viridian power station nnual environmental report · pdf fileannual environmental report 2011...
TRANSCRIPT
Annual Environmental Report 2011 - 777-01
1
VIRIDIAN POWER STATION ANNUAL ENVIRONMENTAL REPORT 2011
REPORT PERIOD – 1ST JANUARY 2011 TO 31ST DECEMBER 2011
Licence Register Number: 777-01 IPC Class 2.10 Licensee: Viridian Power Ltd Location of Activity: Huntstown Quarry,
Huntstown, Finglas, Dublin 11. Description of Activities: The production of energy in combustion plant the rated
thermal input of which is equal to or greater than 50 MW. Coordinates of Location: -632518 53.4126 RBME risk Category B2 NACE Code 3511
Annual Environmental Report 2011 - 777-01
2
TABLE OF CONTENTS
1. INTRODUCTION. . . . . . . . 3 1.1 Q, E, H&S POLICY STATEMENT. . . . 3 2. SUMMARY INFORMATION. . . . . . 4 2.1 EMISSIONS TO WATER. . . . . . 4 2.2 EMISSIONS TO ATMOSPHERE. . . . . . 4 2.3 WASTE MANAGEMENT . . . . . 5 2.4 ENERGY AND WATER CONSUMPTION. . . . . 6 2.4.1 ENERGY INPUT. . . . . . . 6 2.4.2 WATER CONSUMPTION. . . . . . 6 2.5 ENVIRONMENTAL INCIDENTS AND COMPLAINTS. . . 7 2.5.1 ENVIRONMENTAL INCIDENTS. . . . . 7 2.5.2 COMPLAINTS. . . . . . . . 8 2.5.3 MISCELLANEOUS RECORDS. . . . . . 8 APPENDICES. . . . . . . . . 9 APPENDIX 1 EMP 2011 APPENDIX 2 EMP PROPOSED 2011 APPENDIX 3 PRTR TABLES TABLE 1: PROCESS EMISSIONS TO WATER. . . . . 4
TABLE 2: EMISSIONS TO ATMOSPHERE . . . . 4
TABLE 3: ENERGY INPUT . . . . . . 6
TABLE 4: WATER CONSUMPTION. . . . . . 6
TABLE 5: SUMMARY OF COMPLAINTS. . . . . 8
Annual Environmental Report 2011 - 777-01
3
1.1
Quality, Environmental, Health & Safety Policy
Huntstown Power Station is a combined cycle power station and is situated at Huntstown
Quarry, near Finglas, Co. Dublin. Huntstown Power Station produces electricity for export to
the National Grid. The Power Station is owned by the Viridian Group and is operated and
maintained by Gensys Power Ltd., a wholly owned subsidiary of the Viridian Group.
Gensys Power Ltd. is committed to operating the Huntstown Power Station to the highest
standards of Health & Safety as detailed in the Safety, Health & Welfare at Work Act, 2005.
Huntstown Power Station is a lower tier Seveso site under the COMAH regulations and fully
committed to the safe, efficient, profitable and reliable production of electrical energy in order
to meet the long term expectations of both the customers and shareholders.
GenSys will fulfil its responsibilities towards employees, clients, partners, visitors, neighbours
and the environment by demonstrating leadership and commitment to Quality, Environmental,
Health & Safety Management Systems and complying with all relevant legislation and other
requirements. GenSys is committed to achieving continual improvement, to prevention of
pollution and meeting relevant corporate objectives by establishing local objectives that support
them. We are also committed to providing adequate resources to achieve the objectives and
aims of this policy.
At GenSys we are fully aware of the impact that our activities may have on the environment
and as a result we are committed to high standards of environmental care and to continually
improving our environmental performance in line with our IPPC licenses. The Company will
have a philosophy of integrating quality, health & safety and environmental issues into all its
activities and ensure that all business decisions are aligned with the aims of this policy.
