introductionaasrc.org/wp-content/uploads/2015/06/current-harmonics... · web viewmodel had been...
TRANSCRIPT
Current harmonics mitigation from grid connected variable speed wind turbine due
to nonlinear loads using shunt active power filter
Abstract: Quality of power now-a-days is of high concern due to increasing demand of
supply and energy resources are limited; another cause is amplified penetration of nonlinear
loads on the power system. To overcome energy mandate, technologists are shifting to the
renewable energies' side; wind or solar, and so on. For mitigating effect of nonlinear loads
various techniques have been used by researchers in past decades. Scholars used shunt
active power filter (APF) to mitigate current harmonics from the fixed wind turbine
generator (WTG), in this paper shunt APF has been applied with variable-speed wind
turbine generator using synchronous reference frame (SRF) for the extraction of
compensation signal for APF. Gate driver signals are generated from Bang-Bang Controller
(Hysteresis Band Current Controller HBCC). Model had been developed using
MATLAB/SIMULINK, simulation results portraying decreased THD levels within the
system and clearly reveal the effectiveness of Shunt APF in meeting the IEEE-519 standard
recommended for harmonic levels.
Keywords: Wind Turbine Generator, Shunt Active Power Filter, Synchronous Reference
Frame, THD
1. Introduction
The added utilization of power electronics controlled devices and loads with nonlinear
characteristics in the power system has increased distortion level in current and voltage
waveforms in shape of ‘Harmonics' [1]
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Various problems caused by harmonics in the power system and also cause an effect on
consumer products, such as distorted voltage waveforms, equipment overheating, blown
capacitor fuses, transformer overheating, excessive neutral currents, low power factor, etc.
[2-5]. Different techniques have been employed by the researchers in the last decades to
mitigate the issue of harmonics and to provide consistent and sinusoidal power to the
consumers who does not damage to their equipment. Furthermore, generation of current
harmonics induces more losses in the generator and thereby producing more heat, which in
turn reduces efficiency and life of the generator [6]. Like is the case with grid tied wind
turbine generator who is, likewise, regarded by these current harmonics and supply
distorted waveform at the level of common coupling (PCC).
Passive and Active filters have been enforced to reduce harmonic distortion. Passive filters
have the drawback that it only provides over or under compensated for harmonics,
whenever a change in load occurs, and they have bulky size, component ageing, resonance
problem and fixed compensation performance [7]. Whereas, active filter recognized as an
active power filter (APF) is preferred over the passive filter. Active Power Filter offers a
benevolent solution to the problems of power quality, which allow the compensation of
current harmonics and together with reactive power compensation.
The SAPF operates by injecting the reactive, unbalanced, and harmonic load current
components into the utility system with the same magnitudes as the non-active load
currents demanded by a given nonlinear load but with opposite phases [8-11]. The method
for extraction of harmonic compensation signal and determination of reference current play
a central role as these are related to accuracy and speed of Shunt APF response and also
matters the design and application of Shunt APF [12]. The reference current extraction
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
methods are categorized into two groups, Time domain and frequency-domain [13, 14].
Time-domain methods include d–q transformation (or SRF), p–q transformation (or
instantaneous reactive power), symmetrical component transformation, etc., are based upon
the measurements and transformation of three-phase quantities [9]. Time domain as
compared with the frequency domain has the fast response whereas frequency domain,
based on Fourier's transformation has an accurate response [12]. The compensation method
used within this paper is synchronous reference frame (SRF) technique based upon time
domain control type in which all harmonic load current components are targeted and
compensated. The control strategy and the current injection will depend on reference signal
extraction method The performance of Shunt APF with the grid-connected variable-speed
wind turbine is then analyzed by calculating total harmonic distortion of compensated
quantities using MATLAB/SIMULINK software.
