    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 12 PAGE 00 OF 14

    REVISION HISTORY SHEET

    REV. DATE NATURE OF CHANGE REASONS PREPARED BY APPROVED BY

    NO.

    00 FIRST ISSUE ------

    REVISIONS 00 APPROVED BY S.K.Iyengar

    PREPARED BY ISSUED BY DATE

    Prachi Rao.V D & PS 16-12-06

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    2/15

    P.S NO. : PS/441/316PURCHASE SPECIFICATION

    REV. NO : 00

    GROUP : DRIVES & POWER SUPPLIESA4 10 PAGE 01 OF 14

    REVISIONS 00 APPROVED BY S.K.Iyengar

    PREPARED BY ISSUED BY DATE

    Prachi Rao.V D & PS 16-12-06

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    TECHNICAL SPECIFICATION OF VFD FOR 850 kW SQUIRREL

    CAGE INDUCTION MOTOR

    1. Application : ID Fan Drive (Squirrel Cage Induction Motor)

    2. Quantity : 4 Nos. Fully Assembled Units (CBU)

    CBU Units Completely Assembled & Tested Panel

    3. Input voltage : 690 V +10 %,-15% (From a 6.6 KV / 690V ,3, 50Hz Transformer)

    4. Input phases : 3

    5. Input frequency : 50 Hz 5 %

    6. Ambient : 50C

    temperature Necessary derating in VFD Rating shall be done to account forthe above.

    7. Motor data : Rated Power : 850 KW

    Rated Voltage : 690VRated Speed : 750 rpm

    Power factor : 0.85Sine wave Efficiency(%): 94Motor is designed for operation with IGBT PWM Inverter

    8. Power/Torque vs Speed: Torque Speed2, Power Speed

    3

    9. Relative Humidity : < 95% (non condensing)

    10. Altitude : Max 1000mts above mean sea level

    11. Location of VFD Panels : Indoor, Air-Conditioned Room

    12. Output voltage of VFD : 0 to Vin

    13. Output Current of VFD : 980 Amps at 50 deg C

    14. Output Frequency : 0 to 50Hza) Resolution : 0.001 Hzb) Accuracy : 0.01%

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    3/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 02 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindi

    rectlyinanywaydetrimentaltotheinterestofthecompany.

    15. VFD Panel Construction

    a) Protection Class : IP42

    b) Panel :Free standing, floor mounting type, comprising of rigid welded structural

    frames with Cold Rolled Sheet Steel enclosure of minimum thickness2 mm for load bearing and 1.6 mm for other members. All doors &removable covers shall have neoprene gaskets. Ventilating louvers shallhave easily removable and washable dust filters

    c) Cooling : Air Cooled (Natural or Forced Air Cooled)lf forced air cooling is adopted, same shall be with low noise ventilationfans at the top of the cubicle, which shall suck air through the Power

    modules.The arrangement shall preferably be such that ventilation airpasses only through Power modules heat sinks in a separate duct toprevent dust deposition. Suitable thermal relays for exit air temperaturemonitoring and control shall also be incorporated.

    d) Door Interlock: The VFD shall have a door- interlocked input AC line disconnect switchwith fuses. The fuses should be of semiconductor type and have asasymmetrical short circuit interrupting capability of 200 kA

    e) Painting : All exterior surfaces of panels shall be given one primer coat, one fillercoat and finished with two coats of lacquer Paint. Interior surfaces shall

    be primed and finished with one coat of Paint. Exterior and Colour as pershall be as per Shade to be finalised at the time of final drawing approval.

    f) Limiting Dimensions: Height of Panels from finished floor level shall be 2400mm

    g) Cables : Unarmoured Type, Stranded Aluminium Conductor

    Details of Cable Size, Outside Diameter of Cable, No. of Cables etcshall be given by BHEL during drawing approval stage.

    Cable Gland Plates shall be blank (undrilled) to be drilled at site. Gland Plates shall be

    4mm thk Aluminium (steel not allowed)

    16. Noise Level : Less than 80 dB at a distance of 3 ft.

    17. Storage temperature: -40C to +60 C

    18. Vibration : According to IEC68 - 2-6

    19. Interference : According to IEC801 parts 2,3,4Immunity The panels shall be designed so as to have low Radio Frequency

    Interference (RFl) and Electromagnetic Interference (EMl).

