farm electrical substation
20/66 kV, as it is shown in the figure 2.
Figure 5 shows the classification of measured voltage dip
according to the characterization established in [18]. It can
be seen that voltage dips are undoubtedly classified. More-
over, real data measured results are not over the theoretical
curves on the contrary of simulation based results but
in any way very near to them. This is due to factors suchas fault impedance neglected in the theoretical curves and
simulations and load effects.
On the other hand, this characterization and classification
method presents some disadvantages such as, obviously it is
not adequate to multistage voltage dips, in which the fault
and therefore, the voltage dip itself evolves to a different
type. Moreover, during the evolution in time of the fault, the
voltage dip can not be correctly characterized, since it is based
on the theoretical relationship between the minimum phase-to-
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1.5
1
0.5
0
0.5
1
1.5
Time (s)
Vo
ltage(pu)
(a) Voltage waveforms
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0.75
0.8
0.85
0.9
0.95
1
1.05
1.1
Time (s)
Voltage(pu)
(b) Space vector voltage (amplitude)
0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5200
150
100
50
0
50
100
150
200Voltage space vector angle
Time [s]
Angle[Deg]
(c) Space vector voltage (angle)
Fig. 3. Example of voltage dip measured
-
7/29/2019 Voltage Dips Characterization at Wind projects
5/6
0 0.5 1 1.5
1.5
1
0.5
0
0.5
1
1.5
Time (s)
Voltage[(pu)
(a) Voltage waveforms
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0.88
0.9
0.92
0.94
0.96
0.98
1
1.02
1.04
1.06
Time (s)
Voltage(pu)
(b) Space vector voltage (amplitude)
0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3
200
150
100
50
0
50
100
150
200
Time (s)
Angle(deg)
(c) Space vector voltage (angle)
Fig. 4. Example of voltage dip
neutral voltage and the minimum phase-to-phase voltage. In
the application of this method to measured voltage dips, as
the presented here, other considerations must be taken into
account, as the selected point reflects the voltage dip type.
So, minimum density of measured data around zones must be
established, and only these zones accessed for consideration in
the classification of dips. Finally, as it was commented above,
it is usually assumed that the voltage profile during voltage dip
is rectangular, failing in the characterization of non-rectangular
dip, overestimating it.
IV. CONCLUSIONS
Voltage dips are a major concern in wind energy indus-
try, due to the imposition by some national grid codes of
requiring uninterrupted generation throughout power system
disturbances, such as the voltage dips.
Two power quality analyzers have been installed in a wind
farm, being the first one located inside a multi-megawatt wind
turbine, and the second one in the wind farm substation.
Voltage dip records from instantaneous voltages measured
using the power quality trigger abilities have been char-acterized taking into account their waveforms along the dip.
Basically, the presented method previously applied by its
authors to simulated voltage dips obtains a value for each
voltage dip according to the relationship between the minimum
phase-to-neutral and the minimum phase-to-phase voltages,
being classified according to the distance of that point to six
theoretical curves.
Disadvantages of the used method have also been high-
lighted, such as being this point representative of the voltage
dip without taking into account measurement errors, for
example or the errors in the characterization of multistage
voltage dips.
ACKNOWLEDGMENT
The financial support provided by the Ministerio de
Educacion y Ciencia ENE2006-15422-C02-01/ALT and
ENE2006-15422-C02-02/ALT is gratefully acknowledged.
The authors also would like to thank to Mr. Juan Manuel
Abellan from Dea y Energas Renovables, the Moralejo
wind farm people located in Alpera, Albacete (Spain) and
Gamesa technicians for their support in the measurements.
REFERENCES
[1] Recommended practices and requirements for harmonic control inelectrical power systems, IEEE Standard 519-1992.
[2] M. T. Aung and J. V. Milanovic, The influence of transformer winding
connections on the propagation of voltage sags, IEEE Transactions onPower Delivery, vol. 21, no. 1, pp. 262269, January 2006.