Annual Environmental Report 2011 - 777-01
4
2.Summary Emissions 2.1 Self-Monitoring Data – Process Emissions to Water
Parameter Unit Max. Licensed
Emission per year 2009 2010
2011
Volume M3/yr 219,000 36,484 13,441 14,543.69
Suspended Solids Kg/yr 6,570 412.96 50.4 72.72
Nitrate Kg/yr n/a 95.43 20.62 19.82
BOD Kg/yr 4380 36.71 13.44 14.54
COD Kg/yr 10,950 376.26 191.12 290.87
Total Dissolved Solids Kg/yr
438,000 28,623.4 10,343.09 6215.0
Total Nitrogen Kg/yr n/a 54.26 22.48 34.97
Total Phosphorus Kg/yr 21.9 1.028 0.56 0.73
Ammonia Kg/yr 328.5 5.87 4.28 15.25
Table 1: Process Emissions to Water 2.2 Self-Monitoring Data – Emissions to Atmosphere
Table 2 – Emissions to Atmosphere *From CEMS ** Calculated under ETS
Emissions to air
Parameter Unit 2009 2010 2011
Sox Kg/yr 9,846 10,026 9,792*
Nox Kg/yr 576,622 667,532 510,568*
Co2 Kg/yr 1,043,359,000 1,039,070,000 931,269,000**
CO Kg/yr 47,245 269,248 193,656*
Annual Environmental Report 2011 - 777-01
5
2.3 Waste Management
SECTION A‐PRTR WASTE TRANSFERS TAB‐ TO BE COMPLETED BY ALL IPPC AND WASTE FACILITIES
See PRTR
SECTION B‐ WASTE ACCEPTED ONTO SITE‐TO BE COMPLETED BY ALL IPPC AND WASTE FACILITIES
1 Were any wastes accepted onto your site for recovery or disposal or treatment prior to recovery or disposal within the boundaries of your facility ?; (waste generated within your boundaries is to be captured through PRTR reporting) No
If yes please enter details in table 1 below
2
Did your site have any rejected consignments of waste in the current reporting year? If yes please give a brief explanation in the additional information No
3
Was waste accepted onto your site that was generated outside the Republic of Ireland? If yes please state the quantity in tonnes in additional information No
Annual Environmental Report 2011 - 777-01
6
2.4 ENERGY AND WATER CONSUMPTION 2.4.1 ENERGY Consumption (01/01/11 – 31/12/11)
Energy Usage
Energy Consumption
Sulphur Content Unit
2010
2011
Heavy Fuel Oil M3/yr
Light Fuel Oil 15.00% M3/yr 359.68 290.59
Natural Gas NM3/yr 477,651,084.8 429,211,655.57
Electricity MWhr 45,007 40,371
Coal Kg/yr 0 0
Table 3: Energy Input (total used on site)
2.4.2 WATER CONSUMPTION (01/01/11 – 31/12/11)
Well Water
Quantity
2008 (m3)
Quantity
2009 (m3)
Quantity
2010 (m3)
Quantity
2011 (m3)
Rate (m3/day)
Well Water
53,153
42,282.74
27,053
33,863
92.77 m3/day
Potable water
34,274 44,929 11,780 903 2.47 m3/day
Table 4: Water Consumption Summary
Annual Environmental Report 2011 - 777-01
8
2.5.2 ENVIRONMENTAL COMPLAINTS
Category
Number of Complaints
(01/1/10 – 31/12/10)
Odour 0 Noise 0 Water 0 Procedural 0 Miscellaneous 0 Total 0
Table 5: Summary of Complaints
2.5.3 MISCELLANEOUS RECORDS
Bund Testing was carried out during 2011. The results and reports are available on-site.
Annual Environmental Report 2011 - 777-01
9
APPENDIX 1
Environmental Management Programme
( 2011 – resulting from EHS Management Meetings)
Environmental Aspect: Energy and Resource Usage/Product Stewardship Objective No. 1: Minimise and reduce energy and resource usage. Relevant Legislation: Protection of the Environment Act 2003 (Commencement) Order 2004 Objective No.1 Target Action Due Date Resp. Status Minimise and reduce energy and resource usage.
1.1 Investigate options for
further
energy/resource
reduction Viridian.
a) Investigate areas for energy/resource reduction.
b) Implement energy/resource reduction measures.
c) Report on progress of energy reduction measures.
31/08/11 Kieran Adams/ Karina Ruddy
Complete
1.2 Investigate alternative
operation plan for
Auxiliary Boiler
a) Look at current operating methodology for Auxiliary Boiler (complete)
b) Identify means of reducing energy consumed by Aux. Boiler
c) Implement new operating strategy for Aux. Boiler
31/12/11 P Mervyn Complete
1.3 External lighting
energy reduction
a) Survey the external lighting in use around site and current operating policy. (Note: Due to security & safety reasons external road lighting will not be surveyed as per EHS meeting Nov 2010)
b) Investigate the feasibility of installing light sensors or other energy reduction methods
c) Install equipment d) Report on reduction
31/12/11 D Geraghty
15% Complete (1 area, Control room lighting
complete)
1.4 Auxiliary Boiler Project a) DG to test Aux Boiler to investigate how long it takes to recover from cold
b) From this test investigate whether it is advisable to leave the Aux Boiler off for long periods
31/04/11 D Geraghty
Complete
Environmental Aspect: Supply Side Activities Objective No.2: Establish the environmental and health and safety probity of suppliers and contractors
Relevant Legislation: Safety, Health and Welfare at Work Act 2005 Objective No.2 Target Action Due Date Resp. Status Establish the environmental probity of suppliers.
2.1 Develop method for control of suppliers.
(a) Continue promoting environmental awareness amongst suppliers/vendors by issuing them with environmental documentation (i.e. environmental policy). (Ongoing)
Ongoing K Ruddy Complete apart from
Ongoing Issues
2.2 Incorporate EHS
Probity into Vendor
Approval System.
(a) Develop a checksheet to be completed following site induction.
(b) Ensure all method statements, risk assessments lifting plans are all submitted and approved prior to Phase 1 & 2 Outages.
(c) Environmental and safety audit to be carried out during both outages.
