voltage control technologies

Upload: adeniji-olusegun

Post on 03-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Voltage Control Technologies

    1/12

    POWER ENGINEERING JOURNAL JUNE 2000 129

    Power flow management

    Innovative power flowmanagement and voltagecontrol technologies

    Power flow control concepts

    Power flows can be influenced bycontrolling the basic electrical

    parameters, namely impedance of the

    transmission line and system voltages,

    as shown in eqn. 1:

    PS = Re US

    QS = Im US(1)

    wherePS = active power across the transmission line

    QS = reactive power at the sending end

    US = sending end voltage

    UR = receiving end voltage

    Xl = impedance of the transmission line

    To be able to control the flows of active power

    P and/or reactive power Q, one or several of

    these parameters can be controlled by power

    equipment already available or under

    development. The control of the basic electrical

    parameters can be achieved using a shunt

    control device, series control device, shunt

    current injection device, series voltage

    injection device or a combination of these.

    In this article the following model

    assumptions are used:

    4 lossless transmission lines

    4 sending and receiving ends are stiff nodes and

    their voltages are equal in magnitude

    4 performance characteristics are drawn for

    midpoint location of control devices.

    Shunt control device

    The impact on power flow due to a capacitive

    shunt device with a reactance ofXC can be

    investigated using the transmission model,

    vector diagram and mathematical relationsshown in Fig. 1. Shunt devices basically impact

    the voltage at the point of connection. When

    connected to weak nodes in the power system,

    for example in the midpoint or in the receiving

    end of a long transmission line, the power flow

    can be influenced substantially by the change of

    voltage due to the shunt device.

    Series control device

    The voltage in series with the line can be

    created by the natural voltage drop caused by

    the line current across an impedance element

    with a capacitive reactance ofXC. The insertion

    of a series compensation device in a

    transmission line directly impacts the power

    Driven by ever increasing energy demands, environmental constraints, deregulation

    and privatisation of the power supply industry, existing transmission systems are

    often operated and stressed to the limit and occasionally beyond the performance

    capability of their original design in order to maximise asset utilisation. To ensurethat under these conditions the economical, reliable and secure operation of the

    grid is maintained, the need for various aspects of power flow management within

    the power systems is becoming increasingly evident.

    by E. Wirth and A. Kara

    US URjXl

    *

    US URjXl

    *

  • 7/28/2019 Voltage Control Technologies

    2/12

    130 POWER ENGINEERING JOURNAL JUNE 2000

    1 Transmission-line

    model, power flow

    equations and vector

    diagram of the system

    with a shunt controldevice

    2 Transmission-line

    model, power flow

    equations and vector

    diagram of the system

    with a series control

    device

    flow on the line. The influence of a capacitive

    element providing the series voltage can be

    investigated using the equations shown in

    Fig. 2.

    Shunt current injection device

    Power flow control devices can utilise the

    physical principles described above, or

    depending on their construction and operating

    mode, can be based on the concepts of

    controllable shunt current injection and

    controllable series voltage injection. The

    concept of a device based on shunt current

    injection can be demonstrated using the system

    shown in Fig. 3. Ii is the controllable shunt

    current injected to the midpoint of the

    transmission system.

    Series voltage injection device

    As mentioned already, the series voltage can be

    provided by a controlled voltage source. The

    series voltage device can be constructed such

    that the injected voltages magnitude UTand/or

    phase angle can be varied. The impact onpower flow can be investigated by using the

    transmission model, vector diagram and

    equations shown in Fig. 4.

    Impact of power flow control and reactive

    power compensation devices on system

    performance

    By employing devices that can control the basic

    electrical parameters, power system

    performance can be significantly improved.