2. Topology and Operational Principle of Shunt Active Power Filter
Shunt Active Power Filter widely used among all the filters [15-22]. Shunt APF induces the
compensation current in the system which is equal in magnitude but in anti-phase to
measured harmonic load current to mitigate the effect of harmonics from supply side and
deliver almost sinusoidal power to consumers. Figure 1, depicting shunt APF with the grid-
connected wind turbine generator. Shunt APF has two main parts reference current
extraction method and gate driver signal for inverter. Reference current been extracted from
the load current measured at PCC and accordingly APF will supply/draw current at PCC.
The effectiveness of SAPF depends on gate driver signal control [23]. For application of
APF various PWM current control techniques have been proposed by many researchers.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
But in terms of quick current controllability and easy implementation, HCC has highest
rating among other methods such as sinusoidal- PWM and triangular current controller [24,
25]. Line inductance used here in order to remove ripples generated by filter. For
maintaining and regulation of DC voltage dc link capacitor is used with conventional PI
controller. A full bridge diode rectifier also connected at the point of common coupling
(PCC). Combination of R, L and C loads is connected across the bridge rectifier (source of
harmonics generation). Principal operation of SAPF, the current controlled compensation to
draw/supply current from/to the power system (PCC). This compensation of current enables
the active power filter to cancel and compensate reactive power drawn by nonlinear loads.
3. Harmonic Current Extraction Technique
Synchronous Reference Frame method to extract the harmonic current was developed in
MATLAB/SIMULINK for SAPF under the unbalance condition due to variable wind
speed. Under SRF method distorted 3-phase load current is transferred from it’s a-b-c
stationary reference frame to d-q reference frame [26] using equation (1).
[ id
iq]=[ sin θ sin(θ−2 π3 ) sin(θ+
2π3 )
cosθ cos(θ−2π3 ) cos (θ+ 2 π
3 )]∗[ia
ib
ic] (1 )
The components of current Id and Iq extracted from the load current represent active and
reactive power components of current and can be decomposed using equation (2 and 3).
id=id+~id (2 )
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
iq=iq+~iq (3 )
For filtering harmonic contents extracted id-iq current passed through low-pass filter (LPF)
and allowed only the fundamental frequency components. Function of PI controller is to
regulate capacitor dc link voltage. The dc capacitor voltage is sensed and compared with
some set reference voltage to calculate error voltage. This voltage error is involved with PI
gain (KP=0.1 and KI-1) to regulate capacitance in dynamic conditions. Further the output
of PI controller is subtracted from d-axis current to eradicate steady-state error [27]. The
procedure is then developed to extract the reference signal in d-q rotating frame, which is
converted back to a-b-c stationery frame using inverse Park’s transformation utilizing
equation (4,5 and 6). Figure 2 depicting Simulink model for SRF method.
isa¿ =id sin (ωt )+cos ( ωt ) ( 4 )
isb¿ =id sin(ωt−2 π
3 )+cos(ωt−2 π3 ) (5 )
isc¿ =id sin(ωt+ 2π
3 )+cos(ωt+ 2 π3 ) (6 )
4. Gating Signal Generator for APF
The different approaches for generating gate driver signals, such as hysteresis-based current
control (HBCC), PWM current or voltage control, deadbeat control, sliding mode of current
control, PI controller, fuzzy-based current control, and Neural network-based current
control, can be instigated to obtain the switching signal for APF. HBCC is considered for
this paper (Simulink model shown in Figure 3) because of its characteristics by having
unconditioned stability, quick response, and good accuracy.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
5. System Parameters and Working
The 1.5 MVA 575 V variable speed PMSG based wind turbine is connected with 120kV,
60 Hz grid through 30km transmission line to analyze the effect of nonlinear loads. At the
point of common coupling, nonlinear load is attached, which is generating current
harmonics and affecting utility supply, furthermore, affecting current supplied by WT.
Therefore, increase in total harmonic distortion in current and voltage at PCC. Proposed
system for mitigating these harmonics is connected at PCC. Simulation results presenting a
decrease in THD level within the utility system and at PMSG.
