Page 1: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

VerticalSelf-ContainedAir Conditioning

Air and Water Cooled

5 - 15 Tons

50 Hz

PKG-PRC006-EN

Page 2: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN©American Standard Inc. 2000

Introduction

The TRANE Company, a world leader inthe HVAC industry, has developedanother option to meet the needs of ourcustomers . . . the Genius! Built toprovide not only the indoor comfort butalso the confidence that the unit isreliable, durable, easy to install andmaintain.

The Genius line has been designed tosatisfy the demands of the internationalmarkets.

IAQ standards, microcontrols andsimplified maintenance were allconsidered during its design.

Water Cooled Unit

Page 3: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

3

Contents

PKG-PRC006-EN

Introduction 2

Features and Benefits 4

Model Number Description 8

General Data 9

Selection Procedure 10

Performance Data 11

Controls 36

Electrical Data 37

Dimensions 47

Mechanical Specification 51

Page 4: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN4

Features andBenefits

The Genius line was built to provide notonly ultimate indoor comfort but alsothe comfort of knowing that our self-contained units are reliable as well aseasy to install and maintain.

Genius is the most flexible vertical self-contained of the market. Suitable to usein offices, residences or restaurants.Available as water cooled, integrated aircooled (or package unit) or with remoteair coded condenser; the modern designof the Genius line allows you, for the firsttime, to select the color of the unit.

Why Consider Self-ContainedFloor-by-Floor Systems?

Improved Cash Management

• Factory installed options and testing:Reduces field labor and installation riskand improves system reliability

• Requires less sophisticated maintenancethan built-up systems

Tenant Satisfaction

• Complete HVAC system on each floor orarea minimizes tenant inconvenienceduring routine maintenance.

• Tenants can control system after hoursto increase productivity and minimizeexpense

Low First Cost

• Factory packaged controls and pipingreduce field labor, installation time andcost

• Flexible arrangement to match mostbuilding configurations

Lower Installed Cost

• Single point power connection• Single point water connection• Factory commissioned and tested

controls• Factory installed options

Economical Operation

• Floor-by-floor system results in energysavings since only air conditioners onfloors requiring cooling need to operate

• Annual system energy consumptioncomparable to central chilled watersystem but with significant energyconsumption reduction during partialoccupancy and after-hours

Assured Acoustical Performance

• Horizontal discharge plenum providessmooth airflow, reducing static pressurelosses for optimum acousticalperformance.

• Scroll compressor design smooths gasflow for quieter operation

Micro ControlsTrane was the first to introduceMicroelectronics to commercial unitaryproducts and has continued to expandits application to other products.

The new self-contained with Microprovides the highest performance,reliability and best serviceability in theindustry. Trane, a world classmanufacturer can provide this winningcombination for your facility.

The Trane Micro, provided as a factoryinstalled option, was designed with twothoughts in mind: reliability and comfort.The Micro accurately orchestrates allother system operations whether it isheating or cooling.

Since it is factory mounted it will providesmooth, trouble-free start-up.

The microprocessor provides powerfuloperation and diagnostic information.The micro eliminates the need for a fieldinstalled anti short-cycle timer and timedelay relays, which are an integral partof the micro controller.

The IAQ standard, the microelectronicsand the simplified maintenancecapability were all considered a priorityduring the design phase of this self-contained unit.

SRVE(with discharge plenum)

Page 5: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

5PKG-PRC006-EN

Features andBenefits

Air Handling Section

In accordance to the ASHRAE Standard62-89 for Indoor Air Quality, Trane hasdeveloped an exclusive and innovativedesign for the drain pan. This designinsures proper drainage, preventingconditions of water stagnation that couldresult in microbial growth.

All the air handlers feature a factoryinstalled belt drive and ball bearingevaporator fan with adjustable shelves.The unit can be installed indoors; thecondenser air can be ducted to theoutside or installed in a remote location.

For free horizontal application, theoptional discharge plenum withaluminum grills insures a quietoperation and maintains the aestheticsof the units.

In the return section an optionalaluminum grill grants an easy andelegant installation.

3 Filter TypesTo meet Commercial and Industrialneeds you can select the filter media forthe application.

Nylon Electrostatic FiltersWire Mesh Permanent FiltersThrowaway FiltersMany other options available as special(Contact your local TraneRepresentative).

Scroll Compressoroffers significant efficiency and reliablebenefits. With fewer moving parts thancomparable reciprocating compressors,there is less internal friction andtherefore greater efficiency. A smoothcompressor cycle, due to the low torquevariation, creates less stress on themotor for greater reliability andefficiency.

How the Scroll Compressor Works

GeneralThe compressor has two scrolls. The topscroll is fixed and the bottom scrollorbits. Each scroll has walls in a spiralshape that intermesh.

Inlet — First OrbitAs the bottom scroll orbits, tworefrigerant gas pockets are formed andenclosed.

Compression — Second orbitThe refrigerant gas is compressed as thevolume is reduced closer to the center ofthe scroll.

Discharge — Third OrbitThe gas is compressed further anddischarged through a small port in thecenter of the fixed scroll.

Page 6: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN6

Features andBenefits

Integrated Self-Contained Systems:Profitable, Simple

Integrated Comfort™ System (ICS)Trane’s Integrated Comfort™ systemimproves job profit and increases jobcontrol by combining Trane self-contained units and a Tracker® buildingmanagement system. This integratedsystem provides total building comfortand control. The primary motivation forbuilding owners/managers in making thepurchasing decision of an HVAC controlssystem is no longer just saving energy; itis having the ability to automate theirfacilities and the convenience of interfaceto control systems.

As an additional benefit the Microallows the Genius to be integrated tothe Tracker. This ability allows themultiple units to be controlled anddiagnosed from a central location, fromacross town or even across the country.

Just imagine the HVAC installed in yourfacility capable of being scheduled,monitored and let you know when it ishaving problems.

Genius is three times ingenious in manyways.

Available in 3 models

SRVE - Self-contained unit withINTEGRATED air cooled condenser

SIVE - Self contained unit with REMOTEair-cooled condenser

SAVE - Self-contained WATER-cooledunit with shell and tube condenser

Available 3 Colors

The attractive highly functional design ofthe Genius line offers the customers theselection of three equipment colors toblend with any architectural style:

GrayBlackRed

3 Motor SizesThe units have the capability to meet anystatic pressure application up to 1.5”with their 3 options:

- Low Static Motor Option- Medium Static Option- High Static Option

Programmable Thermostat (PT)PT programming is very simple! PT hasa display that shows the hour, the day ofthe week, the selected program and theambient temperature. PT can beprogrammed for up to four setpoints foreach day of the week. Using the button“timed-override” the customer canprolong the machine operation beyondthe programmed schedule, according tocustomer needs.

3 Filter OptionsThree filter options exist which may beinstalled in Genius units.

1. Permanent washable filters ofelectrostatic fabric (standard).

2. Disposable 2” filters.3. The combination of the two placed in

series.

3 Control Options

Standard ThermostatAll units are furnished with a standardthermostat that can be installedremotely or directly on the equipment.

MicrocontrolThis state of the art control offers acomplete family of sensors and wallmounted devices to compliment thecapabilities of the Trane Micro.

Page 7: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

7PKG-PRC006-EN

FeaturesSummary

Quality and Reliability

• Galvanized steel casing• Synthetic enamel paint• Innovative Drain Pan• Scroll Compressors

Flexibility

• Air or Water Cooled• Free discharge plenum or ducted

discharge• Voltages available:

220/3/60, 440/3/60, 380/3/60 and 380/50/3

Controls

• Thermostat unit mounted or remote• Optional Programmable thermostat• Optional Microprocessor• ICS compatible, Tracker is your ideal

partner for small buildings applications.

Filters

• Throwaway• Washable - Nylon type• Washable - Aluminum Mesh

Wide range of Models available:

SRVE: Self Contained with Integral Air Cooled Condenser

SIVE: Self Contained with Remote Air Condenser

SAVE: Self Contained with Water cooled

Nominal Capacity: From 5 to 15 Tons

You can reach up to 1.5” esp with our Double Inlet Forward curvedSupply fan. It also has variable V-belt drives.

The case has been insulated with BIDIM insulation.

Other options:Aluminum decorative grillPlenum discharge box for free air dischargeService ValvesSight GlassSolenoid Valve

Page 8: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN8

ModelNumberDescription

Page 9: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

9PKG-PRC006-EN

Table GD-1 — Genius – General DataSAVE Model 050 T 075 T 100 2T 125 2T 150 2T

Nominal TR Capacity 5 7.5 10 12.5 15Length (mm) 960 1190 1500 1700 1700Depth (mm) 600 600 600 600 600Height (mm) 2000 2000 2000 2000 2000Height w/ Plenum Box (mm) 2295 2295 2295 2295 2295Net Weight (kg) 247 288 376 440 461SRVE Model 050 T 075 T 100 2T 125 2T 150 2T

Nominal TR Capacity 5 7.5 10 12.5 15Length (mm) 960 1190 1500 1700 1700Depth (mm) 720 720 830 1000 1000Height (mm) 2000 2000 2000 2000 2000Height w/ Plenum Box (mm) 2295 2295 2295 2295 2295Net Weight (kg) 268 310 416 459 490SIVE Model 050 T 075 T 100 2T 125 2T 150 2TNominal TR Capacity 5 7.5 10 12.5 15Evaporator UnitsQuantity/Model 1/SIVE050 1/SIVE075 1/SIVE100 1/SIVE125 1/SIVE 150Length (mm) 960 1190 1500 1700 1700Depth (mm) 600 600 600 600 600Height (mm) 2000 2000 2000 2000 2000Height w/ Plenum Box (mm) 2295 2295 2295 2295 2295Net Weight (kg) 190 225 235 347 392Condensing UnitsQuantity/Model 1/CRCB050 1/CRCB075 1/CRCB100 1/CRCB125 1/CRCB150Length (mm) 987 1241 1341 1646 1646Depth (mm) 631 631 631 714 714Height (mm) 890 890 941 1018 1247Net Weight (kg) 93 124 139 180 212CompressorQuantity TR 1 / 5 1 / 7.5 2 / 5 5 + 7.5 2 / 7.5Evaporator CoilRows 3 3 3 3 4Finned Height (mm) 536 508 612 663 714Finned Length (mm) 711 965 1143 1328 1321Finned Clearance (m) 0.38 0.49 0.70 0.88 0.94FPF ( Fins Per Foot) 132 132 132 132 132Evaporator FanQuantity 1 1 2 2 2Diameter x Length 270 x 270 321 x 321 270 x 270 321 x 321 321 x 321Plenum Box Option (CV) 0.5 0.5 0.5 0.5 1.0Standard Motor Option (CV) 1.0 1.5 1.5 2.0 3.0Motor Option 1 (CV) 1.0 2.0 2.0 3.0 4.0Motor Option 2 (CV) 1.5 3.0 3.0 4.0 5.0Minimum Air Flow (m3/h) 3060 4590 6120 7650 9180Maximum Air Flow (m3/h) 3825 5740 7650 9560 11475Condenser Fan(SRVE and CRCB)Quantity 1 1 2 2 2Diameter x Length 321 x 321 321 x 321 270 x 270 321 x 321 321 x 321Motor (CV) 1.0 3.0 3.0 4.0 5.0Air Flow (CFM) 5450 8315 9935 13930 17320Water Condenser(SAVE)Minimum Water Flow GPM 1.4 2.0 2.7 3.4 4.1Maximum Water Flow GPM 4.0 6.0 8.0 9.9 11.9Maximum Pressure Drop (ca feet) 1.9 4.6 1.8 3.0 3.1Condenser Coil(SRVE, CRCB)Rows 4 4 4 4 4Finned Height (mm) 711 813 864 940 1168Finned Length (mm) 762 1016 1143 1473 1473FPF (Fins per Foot) 168 168 168 168 168

GeneralData

Page 10: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN10

SelectionProcedure

The selection of a Genius self-containedunit can be accomplished in three easysteps.1LOAD: Determine the load requirementsfor heating and cooling (include outsideair) using Trane’s load estimate forms,TRACE® Easy/600 or any standardmethod.2UNIT TYPE: Self-contained airconditioners are available in eitherwater-cooled or remote air-cooledmodels to match individual needs.3SELECT THE UNIT: The conditions underwhich the unit must operate and thedesign load will give the final selection.

SELECTION EXAMPLE

Design ConditionsWater-cooled unitEntering air temperature — 80/67 FTotal gross capacity required —50,000 BTUHEntering water temperature — 85 FLeaving water temperature — 92 FAirflow — 1,950 CFM at 0.5” duct staticpressure.380V/3/50Hz Voltage

Unit SelectionTentatively select a 5-ton unit — ModelSAVE050. Refer to Table PD-6 to obtaingross total and sensible unit capabilities,gpm, and leaving water temperature atnominal conditions:

Total MBh — 54.4Sensible MBh — 39.8GPM — 12.8LWT — 95

The SAVE 050 meets the total andsensible design requirements.

Since the difference between enteringand leaving water is 7 F, multiply thecapacities and water flow by correctionfactors on Table PD-??.

Cooling capacity multiplier 1.01Sensible capacity multiplier 1.01Water flow multiplier 1.39

54.4 x 1.01 = 54.95 MBh39.8 x 1.01 + 40.20 MBh12.8 x 1.39 + 17.8 GPM

Refer to Table PD-1 to determineapproximate brake horsepower and fanrpm:1035 rpm and 1.09 bhp.

Determine net capacities by subtractingfan motor heat from gross capacities:2.8 x 1.09 bph = 3.1 MBhNet total capacity =67.8 - 3.1 = 64.7 MBh

Net sensible capacity =48.7 - 3.1 = 45.6 MBh

Qs = 1.085 x CFM x (Tr-TS)40,200 = 1.085 x 1950 x (80-TS)TS = 80 - 40,200

(1.085) (1950)

TS = 61 F

Design Conditions— 80 F/67 F DB/WB return air

temperature— 95 F Ambient

— 95,000 BTUH Total Net— 76,500 BTUH Sensible Net

— 0.39 External Static Pressure(evaporator fan)

— 4200 CFM— 0.25 External static pressure

(condenser fan)

Required1. Select unit2. Fan speed and BHP for a) Evaporator fan b) Condenser fan3. Supply air temperature DB

Solution1. Select Unit

Initially Select aa 10-Ton Unit

From Table PD-13

80/67 EAT95 F AMB = 107.8 MBh Total Gross4200 CFM 81.5 MBh Sensible

2. Fan speed and BHP determination

Total Static Pressure

Evaporator Condenser0.380 esp 0.250 esp

From Table PD-3Evaporator10-ton unit4200 CFM = 1078 RPM

Note: If values fall between cfm’s oresp’s it is proper to interpolate betweenvalues. Do not extrapolate beyondvalues in catalog. Contact Tranemarketing department for assistance.

Fan Motor Heat Equation

Fan motor heat = 3.2 x 2.5 = 8.0 MBhNet total capacity = 128.3 - 8.0 = 120.3MBhNet sensible capacity = 101.3 - 8.0 = 93.3MBh

Conclusion:Required — 95,000 BTUH Total Net

76,500 BTUH TotalSensible Net

Provided — 120,300 BTUH Total Net93,300 BTUH Total Net

The 10-ton unit is the proper choice forthis application.

Page 11: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

11PKG-PRC006-EN

Three transmission options exist for theevaporator fan motor: Std. option,option 1, option 2. In addition, there is anoption for those cases in which the unitis operated with a plenum box. Themotors for each transmission option canbe found in the general facts tables.

PerformanceData

FanData

Table PD-1 — Fan Performance SRVE/SIVE/SAVE 5 Tons External static pressure with permanent air filter inches of water (Pa)

.08 .16 .24 .31 .39Model Airflow (19.9) (39.8) (59.8) (77.2) (97.1)

Option 5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP1802 3060 815 0.40 852 0.43 888 0.45 923 0.48 957 0.51

MT 1.0 CV 1877 3188 843 0.45 879 0.48 914 0.51 948 0.53MS: 78,5 A 106,5 1952 3315 869 0.50 904 0.53 938 0.56

STD BS: 159 (7") 2028 3443 897 0.56 931 0.59 964 0.62B: 1X A34 2102 3570 925 0.62 957 0.65

2178 3698 952 0.682253 3825

External static pressure with permanent air filter inches of water (Pa).08 .16 .24 .31 .39 .50 .63 .79

Model Airflow (19.9) (39.8) (59.8) (77.2) (97.1) (124.5) (156.9 (196.7)Option 5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1802 3060 990 0.54 1055 0.61 1117 0.68MT 1.0 CV 1877 3188 981 0.57 1013 0.60 1076 0.67 1136 0.74MS: 78,5 A 106,5 1952 3315 971 0.59 1003 0.62 1035 0.66 1096 0.73 1155 0.80

OP1 BS: 133 (6") 2028 3443 996 0.65 1027 0.68 1058 0.72 1117 0.79B: 1X A32 2102 3570 989 0.68 1020 0.71 1051 0.75 1081 0.78 1139 0.85

2178 3698 984 0.71 1015 0.74 1045 0.78 1075 0.81 1104 0.852253 3825 981 0.75 1012 0.78 1042 0.81 1071 0.85 1100 0.88 1128 0.92

External static pressure with permanent air filter inches of water (Pa).63 .79 .94 1.10 1.26 1.42 1.57

Model Airflow (156.9) (96.7) (234.1) (273.9) (313.7) (353.6) (390.9)Option 5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1802 3060 1176 0.75 1234 0.83 1289 0.91 1343 0.98 1395 1.05MT 1.5 CV 1877 3188 1195 0.81 1251 0.89 1305 0.97 1358 1.05 1409 1.12MS: 78.5 A 106.5 1952 3315 1212 0.88 1267 0.95 1320 1.03 1372 1.11 1422 1.19

OP2 BS: 108 (5") 2028 3443 1175 0.86 1230 0.94 1284 1.02 1337 1.10 1387 1.18B: 1X A31 2102 3570 1195 0.93 1249 1.01 1302 1.09 1353 1.16 1403 1.24

2178 3698 1160 0.92 1215 1.00 1269 1.08 1320 1.15 1371 1.23 1420 1.312253 3825 1183 0.99 1237 1.07 1289 1.14 1340 1.22 1389 1.30

MT = Motor (CV).MS = Motor Sheave, variable pitch (mm).FS = Fan Sheave (mm).B = Belt.

