vibration isolation using six degree-of-freedom quasi...

47
1 Vibration isolation using six degree-of-freedom quasi-zero stiffness magnetic levitation Authors: Name: Dr Tao Zhu 1 (corresponding author) Address: School of Mechanical Engineering, The University of Adelaide, North Terrace Campus, South Australia, Australia. 5005 Institution: The University of Adelaide; The University of Nottingham UNNC Fax: (61) 8 83134367 Email: [email protected] Name: Associate Professor Benjamin Cazzolato Address: School of Mechanical Engineering, The University of Adelaide, North Terrace Campus, South Australia, Australia. 5005 Institution: The University of Adelaide; Tel: (61) 8 83135449 Fax: (61) 8 83134367 Email: [email protected] Name: Dr William S P Robertson Address: School of Mechanical Engineering, The University of Adelaide, North Terrace Campus, South Australia, Australia. 5005 Institution: The University of Adelaide; Fax: (61) 8 83134367 Email: [email protected] Name: Associate Professor Anthony Zander Address: School of Mechanical Engineering, The University of Adelaide, North Terrace Campus, South Australia, Australia. 5005 Institution: The University of Adelaide; Fax: (61) 8 83134367 1 Present address: The University of Nottingham UNNC

Upload: dangnhan

Post on 27-Aug-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

1

Vibration isolation using six degree-of-freedom quasi-zero stiffness

magnetic levitation

Authors:

Name: Dr Tao Zhu1 (corresponding author)

Address: School of Mechanical Engineering, The University of Adelaide, North Terrace

Campus, South Australia, Australia. 5005

Institution: The University of Adelaide; The University of Nottingham UNNC

Fax: (61) 8 83134367

Email: [email protected]

Name: Associate Professor Benjamin Cazzolato

Address: School of Mechanical Engineering, The University of Adelaide, North Terrace

Campus, South Australia, Australia. 5005

Institution: The University of Adelaide;

Tel: (61) 8 83135449

Fax: (61) 8 83134367

Email: [email protected]

Name: Dr William S P Robertson

Address: School of Mechanical Engineering, The University of Adelaide, North Terrace

Campus, South Australia, Australia. 5005

Institution: The University of Adelaide;

Fax: (61) 8 83134367

Email: [email protected]

Name: Associate Professor Anthony Zander

Address: School of Mechanical Engineering, The University of Adelaide, North Terrace

Campus, South Australia, Australia. 5005

Institution: The University of Adelaide;

Fax: (61) 8 83134367

1 Present address: The University of Nottingham UNNC

Page 2: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

2

Email: [email protected]

Keywords

Zero stiffness, vibration isolation, magnetic levitation

Page 3: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

3

Abstract

In laboratories and many high-tech manufacturing applications, passive vibration isolators are

often used to isolate vibration sensitive equipment from ground-borne vibrations. However,

in traditional passive isolation devices, where the payload weight is supported by elastic

structures with finite stiffness, a design trade-off between the load capacity and the vibration

isolation performance is unavoidable. Low stiffness springs are often required to achieve

vibration isolation, whilst high stiffness is desired for supporting payload weight. In this

paper, a novel design of a six-DOF (six degree of freedom) vibration isolator is presented, as

well as the control algorithms necessary for stabilising the passively unstable maglev system.

The system applies magnetic levitation as the payload support mechanism, which realizes

inherent quasi-zero stiffness levitation in the vertical direction, and zero stiffness in the other

five DOFs. While providing near zero stiffness in multiple DOFs, the design is also able to

generate static magnetic forces to support the payload weight. This negates the trade-off

between load capacity and vibration isolation that often exists in traditional isolator designs.

The paper firstly presents the novel design concept of the isolator and associated theories,

followed by the mechanical and control system designs. Experimental results are then

presented to demonstrate the vibration isolation performance of the proposed system in all six

directions.

Page 4: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

4

1. Introduction and background

In laboratories and many high-tech manufacturing applications, passive vibration isolators are

often used to isolate vibration sensitive equipment from ground-borne vibration. However, in

traditional passive isolation devices, where the payload weight is supported by a resilient

structure, a design trade-off between the load capacity and the isolation performance is

unavoidable [1, 2]. This is due to the necessity of using a high stiffness support to carry the

payload weight to avoid excessive static isolator deflection, which is contrary to the

requirements for vibration isolation. In order to isolate ground vibration, low stiffness support

is normally preferred for reducing the sensitivity of the plant to external disturbances.

Another disadvantage of many spring-damper type designs is that they normally only provide

effective isolation in one direction. However, vibrations potentially exist in all six degrees of

freedom (DOF). Cross coupling between axes often occurs in single-DOF isolator designs,

such that vibration is transmitted from other DOFs into the primary working direction of the

isolator, which significantly limits the performance of the single DOF designs. In some

advanced applications, such as in semi-conductor manufacturing, multi-DOF vibration

isolators are often essential to fulfil the stringent vibration isolation requirements.

Whilst passive designs are commonly used in most applications, actively controlled isolators

are finding increased applications due to their enhanced performance over the passive designs.

Some examples of commercially available active isolators are the optical tables produced by

Newport [3] and Herzan [4], which are designed for laboratory uses to isolate vibration

sensitive equipment. In gravitational wave monitoring projects (LIGO [5] and VIRGO [6]),

multi-DOF active vibration isolators [7] are also used to isolate the instruments from ground-

borne vibrations in multiple directions. The advantages of active vibration control have been

well demonstrated by the literature. However, the application of active vibration control is

still limited by the drawbacks of the active designs, such as high power consumption and

significantly increased system complexity and cost over traditional passive designs.

The demand for high performance vibration isolation systems has drawn significant research

attention over the past two decades, and magnetic levitation (maglev) has demonstrated its

potential in vibration isolation applications. Previously the technology was mainly applied to

maintain a constant levitation gap, such as in maglev trains and maglev bearings [8-10]. The

non-linear magnetic force-displacement relationship was also found to benefit vibration

isolation as this unique feature of maglev enables creation of low stiffness supporting

Page 5: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

5

structures. Robertson et al. [11, 12] proposed a quasi-zero (infinitely close to zero around the

operating point) stiffness magnetic spring for vibration isolation. In their model, permanent

magnets were used to establish maglev system which had quasi-zero stiffness around the

nominal operating position. A tuneable high-static-low-dynamic stiffness vibration isolator

was developed by Zhou and Liu [13], in which electromagnets were used to statically

manipulate the magnetic field to generate a quasi-zero stiffness zone. An alternative approach

to quasi-zero stiffness is quasi-infinite stiffness, whereby the plant is tied to a high impedance

element (such as a plinth), thus isolating the plant from direct on-board excitation. For

example, Mizuno et al. [14] proposed a single-DOF maglev vibration isolator, which used a

number of electromagnets to create a negative stiffness member and counteract the stiffness

of the mechanical springs so that the resultant system stiffness is infinitely large. The infinite

stiffness design was later expanded to a three DOF [15, 16], and a full six-DOF system [17,

18] by applying the same design principle in multiple directions. More developments on

quasi-zero stiffness isolators and maglev isolators are presented in [19-24].

According to Earnshaw’s theorem [25], passive magnetic levitation is inherently unstable.

Therefore, active controls are necessary to enable the operation of maglev systems. The

controller for such isolation systems must be designed carefully such that the vibration

induced by the control system from sensor and electronic noise is negligible. Previous

researchers have investigated a number of low noise control approaches for maglev based

isolation systems. A K-filter based design was proposed by Yang et al. [26]. Their system

was designed to achieve accurate maglev positioning where noisy position sensors are used.

However, in order to realize accurate positioning, the proposed K-filter design has high

levitation stiffness, which is counter to the requirements necessary for ground vibration

isolation. Back-stepping based controller designs were also studied by Wai and Lee [27] for

maglev rail systems. The three controller designs presented in their paper also result in high

levitation stiffness since their aim is to maintain a constant levitation gap. A classic PID

control approach was proposed by Zheng et al. [28]. In their system, the levitation stiffness

and damping are directly controlled through the proportional and derivative gains of the PID

controller. A tracking differentiator was also embedded in the PID controller to suppress

noise within the differentiation loop.

The previous active isolation systems have all demonstrated their potential to improve the

isolation performance when compared to traditional passive systems. However, most of the

Page 6: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

6

designs showed poor performance at low frequencies, and the trade-off between vibration

isolation and payload support still exists. These designs also exhibited higher resonance

frequencies of the fundamental rigid body modes compared to many of the existing high

performance passive vibration isolation systems. In this paper, a novel design of a six-DOF

maglev vibration isolator is presented. The design provides quasi-zero/zero stiffness (quasi-

zero stiffness in the vertical direction and zero stiffness in the other five DOFs) levitation in

multi-DOF, which enables effective vibration isolation in all six DOFs. The novel design also

allows the payload to be supported solely by the permanent magnets with a static magnetic

force, hence the trade-off between load capacity and vibration isolation is avoided. The

vertical supporting force is adjustable by changing the magnet separations so that the

magnitude of the supporting force can match the payload weight to minimize the energy

consumption of the magnetic levitation.

This paper is structured as follows. It starts with the description of the design concept and

theoretical background, followed by the mechanical and control system designs for

implementation of the proposed maglev vibration isolation. Experimental results and

discussions are presented at the end.