    One of the major aims of improving a

    transmission systems performance is to

    increase its power transfer capability. By usingthe concepts discussed above, it is possible to

    quantify the impact that shunt and series

    control devices have on power transfer

    Power flow management

    Um

    IcXc

    *

    US

    PS = Re US

    US URUm

    2Xc

    Xl1 UR

    UR

    Xl/2 Xl/2 IR

    IRIS

    Ic

    IS

    ( ( jXl 4XcXl(1 )*

    QS = Im US

    US

    2Xc

    Xl1 UR( (US

    jXl 4Xc

    Xl(1 )

    Um1

    *

    Um2US

    PS = Re US

    US URUm2 Um1

    UR

    XcXl/2 Xl/2 I

    I

    I

    US URj(Xl Xc)*

    QS = Im US US URj(Xl Xc)

  • 7/28/2019 Voltage Control Technologies

    3/12

    POWER ENGINEERING JOURNAL JUNE 2000 131

    capability and reactive power requirements in

    transmission systems. The reactive power

    balance is one of the many requirements that

    enforces a practical limit on how much activepower P can be transferred over a system. Series

    devices providing a specific amount of

    compensation in general enable more active

    power to be transferred with less sending end

    reactive power supply requirements as

    compared with a shunt device. Capacitive

    series devices increase the transfer capability

    (their reactive power output increases also with

    line loading) and, in addition to increasing the

    stability limit, the voltage regulation

    capabilities of the system are significantly

    improved.

    Shunt compensation and control devices

    improving voltage maintenance and power

    transfer capability through reactive current

    supply

    Shunt devices help maintain the system voltage

    when transferred power is varied. Shuntreactors are used to compensate for the reactive

    power surplus in case of reduced power transfer

    or open transmission lines. In case of long

    transmission lines, some of the shunt reactors

    are permanently connected to the system to

    give maximum security against overvoltages in

    the event of sudden load rejection or opening of

    lines. The conventional shunt capacitor

    compensation provides the most economical

    reactive power source for voltage control in

    cases when additional voltage support is

    required.Conventional shunt control devices and

    modern shunt current injection devices, e.g.

    the STATCOM, can also control the power flow

    Power flow management

    3 Transmission-line

    model, power flowequations and vector

    diagram of the system

    with a shunt current

    injection device

    4 Transmission-line

    model, power flow

    equations and vector

    diagram of the system

    with a series voltage

    injection device. The

    equations are based on

    the concept with active

    powerPT drawn from

    the network andreactive powerQTgenerated locally,

    shown in Fig. 6.

    Um1 Um2US

    Um1= UR +jX2IR UT

    Um1*

    UR

    UTjX1IS

    US

    jX2IR

    Um2

    Um1

    UR

    X1 X2 IRIS UT

    US = Um1 +jX1 IR + Re(UTIR*)

    Um1*IS = IR +

    PS = Re (US IS*)

    QS = Im (US IS*)

    Re(UTIR*)

    Um

    *

    US

    PS = Re US

    UR

    IR

    Ii

    IS

    US UR IijXl 2*

    QS = Im US US UR IijXl 2

    Xl/2 Xl/2

    US URUm

    IS IR

    Ii

  • 7/28/2019 Voltage Control Technologies

    4/12

    through a transmission system in a limited

    range by supplying or absorbing reactive

    current at the point of connection to the

    system.

    Series voltage injection devices improving

    flexibility and enhancing system performance

    In the case of the series voltage injection

    devices, further system performance

    improvement can be achieved by providing

    greater operational flexibility in addition to

    increasing power transfer capability. There are

    basically two ways of generating this series

    voltage. One way is to draw all the active power

    PT and reactive power QT requirements needed

    to generate this voltage from the network, as

    shown in Fig. 5. The other way is to draw only

    the active power from the network and provide

    the reactive power required locally as in Fig. 6.