Page 12: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN12

PerformanceData

Table PD-2 — Fan Performance SRVE/SIVE/SAVE 7.5 Tons External static pressure with permanent air filter inches of water (Pa)

.08 .16 .24 .31 .39Model Airflow (19.9) (39.8) (59.8) (77.2) (97.1)

Option 7.5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2703 4590 688 0.64 720 0.68 751 0.72 781 0.77 811 0.82

MT 1.5 CV 2815 4780 712 0.72 743 0.76 773 0.81 802 0.86 831 0.91MS: 78,5 A 106,5 2927 4970 735 0.81 765 0.85 794 0.90 822 0.95

STD BS: 184 (8") 3041 5163 760 0.90 788 0.95 816 1.00B: 1X A33 3154 5355 784 1.01 811 1.06 838 1.10

3257 5548 808 1.12 834 1.173380 5740 834 1.24

FanData

External static pressure with permanent air filter inches of water (Pa).16 .24 .31 .39 .50 .63 .79 .94 1.10 1.26

Model Airflow (39.8) (59.8) (77.2) (97.1) (124.5) (156.9) (196.7) (234.1) (273.9) (313.7)Option 7.5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2703 4590 840 0.87 896 0.97 950 1.08 1002 1.19 1052 1.30 1100 1.41MT 2.0 CV 2815 4780 859 0.96 913 1.06 966 1.17 1017 1.28 1066 1.39 1113 1.50MS: 78,5 A 106,5 2927 4970 850 0.99 877 1.05 931 1.16 982 1.26 1031 1.37 1079 1.49 1126 1.60

OP1 BS: 133 (6") 3041 5163 844 1.05 871 1.10 897 1.15 949 1.25 999 1.36 1047 1.47 1094 1.59B: 1X A30 3154 5355 865 1.15 891 1.21 917 1.26 968 1.36 1016 1.47 1064 1.59 1110 1.71

3267 5548 861 1.22 886 1.27 912 1.32 937 1.37 986 1.47 1034 1.58 1080 1.70 1125 1.833380 5740 859 1.29 885 1.34 910 1.39 935 1.44 959 1.49 1007 1.59 1053 1.70 1098 1.83

External static pressure with permanent air filter inches of water (Pa)1.10 1.26 1.42 1.57

Model Airflow (273.9) (313.7) (353.6) (390.9)Option 7.5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP

2703 4590 1147 1.51 1193 1.60MT 3.0 CV 2815 4780 1159 1.61 1204 1.75MS: 80 A 110 2927 4970 1171 1.74 1215 1.88

OP2 BS: 105 (5") 3041 5163 1140 1.72 1184 1.86 1227 2.03B: 1X B26 3154 5355 1154 1.83 1198 2.01 1240 2.17

3267 5548 1169 1.97 1211 2.16 1253 2.343380 5740 1142 1.96 1185 2.15 1227 2.32 1268 2.50

MT = Motor (CV).MS = Motor Sheave, variable pitch (mm).FS = Fan Sheave (mm).B = Belt.

Page 13: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

13PKG-PRC006-EN

Table PD-3 — Fan Performance SRVE/SIVE/SAVE 10 Tons External static pressure with permanent air filter inches of water (Pa)

.08 .16 .24 .31Model Airflow (19.9) (39.8) (59.8) (77.2)

Option 10 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP3604 6120 839 0.84 875 0.89 911 0.94 945 1.00

MT 1.5 CV 3754 6375 866 0.94 902 0.99 936 1.05 969 1.11MS: 78,5 A 106,5 3905 6630 895 1.04 929 1.10 963 1.16

STD BS: 159 (7") 4055 6885 924 1.16 957 1.22B: 1X A33 4205 7140 954 1.29

4355 73954505 7650

PerformanceData

FanData

External static pressure with permanent air filter inches of water (Pa).08 .16 .24 .31 .39 .50 .63

Model Airflow (19.9) (39.8) (59.8) (77.2) (97.1) (124.5) (156.9)Option 10 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3604 6120 979 1.07 1012 1.13 1075 1.26MT 2.0 CV 3754 6375 1002 1.17 1034 1.24 7096 1.38MS: 78,5 A 106,5 3905 6630 995 1.23 1027 1.29 1058 1.36 1118 1.51

OP1 BS: 133 (6") 4055 6885 989 1.28 1021 1.35 1051 1.42 1082 1.49B: 1X A31 4205 7140 986 1.35 1017 1.42 1048 1.49 1078 1.56 1107 1.63

4355 7395 984 1.42 1015 1.49 1045 1.55 1075 1.63 1104 1.704505 7650 1013 1.56 1043 1.63 1072 1.70 1101 1.77

External static pressure with permanent air filter inches of water (Pa).39 .50 .63 .79 .94 1.10 1.26 1.42 1.57

Model Airflow (97.1) (124.5) (156.9) (196.7) (234.1) (273.9) (313.7) (353.6) (390.9)Option 10 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3604 6120 1136 1.41 1195 1.55 1252 1.71 1307 1.87 1360 2.01 1412 2.16MT 3.0 CV 3754 6375 1156 1.53 1213 1.68 1269 1.83 1322 1.98 1375 2.14 1425 2.29MS: 80 A 110 3905 6630 1176 1.66 1232 1.81 1287 1.97 1340 2.12 1391 2.28 1441 2.43

OP2 BS: 105 (5") 4055 6885 1140 1.64 1197 1.79 1252 1.94 1305 2.10 1357 2.26 1407 2.42 1456 2.57B: 1X B30 4205 7140 1164 1.78 1220 1.93 1273 2.08 1325 2.24 1376 2.40 1425 2.56 1473 2.71

4355 7395 1132 1.77 1188 1.92 1242 2.07 1295 2.23 1346 2.39 1395 2.54 1444 2.714505 7650 1130 1.84 1157 1.92 1212 2.06 1265 2.22 1316 2.37 1366 2.53 1414 2.69

MT = Motor (CV).MS = Motor Sheave, variable pitch (mm).FS = Fan Sheave (mm).B = Belt.

Page 14: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN14

Table PD-4 — Fan Performance SRVE/SIVE/SAVE 12.5 Tons External static pressure with permanent air filter inches of water (Pa)

.08 .16 .24 .31 .39 .50Model Airflow (19.9) (39.8) (59.8) (77.2) (97.1) (124.5)

Option 12.5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP4505 7650 630 0.81 666 0.89 701 0.98 735 1.08 768 1.18 800 1.29

MT 2.0 CV 4694 7970 649 0.93 684 1.01 718 1.09 751 1.18 783 1.27 814 1.37MS: 78,5 A 106,5 4882 8290 670 1.04 703 1.12 736 1.20 768 1.29 799 1.39

STD BS: 184 (8") 5069 8608 690 1.15 723 1.24 754 1.32 785 1.41 816 1.51B: 1X A33 5256 8925 711 1.28 743 1.37 774 1.46 804 1.55

5445 9243 731 1.41 762 1.50 792 1.605630 9560 753 1.56 783 1.65 812 1.75

PerformanceData

FanData

External static pressure with permanent air filter inches of water (Pa).31 .39 .50 .63 .79 .94 1.10

Model Airflow (77.2) (97.1) (124.5) (156.9) (196.7) (234.1) (273.9)Option 12.5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

4505 7650 861 1.50 919 1.62 975 1.88 1029 2.06MT 3.0 CV 4694 7970 874 1.57 931 1.79 985 2.00 1038 2.23MS: 80 A 110 4882 8290 830 1.49 888 1.69 944 1.91 997 2.13 1049 2.35

OP1 BS: 143 (6") 5069 8608 845 1.61 902 1.82 957 2.04 1010 2.26 1060 2.48B: 1X B30 5256 8925 833 1.65 862 1.75 918 1.97 971 2.18 1023 2.40

5445 9243 821 1.69 850 1.79 878 1.90 932 2.11 985 2.33 1035 2.555630 9560 841 1.85 868 1.95 896 2.06 949 2.27 1000 2.49

External static pressure with permanent air filter inches of water (Pa).94 1.10 1.26 1.42 1.57

Model Airflow (234.1) (273.9) (313.7) (353.6) (390.9)Option 12.5 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

4505 7650 1081 2.26 1131 2.52 1179 2.73MT 4.0 CV 4694 7970 1089 2.44 1139 2.65 1187 2.81MS: 80 A 110 4882 8290 1099 2.56 1148 2.77 1195 2.92

OP2 BS: 118 (5") 5069 8608 1109 2.69 1156 2.89 1203 3.13B: 1X B27 5256 8925 1073 2.62 1121 2.84 1167 2.95 1213 3.20

5445 9243 1084 2.77 1131 2.98 1177 3.105630 9560 1050 2.71 1098 2.93 1144 3.15 1189 3.30

MT = Motor (CV).MS = Motor Sheave, variable pitch (mm).FS = Fan Sheave (mm).B = Belt.

Page 15: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

15PKG-PRC006-EN

Table PD-5 — Fan Performance SRVE/SIVE/SAVE 15 Tons External static pressure with permanent air filter inches of water (Pa)

.08 .16 .24 .31 .39Model Airflow (19.9) (39.8) (59.8) (77.2) (97.1)

Option 15 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP5406 9180 664 1.22 696 1.30 728 1.38 759 1.48 789 1.57

MT 3.0 CV 5632 9563 686 1.36 717 1.45 747 1.54 777 1.64 806 1.73MS: 80 A 110 5857 9945 707 1.52 737 1.61 766 1.71 795 1.81

STD BS: 194 (8") 6080 10323 728 1.69 757 1.79 785 1.89B: 1X B33 6302 10700 749 1.88 777 1.98 804 2.08

6530 11088 771 2.08 798 2.196758 11475 793 2.30

PerformanceData

FanData

External static pressure with permanent air filter inches of water (Pa).16 .24 .31 .39 .50 .63 .79 .94 1.10 1.26

Model Airflow (39.8) (59.8) (77.2) (97.1) (124.5) (156.9) (196.7) (234.1) (273.9) (313.7)Option 15 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

5406 9180 818 1.66 875 1.87 930 2.08 983 2.30 1033 2.52 1082 2.74MT 4.0 CV 5632 9563 835 1.83 890 2.03 944 2.25 995 2.47 1045 2.69MS: 80 A 110 5857 9945 824 1.91 852 2.01 906 2.21 958 2.43 1008 2.65 1057 2.87

OP1 BS: 143 (6") 6080 10323 813 1.99 841 2.09 868 2.19 921 2.40 972 2.61 1021 2.83 1069 3.06B: 1X B29 6302 10700 832 2.19 858 2.28 885 2.39 936 2.59 986 2.80 1034 3.02

6530 11088 825 2.29 851 2.40 877 2.50 903 2.60 953 2.81 1002 3.02 1049 3.246758 11475 819 2.41 845 2.52 871 2.62 896 2.72 921 2.85 970 3.03 1017 3.23 1064 3.46

External static pressure with permanent air filter inches of water (Pa)1.10 1.26 1.42 1.57

Model Airflow (273.9) (313.7) (353.6) (390.9)Option 15 TR CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP

5406 9180 1130 2.95 1176 3.17MT 5.5 CV 5632 9563 1093 2.91 1140 3.13 1185 3.37MS: 80 A 110 5857 9945 1104 3.10 1150 3.33 1194 3.58

OP2 BS: 118 (5") 6080 10323 1115 3.29 1160 3.53 1204 3.80B: 1X B27 6302 10700 1081 3.26 1126 3.50 1171 3.77 1214 4.02

6530 11088 1095 3.48 1139 3.74 1183 4.00 1225 4.276758 11475 1108 3.71 1152 4.00 1195 4.20 1236 4.45

MT = Motor (CV).MS = Motor Sheave, variable pitch (mm).FS = Fan Sheave (mm).B = Belt.

Page 16: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN16

Water Cooled50 Hz

PerformanceData

Table PD-6 — Gross Cooling Capacities SAVE-050 English ENT Water Temp. (°F)

75 85Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM75 49.4 40.9 11.9 55.3 31.2 12.8 61.7 21.5 14.1 48.1 40.2 11.5 53.9 30.6 12.8 60.3 21.0 14.1

1800 80 50.0 48.1 11.9 55.3 39.1 12.8 61.7 29.3 14.1 48.7 47.2 11.9 53.9 38.5 12.8 60.2 28.8 14.185 52.0 51.0 12.3 55.2 45.6 12.8 61.6 35.8 14.1 50.9 49.9 12.3 53.8 45.0 12.8 60.2 35.3 14.190 54.5 53.4 12.8 55.5 51.6 12.8 61.6 42.2 14.1 53.4 52.3 12.8 54.2 50.9 12.8 60.1 41.7 14.175 50.1 42.3 11.9 55.9 32.0 13.2 62.3 21.7 14.1 48.6 41.6 11.9 54.5 31.4 12.8 60.9 21.2 14.1

1950 80 50.8 49.5 11.9 55.8 40.4 12.8 62.3 30.0 14.1 49.5 48.5 11.9 54.4 39.8 12.8 60.8 29.5 14.185 53.3 52.2 12.3 55.8 47.3 12.8 62.2 36.9 14.1 52.0 51.0 12.3 54.4 46.7 12.8 60.8 36.4 14.190 55.7 54.6 12.8 56.3 53.4 13.2 62.2 43.7 14.1 54.6 53.5 12.8 55.0 52.7 13.2 60.7 43.2 14.175 50.6 43.6 11.9 56.5 32.8 13.2 62.9 21.9 14.5 49.1 42.9 11.9 55.0 32.2 13.2 61.4 21.4 14.1

2100 80 51.7 50.6 11.9 56.5 41.6 13.2 62.8 30.7 14.1 50.5 49.5 11.9 54.9 41.0 13.2 61.3 30.2 14.185 54.3 53.2 12.8 56.5 48.9 13.2 62.8 38.0 14.1 53.1 52.0 12.8 55.0 48.3 13.2 61.3 37.5 14.190 56.9 55.8 13.2 57.2 55.2 13.2 62.7 45.3 14.1 55.7 54.6 13.2 55.8 54.2 13.2 61.2 44.6 14.175 51.0 45.0 11.9 57.0 33.5 13.2 63.5 22.1 14.5 49.5 44.2 11.9 55.4 32.9 13.2 61.9 21.6 14.5

2250 80 52.5 51.5 12.3 56.9 42.8 13.2 63.4 31.3 14.5 51.3 50.3 12.3 55.4 42.2 13.2 61.8 30.8 14.185 55.2 54.1 12.8 57.0 50.4 13.2 63.4 39.0 14.5 54.0 52.9 12.8 55.5 49.8 13.2 61.8 38.5 14.190 57.9 56.8 13.2 58.0 56.5 13.2 63.2 46.6 14.5 56.7 55.6 13.2 56.7 55.6 13.2 61.7 46.1 14.1

Table PD-6 — Gross Cooling Capacities SAVE-050 (Cont.) ENT Water Temp. (°F)

95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM75 46.7 39.6 11.5 52.4 30.1 12.8 58.6 20.4 14.1

1800 80 47.5 46.3 11.9 52.3 37.9 12.8 58.6 28.3 14.185 49.8 48.8 12.3 52.3 44.3 12.8 58.5 34.7 14.190 52.2 51.2 12.8 52.8 50.2 12.8 58.5 41.1 14.175 47.2 41.0 11.9 52.9 30.8 12.8 59.2 20.6 14.1

1950 80 48.4 47.5 11.9 52.9 39.2 12.8 59.2 28.9 14.185 50.9 49.9 12.3 52.9 46.1 12.8 59.1 35.9 14.190 53.5 52.4 12.8 53.7 51.9 13.2 59.1 42.6 14.175 47.7 42.3 11.9 53.5 31.6 12.8 59.7 20.8 14.1

2100 80 49.2 48.3 11.9 53.4 40.4 12.8 59.7 29.6 14.185 51.8 50.8 12.8 53.5 47.6 12.8 59.6 36.9 14.190 54.5 53.4 13.2 54.5 53.3 13.2 59.6 44.1 14.175 48.2 43.5 11.9 53.9 32.4 13.2 60.3 21.0 14.1

2250 80 50.2 49.2 12.3 53.9 41.6 13.2 60.2 30.3 14.185 52.7 51.7 12.8 54.0 49.1 13.2 60.2 37.9 14.190 55.4 54.3 13.2 55.4 54.3 13.2 60.1 45.6 14.1

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.