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    4/15

    P.S NO. : PS/441/316PURCHASE SPECIFICATION

    REV. NO : 00

    GROUP : DRIVES & POWER SUPPLIESA4 11 PAGE 03 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    20. VFD Efficiency : Shall be > 96%

    21. Overload Duty : Class II Duty Overload as per IEC 146-1(150% of Motor Rated Current for 60 secs at 50 deg C)

    22. VFD Requirements :

    a) Analog Input : 2 nos. User programmable.

    b) Analog Outputs : 2 nos. 4 20 mA (Isolated)

    c) Digital Inputs : 8 nos. optocoupled. User programmable

    d) Digital Outputs : 4 nos. user programmable relay outputs for VFD ON,

    VFD Ready, VFD Fault and VFD Alarm.

    e) Varistors : Metal Oxide Varistors (MOVs) shall be provided for transientvoltage suppression on the 3-phase AC incoming power line.

    f) Input Choke : Input chokes to be provided if necessary.

    g) Local/Remote : Selector switch shall be provided for operator to select

    Switch Local - Operation from VFD Panel for Speed Control or(Door Mounted) Remote - Operation from DCS Panel

    If VFD is set for speed reference from Remote, it shall be possible to program the VFD toeither shutdown, go to minimum speed or continue operation at its last known speedreference point whenever a loss of speed reference is detected.

    h) Door Mounted Local Start/Stop Pushbutton : To be provided

    i) Door Mounted Emergency Stop : Lockable Push-Button to be provided.

    j) Anticondensation Heater :One heater to be provided inside the Inverter.

    k) Motor Space Heater Feeder: One 230 V, 1200 W (Approx.)feeder to be provided onterminals for Motor Space heater. Final rating shall be provided during drawing stage

    l) PLC : PLC shall be provided for Interlocking and Protection

    23. Braking Unit:Braking unit : For 850 KW Motor

    Resistor value 6.0 Ohms

    Peak Power 150 KW

    Average Power 104 KW

    Nominal Power 17.3 KW

    Cycle Time 100 secs ON500 secs OFF

    Number of Braking Units used in the Inverter to be specified.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    5/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 04 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    24.Input transformer

    BHEL shall provide the Input Transformer.

    25.Input Breaker, Output Breaker & Bypass Breaker:

    BHEL shall provide the Input Breaker, Output Breaker & Bypass Breaker:

    26. VFD Features:

    b) Soft Start & Auto Restart

    c) Auto Speed Search Facility (Catch on Fly) shall be available for starting into rotatingloads.

    d) Power loss ride through (Kinetic Buffering) for minimum 2 secs time

    e) Automatic VFD tuning during start-up.

    f) Flux optimisation function shall be provided to reduced the total energy consumptionand noise level in case drive is operated below nominal load.

    g) DC magnetising features shall be provided to automatically magnetise the motor beforestart to ensure the highest possible break away torque.

    h) Selectable reverse run prohibition

    i) Adjustable motor overload feature

    j) Settable minimum and maximum operating frequency

    k) VFD shall produce not greater than 1 % torque pulsation to the shaft of drivenequipment.

    l) Field adjustable Torque limits and acceleration & deceleration ramps.

    m) Eight (8) user programmable preset speeds.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    6/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 05 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    27. Controls And Monitoring

    a) VFD shall be with an interactive and user-friendly door mounted digital operatorinterface with LCD display and sealed membrane type keypad.

    b) The operator interface shall be used for drive programming, drive monitoring anddrive trouble shooting. The operator interface must also be able to start and stop thedrive, reset VFD faults and manually adjust the VFD's speed reference.

    c) The operator interface shall have LED indicators for drive fault, drive run, drive incurrent limit and forward direction of rotation.

    d) The digital operator shall allow simple monitoring of inverter operating conditionsincluding speed, current, voltage, torque, power etc.

    e) Messages shall be Alpha numeric in nature. All the fault messages shall be in clearEnglish language.

    f) The operator interface shall be removable and remote mountable.

    g) The operator interface shall be able to display all real time operating variablesand all drive programming parameters.

    h) The operator interface shall be capable of displaying a specific user selected

    parameter on power-up. This power-up parameter would typically be a parameterthat is important to the operator such as motor speed or motor load.

