    VMAX3 Installation and

    Maintenance

    Lab Guide

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    2/34 

    Copyright 

    Copyright ©2014 EMC Corporation. All Rights Reserved. Published in the USA. EMC believes the informationin this publication is accurate as of its publication date. The information is subject to change without notice.

    THE INFORMATION IN THIS PUBLICATION IS PROVIDED “AS IS.” EMC CORPORATION MAKES NOREPRESENTATIONS OR WARRANTIES OF ANY KIND WITH RESPECT TO THE INFORMATION IN THIS

    PUBLICATION, AND SPECIFICALLY DISCLAIMS IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS

    FOR A PARTICULAR PURPOSE. 

    Use, copying, and distribution of any EMC software described in this publication requires an applicable

    software license. The trademarks, logos, and service marks (collectively "Trademarks") appearing in thispublication are the property of EMC Corporation and other parties. Nothing contained in this publicationshould be construed as granting any license or right to use any Trademark without the prior written

    permission of the party that owns the Trademark. 

    Acartus, Access Logix, AdvantEdge, AlphaStor, ApplicationXtender, ArchiveXtender, Atmos, Authentica,

    Authentic Problems, Automated Resource Manager, AutoStart, AutoSwap, AVALONidm, Avamar, Captiva,

    Catalog Solution, C-Clip, Celerra, Celerra Replicator, Centera, CenterStage, CentraStar, ClaimPack,

    ClaimsEditor, CLARiiON, ClientPak, Codebook Correlation Technology, Common Information Model,

    Configuration Intelligence, Configuresoft, Connectrix, CopyCross, CopyPoint, Dantz, DatabaseXtender, DataDomain, Direct Matrix Architecture, DiskXtender, DiskXtender 2000, Document Sciences, Documentum,

    elnput, E-Lab, EmailXaminer, EmailXtender , EMC2, EMC, EMC Centera, EMC ControlCenter, EMC LifeLine,

    EMC OnCourse, EMC Proven, EMC Snap, EMC SourceOne, EMC Storage Administrator, Enginuity, eRoom,

    Event Explorer, FarPoint, FirstPass, FLARE, FormWare, Geosynchrony, Global File Virtualization, GraphicVisualization, Greenplum, HighRoad, HomeBase, InfoMover, Infoscape, Infra, InputAccel, InputAccel

    Express, Invista, Ionix, ISIS, Max Retriever, MediaStor, MirrorView, Navisphere, NetWorker, nLayers,OnAlert, OpenScale, PixTools, Powerlink, PowerPath, PowerSnap, QuickScan, Rainfinity, RepliCare,

    RepliStor, ResourcePak, Retrospect, RSA, the RSA logo, SafeLine, SAN Advisor, SAN Copy, SAN Manager,Smarts, SnapImage, SnapSure, SnapView, SRDF, StorageScope, SupportMate, SymmAPI, SymmEnabler,

    Symmetrix, Symmetrix DMX, Symmetrix VMAX, TimeFinder, UltraFlex, UltraPoint, UltraScale, Unisphere,

    VMAX, Vblock, Viewlets, Virtual Matrix, Virtual Matrix Architecture, Virtual Provisioning, VisualSAN,VisualSRM, Voyence, VPLEX, VSAM-Assist, WebXtender, xPression, xPresso, YottaYotta

     

    Revision Date: November 2014

    Revision Number: MR-7CP-VMAX3IM

    EMC Education Service

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    3/34

     

    3

    Document Revision History

    Rev File Name  Date 

    1 VMAX3withHYPERMAX_OS_5977_Installation

    and_Maintenance_LabGuide.docx

    7/21/2014

    2 VMAX3withHYPERMAX_OS_5977_Installation

    and_Maintenance_LabGuide.docx

    8/20/2014

    3 VMAX3_Installation

    and_Maintenance_LabGuide.docx

    9/24/14

    4 VMAX3_Installation

    and_Maintenance_LabGuide.docx

    11/2014

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    4/34

     

