vkkw sprinklers general information ul
TRANSCRIPT
![Page 1: Vkkw Sprinklers General Information Ul](https://reader035.vdocuments.us/reader035/viewer/2022082202/55cf9d6f550346d033ad9b6f/html5/thumbnails/1.jpg)
Residential Automatic Sprinklers
Sprinklers For Replacement Use Only In Existing Sprinkler Systems:
Sprinkler Identification Numbers (SIN) C1296, C1297, C1396, C2296, C2297, C2596, C3296 and C3396.
Are intended for replacement use only in existing sprinkler systems.
Pendent and horizontal sidewall sprinklers for wet systems only with a maximum pressure of 175 psig. Models C3296, C1296, C3396, C2297,
C1396 sprinklers, decorative teflon, chrome plated, bright and brushed brass and white painted are identified by a Fluorescent Green compression
screw. The Model C2596 is a concealed decorative type sprinkler identified with a plain brass sprinkler and brass, chrome and white painted cover
plates for decorative purposes only.
VKKW.EX3385
Residential Automatic Sprinklers
Page Bottom
See General Information for Residential Automatic Sprinklers
CENTRAL SPRINKLER CO EX3385
451 N CANNON AVE
LANSDALE, PA 19446 USA
Max
Coverage
Area
Min Flow
Rate GPM/
Sprinkler
Min
Pressure
(psig)
Model
Type
Ft
Single
Sprinkler
Multiple
Sprinkler
Single
Sprinkler
Multiple
Sprinkler
K
Factor
Temp
Rating FWidth Length
C3296 16 16 30 21 32.0 15.7 5.3 155
Pendent
C3296 16 16 30 21 32.0 15.7 5.3 155
Recessed
Pendent
C3296 14 14 24 17 20.5 10.3 5.3 155
Pendent
C3296 14 14 24 17 20.5 10.3 5.3 155
Recessed
Pendent
C3296 12 12 22 16 17.2 9.1 5.3 155
Recessed
Pendent
C2296 16 16 16 12 13.8 7.8 4.3 155
Pendent
C2296 14 14 14 11.5 10.6 7.1 4.3 155
Pendent
C2296 18 18 19 16 19.5 13.8 4.3 155
Recessed
Page 1 of 5VKKW.EX3385 - Residential Automatic Sprinklers
16/01/2013http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=...
![Page 2: Vkkw Sprinklers General Information Ul](https://reader035.vdocuments.us/reader035/viewer/2022082202/55cf9d6f550346d033ad9b6f/html5/thumbnails/2.jpg)
Pendent
C2296 12 12 13 11.5 9.1 7.1 4.3 155
Concealed+
C2296 18 18 19 14 19.5 10.6 4.3 155
Pendent
C2296 14 14 14 11.5 10.6 7.1 4.3 155
Recessed
Pendent
C2296 16 16 16 12 13.8 7.8 4.3 155
Recessed
Pendent
C2297 20 20 20 16 21.6 13.8 4.3 155
Pendent
C2297 14 14 16 13.5 13.8 9.1 4.3 155
Concealed+
C2297 16 16 21 15 19.5 10.6 4.3 155
Concealed+
C2596 12 12 18 13 18.4 9.6 4.2 160
Concealed+
C2596 16 16 18 13 18.4 9.6 4.2 160
Concealed+
C2596 18 18 24 17 32.7 16.4 4.2 160
Concealed+
C2596 20 20 24 17 32.7 16.4 4.2 160
Concealed+
C2297 20 20 20 16 21.6 13.8 4.3 155
Recessed
Pendent
C2297 16 16 18 14 17.5 10.6 4.3 155
Pendent
C2297 16 16 18 14 17.5 10.6 4.3 155
Recessed
Pendent
C2297 12 12 13 11.5 9.1 7.1 4.3 155
Pendent
C2297 12 12 13 11.5 9.1 7.1 4.3 155
Recessed
Pendent
C3396 16 20 30 25 30.9 21.4 5.4 155
Horizontal
Sidewall
Page 2 of 5VKKW.EX3385 - Residential Automatic Sprinklers
16/01/2013http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=...