    The power flow control capabilities of

    devices capable of coupling a series voltage

    with a variable phase angle are shown in

    Fig. 7. The impact on power flow control of theformer concept is shown by the green curve and

    of the latter by the purple one. Both the curves

    are for series voltages of 20% of the nominal

    sending end system voltage and a transmission

    angle of 60 between the receiving andsending end voltages. As the phase angle ofthe series injected voltage is varied between 0

    and 360, the active power flowing through the

    transmission system can theoretically be

    controlled for a range from a maximum

    through to minimum values. From Fig. 7, it can

    also be seen that the locally provided reactive

    power concept has a bigger impact on power

    flow control compared with obtaining reactive

    power from the network.

    Fig. 8 shows the improvement and the limits

    (0 and 180) in power transfercapability with the different series voltage

    injection concepts, for an injected voltage

    magnitude of 20% of nominal system voltage,

    over a range of transmission angles . Thepurple band shows the operating capability of

    the series voltage injection device with locally

    supplied reactive power QT whilst the green

    meshed band is due to a device drawing activeand reactive power from the power system. The

    bands indicate the control ranges of devices for

    varying between 0 and 180.

    132 POWER ENGINEERING JOURNAL JUNE 2000

    Power flow management

    7 Achievable

    transmitted active

    power for the different

    series voltage injection

    concepts and a

    transmission angle of 60

    8 Impact on power

    transfer capability using

    different series voltage

    injection concepts for

    transmission angles between 0 and 90

    UT

    PS

    QS

    PT,QT

    PT,QT

    1600

    1200

    800

    PS,MW

    400

    0 30

    , deg

    60 90

    PTfrom network, QTlocal generated

    PT, QTfrom network

    no control

    180

    0

    1600

    1200

    800

    PS,MW

    400

    0 90

    PTfrom network, QTlocal generated

    180

    , deg

    270 360

    PT, QTfrom network

    UT

    PS

    QS

    PT

    QT

    5 Series voltage injection with Pand Q

    from network

    6 Series voltage injection with Ptaken

    from network, Qgenerated locally

  • 7/28/2019 Voltage Control Technologies

    5/12

    POWER ENGINEERING JOURNAL JUNE 2000 133

    Solutions to transmission system concerns

    using power flow control technologies

    Finding the most cost-effective solution to the

    various issues limiting transmission

    performance is attracting ever growing interest

    as utilities deregulate and a competitive

    electrical supply environment is becoming a

    norm rather than an exception. Power flow

    control technologies can provide the key to

    these solutions. An overview of the

    transmission issues and the possible effective

    solutions are summarised in Table 1. These

    solutions include both conventional as well as

    innovative technologies, though they are by no

    means exhaustive. In must be noted that, due to

    the wide range of network configurations and

    Power flow management

    9 (a) TCSC system and

    (b) its performance

    characteristics

    PSXC

    a

    US UR

    X1 X2

    thermal line overload issues tripping of parallel circuit

    voltage and low voltage at heavy load

    reactive power high voltage at light load control issues voltage deviation following outage

    power flow parallel line load sharing issues post-fault sharing

    power flow control

    dynamic and lack synchronising torque stability issues dynamic flow control

    and transient stabilitypower oscillations voltage stability

    BSC

    BSR

    TCSC

    ASC

    SVC

    STATCOM

    TCPAR

    QBT

    IPC

    UPFC

    BDV = breaker switched capacitor

    BSC = breaker switched reactor

    IPC = interphase power controller

    QBT = quadrature boosting transformer

    STATCOM = static synchronous compensator

    SVC = static VAr compensator

    TCPAR = thyristor-controlled phase-angle regulator

    TCSC = thyristor-controlled series capacitor

    UPFC = unified power flow controller

    12

    10

    08

    06

    04

    02

    0

    200 40 60 80, deg

    b

    PS,pu

    100 120 140

    Xcmax compensation

    Xcmincompensation

    no compensation

    160 180

    ASC = advanced series compensator

    Table 1 Overview of transmission system limitations and possible solutions using control devices

  • 7/28/2019 Voltage Control Technologies

    6/12

    system operation procedures, proper corrective

    actions to deal with various issues are of

    necessity application dependent.2

    In steady-state conditions the total power

    flow on all lines that connect two power

    systems is determined by unbalance betweenpower production and load demand including

    losses in the individual systems. On the other

    hand, during transients the power flow control

    equipment can also have an impact on the total

    power exchange between the systems. Power

    flow control technologies and equipment can

    thus be generally categorised according to their

    ability to solve steady-state or dynamic problem

    domains.