Ongoing K Ruddy / K Adams
Complete for 2011
Environmental Aspect: Emissions Objective No. 3: Identification & Reduction of Fugitive Emissions Objective No.3 Target Action Due Date Resp. Status Carry out risk assessments of all chemicals onsite and ensure M.S.D.S sheets are in compliance with current legislation.
3.1 - Complete Chemical Risk Assessments for all chemicals on site
(a) Complete risk assessments for all chemicals on site. (b) Check that they are specific to the tasks used on site
i.e. pouring/mixing (c) Setup a database for these Chemical Risk assessments
allowing them to be easily accessible to staff via Viridian Website or another website.
(d) Any chemicals which are found to be a high risk look at getting a replacement which is less hazardous.
(e) Audit required to ensure all chemicals are captured (f) System required for new chemicals to ensure they are
on the database.
31/09/2011
A Moloney, Complete
3.2 – Ensure all M.S.D.S. comply with Annex II of the Reach regulations.
(a) Complete a review all MSDS on site to determine how many comply with Annex II of the REACH Regulations regarding layout of the MSDS (closed)
(b) Contact to be made with contractors / suppliers of non-compliant MSDS sheets and request made for re-issue of MSDS which comply with REACH regulations.
(c) Update chemical risk assessment data base with MSDS sheets.
01/09/11 A Moloney, Project team
Complete
Prevent glycol from entering water discharges/ release from site
3.3 Conduct Engineering study and complete corrective actions which have been identified.
(a) Conduct Engineering Study and Containment Gap Review of CCCW system
(b) Review recommendations arising from the study and action accordingly. (CCCW cooler has been replaced to reduce the risk of a leak from the system)
10/01/10 Engineering Department
, Project Team
Complete
3.4 Install monitoring system for TOC to increase the detection of fugitive emissions/glycol
(a) Investigate the feasibility of installing a TOC meter (b) Compile quotations and select most suitable product. (c) Identify mechanical/electrical installation requirements (d) Install and test TOC meter
1/04/11 Maintenance Depart, A
Moloney, K Adams
Complete
Environmental Risk Assessments Objective No. 5: PRAD – Risk Assessment Register
Relevant Legislation: Safety, Health and Welfare at Work Act 2005 Objective No.5 Target Action Due Date Resp. Status PRAD Risk Assessment Register
5.1 – Review and update PRAD (a) PRAD needs to be developed so that specific hazards and controls are included
Ongoing
K Ruddy
Ops / Maint
Complete
5.2 Review Risk Assessment and Method Statement approval process to ensure staff and contractors apply sufficient considerations in reviewing environmental risks.
(a) Define changes required to improve risk assessments Environmental consideration.
(b) External contractor to complete template to enable Environmental specialist risk assessment
(c) Template to be incorporated into PRAD, Risk assessment database
31/12/11 K Ruddy Complete
Environmental Aspect/Heath and Safety Risk: Hazardous Chemicals Objective No.4: Reduce Hazardous Chemicals Onsite Relevant Legislation: Safety, Health and Welfare at Work (Chemical Agents) Regulations 2001 and Waste Regulations Objective No.4 Target Action Due Date Resp. Status Reduce the potential impact of hazardous chemicals and waste on site.
4.1 Reduction in laboratory hazardous chemicals
(a) Any hazardous chemicals used for laboratory analysis should be assessed and if possible replaced by a less hazardous chemical.
31/03/2010
A Moloney Survey complete
4.3 Reduction in
hydrazine
(a) Hydrazine to be removed from dosing skids for safe storage in the chemical storage area (closed)
(b) Investigate the feasibility of replacing the hydrazine by a less hazardous option, possibly Carbohydrazide (ongoing)
(c) Modify dosing skids as required.
29/02/2012 A Moloney / K Ruddy
Complete -all
hydrazine remove,
dosing skid installed
Environmental Legislation: GHG Permit Objective No. 6: Gas Constituents & Air Intake filters differential pressure. Objective No.6 Target Action Due Date Resp. Status Assess the constituents of the Gas for major variations
6.1 Bord Gais Gas data results should be monitored by using graph functions.
(a) Monthly monitoring of gas data for major discretions (b) Graphing and reporting on the constituents of the gas should ensure that plant is running at maximum efficiency by highlighting irregularities in the gas burn / humming effects
Ongoing D Geraghty Open – Monthly
Graph the efficiency of the Air Filters at the Air Intake Area
6.2 In order to improve the efficiency of the unit and therefore increase the power output compared to emissions.
(a) Monthly graphing of the efficiency of the Air Filters in the Air Intake Area. If the differential pressure between the filters increases then the efficiency of the compressor could be compromised due to dirt entering in the air. This study should ensure that any issues are picked up before they have a detrimental effect.