2. Theoretical background

The novel isolator design presented in this paper is based on a unique quasi-zero stiffness

maglev system, which is composed of two pairs of rare earth magnets. The system has no

mechanical connections between the frame and the floater, and hence avoids the issues seen

in some of the traditional mechanical spring based isolators, where parasitic high frequency

modes act to degrade the high frequency isolation performance. This section explains the

theoretical background of the isolation system design.

2.1. Maglev system model

A simplified schematic (also discussed in [29]) of the maglev system, which consists of four

identical cylindrical magnets, is shown in Figure 1, Magnets 1 and 4 are fixed to ground and

Magnets 2 and 3 are floating and connected through the rigid linkage. N and S represent the

north and south poles of the magnetisation respectively. The top pair of magnets (1 and 2) has

the same polarisation, which generates an attraction force F12= [F12X, F12Y, F12Z] T, and the

bottom pair has the opposite magnetisation directions, which generates a repulsive force F43=

Page 7: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

7

[F43X, F43Y, F43Z]T. The assembly of Magnet 2, Magnet 3 and the Linkage collectively form

the floater. It is able to move in six DOFs and is isolated from external vibration.

2.2. Calculation of magnetic forces and stiffness

The analytical method used here for the calculation of the magnetic forces is discussed in

detail in [30-32]. Robertson et al. further investigated and simplified the calculations [33, 34]

for determining magnetic forces and torques. Robertson has also provided a Matlab script [35]

to carry out the force and torque calculations, which has been applied in this research to

perform the required calculations.

Explicit calculations of 3D magnetic forces and torques are often computationally expensive.

In order to reduce the execution time of the calculations required for analysing the maglev

system, the 3D magnetic forces are approximated using a single dimensional method. In the

3D calculations, all the forces in the X, Y and Z directions have to be modelled and

calculated individually. However, with the 1D approximation, the necessary force modelling

is reduced to only the coaxial force between the two cylindrical magnets. Magnetic forces

along the axes of the coordinate system can then be approximated based on the geometric

relationships between the three directions. Figure 2 shows a schematic of this approximation

α

β

γ

N

S

N S

S N

Lin

kag

e

N

S

F12 (Attraction)

F43 (Repulsion)

Magnet 1 (Fixed)

Magnet 2 (Floating)

Magnet 3 (Floating)

Magnet 4 (Fixed)

Z

Y

X

Floater

Top magnet pair

Bottom magnet pair

Figure 1: Schematic of the magnetic levitation system.

Page 8: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

8

in the YZ plane, where �� and �� are the magnet separations in the Y and Z directions

respectively. Two cases with equivalent relative positions of the magnet centres are shown

here to demonstrate the differences between the 3D and 1D calculations. In Figure 2(a), all

the forces � = [��, ��, ��] are calculated explicitly. This method is relatively complicated,

and the calculations of the forces are required in all three directions. In contrast, the

simplified 1D approach (shown in Figure 2(b)) only requires modelling of the coaxial force (��) using the method described in [33]. In order to obtain forces along the three axes (X, Y,

Z) of the coordinate sytsem, the coaxial force is then projected onto the three axes using the

geometric transformation

�X = ���X��X2 + �Y2 + �Z2�Y = ���Y��X2 + �Y2 + �Z2�Z = ���Z��X2 + �Y2 + �Z2

. (1)

The combination of the coaxial force calculation and the geometric transformation is a

significantly simpler approach compared to the full 3D force calculation. The 1D

approximation method was shown to reduce the calculation time by approximately two orders

of magnitude.

A comparison between the force calculation results using the 3D and the 1D methods is

shown in Figure 3 for the example case shown in Figure 2. Table 1 shows the geometric and

magnetic parameters used in the force calculations.

FFFF ��

��

dY dY

Figure 2: Magnetic forces resulting from horizontal displacement between two magnets, (a) 3D calculation model; (b) 1D approximation model.

�Y ≪ �Z ≈

YZ plane

Y

Z

X

�� ��

��

�� ��

(a) (b)

Page 9: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

9

Table 1: Physical parameters used in the 3D and 1D force calculations.

Parameter Value

Magnet length 40mm

Magnet width 40mm

Magnet height 20mm

Magnetisation 1.48T

Vertical distance between

magnet centres (�Z) 100mm

Horizontal distance between

magnet centres (�Y) -10mm to 10mm

The 1D approximation to the 3D forces was found to be reasonably accurate with small non-

coaxial displacements (within about 10% of the coaxial displacement). For example, as

shown in Figure 3, the 1D approximation is reasonably accurate when|��| ≤ 0.1��. For the

100mm magnet vertical separation, the horizontal displacement range shown in the figure is −10mm ≤ �� ≤ 10mm. The error between the 1D and 3D methods remains within 0.17N

throughout the -10mm to 10mm displacement range. Despite the small errors in the 1D

approximation method, the magnetic force displacement relationship predicted by the 1D

method fits the trend of the 3D results relatively well. It is not a primary focus in this research

to accurately model the magnetic forces, and the 1D approximation provides a significant

calculation time reduction. Therefore, the small calculation error introduced by the 1D

Figure 3: Comparison between the 3D method and the 1D approximation for calculating ��.

-10 -5 0 5 10-6

-4

-2

0

2

4

6

Horizontal displacement (mm)

Horizonta

l fo

rce (

N)

1D approximation

3D calculation

Relative error

Page 10: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

10

approximation method is considered to be an acceptable compromise with computational

speed in this research for investigating the stiffness behaviour of the proposed maglev system.

The aforementioned calculations and comparisons were based on cubic shaped magnets

rather than the cylindrical magnets used in the system model (Figure 1). This is due to the

fact that, to the author’s best knowledge, there was no practical approach available for

calculating the 3D forces between cylindrical magnets at the time this analysis was carried

out. A method of force calculation between cylindrical magnets was only available for

estimating the coaxial forces, which is another reason why the 3D to 1D approximation is

necessary for the modelling and simulation components of this research. It is considered

reasonable to assume that both cubic and cylindrical magnets have similar force-displacement

behaviours in the scenarios analysed here. Therefore, the 1D approximation method is also

considered suitable for cylindrical magnets. Table 2 lists the physical parameters of the

cylindrical magnets used in the design of the maglev isolator.

Table 2: Physical parameters of the cylindrical magnets.

Parameter Value

Magnet diameter 50.8mm

Magnet thickness 25.4mm

Magnetisation 1.48T

Magnet type Nickel plated rare earth magnet

The calculations of magnet forces and torques are based on the following assumptions:

Assumption 1: The magnetisation is uniform across the volume of all magnets.

This assumption ensures that the effective centre of magnetisation is at the geometric centre

of the magnets. Hence, the magnetic forces also originate from the geometric centre of the

magnets. In the subsequent sections, the determination of the nominal operating position of

the floater (the midpoint between two fixed magnets, refer to Figure 1) will be directly related

to the location of the centre of magnetisation.

Assumption 2: All mechanical components have relative magnetic permeability equal to

unity.

Page 11: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

11

The analysis in the subsequent sections will show the stiffness behaviour of the proposed

maglev vibration isolator in multiple DOFs. In order to realise the favourable force-

displacement relationship of the maglev, it is essential that the floater has no external

interference from the supporting isolator frame, and the flux of the magnetic field is not

distorted. The material selection in the design of the physical isolation system (presented in

Section 5) has ensured, where possible, that all components in the maglev isolator behave

magnetically as if they were in a vacuum.

Assumption 3: Interaction forces between Magnets 1 and 3 and Magnets 2 and 4 are

sufficiently small to be neglected.

For simplicity of the analysis, the force-displacement behaviour between the floater and the

fixed magnets is assumed to be a result of the two adjacent magnet pairs (Magnet 1 and 2,

and Magnets 3 and 4). The total force between Magnets 1 and 3 and between Magnets 2 and

4 was calculated to be 0.0312N with 100mm separation between the top and bottom magnet

pairs. At this separation the total force between the top and bottom magnet pairs is 39.13N.

Therefore, forces between Magnets 1 and 3 and between Magnet 2 and 4 are assumed to have

negligible influence on the floater force-displacement behaviour and were not considered in

the analysis.

3. 6-DOF modelling of the floater forces and torques

In the design of the proposed quasi-zero stiffness maglev system (Figure 1), the floater

assembly consists of two magnets that are rigidly connected via a mechanical linkage, and

vibration isolation is achieved by attaching the payload to the floater assembly. Therefore, the

forces and torques experienced by the floater as a rigid body are of primary interest, as it

governs the vibration isolation performance of the maglev system. The previous sections

have discussed the calculation of the magnetic forces between a pair of magnets. This section

will explain the modelling method used to calculate the forces and torques experienced by the

floater assembly as a rigid body.

A free body diagram of the proposed quasi-zero stiffness maglev system is shown in Figure 4,

where !"# and !$% are the nominal (when the floater has zero angular displacement and the

floater COG is at the midpoint between the two centres of the fixed magnets) vertical

separations between the top and bottom magnet pairs, and 2& is the length of the floater

Page 12: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

12

assembly between the two centres of the floating magnets. In Figure 4, a Cartesian coordinate

system, with its origin at the midpoint between the two fixed magnets (the nominal operating

position), is used to describe the positions of the magnet centres and the poses of the floater

assembly. '( , ') , '* , '+ and ', are the positions of the centres of Magnet 1, Magnet 2,

Magnet 3, Magnet 4, and the floater respectively. -,(., /, 0) represents the angular

displacements of the floater, which are defined from the magnet coordinates as

. = tan4"(5 − 5#6# − 6) / = tan4"(7# − 76# − 6) 0 = tan4"(7# − 75# − 5)

(2)

From the expressions presented previously on the 3D to 1D calculation simplification, it can

be proven that �() has the same direction as the vector connecting the centres of Magnets 1

and 2 ('( − ')), and similarly for �+*. From Eq. (1), it can be shown that the components of

the forces acting between magnet pairs are given by

N

N

N

S

N

Magnet 1 (Fixed)

Magnet 2 (Floating)

Magnet 3 (Floating)

Magnet 4 (Fixed)

α β

γ

Z

Y

X

Figure 4: Free body diagram of the maglev system model.