    Thermal issues are generally related to

    thermal limits caused by a change in the

    network configuration during outages and can

    be overcome by rearranging the network or byadding a power flow control equipment.

    Voltage and reactive power control issues are

    related to voltage constraints in the power

    system. Low voltage at heavy load can be a

    limiting factor under steady-state conditions.

    The corrective actions include correcting the

    power factor and compensating the reactive

    losses in lines by supplying reactive power.

    High voltage at light load is an undesirableoccurrence in the transmission and distribution

    systems and may be diminished using

    mechanically switched shunt capacitors or

    reactors to supplement the action of

    tapchangers. Low voltage as well as high

    voltage following outages can exceed the

    voltage limits so that corrective actions have to

    be taken to avoid further equipment damage.

    Power flow issues are generally related to

    controlling the active power in the power

    system for better utilisation of the transmission

    assets, minimisation of losses, limit flows to

    contract paths, post contingency strategies etc.Dynamic and stability issues are related to

    dynamic performance of the power system.

    Transient stability describes the ability of the

    134 POWER ENGINEERING JOURNAL JUNE 2000

    Power flow management

    PS

    US UR

    X1

    UT X2

    a

    10 (a) ASC system,

    (b) its steady-state

    operating and

    (c) performance

    characteristics

    inductive capacitive UT, pu

    I, pu

    b

    16

    14

    12

    10

    08

    06

    04

    02

    0

    0

    PS,pu

    02

    20 40 60 80

    , deg

    c

    UT= 05 pucapacitive compensation

    UT= 0no compensation

    UT= 05 puinductive compensation

    100 120 140 160 18004

  • 7/28/2019 Voltage Control Technologies

    7/12

    POWER ENGINEERING JOURNAL JUNE 2000 135

    Power flow management

    11 (a) SVC system,(b) its steady-state

    operating and

    (c) performance

    characteristics

    power system to survive the first few seconds

    after a major disturbance and can be improved

    by extracting energy from the sending end of

    the network, supplying energy to the receivingsystem respectively by increasing the

    synchronising power between sending and

    receiving ends. Power system oscillation

    describes sustained or growing power swing

    oscillations (generally in range below 1.5 Hz)

    between generators or group of generators,

    initiated by a disturbance (fault, major load

    changes etc.). Solutions to this problem lie in

    the use of equipment that permits dynamic

    damping of these oscillations. Voltage stability

    problem is a slow process caused by progressive

    increase in load and can be improved by voltage

    support, e.g. by using reserve devices, co-

    ordinating system load tapchangers, automatic

    undervoltage load shedding or generator

    control action.

    Power flow control devices and their

    performance characteristics

    As Table 1 shows, solutions to the transmission

    issues can be addressed by various power flowcontrol devices. Their application and

    suitability to solve a particular problem depend

    on many factors covering technical as well as

    economical considerations. This section

    provides brief descriptions of the technical

    capability, technology and performance of each

    of the devices listed in Table 1, allowing a first

    estimate of device suitability for an intended

    application.