Ongoing Production Managers
Ongoing- Monthly
Environmental Aspect: Release to water Objective No. 1: Ensure all discharges are within IPPC licence conditions. Relevant Legislation: IPPC licence
Objective No.1 Target
Action Due Date Resp. Status
1.1 Increase Monitoring On discharges a) Prepare a schedule of testing from the Quarterly list of parameters in the IPPC
licence. This is additional testing to the licence requirements.
b) Carry out testing regime, as per above, review and adjust based on results
15/06/12 Chem In Progress
1.2 Ensure all IPPC licence related water
discharge alarms are correct and
distinguished clearly
a) Review all site alarms for IPPC licence compliance
b) Identify any improvement items, make recommendations to ensure a robust
monitoring and alarm system to the D.C.S is in place.
c) Implement recommendations
31/12/12 Ops/Sys In Progress
Environmental Aspect: Hazardous Materials Objective No.2: Reduce quantity of hazardous materials and ensure they are correctly stored
Relevant Legislation: IPPC licence Target Action Due Date Resp. Status 2.1 Removal of hydrazine
(d) Hydrazine to be removed from dosing skids for safe storage in the chemical
storage area
(e) Investigate the feasibility of replacing the hydrazine by a less hazardous
option, possibly Carbohydrazide
(f) Remove hydrazine and modify dosing skids
29/02/12 Chemist Complete
2.2 Remove hazardous materials
from main stores a) Carry out an audit of the chemicals/hazardous materials in the stores
b) Segregate all chemicals/hazardous materials from the main stores. Provide a
designated area with suitable storage requirements for all store’s
chemicals/materials.
c) Update location on CMMS.
31/03/12 Project team
In Progress
2.2 Improve management and control
of Materials brought to site a) Procedure to be compiled to include further control measures for the selection and introduction of hazardous materials onsite. ENV‐016
29/02/12 Station Chemist
Complete
Environmental Aspect: Hazardous Waste Objective No. 3: Ensure all Hazardous waste is stored and disposed of in accordance with IPPC licence conditions.
Target Action Due Date Resp. Status 3.1 Ensure compliance with IPPC
licence regarding waste storage and disposal.
a) Waste contractor to be audited
b) Weekly audit of the Chemical and Waste storage area
c) 6 monthly audit to be carried out of Waste certification documents and Waste Contractors Permits.
31/07/2012 Tech Services/Operations
OPEN
Environmental Aspect: Non‐Hazardous Waste Objective No.4: Reduce Non‐Hazardous waste generated Onsite Relevant Legislation: IPPC licence Target
Action Due Date Resp. Status
4.1 Reduce quantity of non‐
hazardous waste produced
(a) Compile a detailed breakdown of hazardous waste streams onsite.
(b) Review breakdown and propose objectives for reduction of Non‐Hazardous
waste onsite.
31/03/2013 Tech Services
OPEN
4.2 Ensure compliance with IPPC
licence regarding waste storage
and disposal
(a) 6 monthly audit to be carried out of Waste certification documents and Waste Contractors Permits.
31/07/2012 Tech Services
OPEN
Environmental Aspect: Emissions to Atmosphere Objective No. 5: Ensure compliance with Air Emissions Quality Standard EN14181 Relevant Legislation: EN14181 Target Action Due Date Resp. Status 5.1 Review site compliance with EN14181
a) Review of continuous emissions monitoring system performance including data availability, calibration history, documented maintenance, reliability and reporting of emission limit value breaches;
b) Performance and reliability of air emissions abatement equipment; e.g. CEMS. Carry out an audit to ensure compliance
c) Ensure QAL 1, 2 & 3, and AST are carried out in compliance with legislation.
d) Review Previous Air Audit carried out by the EPA
31/06/12
31/06/12
Ongoing
31/04/12
ECI/Tech Services
OPEN
Environmental Aspect: Potential Land Contamination Objective No. 6: Reduce the risk of potential land contamination
Relevant Legislation: Target Action Due Date Resp. Status6.1 Ensure integrity test of
underground pipework
a) Underground pipework survey to be carried out of Foul and Surface water
lines
b) Complete any works identified in the survey.
31/06/12Tech
Services
In progress
6.2. Ensure appropriate
Environmental consideration
i.e. Risk assessments are carried
out for every task
a) Ensure staff awareness on importance of Environmental Risk assessments
b) Audit Risk assessments to ensure appropriate controls are in place to
prevent any Environmental issues.
31/07/12 Ops / Maint
In progress
Environmental Aspect: Natural Resource Consumption/Product Stewardship Objective No. 7: Minimise and reduce energy and resource usage.
Relevant Legislation: Protection of the Environment Act 2003 (Commencement) Order 2004
Target Action Due Date Resp. Status7.1 Reduce energy usage in the UCA
building
a) Investigate the feasibility of installing light sensors in the UCA buildingb) Install equipment c) Report on reduction
30/04/12 Ops / Maint
In progress
7.2. Reduce house load a) Investigate the potential of using one set of Air Compressors to supply both plants, i.e. Phase 1 Air Compressors feeding Phase 2 plant. b) Carry out the required changes, Plant Mods, to allow sharing of Air
Compressors between plants
31/06/12 Ops / Maint
In progress
7.3 Reduce water consumption a) Introduce monitoring to the potable water system b) Install continuous monitoring on the potable water system. This will ensure early detection of leaks.