(°F) GPM MBh MBh4.5 2.21 1.01 1.017.2 1.39 1.01 1.0110.0 1.00 1.00 1.0012.6 0.79 0.99 1.0015.3 0.66 0.99 1.0018.0 0.56 0.98 0.99

Page 17: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

17PKG-PRC006-EN

Table PD-6 — Gross Cooling Capacities SAVE-050 Metric ENT Water Temp. (°C)

24.0 29.5Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s24 14.5 12.0 0.75 16.2 9.1 0.81 18.1 6.3 0.89 14.1 11.8 0.72 15.8 9.0 0.81 17.7 6.2 0.89

3060 27 14.6 14.1 0.75 16.2 11.5 0.81 18.1 8.6 0.89 14.3 13.8 0.75 15.8 11.3 0.81 17.6 8.4 0.8929 15.2 14.9 0.78 16.2 13.4 0.81 18.1 10.5 0.89 14.9 14.6 0.78 15.8 13.2 0.81 17.6 10.3 0.8932 16.0 15.7 0.81 16.3 15.1 0.81 18.1 12.4 0.89 15.6 15.3 0.81 15.9 14.9 0.81 17.6 12.2 0.8924 14.7 12.4 0.75 16.4 9.4 0.83 18.3 6.4 0.89 14.2 12.2 0.75 16.0 9.2 0.81 17.8 6.2 0.89

3315 27 14.9 14.5 0.75 16.4 11.8 0.81 18.3 8.8 0.89 14.5 14.2 0.75 15.9 11.7 0.81 17.8 8.6 0.8929 15.6 15.3 0.78 16.4 13.9 0.81 18.2 10.8 0.89 15.2 14.9 0.78 15.9 13.7 0.81 17.8 10.7 0.8932 16.3 16.0 0.81 16.5 15.7 0.83 18.2 12.8 0.89 16.0 15.7 0.81 16.1 15.5 0.83 17.8 12.7 0.8924 14.8 12.8 0.75 16.5 9.6 0.83 18.4 6.4 0.92 14.4 12.6 0.75 16.1 9.4 0.83 18.0 6.3 0.89

3570 27 15.2 14.8 0.75 16.5 12.2 0.83 18.4 9.0 0.89 14.8 14.5 0.75 16.1 12.0 0.83 18.0 8.9 0.8929 15.9 15.6 0.81 16.5 14.3 0.83 18.4 11.1 0.89 15.5 15.2 0.81 16.1 14.2 0.83 18.0 11.0 0.8932 16.7 16.3 0.83 16.8 16.2 0.83 18.4 13.3 0.89 16.3 16.0 0.83 16.4 15.9 0.83 17.9 13.1 0.8924 14.9 13.2 0.75 16.7 9.8 0.83 18.6 6.5 0.92 14.5 13.0 0.75 16.2 9.7 0.83 18.1 6.3 0.92

3825 27 15.4 15.1 0.78 16.7 12.6 0.83 18.6 9.2 0.92 15.0 14.7 0.78 16.2 12.4 0.83 18.1 9.0 0.8929 16.2 15.9 0.81 16.7 14.8 0.83 18.6 11.4 0.92 15.8 15.5 0.81 16.3 14.6 0.83 18.1 11.3 0.8932 17.0 16.6 0.83 17.0 16.5 0.83 18.5 13.6 0.92 16.6 16.3 0.83 16.6 16.3 0.83 18.1 13.5 0.89

Table PD-6 — Gross Cooling Capacities SAVE-050 (Cont.) ENT Water Temp. (°C)

35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s24 13.7 11.6 0.72 15.4 8.8 0.81 17.2 6.0 0.89

3060 27 13.9 13.6 0.75 15.3 11.1 0.81 17.2 8.3 0.8929 14.6 14.3 0.78 15.3 13.0 0.81 17.1 10.2 0.8932 15.3 15.0 0.81 15.5 14.7 0.81 17.1 12.0 0.8924 13.8 12.0 0.75 15.5 9.0 0.81 17.4 6.0 0.89

3315 27 14.2 13.9 0.75 15.5 11.5 0.81 17.4 8.5 0.8929 14.9 14.6 0.78 15.5 13.5 0.81 17.3 10.5 0.8932 15.7 15.4 0.81 15.7 15.2 0.83 17.3 12.5 0.8924 14.0 12.4 0.75 15.7 9.3 0.81 17.5 6.1 0.89

3570 27 14.4 14.2 0.75 15.6 11.8 0.81 17.5 8.7 0.8929 15.2 14.9 0.81 15.7 13.9 0.81 17.5 10.8 0.8932 16.0 15.7 0.83 16.0 15.6 0.83 17.5 12.9 0.8924 14.1 12.8 0.75 15.8 9.5 0.83 17.7 6.2 0.89

3825 27 14.7 14.4 0.78 15.8 12.2 0.83 17.6 8.9 0.8929 15.5 15.2 0.81 15.8 14.4 0.83 17.6 11.1 0.8932 16.2 15.9 0.83 16.2 15.9 0.83 17.6 13.4 0.89

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.(°C) l/s kW kW2.5 2.21 1.01 1.014.0 1.39 1.01 1.015.5 1.00 1.00 1.007.0 0.79 0.99 1.008.5 0.66 0.99 1.0010.0 0.56 0.98 0.99

Water Cooled50 Hz

PerformanceData

Page 18: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN18

PerformanceData

Water Cooled50 Hz

Table PD-7 — Gross Cooling Capacities SAVE-075 English ENT Water Temp. (°F)

75 85Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM75 71.3 59.5 16.3 80.2 45.4 17.6 90.0 31.3 19.8 69.2 58.6 15.9 77.9 44.5 17.6 87.3 30.2 19.4

2700 80 72.4 69.9 16.3 80.2 57.0 17.6 89.9 42.9 19.4 70.5 68.5 16.3 77.8 56.1 17.6 87.2 41.8 19.485 75.8 74.0 16.7 80.1 66.8 17.6 89.9 52.4 19.4 74.0 72.2 16.7 77.8 65.7 17.6 87.1 51.4 19.490 79.6 77.7 17.6 80.8 75.7 18.1 89.8 62.0 19.4 77.7 75.9 17.6 78.6 74.4 17.6 87.0 61.0 19.475 72.2 61.6 16.3 81.2 46.7 18.1 91.0 31.6 19.8 70.1 60.7 16.3 78.6 45.6 17.6 88.2 30.6 19.8

2925 80 73.7 71.8 16.3 81.1 59.0 18.1 90.8 43.9 19.8 71.9 70.2 16.3 78.0 58.0 17.6 88.1 42.9 19.485 77.5 75.7 17.2 81.1 69.1 18.1 90.8 54.0 19.8 75.7 73.9 17.2 78.7 68.1 17.6 88.0 53.1 19.490 81.4 79.5 18.1 82.0 78.1 18.1 90.7 64.2 19.8 79.5 77.6 18.1 79.8 76.8 18.1 88.0 63.2 19.475 72.9 63.6 16.3 81.9 47.8 18.1 91.8 31.9 19.8 70.8 62.5 16.3 79.5 46.8 18.1 88.9 30.8 19.8

3150 80 75.1 73.3 16.7 81.8 60.8 18.1 91.7 44.8 19.8 73.3 71.5 16.7 79.4 59.8 18.1 88.9 43.9 19.885 79.0 77.1 17.6 81.9 71.5 18.1 91.7 55.6 19.8 77.1 75.2 17.6 79.5 70.5 18.1 88.8 54.7 19.890 83.0 81.0 18.5 83.2 80.4 18.5 91.6 66.2 19.8 81.0 79.1 18.5 81.1 78.9 18.5 88.7 65.3 19.875 73.7 65.4 16.3 82.7 48.9 18.1 92.5 32.2 20.3 71.4 64.4 16.3 80.1 47.9 18.1 89.7 31.2 19.8

3375 80 76.3 74.5 17.2 82.6 62.5 18.1 92.4 45.8 20.3 74.4 72.7 17.2 80.0 61.6 18.1 89.6 44.8 19.885 80.4 78.5 17.6 82.7 73.7 18.5 92.4 57.1 20.3 78.4 76.6 17.6 80.2 72.6 18.1 89.6 56.1 19.890 84.5 82.5 18.5 84.5 82.3 18.5 92.3 68.3 20.3 82.5 80.5 18.5 82.4 80.4 18.5 89.5 67.4 19.8

Table PD-7 — Gross Cooling Capacities SAVE-075 (Cont.) ENT Water Temp. (°F)

95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM75 67.0 57.6 15.9 75.4 43.5 17.6 84.5 29.3 19.4

2700 80 68.6 67.0 16.3 75.3 55.1 17.6 84.4 40.9 19.485 72.2 70.5 16.7 75.3 64.7 17.6 84.3 50.5 19.490 75.8 74.0 17.6 76.2 73.1 17.6 84.3 60.0 19.475 67.8 59.6 16.3 76.1 44.7 17.6 85.3 29.6 19.4

2925 80 70.0 68.3 16.3 76.1 57.0 17.6 85.2 41.9 19.485 73.7 71.9 17.2 76.1 67.1 17.6 85.1 52.1 19.490 77.4 75.6 18.1 77.5 75.2 18.1 85.0 62.2 19.475 68.5 61.5 16.3 76.9 45.8 17.6 86.1 29.9 19.4

3150 80 71.2 69.6 16.7 76.7 58.8 17.6 86.0 42.9 19.485 75.1 73.3 17.6 77.0 69.4 18.1 85.9 53.6 19.490 78.9 77.0 18.1 78.9 77.0 18.1 85.8 64.4 19.475 69.2 63.2 16.3 77.5 46.9 18.1 86.6 30.1 19.8

3375 80 72.4 70.7 17.2 77.4 60.6 18.1 86.6 43.8 19.885 76.3 74.5 17.6 77.7 71.4 18.1 86.5 55.1 19.890 80.2 78.4 18.5 80.2 78.4 18.5 86.5 66.3 19.8

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.

(°F) GPM MBh MBh4.5 2.21 1.01 1.017.2 1.39 1.01 1.0110.0 1.00 1.00 1.0012.6 0.79 0.99 1.0015.3 0.66 0.99 1.0018.0 0.56 0.98 0.99

Page 19: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

19PKG-PRC006-EN

PerformanceData

Water Cooled50 Hz

Table PD-7 — Gross Cooling Capacities SAVE-075 Metric ENT Water Temp. (°C)

24.0 29.5Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s24 20.9 17.4 1.03 23.5 13.3 1.11 26.4 9.2 1.25 20.3 17.2 1.00 22.8 13.0 1.11 25.6 8.9 1.22

4590 27 21.2 20.5 1.03 23.5 16.7 1.11 26.3 12.6 1.22 20.7 20.1 1.03 22.8 16.4 1.11 25.6 12.3 1.2229 22.2 21.7 1.06 23.5 19.6 1.11 26.3 15.3 1.22 21.7 21.2 1.06 22.8 19.3 1.11 25.5 15.1 1.2232 23.3 22.8 1.11 23.7 22.2 1.14 26.3 18.2 1.22 22.8 22.2 1.11 23.0 21.8 1.11 25.5 17.9 1.2224 21.2 18.0 1.03 23.8 13.7 1.14 26.7 9.3 1.25 20.5 17.8 1.03 23.0 13.4 1.11 25.8 9.0 1.25

4970 27 21.6 21.1 1.03 23.8 17.3 1.14 26.6 12.9 1.25 21.1 20.6 1.03 22.9 17.0 1.11 25.8 12.6 1.2229 22.7 22.2 1.08 23.8 20.3 1.14 26.6 15.8 1.25 22.2 21.7 1.08 23.0 20.0 1.11 25.8 15.6 1.2232 23.9 23.3 1.14 24.0 22.9 1.14 26.6 18.8 1.25 23.3 22.7 1.14 23.4 22.5 1.14 25.8 18.5 1.2224 21.4 18.6 1.03 24.0 14.0 1.14 26.9 9.3 1.25 20.8 18.3 1.03 23.3 13.7 1.14 26.1 9.0 1.25

5355 27 22.0 21.5 1.06 24.0 17.8 1.14 26.9 13.1 1.25 21.5 21.0 1.06 23.3 17.5 1.14 26.1 12.9 1.2529 23.1 22.6 1.11 24.0 21.0 1.14 26.9 16.3 1.25 22.6 22.1 1.11 23.3 20.7 1.14 26.0 16.0 1.2532 24.3 23.8 1.17 24.4 23.6 1.17 26.8 19.4 1.25 23.7 23.2 1.17 23.8 23.1 1.17 26.0 19.1 1.2524 21.6 19.2 1.03 24.2 14.3 1.14 27.1 9.4 1.28 20.9 18.9 1.03 23.5 14.0 1.14 26.3 9.1 1.25

5740 27 22.4 21.8 1.08 24.2 18.3 1.14 27.1 13.4 1.28 21.8 21.3 1.08 23.5 18.0 1.14 26.2 13.1 1.2529 23.5 23.0 1.11 24.2 21.6 1.17 27.1 16.7 1.28 23.0 22.4 1.11 23.5 21.3 1.14 26.2 16.4 1.2532 24.8 24.2 1.17 24.8 24.1 1.17 27.1 20.0 1.28 24.2 23.6 1.17 24.1 23.6 1.17 26.2 19.7 1.25

Table PD-7 — Gross Cooling Capacities SAVE-075 (Cont.) ENT Water Temp. (°C)

35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s24 19.6 16.9 1.00 22.1 12.7 1.11 24.8 8.6 1.22

4590 27 20.1 19.6 1.03 22.1 16.1 1.11 24.7 12.0 1.2229 21.2 20.7 1.06 22.1 19.0 1.11 24.7 14.8 1.2232 22.2 21.7 1.11 22.3 21.4 1.11 24.7 17.6 1.2224 19.9 17.5 1.03 22.3 13.1 1.11 25.0 8.7 1.22

4970 27 20.5 20.0 1.03 22.3 16.7 1.11 25.0 12.3 1.2229 21.6 21.1 1.08 22.3 19.7 1.11 24.9 15.3 1.2232 22.7 22.1 1.14 22.7 22.1 1.14 24.9 18.2 1.2224 20.1 18.0 1.03 22.5 13.4 1.11 25.2 8.8 1.22

5355 27 20.9 20.4 1.06 22.5 17.2 1.11 25.2 12.6 1.2229 22.0 21.5 1.11 22.6 20.3 1.14 25.2 15.7 1.2232 23.1 22.6 1.14 23.1 22.6 1.14 25.1 18.9 1.2224 20.3 18.5 1.03 22.7 13.7 1.14 25.4 8.8 1.25

5740 27 21.2 20.7 1.08 22.7 17.7 1.14 25.4 12.8 1.2529 22.4 21.8 1.11 22.8 20.9 1.14 25.3 16.1 1.2532 23.5 23.0 1.17 23.5 23.0 1.17 25.3 19.4 1.25

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.(°C) l/s kW kW2.5 2.21 1.01 1.014.0 1.39 1.01 1.015.5 1.00 1.00 1.007.0 0.79 0.99 1.008.5 0.66 0.99 1.0010.0 0.56 0.98 0.99

Page 20: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN20

PerformanceData

Water Cooled50 Hz

Table PD-8 — Gross Cooling Capacities SAVE-100 English ENT Water Temp. (°F)

75 85Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM75 98.6 81.1 23.9 110.1 62.1 26.2 122.5 42.9 28.9 95.7 79.8 23.9 107.2 60.9 26.2 119.5 41.8 28.9

3600 80 99.3 95.5 23.9 110.0 77.5 26.2 122.4 58.3 28.9 96.8 93.8 23.9 107.1 76.3 26.2 119.4 57.2 28.985 103.2 101.7 24.8 109.9 90.2 26.2 122.3 70.9 28.9 101.0 99.5 24.8 107.0 89.0 26.2 119.3 69.9 28.990 108.0 106.5 25.7 110.3 102.3 26.2 122.2 83.6 28.9 105.8 104.2 25.7 107.5 101.0 26.2 119.2 82.5 28.975 99.7 83.8 24.4 111.3 63.6 26.6 123.8 43.3 28.9 96.9 82.5 23.9 108.3 62.5 26.6 120.8 42.2 28.9

3900 80 101.0 98.4 24.4 111.2 80.0 26.6 123.6 59.6 28.9 98.4 96.6 24.4 108.2 78.8 26.2 120.6 58.5 28.985 105.5 103.9 25.3 111.1 93.5 26.6 123.6 73.1 28.9 103.1 101.6 25.3 108.1 92.3 26.2 120.5 72.0 28.990 110.5 108.9 26.2 111.8 106.0 26.6 123.5 86.5 28.9 108.1 106.6 26.2 109.2 104.4 26.6 120.4 85.5 28.975 100.7 86.5 24.4 112.3 65.2 26.6 124.9 43.7 29.3 97.8 85.1 24.4 109.4 63.9 26.6 121.9 42.6 29.3

4200 80 102.6 100.8 24.8 112.2 82.4 26.6 124.7 60.9 29.3 100.1 98.7 24.8 109.3 81.2 26.6 121.8 59.8 29.385 107.5 106.0 25.7 112.2 96.7 26.6 124.6 75.1 29.3 105.2 103.6 25.7 109.3 95.5 26.6 121.7 74.0 29.390 112.7 111.0 26.6 113.4 109.2 27.1 124.5 91.3 29.3 110.3 108.7 26.6 110.7 107.6 26.6 121.6 88.3 28.975 101.7 89.0 24.4 113.3 66.7 27.1 125.9 44.0 29.3 98.7 87.6 24.4 110.3 65.5 26.6 122.8 43.0 29.3

4500 80 104.2 102.7 25.3 113.2 84.7 27.1 125.8 62.1 29.3 101.8 100.3 25.3 110.2 83.5 26.6 122.7 61.1 29.385 109.4 107.8 26.2 113.3 99.6 27.1 125.7 77.2 29.3 106.9 105.3 26.2 110.3 98.4 26.6 122.6 76.1 29.390 114.6 112.9 27.1 114.9 112.1 27.1 125.6 92.0 29.3 112.1 110.5 27.1 112.2 110.2 27.1 122.5 90.9 29.3

Table PD-8 — Gross Cooling Capacities SAVE-100 (Cont.) ENT Water Temp. (°F)

95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM75 93.0 78.5 23.9 104.1 59.7 26.2 116.3 40.7 28.4

3600 80 94.2 92.0 23.9 104.0 75.0 26.2 116.2 56.1 28.485 98.7 97.3 24.8 104.0 87.8 26.2 116.1 68.8 28.490 103.4 101.9 25.7 104.8 99.5 26.2 116.0 81.4 28.475 94.0 81.2 23.9 105.3 61.3 26.2 117.6 41.1 28.9

3900 80 95.9 94.5 24.4 105.2 77.6 26.2 117.5 57.4 28.985 100.8 99.3 25.3 105.2 91.0 26.2 117.4 70.9 28.990 105.8 104.2 26.6 106.4 102.8 26.6 117.3 84.2 28.975 94.9 83.7 24.4 106.3 62.7 26.6 118.6 41.5 28.9

4200 80 97.8 96.4 24.8 106.2 80.0 26.6 118.5 58.7 28.985 102.7 101.2 25.7 106.2 94.1 26.6 118.4 72.9 28.990 107.8 106.3 26.6 107.9 105.8 26.6 118.3 87.1 28.975 95.8 86.3 24.4 107.2 64.2 26.6 119.5 41.9 29.3

4500 80 99.3 97.9 25.3 107.1 82.3 26.6 119.4 60.0 29.385 104.5 102.9 26.2 107.2 97.1 26.6 119.3 74.9 29.390 109.7 108.1 27.1 109.6 108.0 27.1 119.2 89.8 29.3

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.