    Breaker switched capacitor and reactor (BSC,

    BSR)

    Shunt-connected equipment of these types

    allow the reactive power to be supplied via

    capacitor banks or absorbed via reactor banks

    and thus have significant influence on the

    PS

    a

    US UR

    X1 X2

    inductivecapacitive

    Ush, pu

    Ish, pu

    b

    12

    10

    08

    06

    04

    02

    0200 40 60 80

    , deg

    c

    PS,pu

    100 120 140

    SVC on capacitive limit

    no control

    SVC on inductive limit

    160 180

  • 7/28/2019 Voltage Control Technologies

    8/12

    136 POWER ENGINEERING JOURNAL JUNE 2000

    Power flow management

    voltage at the point of connection. Series-

    connected equipment allow the impedance

    characteristics of the transmission system

    where they are installed to be varied and thushave direct impact on the power transfer

    capability. These devices can be permanently

    connected to a system or are connected through

    circuit breakers. Breaker switched devices offer

    greater operational flexibility in terms of

    allowing the operators to adapt to changing

    reactive power requirements of their power

    systems. Their performance is limited by their

    step-wise control characteristics.

    Thyristor-controlled series capacitor (TCSC)

    The thyristor-controlled series capacitor system

    is shown in Fig. 9 together with its performance

    characteristics. The variation of capacitance

    can be achieved by varying the thyristor-

    controlled reactance that is connected in

    parallel to the capacitor. The reactance is

    determined by the thyristor valve firing angle.

    The controllable parameter influencing the

    power flow is the capacitance of the TCSC.

    Advanced series compensator (ASC)

    In contrast to the TCSC where the reactive

    power is produced or consumed by capacitors

    and reactors, advanced series compensators usepower electronics elements with turn-off

    capability such as integrated gate commutated

    thyristors (IGCT). By proper repetitive

    switching of the IGCTs, the phases of the

    system are connected and/or disconnected

    causing reactive power to flow among them.

    The main difference from the TCSC is that the

    injected series voltage UT of the ASC does not

    depend on line current. The controllable

    parameter here is the series injected voltage and

    is coupled in general to the power system via a

    booster transformer. Fig. 10 shows an ASCsystem with its corresponding performance

    characteristics.

    Static VAr compensator (SVC)

    An SVC consists of a combination of fixed

    capacitors, thyristor-switched capacitors and

    thyristor-controlled reactors connected in

    parallel with the power system in most cases via

    a step-up transformer. The maximum SVC

    reactive currents are dependent on SVC

    terminal voltage. The reactive power produced

    or consumed by an SVC is generated or

    absorbed by passive reactive components. The

    controllable parameter in this equipment is the

    parallel capacitive or inductive susceptance.

    PS

    US UR

    X1 X2

    a

    12 (a) STATCOM system, (b) its steady-state operating and

    (c) performance characteristics

    inductivecapacitive

    Ush, pu

    Ish, pu

    b

    16

    14

    12

    10

    08

    06

    04

    02

    0

    0

    PS,pu

    02

    20 40 60

    , deg

    c

    STATCOM on capacitive limit

    no control

    STATCOM on inductive limit

    80 100 120 140 160 18004

  • 7/28/2019 Voltage Control Technologies

    9/12

    POWER ENGINEERING JOURNAL JUNE 2000 137

    Power flow management

    13 (a) TCPAR system,

    (b) its steady-state

    operating and

    (c) performance

    characteristics

    Within the SVC rating, its susceptance can be

    continuously controlled. When the SVC

    reaches its capacitive or inductive limit, it then

    acts as a parallel capacitor or reactor,

    respectively. Fig. 11 shows a SVC system, its

    steady-state operating and performance

    characteristics.

    Static synchronous compensator (STATCOM)

    By employing power electronics elements with

    turn-off capability as in the case of the ASC, the

    SVC system can be similarly improved to

    become a static synchronous compensator

    (STATCOM). The STATCOM basically consists

    of an IGCT converter and a DC circuit. The

    reactive power generation or absorption is

    performed by the system itself and in balanced

    conditions reactive elements are necessary for

    energy storage during short periods betweenpower electronic switching. From the

    STATCOM operating characteristics in Fig. 12,

    it is evident that it can supply constant reactive

    current almost over the entire range,

    independent of the terminal voltage. The

    STATCOM controllable parameter is its reactive

    current.