    4

    Table of Contents

    LAB EXERCISES ........................................................................................................ 5 

    LAB 1:  SOLVE DESKTOP AND PROCEDURE GENERATOR ........................................................7 

    LAB 2:  VMAX3 COMPONENT LOCATIONS .........................................................................9 

    LAB 3: OBTAINING SERVICE LEVEL CREDENTIALS ................................................................15 

    LAB 4: IPSWITCHER TOOL .............................................................................................17 

    LAB 5:  PART 1  – PREPARE SYSTEM FOR INSTALL ...............................................................19 

    LAB 5:  PART 2  – INSTALL SYSTEM ..................................................................................21 

    LAB 6: PART 1 - SIMPLIFIED SYMMWIN ...........................................................................23 

    LAB 6: PART 2 - SIMPLIFIED SYMMWIN SIMULATOR ..........................................................27 

    LAB 7:  FIELD REPLACEABLE UNITS (FRUS).......................................................................29 

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    5/34

     

    5

    Lab Exercises

    Purpose: To identify the steps necessary to install and perform

    replacements of VMAX3 array components.

    Tasks:

    Download SolVe-Desktop

    Download Symmetrix Procedure Generator

    Locate and identify components

    Prepare for installation

    Install a VMAX3 system

    Navigate Simplified Symmwin

    Perform FRU activities 

    References: VMAX3 with HYPERMAX OS 5977 Installation and

    Maintenance courseware

    VMAX3 with HYPERMAX OS 5977 Installation and

    Maintenance Guide

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    6/34

     

    6

    This slide intentionally left blank.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    7/34

     

    7

    Lab 1: SolVe Desktop and Procedure Generator 

    Step Action

    1  Navigate to www.support.emc.com 

    In the “search” field type solve-desktop 

    3  Download SolVe-Desktop

    4  Click on VMAX Family and DMX to download

    5  Once download is complete click on VMAX Family and DMX  and click Begin 

    6  Familiarize yourself with the interface/options and when ready click Partner and

    Internal Procedures – Navigate to appropriate Procedure Generator

    http://www.support.emc.com/http://www.support.emc.com/http://www.support.emc.com/http://www.support.emc.com/

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    8/34

     

    8

    This slide intentionally left blank.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    9/34

     

    9

    Lab 2: VMAX

    3

     Component Locations 

    Step Action

    1  What type of system is displayed (circle answer)?

    Single engine Dual Engine

    Identify the components below.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    10/34

     

    10

    Step Action

    2  In System Bay 1, a KVM and a pair of Ethernet switches are present. What takes

    the place of these components in System Bays 2 through 8?

    3  In a dual engine system bay, what component does SPS 2A/2B support?

    4  What is the maximum number of DAEs that can be installed in a single engine

    system bay?

    5  What is the maximum number of engines that can be installed in a bay?

    6  How many SPS pairs are installed in System Bay 1 of a fully-populated dual

    engine configuration?

    How many SPS pairs are installed in each of System Bays 2-4 in a dual engine

    configuration?

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    11/34

     

    11

    Step Action

    7  Identify the modules marked in the engine below.

    Use the following types of Modules: Mgmt, Flash, FE, BE, SIB

    Is the engine displayed Engine 1?

    Why or why not?

    8  Label the Odd and Even directors in the engine diagram below.

    Director

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    12/34

     

    12

    Step Action

    9  Label the Power Zones (A or B) for the directors in the diagram below.

    Power Zone

    10 

    How many fans support a single director?

    11  What is the highlighted component in the DAE displayed below?

    What connects to this component?

    What type of DAE is displayed?

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    13/34

     

    13

    Step Action

    12  What is the highlighted component in the DAE below?

    What is the purpose of this component?

    What type of DAE is displayed?

    13  Identify the DAE numbers and associated engines (odd or even) below.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    14/34

     

    14

    Step Action

    14  Identify the routing location for the three different cable types (Host, System

    and Power).