'((7", 5", 6")

')(7#, 5#, 6#)

'*(7%, 5%, 6%)

'+(7$, 5$, 6$)

COG

',(7, 5, 6)

�()(�"#�, �"#�, �"#�)

�+*(�$%�, �$%�, �$%�)

2l

-,(., /, 0)

!"#

!$%

Page 13: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

13

�"#� = |�()|∙ (7" − 7#)|'( − ')|�"#� = |9()|∙ (5" − 5#)|'( − ')|�"#� = |9()|∙ (6" − 6#)|'( − ')|�$%� = |9+*|∙ (7% − 7$)|'* − '+|�$%� = |9+*|∙ (5% − 5$)|'* − '+|�$%� = |9+*| ∙ (6% − 6$)|'* − '+| :;

;;;;<;;;;;=

. (3)

To calculate the magnetic forces along the X, Y and Z directions, the coordinates of the four

magnets are required.

Magnets 1 and 4 are two fixed magnets. According to the geometric design of the maglev

system, with the nominal magnet separation ! = !"# = !$%, the distance between the centres

of the fixed magnets is ! + &. This gives

'( = [0 0 ! + &],'+ = [0 0 −! − &] (4)

as the coordinates of the fixed magnets. The coordinates of the floating magnets change with

the pose of the floater (', and -,). However, the coordinates of the floating magnets always

satisfy the following geometric constraints:

7# − 7 = −(7% − 7) 5# − 5 = −(5% − 5) 6# − 6 = −(6% − 6) (7# − 7)# + (5# − 5)# + (6# − 6)# = &#. (5)

Solving Eqs. (2) and (5) for 7#, 5#, 6#, 7%, 5% and 6% yields

Page 14: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

14

7# = & ∙ tan(/) ∙ > 1tan#(−.) + tan#(/) + 1 + 7

5# = & ∙ tan(−.) ∙ > 11 + tan#(−.) + tan#(−.)tan#(/) + 5

6# = & ∙ > 11 + tan#(−.) + tan#(/) + 6 7% = −& ∙ tan(/) ∙ > 1tan#(−.) + tan#(/) + 1 + 7

5% = −& ∙ tan(−.) ∙ > 11 + tan#(−.) + tan#(−.)tan#(/) + 5

6% = −& ∙ > 11 + tan#(−.) + tan#(/) + 6

(6)

Hence, for any arbitrary floater pose (7, 5, 6, ., /, 0), the coordinates of the floater magnet

centres can be calculated using Eq. (6). Substituting Eqs. (4) and (6) into Eq. (3) gives

�"#� = −|�()|(7 + & ∙ tan(/) ∙ ?)�(& + ! − 6 − & ∙ ?)# + (5 − & ∙ tan(.) ∙ ?)# + (7 + & ∙ tan(/) ∙ ?)# �"#� = −|�()|(5 − & ∙ tan(.) ∙ ?)�(& + ! − 6 − & ∙ ?)# + (5 − & ∙ tan(.) ∙ ?)# + (7 + & ∙ tan(/) ∙ ?)# �"#� = |�()|(& + ! − 6 − & ∙ ?)�(& + ! − 6 − & ∙ ?)# + (5 − & ∙ tan(.) ∙ ?)# + (7 + & ∙ tan(/) ∙ ?)# �$%� = |�+*|(7 − & ∙ tan(/) ∙ ?)�(7 − & ∙ tan(/) ∙ ?)# + (& + ! + 6 − & ∙ ?)# + (5 + & ∙ tan(.) ∙ ?)#

�$%� = |�+*|(5 + & ∙ tan(.) ∙ ?)�(7 − & ∙ tan(/) ∙ ?)# + (& + ! + 6 − & ∙ ?)# + (5 + & ∙ tan(.) ∙ ?)#

�$%� = |�+*|(& + ! + 6 − & ∙ ?)�(7 − & ∙ tan(/) ∙ ?)# + (& + ! + 6 − & ∙ ?)# + (5 + & ∙ tan(.) ∙ ?)#

(7)

where

? = > 1tan(.)# + tan(/)# + 1, (8)

Page 15: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

15

and the magnitudes of �() and �+* can be determined using the method described in [33].

Therefore, the 3D magnetic forces between the two pairs of magnets can now be calculated

for any given floater pose. Thus, the resultant forces and torques (�� , �� , �� , @A , @B , @C)

experienced by the COG of the floater may be calculated as

�� = �"#� + �$%� �� = �"#� + �$%� �� = �"#� + �$%� @A = �"#� ∙ (6 − 6#) + �$%� ∙ (6 − 6%) @B = �"#� ∙ (6# − 6) + �$%� ∙ (6% − 6) @C = 0. (9)

In Eq. (9), the torque around the floater COG in the γ direction is zero. This is due to the fact

that the resultant force vectors between top and bottom magnet pairs always intersect the Z

axis of the coordinate system shown in Figure 4.

4. 6-DOF levitation stiffness

It was mentioned previously that the proposed maglev isolator can realise quasi-zero stiffness

levitation in the vertical direction, and zero stiffness in the remaining five DOFs. This section

demonstrates the theoretical realisation of the quasi-zero/zero levitation stiffness.

4.1. Quasi-zero stiffness in the vertical direction (Z)

A major advantage of the proposed maglev isolator over traditional isolator designs is the

ability of the maglev system to realise quasi-zero payload support stiffness in the vertical (Z)

direction, while still providing a static payload supporting force. Figure 5(a) shows a case

where the floater motion is in the vertical direction. Using the calculation method outlined in

Section 3, the relationship between the vertical displacement (6 ) and the total vertical

magnetic force �� is shown in Figure 5(b), where ! = 100mm is chosen to be the nominal

separation between the magnets in this case. Table 2 lists the parameters of the magnets used

to obtain the plot data.

Page 16: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

16

In Figure 5(b), the slope of the tangent line to the force-displacement curve is the stiffness of

the levitation in the vertical direction. It can be seen that at the nominal operating position,

where the COG of the floater is at the midpoint between the two fixed magnets, the stiffness

of the levitation is zero. For a displacement (comparable to the displacement of ordinary

laboratory floor vibration) within a small region around the nominal operating position, the

levitation stiffness remains close to zero. Therefore, in the vertical direction, the magnetic

levitation has quasi-zero stiffness around the nominal operating point.

In Figure 5(b), the vertical magnetic force (��, approximately 39N in this case) at the nominal

operating position is the load capacity of the isolator. This vertical force is designed to

balance the weight of the payload and is not the result of elastic deformation of the

supporting structure. The magnitude of the payload supporting force is adjustable by

changing the separations between the top and bottom magnet pairs so that the supporting

force matches the payload weight. Therefore, the maglev system is able to provide quasi-zero

levitation stiffness while still generating a passive magnetic force to support the static weight

of the payload. This feature allows the 6-DOF maglev isolator design to avoid the usual

compromise made between load capacity and isolation performance, which normally exists in

linear vibration isolation systems.

In the preceding analysis of the maglev system, the floater motion was constrained in the

vertical direction. However, it is also important to investigate the sensitivity of the vertical

-30 -20 -10 0 10 20 3020

30

40

50

60

70

80

Vertical displacement of the floater (mm)

Ver

tica

l fo

rce

Fz

(N)

Normaloperatingposition

p=100mm

Slope=0Tangent line

XZ plane

Y

X

Z

p

p

N

S

N

N

S

S

F12Z

F43Z

z

Nominal operating condition

z = 0

Figure 5: Force displacement behavior of the maglev system in the vertical direction (Z). See Table 3 for details of parameters used to define the system, (a): Schematic of the maglev system; (b) Force-

displacement relationship in the vertical direction.

(a)

Nominal operating position

F

(b)

Page 17: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

17

magnetic force to the displacements in the remaining five DOFs since external vibrations

propagate in multiple directions. Using the equations derived in Section 3, the vertical

magnetic force, �D, was calculated with combined floater displacements.

The five subplots of Figure 6 show the magnitudes of the vertical force when the Z (vertical)

displacement is combined with the X, Y, α, β and γ displacements respectively. From Figure

6(a) to Figure 6(d), it can be seen in each case considered that the vertical magnetic forces are

dependent on the magnitudes of both of the displacements, and with any given vertical

displacement (6), the vertical force has the maximum value when the displacement in the

non-vertical direction is zero. The cross coupling from the X, Y, α and β directions to the Z

direction result from the magnet axial misalignments introduced by the corresponding

displacements. Motions in these four DOFs effectively increase the distances between the

magnets for both the top and bottom magnet pairs, thus reducing the forces generated

between the magnets. In addition, the axial misalignment between the floater magnets and the

fixed magnets means that only a portion of the total magnetic force is in the vertical direction,

which also explains why the vertical magnetic force is a maximum at zero non-vertical floater

displacements for any given vertical displacement. The cross-coupling effect is undesirable in

this instance where the maglev system is used as a vibration isolation device. The disturbance

to the vertical direction may be introduced from other DOFs through cross-coupling effects.