![Page 3: Vkkw Sprinklers General Information Ul](https://reader035.vdocuments.us/reader035/viewer/2022082202/55cf9d6f550346d033ad9b6f/html5/thumbnails/3.jpg)
C3396 16 20 30 25 30.9 21.4 5.4 155
Recessed
Horizontal
Sidewall
C3396 16 18 22 20 16.6 13.7 5.4 155
Horizontal
Sidewall
C3396 16 18 22 20 16.6 13.7 5.4 155
Recessed
Horizontal
Sidewall
C3396 12 12 20 18 13.7 11.1 5.4 155
Horizontal
Sidewall
C3396 12 12 20 18 13.7 11.1 5.4 155
Recessed
Horizontal
Sidewall
C1396 16 16 16 13 20.9 13.8 3.5 155,
Horizontal 175
Sidewall
C1396 16 18 19 18 29.5 26.4 3.5 155
Horizontal
Sidewall++
C1396 16 18 19 18 29.5 26.4 3.5 155
Recessed
Horizontal
Sidewall
C1396 16 16 16 13 20.9 13.8 3.5 155,
Recessed 175
Horizontal
Sidewall
C1396 14 14 14 12 16.0 11.8 3.5 155,
Horizontal 175
Sidewall++
C1396 14 14 14 12 16.0 11.8 3.5 155,
Recessed 175
Horizontal
Sidewall++
C1396 12 12 14 11 16.0 9.9 3.5 155,
Horizontal 175
Page 3 of 5VKKW.EX3385 - Residential Automatic Sprinklers
16/01/2013http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=...
![Page 4: Vkkw Sprinklers General Information Ul](https://reader035.vdocuments.us/reader035/viewer/2022082202/55cf9d6f550346d033ad9b6f/html5/thumbnails/4.jpg)
Sidewall++
C1396 12 12 14 11 16.0 9.9 3.5 155,
Recessed 175
Horizontal
Sidewall++
C1296, 20 20 16 16 28.4 28.4 3.0 155,
C1297 20 20 16 16 28.4 28.4 3.0 155,
Pendent and 175
Recessed
Pendent
C1296 18 18 14 13 21.8 18.8 3.0 155
Pendent and
Recessed
Pendent
C1296 16 16 11 11 13.4 13.4 3.0 155
Pendent and
Recessed
Pendent
C1297 12 12 10 8 11.1 7.1 3.0 155,
Pendent and 175
Recessed
Pendent
C1297 18 18 15 13 25.0 18.8 3.0 175
Pendent and
Recessed
Pendent
C1296 16 16 12 11 16.0 13.4 3.0 175
Pendent and
Recessed
Pendent
C1296 20 20 16 16 28.4 28.4 3.0 155,
C1297 20 20 16 16 28.4 28.4 3.0 155,
Pendent 175
Extended*
C1296, 18 18 14 13 21.8 18.8 3.0 155,
C1297 18 18 14 13 21.8 18.8 3.0 155,
Pendent 175
Extended*
C1296, 16 16 14 11 21.8 13.4 3.0 155,
C1297 16 16 14 11 21.8 13.4 3.0 155,
Pendent 175
Page 4 of 5VKKW.EX3385 - Residential Automatic Sprinklers
16/01/2013http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=...
![Page 5: Vkkw Sprinklers General Information Ul](https://reader035.vdocuments.us/reader035/viewer/2022082202/55cf9d6f550346d033ad9b6f/html5/thumbnails/5.jpg)
+Coverplate rated 135F.
++Listed for installation 4-12 in. below ceiling.
*Listed for installation at 4-8 in. below ceiling.
© 2013 UL LLC
When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment database
for additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the
data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2013 UL LLC".
Extended*
C1296, 14 14 12 9 16.0 9.0 3.0 155,
C1297 14 14 12 9 16.0 9.0 3.0 155,
Pendent 175
Extended*
C1296, 12 12 11 8 13.4 7.1 3.0 155,
C1297 12 12 11 8 13.4 7.1 3.0 155,
Pendent and 175
Extended*