    End of Lab Exercise

    Outside Rear

    Middle Rear

    Inside Rear Outside

    Middle

    Inside

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    15/34

     

    15

    Lab 3: Obtaining Service Level Credentials

    Step Action

    1  Log on to Central Manager at http://slc.emc.com/psscm/ 

    (Provide your RSA credentials when prompted)

    2  Select Credential Manager  and click Request Credential . Enter in necessary

    information to request credentials.

    Serial Number:

    Leave other fields at the default and click Create.

    End of Lab Exercise  

    http://slc.emc.com/psscm/http://slc.emc.com/psscm/http://slc.emc.com/psscm/http://slc.emc.com/psscm/

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    16/34

     

    16

    This slide intentionally left blank.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    17/34

     

    17

    Lab 4: IPSwitcher Tool

    Step Action

    1  Navigate to http://support.emc.com and download the IPSwitcher Tool

    Follow the instructions outlined in Module 3 Slide 66 of your student guide to

    establish a connection from the red Ethernet cable provided on the POS Work

    Tray.

    End of Lab Exercise  

    http://support.emc.com/http://support.emc.com/http://support.emc.com/http://support.emc.com/

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    18/34

     

    18

    This slide intentionally left blank.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    19/34

     

    19

    Lab 5: Part 1 Prepare System for Install

    Step Action

    1  Note: For lab purposes, please refer to the Installation module of this course for proper

    cable routing and port locations. For customer installations, always use the VMAX 3 with

    HYPERMAX OS 5977 Installation and Maintenance Guide.

    2  Verify DAE cabling.

    Verify the cables are attached to the correct ports of the LCCs or ICMs.

    Check for loose cables by carefully pulling on each cable to verify it is fully seated.

    3  Verify SPS Power and monitor cabling.

    Although pre-installed, cabling could have moved while the system was physically movedfrom the warehouse to the customer or lab site. Therefore, check to ensure all DAEs

    have their cables correctly plugged in, based on color coding, as dictated by the power

    zone (A or B) they supply power to.

    Power zone ‘A’ has gray cables attached to it, while power zone ‘B’ has  black cables in

    the same bay.

    Check all power cable connections to ensure cables are properly secured with their

    respective bails.

    4  Verify general cabling.

    Visually inspect all (not aforementioned) inter-bay and intra-bay communication,

    monitoring and power cables and ensure they are properly run between the various

    modules, cable tied and seated. These modules include but are not limited to; MIBE, SPS,

    Server, KVM and Ethernet switches.

    5  Ensure ALL modules are seated properly with tab pushed in.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    20/34

     

    20

    Step Action

    6  Check to ensure all PDUs (Power Distribution Units) have their cables correctly plugged

    in, based on color coding, as directed by the power zone (A or B) they supply power to.

    Power zone ‘A’ has gray cables attached to it, while power zone ‘B’ is populated withblack cables in the same bay.

    Check all PDU power cable connections to ensure cables are properly configured.

    Important: Loose cables could trigger sparks or lead to component damage.

    7  Check SPS connections and settings.

    Verify that the SPS breakers are all ON. Turn them ON

    should they be OFF.

    (refer to diagram on right)

    8  Check the power supplied to the VMAX Bays.

    Is AC connected to the PDU in each bay (if more than one)?

    Turn all PDU breakers ON if they are turned OFF. 

    (refer to diagram on right)

    End of Lab Exercise  

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    21/34

     

    21

    Lab 5: Part 2 Install System

    Step Action

    1  Log on. Follow the login instructions as outlined in SymmWin Security Login 

    section of the Installation Manual .

    Obtain a server security credential and password from Central Manager

    http://slc.emc.com/psscm (Use your NT login or password to log on to Central

    Manager). If you do not have access to Central Manager, your instructor will

    supply a default credential.

    2  Click the Simplified Symmwin button from the Gadget box

    on the right to log into Simplified Symmwin using your

    credential and password.

