vfd biasing methods

13
Delta VFD Biasing M Series www.nfiautomation.org

Upload: nfi-industrial-automation-training-academy

Post on 24-Dec-2014

653 views

Category:

Technology


6 download

DESCRIPTION

This presentation explains specifically how to vary the gain & offset of VFD to make customize Voltage by Frequency curves Unlock our Online VFD Course "Learn VFD in a Day" with 57+ High Quality Video tutorials for $49 only! Course link: https://www.udemy.com/learn-vfd-in-a-day/?couponCode=slideshare

TRANSCRIPT

Page 1: VFD Biasing Methods

Delta

VFD BiasingM Series

www.nfiautomation.org

Page 2: VFD Biasing Methods

VFD Biasing

0 5V 10V

1 Volt = 5 Hz

0 Hz

25 Hz

50 Hz

Pr.03=50Hz--Max. output Freq.

Pr.48=0%--bias adjustment

Pr.49=0 -- bias polarity

Pr.50=100% -- pot. freq. gain

Pr.51=0 -- REV disable in negative bias

www.nfiautomation.org

Page 3: VFD Biasing Methods

0 5V 10V

1 Volt = 5 Hz

0 Hz

25 Hz

50 Hz

10 Hz

Bias Adjustment

Bias Adjustment =

(Bias Range)/(Full range) x 100

= 10/50 x 100

= 20%

Pr.03= 50Hz--Max. output Freq.

Pr.48= 20%--bias adjustment

Pr.49= 0 -- bias polarity

Pr.50= 100% -- pot. freq. gain

Pr.51= 0 -- REV disable in negative bias

VFD Biasing

www.nfiautomation.org

Page 4: VFD Biasing Methods

0 5V 10V

0 Hz

25 Hz

50 Hz

10 Hz

Bias Adjustment

(Full Freq. Range – Bias Freq. range) / (Full voltage range) = (Bias Freq. – 0 Hz) / XV

Bias Adjustment = (XV/ Full voltage Range) x 100

Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

Pot. Freq Gain

-2.5V

Pr.03= 50Hz--Max. output Freq.

Pr.48= 25%--bias adjustment

Pr.49= 0 -- bias polarity

Pr.50= 80% -- pot. freq. gain

Pr.51= 0 -- REV disable in negative bias

VFD Biasing

www.nfiautomation.org

Page 5: VFD Biasing Methods

0 5V

1 Volt = 5 Hz

0 Hz

25 Hz

50 Hz

Pot. Freq Gain

10V

Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

Pr.03= 50Hz--Max. output Freq.

Pr.48= 0%--bias adjustment

Pr.49= 0 -- bias polarity

Pr.50= 200% -- pot. freq. gain

Pr.51=0 -- REV disable in negative bias

VFD Biasing

www.nfiautomation.org

Page 6: VFD Biasing Methods

0 5V 10V

50 Hz

15 Hz

Bias Adjustment

Pot. Freq Gain

4.28

Pr.03= 50Hz--Max. output Freq.

Pr.48= 42.8 %bias adjustment

Pr.49= 0 -- bias polarity

Pr.50= 70 % pot. freq. gain

Pr.51= 0 -- REV disable in negative bias

VFD Biasing

www.nfiautomation.org

(Full Freq. Range – Bias Freq. range) / (Full voltage range) = (Bias Freq. – 0 Hz) / XV

Bias Adjustment = (XV/ Full voltage Range) x 100

Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

Page 7: VFD Biasing Methods

0 5V 10V

0 Hz

25 Hz

50 Hz

Bias Adjustment

Bias Adjustment =

(Bias Voltage Range)/(Full Voltage range) x 100

= 1/10 x 100

= 10%

1

Pr.03= 50Hz--Max. output Freq.

Pr.48= 10%--bias adjustment

Pr.49= 1 -- bias polarity

Pr.50= 100% -- pot. freq. gain

Pr.51= 0 -- REV disable in negative bias

VFD Biasing

www.nfiautomation.org

45 Hz

Page 8: VFD Biasing Methods

0 5V 10V

0 Hz

25 Hz

50 HzPr.03= 50Hz--Max. output Freq.

Pr.48= ____ bias adjustment

Pr.49= 1 -- bias polarity

Pr.50= ____-- pot. freq. gain

Pr.51= 0 -- REV disable in negative bias

Pot. Freq Gain

Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

Bias Adjustment =

(Bias Voltage Range)/(Full Voltage range) x 100

= 1/10 x 100

= 10%

VFD Biasing

www.nfiautomation.org

Bias Adjustment

Page 9: VFD Biasing Methods

0 5V 10V

0 Hz

25 Hz

50 Hz

Pr.03= 50Hz--Max. output Freq.

Pr.48= 50%--bias adjustment

Pr.49= 1 -- bias polarity

Pr.50= 200% -- pot. freq. gain

Pr.51= 1 -- REV disable in negative bias

Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

Bias Adjustment =

(Bias Voltage Range)/(Full Voltage range) x 100

= 5/10 x 100

= 50%

25 Hz

50 Hz

7.5V

2.5V

VFD Biasing

www.nfiautomation.org

Rev

Fwd

Page 10: VFD Biasing Methods

0 5V 10V

0 Hz

25 Hz

50 HzPr.03=50Hz--Max. output Freq.

Pr.48=100%--bias adjustment

Pr.49=1 -- bias polarity

Pr.50=100% -- pot. freq. gain

Pr.51=1 -- REV disable in negative bias

Bias Adjustment =

(Bias Voltage Range)/(Full Voltage range) x 100

= 10/10 x 100

= 100%

VFD Biasing

www.nfiautomation.org

Page 11: VFD Biasing Methods

Learn 4 PLC’s in a Day100+ Video Tutorials

Life time Access

nfipresents

Lea

rn t

o C

od

e |

Co

de

to

Le

arn

Coupon Code https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare

in $99 $49

For more courses visit www.nfiautomation.org

Course Outline

• 100+ PLC Video Tutorials

• Doubt Clearing Complementary LIVE Sessions on Team Viewer

• Ladder Logic Programming

• PLC Presentations, PLC Circuits, PLC Codes

• FREE PLC Simulation Software for Practice

PLC – Programmable Logic Controller

Delta DVP 14 SS + 16 SP

Allen Bradley M1000

Siemens S7 200

Schneider

Analog Cards Programming

04 AD – Analog to Digital

04DA- Digital to Analog

Page 12: VFD Biasing Methods

PLC & VFD Advanced

Course4 PLC’s Training

Platforms

For more courses visit www.nfiautomation.org

Course Highlights:

• 30 Live Practical Classes on PLC, Analog Cards & AC drives- VFD

• 100+ PLC Video Tutorials with Lifetime Access & FREE PLC Simulator

• FREE Circuits Diagram

$149

Course Link:http://www.wiziq.com/course/28882-plc-and-ac-drives-online-certificate-trainaing-course

Page 13: VFD Biasing Methods

Thankswww.nfiautomation.org

nfi