31/10/12 ECI Not started
Health and Safety & Environmetnal Targets Objective No. 8: Report on all near miss and accident/incidents Relevant Legislation: Target Action Due Date Resp. Status 8.1 Near Miss and Accident/Incident Reporting
a) Ensure reports are completed for all near miss and accident/incidents b) Identify corrective actions to be carried out as a result of near miss and
accident/incidents c) Ensure corrective actions are carried out as per agreed timeline.
N/A
Ops / Maint
Ongoing
8.2 Workplace Inspections/audits a) Carry out four workplace inspections per year and one inspection per scheduled
b) Identify corrective actions to be carried out as a result of workplace inspection/audit
c) Ensure corrective actions are carried out as per agreed timeline.
N/A Safety Officer / Safety
Representative
Ongoing
Health and Safety Targets Objective No. 9: Identify any safety issues site wide Relevant Legislation:
Target Action Due Date Resp. Status 8.1 Identify hazards on site and minimise where possible
a) T.M.S to carry out an site wide risk assessment to identify hazards onsite.
b) Review TMS Risk assessments
c) Complete any corrective actions identified as a result of the Risk Assessment
Complete
Complete
30/06/12
OPS/Project team/Maint
In Progress
Environmental Legislation: Co2 Carbon Levy Legislation Objective No. 10: Ensure Gensys is compliant with the Legislation Relevant Legislation: Electricity Regulation (Amendment) (Carbon Revenue Levy) Act 2010 Target Action Due Date Resp. Status6.1 Calculate Co2 emissions and report
to the CER on a quarterly basis.
a) Calculate Co2 emissions on a quarterly basis
b) Audit calculations and emission figures
c) Submit reports to CER
d) Resolve any corrective actions as a result of audits/ reports
Ongoing K Ruddy Open –Quarterly
Sheet : Facility ID Activities AER Returns Workbook 30/3/2012 15:57
| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | 4869 30/03/2012 15:57
Guidance to completing the PRTR workbook
Version 1.1.13
REFERENCE YEAR 2011
1. FACILITY IDENTIFICATIONParent Company Name Viridian Power Limited
Facility Name Viridian Power LimitedPRTR Identification Number P0777
Licence Number P0777-01
Waste or IPPC Classes of ActivityNo. class_name
2.1The operation of combustion installations with a rated thermal input equal to or greater than 50MW
Address 1 Parsons Brinckerhoff LimitedAddress 2 Manchester Technology CentreAddress 3 Oxford RoadAddress 4 Manchester M1 7ED
DublinCountry Ireland
Coordinates of Location -6.32607 53.4116River Basin District IEEA
NACE Code 3511Main Economic Activity Production of electricity
AER Returns Contact Name Brian KinsellaAER Returns Contact Email Address [email protected]
AER Returns Contact Position Plant ManagerAER Returns Contact Telephone Number 01-8645900
AER Returns Contact Mobile Phone NumberAER Returns Contact Fax Number 01-8645927
Production Volume 0.0Production Volume Units
Number of Installations 0Number of Operating Hours in Year 0
Number of Employees 0User Feedback/Comments
AER Returns Workbook
| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0483_2011.xls | Return Year : 2011 | Page 1 of 1
User Feedback/CommentsWeb Address
2. PRTR CLASS ACTIVITIESActivity Number Activity Name1(c) Thermal power stations and other combustion installations
3. SOLVENTS REGULATIONS (S.I. No. 543 of 2002)Is it applicable? No
Have you been granted an exemption ? NoIf applicable which activity class applies (as per
Schedule 2 of the regulations) ?Is the reduction scheme compliance route being
used ?
| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0483_2011.xls | Return Year : 2011 | Page 1 of 1
Sheet : Releases to Air AER Returns Workbook 30/3/2012 15:57
4.1 RELEASES TO AIR Link to previous years emissions data | PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | 30/03/2012 15:58
8 11 19 19 27 28 6 6 6SECTION A : SECTOR SPECIFIC PRTR POLLUTANTS
Please enter all quantities in this section in KGsQUANTITY
No. Annex II Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year08 Nitrogen oxides (NOx/NO2) M ALT EN14181 510568.0 510568.0 0.0 0.003 Carbon dioxide (CO2) C ETS 931269000.0 931269000.0 0.0 0.002 Carbon monoxide (CO) M ALT EN14181 193656.0 193656.0 0.0 0.011 Sulphur oxides (SOx/SO2) M ALT EN14181 9792.8 9792.8 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
SECTION B : REMAINING PRTR POLLUTANTSPlease enter all quantities in this section in KGs
QUANTITY
No. Annex II Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year0.0 0.0 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
SECTION C : REMAINING POLLUTANT EMISSIONS (As required in your Licence)Please enter all quantities in this section in KGs
QUANTITY
Pollutant No. Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year210 Dust M ALT EN13284-1:2002 7543.0 7543.0 0.0 0.0
0.0 0.0 0.0 0.0* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
Additional Data Requested from Landfill operators
Landfill: Viridian Power LimitedPlease enter summary data on the quantities of methane flared and / or utilised
additional_pollutant_no T (Total) kg/Year M/C/E Method CodeDesignation or
DescriptionFacility Total Capacity
m3 per hourTotal estimated methane generation (as per
site model) 0.0 N/AMethane flared 0 0 0 0 (Total Flaring Capacity)
Method Used
Method Used
RELEASES TO AIRPOLLUTANT METHOD
Method Used
POLLUTANT
RELEASES TO AIR
RELEASES TO AIRMETHOD
POLLUTANT METHODMethod Used
For the purposes of the National Inventory on Greenhouse Gases, landfill operators are requested to provide summary data on landfill gas (Methane) flared or utilised on their facilities to accompany the figures for total methane generated. Operators should only report their Net methane (CH4) emission to the environment under T(total) KG/yr for Section A: Sector specific PRTR pollutants above. Please complete the table below:
| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | Page 1 of 1
Methane flared 0.0 0.0 (Total Flaring Capacity)Methane utilised in engine/s 0.0 0.0 (Total Utilising Capacity)
Net methane emission (as reported in Section A above) 0.0 N/A
| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | Page 1 of 1
Sheet : Releases to Waters AER Returns Workbook 30/3/2012 15:58
4.2 RELEASES TO WATERS Link to previous years emissions data | PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | 30/03/2012 15:58
8 9 17 17 25 31 6 6 6SECTION A : SECTOR SPECIFIC PRTR POLLUTANTS Data on ambient monitoring of storm/surface water or groundwater, conducted as part of your licence requirements, should NOT be submitted under AER / PRTR Reporting as th
Please enter all quantities in this section in KGsQUANTITY
No. Annex II Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year
12 Total nitrogen M OTHAWWA Standard 4500-NO3, Konelab analyser 34.97 34.97 0.0 0.0
13 Total phosphorus MEN ISO 6878:2004 0.73 0.73 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
SECTION B : REMAINING PRTR POLLUTANTSPlease enter all quantities in this section in KGs
QUANTITY
No. Annex II Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year0.0 0.0 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
SECTION C : REMAINING POLLUTANT EMISSIONS (as required in your Licence)Please enter all quantities in this section in KGs
QUANTITY
Pollutant No. Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year
238 Ammonia (as N) M OTHStandard Method -Konelab Analyser 15.25 15.25 0.0 0.0
240 Suspended Solids M OTH Gravimetric 72.72 72.72 0.0 0.0
306 COD M OTHStandard Method - Hach Method 8000 290.87 290.87 0.0 0.0
303 BOD M OTH
Based on Standard methods for the examination of water & waste water 21st ed. 2005 14.54 14.54 0.0 0.0
327 Nitrate (as N) M OTHAWWA Standard 4500-NO3 Konelab Analyser 19.82 19.82 0.0 0.0
363 Total Dissolved Solids M OTH
Standard methods for the examination of water & waste water 21st ed. 2005 6215.0 6215.0 0.0 0.0
324 Mineral oils M OTH
Standard Method - Adapted from USEPA 8015B 1.45 1.45 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
RELEASES TO WATERS
RELEASES TO WATERS
Method Used
POLLUTANTMethod Used
POLLUTANT
POLLUTANTRELEASES TO WATERS
Method Used
| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | Page 1 of 1
Sheet : Releases to Wastewater or Sewer AER Returns Workbook 30/3/2012 15:58
4.3 RELEASES TO WASTEWATER OR SEWER Link to previous years emissions data | PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2 30/03/2012 15:58
8 8 16 16 6 6 6 6SECTION A : PRTR POLLUTANTS
Please enter all quantities in this section in KGsQUANTITY
No. Annex II Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year0.0 0.0 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
SECTION B : REMAINING POLLUTANT EMISSIONS (as required in your Licence)Please enter all quantities in this section in KGs