[3] D. J. Won, S. J. Ahn, and S. I. Moon, A modified sag characteriza-tion using voltage tolerance curve for power quality diagnosis, IEEETransactions on Power Delivery, vol. 20, no. 4, pp. 26382643, October2005.
[4] C. Fitzer, M. Barnes, and P. Green, Voltage sag detection technique for adynamic voltage restorer, IEEE Transactions on Industry Applications,vol. 40, no. 1, pp. 203212, January/February 2004.
[5] I. Erlich and U. Bachmann, Grid code requirements concerning con-nection and operation of wind turbines in germany, in IEEE Power
Engineering Society General Meeting, San Francisco, California, June2005.
-
7/29/2019 Voltage Dips Characterization at Wind projects
6/6
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.90
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
PN voltage (pu)
PP
voltage(pu)
A,E
B
C
D
F
G
Fig. 5. Relation between phase-to-phase and phase-to-neutral measured dip magnitudes
[6] A. Dahlgren, C. Klippel, and A. Juntti, Recorded fault ride through
capability for two types of wind turbine generators, in Nordic windpower conference, Espoo, Finland, May 2006.
[7] M. F. McGranaghan, D. R. Mueller, and M. J. Samotyj, Voltage sags inindustrial systems, IEEE Transactions on Industry Applications, vol. 29,no. 2, pp. 391403, 1993.
[8] M. H. J. Bollen, G. Olguin, and M. Martins, Voltage dips at theterminals of wind power installations, Wind Energy, vol. 8, pp. 307318, 2005.
[9] E. Gomez, J. A. Fuentes, A. Molina, F. Ruz, and F. Jimenez, Resultsusing different reactive power definitions for wind turbines submittedto voltage dips: Application to the spanish grid code, in 2006 IEEEPower Systems Conference and Expo, October-November 2006.
[10] E. Gomez, J. Fuentes, A. Molina, F. Ruz, and F. Jimenez, Field testsof wind turbines submitted to real voltage dips under the new spanishgrid code requirements, Wind Energy, 2007, accepted for publication.
[11] C. Jauch, J. Matevosyan, T. Ackermann, and S. Bolik, Internationalcomparison of requirements for connection of wind turbines to power
systems, Wind Energy, vol. 8, pp. 295306, 2005.[12] C. Jauch, P. Sorensen, and B. Bak-Jensen, International review of
grid connection requirements for wind turbines, in Nordic wind powerconference, Goteborg, March 2004.
[13] J. Matevosyan, T. Ackermann, S. Bolik, and L. Sder, Comparison ofinternational regulations for connection of wind turbines to the network,in Nordic wind power conference, Goteborg, March 2004.
[14] M. H. J. Bollen, Algorithms for characterizing measured three-phaseunbalanced voltage dips, IEEE Transactions on Power Delivery, vol. 18,no. 3, pp. 937944, July 2003.
[15] M. H. J. Bollen and L. D. Zhang, Different methods for classificationof three-phase unbalanced voltage dips due to faults, Electric PowerSystems Research, vol. 66, pp. 5969, 2003.
[16] L. Zhang and M. H. J. Bollen, Characteristic of voltage dips (sags) in
power systems, IEEE Transactions on Power Delivery, vol. 15, no. 2,pp. 827832, April 2000.
[17] R. Leborgne and D. Karlsson, Phasor based voltagge sag monitoringand characterisation, in International Conference on Electricity Distri-bution, June 2005.
[18] R. Leborgne, G. Olguin, and M. H. J. Bollen, The influence of pq-monitor connection on voltage dip measurements, in IEE MedPowerConference, 2004.
[19] S. Z. Djokic, J. V. Milanovic, D. J. Chapman, and M. F. McGranaghan,Shortfalls of existing methods for classification and presentation of volt-age reduction events, IEEE Transactions on Power Delivery, vol. 20,no. 2, April 2005.