However, it can be observed from Figure 6 that, under the nominal operating condition (the

floater has zero displacements and poses), the cross-coupling stiffness is quasi-zero between

Z and the four non-vertical DOFs (X, Y, α and β). Therefore, during operation of the maglev

isolator, the floater should be levitated at the nominal operating position to optimise the

vibration isolation performance in multiple DOFs.

Figure 6(e) shows that the vertical force generated by the maglev system is not affected by

the displacement in the γ direction. This can also be observed from the system model in

Figure 4 which shows that the γ displacement does not influence the relative positions

between the two magnet pairs.

Page 18: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

18

Figure 6: Floater force-displacement behavior of F� with cross-DOF displacements, (a): F� in the ZX plane; (b): F� in the ZY plane; (c): F� in the Zα plane; (d): F� in the Zβ plane; (e): F� in the Zγ plane.

(a) (b)

(c)

(d)

(e)

Page 19: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

19

4.2. Zero stiffness in the horizontal directions (X and Y)

As mentioned previously, the proposed maglev system is able to achieve zero levitation

stiffness in the horizontal directions (X and Y). Figure 7 shows a free body diagram of the

floater in the YZ plane with a displacement in the Y direction. The forces experienced by the

floater from both pairs of fixed magnets are resolved as shown in the figure. With floater

displacement only in the Y direction, the magnetic force calculation may be simplified to

E;;;F;;;G�"#� = |F"#| ∙ −5

�5# + !"##�"#� = |F"#| ∙ !

�5# + !"##�$%� = |F$%| ∙ 5

�5# + !$%#�$%� = |F$%| ∙ !

�5# + !$%#

(10)

Under the nominal operating condition, where !"# = !$%, it can be observed that the vector

forces between the two pairs of magnets have the same magnitudes, i.e. |�()| = |�+*|. Hence,

from Eq. (10), it can be shown that

�� = �"#� + �$%� = 0 (11)

F12Y

F12Z

!"#

!$%

2l

5 COG Tα

F43Z

F43

F43Y

N

S

N

N

S

YZ plane

X

Y

Z

F12

Figure 7: Free body diagram of the floater under horizontal displacement

Page 20: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

20

for all values of 5. Therefore, the total force experienced by the floater in the Y direction is

zero regardless of the displacement, which leads to the conclusion that the stiffness in the Y

direction remains zero under the nominal operating condition. The derivations for

demonstrating the zero levitation stiffness in the X direction are identical to the preceding

discussion. For a displacement in the X direction, the equations for calculating the relevant

forces in the XZ plane become

E;;;F;;;G�"#� = |F"#| ∙ −7

�7# + !"##�"#� = |F"#| ∙ !

�7# + !"##�$%� = |F$%| ∙ 7

�7# + !$%#�$%� = |F$%| ∙ !

�5# + !$%#

. (12)

Hence, under the nominal operating condition, where |�()| = |�+*|, the total magnetic force

in the X direction can be shown to be equal to zero using the same principles. With evidence

of zero stiffness levitation in both the X and Y directions, it is reasonable to conclude that the

levitation stiffness equals zero in any arbitrary direction within the XY plane.

The realisation of zero levitation stiffness in the horizontal plane (XY plane) requires equal

distances between the two magnet pairs. However, this cannot always be guaranteed during

operation of the isolator due to the multi-DOF nature of the external vibration. Hence, the

force displacement behaviour of the horizontal floater forces was also analysed under

combined displacements. Figure 8 and Figure 9 show the cross-DOF force-displacement

behaviours for displacements in the X and Y directions respectively.

It can be seen from Figure 8(a) and Figure 9(a) that the horizontal force in either the X or Y

direction remains zero for any displacement in the XY plane (the color gradient on the flat

plane is caused by the force calculation uncertainties, which are on the order of 10-14N). This

result agrees with the expression for the zero horizontal stiffness derived previously. Figure

8(b) and Figure 9(b) show that the displacement in the vertical direction changes the zero

stiffness property of the maglev in both the X and Y directions. This is because the vertical

displacement interrupts the condition, |�()| = |�+*|, needed for achieving the zero horizontal

stiffness. As shown by Figure 8(b), the vertical displacement changes the horizontal stiffness

Page 21: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

21

linearly from HIJHK = 0N/m at 6 = 0mm to a maximum of

HILHK = 55.033N/m at 6 = 3mm

(displacement constraint from the mechanical isolator design shown in Section 5). At the

magnet nominal separation ( ! = 100 mm) used in this analysis, the vertical payload

supporting force is 39.13N (Figure 5(b)). This corresponds to a payload of approximately 4kg.

Hence, with this combination of payload mass and system stiffness, the natural frequency of

the system in the horizontal direction is OPJ = "#Q R ST = 0.5903Hz. This indicates that, even

with the highest induced stiffness, the system can still be expected to provide excellent

vibration isolation in the X direction. Therefore, with small vertical excitations (comparable

to the magnitude of laboratory floor vibration), the induced stiffness in the horizontal

directions has no significant impact on the vibration isolation performance in the X direction.

The same conclusion can be made from Figure 9(b) for the Y direction.

Figure 8(d) and Figure 9(c) show the cross couplings between the β and X directions and the

α and Y directions respectively. The figures show that with a given angular displacement in

the β direction, a constant force in the X direction is created for all values of 7 (displacement

in the X direction). Similarly, a given α displacement will have the same effect in the Y

direction. These cross-coupling effects can also be analytically observed from Figure 10,

which shows that a floater rotation in the α direction creates a horizontal force in the Y

direction, and is calculated as

�� = �"#� + �$%� (13)

for the cross-coupled force in the Y direction, and

�� = �"#� + �$%� (14)

for the cross-coupled force in the X direction. These cross-coupling effects are undesirable in

terms of vibration isolation since they introduce disturbances into the horizontal direction

from the rotational excitations. However, with the small rotational excitations from

laboratory floor vibration, this cross-coupling effect is not expected to introduce significant

disturbance to the performance of the system in the horizontal directions.

Page 22: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

22

Figure 8: Floater force-displacement behavior of F� with cross-DOF displacements, (a): F� in the XY plane; (b): F� in the XZ plane; (c): F� in the Xα plane; (d): F� in the Xβ plane; (e): F� in the Xγ plane.

(a) (b)

(c) (d)

(e)

Page 23: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

23

Figure 9: Floater force-displacement behavior of F� with cross-DOF displacements, (a): F� in the YX plane; (b): F� in the YZ plane; (c): F� in the Yα plane; (d): F� in the Yβ plane; (e): F� in the Yγ plane.

(e)

(a) (b)

(c) (d)

Page 24: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

24

4.3. Zero stiffness in the rotational DOFs (α, β and γ)

The levitation stiffness of the proposed maglev system is also zero in the three rotational

DOFs. An example is shown in Figure 10 where the floater is rotated within the YZ plane by

a rotational displacement (-α). The torque generated by the magnetic forces around the centre

of the floater can be calculated as

@A = �"#� ∙ &X − �$%� ∙ &X, (15)

where &′ is the vertical distance between the centre of the floater and the floater magnet and is

the lever arm for the torque. For simplicity of the analysis, the torque calculation only

considers the mechanical torque created by the horizontal forces on the floater from the fixed

magnets. The magnetic torque [36] between the magnet pairs is neglected due to its small

value. For a horizontal displacement within [-3mm 3mm] (constrained mechanically by the

isolator design presented in Section 5), the largest magnetic torque was calculated to be 2.89

percent of the mechanical torque generated by the horizontal forces (�"#�and�$%�).

It is evident from Figure 10 that when the floater is at the nominal operating condition (equal

nominal separation between the magnet pairs), the horizontal forces, �"#�and �$%�, have the

same magnitude. Therefore,

@A = �"#� ∙ &X − �$%� ∙ &X = 0. (16)

This shows that for any rotational displacement in the α direction, @A = 0. Therefore, the

floater has zero levitation stiffness in the α direction. Due to symmetry, the same principles

can be applied to demonstrate the zero stiffness property of the maglev in the β direction.

Page 25: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

25

The preceding analysis assumed zero floater displacement in the remaining DOFs. To

investigate the torque displacement behaviour in the 6-DOF space, the mechanical torque on

the floater was examined for cases with combined displacements. Figure 11 and Figure 12

show the torque-displacement behaviour of the floater for various displacement combinations.

In Figure 11(b) and Figure 12(a), cross coupling is shown between the Y and α directions and

the X and β directions respectively. For a given horizontal displacement in the Y direction, a

constant torque is generated for all angular displacements, ., and with a fixed displacement

in X, a constant torque is created in the β direction for all /. This cross-coupling effect can

also be demonstrated analytically for horizontal displacement, 5, as illustrated in Figure 7.

The mechanical torque created is

@A = �"#� ∙ & − �$%� ∙ &. (17)

Similarly, with an 7 displacement, the torque in the β direction is

@B = −�"#� ∙ & + �$%� ∙ &. (18)

p12

p43 YZ plane

X

Y

Z

N

S

F12

F43 F43Z

F43Y

F12Y

F12Z

COG

FY -α

Figure 10: A schematic of the floater under rotational displacement.