6. Simulation Results
Simulations of the system without compensation are shown in Figure 4, THD level of
PMSG current for Phase A, Phase B and Phase C are 5.76%, 4.62% and 4.83%
respectively. The PCC current THD level is 7.42%, 6.75% and 5.70% for Phase A, B and C
respectively. PCC voltage THD level for its corresponding Phase A, B and C are 8.05%,
7.30% and 6.76%.
The simulation results of the system with Shunt APF is shown in Figure 5 with reduced
THD levels. THD level of PMSG current reduced to 1.15%, 1.24% and 2.19% from 5.76%,
4.62% and 4.83% for their respective phase A, B and C. whereas, PCC current THD level
decreased from 7.42%, 6.75% and 5.70% to 0.18%, 019% and 0.19% of their
corresponding Phase A, B and C. Voltage THD at PCC decreased to 0.80%, 1.01% and
0.55% from 8.05%, 7.30% and 6.76% of their Phase A, B and C respectively. The
compensated current injected by Shunt APF to mitigate the effect of harmonics is depicted
in Figure 6.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
7. Summary of Simulation Results
Figure 7 below elaborating the percentage magnitude of total harmonic distortion in each
phase of PMSG current, PCC current and PCC voltage without compensation.
Consequence giving the picture that system is not running under the harmonic standard
(IEEE-519) specified by IEEE [28].
After the application of Shunt APF along with synchronous reference frame method for the
extraction of harmonic components under the variable speed of wind, system having
decreased level of THD magnitude as specified in Figure 8.
Summarizing chart for Figure-7 and 8 is displayed in table below, where the phase to phase
comparison with the system without compensation and with SAPF is shown. Results
showing that using SAPF system THD level has reduced to limits stated in IEEE-519.
8. Conclusion
Application of Shunt Active Power Filter with grid-connected variable-speed PMSG based
with turbine generator was studied in this paper to mitigate the effect of harmonics due to
nonlinear loads. Simulation results gave evident in reduction of current and voltage
harmonics level within the system. With the use of this technique, drop in harmonics will
decrease heat caused and therefore, will not affect life span of the generator. On the other
hand, with the application of SAPF voltage supplied to consumers also having the
sinusoidal waveform which in turn will not damage their appliances and utilities.
References
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
[1] G. Singh, A. Singh, and R. Mitra, "A simple fuzzy logic based robust active power
filter for harmonics minimization under random load variation," Electric power
systems research, vol. 77, pp. 1101-1111, 2007.
[2] J. S. Subjak Jr and J. S. Mcquilkin, "Harmonics-causes, effects, measurements, and
analysis: an update," Industry Applications, IEEE Transactions on, vol. 26, pp.
1034-1042, 1990.
[3] L. Duarte and M. Alves, "The degradation of power capacitors under the influence
of harmonics," in Harmonics and Quality of Power, 2002. 10th International
Conference on, 2002, pp. 334-339.
[4] V. Wagner, J. Balda, D. Griffith, A. McEachern, T. Barnes, D. Hartmann, et al.,
"Effects of harmonics on equipment," Power Delivery, IEEE Transactions on, vol.
8, pp. 672-680, 1993.
[5] A. M. Massoud, S. Ahmed, and A. S. Abdel‐Khalik, "Active Power Filter," Power
Electronics for Renewable Energy Systems, Transportation and Industrial
Applications, pp. 534-572, 2014.
[6] J. Tsai and K. Tan, "H APF harmonic mitigation technique for PMSG wind energy
conversion system," in Power Engineering Conference, 2007. AUPEC 2007.
Australasian Universities, 2007, pp. 1-6.
[7] A. Prasad, P. D. Ziogas, and S. Manias, "An active power factor correction
technique for three-phase diode rectifiers," Power Electronics, IEEE Transactions
on, vol. 6, pp. 83-92, 1991.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
[8] Z. Shu, Y. Guo, and J. Lian, "Steady-state and dynamic study of active power filter
with efficient FPGA-based control algorithm," Industrial Electronics, IEEE
Transactions on, vol. 55, pp. 1527-1536, 2008.