(°F) GPM MBh MBh4.5 2.21 1.01 1.017.2 1.39 1.01 1.0110.0 1.00 1.00 1.0012.6 0.79 0.99 1.0015.3 0.66 0.99 1.0018.0 0.56 0.98 0.99

Page 21: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

21PKG-PRC006-EN

PerformanceData

Water Cooled50 Hz

Table PD-8 — Gross Cooling Capacities SAVE-100 Metric ENT Water Temp. (°C)

24.0 29.5Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s24 28.9 23.8 1.51 32.3 18.2 1.65 35.9 12.6 1.82 28.1 23.4 1.51 31.4 17.9 1.65 35.0 12.3 1.82

6120 27 29.1 28.0 1.51 32.2 22.7 1.65 35.9 17.1 1.82 28.4 27.5 1.51 31.4 22.3 1.65 35.0 16.8 1.8229 30.2 29.8 1.57 32.2 26.4 1.65 35.8 20.8 1.82 29.6 29.2 1.57 31.4 26.1 1.65 35.0 20.5 1.8232 31.7 31.2 1.62 32.3 30.0 1.65 35.8 24.5 1.82 31.0 30.5 1.62 31.5 29.6 1.65 34.9 24.2 1.8224 29.2 24.6 1.54 32.6 18.6 1.68 36.3 12.7 1.82 28.4 24.2 1.51 31.7 18.3 1.68 35.4 12.4 1.82

6630 27 29.6 28.8 1.54 32.6 23.4 1.68 36.2 17.5 1.82 28.8 28.3 1.54 31.7 23.1 1.65 35.4 17.1 1.8229 30.9 30.5 1.59 32.6 27.4 1.68 36.2 21.4 1.82 30.2 29.8 1.59 31.7 27.1 1.65 35.3 21.1 1.8232 32.4 31.9 1.65 32.8 31.0 1.68 36.2 25.3 1.82 31.7 31.2 1.65 32.0 30.6 1.68 35.3 25.0 1.8224 29.5 25.3 1.54 32.9 19.1 1.68 36.6 12.8 1.85 28.7 25.0 1.54 32.0 18.7 1.68 35.7 12.5 1.85

7140 27 30.1 29.5 1.57 32.9 24.2 1.68 36.6 17.9 1.85 29.3 28.9 1.57 32.0 23.8 1.68 35.7 17.5 1.8529 31.5 31.0 1.62 32.9 28.3 1.68 36.5 22.0 1.85 30.8 30.4 1.62 32.0 28.0 1.68 35.7 21.7 1.8532 33.0 32.5 1.68 33.2 32.0 1.71 36.5 26.8 1.85 32.3 31.8 1.68 32.4 31.5 1.68 35.6 25.9 1.8224 29.8 26.1 1.54 33.2 19.5 1.71 36.9 12.9 1.85 28.9 25.7 1.54 32.3 19.2 1.68 36.0 12.6 1.85

7650 27 30.5 30.1 1.59 33.2 24.8 1.71 36.9 18.2 1.85 29.8 29.4 1.59 32.3 24.5 1.68 36.0 17.9 1.8529 32.0 31.6 1.65 33.2 29.2 1.71 36.8 22.6 1.85 31.3 30.9 1.65 32.3 28.8 1.68 35.9 22.3 1.8532 33.6 33.1 1.71 33.7 32.9 1.71 36.8 27.0 1.85 32.9 32.4 1.71 32.9 32.3 1.71 35.9 26.6 1.85

Table PD-8 — Gross Cooling Capacities SAVE-100 (Cont.) ENT Water Temp. (°C)

35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s24 27.2 23.0 1.51 30.5 17.5 1.65 34.1 11.9 1.79

6120 27 27.6 27.0 1.51 30.5 22.0 1.65 34.1 16.4 1.7929 28.9 28.5 1.57 30.5 25.7 1.65 34.0 20.2 1.7932 30.3 29.9 1.62 30.7 29.2 1.65 34.0 23.9 1.7924 27.5 23.8 1.51 30.8 18.0 1.65 34.5 12.0 1.82

6630 27 28.1 27.7 1.54 30.8 22.7 1.65 34.4 16.8 1.8229 29.5 29.1 1.59 30.8 26.7 1.65 34.4 20.8 1.8232 31.0 30.5 1.68 31.2 30.1 1.68 34.4 24.7 1.8224 27.8 24.5 1.54 31.1 18.4 1.68 34.8 12.2 1.82

7140 27 28.7 28.2 1.57 31.1 23.4 1.68 34.7 17.2 1.8229 30.1 29.7 1.62 31.1 27.6 1.68 34.7 21.4 1.8232 31.6 31.1 1.68 31.6 31.0 1.68 34.7 25.5 1.8224 28.1 25.3 1.54 31.4 18.8 1.68 35.0 12.3 1.85

7650 27 29.1 28.7 1.59 31.4 24.1 1.68 35.0 17.6 1.8529 30.6 30.2 1.65 31.4 28.4 1.68 35.0 22.0 1.8532 32.1 31.7 1.71 32.1 31.6 1.71 34.9 26.3 1.85

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.(°C) l/s kW kW2.5 2.21 1.01 1.014.0 1.39 1.01 1.015.5 1.00 1.00 1.007.0 0.79 0.99 1.008.5 0.66 0.99 1.0010.0 0.56 0.98 0.99

Page 22: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN22

PerformanceData

Water Cooled50 Hz

Table PD-9 — Gross Cooling Capacities SAVE-125 English ENT Water Temp. (°F)

75 85Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM75 122.6 103.1 28.2 137.2 78.8 30.8 153.0 54.0 33.9 119.0 101.5 27.7 133.1 77.1 30.8 148.6 52.6 33.5

4500 80 123.9 121.3 28.2 137.0 98.7 30.8 152.8 74.0 33.9 120.5 118.9 28.2 133.0 97.0 30.8 148.5 72.3 33.585 129.3 128.6 29.5 137.0 115.2 30.8 152.7 90.4 33.9 126.2 125.6 29.5 132.9 113.5 30.8 148.3 88.7 33.590 135.5 134.8 30.4 137.8 130.5 30.8 152.6 106.7 33.9 132.3 131.7 30.4 133.9 128.4 30.8 148.3 105.0 33.575 124.0 106.8 28.2 138.7 80.8 31.3 154.6 54.6 34.3 120.2 104.9 28.2 134.9 79.2 30.8 150.1 53.1 33.9

4875 80 126.1 124.8 28.6 138.6 101.9 31.3 154.4 75.7 34.3 122.8 122.0 28.6 134.9 100.2 30.8 149.8 74.1 33.985 132.0 131.4 29.9 138.4 119.3 31.3 154.3 93.1 34.3 128.9 128.3 29.9 134.9 117.7 30.8 149.8 91.5 33.990 138.4 137.7 31.3 139.8 135.1 31.3 154.3 110.5 34.3 135.2 134.6 31.3 135.9 132.8 31.3 149.7 108.9 33.975 125.3 110.0 28.6 140.0 82.8 31.7 155.9 55.1 34.3 121.5 108.4 28.2 135.9 81.1 31.3 151.3 53.6 34.3

5250 80 128.2 127.5 29.1 139.9 105.0 31.3 155.8 77.3 34.3 125.0 124.4 29.1 135.7 103.4 31.3 151.3 75.8 34.385 134.6 134.0 30.4 139.9 123.4 31.3 155.6 95.7 34.3 131.4 130.7 30.4 135.8 121.6 31.3 151.1 94.2 34.390 141.1 140.5 31.7 141.8 139.1 31.7 155.6 114.1 34.3 137.9 137.2 31.7 138.1 136.5 31.7 151.0 112.4 33.975 126.4 113.3 28.6 141.2 84.7 31.7 157.2 55.6 34.8 122.6 111.5 28.6 136.9 83.0 31.3 152.6 54.0 34.3

5625 80 130.3 129.7 29.5 141.0 108.0 31.7 157.1 79.0 34.8 127.1 126.5 29.5 136.8 106.3 31.3 152.4 77.3 34.385 136.9 136.3 30.8 141.1 127.3 31.7 156.9 98.3 34.8 133.6 132.9 30.8 137.0 125.3 31.3 152.4 96.8 34.390 143.6 143.0 32.1 143.8 142.4 32.1 156.8 117.6 34.8 140.2 139.5 32.1 140.2 139.3 32.1 152.2 116.0 34.3

Table PD-9 — Gross Cooling Capacities SAVE-125 (Cont.) ENT Water Temp. (°F)

95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM75 115.1 99.7 27.7 128.9 75.5 30.4 144.1 50.9 33.5

4500 80 117.2 116.2 28.2 128.8 95.3 30.4 143.9 70.7 33.585 123.0 122.4 29.5 128.8 111.6 30.4 143.8 87.2 33.590 129.1 128.4 30.4 130.0 126.3 30.8 143.5 103.5 33.575 116.5 103.1 28.2 130.3 77.4 30.8 145.3 51.4 33.5

4875 80 119.5 118.9 28.6 130.1 98.4 30.8 145.3 72.4 33.585 125.6 125.0 29.9 130.2 115.8 30.8 145.1 89.9 33.590 131.8 131.2 30.8 132.2 130.2 31.3 145.0 107.2 33.575 117.5 106.4 28.2 131.5 79.4 30.8 146.6 51.8 33.9

5250 80 121.6 121.0 29.1 131.4 101.6 30.8 146.5 74.1 33.985 127.9 127.3 30.4 131.6 119.7 30.8 146.4 92.5 33.990 134.3 133.7 31.7 134.3 133.3 31.7 146.3 110.9 33.975 118.8 109.5 28.6 132.5 81.2 31.3 147.7 52.4 33.9

5625 80 123.7 123.1 29.5 132.4 104.6 31.3 147.5 75.8 33.985 130.1 129.5 30.8 132.8 123.4 31.3 147.5 95.1 33.990 136.6 136.0 32.1 136.5 135.9 32.1 147.3 114.3 33.9

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.

(°F) GPM MBh MBh4.5 2.21 1.01 1.017.2 1.39 1.01 1.0110.0 1.00 1.00 1.0012.6 0.79 0.99 1.0015.3 0.66 0.99 1.0018.0 0.56 0.98 0.99

Page 23: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

23PKG-PRC006-EN

PerformanceData

Water Cooled50 Hz

Table PD-9 — Gross Cooling Capacities SAVE-125 Metric ENT Water Temp. (°C)

24.0 29.5Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s24 35.9 30.2 1.78 40.2 23.1 1.94 44.8 15.8 2.14 34.9 29.7 1.75 39.0 22.6 1.94 43.5 15.4 2.11

7650 27 36.3 35.6 1.78 40.2 28.9 1.94 44.8 21.7 2.14 35.3 34.8 1.78 39.0 28.4 1.94 43.5 21.2 2.1129 37.9 37.7 1.86 40.2 33.7 1.94 44.7 26.5 2.14 37.0 36.8 1.86 39.0 33.3 1.94 43.4 26.0 2.1132 39.7 39.5 1.92 40.4 38.2 1.94 44.7 31.3 2.14 38.8 38.6 1.92 39.2 37.6 1.94 43.4 30.8 2.1124 36.3 31.3 1.78 40.6 23.7 1.97 45.3 16.0 2.17 35.2 30.7 1.78 39.5 23.2 1.94 44.0 15.6 2.14

8285 27 37.0 36.6 1.81 40.6 29.9 1.97 45.2 22.2 2.17 36.0 35.7 1.81 39.5 29.4 1.94 43.9 21.7 2.1429 38.7 38.5 1.89 40.6 35.0 1.97 45.2 27.3 2.17 37.8 37.6 1.89 39.5 34.5 1.94 43.9 26.8 2.1432 40.6 40.4 1.97 41.0 39.6 1.97 45.2 32.4 2.17 39.6 39.4 1.97 39.8 38.9 1.97 43.9 31.9 2.1424 36.7 32.2 1.81 41.0 24.3 2.00 45.7 16.1 2.17 35.6 31.8 1.78 39.8 23.8 1.97 44.3 15.7 2.17

8920 27 37.6 37.4 1.83 41.0 30.8 1.97 45.7 22.7 2.17 36.6 36.4 1.83 39.8 30.3 1.97 44.3 22.2 2.1729 39.4 39.3 1.92 41.0 36.2 1.97 45.6 28.1 2.17 38.5 38.3 1.92 39.8 35.6 1.97 44.3 27.6 2.1732 41.4 41.2 2.00 41.5 40.8 2.00 45.6 33.4 2.17 40.4 40.2 2.00 40.5 40.0 2.00 44.2 33.0 2.1424 37.0 33.2 1.81 41.4 24.8 2.00 46.1 16.3 2.19 35.9 32.7 1.81 40.1 24.3 1.97 44.7 15.8 2.17

9560 27 38.2 38.0 1.86 41.3 31.6 2.00 46.0 23.2 2.19 37.2 37.1 1.86 40.1 31.1 1.97 44.6 22.7 2.1729 40.1 39.9 1.94 41.4 37.3 2.00 46.0 28.8 2.19 39.1 39.0 1.94 40.2 36.7 1.97 44.6 28.4 2.1732 42.1 41.9 2.03 42.1 41.7 2.03 45.9 34.5 2.19 41.1 40.9 2.03 41.1 40.8 2.03 44.6 34.0 2.17

Table PD-9 — Gross Cooling Capacities SAVE-125 (Cont.) ENT Water Temp. (°C)

35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s24 33.7 29.2 1.75 37.8 22.1 1.92 42.2 14.9 2.11

7650 27 34.3 34.1 1.78 37.8 27.9 1.92 42.2 20.7 2.1129 36.0 35.9 1.86 37.8 32.7 1.92 42.1 25.5 2.1132 37.8 37.6 1.92 38.1 37.0 1.94 42.1 30.3 2.1124 34.1 30.2 1.78 38.2 22.7 1.94 42.6 15.1 2.11

8285 27 35.0 34.8 1.81 38.1 28.8 1.94 42.6 21.2 2.1129 36.8 36.6 1.89 38.2 33.9 1.94 42.5 26.3 2.1132 38.6 38.4 1.94 38.7 38.2 1.97 42.5 31.4 2.1124 34.4 31.2 1.78 38.5 23.3 1.94 43.0 15.2 2.14

8920 27 35.6 35.5 1.83 38.5 29.8 1.94 42.9 21.7 2.1429 37.5 37.3 1.92 38.6 35.1 1.94 42.9 27.1 2.1432 39.4 39.2 2.00 39.4 39.1 2.00 42.9 32.5 2.1424 34.8 32.1 1.81 38.8 23.8 1.97 43.3 15.3 2.14

9560 27 36.2 36.1 1.86 38.8 30.7 1.97 43.2 22.2 2.1429 38.1 37.9 1.94 38.9 36.2 1.97 43.2 27.9 2.1432 40.0 39.8 2.03 40.0 39.8 2.03 43.2 33.5 2.14

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.(°C) l/s kW kW2.5 2.21 1.01 1.014.0 1.39 1.01 1.015.5 1.00 1.00 1.007.0 0.79 0.99 1.008.5 0.66 0.99 1.0010.0 0.56 0.98 0.99

Page 24: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN24

PerformanceData

Water Cooled50 Hz

Table PD-10 — Gross Cooling Capacities SAVE-150 English ENT Water Temp. (°F)

75 85Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM75 149.7 130.1 36.0 167.4 97.8 38.8 186.7 65.1 43.0 144.9 128.1 35.1 162.0 95.6 38.8 180.6 63.0 42.5

5400 80 153.6 150.8 36.0 167.2 124.2 38.8 186.6 91.5 43.0 149.5 146.8 36.0 161.8 122.1 38.8 180.4 89.4 42.585 161.3 158.4 37.9 167.5 145.9 38.8 186.4 113.4 43.0 157.1 154.3 37.4 162.2 143.6 38.8 180.3 111.2 42.590 169.3 166.2 39.3 169.9 164.6 39.7 186.3 135.1 43.0 164.9 161.9 39.3 165.1 161.3 39.3 180.1 133.0 42.575 151.5 134.7 35.6 169.1 100.5 39.3 188.5 65.8 43.4 146.7 132.4 35.6 163.5 98.4 38.8 182.3 63.8 43.0

5850 80 156.7 153.9 37.0 169.0 128.7 39.3 188.4 93.9 43.4 152.5 149.8 36.5 163.3 126.5 38.8 182.1 91.8 43.085 164.8 161.8 38.3 169.5 151.5 39.3 188.2 117.2 43.4 160.4 157.5 38.3 164.1 149.0 39.3 182.0 115.1 43.090 173.0 169.9 40.2 173.0 169.5 40.2 188.1 140.3 43.4 168.5 165.4 39.7 168.4 165.3 39.7 181.8 138.2 42.575 153.1 139.2 36.0 170.6 103.2 39.7 190.1 66.5 43.4 148.2 136.6 36.0 164.9 101.0 39.3 183.8 64.4 43.0

6300 80 159.7 156.8 37.4 170.5 133.0 39.7 190.0 96.2 43.4 155.3 152.4 37.4 164.8 130.8 39.3 183.6 94.0 43.085 167.9 164.9 39.3 171.3 156.7 39.7 189.8 120.8 43.4 163.3 160.4 38.8 166.0 154.1 39.3 183.5 118.8 43.090 176.3 173.1 40.6 176.2 173.0 40.6 189.7 145.3 43.4 171.6 168.5 40.6 171.5 168.4 40.6 183.4 143.2 43.075 154.6 143.2 36.5 171.9 105.8 39.7 191.6 67.2 43.9 149.7 140.6 36.0 166.2 103.6 39.7 185.0 65.0 43.4

6750 80 162.3 159.3 37.9 171.8 137.2 39.7 191.3 98.5 43.9 157.8 154.9 37.9 166.1 134.9 39.7 184.9 96.3 43.485 170.8 167.7 39.7 173.1 161.5 40.2 191.2 124.4 43.9 166.1 163.1 39.7 167.6 158.7 39.7 184.7 122.3 43.490 179.3 176.0 41.6 179.3 176.0 41.6 191.1 150.3 43.9 174.5 171.3 41.1 174.5 171.3 41.1 184.6 148.1 43.4

Table PD-10 — Gross Cooling Capacities SAVE-150 (Cont.) ENT Water Temp. (°F)

95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73DB

CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM75 139.9 125.4 35.1 156.2 93.4 38.3 174.2 60.9 42.0

5400 80 145.2 142.6 36.0 156.1 119.8 38.3 174.0 87.2 42.085 152.6 149.9 37.4 156.6 141.1 38.3 173.9 109.1 42.090 160.3 157.4 39.3 160.2 157.3 39.3 173.8 130.8 42.075 141.6 129.8 35.1 157.7 96.1 38.8 175.8 61.6 42.0

5850 80 148.1 145.4 36.5 157.6 124.2 38.8 175.6 89.6 42.085 155.8 153.0 38.3 158.5 146.4 38.8 175.5 112.8 42.090 163.6 160.7 39.7 163.5 160.6 39.7 175.4 136.0 42.075 143.1 133.9 35.6 159.0 98.8 38.8 177.2 62.2 42.5

6300 80 150.7 148.0 37.0 158.9 128.6 38.8 177.0 91.9 42.585 158.6 155.7 38.8 160.3 151.2 39.3 176.9 116.5 42.590 166.7 163.7 40.2 166.6 163.6 40.2 176.8 141.0 42.575 144.7 137.7 36.0 160.2 101.4 39.3 178.3 62.8 43.0

6750 80 153.1 150.3 37.4 160.1 132.7 39.3 178.2 94.1 43.085 161.2 158.3 39.3 162.1 155.6 39.7 178.1 120.1 43.090 169.4 166.4 41.1 169.3 166.2 41.1 178.0 145.9 43.0

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.