&’&’Tα=0

Page 26: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

26

Figure 11: Floater force-displacement behavior of TA with cross-DOF displacements, (a): TA in the αX plane; (b): TA in the αY plane; (c): TA in the αZ plane; (d): Tα in the αβ plane; (e): Tα in the αγ plane.

(e)

(a) (b)

(c)

(d)

Page 27: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

27

Figure 12: Floater force-displacement behavior of TB with cross-DOF displacements, (a): TB in the βX

plane; (b): TB in the βY plane; (c): TB in the βZ plane; (d): Tβ in the βα plane; (e): Tβ in the βγ plane.

(a)

(b)

(c)

(d)

(e)

Page 28: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

28

In Figure 11(c) and Figure 12(c), a similar cross-coupling effect is shown between the

vertical (Z) and the rotational (α and β) directions. The displacement in the Z direction

increases the rotational stiffness of the maglev linearly from 0Nm/rad to a maximum of

H]̂H_ = 0.4952Nm/rad at 6 = 3mm. For the mechanical design of the isolator, the floater

moment of inertia is a��= 0.0853kgm2 (Table 3). Therefore, in the α direction, the maximum

natural frequency is OPb = "#QR ScJJ = 0.3835Hz, which is an indication of the excellent

rotational vibration isolation that is potentially achievable by the system even at the largest

rotational stiffness induced by cross coupling. Therefore, with the small rotational excitation

that the isolator would experience during normal operation, the introduced rotational stiffness

is not expected to influence the vibration isolation performance of the maglev isolator in the

rotational DOFs.

In the proposed maglev vibration isolation system, the levitation stiffness is zero in the γ

direction. This is due to the fact that the system is axisymmetric and as such there are neither

mechanical constraints nor magnetic force constraints on the floater. The floater is able to

move freely without any interference, and the γ direction is only actively stabilised using the

maglev positioning control (discussed in Section 6). Therefore, theoretically, the maglev

system itself has inherent zero stiffness in the γ direction.

5. Mechanical system of the isolator

In order to validate the theoretical performance of the proposed vibration isolator design, a 6-

DOF maglev vibration isolator was designed and manufactured. This section provides and

overview of the mechanical design of the isolation system.

Figure 13(a) shows a photograph of the constructed isolation system, and Figure 13(b) is a

schematic highlighting the maglev components in the mechanical design. The isolator design

uses the Payload Connectors to attach the payload to the floater for achieving vibration

isolation for the payload. This design allows the isolator to be connected to any mechanical

system that is attachable to the payload connectors. Multiple isolators may also be combined

to suit a wide range of applications. For example, four isolators could be installed at the

corners of a rectangular table top to create a vibration isolation platform.

Page 29: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

29

As discussed in Section 4.1 that the load capacity of the isolator can be adjusted through

changing the separations between the permanent magnets. In order to control the magnet

separation, two Magnet Position Control units (Figure 14) driven by DC servo motors, were

installed at the top and bottom of the vibration isolator frame and used to control the positions

of the permanent magnets. A threaded linear drive system was used on each Magnet Position

Control unit to transfer motor rotation to the required linear motion for relocating the magnet

in the vertical direction.

In the maglev vibration isolator, twelve solenoids and six laser sensors are used to control and

monitor the position of the floater respectively in the 6-DOF space. The structure and

working principles of the actuation and sensing systems are discussed in Section 6. The

physical properties of the isolation system are listed in Table 3, and Table 4 shows the

specifications of the isolation system electronics.

Figure 13: Illustration of the components of the 6-DOF maglev vibration isolator, (a): Photograph of the maglev isolation system; (b): Schematic of the maglev system

(a) (b)

v

Page 30: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

30

Table 3: Physical properties of the vibration isolation system.

Item Description

Frame material Aluminium 6061-T6

Weight Frame: 19.6kg Floater: 6.4kg

Floater moments of inertia aee = 0.0853kgm2 aff = 0.0851kgm2 agg = 0.0186 kgm2

Dimensions Length: 230mm Width: 230mm Height: 1020mm

Primary magnet Magnet 1 to 4

Ø50.8mm × 25.4mm; Grade: N52; Magnetisation: 1.48T

Actuator magnet (Refer to Figure 15)

Ø19.05mm × 76.2mm; Grade: N52; Magnetisation: 1.48T

Max. allowable vibration Translational: ±3mm; Rotational: ±0.85deg

Table 4: Specification of system electronics.

Item Description

Laser sensor Model: Acuity AR200; Range: 21±6mm; Resolution: 3µm; Output: analogue ±10 V; Max. sampling frequency: 1250Hz

Coil (actuator) Number of turns: 1000; Wire diameter: 0.85mm; Resistance 3.7Ohm; Inductance: 95mH; Sensitivity: 3.04N/A

Actuator amplifier Model: Maxon LSC30/2 4-Q-DC; Operation mode: current control; Max. current output:±2A

Magnet positioning motor Model: Maxon EC 45 flat; Power: 50W; Controller: EPOS2 24/5

Primary Magnet

Timing Pulley

Timing Belt

Threaded Linear Drive

Drive Motor

Figure 14: Detailed view of the Magnet Position Control unit.

Page 31: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

31

6. Maglev stabilization system

As previously mentioned, passive magnetic levitation is inherently unstable [25]. Therefore,

an active stabilization system is necessary to enable the operation of the maglev system. In

this design, the maglev stabilization is comprised of a 6-DOF laser position monitoring

system and a 6-DOF actuation system, shown in Figure 15 and Figure 16 respectively.

Floater Assembly

Frame Assembly

Solenoids Actuator Magnets

(a)

Z

Y

X

Figure 16: The Frame Assembly, (a) Assembly with 4 solenoids used to control the floater motion in the XZ plane; (b) Assembly with 12 solenoids for full 6-DOF floater motion control.

(b)

Y

X

Z

Figure 15: 6-DOF laser position monitoring system.

Page 32: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

32

The laser position sensing system includes six laser sensors fixed to the frame to provide

displacement data of the levitated floater. The laser sensors are arranged to monitor the

motion of the six points on the floater as shown in Figure 15. The six coordinates (x, y, z, α, β

and γ) of the COG of the floater are then derived based on the displacements measured by the

laser sensors according to

7 = 7" + 7#25 = 5" + 5#26 = 6" + 6#2. = arctan5# − 5"kl/ = arctan 6# − 6"kD0 = arctan7# − 7"km

:;;;;;<;;;;;=

, (19)

where 7n, 5n and 6n represent the displacement readings from the accordingly named sensors,

and Lx = Ly = Lz = 270mm are the distances between each pair of laser monitoring points (e.g.,

Lx is the distance between the laser points of sensors X1 and X2).

The 6-DOF actuation system consists of six pairs of solenoids. Each pair of solenoids is

coupled with one actuator magnet attached to the floater, and is driven in series in order to

double the actuation capacity on each actuator magnet compared to the capacity achievable

from only one solenoid. Figure 16(a) show two pairs of solenoids attached to the frame

assembly in the XZ plane. By driving both pairs of solenoids collectively, forces can be

generated in the Z direction, and by driving the two pairs differentially, torques are generated

in the β direction. The two pairs of actuators in the XZ plane have the ability to control the

floater motion in the two DOFs (Z and β) within the XZ plane. Therefore, with the six pairs

of solenoids installed as shown in Figure 16(b), the floater motion is controllable in all six

DOFs. The relationships between the individual actuation forces from each of the solenoids

and the resultant force/torque experienced by the floater are

Page 33: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

33

�X = OXa + OXb + OXc + OXd�Y = OYa + OYb + OYc + OYd�Z = OZa + OZb + OZc + OZd@α = 12 k′X pqOZa + OZbr − qOZc + OZdrs@β = 12 k′Y pqOXa + OXbr − qOXc + OXdrs@γ = 12 k′Z pqOYa + OYbr − qOYc + OYdrs

:;;;<;;;=, (20)

where Ovw (k ∈(X, Y, Z), l ∈(a, b, c, d)) represents the actuation force generated by the

solenoid labelled accordingly, and k′y (m ∈(X, Y, Z)) represents the distance between the

point of actuation and the centre of gravity of the floater on each axis. Due to the fact that

every pair of solenoids is driven in series to generate an equal actuation force, Eq. (20) can

then be simplified to

�X = 2OXa + 2OXc�Y = 2OYa + 2OYc�Z = 2OZa + 2OZc@α = 12 k′X pq2OZar − q2OZcrs@β = 12 k′Y pq2OXar − q2OXcrs@γ = 12 k′Z pq2OYar − q2OYcrs

:;;;<;;;=. (21)

The mechanical design of the actuation system is such that the actuation forces/torques in

each DOF are orthogonal to all the other DOFs, that the actuation system is theoretically

decoupled in the 6-DOF space. This can be seen from Eq. (21) since there always exists a set

of unique solutions to the solenoid forces (fXa, fXc, fYa, fYc, fZa, fZc) for an arbitrary given set of

required actuation forces/torques (��, ��, ��, @A, @B, @C ). Therefore, the actuation system is

decoupled in the 6-DOF space, and SISO (single input single output) control loops may be

used to allow decoupled performance control for stabilising the maglev in each DOF.

