Technical Data- viledon CP/DP Filter
Particle Removal Efficiency Resistance Curve52.2 Duopleat Test # BHT 07-887
0
10
20
30
40
50
60
70
80
90
100
0.1 1 10
Particle Diameter (um)
Rem
ova
l Eff
icie
ncy
%
Initial Load 1 Load 2 Load 3 Load 4 Load 5
Resistance 52.2 Duopleat Test BHT 07-887
0.06
0.13
0.23
0.32
0.42
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
500 1000 1500 2000 2500
Air Flow Rate (CFM)
Res
ista
nce
(in
WG
)
Freudenberg Filtration Technologies LP2975 Pembroke RoadHopkinsville, Ky 42240Tel: 1-270-887-5145Fax: 1-270-890-0743www.freudenberg-filter.com
The figures given are mean values subject to tolerances due to normal production fluctuations. Our explicit written confirmation is always required for the correctness and applicability of the information involved in any particular case.
viledon® is a registered trademark of Freudenberg
Characteristics unit1/1
(24x24)1/2
(12x12)5/6
(24x20)Header Size in. 23-3/8x23-3/8 11-3/8x23-3/8 23-3/8x19-3/8
Depth in. 11-1/2 11-1/2 11-1/2
Weight lb. 12 6 8.4
Du
oPl
eat
Gra
ph
Performance Unit CP-DP 1/1Burst Strength (BHT 07-887) “w.g. >4
Dust Holding Capacity grams 407/151
Performance Unit CP 1/1 DP 1/1Rated Air Flow CFM 1968 1968
Initial Resistance “w.g. .28 .32
Final Resistance* “w.g. 1.5 1.5
MERV@1968 1-16 8 15
Media Area ft2 105 105
Carbon Weight (lbs/g) 9.7/4,400 9.7/4,400