    Thyristor-controlled phase angle regulator

    (TCPAR)

    Phase-shifting transformers (PST) are

    transformers with complex turn ratios. The

    phase difference between the PST terminal

    voltages is achieved by connecting a boosting

    transformer in series with the transmission

    line, as shown in Fig. 13. The active and

    reactive powers that are injected into the

    transmission line must be taken from the

    network by the shunt transformer and

    redirected to the boosting transformer. If losses

    are neglected, the PST does not produce or

    consume reactive power.The thyristor-controlled phase angle

    regulator is one type of PST with equal input

    and output voltage magnitudes but with a

    PS

    UT

    a

    US URUM

    X1

    UT

    US

    UMUR

    +

    b

    10

    09

    08

    07

    06

    05

    04

    03

    01

    02

    050 0 50 100

    PS,pu

    , deg

    c

    150 200 250

    =40

    =10

    =0

  • 7/28/2019 Voltage Control Technologies

    10/12

    phase shift between these voltages. The TCPARis controlled extremely quickly by a static

    thyristor based on-load tapchanger. The

    controllable parameter of the TCPAR is the

    voltage phase shift angle . Fig. 13 shows alsothe steady-state operating and performance

    characteristics of the TCPAR.

    Quadrature booster transformer (QBT)

    The quadrature booster transformer is another

    type of PST where the phasor of the injected

    voltage is shifted by a constant angle withrespect to the input voltage vector. Various

    types of QBT enable various angles. Thecontrollable parameter of the QBT is the

    magnitude of the injected voltage UT. Fig. 14

    shows a QBT system with =90, its steady-

    state operating and performancecharacteristics.

    Interphase power controller (IPC)

    The interphase power controller is a series-

    connected device, where the major

    components in each of the phases are a reactor

    and a capacitor subjected to individually phase-

    shifted voltages provided by two phase shifting

    transformers PAR1 and PAR2. There are many

    IPC configurations, depending on specific

    application requirements and on the method

    used to implement the internal phase shifts. In

    the case where the reactor (XA) and thecapacitor (XA) form a conjugate pair, each

    terminal of the IPC will behave as a voltage-

    dependent current source and provide the IPC

    138 POWER ENGINEERING JOURNAL JUNE 2000

    Power flow management

    14 (a

    ) QBT system,(b) its steady-state

    operating and

    (c) performance

    characteristics

    PSUT

    a

    US URUM

    X1

    b

    UTUS

    UM UR

    12

    10

    08

    06

    04

    02

    00

    UT=05 UT=05

    UT=0

    PS,pu

    50

    , deg

    c

    100 150 20050

  • 7/28/2019 Voltage Control Technologies

    11/12

    POWER ENGINEERING JOURNAL JUNE 2000 139

    with the unique decoupling effect property, a

    feature that is desirable. The controllable

    parameters are the phase shift angles 1 and 2

    of PAR1 and PAR2, respectively. Fig. 15 showsan IPC system and its performance

    characteristics.

    Unified power flow controller (UPFC)

    The basic structure of the unified power flow

    controller and its performance characteristics

    are shown in Fig. 16. It consists of shunt

    (exciting) and series (boosting) transformers.

    Both of these are connected by two IGCT

    converters and a DC circuit represented by the

    capacitor. One difference between the UPFC

    and a PST is that the UPFC reactive powerinjected into the line by the series branch does

    not need to be transmitted from the parallel

    branch. It is generated by the converter

    connected to the series branch. The active

    power injected into the system by the series

    branch must be taken from the system by the

    parallel branch and transmitted to the series

    branch over the DC circuit. Additionally, the

    reactive power of the parallel branch can be

    controlled in the same manner as for the

    STATCOM. The voltage UTcan be of any phase

    with respect to the input voltage US and can

    have any magnitude ranging from 0 to UTmaxcorresponding to the dimension of the UPFC.