However, in practice, slight coupling effects may exist between the translational and

rotational DOFs for a number of reasons. The solenoid actuators may not be identical on both

sides of the floater (refer to Figure 16(a)), which can lead to an undesired torque being

generated while the solenoid pairs are driven collectively for vertical actuation. The offset

between the geometric and gravity centres of the floater may also contribute to the cross

coupling, since the actuation is applied with respect to the geometric centre of the floater,

Page 34: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

34

while the floater motion is subject to its centre of gravity. These aspects have been considered

in the mechanical design of the isolator to minimize the cross coupling in the actuation

system.

In the maglev isolation system, a dSPACE DS1103 platform is used to execute the controller

designs. Matlab Simulink and dSPACE Control Desk are used to design and configure the

controller algorithms respectively. Figure 17 shows the structure of the maglev stabilization

controller. Six PID controllers are used in parallel for floater position regulation in six DOFs.

The PID type controller was chosen for its ability to directly control the levitation stiffness

and damping. The feedback signals to the PID controllers are the floater displacements

relative to the frame in each DOF (given by Eq. (19)). Therefore, the proportional gains

directly control the levitation stiffness and the derivative gains control the relative damping

of the floater with respect to the frame. In order to isolate ground vibration, low stiffness is

desirable as it reduces the system resonance frequency, and thus, vibration transmissibility.

The gains in the PID controllers were tuned in the frequency domain in order to achieve

minimum system natural frequency and transmissibility.

7. Experimental results and discussions

A number of tests were completed to quantify the performance of each subsystem, as well as

the ground vibration transmissibility of the system. This section will present the experimental

performance of the maglev stabilization controller and the isolator transmissibilities in all six

DOFs.

Figure 17: Structure of the maglev stabilization controller.

Isolator

- +

6-D position

command

[x, y, z, α, β

, γ]

dSPACE DS1103

6 × PID SISO loops

in series with LP

filters (Eq. (22))

Coordinate transformatio

6 × Maxon

LSC30 current

amplifier

6-DOF actuation

6-DOF laser position

monitoring

FX FY FZ

Tα Tβ Tγ

Coordinate Transformation

Eq. (19)

[x1, x2, y1,

y2, z1, z2]

Page 35: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

35

7.1. Performance of the maglev stabilization control

The performance of the maglev stabilization control is critical to the overall performance of

the vibration isolator. The active control forces resulting from the levitation stabilization

controller can significantly increase the vibration amplitude on the floater. Therefore, this

self-induced vibration from the levitation stabilization system must be kept within an

acceptable range for the intended application. To avoid excitation of high frequency

structural modes of the floater assembly, a second order low-pass filter is used in series with

each PID controller to attenuate the control signal beyond 200Hz. The transfer function of the

low-pass filters is given as

k{(|) = }#(| + })# , } = 200Hz = 1257rad/s (22)

where k{(|) and } represent the transfer function and the cut off frequency of the filter

respectively. The transfer function of the PID controllers is

�(|) = {n + �n| + ��| (23)

where �(|) represents the controller transfer function, and {n, �n and �� (� ∈ [X, Y, Z, α, β, γ]) represent the proportional, integrative and derivative gains of the ith PID controller.

In order to isolate vibration, low stiffness is desirable for reducing the system resonance

frequency and post-resonance vibration transmissibility. The PID controller gains were tuned

in the frequency domain to achieve minimum system natural frequency and transmissibility

while maintaining the stability of the maglev. Table 5 contains a set of PID gains that has

been found to achieve low natural frequency and low relative damping while also

maintaining stable levitation with acceptable peak response.

Page 36: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

36

Table 5: Levitation stabilization controller gains used for transmissibility measurements.

Item Value Item Value

PX 2250 N/m Pα 320 Nm/rad

IX 112.5 N/m•s Iα 240 Nm/rad•s

DX 26.3 N•s/m Dα 3.4 Nm•s/rad

PY 2250 N/m Pβ 320 Nm/rad

IY 112.5 N/m•s Iβ 240 Nm/rad•s

DY 26.3 N•s/m Dβ 3.4 Nm•s/rad

PZ 675 N/m Pγ 64 Nm/rad

IZ 67.5 N/m•s Iγ 24 Nm/rad•s

DZ 6 N•s/m Dγ 1.2 Nm•s/rad

The residual vibration levels on the floater during levitation were measured in six DOFs for

the PID gains listed in Table 5. Figure 18(a) shows the translational vibrations in the X, Y

and Z directions in a quiet laboratory environment, and are comprised of ground-borne

vibration and vibration induced by sensor noise and amplifier noise from the active control

loops. The translational vibrations are compared with the VC-E vibration criterion [37],

which is the most demanding criterion specified for the operation of extremely vibration-

sensitive equipment. The results show that, in the translational directions, the magnitude of

the residual vibration on the floater is below the VC-E threshold, which is an indication of the

satisfactory performance achieved by the maglev stabilization system. The self-induced

vibrations in the rotational DOFs are shown in Figure 18(b). To the best knowledge of the

authors, no vibration standard exists yet to assess the system performance in the rotational

DOFs.

(a) (b)

Figure 18: Levitation induced vibration: (a) in the X, Y and Z directions; (b) in the α, β and γ directions.

100

101

102

-220

-200

-180

-160

-140

-120

Vib

ration V

elo

city

(dB

re.

1 r

ad/s

ec)

Frequency (Hz)

alpha

beta

gamma

100

101

102

-20

0

20

40

60

80

Vib

ration V

elo

city

(dB

re.

1 m

icro

-inch/s

ec)

Frequency (Hz)

X

Y

Z

VC-E

Page 37: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

37

7.2. Vibration transmissibility

Apart from the vibration induced by the levitation system, the external vibration

transmissibilities are the most important performance measure of the 6-DOF maglev isolator.

In order to obtain the transmissibility measurements in six DOFs, a testing platform was

designed and constructed. Figure 19 shows a photograph of the testing platform assembly

configured for excitation in the Y direction. The design of the testing platform allows it to be

assembled in five additional ways to allow excitations in the other five DOFs.

The velocity transmissibilities of the isolator were measured in all six DOFs. A set of six

geophones (SENSOR model LF-24) were installed on both the floater and the isolator frame

to quantify the amount of vibration attenuation achieved. Six experiments were conducted to

capture the isolator transfer function in each of the six DOFs. During each measurement, the

isolator frame was excited predominately in one DOF using a high capacity shaker (MB

Dynamics model 110) with a swept sine input signal, and the vibration transmissibilities were

recorded by a Brüel & Kjær Photon+ dynamic signal analyser. Figure 20 shows the measured

transmissibilities of the isolator in six DOFs with the PID controller gains described in Table

5.

Figure 19: 6-DOF vibration transmissibility testing platform (current view shows Y direction excitation).

Page 38: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

38

In Figure 20, the solid lines represent the measured isolator responses to the external

vibrations in each of the six DOFs, and the dashed lines are the theoretical responses of the

isolation system assuming zero stiffness in all directions. The theoretical zero stiffness

system responses are derived using the control system structure described in Figure 21, which

is a schematic of each PID control loop for stabilizing a single DOF. The control system has

six such loops to stabilize the floater in 6-DOF. The derivation of the theoretical zero-

stiffness responses is based on the following:

• The plant (the isolation system) has negligible inherent damping due to non-

contact magnetic levitation.

• The system responses of the Solenoid Actuator, Actuator Amplifier and Laser

Sensor are linear in the frequency range of measurement in (0.5-20Hz).

Figure 20: Vibration transmissibilities in the six DOFs, (a): X direction; (b): Y direction; (c): Z direction; (d): α direction; (e): β direction; (f): γ direction; (solid curve: measured isolator response; dashed curve: predicted

isolator response with zero inherent stiffness).

100

101

-30

-20

-10

0

10

20

30

Frequency (Hz)

(a)

Tra

nsm

issib

ility

in X

(dB

)

Experimental

Theoretical

100

101

-30

-20

-10

0

10

20

30

Tra

nsm

issib

ility

in Y

(dB

)

Frequency (Hz)

(b)

Experimental

Theoretical

100

101

-30

-20

-10

0

10

20

30

Frequency (Hz)

(c)

Tra

nsm

issib

ility

in Z

(dB

)

Experimental

Theoretical

100

101

-15

-10

-5

0

5

10

15

Frequency (Hz)

(d)

Tra

nsm

issib

ility

in A

lpha (

dB

)

Experimental

Theoretical

100

101

-15

-10

-5

0

5

10

15

Tra

nsm

issib

ility

in B

eta

(dB

)

Frequency (Hz)

(e)

Experimental

Theoretical

100

101

-15

-10

-5

0

5

10

15

Frequency (Hz)

(f)

Tra

nsm

issib

ility

in G

am

ma (

dB

)

Experimental

Theoretical

Page 39: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

39

• The laser displacement sensors are attached to the Frame Assembly of the isolator

and hence the motion of the reference points of the laser sensor measurements

have the same amplitude and phase as the external vibration.