(°F) GPM MBh MBh4.5 2.21 1.01 1.017.2 1.39 1.01 1.0110.0 1.00 1.00 1.0012.6 0.79 0.99 1.0015.3 0.66 0.99 1.0018.0 0.56 0.98 0.99

Page 25: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

25PKG-PRC006-EN

PerformanceData

Water Cooled50 Hz

Table PD-10 — Gross Cooling Capacities SAVE-150 Metric ENT Water Temp. (°C)

24.0 29.5Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s TGC SHC l/s24 43.9 38.1 2.27 49.1 28.6 2.45 54.7 19.1 2.71 42.5 37.5 2.21 47.5 28.0 2.45 52.9 18.5 2.68

9180 27 45.0 44.2 2.27 49.0 36.4 2.45 54.7 26.8 2.71 43.8 43.0 2.27 47.4 35.8 2.45 52.9 26.2 2.6829 47.3 46.4 2.39 49.1 42.7 2.45 54.6 33.2 2.71 46.0 45.2 2.36 47.5 42.1 2.45 52.8 32.6 2.6832 49.6 48.7 2.48 49.8 48.2 2.51 54.6 39.6 2.71 48.3 47.4 2.48 48.4 47.3 2.48 52.8 39.0 2.6824 44.4 39.5 2.24 49.6 29.5 2.48 55.2 19.3 2.74 43.0 38.8 2.24 47.9 28.8 2.45 53.4 18.7 2.71

9945 27 45.9 45.1 2.33 49.5 37.7 2.48 55.2 27.5 2.74 44.7 43.9 2.30 47.9 37.1 2.45 53.4 26.9 2.7129 48.3 47.4 2.42 49.7 44.4 2.48 55.1 34.3 2.74 47.0 46.1 2.42 48.1 43.7 2.48 53.3 33.7 2.7132 50.7 49.8 2.53 50.7 49.7 2.53 55.1 41.1 2.74 49.4 48.5 2.51 49.3 48.4 2.51 53.3 40.5 2.6824 44.8 40.8 2.27 50.0 30.2 2.51 55.7 19.5 2.74 43.4 40.0 2.27 48.3 29.6 2.48 53.9 18.9 2.71

10710 27 46.8 45.9 2.36 50.0 39.0 2.51 55.7 28.2 2.74 45.5 44.7 2.36 48.3 38.3 2.48 53.8 27.6 2.7129 49.2 48.3 2.48 50.2 45.9 2.51 55.6 35.4 2.74 47.9 47.0 2.45 48.6 45.2 2.48 53.8 34.8 2.7132 51.7 50.7 2.56 51.6 50.7 2.56 55.6 42.6 2.74 50.3 49.4 2.56 50.3 49.3 2.56 53.7 42.0 2.7124 45.3 42.0 2.30 50.4 31.0 2.51 56.1 19.7 2.77 43.9 41.2 2.27 48.7 30.4 2.51 54.2 19.0 2.74

11475 27 47.6 46.7 2.39 50.4 40.2 2.51 56.1 28.9 2.77 46.2 45.4 2.39 48.7 39.5 2.51 54.2 28.2 2.7429 50.0 49.1 2.51 50.7 47.3 2.53 56.0 36.5 2.77 48.7 47.8 2.51 49.1 46.5 2.51 54.1 35.8 2.7432 52.5 51.6 2.62 52.5 51.6 2.62 56.0 44.0 2.77 51.1 50.2 2.59 51.1 50.2 2.59 54.1 43.4 2.74

Table PD-10 — Gross Cooling Capacities SAVE-150 (Cont.) ENT Water Temp. (°C)

35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0DB

m3/h (°C) TGC SHC l/s TGC SHC l/s TGC SHC l/s24 41.0 36.7 2.21 45.8 27.4 2.42 51.1 17.8 2.65

9180 27 42.5 41.8 2.27 45.7 35.1 2.42 51.0 25.6 2.6529 44.7 43.9 2.36 45.9 41.4 2.42 51.0 32.0 2.6532 47.0 46.1 2.48 46.9 46.1 2.48 50.9 38.3 2.6524 41.5 38.0 2.21 46.2 28.2 2.45 51.5 18.1 2.65

9945 27 43.4 42.6 2.30 46.2 36.4 2.45 51.5 26.3 2.6529 45.6 44.8 2.42 46.4 42.9 2.45 51.4 33.1 2.6532 48.0 47.1 2.51 47.9 47.1 2.51 51.4 39.8 2.6524 41.9 39.2 2.24 46.6 28.9 2.45 51.9 18.2 2.68

10710 27 44.2 43.4 2.33 46.6 37.7 2.45 51.9 26.9 2.6829 46.5 45.6 2.45 47.0 44.3 2.48 51.8 34.1 2.6832 48.8 48.0 2.53 48.8 47.9 2.53 51.8 41.3 2.6824 42.4 40.4 2.27 46.9 29.7 2.48 52.3 18.4 2.71

11475 27 44.8 44.0 2.36 46.9 38.9 2.48 52.2 27.6 2.7129 47.2 46.4 2.48 47.5 45.6 2.51 52.2 35.2 2.7132 49.6 48.7 2.59 49.6 48.7 2.59 52.2 42.7 2.71

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Capacity Correction Factor TableDelta TWater Total Cap. Sens. Cap.(°C) l/s kW kW2.5 2.21 1.01 1.014.0 1.39 1.01 1.015.5 1.00 1.00 1.007.0 0.79 0.99 1.008.5 0.66 0.99 1.0010.0 0.56 0.98 0.99

Page 26: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN26

PerformanceData

Air Cooled50 Hz

Table PD-11 — Gross Cooling Capacities SRVE-050 English Ambient Temperature (°F)

85 95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 48.7 41.1 54.5 31.2 60.8 21.2 47.2 40.4 52.9 30.5 59.0 20.6

1800 80 49.4 48.1 54.4 39.2 60.7 29.2 48.1 47.0 52.8 38.6 58.9 28.685 51.7 50.8 54.4 45.9 60.7 35.9 50.5 49.5 52.8 45.2 58.9 35.390 54.2 53.1 54.8 51.9 60.6 42.5 52.9 51.9 53.3 51.1 58.9 41.975 49.2 42.4 55.0 32.0 61.4 21.4 47.7 41.8 53.4 31.3 59.6 20.8

1950 80 50.2 49.3 55.0 40.6 61.4 30.0 49.1 48.2 53.3 39.9 59.6 30.085 52.8 51.8 55.0 47.6 61.3 37.0 51.5 50.5 53.4 46.9 59.5 36.490 55.4 54.4 55.7 53.7 61.3 44.1 54.1 53.0 54.3 52.7 59.5 43.575 49.7 43.8 55.5 32.8 61.9 21.6 48.2 43.2 53.9 32.1 60.1 21.0

2100 80 51.2 50.2 55.4 41.8 61.9 30.7 49.9 49.0 53.9 41.2 60.0 30.085 53.9 52.8 55.5 49.2 61.8 38.2 52.5 51.5 54.0 58.9 60.0 37.490 56.5 55.4 56.5 55.2 61.8 45.6 55.1 54.1 55.1 54.1 59.9 44.975 50.1 45.1 56.0 33.6 62.4 21.8 48.2 44.4 54.3 32.9 60.5 21.2

2250 80 52.1 51.1 56.0 43.1 62.3 31.3 50.8 49.8 54.3 42.4 60.5 30.785 54.7 53.7 56.1 50.8 62.3 39.2 53.4 52.4 54.5 50.0 60.4 38.690 57.5 56.4 57.5 56.4 62.2 47.0 56.1 55.0 56.1 55.0 60.4 46.4

Table PD-11 — Gross Cooling Capacities SRVE-050 (Cont.) English Ambient Temperature (°F)

105 115Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 45.7 39.7 51.2 29.9 57.1 19.9 44.2 39.0 49.4 29.1 55.0 19.1

1800 80 46.8 45.9 51.1 37.9 57.0 28.0 45.5 44.6 49.4 37.2 54.9 27.385 49.2 48.3 51.1 44.5 57.0 34.6 47.8 46.9 49.4 43.8 54.9 33.990 51.6 50.7 51.8 50.1 56.9 41.2 50.1 49.2 50.2 49.1 54.8 40.575 46.2 41.1 51.7 30.7 57.7 20.1 44.6 40.4 49.8 30.0 55.4 19.3

1950 80 47.8 46.9 51.6 39.2 57.6 28.6 46.4 45.6 49.8 38.5 55.4 27.985 50.2 49.3 51.7 46.2 57.6 35.7 48.8 47.8 49.9 45.3 55.3 34.990 52.7 51.7 52.7 51.6 57.5 42.7 51.2 50.2 51.2 50.2 55.3 42.075 46.6 42.3 52.2 31.4 58.1 20.3 45.2 41.6 50.2 30.8 55.9 19.6

2100 80 48.7 47.7 52.1 40.5 58.1 29.3 47.3 46.4 50.2 39.7 55.9 28.685 51.2 50.2 52.3 47.7 58.0 36.8 49.7 48.8 50.5 46.9 55.8 36.190 53.7 52.7 53.6 52.6 58.0 44.2 52.2 51.2 52.2 51.2 55.8 43.575 47.2 43.6 52.6 32.2 58.5 20.5 45.6 42.7 50.7 31.5 56.3 19.8

2250 80 49.4 48.5 52.5 41.7 58.4 30.0 48.0 47.1 50.6 41.0 56.2 29.285 52.1 51.1 52.8 49.2 58.4 37.9 50.5 49.5 51.0 48.3 56.2 37.190 54.6 53.6 54.6 53.6 58.4 45.7 53.0 52.0 53.0 52.0 56.1 44.9

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Page 27: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

27PKG-PRC006-EN

PerformanceData

Air Cooled50 Hz

Table PD-11 — Gross Cooling Capacities SRVE-050 MetricAmbient Temperature (°C)

29.5 35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 14.3 12.0 16.0 9.1 17.8 6.2 13.8 11.8 15.5 8.9 17.3 6.0

3060 27 14.5 14.1 15.9 11.5 17.8 8.6 14.1 13.8 15.5 11.3 17.3 8.429 15.2 14.9 15.9 13.4 17.8 10.5 14.8 14.5 15.5 13.3 17.3 10.332 15.9 15.6 16.1 15.2 17.8 12.5 15.5 15.2 15.6 15.0 17.3 12.324 14.4 12.4 16.1 9.4 18.0 6.3 14.0 12.3 15.7 9.2 17.5 6.1

3315 27 14.7 14.4 16.1 11.9 18.0 8.8 14.4 14.1 15.6 11.7 17.5 8.829 15.5 15.2 16.1 14.0 18.0 10.9 15.1 14.8 15.7 13.7 17.4 10.732 16.2 15.9 16.3 15.7 18.0 12.9 15.8 15.5 15.9 15.5 17.4 12.724 14.6 12.8 16.3 9.6 18.1 6.3 14.1 12.7 15.8 9.4 17.6 6.2

3570 27 15.0 14.7 16.2 12.3 18.1 9.0 14.6 14.4 15.8 12.1 17.6 8.829 15.8 15.5 16.3 14.4 18.1 11.2 15.4 15.1 15.8 17.3 17.6 11.032 16.6 16.2 16.6 16.2 18.1 13.4 16.2 15.9 16.2 15.9 17.6 13.224 14.7 13.2 16.4 9.8 18.3 6.4 14.1 13.0 15.9 9.6 17.7 6.2

3825 27 15.3 15.0 16.4 12.6 18.3 9.2 14.9 14.6 15.9 12.4 17.7 9.029 16.0 15.7 16.4 14.9 18.3 11.5 15.7 15.4 16.0 14.7 17.7 11.332 16.8 16.5 16.8 16.5 18.2 13.8 16.4 16.1 16.4 16.1 17.7 13.6

Table PD-11 — Gross Cooling Capacities SRVE-050 (Cont.) MetricAmbient Temperature (°C)

40.5 46Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 13.4 11.6 15.0 8.7 16.7 5.8 13.0 11.4 14.5 8.5 16.1 5.6

3060 27 13.7 13.4 15.0 11.1 16.7 8.2 13.3 13.1 14.5 10.9 16.1 8.029 14.4 14.1 15.0 13.0 16.7 10.2 14.0 13.7 14.5 12.8 16.1 9.932 15.1 14.8 15.2 14.7 16.7 12.1 14.7 14.4 14.7 14.4 16.1 11.924 13.5 12.0 15.2 9.0 16.9 5.9 13.1 11.8 14.6 8.8 16.2 5.7

3315 27 14.0 13.7 15.1 11.5 16.9 8.4 13.6 13.4 14.6 11.3 16.2 8.229 14.7 14.4 15.2 13.5 16.9 10.5 14.3 14.0 14.6 13.3 16.2 10.232 15.4 15.1 15.4 15.1 16.8 12.5 15.0 14.7 15.0 14.7 16.2 12.324 13.7 12.4 15.3 9.2 17.0 5.9 13.2 12.2 14.7 9.0 16.4 5.7

3570 27 14.3 14.0 15.3 11.9 17.0 8.6 13.9 13.6 14.7 11.6 16.4 8.429 15.0 14.7 15.3 14.0 17.0 10.8 14.6 14.3 14.8 13.7 16.3 10.632 15.8 15.5 15.7 15.4 17.0 13.0 15.3 15.0 15.3 15.0 16.3 12.724 13.8 12.8 15.4 9.5 17.1 6.0 13.4 12.5 14.9 9.2 16.5 5.8

3825 27 14.5 14.2 15.4 12.2 17.1 8.8 14.1 13.8 14.8 12.0 16.5 8.629 15.3 15.0 15.5 14.4 17.1 11.1 14.8 14.5 14.9 14.1 16.5 10.932 16.0 15.7 16.0 15.7 17.1 13.4 15.5 15.2 15.5 15.2 16.4 13.2

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Page 28: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN28

PerformanceData

Air Cooled50 Hz

Table PD-12 — Gross Cooling Capacities SRVE-075 English Ambient Temperature (°F)

85 95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 69.0 58.8 77.4 44.5 86.5 30.2 66.8 57.7 74.8 43.5 83.5 29.1

2700 80 70.3 68.6 77.4 56.2 86.4 41.8 68.3 67.0 74.7 55.1 83.4 40.885 73.8 72.4 77.3 65.8 86.3 51.4 71.8 70.4 74.7 64.8 83.3 50.390 77.4 75.9 78.1 74.5 86.3 61.1 75.3 73.8 75.7 73.1 83.3 60.075 69.9 60.8 78.2 45.7 87.3 30.5 67.5 59.7 75.6 44.6 84.3 29.4

2925 80 71.7 70.3 78.1 58.0 87.2 42.7 69.6 68.3 75.5 57.0 84.2 41.785 75.4 73.9 78.1 68.2 87.1 53.0 73.3 71.9 75.6 67.2 84.2 52.090 79.1 77.6 79.3 76.9 87.1 63.2 76.9 75.4 77.0 75.2 84.1 62.275 70.5 62.7 79.0 46.8 88.1 30.8 68.2 61.6 76.2 45.8 85.0 29.6

3150 80 72.9 71.6 78.9 59.9 88.0 43.8 70.9 69.6 76.1 58.9 84.9 42.785 76.7 75.3 79.0 70.5 87.9 54.6 74.6 73.2 76.3 69.4 84.8 53.690 80.6 79.0 80.6 78.8 87.9 65.3 78.3 76.9 78.2 76.8 84.8 64.375 71.2 64.5 79.6 47.9 88.7 31.0 68.8 63.3 76.7 46.8 85.7 30.0

3375 80 74.2 72.8 79.5 61.7 88.6 44.7 72.1 70.7 76.7 60.5 85.5 43.785 78.0 76.5 79.7 72.7 88.6 56.1 75.8 74.4 77.1 71.5 85.4 55.090 81.9 80.4 81.8 80.3 88.5 67.4 79.6 78.1 79.6 78.1 85.4 66.3