    i) All VFD operating parameter shall be stored in nonvolatile memory (EEPROM).

    j) The drive shall have built in monitoring of following parameters as minimum on

    its digital operator interface and these parameter shall also be displayed at plantDCS :

    Output FrequencyOutput Current

    Motor SpeedOutput Voltage

    DC Bus VoltageOutput Power (lt shall be possible to display power output of the drive in KWand the accumulated power output over the time (kWHr)

    TorqueDigital Input Status

    Digital Output StatusAnalog Input Status

    k) Necessary transducer shall be provided with 4-20 mA output for indicating

    motor speed and current in the DCS. Transducer shall be capable of driving

    500 ohms load.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    7/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 06 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    l) The following indications shall be provided on the Panel Door:- Motor Running

    - Motor Stopped/Tripped- AC Mains "On"

    - System "Ready to Start"- VFD System Fault

    m) The VFD shall store fault logs of minimum last 10 faults in memory.

    n) The interface details of VFD shall be incorporated as required for data

    communication with DCS system with serial interfaces with RS485 & RS 422data links. Necessary hardware shall be included in the scope and the interface

    protocol (i.e. modbus or profibus) shall be defined.

    28. Protection :

    Following protections shall be built in within the inverter and any other protection as required:

    a) Motor Overload / Over Torque

    b)Instantaneous Over current (This device shall monitor the peak output currentcontinuously and shall provide instantaneous shutdown without componentfailure whenever its trip point is surpassed. The trip point must be greater than

    or equal to 250 % of the VFD's rated full load output current)

    c) Ground Fault

    d) Over Voltage/Under VoltageVFD shall be able to withstand 30% dip in supply voltage for 3 cycles without

    damage to semiconductors or fuses.

    e) Output Short Circuit

    f) Output Phase Loss/Fuse Failure

    g) Phase Sequence Protection

    h) Input Phase Loss/Single Phasing Preventer

    i) Over Speedj) Heat sink over temperature/VFD Panel Temperature High Stall prevention

    (During acceleration, deceleration andconstant speedoperation)

    k) Loss of Cooling Fans

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    8/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 07 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    29.Type of control:-

    Completely programmable by the user as :-

    a. Flux vector control with speed feedbackb. Flux vector control without speed feedbackc. Scalar v/f.

    VFD shall be capable of maintaining motor speed within 60.5% of maximum

    speed without the use of a motor mounted encoder or tachometer.

    The drive shall have programmable V/F patterns along with a user definable

    custom V/F patterns.

    30.Harmonic limitations Shall be as per IEEE 519

    Refer Pg. 14 of 14 of this specification for Single Line Diagram

    l) Voltage harmonicsMaximum individual voltage harmonics to be limited to 3% and Total Harmonic

    Distortion of System to be limited to 5% as per IEEE 519.

    ll) Current Harmonicsa) Source side

    i) 5thharmonic Maximum 30 %

    ii) 7

    th

    harmonic Maximum 20 %iii) 11

    th harmonic Maximum 10%

    31.Switching frequency:-

    Shall not be less than 2 kHz.

    32. Auxiliary Supply:

    110V AC, 1 KVA, 1Ph, 50 Hz UPS feeder shall be made available. Load requirement to be

    indicated by vendor. All other supplies required to be derived from input feeder to VFD.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    9/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 08 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofth

    ecompany.

    33. SparesSupplier should quote item wise price for the following spares:

    MANDATORY SPARES:Unpriced List of Spares quoted for shall be provided in the Technical Offer.

    BHEL reserves the option of deleting or changing the quantities of the items listed below.Unit Prices shall remain firm irrespective of any change.

    a) Electronic Cards : 2 No. of each type and rating

    b) Power Supply : 2 No. of each type

    c) Door Interface Module : 2 No. with necessary connecting cables and

    fixing hardwares.

    d) Relays & Contactors : 2 no. of each type

    e) Semi-conductor fuses : 6 nos. AC Fuses4 nos. DC Fuses

    f) Other fuses : 2 sets (1 set refers to the total qty required for one Drive)

    g) Converter Power Stack: 2 No. with Control Card

    h) Inverter IGBT Stack : 4 Nos. with Control Card

    i) Braking Unit : 2 Unit

    j) Limit Switch : 2 No.

    k) Pushbuttons and lamps : 2 set

    l) Cooling Fan : 2 no. of each type

    m) PLC : 2 no.

    n) Tools & Tackles : Any special tools & tackles required for commissioningand troubleshooting shall be provided.

    o) Small Rating IGBT Inverter : 1 No.0.75KW or higher, 690V,3Ph, 50Hz This Inverter is to be used for training and simulation

    using the same electronic controller purpose.