QUANTITY
Pollutant No. Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year F (Fugitive) KG/Year0.0 0.0 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
OFFSITE TRANSFER OF POLLUTANTS DESTINED FOR WASTE-WATER TREATMENT OR SEWER
OFFSITE TRANSFER OF POLLUTANTS DESTINED FOR WASTE-WATER TREATMENT OR SEWER
Method Used
Method Used
POLLUTANT METHOD
POLLUTANT METHOD
Link to previous years emissions data Page 1 of 1Link to previous years emissions data Page 1 of 1
Sheet : Releases to Land AER Returns Workbook 30/3/2012 15:58
4.4 RELEASES TO LAND Link to previous years emissions data | PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | 30/03/2012 15:59
8 8 16 16 6 6 6 6SECTION A : PRTR POLLUTANTS
Please enter all quantities in this section in KGsQUANTITY
No. Annex II Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year0.0 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
SECTION B : REMAINING POLLUTANT EMISSIONS (as required in your Licence)Please enter all quantities in this section in KGs
QUANTITY
Pollutant No. Name M/C/E Method Code Designation or Description Emission Point 1 T (Total) KG/Year A (Accidental) KG/Year0.0 0.0 0.0
* Select a row by double-clicking on the Pollutant Name (Column B) then click the delete button
POLLUTANT METHODMethod Used
RELEASES TO LAND
RELEASES TO LAND
POLLUTANT METHODMethod Used
| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | Page 1 of 1| PRTR# : P0777 | Facility Name : Viridian Power Limited | Filename : P0777_2011.xls | Return Year : 2011 | Page 1 of 1
Sheet : Treatment Transfers of Waste AER Returns Workbook 31/3/2012 10:2
5. ONSITE TREATMENT & OFFSITE TRANSFERS OF WASTE | PRTR# : P0483 | Facility Name : Huntstown Power Company Limited | Filename : P0483_2011.xls | Return Year : 2011 | 31/03/2012 10:02
5 29 Please enter all quantities on this sheet in Tonnes 22
Quantity (Tonnes per
Year)
Haz Waste : Name and Licence/Permit No of Next
Destination Facility Non Haz Waste: Name and Licence/Permit No of
Recover/Disposer
Haz Waste : Address of Next Destination Facility
Non Haz Waste: Address of Recover/Disposer
Name and License / Permit No. and Address of Final Recoverer /
Disposer (HAZARDOUS WASTE ONLY)
Actual Address of Final Destination i.e. Final Recovery / Disposal Site (HAZARDOUS WASTE ONLY)
Transfer DestinationEuropean Waste
Code Hazardous Quantity T/Year Description of Waste
Waste Treatment Operation M/C/E Method Used
Location of Treatment Name and Licence / Permit No. of Recoverer / Disposer / Broker Address of Recoverer / Disposer / Broker Name and Address of Final Destination i.e. Final Recovery / Disposal Site (HAZARDOUS WASTE ONLY) Licence / Permit No. of Final Destination i.e. Final Recovery / Disposal Site (HAZARDOUS WASTE ONLY)
Within the Country 20 01 01 No 3.506 paper and cardboard R3 M Weighed Offsite in Ireland Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Within the Country 20 03 01 No 15.675 mixed municipal waste D5 M Weighed Offsite in IrelandGreenstar Limited,CP D 735/5
Ballyogan Road Sandyford,Unit 6 Ballyogan Business Park,Dublin ,18,Ireland
Within the Country 20 01 40 No 3.46 metals R4 M Weighed Offsite in IrelandGreenstar Limited,CP D 735/5
Ballyogan Road Sandyford,Unit 6 Ballyogan Business Park,Dublin ,18,Ireland
Within the Country 20 01 38 No 6.22 wood other than that mentioned in 20 01 37 R12 M Weighed Offsite in IrelandGreenstar Limited,CP D 735/5
Ballyogan Road Sandyford,Unit 6 Ballyogan Business Park,Dublin ,18,Ireland
Within the Country 15 01 01 No 2.34 paper and cardboard packaging R3 M Weighed Offsite in IrelandGreenstar Limited,CP D 735/5
Ballyogan Road Sandyford,Unit 6 Ballyogan Business Park,Dublin ,18,Ireland
Within the Country 20 01 33 Yes 0.115
batteries and accumulators included in 16 06 01, 16 06 02 or 16 06 03 and unsorted batteries and accumulators containing these batteries R4 M Weighed Offsite in Ireland
Irish Lamp Recycling ,WFP-KE-08-0348-01 .,Athy,Kildare,.,Ireland
KMK Metals,113-2,.,Tullamore,Co. Offaly,.,Ireland
.,Tullamore,Co. Offaly,.,Ireland
Within the Country 20 01 35 Yes 0.28
discarded electrical and electronic equipment other than those mentioned in 20 01 21 and and 20 01 23 containing hazardous components R4 M Weighed Offsite in Ireland
Irish Lamp Recycling ,WFP-KE-08-0348-01 .,Athy,Kildare,.,Ireland
KMK Metals,113-2,.,Tullamore,Co. Offaly,.,Ireland
.,Tullamore,Co. Offaly,.,Ireland
Within the Country 20 01 21 Yes 0.0335fluorescent tubes and other mercury-containing waste R4 M Weighed Offsite in Ireland
Irish Lamp Recycling ,WFP-KE-08-0348-01 .,Athy,Kildare,.,Ireland
KMK Metals,113-2,.,Tullamore,Co. Offaly,.,Ireland
.,Tullamore,Co. Offaly,.,Ireland
Within the Country 16 10 02 No 767.0aqueous liquid wastes other than those mentioned in 16 10 01 D8 M Weighed Offsite in Ireland
Dublin City Council ,WWTP Ringsend , ,Ringsend Dublin,4,Ireland
paint inks adhesives and resins containingGreenogue Business Park Rathcoole Dublin 24 Ire
ATM Morerdijk ,821780,Vlasweg 12,.,NL-4782 PW Vlasweg 12 NL-4782 PW
Method Used
To Other Countries 20 01 27 Yes 0.02paint, inks, adhesives and resins containing dangerous substances R1 M Weighed Abroad Rilta Environmental,192-2
Park,Rathcoole,Dublin,24,Ireland