    The controllable UPFC parameters are phase

    and magnitude of the injected voltage UT and

    the magnitude of the parallel branch reactive

    current.

    Innovative system solutions the key to

    cost-effective power flow control

    Driven by ever increasing energy demands,

    environmental constraints, deregulation and

    privatisation of the power supply industry,

    existing transmission systems are oftenoperated and stressed to the limit of, and

    occasionally beyond, the performance

    capability of their original design. To ensure

    that under these conditions the economical,

    reliable and secure operation of the grid is

    maintained, power flow management concepts

    employing innovative technologies have been

    proposed.

    Load sharing and loss minimisation,

    regulating power flow through transmission

    corridor, transient stability enhancement and

    rapid power flow management to prevent

    overloads as well as controlling power flow

    patterns are transmission issues that are of

    concern and interest to system operators

    worldwide. Technical solutions for these

    concerns have been proposed and discussed.

    In Fig. 17 a 200MVA phase-shifting

    regulating transformer for 240kV/132kV based

    on a new compact concept is shown. The two

    booster transformers for in-phase control and

    quadrature control, normally connected in

    series with the main transformer, are replaced

    by only few extra windings inside the main

    transformer tank. This considerably reduces

    not only the investment costs but also the

    operating costs. The main saving is in the

    transformer cores and the copper windings.

    Another key benefit is the significantly smaller

    space that is required.

    Utilities share many of the common energy

    transmission problems yet have differenttechnical, economical and environmental

    requirements. In order that their needs are

    individually met, and cost-effective solutions

    Power flow management

    15 (a) IPC system and

    (b) its performance

    characteristics

    PS

    URUS

    X1

    PAR 1

    a

    XA

    XA

    PAR 2

    1

    2

    12

    10

    08

    06

    04

    02

    090 0

    , deg

    PS,pu

    XIPCX1

    90

    XIPC =XA

    1 + 22 sin2

    IPC =1 + 2

    2

    b

  • 7/28/2019 Voltage Control Technologies

    12/12

    are provided, the key lies in the application of

    innovative power flow control technologies.

    Co-operation between the power industry

    partners can develop optimised solutions

    capable of meeting the performance

    requirements demanded in the new and

    evolving electrical utility environment.

    References

    1 DUNLOP, R. D., GUTMAN, R., AND MARCHENKO,

    R. P.: Analytical development of loadability

    characteristics for EHV and UHV transmission lines,

    IEEE Trans., March/April 1979, PAS-98, pp.606617

    2 CIGRE TF 38-01-06: Load flow control in high

    voltage power systems using FACTS controllers,

    CIGRE, January 1996

    3 WIRTH, E., and RAVOT, J. -F.: Regulating

    transformers in power systems new concepts and

    applicationsABB Review, 4/1997

    4 JAUCH, T., KARA, A., KIEBOOM, G., and WIRTH,

    E.: Operational aspects and benefits of interphase

    power controllers with conventional or electronically

    switched phase shifting devices a robust FACTS

    application, CIGRE-Session, Paris, August 1998

    5 LINDER, S. et al.: A new range of reverse conducting

    gate-commutated thyristors for high-voltage

    medium-power applications, Proceedings of the 7th

    European Conference on Power Electronics and

    Applications, Trondheim, Norway, September 1997

    IEE: 2000

    The authors are with ABB High Voltage Technologies

    Ltd., Dept. AET, PO Box 8546, CH8050, Zurich,

    Switzerland.

    140 POWER ENGINEERING JOURNAL JUNE 2000

    Power flow management

    16 (a) UPFC system

    and (b) its performance

    characteristicsPS UT

    US UR

    X1

    a

    17 200 MVA phase-

    shifting regulated

    transformer for 240

    kV/132 kV based on a

    new compact concept

    12

    10

    08

    06

    04

    02

    00

    UT=05 puP maximum

    UT=05 puP minimum

    UT=0

    PS,pu

    50

    , deg

    b

    100 150 20050