    Note: If the AutoLogin feature is enabled, you will be

    logged directly into either Simplified Symmwin or Symmwin

    (based on your access level). If you are logged directly into

    Simplified Symmwin, proceed to the next step. If you are

    logged into Symmwin, minimize the screen to display the

    desktop, look for the Gadget box on the right and click the

    Simplified Symmwin button to log in.

    From the Site Info Block, take note of the following:

    VMAX Model

    System Bay 1 Serial Number

    Code level

    4  From the System Management Block select Verify VMAX Setup and follow the

    instructions.

    Were there any issues present during the Cable check?

    Were there any issues during the Power Verification?

    End of Lab Exercise  

    http://slc.emc.com/psscmhttp://slc.emc.com/psscmhttp://slc.emc.com/psscm

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    22/34

     

    22

    This slide intentionally left blank.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    23/34

     

    23

    Lab 6: Part 1 - Simplified SymmWin

    Step Action

    1  Note: Actions performed in this exercise using the Engineering

    credential/password are for lab purposes only. This is not standard operating

    procedure for customer environments. 

    2  Using the credential and password provided by the instructor, log into Simplified

    SymmWin.

    What User and Role is displayed?

    3  Which View Blocks are displayed by default?

    Expand the Site Note View Block to full screen and add a note

    Simplified SymmWin Lab .

    Once complete, use the icon to return the Site Note View Block to fit on the

    screen (or minimize it to remove it from the display).

    Note: If you remove it and want to view Site Note again, simply click on the SiteNote button on the lower left of the screen.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    24/34

     

    24

    Step Action

    5  Expand the Tasks View Block to full screen. Note that Task Actions will differ

    based on User and Role. Because we are using Engineering credentials for this

    lab, we have the option to Add a FRU. This option may not be available based on

    your personal User and Role credentials.

    Note: Adding FRUs to the Tasks list is for lab purposes only, and should not be

    done in customer environments.

    Click on the Add button to add a FRU for replacement.

    Select FRU Type:  Director Power Supply

    SR Number:  12345678

    SR Reason:  Lab

    Limitations:  None

    Choose any director’s power supply. We will perform a replacement of this

    power supply later in the lab. For now, leave the task in the Tasks View Block.

    6  Log File content is saved to the local clipboard. Open notepad (Start All

    Programs Accessories Notepad) and use Ctrl-V to paste the content into

    the notepad.

    What is the name of the log file that was generated?

    What is the serial number of the component to be replaced?

    This log file should be saved and attached to the failed component upon return.

    For lab purposes, close the notepad without saving.

    7  Return the Tasks View Block to fit on the screen (or minimize to remove it from

    the screen).

    8  Open additional View Blocks to answer the following questions.

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    25/34

     

    25

    Step Action

    9  What is the Spare Service Type in this system?

    In which View Block did you locate this information?

    10  What is the MMCS Id?

    This MMCS is physically located next to which director?

    11  Which View Block provides the Health Check Script?

    Run the Health Check from the appropriate View Block. Report any issues to the

    instructor.

    12  Close Simplified SymmWin by clicking the X in the upper right corner of the

    screen. When prompted, choose “Leave this page”. 

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    26/34

     

    26

    This page intentionally left blank

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    27/34

     

    27

    Lab 6: Part 2 - Simplified SymmWin Simulator

    Step Action

    1  Note: This Desktop Simulator is for practice purposes only. The Simplified

    SymmWin Simulator is not NOT to be used in customer environments. 

    2  Navigate to SolVe Desktop and click on VMAX Family

    and DMX icon.

    3  Expand VMAX 100K, 200K, 400K  and select VMAX Family CS Document Viewer .

    (if prompted – click to allow blocked content)

    4  In the left pane, select Installing Simplified SymmWin Simulator  and follow the

    onscreen instructions.

    5  Take some time to familiarize yourself with the desktop version of Simplified

    SymmWin.

    End of Lab Exercise  

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    28/34

     

    28

    This page intentionally left blank

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    29/34

     

    29

    Lab 7: Field Replaceable Units (FRUs)

     

    Step Action

    1  Warning: Always wear ESD heel straps or an ESD wrist strap and use static

    dissipative mat for all component replacements.