4782 PW Moerdijk,.,Netherlands
Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
To Other Countries 06 01 06 Yes 0.495 other acids R6 M Weighed Abroad Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Ravatech S.A. ,0421 021 761,Zoning Industrial Estate, , ,BE B 4480 Engis,Belgium
Zoning Industrial Estate, , ,BE B 4480 Engis,Belgium
To Other Countries 18 02 08 No 0.0105medicines other than those mentioned in 18 02 07 R1 M Weighed Abroad ATM Morerdijk ,821780
Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
To Other Countries 11 01 09 Yes 0.2755sludges and filter cakes containing dangerous substances R1 M Weighed Abroad Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Zimmermann Sonderabfallentsorgung und Verwertung & Co.,E75475049,Gottieb-Daimier Strasse 31 ,DE 33334 ,Gutersioh,DE 33334 ,Germany
Gottieb-Daimier Strasse 31 ,DE 33334 ,Gutersioh,DE 33334 ,Germany
To Other Countries 15 02 02 Yes 12.177
absorbents, filter materials (including oil filters not otherwise specified), wiping cloths, protective clothing contaminated by dangerous substances R1 M Weighed Abroad Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
ATM Morerdijk ,821780,Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
To Other Countries 16 05 07 Yes 2.91discarded inorganic chemicals consisting of or containing dangerous substances R6 M Weighed Abroad Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Ravatech S.A. ,0421 021 761,Zoning Industrial Estate, , ,BE B 4480 Engis,Belgium
Zoning Industrial Estate, , ,BE B 4480 Engis,Belgium
To Other Countries 08 01 11 Yes 0.775waste paint and varnish containing organic solvents or other dangerous substances R1 M Weighed Abroad Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
ATM Morerdijk ,821780,Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
| PRTR# : P0483 | Facility Name : Huntstown Power Company Limited | Filename : P0483_2011.xls | Return Year : 2011 | Page 1 of 2
Sheet : Treatment Transfers of Waste AER Returns Workbook 31/3/2012 10:2
Quantity (Tonnes per
Year)
Haz Waste : Name and Licence/Permit No of Next
Destination Facility Non Haz Waste: Name and Licence/Permit No of
Recover/Disposer
Haz Waste : Address of Next Destination Facility
Non Haz Waste: Address of Recover/Disposer
Name and License / Permit No. and Address of Final Recoverer /
Disposer (HAZARDOUS WASTE ONLY)
Actual Address of Final Destination i.e. Final Recovery / Disposal Site (HAZARDOUS WASTE ONLY)
Transfer DestinationEuropean Waste
Code Hazardous Quantity T/Year Description of Waste
Waste Treatment Operation M/C/E Method Used
Location of Treatment Name and Licence / Permit No. of Recoverer / Disposer / Broker Address of Recoverer / Disposer / Broker Name and Address of Final Destination i.e. Final Recovery / Disposal Site (HAZARDOUS WASTE ONLY) Licence / Permit No. of Final Destination i.e. Final Recovery / Disposal Site (HAZARDOUS WASTE ONLY)
Method Used
Within the Country 13 07 01 Yes 0.037 fuel oil and diesel D9 M Weighed Offsite in Ireland Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Rilta Environmental ,192-2,Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Within the Country 16 10 01 Yes 45.578aqueous liquid wastes containing dangerous substances D9 M Weighed Offsite in Ireland Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Rilta Environmental ,192-2,Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Within the Country 15 01 10 Yes 0.98packaging containing residues of or contaminated by dangerous substances R4 M Weighed Offsite in Ireland Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Rilta Environmental ,192-2,Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
To Other Countries 16 05 06 Yes 0.39
laboratory chemicals, consisting of or containing dangerous substances, including mixtures of laboratory chemicals R1 M Weighed Abroad Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
ATM Morerdijk ,821780,Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
Within the Country 13 02 08 Yes 2.38 other engine, gear and lubricating oils D9 M Weighed Offsite in Ireland Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Rilta Environmental ,192-2,Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Within the Country 13 05 07 Yes 15.62 oily water from oil/water separators D9 M Weighed Offsite in Ireland Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
Rilta Environmental ,192-2,Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Greenogue Business Park ,.,Rathcoole Dublin,24,Ireland
Within the Country 20 03 04 No 195.0 septic tank sludge D8 M Weighed Offsite in IrelandDublin City Council ,WWTP Ringsend , ,Ringsend Dublin,4,Ireland
To Other Countries 08 04 09 Yes 0.06
waste adhesives and sealants containing organic solvents or other dangerous substances R3 M Weighed Abroad Rilta Environmental,192-2
Greenogue Business Park,Rathcoole,Dublin,24,Ireland
ATM Morerdijk ,821780,Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
Vlasweg 12,.,NL-4782 PW Moerdijk,.,Netherlands
* Select a row by double-clicking the Description of Waste then click the delete button
| PRTR# : P0483 | Facility Name : Huntstown Power Company Limited | Filename : P0483_2011.xls | Return Year : 2011 | Page 2 of 2