Table PD-12 — Gross Cooling Capacities SRVE-075 (Cont.) English Ambient Temperature (°F)

105 115Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 64.3 56.6 72.1 42.4 80.5 28.1 61.8 55.4 69.1 41.3 77.2 26.9

2700 80 66.3 65.0 72.0 54.1 80.4 39.6 64.1 62.9 69.1 52.9 77.2 38.685 69.6 68.3 72.0 63.7 80.2 49.3 67.4 66.1 69.2 62.4 77.1 48.390 73.1 71.8 73.3 71.5 80.2 58.9 70.8 69.5 70.8 69.5 77.0 57.875 65.0 58.6 72.7 43.6 81.1 28.3 62.4 57.3 69.8 42.4 77.9 27.3

2925 80 67.5 66.3 72.6 56.0 81.1 40.7 65.3 64.1 69.8 54.8 77.8 39.685 71.0 69.7 72.8 65.9 81.0 50.9 68.8 67.5 70.0 64.6 77.7 49.890 74.6 73.2 74.6 73.2 80.9 61.1 72.3 70.9 72.2 70.8 77.7 60.075 65.7 60.3 73.4 44.6 81.7 28.6 63.2 59.0 70.4 43.6 78.4 27.5

3150 80 68.7 67.4 73.3 57.7 81.7 41.6 66.5 65.2 70.3 56.6 78.3 40.685 72.3 70.9 73.6 68.0 81.6 52.4 70.0 68.6 70.8 66.7 78.3 51.390 76.0 74.6 75.9 74.5 81.6 63.1 73.6 72.2 73.5 72.1 78.2 62.175 66.4 62.0 73.9 45.8 82.3 28.9 63.7 60.6 70.8 44.6 79.0 27.8

3375 80 69.9 68.5 73.8 59.5 82.3 42.5 67.4 66.1 70.8 58.3 78.9 41.585 73.5 72.1 74.3 70.0 82.2 53.9 71.0 69.7 71.4 68.5 78.8 52.890 77.3 75.8 77.2 75.7 82.2 65.2 74.7 73.3 74.6 73.2 78.8 64.1

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Page 29: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

29PKG-PRC006-EN

PerformanceData

Air Cooled50 Hz

Table PD-12 — Gross Cooling Capacities SRVE-075 MetricAmbient Temperature (°C)

29.5 35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 20.2 17.2 22.7 13.0 25.3 8.8 19.6 16.9 21.9 12.7 24.5 8.5

4590 27 20.6 20.1 22.7 16.5 25.3 12.3 20.0 19.6 21.9 16.2 24.4 11.929 21.6 21.2 22.6 19.3 25.3 15.1 21.0 20.6 21.9 19.0 24.4 14.832 22.7 22.2 22.9 21.8 25.3 17.9 22.1 21.6 22.2 21.4 24.4 17.624 20.5 17.8 22.9 13.4 25.6 8.9 19.8 17.5 22.1 13.1 24.7 8.6

4970 27 21.0 20.6 22.9 17.0 25.6 12.5 20.4 20.0 22.1 16.7 24.7 12.229 22.1 21.7 22.9 20.0 25.5 15.5 21.5 21.1 22.1 19.7 24.7 15.232 23.2 22.7 23.2 22.5 25.5 18.5 22.5 22.1 22.6 22.0 24.6 18.224 20.7 18.4 23.1 13.7 25.8 9.0 20.0 18.0 22.3 13.4 24.9 8.7

5355 27 21.4 21.0 23.1 17.6 25.8 12.8 20.8 20.4 22.3 17.3 24.9 12.529 22.5 22.1 23.1 20.7 25.8 16.0 21.9 21.5 22.4 20.3 24.9 15.732 23.6 23.2 23.6 23.1 25.8 19.1 23.0 22.5 22.9 22.5 24.9 18.824 20.9 18.9 23.3 14.1 26.0 9.1 20.2 18.6 22.5 13.7 25.1 8.8

5740 27 21.7 21.3 23.3 18.1 26.0 13.1 21.1 20.7 22.5 17.7 25.1 12.829 22.9 22.4 23.4 21.3 26.0 16.4 22.2 21.8 22.6 20.9 25.0 16.132 24.0 23.6 24.0 23.5 25.9 19.8 23.3 22.9 23.3 22.9 25.0 19.4

Table PD-12 — Gross Cooling Capacities SRVE-075 (Cont.) MetricAmbient Temperature (°C)

40.5 46Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 18.9 16.6 21.1 12.4 23.6 8.2 18.1 16.2 20.3 12.1 22.6 7.9

4590 27 19.4 19.1 21.1 15.9 23.5 11.6 18.8 18.4 20.3 15.5 22.6 11.329 20.4 20.0 21.1 18.7 23.5 14.4 19.8 19.4 20.3 18.3 22.6 14.132 21.4 21.0 21.5 20.9 23.5 17.3 20.8 20.4 20.8 20.4 22.6 16.924 19.0 17.2 21.3 12.8 23.8 8.3 18.3 16.8 20.4 12.4 22.8 8.0

4970 27 19.8 19.4 21.3 16.4 23.8 11.9 19.1 18.8 20.4 16.1 22.8 11.629 20.8 20.4 21.3 19.3 23.7 14.9 20.2 19.8 20.5 18.9 22.8 14.632 21.9 21.5 21.9 21.5 23.7 17.9 21.2 20.8 21.2 20.8 22.8 17.624 19.3 17.7 21.5 13.1 24.0 8.4 18.5 17.3 20.6 12.8 23.0 8.0

5355 27 20.1 19.8 21.5 16.9 24.0 12.2 19.5 19.1 20.6 16.6 23.0 11.929 21.2 20.8 21.6 19.9 23.9 15.4 20.5 20.1 20.8 19.5 23.0 15.032 22.3 21.9 22.2 21.8 23.9 18.5 21.6 21.2 21.5 21.1 22.9 18.224 19.4 18.2 21.7 13.4 24.1 8.5 18.7 17.8 20.8 13.1 23.1 8.1

5740 27 20.5 20.1 21.6 17.4 24.1 12.5 19.8 19.4 20.8 17.1 23.1 12.229 21.5 21.1 21.8 20.5 24.1 15.8 20.8 20.4 20.9 20.1 23.1 15.532 22.6 22.2 22.6 22.2 24.1 19.1 21.9 21.5 21.9 21.5 23.1 18.8

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Page 30: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN30

PerformanceData

Air Cooled50 Hz

Table PD-13 — Gross Cooling Capacities SRVE-100 English Ambient Temperature (°F)

85 95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 97.6 81.5 109.2 62.1 121.5 42.3 94.7 80.2 105.9 60.7 117.9 41.1

3600 80 98.8 95.8 109.1 77.9 121.4 58.1 96.1 93.8 105.8 76.5 117.8 56.885 103.2 101.3 109.0 91.0 121.3 71.2 100.7 98.8 105.7 89.7 117.7 69.990 108.1 106.1 109.6 103.2 121.2 84.2 105.5 103.5 106.5 101.5 117.6 82.975 98.8 84.3 110.4 63.7 122.8 42.7 95.7 82.9 107.0 62.3 118.9 41.5

3900 80 100.5 98.4 110.2 80.4 122.6 59.5 97.9 96.1 106.9 79.0 118.8 58.285 105.5 103.5 110.1 94.3 122.5 73.4 102.8 100.9 106.9 92.9 118.7 72.190 110.5 108.4 111.3 106.6 122.4 87.2 107.8 105.8 108.2 104.7 118.7 85.975 99.8 86.9 111.3 65.2 123.8 43.2 96.7 85.6 107.9 63.9 120.0 41.8

4200 80 102.3 100.4 111.2 82.9 123.7 60.8 99.8 97.9 107.8 81.5 119.9 59.585 107.4 105.4 111.2 97.5 123.6 75.5 104.7 102.8 107.9 96.1 119.8 74.290 112.6 110.5 112.9 109.7 123.5 90.1 109.8 107.7 109.8 107.5 119.7 88.775 100.7 89.5 112.3 66.7 124.8 43.6 97.6 88.0 108.8 65.3 120.8 42.2

4500 80 104.0 102.0 112.2 85.3 124.6 62.1 101.3 99.4 108.7 83.9 120.7 60.885 109.2 107.1 112.3 100.5 124.6 77.5 106.4 104.4 108.9 99.0 120.6 76.290 114.5 112.3 114.5 112.2 124.4 92.9 111.6 109.5 111.6 109.5 120.5 91.5

Table PD-13 — Gross Cooling Capacities SRVE-100 (Cont.) English Ambient Temperature (°F)

105 115Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 91.6 78.7 102.4 59.4 113.8 39.7 88.5 77.4 98.7 57.8 109.5 38.2

3600 80 93.5 91.6 102.3 75.1 113.7 55.4 90.7 89.0 98.6 73.6 109.4 53.985 98.1 96.2 102.3 88.2 113.6 68.5 95.3 93.5 98.6 86.6 109.3 67.090 102.8 100.9 103.4 99.6 113.5 81.5 99.9 98.0 100.0 97.5 109.2 80.075 92.6 81.5 103.4 60.9 114.9 40.0 89.5 80.0 99.5 59.4 110.5 38.6

3900 80 95.3 93.5 103.2 77.7 114.8 56.8 92.5 90.8 99.5 76.2 110.4 55.285 100.1 98.2 103.4 91.4 114.7 70.6 97.2 95.4 99.6 89.9 110.2 69.290 104.9 103.0 105.1 102.5 114.6 84.5 101.8 99.8 101.8 99.8 110.1 82.975 93.6 84.0 104.3 62.4 115.9 40.5 90.3 82.5 100.4 60.9 111.2 38.9

4200 80 97.0 95.2 104.2 80.1 115.8 58.1 94.1 92.4 100.3 78.6 111.2 56.685 101.9 99.9 104.4 94.5 115.7 72.8 98.9 97.0 100.6 92.8 111.1 71.290 106.9 104.8 106.7 104.7 115.5 87.4 103.6 101.6 103.6 101.6 111.0 85.875 94.5 86.5 105.1 63.9 116.6 40.8 91.2 84.9 101.1 62.4 111.9 39.3

4500 80 98.6 96.7 104.9 82.5 116.5 59.4 95.6 93.8 101.0 81.0 111.8 57.885 103.6 101.6 105.4 97.3 116.4 74.8 100.4 98.5 101.6 95.5 111.8 73.290 108.7 106.6 108.5 106.5 116.4 90.1 105.3 103.3 105.2 103.2 111.7 88.5

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Page 31: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

31PKG-PRC006-EN

PerformanceData

Air Cooled50 Hz

Table PD-13 — Gross Cooling Capacities SRVE-100 MetricAmbient Temperature (°C)

29.5 35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 28.6 23.9 32.0 18.2 35.6 12.4 27.7 23.5 31.0 17.8 34.5 12.0

6120 27 29.0 28.1 32.0 22.8 35.6 17.0 28.2 27.5 31.0 22.4 34.5 16.629 30.3 29.7 31.9 26.7 35.5 20.9 29.5 29.0 31.0 26.3 34.5 20.532 31.7 31.1 32.1 30.2 35.5 24.7 30.9 30.3 31.2 29.7 34.4 24.324 29.0 24.7 32.3 18.7 36.0 12.5 28.1 24.3 31.3 18.3 34.9 12.2

6630 27 29.4 28.8 32.3 23.6 35.9 17.4 28.7 28.2 31.3 23.2 34.8 17.129 30.9 30.3 32.3 27.6 35.9 21.5 30.1 29.6 31.3 27.2 34.8 21.132 32.4 31.8 32.6 31.2 35.9 25.5 31.6 31.0 31.7 30.7 34.8 25.224 29.2 25.5 32.6 19.1 36.3 12.7 28.3 25.1 31.6 18.7 35.2 12.3

7140 27 30.0 29.4 32.6 24.3 36.2 17.8 29.2 28.7 31.6 23.9 35.1 17.429 31.5 30.9 32.6 28.6 36.2 22.1 30.7 30.1 31.6 28.2 35.1 21.732 33.0 32.4 33.1 32.2 36.2 26.4 32.2 31.6 32.2 31.5 35.1 26.024 29.5 26.2 32.9 19.5 36.6 12.8 28.6 25.8 31.9 19.1 35.4 12.4

7650 27 30.5 29.9 32.9 25.0 36.5 18.2 29.7 29.1 31.8 24.6 35.4 17.829 32.0 31.4 32.9 29.4 36.5 22.7 31.2 30.6 31.9 29.0 35.3 22.332 33.5 32.9 33.5 32.9 36.5 27.2 32.7 32.1 32.7 32.1 35.3 26.8

Table PD-13 — Gross Cooling Capacities SRVE-100 (Cont.) MetricAmbient Temperature (°C)

40.5 46Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 26.8 23.1 30.0 17.4 33.4 11.6 25.9 22.7 28.9 16.9 32.1 11.2

6120 27 27.4 26.9 30.0 22.0 33.3 16.2 26.6 26.1 28.9 21.6 32.1 15.829 28.7 28.2 30.0 25.8 33.3 20.1 27.9 27.4 28.9 25.4 32.0 19.632 30.1 29.6 30.3 29.2 33.3 23.9 29.3 28.7 29.3 28.6 32.0 23.424 27.1 23.9 30.3 17.9 33.7 11.7 26.2 23.4 29.2 17.4 32.4 11.3

6630 27 27.9 27.4 30.3 22.8 33.6 16.6 27.1 26.6 29.2 22.3 32.3 16.229 29.3 28.8 30.3 26.8 33.6 20.7 28.5 27.9 29.2 26.3 32.3 20.332 30.8 30.2 30.8 30.1 33.6 24.7 29.8 29.3 29.8 29.3 32.3 24.324 27.4 24.6 30.6 18.3 34.0 11.9 26.5 24.2 29.4 17.9 32.6 11.4

7140 27 28.4 27.9 30.5 23.5 33.9 17.0 27.6 27.1 29.4 23.0 32.6 16.629 29.9 29.3 30.6 27.7 33.9 21.3 29.0 28.4 29.5 27.2 32.6 20.932 31.3 30.7 31.3 30.7 33.9 25.6 30.3 29.8 30.3 29.8 32.5 25.124 27.7 25.4 30.8 18.7 34.2 11.9 26.7 24.9 29.6 18.3 32.8 11.5

7650 27 28.9 28.3 30.8 24.2 34.1 17.4 28.0 27.5 29.6 23.7 32.8 16.929 30.3 29.8 30.9 28.5 34.1 21.9 29.4 28.9 29.8 28.0 32.8 21.532 31.8 31.2 31.8 31.2 34.1 26.4 30.8 30.3 30.8 30.2 32.7 25.9

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Page 32: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN32

PerformanceData

Air Cooled50 Hz

Table PD-14 — Gross Cooling Capacities SRVE-125 EnglishAmbient Temperature (°F)

85 95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 121.5 99.8 135.6 75.7 150.9 51.3 117.4 98.0 131.2 73.9 145.8 49.6

4500 80 123.1 116.8 135.5 95.2 150.8 70.9 119.7 114.0 131.0 93.5 145.8 69.185 128.9 123.3 135.4 111.3 150.7 86.9 125.5 120.0 131.0 109.6 145.7 85.390 135.0 129.1 136.5 126.2 150.6 103.1 131.4 125.7 132.4 123.8 145.5 101.475 122.8 103.2 137.1 77.6 152.4 51.8 118.6 101.4 132.9 75.9 147.3 50.2

4875 80 125.4 119.7 136.9 98.4 152.3 72.4 121.9 116.6 132.9 98 147.1 70.885 131.6 125.9 136.9 115.5 152.1 89.6 128.1 122.5 132.9 113.7 147.0 88.090 137.9 131.8 138.6 130.3 152.1 106.7 134.2 128.3 134.4 127.6 146.9 105.175 124.0 106.5 138.3 79.5 153.7 52.3 119.9 104.6 133.7 77.8 148.5 50.5

5250 80 127.5 122.0 138.1 101.5 153.6 74.2 124.1 118.7 133.4 99.6 148.3 72.585 134.0 128.1 138.2 119.5 153.4 92.2 130.3 124.6 133.7 117.5 148.3 90.590 140.4 134.3 140.7 133.8 153.4 110.3 136.6 130.6 136.7 130.5 148.1 108.775 125.2 109.6 139.4 81.4 154.9 52.6 121.0 107.5 134.6 79.5 149.6 51.0

5625 80 129.7 124.0 139.2 104.3 154.7 75.7 126.1 120.6 134.5 102.6 149.4 74.185 136.2 130.3 139.5 123.1 154.6 94.8 132.5 126.7 135.0 121.0 149.3 93.190 142.8 136.6 142.7 136.4 154.4 113.8 138.9 132.9 138.8 132.8 149.2 112.1

Table PD-14 — Gross Cooling Capacities SRVE-125 (Cont.) EnglishAmbient Temperature (°F)

105 115Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 113.2 96.0 126.4 72.1 140.7 47.8 109.0 94.1 121.6 70.2 135.1 45.9

4500 80 116.0 110.8 126.3 91.7 140.6 67.3 112.3 107.4 121.4 89.7 135.0 65.485 121.8 116.5 126.3 107.6 140.3 83.4 118.0 112.9 121.5 105.7 134.8 81.690 127.7 122.2 128.1 121.2 140.3 99.5 123.8 118.4 123.8 117.9 134.7 97.775 114.5 99.5 127.7 73.8 141.8 48.3 110.1 97.3 122.6 72.1 136.2 46.5

4875 80 118.4 113.2 127.5 94.8 141.8 69.0 114.5 109.5 122.6 92.9 136.1 67.285 124.3 118.9 127.6 111.7 141.6 86.2 120.4 115.2 122.8 109.5 136.0 84.490 130.3 124.6 130.4 124.3 141.5 103.2 126.2 120.7 126.1 120.6 135.9 101.475 115.6 102.5 128.7 75.8 143.0 48.7 111.1 100.3 123.6 74.1 137.2 46.9