    RECOMMENDED/COMMISSIONING SPARES:Besides these spares Supplier will provide the list of recommended spares during

    commissioning and for five(5) years trouble free operation with item-wise price.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    10/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 09 OF 14

    34. Maintenance :

    The procedure for maintenance of VFD panels, and the schedule thereof shall be mentioned in theoffer.

    35. Inspection, Training & Commissioning Support:

    a) Customer and BHEL representative will be present at msnufacturers works for witnessing of finaltesting. This is to be incorporated in the Quality Plan. No charges are applicable for this.

    b) Training for two persons from BHEL/customer for a period of 2 weeks at manufacturers

    works free of cost.

    c) Two (2) visits of experts to site during commissioning free of cost for a period of 10 daysper visit free of cost.

    36.Software for computer interface :

    This software should be an easy to use commissioning tool for drives and shall be provided along withthe system. The interface details of VFD shall be incorporated as required for data communication

    with DCS system with serial interfaces with RS485 & RS 422 data links. Necessary hardware shall beincluded in the scope and the interface protocol (i.e. modbus or profibus) shall be defined.

    37.Testing & Quality Plan :

    a) Routine tests shall be carried out on all Panels as per relevant standards.

    b) Type test certificates for similar equipment supplied by the Bidder shallbe submitted along with offer.

    c) Test Protocol and Quality Plan for approval shall be submitted by supplier along with offer.These documents shall explicitly list out all final tests done on the Fully Assembled Unit.

    d) Sl.Nos.18, 19 & 20 of Data Sheet to be demonstrated by manufacturers works.

    38. Information required along with offer :

    a) Dimensional Drg of Panels along with minimum clearance to be mantained for effective coolingb) Tentative Schemec) Weightd) Losses at Rated Load (Total including Cooling Fans)e) Quantity and Rating of Cooling Fans providedf) Experience list of similar ratingg) Catalogh) User Manuali) Confirmation to all pts in Sl.39 (a) to (f)

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuse

    directlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    11/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 10 OF 14

    39. Confirmations required from Supplier :

    a) After Sales Service & Support shall be given by vendor along with of for a minimum period of10 (ten) years. Address of the after sales and service representative in India to be given. The sameshall be binding on the Principals irrespective ofany change in the Indian Representative.

    Annual Maintenance Contract (AMC) for the above period to be provided for the system if thesame is required by customer. Price for the same shall be indicated in the offer as an optional price.

    b) The availability of VFD shall be greater than 99.90% for a period of 10 years after commissioning.

    Further supplier shall give extended warranty of five years. Price for the period of ExtendedWarranty shall be indicated separately.

    c) Mean Time Between failures (MTBF) shall be greater than 40000 running hours. All componentsof VFD shall be considered for MTBF calculations

    d) The vendor shall confirm that supply of spares and services shall be rendered for a period of10 years after commissioning. A Revolving Bank Guarantee for a period of 2 years (with a claim

    period of 6 months) equal to 10% of the value of Purchase Order shall be furnished as a guaranteetowards the supply of spares and services. The same shall be renewable for the above stipulated

    period of 10 years. In case of breach of such an agreement for the supply of spares and services,this guarantee shall be invoked by BHEL.

    The prices of any spares and services during this period shall be decided keeping the quotedprices with this bid as base and applying increase/decrease after mutual discussions and

    acceptance as and when such a requirement arises.

    e) Bank Guarantee Charges shall be borne by vendor.

    40. Confirmations/Deviations to Specification :

    Point-wise confirmation to this specification to be given along with offer. Deviations if any, shall be

    indicated separately. If there are no deviations to the specifications, supplier shall mention the sameexplicitly. A reply from vendor stating that Equipment will generally meet the specifications

    will not be accepted by BHEL.