[9] R. S. Herrera, P. Salmerón, and H. Kim, "Instantaneous reactive power theory
applied to active power filter compensation: Different approaches, assessment, and
experimental results," Industrial Electronics, IEEE Transactions on, vol. 55, pp.
184-196, 2008.
[10] K.-K. Shyu, M.-J. Yang, Y.-M. Chen, and Y.-F. Lin, "Model reference adaptive
control design for a shunt active-power-filter system," Industrial Electronics, IEEE
Transactions on, vol. 55, pp. 97-106, 2008.
[11] S. A. González, R. García-Retegui, and M. Benedetti, "Harmonic computation
technique suitable for active power filters," Industrial Electronics, IEEE
Transactions on, vol. 54, pp. 2791-2796, 2007.
[12] S. Rahmani, N. Mendalek, and K. Al-Haddad, "Experimental design of a nonlinear
control technique for three-phase shunt active power filter," Industrial Electronics,
IEEE Transactions on, vol. 57, pp. 3364-3375, 2010.
[13] B. N. Singh, B. Singh, A. Chandra, P. Rastgoufard, and K. Al-Haddad, "An
improved control algorithm for active filters," Power Delivery, IEEE Transactions
on, vol. 22, pp. 1009-1020, 2007.
[14] S. George and V. Agarwal, "A DSP based optimal algorithm for shunt active filter
under nonsinusoidal supply and unbalanced load conditions," Power Electronics,
IEEE Transactions on, vol. 22, pp. 593-601, 2007.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
[15] M. Aredes and E. H. Watanabe, "New control algorithms for series and shunt three-
phase four-wire active power filters," Power Delivery, IEEE Transactions on, vol.
10, pp. 1649-1656, 1995.
[16] H. Akagi, "Control strategy and site selection of a shunt active filter for damping of
harmonic propagation in power distribution systems," Power Delivery, IEEE
Transactions on, vol. 12, pp. 354-363, 1997.
[17] M. I. M. Montero, E. R. Cadaval, and F. B. González, "Comparison of control
strategies for shunt active power filters in three-phase four-wire systems," Power
Electronics, IEEE Transactions on, vol. 22, pp. 229-236, 2007.
[18] H. Akagi, H. Fujita, and K. Wada, "A shunt active filter based on voltage detection
for harmonic termination of a radial power distribution line," Industry Applications,
IEEE Transactions on, vol. 35, pp. 638-645, 1999.
[19] M. K. Mishra, A. Joshi, and A. Ghosh, "A new algorithm for active shunt filters
using instantaneous reactive power theory," Power Engineering Review, IEEE, vol.
20, pp. 56-58, 2000.
[20] A. Chandra, B. Singh, B. Singh, and K. Al-Haddad, "An improved control
algorithm of shunt active filter for voltage regulation, harmonic elimination, power-
factor correction, and balancing of nonlinear loads," Power Electronics, IEEE
Transactions on, vol. 15, pp. 495-507, 2000.
[21] A. M. Al-Zamil and D. A. Torrey, "A passive series, active shunt filter for high
power applications," Power Electronics, IEEE Transactions on, vol. 16, pp. 101-
109, 2001.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
[22] M. El-Habrouk, M. Darwish, and P. Mehta, "Active power filters: A review," IEE
Proceedings-Electric Power Applications, vol. 147, pp. 403-413, 2000.
[23] P. Karuppanan and K. K. Mahapatra, "PI and fuzzy logic controllers for shunt active
power filter—A report," ISA transactions, vol. 51, pp. 163-169, 2012.
[24] A. Nabae, S. Ogasawara, and H. Akagi, "A novel control scheme for current-
controlled PWM inverters," Industry Applications, IEEE Transactions on, pp. 697-
701, 1986.
[25] D. M. Brod and D. W. Novotny, "Current control of VSI-PWM inverters," Industry
Applications, IEEE Transactions on, pp. 562-570, 1985.
[26] A. Massoud, S. Finney, and B. Williams, "Review of harmonic current extraction
techniques for an active power filter," in Harmonics and Quality of Power, 2004.