5250 80 120.4 115.2 128.6 97.9 142.8 70.7 116.4 111.3 123.5 95.9 137.1 68.785 126.6 121.0 129.0 115.3 142.8 88.8 122.5 117.1 124.1 113.1 137.0 86.990 132.7 126.9 132.6 126.8 142.6 106.8 128.4 122.8 128.4 122.8 136.9 104.975 116.6 105.4 129.7 77.7 144.0 49.2 112.2 103.1 124.5 75.8 138.2 47.3

5625 80 122.2 116.9 129.6 100.7 143.9 72.2 118.3 113.1 124.4 98.9 138.0 70.485 128.5 122.9 130.2 118.8 143.8 91.3 124.3 118.9 125.3 116.3 138.0 89.390 134.8 129.0 134.7 128.9 143.6 110.2 130.4 124.7 130.4 124.7 137.8 108.4

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Page 33: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

33PKG-PRC006-EN

PerformanceData

Air Cooled50 Hz

Table PD-14 — Gross Cooling Capacities SRVE-125 MetricAmbient Temperature (°C)

29.5 35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 35.6 29.2 39.7 22.2 44.2 15.0 34.4 28.7 38.4 21.6 42.7 14.6

7650 27 36.1 34.2 39.7 27.9 44.2 20.8 35.1 33.4 38.4 27.4 42.7 20.329 37.8 36.1 39.7 32.6 44.2 25.5 36.8 35.2 38.4 32.1 42.7 25.032 39.5 37.8 40.0 37.0 44.1 30.2 38.5 36.8 38.8 36.3 42.6 29.724 36.0 30.2 40.2 22.7 44.7 15.2 34.7 29.7 38.9 22.2 43.2 14.7

8285 27 36.7 35.1 40.1 28.8 44.6 21.2 35.7 34.2 38.9 28.7 43.1 20.729 38.6 36.9 40.1 33.8 44.6 26.3 37.5 35.9 38.9 33.3 43.1 25.832 40.4 38.6 40.6 38.2 44.6 31.3 39.3 37.6 39.4 37.4 43.0 30.824 36.3 31.2 40.5 23.3 45.0 15.3 35.1 30.6 39.2 22.8 43.5 14.8

8920 27 37.4 35.7 40.5 29.7 45.0 21.7 36.4 34.8 39.1 29.2 43.5 21.329 39.3 37.5 40.5 35.0 44.9 27.0 38.2 36.5 39.2 34.4 43.5 26.532 41.2 39.4 41.2 39.2 44.9 32.3 40.0 38.3 40.0 38.2 43.4 31.824 36.7 32.1 40.8 23.8 45.4 15.4 35.4 31.5 39.5 23.3 43.8 14.9

9560 27 38.0 36.3 40.8 30.6 45.3 22.2 37.0 35.3 39.4 30.1 43.8 21.729 39.9 38.2 40.9 36.1 45.3 27.8 38.8 37.1 39.5 35.5 43.7 27.332 41.8 40.0 41.8 40.0 45.3 33.4 40.7 38.9 40.7 38.9 43.7 32.8

Table PD-14 — Gross Cooling Capacities SRVE-125 (Cont.) MetricAmbient Temperature (°C)

40.5 46Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 33.2 28.1 37.1 21.1 41.2 14.0 31.9 27.6 35.6 20.6 39.6 13.5

7650 27 34.0 32.5 37.0 26.9 41.2 19.7 32.9 31.5 35.6 26.3 39.5 19.229 35.7 34.1 37.0 31.5 41.1 24.4 34.6 33.1 35.6 31.0 39.5 23.932 37.4 35.8 37.5 35.5 41.1 29.2 36.3 34.7 36.3 34.6 39.5 28.624 33.5 29.2 37.4 21.6 41.6 14.2 32.3 28.5 35.9 21.1 39.9 13.6

8285 27 34.7 33.2 37.4 27.8 41.6 20.2 33.5 32.1 35.9 27.2 39.9 19.729 36.4 34.8 37.4 32.7 41.5 25.3 35.3 33.7 36.0 32.1 39.9 24.732 38.2 36.5 38.2 36.4 41.5 30.2 37.0 35.4 37.0 35.3 39.8 29.724 33.9 30.0 37.7 22.2 41.9 14.3 32.6 29.4 36.2 21.7 40.2 13.7

8920 27 35.3 33.7 37.7 28.7 41.8 20.7 34.1 32.6 36.2 28.1 40.2 20.129 37.1 35.5 37.8 33.8 41.8 26.0 35.9 34.3 36.4 33.1 40.1 25.532 38.9 37.2 38.9 37.2 41.8 31.3 37.6 36.0 37.6 36.0 40.1 30.724 34.2 30.9 38.0 22.8 42.2 14.4 32.9 30.2 36.5 22.2 40.5 13.9

9560 27 35.8 34.3 38.0 29.5 42.2 21.2 34.7 33.1 36.5 29.0 40.4 20.629 37.7 36.0 38.2 34.8 42.1 26.7 36.4 34.8 36.7 34.1 40.4 26.232 39.5 37.8 39.5 37.8 42.1 32.3 38.2 36.6 38.2 36.6 40.4 31.8

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Page 34: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN34

PerformanceData

Air Cooled50 Hz

Table PD-15 — Gross Cooling Capacities SRVE-150 English Ambient Temperature (°F)

85 95Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 146.1 128.9 162.8 96.2 180.9 63.1 140.9 126.4 156.9 93.9 174.3 60.8

5400 80 150.6 147.8 162.6 122.9 180.8 89.8 146.2 143.4 156.7 120.5 174.2 87.585 158.3 155.3 163.0 144.6 180.6 111.8 153.6 150.7 157.3 142.0 174.1 109.590 165.9 162.8 166.0 162.2 180.5 133.7 161.0 158.0 161.0 158.0 173.8 131.575 147.8 133.4 164.3 99.0 182.5 63.9 142.6 130.8 158.3 96.6 175.8 61.6

5850 80 153.7 150.8 164.2 127.4 182.4 92.1 149.0 146.2 158.2 125.0 175.6 89.985 161.4 158.4 164.9 150.1 182.3 115.7 156.6 153.6 159.1 147.3 175.5 113.390 169.3 166.1 169.3 166.1 182.1 138.9 164.3 161.2 164.2 161.1 175.3 136.775 149.4 137.7 165.7 101.6 184.0 64.5 144.1 134.9 159.5 99.3 177.1 62.2

6300 80 156.4 153.4 165.6 131.7 183.8 94.4 151.6 148.7 159.4 129.4 176.9 92.185 164.4 161.3 166.7 155.1 183.7 119.3 159.3 156.3 160.9 152.2 176.8 117.090 172.5 169.2 172.4 169.1 183.6 144.0 167.3 164.1 167.2 164.0 176.7 141.875 150.8 141.7 167.0 104.2 185.2 65.1 145.5 138.6 160.7 101.8 178.2 62.8

6750 80 158.9 155.9 166.8 135.9 185.1 96.7 153.9 151.0 160.6 133.5 178.1 94.385 167.0 163.8 168.4 159.7 185.0 122.9 161.9 158.8 162.6 156.4 178.0 120.590 175.2 171.9 175.2 171.9 184.9 148.9 169.9 166.7 169.8 166.6 178.0 146.5

Table PD-15 — Gross Cooling Capacities SRVE-150 (Cont.) English Ambient Temperature (°F)

105 115Entering Wet Bulb Temperature (°F)

Ent. 61 67 73 61 67 73DB

CFM (ºF) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC75 135.5 123.7 150.6 91.5 167.4 58.6 130.0 120.9 144.3 89.1 160.3 56.2

5400 80 141.4 138.7 150.5 118.1 167.3 85.2 136.4 133.9 144.2 115.8 160.2 82.885 148.6 145.8 151.4 139.3 167.2 107.1 143.5 140.8 145.2 136.2 160.1 104.790 155.9 153.0 155.9 153.0 167.1 129.1 150.6 147.8 150.5 147.7 160.0 126.775 137.1 128.0 152.0 94.2 168.8 59.2 131.6 124.9 145.5 91.8 161.5 56.9

5850 80 144.2 141.4 151.9 122.6 168.7 87.5 139.0 136.3 145.4 120.1 161.4 85.285 151.6 148.7 153.2 144.3 168.5 111.0 146.3 143.5 147.1 141.0 161.3 108.690 159.0 156.0 159.0 156.0 168.4 134.3 153.6 150.7 153.5 150.6 161.3 131.975 138.7 131.9 153.2 96.9 169.9 59.9 133.0 128.4 146.6 94.4 162.6 57.5

6300 80 146.5 143.7 153.1 126.9 169.8 89.8 141.3 138.6 146.6 124.3 149.9 87.585 154.1 151.2 155.0 148.8 169.7 114.6 148.7 145.9 148.9 145.0 162.4 112.290 161.9 158.8 161.8 158.7 169.7 139.3 156.1 153.2 156.1 153.2 149.9 136.875 140.0 135.3 154.2 99.4 171.0 60.4 134.5 131.5 147.5 96.9 163.7 58.0

6750 80 148.7 145.9 154.2 130.9 170.9 92.0 143.3 140.6 147.7 128.3 163.5 89.785 156.5 153.5 156.8 152.7 170.8 118.3 150.9 148.1 150.8 148.0 163.4 115.990 164.3 161.2 164.3 161.2 170.9 144.0 158.6 155.6 158.5 155.5 163.7 141.3

Notes:TGC = Total Gross Capacity (MBh)SHC = Sensible Heat Capacity (MBh)

Page 35: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

35PKG-PRC006-EN

PerformanceData

Air Cooled50 Hz

Table PD-15 — Gross Cooling Capacities SRVE-150 MetricAmbient Temperature (°C)

29.5 35.0Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 42.8 37.8 47.7 28.2 53.0 18.5 41.3 37.0 46.0 27.5 51.1 17.8

9180 27 44.1 43.3 47.6 36.0 53.0 26.3 42.8 42.0 45.9 35.3 51.0 25.629 46.4 45.5 47.8 42.4 52.9 32.8 45.0 44.2 46.1 41.6 51.0 32.132 48.6 47.7 48.6 47.5 52.9 39.2 47.2 46.3 47.2 46.3 50.9 38.524 43.3 39.1 48.1 29.0 53.5 18.7 41.8 38.3 46.4 28.3 51.5 18.0

9945 27 45.0 44.2 48.1 37.3 53.5 27.0 43.7 42.8 46.3 36.6 51.5 26.329 47.3 46.4 48.3 44.0 53.4 33.9 45.9 45.0 46.6 43.2 51.4 33.232 49.6 48.7 49.6 48.7 53.4 40.7 48.1 47.2 48.1 47.2 51.4 40.024 43.8 40.4 48.5 29.8 53.9 18.9 42.2 39.5 46.7 29.1 51.9 18.2

10710 27 45.8 45.0 48.5 38.6 53.9 27.7 44.4 43.6 46.7 37.9 51.8 27.029 48.2 47.3 48.9 45.4 53.8 35.0 46.7 45.8 47.2 44.6 51.8 34.332 50.5 49.6 50.5 49.6 53.8 42.2 49.0 48.1 49.0 48.1 51.8 41.524 44.2 41.5 48.9 30.5 54.3 19.1 42.6 40.6 47.1 29.8 52.2 18.4

11475 27 46.6 45.7 48.9 39.8 54.2 28.3 45.1 44.2 47.1 39.1 52.2 27.629 48.9 48.0 49.4 46.8 54.2 36.0 47.4 46.5 47.6 45.8 52.2 35.332 51.3 50.4 51.3 50.4 54.2 43.6 49.8 48.9 49.8 48.8 52.2 42.9

Table PD-15 — Gross Cooling Capacities SRVE-150 (Cont.) MetricAmbient Temperature (°C)

40.5 46Entering Wet Bulb Temperature (°C)

Ent. 16.0 19.5 23.0 16.0 19.5 23.0DB

m3/h (ºC) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC24 39.7 36.2 44.1 26.8 49.0 17.2 38.1 35.4 42.3 26.1 47.0 16.5

9180 27 41.4 40.7 44.1 34.6 49.0 25.0 40.0 39.2 42.2 33.9 46.9 24.329 43.5 42.7 44.4 40.8 49.0 31.4 42.1 41.3 42.6 39.9 46.9 30.732 45.7 44.8 45.7 44.8 49.0 37.8 44.1 43.3 44.1 43.3 46.9 37.124 40.2 37.5 44.5 27.6 49.4 17.3 38.5 36.6 42.6 26.9 47.3 16.7

9945 27 42.2 41.4 44.5 35.9 49.4 25.6 40.7 40.0 42.6 35.2 47.3 25.029 44.4 43.6 44.9 42.3 49.4 32.5 42.9 42.1 43.1 41.3 47.3 31.832 46.6 45.7 46.6 45.7 49.4 39.3 45.0 44.2 45.0 44.1 47.3 38.624 40.6 38.6 44.9 28.4 49.8 17.6 39.0 37.6 43.0 27.7 47.6 16.9

10710 27 42.9 42.1 44.9 37.2 49.8 26.3 41.4 40.6 43.0 36.4 43.9 25.629 45.2 44.3 45.4 43.6 49.7 33.6 43.6 42.8 43.6 42.5 47.6 32.932 47.4 46.5 47.4 46.5 49.7 40.8 45.8 44.9 45.8 44.9 43.9 40.124 41.0 39.6 45.2 29.1 50.1 17.7 39.4 38.5 43.2 28.4 48.0 17.0

11475 27 43.6 42.8 45.2 38.4 50.1 27.0 42.0 41.2 43.3 37.6 47.9 26.329 45.8 45.0 45.9 44.7 50.0 34.7 44.2 43.4 44.2 43.4 47.9 34.032 48.1 47.2 48.1 47.2 50.1 42.2 46.5 45.6 46.4 45.6 48.0 41.4

Notes:TGC = Total Gross Capacity (kW)SHC = Sensible Heat Capacity (kW)

Page 36: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN36

The Genius line offers two Controloptions: Standard Thermostat orMicroprocessor Control.

Standard ThermostatAll units are supplied with a controlthermostat as standard feature. Thisthermostat can be installed remotely orin the equipment, according to the needsof the client.

Microprocessor ControlThe Microprocessor Control UCP (unitcontrol processor) is factory assembledand tested. It controls unit operation inthe independent mode (standalone) or itallows communication when the unit isworking in an integrated comfort system(Tracer, Tracer Summit, Tracker).

Some of the main advantages andbenefits of using the microprocessor are:

Great reliability: As we know, this type ofcontrol has demonstrated itself to behighly reliable, thus avoidingdecalibration or breakdown.

Direct digital control: The IntegralProportional Control allows more precisetemperature control of the area to be air-conditioned. In addition, the temperaturesensing instrument is more sensitivethan the one used in traditional cases.With this instrument joined to the UCP itis possible to guarantee a setpointtemperature of + - 0.5F.

Easy diagnosis: The controller allows theoperator to carry out easy and fast test toverify the operation of the unitcomponents (fans and compressors).

Low suction pressure during start-up:The controller ignores the lowpressurestat information duringcompressor start-up, thus avoiding thatthe unit not start because of the lowpressure. If after 3 minutes the lowpressure is not within the correct range,the unit will deactivate.

Elimination of Compressor cycling: Thecontroller allows the compressor to runfor a minimum of three minutes,followed by three minutes not running(off) to make sure that there is adequateoil return to the compressor(s).

Alternation of Compressor operation:The microprocessor will alternate thecompressors according to the number ofstart-ups and hours of operation of each,

Controls

so that the degree of wear will be similarfor each one.

The microprocessor control provides theoption for simple and directcommunication between the Genius andTRACKER, Tracer or Tracer Summitbuilding administrators. Thiscommunication is achieved simply byinterconnecting the Genius unit and thebuilding administration system with atwisted pair cable.

TRACKERIn addition to being able to control thelighting of your house or building, thispanel can automatically control up to 12Genius. It also allows sending airconditioning system alarms to aMaintenance Central 24 hours a day,thus making possible various functions:

Schedule programming: On theTRACKER you do the annual operatingprogramming of each one of theinterconnected sets of equipment withthe possibility of setting two differentschedules for the initiation andtermination of operation for weekdays,weekends and holidays. The objective isto use the equipment only whennecessary. There is no need for you towaste energy.

Interface with the operator: TheTRACKER has a functional keyboard andliquid crystal display that provides theuser with a rapid visualization of thesystem with a minimum of experience.Access is restricted with a safetypassword.

Zoning: When a variable air volumesystem is controlled, it is capable ofindependently controlling thetemperature of up to 128 different zones,thus optimizing the dimensions of yourequipment as well as your investment.

Optimized start-up: The TRACKERanalyzes the most economical way toturn on the equipment so that you getthe desired temperature at theprogrammed time. This is applicable insetups where various Genius units areinterconnected to the control systemand, instead of turning on all of them atthe same time, they are turned on atdifferent times to avoid peaks in energyconsumption.

Demand limit: Automatically controlsthe programmed electricityconsumption limits of the setup. This isan important economic factor thatmakes the cost of the TRACKERinsignificant when considered on anannual scale.

Record of tendencies: Records up to 192temperature values during a time framethat you determine. This function makesit possible to do a posterior analysis ofthe system’s performance.

Record of alarms: The TRACKERimmediately identifies any breakdownsin the system, which register as alarms.Besides this, the TRACKER store in itsmemory up to 32 alarms withinformation including the date and timeof the event.

Access via telephone line: The TRACKERcan be programmed and supervisedthrough the telephone line. It can also, inthe same way, send warningsconcerning any alarms.

Easy installation: The Genius and theTRACKER leave the factory alreadyprogrammed and tested. Installation andconnection between them is done with atwisted pair.

For more details, consult the TRACKEREngineering Bulletin.

TRACER SUMMITThis is the controller recommended forvery large installations. The Genius’smicroprocessor is also able tocommunicate with the Tracer Summitwhich provides complete integration ofthese units with the Integrated ComfortSystem.