Therefore, with zero isolator stiffness in all the DOFs, and in the absence of the feedback

controller, the transfer function of the plant may be simplified to

�n(|) = 1�|# ; ��(|) = 1ann|#, (24)

where � is the mass of the floater,aii is the floater moment of inertia with respect to its COG,

�n(|) and �j(|) (i ∈(X, Y, Z) and j ∈ (α, β, γ)) represent the transfer function of the plant in

the translational and rotational DOFs respectively. With the simplified plant transfer

functions, the frequency response of the controlled levitation to external vibration is

analogous to a linear mass-spring-damper system with the stiffness and damping from the

PID controller. This frequency response is obtainable through the closed-loop transfer

function of the system, written as

@�n(|) = �(|) × k{(|) × �n(|)1 + �(|) × k{(|) × �n(|)@��(|) = �(|) × k{(|) × ��(|)1 + �(|) × k{(|) × ��(|):;<

;=, (25)

where TFi(|) and TFj(|) represent the system transfer functions in the translational and

rotational DOFs respectively. Substituting Eqs. (22), (23) and (24) into Eq. (25) yields

PID LP

Filter

Laser Sensor

Solenoid

Actuator

Actuator

Amplifier Plant + _

+ + External Vibration

Figure 21: Schematic of the individual PID stabilization control loops.

Command Floater Position

Page 40: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

40

@�n = }#�n|# + }#{n| + }#�n�|� + 2�}|$ +�}#|% + }#�n|# + }#{n| + }#�n@�� = }#��|# + }#{�| + }#��ann|� + 2ann}|$ + ann}#|% +}#��|# + }#{�| + }#��:;<

;=, (26)

which are the transfer functions used to derive the theoretical system responses in Figure 20

assuming zero inherent stiffness of the maglev system in all six DOFs. In Eq. (26), } is the

cut-off frequency of the low-pass filters; {n , �n , �n and {� , �� , �� are the proportional,

integrative and derivative gains of the PID controllers for stabilising levitation in the

translational and rotational DOFs respectively. The floater mass and moments of inertia are

provided in Table 3, and the PID gains used in the transmissibility tests are listed in Table 5.

The measured isolator responses in all six DOFs shown in Figure 20 reveal similar behaviour

to the predicted isolator response derived with the inherent levitation stiffness assumed to be

zero in all directions. Therefore, it is practically demonstrated that the proposed maglev

isolation system has the ability to realise inherent zero-stiffness levitation in all six DOFs.

Figure 20 also shows that the isolator system response is dominated by the gains of the PID

controllers since the experimental results are comparable to the theoretical response derived

with consideration of the influence of the control system dynamics alone. The PID gains used

during the transmissibility measurements were found to be a suitable combination for both

minimising the vibration transmissibility and maintaining a stable levitation based on the

current mechanical and electronic system used in the isolator prototype. With improved

hardware quality, such as improvements to the uniformity of magnetisation of the magnets,

the mechanical component alignment, the laser sensor resolution, the electronic system noise,

the solenoid actuator performance, and the amplifier performance, the stability of the maglev

system may be achieved with lower controller stiffness. This would potentially result in

improved vibration isolation performance. The potential of the proposed maglev vibration

isolation method is thus currently limited by the quality of the hardware, rather than physical

limits relating to the proposed method.

Figure 20(c) shows a small difference between the resonance frequencies in the experimental

and theoretical results. This is due to the fact that quasi-zero stiffness levitation in the vertical

(Z) direction only exists for small displacements from the nominal operation position. Due to

the relatively low isolator resonance frequency in the Z direction, large amplitude excitations

(approximately ±2.5mm floater displacement relative to the frame assembly) were used in

Page 41: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

41

the transmissibility measurements. This level of excitation was necessary to overcome the

initial static friction in the linear bearings used in the testing apparatus, as well as to ensure

high signal to noise ratio in the inertial sensors (geophones). The large floater offset from the

nominal operating position resulted in a small amount of additional stiffness caused by the

vertical magnetic forces, and this effect slightly increased the overall resonance frequency of

maglev isolator in the vertical direction. However, in practical situations of relevance, the

magnitude of typical indoor vibration in the vertical direction is expected to be substantially

smaller than the excitation amplitude used here. Hence, the maglev system is expected to

maintain the quasi-zero stiffness levitation in the vertical direction during normal operation.

According to Figure 20, the experimental and theoretical resonance frequencies for the X, Y

and Z directions are approximately 2.9Hz, 3Hz, 1.8Hz and 3Hz, 3Hz, 1.6Hz respectively.

Vibration attenuation achieved experimentally at 10Hz is -17dB, -15dB and -28dB in the X,

Y and Z directions. These performance measures are comparable to the top of the range

active vibration isolation products offered in the market, such as products from Newport [3]

and Herzan [4]. In addition, the maglev isolator proposed in this paper achieves passive

payload weight support using forces from permanent magnets, which allows the system to be

stabilised with minimal power consumption. Experiments have shown that the maglev only

consumes less than 1W of electricity for levitating a mass of 6.693kg (floater weight with the

added geophones for measurements), much of which is due to parasitic losses in the linear

power stage of the actuator amplifiers.

As mentioned previously, the performance of the developed isolation system is dominated by

the characteristics of the maglev stabilization controller. The vibration isolation performance

may be improved with system hardware of higher quality. As the proposed maglev system is

actively stabilised, the performance of the isolator is able to be actively tuned to satisfy the

requirements for different applications. For example, low controller gains can be used to

address ground vibration isolation, while high controller gains may be used to realise low

isolator compliance to eliminate on board equipment vibrations.

In Figure 20(a), the peak response of the isolator in the X direction shows a larger amplitude

than the theoretical response. This may be caused by a cross-coupling effect existing on the

vibration testing platform. For excitation frequencies above 3Hz, the limited rigidity of the

excitation platform is not able to constrain the excitation energy to be purely within a single

Page 42: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

42

DOF. This phenomenon can also be observed in Figure 22 as the coherences of most of the

cross-coupling measurements show a significant increase beyond 3Hz. The cross coupled

excitation energy is transmitted into the floater through the complex mechanical linkages of

the excitation platform, and results in increased floater vibration at the resonance frequency

in the X direction.

Figure 20(d) and Figure 20(e) show the frequency responses of the isolator in the α and β

directions. The unpredicted behaviour of the isolator responses at low frequencies is a result

of coupling with the gravitational field. During the measurements of the rotational

transmissibility of the isolator, large excitation angles were used to obtain accurate

measurements at low frequencies. This caused a large misalignment between the magnetic

payload supporting force and the gravitational field, which resulted in the unexpected floater

movements at low frequencies.

7.3. 6-DOF isolator cross coupling

The cross-coupled transmissibility of the proposed maglev vibration isolator was measured

between all six orthogonal DOFs through six experiments. In each experiment, the isolator

was excited in predominately one DOF, and the vibration velocity of the floater was recorded

in all six DOFs. Figure 22 shows the measured transmissibility between each pair of DOFs.

The transmissibility plots are mapped from the column index to the row index; for example,

the amplitude of cross transmissibility from the Y direction to the α direction is shown by the

plot in column two and row seven. The coherence of each measurement is shown in the

coherence (Coh) plot located directly below each transmissibility amplitude (Amp) plot. Plots

in Figure 22 are arranged as:

• First quadrant (plots in row 1 to 6 and column 4 to 6):

Transmissibility measurements from the translational DOFs to the rotational DOFs

• Second quadrant (plots in row 1 to 6 and column 1 to 3):

Transmissibility measurements from the translational DOFs to the translational DOFs

• Third quadrant (plots in row 7 to 12 and column 1 to 3):

Transmissibility measurements from the rotational DOFs to the translational DOFs

• Fourth quadrant (plots in row 7 to 12 and column 4 to 6):

Transmissibility measurements from the translational DOFs to the rotational DOFs

Page 43: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

43

100

101

-80-60-40-20

020

Am

p (

dB

)

100

101

0

0.5

1

Coh

100

101

-80-60-40-20

020

Am

p (

dB

)

100

101

0

0.5

1

Coh

100

101

-80-60-40-20

020

Am

p (

dB

)

100

101

0

0.5

1

Co

h

100

101

-80-60-40-20

020

Am

p (

dB

)

100

101

0

0.5

1

Coh

100

101

-80-60-40-20

020

Am

p (

dB

)

100

101

0

0.5

1

Coh

100

101

-80-60-40-20

020

Am

p (

dB

)

100

101

0

0.5

1

Frequency (Hz)

Coh

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

Frequency (Hz)

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

Frequency (Hz)

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

Frequency (Hz)

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

Frequency (Hz)

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

100

101

-80-60-40-20

020

100

101

0

0.5

1

Frequency (Hz)

Figure 22: Measurements of the cross coupling between DOFs. Horizontally across represents the input axis, vertically represents the response axis (FFT properties: DC coupled, 128 averages, 1600 lines,

Hanning window, 24,000Hz sampling frequency).

X (m) Y (m) Z (m) α (rad) β (rad) γ (rad)

X (

m)

Y (

m)

Z (

m)

α (

rad

) β (

rad

) γ

(rad

)

Page 44: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

44

It can be seen that the diagonal plots (X to X, Y to Y, Z to Z, α to α, β to β and γ to γ) in the

second and fourth quadrants have significantly higher amplitudes (by approximately 40 dB

on average) than the cross-DOF transmissibilities. This indicates that each translational DOF

is highly decoupled from the other translational DOFs, and each rotational DOF is also

decoupled from the other rotational DOFs. As discussed in Section 4, the maglev system has

cross coupling between the X and β directions, as well as between the Y and α directions.

These cross couplings can be observed in the measurements shown by the plots in the first

and third quadrants. Plots X to β, β to X, Y to α and α to Y all show relatively high (close to 1)

values of coherence, which indicate the cross-coupling effects between the X and β, and the

Y and α directions. The cross couplings shown from the α and β directions into the Z

direction are caused by the misalignments between the directions of the payload supporting

force and gravity. As discussed previously, these misalignments are a result of the large

amplitudes of excitation used to capture isolator transmissibilities at low frequencies.