    Note: Adding FRUs to the Tasks list is for lab purposes only, and should not be

    done in customer environments.

    2  Using the credential and password provided by the instructor, log into Simplified

    SymmWin.

    3  Go to the Tasks View Block.

    Select the Director Power Supply FRU replacement task created in the Simplified

    Symmwin Lab exercise.

    Select the RUN button to begin the FRU replacement script.

    4  Replace MMCS-1

    Reference step 5 on page 15 of this lab guide to add a Task to replace MMCS-1.

    Reference pages 90-116 in the student guide to access MMCS-2 in order to

    complete the replacement of MMCS-1.

    In which bay is MMCS-1?

    When replacing MMCS-1, what is the role required of MMCS-2?

    When replacing MMCS-1, what are two (2) ways of accessing MMCS-2?

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    30/34

     

    30

    Step Action

    5  Add a task and replace the following component:

     __ SPS Battery

    When you push the Li-Ion SPS battery in and the indicator is yellow; what

    position is the battery in (Off, Parked, Engaged)?

    How many SPSs are in your system?

    6  Add a task and replace the following component:

     __ DIMM Cards

    7  Add a task and replace the following component:

     __ Director Boot Drive

    Did you have to remove the director when replacing the boot drive?

    8  Add a task and replace the following component:

     __ Fiber 8Gb IO Module

    What is the slot number where this IO Module is installed?

    How many ports are on this IO Module?

    Add a task and replace the following component:

     __ SAS 6Gb IO Module

    What type of module is this (BE, FE, Flash, SIB)?

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    31/34

     

    31

    Step Action

    10  Add a task and replace the following component:

     __ Ethernet Switch

    What is cabled into port 4 of Ethernet switch A?

    What is cabled into port 4 of Ethernet switch B?

    When replacing an Ethernet switch, will communication be halted?

    Why or why not?

    11  Add a task and replace the following component:

     __ DAE LCC Card

    Which DAE did you choose?

    What director is this DAE cabled to?

    Which LCC did you choose?

    What type of DAE is this?

    Where is the LCC located in this DAE?

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    32/34

     

    32

    Step Action

    12  Depending on the type of DAE in your lab system, add a task and replace one of

    the following components:

     __ DAE ICM Card __ DAE SSC

    In which type of DAE is the ICM located?

    In which type of DAE is the SSC located?

    13  Add a task and replace the following component:

     __ Drive

    Be sure to add a drive from the appropriate DAE type for the drive replacement.

    What type of DAE is in your lab system?

    How many drives are installed in DAE 3 in your lab system?

    What is the size(s) of the drives in DAE 3?

    14  Add a task and replace the following component:

     __ MIBE (Inifiniband Fabric)

    What type of fabric is installed in your lab system?

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    33/34

     

    33

    15  Time permitting, add and perform replacements for the components listed in

    below.

     __ Director

    Which Director did you choose?

    In which engine is the chosen director located?

     __ Management Module

    Are MMs present in your lab system?

    If yes, choose one to replace. Which one did you choose?

     __ PDU

    Warning: PDU B provides power to the KVM

     __ DAE Power Supply

    Which DAE did you select?

    Which power supply did you select?

    What type of DAE is in your lab system?

     __ Director Fan

  • 8/16/2019 VMAX3 Installation and Maintenance STUDENT LabGuide

    34/34

     

     __ SIB Module

    Is there a SIB module present in each of the directors in your lab system?

    If yes, choose one to replace. Which SIB did you choose?

    Which director?

    Which engine?

    To what components are the SIB ports connected?

     __ Flash IO Module

    How many flash modules are installed in your lab system?

    What size are the flash modules?

    What are they used for?

     __ DAE Fan

     __ SFP/QSFP

     __ SPS Tray

     __ Cables (power, Ethernet, etc.)

    End of Lab Exercise