    41.Maintenance manuals/Documentation to be given after Order Placement:

    a. Erection, Commissioning and Maintenance manuals - 10 Copiesb. All drawings for approvalc. 1 no. CD ROM consisting of final drawings and documentation as mentioned above.d. Test and guarantee certificates.e. Complete Bill of Material (itemwise) for the equipment supplied.

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    12/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 11 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    DATA SHEET

    (To be filled in by supplier and attached along with offer)

    Sl.No Description Unit Specification

    requirement

    Vendors Details

    1.0 Type of Drive Inverter (IGBT BasedPWM Controlled)

    2.0 Manufacturer *

    3.0 Application ID Fan

    4.0 Type of Motor Squirrel Cage InductionMotor

    5.0 Rating of Motor KW 850 KW

    6.0 Quantity 4

    7.0 Rated Power Factor 0.85

    8.0 Efficiency 0.94

    9.0 Ambient Temperature Deg C 50 deg C

    10.0 Power Supply System

    a) Input Supply to VFD 690V, 3 Ph, 50 Hzb) Variation in Voltage +10%, -15%

    c) Variation in Frequency +/- 5%d) Combined Voltage &

    Frequency variation

    +/- 10%

    11.0 VFD Location Indoor

    12.0 VFD Offered :a) VFD Type No *

    b) Rated Output Power KW *c) Rated Output Voltage Volts *

    d) Rated Continuous Currentat 50 deg C temperature Amps 980

    13.0 VFD suitable for Duty

    Class II Overload

    Yes Yes/No

    14.0 a) VFD suitable for siteambient temperature

    b) Derating provided

    Yes

    Yes

    Yes/No

    Yes/No

    15.0 Type of Cooling Air Cooled Yes/No

    16.0 Dimensions *

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    13/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 12 OF 14

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustnotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

    Sl.No Description Unit Specification

    requirement

    Vendors Details

    17.0 Degree of Protection IP 42 Yes/No

    18.0 Power Loss Ride Through

    Time

    Secs 2

    19.0 Auto restart after power loss Yes Yes/No

    20.0 Kinetic Buffering Secs 2 Yes/No

    21.0 Soft Start Yes Yes/No

    22.0 Catch on Fly Yes Yes/No

    23.0 Accelerate/Decelerate time *

    24.0 Harmonic Limitation

    1) Voltage Harmonics As per IEEE 519

    a) Source side

    b) Load side

    2) Current Harmonics

    a) Source side

    (i) 5 Maximum 30%

    (ii) 7 Maximum 20%(iii) 11 Maximum 10%

    25.0 Switching Frequency > 2 KHz

    26.0 No. of Braking Units inInverter

    *

    27.0 Address of Sales & Service

    Respresentative in India

    28.0 Quality Plan submitted Yes/No

    29.0 Test Protocol submitted Yes/No

    30.0 Type test certificate submitted Yes/No

    31.0 Reference List Yes/No

    32.0 Max.cable length without

    output choke

    33.0 Confirmation/Deviationsattached

    Yes/No

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    14/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 13 OF 14

    Sl.No Description Unit Specificationrequirement

    Vendors Details

    34.0 Extended Warranty for 5 years Required

    35.0 Annual Maintenance Contract Supplier to quote.

    Optional to BHEL.36.0 Bank Guarantee for Spares &

    Services for 10 yrs as per

    Sl.39.

    Required.

    37.0 Information reqd.with offer asper Sl.38(a) (i)

    Documents andconfirmation required.

    38.0 Protections offered :To be filled in by vendor

    COPYRIGHTANDCONFIDENTIA

    TheinformationonthisdocumentisthepropertyofBHARATHEAVYELECTRICA

    LSLIMITED.

    Itmustotbeuseddirectlyorindirectlyinanywaydetrimentaltotheinterestofthecompany.

  • 8/13/2019 Vfd Spec for Nlc Slpp Ps441316 Rev 00

    15/15

    P.S NO. : PS/441/316

    PURCHASE SPECIFICATIONREV. NO : 00

    GROUP : DRIVES & POWER SUPPLIES

    A4 11 PAGE 14 OF 14

    6.6 KV, 3 Ph, 50 HzShort-Circuit Level = 360MVA

    6.6KV / 690 V Dd0 Transformer1800 KVA, 6.25% Impedance

    INDUCTION MOTOR

    850KW, 690V, 980 Amps

    SINGLE-LINE DIAGRAM