11th International Conference on, 2004, pp. 154-159.
[27] R. Patel and A. K. Panda, "Real time implementation of PI and fuzzy logic
controller based 3-phase 4-wire interleaved buck active power filter for mitigation
of harmonics with i d–i q control strategy," International Journal of Electrical
Power & Energy Systems, vol. 59, pp. 66-78, 2014.
[28] I. F II, "IEEE recommended practices and requirements for harmonic control in
electrical power systems," 1993.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Figure Captions
Figure 1. Configuration of Shunt APF
Figure 2. Simulink Model for SRF Method
Figure 3. HBCC Simulink Model
Figure 4. PMSG Current, PCC Current and PCC Voltage with their THD Levels without
SAPF
Figure 5. PMSG Current, PCC Current and PCC Voltage with their THD Levels with
SAPF
Figure 6. Compensation Current injected by SAPF
Figure 7. THD Magnitude with compensation
Figure 8. THD Magnitude with SAPF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Figure 2. Simulink Model for SRF Method
Figure 1. Configuration of Shunt APF
Vdc_ref
PLL
abc-dq0
LPF
LPF
dq0-abc
dq0
sin_cosabc
abc
sin_cosdq0
[Vabc]
Supply Voltage
[Iref]
Reference Signal
[Iabc]
Measured Current
Fo=200Hz
Fo=200Hz
[Vdc]
Inverter Capacitor Voltage
PI
1100
Vabc (pu)
Freq
wt
Sin_Cos
VdcABC
ABC
inductor
gABC
+
-
SAPF
A
B
C
PMSG Wind Turbine
A
B
C
a
b
c
PCC
Non-Linear Load
[Pulses]
N
A
B
C
120 kV Grid
1
23456789
101112131415161718192021222324252627282930313233343536373839404142
Figure 3. HBCC Simulink Model
6S6
5S5
4S4
3S3
2S2
1S1
Relay2
Relay1
Relay
Memory5
Memory4
Memory3
Memory2
Memory1
Memory
AND
LogicalOperator8
AND
LogicalOperator7
NOT
LogicalOperator6
NOT
LogicalOperator5
NOT
LogicalOperator4
AND
LogicalOperator3
AND
LogicalOperator2
AND
LogicalOperator1
AND
LogicalOperator
[Iref]
1time
123456789
10111213
15
16
17
18
19202122
24
25
26
27
28
29
30
31
32
Phase A Phase A Phase A
Phase B Phase B Phase B
Phase C Phase C Phase C
PMSG Current PCC Current PCC Voltage
Phase A Phase A Phase A
Figure 4. PMSG Current, PCC Current and PCC Voltage with their THD Levels without SAPF
1
2
3
4
Phase B Phase B Phase B
Phase C Phase C Phase C
Figure 5. PMSG Current, PCC Current and PCC Voltage with their THD Levels with SAPF
Figure 6. Compensation Current injected by SAPF
1
2
3
4
5
6
7
8
9
Compensation Method
PMSG Current PCC Current PCC Voltage
Phase A Phase B Phase C Phase A Phase B Phase C Phase A Phase B Phase C
PMSG Current PCC Current PCC Voltage0.00%
1.00%2.00%
3.00%
4.00%
5.00%6.00%
7.00%
8.00%
9.00%
5.79%
7.42%8.05%
4.62%
6.75%7.30%
4.83%5.70%
6.76%
Phase APhase BPhase C
Total Harmonic Distortion
Mag
nitu
de o
f Har
mon
icsFigure 7. THD Magnitude with compensation
PMSG Current PCC Current PCC Voltage0.00%
0.50%
1.00%
1.50%
2.00%
2.50%
1.15%
0.18%
0.80%
1.24%
0.19%
1.01%
2.19%
0.19%
0.55%
Phase APhase BPhase C
Total Harmonic Distortion
Mag
nitu
de o
f Har
mon
ics (%
)
Figure 8. THD Magnitude with SAPF
3