In Figure 22, the coherence curves of all the cross transmissibility measurements show values

close to 1 beyond 3Hz. This is due to the finite stiffness of the testing platform which allowed

excitation energy in the testing DOF to couple into other DOFs of the testing platform.

8. Conclusion

This paper presents the theory and implementation of a high performance 6-DOF vibration

isolator based on the quasi-zero stiffness maglev system. The theories and experimental

validations presented in this paper reveal the potential of the proposed maglev system as a 6-

DOF vibration isolator. It was experimentally demonstrated that the maglev system is able to

realise inherent quasi-zero stiffness levitation in the vertical direction while providing a static

payload supporting force, and the inherent stiffness of levitation in the remaining five DOFs

are also zero. Although other quasi-zero stiffness isolator designs have been reported in the

literature, the vast majority of them are only able to provide quasi-zero stiffness in one DOF.

The vibration transmissibility measurements have also demonstrated the low resonance

frequencies achieved in multiple DOFs, which further indicates the good performance of the

system as a vibration isolator. It is noteworthy that the performance of the proposed system is

a combined result of both mechanical and electrical systems. Therefore, the performance of

the proposed system can potentially be further improved through embedding hardware with

higher quality and less noise.

Page 45: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

45

References

[1] E.I. Rivin, Passive Vibration Isolation, ASME Press, New York, USA, 2003.

[2] C.M. Harris, Shock and Vibration Handbook, 4th ed., McGrawHill, New York, 1996.

[3] http://www.newport.com/Optical-Tables/139718/1033/catalog.aspx (Accessed 20 December

2011).

[4] http://www.herzan.com/ (Accessed 20 December 2011).

[5] http://www.aigo.org.au/ (Accessed 20 December 2011).

[6] http://www.ego-gw.it/virgodescription/pag_4.html (Accessed 20 December 2011).

[7] Y. Wang, H. J. Liu, “Six degree-of-freedom micro vibration hybrid control system for high

technology facilities”, International Journal of Structural Stability & Dynamics, 9(3), 434-460,

2009.

[8] J. Wang, S. Wang, C. Deng, Y. Zeng, H. Song, H. Huang, “A superhigh speed HTS maglev

vehicle”, International Journal of Modern Physics B, 19(1-3), 399-401, 2005.

[9] H. Hirani, P. Samanta, “Hybrid (hydrodynamic + permanent magnetic) journal bearings”,

Proceedings of the Institution of Mechanical Engineers, Part J, Journal of Engineering

Tribology, 126(8), 881-891, 2007.

[10] J. Sun, J. Feng, “A novel structure of permanent-magnet-biased radial hybrid magnetic

bearing”, Journal of Magnetism and Magnetic Materials, 323(2), 202-208, 2011.

[11] W. Robertson, B. Cazzolato, R. Wood, A. Zander, “Zero-stiffness magnetic springs for active

vibration isolation”, Proceedings of Active 2006 Conference, Adelaide, Australia, 2006.

[12] W. Robertson, B. Cazzolato, A. Zander, “Experimental results of a 1D passive magnetic

spring approaching quasi-zero stiffness and using active skyhook damping”, Proceedings of

Acoustics, Victor Harbor, Australia, 2013.

[13] N. Zhou and K. Liu, "A tunable high-static-low-dynamic stiffness vibration isolator", Journal

of Sound and Vibration, 329, 1254-1273, 2010.

[14] T. Mizuno, M. Takasaki, D. Kishita, K. Hirakawa, “Vibration isolation system combining

zero-power magnetic suspension with springs”, Control Engineering Practice, 15, 187-196,

2007.

[15] M. E. Hoque, M. Takasaki, Y. Ishino, T. Mizuno, “Development of a three-axis active

vibration isolator using zero-power control”, IEEE/ASME Transactions on Mechatronics, 11,

462-470, 2006.

Page 46: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

46

[16] M. E. Hoque, T. Mizuno, Y. Ishino, M. Takasaki, “A three-axis vibration isolation system

using modified zero-power controller with parallel mechanism technique”, Mechatronics, 21

1055-1062, 2011.

[17] T. Mizuno, M. E. Hoque, M. Takasaki, Y. Ishino, “Development of a six-axis hybrid vibration

isolation system using zero-power control”, Proceeding of the 45th IEEE Conference on

Decision and Control, 6531-6536, San Diego, USA, 2006.

[18] M. E. Hoque, T. Mizuno, Y. Ishino, M. Takasaki, “A six-axis hybrid vibration isolation

system using active zero-power control supported by passive weight support mechanism”,

Journal of Sound and Vibration, 329(17), 3417-3430, 2010.

[19] J. L. G. Janssen, J. J. H. Paulides, E. A. Lomonova, B. Delinchant, J. P. Yonnet, "Design

study on a magnetic gravity compensator with unequal magnet arrays," Mechatronics, 23(2),

197-203, 2013.

[20] K. B. Choi, Y. G. Cho, T. Shinshi, A. Shimokohbe, “Stabilization of one degree-of-freedom

control type levitation table with permanent magnet repulsive forces”, Mechatronics, 13(6),

587-603, 2003.

[21] A. Molenaar, E. H. Zaaijer, H. F. van Beek, “A novel low dissipation long stroke planar

magnetic suspension and propulsion stage”, Proceedings of the Sixth International

Symposium on Magnetic Bearings, MIT, Cambridge, USA, 1998.

[22] C. Ding, J. L. G. Janssen, A. A. H. Damen, P. P. J. van den Bosch, “Modeling and control of

a 6-DOF contactless electromagnetic suspension system with passive gravity compensation”,

Proceedings of the XIX international Conference on Electrical Machines, Rome, 2010.

[23] W. Robertson, B. Cazzolato, A. Zander, “Planar analysis of a quasi-zero stiffness mechanism

using inclined linear springs”, Proceedings of Acoustics, Victor Harbor, Australia, 2013.

[24] D. Xu, Q. Yu, J. Zhou, S. R. Bishop, “Theoretical and experimental analyses of a nonlinear

magnetic vibration isolator with quasi-zero-stiffness characteristic”, Journal of Sound and

Vibration, 332(14), 3377-3389, 2013.

[25] S. Earnshaw, “On the nature of the molecular forces which regulate the Constitution of the

aluminiferous Ether”, Transactions of the Cambridge Philosophical Society, 7, 97–112, 1842.

[26] Z. J. Yang, Y. Fukushima, S. Kanae, K. Wada, “Robust non-linear output-feedback control of

a magnetic levitation system by K-filter approach”, IET Control Theory and Applications, 3,

852-864, 2009.

[27] R. J. Wai, J. D. Lee, “Backstepping-based levitation control design for linear magnetic

levitation rail system”, IET Control Theory and Applications, 2(1), 72–86, 2008.

Page 47: Vibration isolation using six degree-of-freedom quasi …data.mecheng.adelaide.edu.au/avc/publications/public_papers/2015... · 1 Vibration isolation using six degree-of-freedom quasi-zero

47

[28] Y. X. Su, C. H. Zheng, D. Sun, B. Y. Duan, “An enhanced fuzzy PD controller with two

discrete nonlinear tracking differentiators”, IEEE Proceedings on Control Theory and

Applications, 151, 675-682, 2004.

[29] T. Zhu, B. Cazzolato, W. Robertson, A. Zander, “The development of a 6 degree of freedom

quasi-zero stiffness Maglev vibration isolator with adaptive-passive load support”,

Proceedings of the 15th International Conference on Mechatronics Technology, Melbourne,

Australia, 2011.

[30] G. Akoun and J.-P. Yonnet, “3D analytical calculation of the forces exerted between two

cuboidal magnets”, IEEE Transactions on Magnetics, 20(5), 1962–1964, 1984.

[31] R. Ravaud, G. Lemarquand, S. Babic, V. Lemarquand, and C. Akyel, “Cylindrical magnets

and coils: Fields, forces, and inductances”, IEEE Transactions on Magnetics, 46(9), 3585–

3590, 2010.

[32] J. L. G. Janssen, J. J. H. Paulides, J. C. Compter, E. A. Lomonova, “Three-dimensional

analytical calculation of the torque between permanent magnets in magnetic bearings”, IEEE

Transactions on Magnetics, 46(6), 1748-1751, 2010.

[33] W. Robertson, B. Cazzolato, A. Zander, “A Simplified Force Equation for Coaxial

Cylindrical Magnets and Thin Coils”, IEEE Transactions on Magnetics, 47(8), 2045-2049,

2011.

[34] W. Robertson, M. Kidner, B. Cazzolato, A. Zander, “Theoretical design parameters for a

quasi-zero stiffness magnetic spring for vibration isolation”, Journal of Sound and Vibration,

329(1-2), 88-103, 2009.

[35] W. Robertson, Matlab code on calculation of magnetic forces and torques,

https://github.com/wspr/magcode/tree/master/matlab (Accessed 28 May 2013).

[36] H. Allag, J. P. Yonnet, “3_D Analytical calculation of the torque and force exerted between

two cuboidal magnets”, IEEE Transactions on Magnetics, 45(10), 3969-3972, 2009.

[37] Miller, H., “Transit noise and vibration impact assessment”, Final Report, U.S. Department of

Transportation, Washington, D. C., 1995.