Varitrac is the name Trane has given toour variable air volume system for smallinstallations. Airflow through the Geniusis constant while the air supply to eachzone is variable. So that this will happen,a bypass gate returns airflow that wasnot required by the zones to the system.The variable air input in each zone iscontrolled by a VAV box that includes amicroprocessor controller. Thiscontroller regulates the amount of airneeded to maintain the desiredtemperature. A panel called the CentralControl Panel (CCP) is used to program,supervise and control the Varitracsystem. Trane personnel can programthe TRACKER and the CCP.

Page 37: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

37PKG-PRC006-EN

ElectricalData

Table ED-1 — Genius – Electrical Features - SRVE/SIVE 050Nominal Operation Values Compressor Fan Motor Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW ASTD 220V 15.40 3.04 3.04 21.48and 380V 4.74 8.92 0.83 1.76 0.83 1.76 6.40 12.44Option 1 440V 7.70 1.52 1.52 10.74

220V 15.40 4.14 3.04 22.58Option 2 380V 4.74 8.92 1.22 2.39 0.83 1.76 6.79 13.07

440V 7.70 2.07 1.52 11.29Plenum Box 220V 15.40 1.80 3.04 20.24Option 380V 4.74 8.92 0.45 1.04 0.83 1.76 6.02 11.72

440V 7.70 0.90 1.52 10.12

Maximum Operation Values Compressor Fan Motor Fan Motor CurrentFan Voltage CMO CMO CMO ASTD 220V 19.90 3.80 3.80 27.50and 380V 11.52 2.19 2.19 15.90Option 1 440V 9.95 1.90 1.90 13.75

220V 19.90 5.18 3.80 28.88Option 2 380V 11.52 2.99 2.19 16.70

440V 9.95 1.13 1.90 12.98Plenum Box 220V 19.90 2.25 3.80 25.95Option 380V 11.52 1.30 2.19 15.01

440V 9.95 1.13 1.90 12.98

Start-up Values Compressor Fan Motor Fan MotorFan Voltage LRA LRA LRASTD 220V 128.00 19.00 19.00and 380V 74.10 11.00 11.00Option 1 440V 64.00 9.50 9.50

220V 128.00 28.60 19.00Option 2 380V 74.10 16.56 11.00

440V 64.00 14.30 9.50Plenum Box 220V 128.00 9.90 19.00Option 380V 74.10 5.73 11.00

440V 64.00 4.95 9.50

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option and Option 1 - evaporator fan motor -1 CV.• Option 2 - evaporator fan motor -1.5 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Power of the condenser fan motor -1 CV.• Size the electrical wiring using the maximum operation currents.

Each unit model has three options forelectric heat.

The following table shows the optionsand their capacities in kW.

Model 5 Ton 7.5 Ton 10 Ton 12.5 Ton 15 TonOption 1 2 kW 3 kW 4 kW 5 kW 6 kWOption 2 4 kW 6 kW 8 kW 2x5 kW 2x6 kWOption 3 6 kW 9 kW 2x6 kW 2x8 kW 2x9 kW

Page 38: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN38

ElectricalData

Table ED-2 — Genius – Electrical Features - SRVE/SIVE 050Nominal Operation Values Compressor Fan Motor Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW A

220V 18.60 4.14 7.32 30.06STD 380V 6.39 10.77 1.22 2.39 2.23 4.23 9.84 17.39

440V 9.30 2.07 3.65 15.02220V 18.60 5.53 7.32 31.45

Option 1 380V 6.39 10.77 1.64 3.19 2.23 4.23 10.26 18.19440V 9.30 2.76 3.65 15.71220V 18.60 7.32 7.32 33.24

Option 2 380V 6.39 10.77 2.23 4.23 2.23 4.23 10.85 19.23440V 9.30 3.66 3.65 16.61

Plenum Box 220V 18.60 7.32 7.32 33.24Option 380V 6.39 10.77 0.45 1.04 2.23 4.23 9.07 16.04

440V 9.30 0.90 3.65 13.85

Maximum Operation Values Compressor Fan Motor Fan Motor CurrentFan Voltage CMO CMO CMO A

220V 24.98 5.18 9.15 39.32STD 380V 14.46 2.99 5.28 22.73

440V 12.49 2.59 4.58 19.66220V 24.98 6.91 9.15 41.04

Option 1 380V 14.46 3.99 5.28 23.73440V 12.49 3.46 4.58 20.52220V 24.98 9.15 9.15 43.28

Option 2 380V 14.46 5.28 5.28 25.02440V 12.49 4.58 4.58 21.64

Plenum Box 220V 24.98 2.25 9.15 36.38Option 380V 14.46 1.30 5.28 21.04

440V 12.49 1.13 4.58 18.19

Start-up Values Compressor Fan Motor Fan MotorFan Voltage LRA LRA LRA

220V 171.00 30.92 60.45STD 380V 99.00 17.85 34.90

440V 85.50 15.46 30.23220V 171.00 48.36 60.45

Option 1 380V 99.00 27.92 34.90440V 85.50 24.18 30.23220V 171.00 60.45 60.45

Option 2 380V 99.00 34.90 34.90440V 85.50 30.23 30.23

Plenum Box 220V 171.00 11.25 60.45Option 380V 99.00 6.50 34.90

440V 85.50 5.63 30.23

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -1.5 CV.• Option 1 - evaporator fan motor -2 CV.• Option 2 - evaporator fan motor -3 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Power of the condenser fan motor -3 CV.• Size the electrical wiring using the maximum operation currents.

Page 39: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

39PKG-PRC006-EN

ElectricalData

Table ED-3 — Genius – Electrical Features - SRVE/SIVE 100Nominal Operation Values Compressor 1 Compressor 2 Fan Motor Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW CNO KW A

220V 15.40 15.40 4.14 7.32 42.26STD 380V 4.74 8.92 4.74 8.92 1.22 2.39 2.23 4.23 12.93 24.46

440V 7.70 7.70 2.07 3.65 21.12220V 15.40 15.40 5.53 7.32 43.65

Option 1 380V 4.74 8.92 4.74 8.92 1.64 3.19 2.23 4.23 13.35 25.26440V 7.70 7.70 2.76 3.65 21.81220V 15.40 15.40 7.32 7.32 45.44

Option 2 380V 4.74 8.92 4.74 8.92 2.23 4.23 2.23 4.23 13.94 26.30440V 7.70 7.70 3.66 3.65 22.71

Plenum Box 220V 15.40 15.40 1.80 7.32 39.92Option 380V 4.74 8.92 4.74 8.92 0.45 1.04 2.23 4.23 12.16 23.11

440V 7.70 7.70 0.90 3.65 19.95

Maximum Operation Values Compressor 1 Compressor 2 Fan Motor Fan Motor CurrentFan Voltage CMO CMO CMO CMO A

220V 19.90 19.90 5.18 9.15 54.13STD 380V 11.52 11.52 2.99 5.28 31.31

440V 9.95 9.95 2.59 4.58 27.06220V 19.90 19.90 6.91 9.15 55.86

Option 1 380V 11.52 11.52 3.99 5.28 32.31440V 9.95 9.95 3.46 4.58 27.93220V 19.90 19.90 9.15 9.15 58.10

Option 2 380V 11.52 11.52 5.28 5.28 33.60440V 9.95 9.95 4.58 4.58 29.05

Plenum Box 220V 19.90 19.90 2.25 9.15 51.20Option 380V 11.52 11.52 1.30 5.28 29.62

440V 9.95 9.95 1.13 4.58 25.60

Start-up Values Compressor 1 Compressor 2 Fan Motor Fan MotorFan Voltage LRA LRA LRA LRA

220V 128.00 128.00 30.92 60.45STD 380V 74.10 74.10 17.85 34.90

440V 64.00 64.00 15.46 30.23220V 128.00 128.00 48.36 60.45

Option 1 380V 74.10 74.10 27.92 34.90440V 64.00 64.00 24.18 30.23220V 128.00 128.00 60.45 60.45

Option 2 380V 74.10 74.10 34.90 34.90440V 64.00 64.00 30.23 30.23

Plenum Box 220V 128.00 128.00 11.25 60.45Option 380V 74.10 74.10 6.50 34.90

440V 64.00 64.00 5.63 30.23

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -1.5 CV.• Option 1 - evaporator fan motor -2 CV.• Option 2 - evaporator fan motor -3 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Power of the condenser fan motor -3 CV.• Size the electrical wiring using the maximum operation currents.

Page 40: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN40

ElectricalData

Table ED-4 — Genius – Electrical Features - SRVE/SIVE 125Nominal Operation Values Compressor 1 Compressor 2 Fan Motor Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW CNO KW A

220V 18.60 15.40 5.53 9.28 48.81STD 380V 6.39 10.77 4.74 8.92 1.64 3.19 2.93 5.36 15.70 28.24

440V 9.30 7.70 2.76 4.64 24.40220V 18.60 15.40 7.32 9.28 50.60

Option 1 380V 6.39 10.77 4.74 8.92 2.23 4.23 2.93 5.36 16.29 29.28440V 9.30 7.70 3.66 4.64 25.30220V 18.60 15.40 9.28 9.28 52.56

Option 2 380V 6.39 10.77 4.74 8.92 2.93 5.36 2.93 5.36 16.99 30.41440V 9.30 7.70 4.64 4.64 26.28

Plenum Box 220V 18.60 15.40 1.80 9.28 45.08Option 380V 6.39 10.77 4.74 8.92 0.45 1.04 2.93 5.36 14.51 26.09

440V 9.30 7.70 0.90 4.64 22.54

Maximum Operation Values Compressor 1 Compressor 2 Fan Motor Fan Motor CurrentFan Voltage CMO CMO CMO CMO A

220V 24.98 19.90 6.91 11.60 63.39STD 380V 14.46 11.52 3.99 6.70 36.67

440V 12.49 9.95 3.46 5.80 31.69220V 24.98 19.90 9.15 11.60 65.63

Option 1 380V 14.46 11.52 5.28 6.70 37.96440V 12.49 9.95 4.58 5.80 32.81220V 24.98 19.90 11.60 11.60 68.08

Option 2 380V 14.46 11.52 6.70 6.70 39.38440V 12.49 9.95 5.80 5.80 34.04

Plenum Box 220V 24.98 19.90 2.25 11.60 58.73Option 380V 14.46 11.52 1.30 6.70 33.98

440V 12.49 9.95 1.13 5.80 29.36

Start-up Values Compressor 1 Compressor 2 Fan Motor Fan MotorFan Voltage LRA LRA LRA LRA

220V 171.00 128.00 48.36 87.00STD 380V 99.00 99.00 27.92 50.23

440V 85.50 85.50 24.18 43.50220V 171.00 128.00 60.45 87.00

Option 1 380V 99.00 99.00 34.90 50.23440V 85.50 85.50 30.23 43.50220V 171.00 128.00 87.00 87.00

Option 2 380V 99.00 99.00 50.23 50.23440V 85.50 85.50 43.50 43.50

Plenum Box 220V 171.00 128.00 11.25 87.00Option 380V 99.00 99.00 6.50 50.23

440V 85.50 85.50 5.63 43.50

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -2 CV.• Option 1 - evaporator fan motor -3 CV.• Option 2 - evaporator fan motor -4 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Power of the condenser fan motor -4 CV.• Size the electrical wiring using the maximum operation currents

Page 41: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

41PKG-PRC006-EN

ElectricalData

Table ED-5 — Genius – Electrical Features - SRVE/SIVE 150Nominal Operation Values Compressor 1 Compressor 2 Fan Motor Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW CNO KW A

220V 18.60 18.60 7.32 11.61 56.13STD 380V 6.39 10.77 6.39 10.77 2.23 4.23 3.54 6.70 18.55 32.47

440V 9.30 9.30 3.66 5.80 28.06220V 18.60 18.60 9.28 11.61 58.09

Option 1 380V 6.39 10.77 6.39 10.77 2.93 5.36 3.54 6.70 19.25 33.60440V 9.30 9.30 4.64 5.80 29.04220V 18.60 18.60 11.61 11.61 60.42

Option 2 380V 6.39 10.77 6.39 10.77 3.54 6.70 3.54 6.70 19.86 34.94440V 9.30 9.30 9.30 5.80 30.20

Plenum Box 220V 18.60 18.60 3.04 11.61 51.85Option 380V 6.39 10.77 6.39 10.77 0.83 1.76 3.54 6.70 17.15 30.00

440V 9.30 9.30 9.30 1.52 25.92

Maximum Operation Values Compressor 1 Compressor 2 Fan Motor Fan Motor CurrentFan Voltage CMO CMO CMO CMO A

220V 24.98 24.98 9.15 14.51 73.62STD 380V 14.46 14.46 5.28 8.38 42.58

440V 12.49 12.49 4.58 7.26 36.82220V 24.98 24.98 11.60 14.51 76.07

Option 1 380V 14.46 14.46 6.70 8.38 44.00440V 12.49 12.49 5.80 7.26 38.04220V 24.98 24.98 14.51 14.51 78.98

Option 2 380V 14.46 14.46 8.38 8.38 45.68440V 12.49 12.49 7.26 7.26 39.50

Plenum Box 220V 24.98 24.98 3.80 14.51 68.27Option 380V 14.46 14.46 2.19 8.38 39.49

440V 12.49 12.49 1.90 7.26 34.14

Start-up Values Compressor 1 Compressor 2 Fan Motor Fan MotorFan Voltage LRA LRA LRA LRA

220V 171.00 171.00 60.45 110.55STD 380V 99.00 99.00 34.90 63.83

440V 85.50 85.50 30.23 55.28220V 171.00 171.00 87.00 110.55

Option 1 380V 99.00 99.00 50.23 63.83440V 85.50 85.50 43.50 55.28220V 171.00 171.00 110.55 110.55

Option 2 380V 99.00 99.00 63.83 63.83440V 85.50 85.50 55.28 55.28

Plenum Box 220V 171.00 171.00 21.96 110.55Option 380V 99.00 99.00 12.68 63.83

440V 85.50 85.50 10.98 55.28

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -3 CV.• Option 1 - evaporator fan motor -4 CV.• Option 2 - evaporator fan motor -5 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Power of the condenser fan motor -5 CV.• Size the electrical wiring using the maximum operation currents.

Page 42: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN42

Table ED-6 — Genius – Electrical Features - SAVE 050Nominal Operation Values Compressor Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW ASTD 220V 14.10 3.04 17.14and 380V 4.17 8.16 0.83 1.76 5.00 9.92Option 1 440V 7.05 1.52 8.57

220V 14.10 4.14 18.24Option 2 380V 4.17 8.16 1.22 2.39 5.39 10.55

440V 7.05 2.07 9.12Plenum Box 220V 14.10 1.80 15.90Option 380V 4.17 8.16 0.45 1.04 4.62 9.20

440V 7.05 0.90 7.95

Maximum Operation Values Compressor Fan Motor CurrentFan Voltage CMO CMO ASTD 220V 19.80 3.80 23.60and 380V 11.46 2.19 13.65Option 1 440V 9.90 1.90 11.80

220V 19.80 5.18 24.98Option 2 380V 11.46 2.99 14.45

440V 9.90 1.90 11.80Plenum Box 220V 19.80 2.25 22.05Option 380V 11.46 1.30 12.76

440V 09.90 1.13 11.03

Start-up Values Compressor Fan MotorFan Voltage LRA LRASTD 220V 128.00 21.96and 380V 74.11 12.68Option 1 440V 64.00 10.98

220V 128.00 21.96Option 2 380V 74.11 17.85

440V 64.00 10.98Plenum Box 220V 128.00 11.25Option 380V 74.11 6.50

440V 64.00 5.63

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option and Option 1 - evaporator fan motor -1 CV.• Option 2 - evaporator fan motor -1.5 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Size the electrical wiring using the maximum operation currents.

ElectricalData

Page 43: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

43PKG-PRC006-EN

ElectricalData

Table ED-7 — Genius – Electrical Features - SAVE 075Nominal Operation Values Compressor Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW A

220V 16.99 4.14 21.13STD 380V 5.68 9.84 1.22 2.39 6.90 12.23

440V 8.50 2.07 10.57220V 14.10 5.53 22.52

Option 1 380V 5.68 9.84 1.64 3.19 7.32 13.03440V 8.50 2.76 11.26220V 14.10 7.32 24.31

Option 2 380V 5.68 9.84 2.23 4.23 7.91 14.07440V 8.50 3.66 12.16

Plenum Box 220V 14.10 1.80 18.79Option 380V 5.68 9.84 0.45 1.04 6.13 10.88

440V 8.50 0.90 9.40

Maximum Operation Values Compressor Fan Motor CurrentFan Voltage CMO CMO A

220V 24.98 5.18 30.16STD 380V 14.46 2.99 17.45

440V 12.49 2.59 15.08220V 24.98 6.91 31.89

Option 1 380V 14.46 3.99 18.45440V 12.49 3.46 15.95220V 24.98 9.15 34.13

Option 2 380V 14.46 5.28 19.74440V 12.49 4.58 17.07

Plenum Box 220V 24.98 2.25 27.23Option 380V 14.46 1.30 15.76

440V 12.49 1.13 13.62

Start-up Values Compressor Fan MotorFan Voltage LRA LRA

220V 171.00 30.92STD 380V 99.00 17.85

440V 85.50 15.46220V 171.00 48.36

Option 1 380V 99.00 27.92440V 85.50 24.18220V 171.00 60.45

Option 2 380V 99.00 34.90440V 85.50 30.23

Plenum Box 220V 171.00 11.25Option 380V 99.00 6.50

440V 85.50 5.63

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -1.5 CV.• Option 1 - evaporator fan motor -2 CV.• Option 2 - evaporator fan motor -3 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Size the electrical wiring using the maximum operation currents.

Page 44: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN44

Table ED-8 — Genius – Electrical Features - SAVE100Nominal Operation Values Compressor 1 Compressor 2 Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW A

220V 14.10 14.10 4.14 32.34STD 380V 4.17 8.16 4.17 8.16 1.22 2.39 9.56 18.71

440V 7.05 7.05 2.07 16.17220V 14.10 14.10 5.53 33.73

Option 1 380V 4.17 8.16 4.17 8.16 1.64 3.19 9.98 19.51440V 7.05 7.05 2.76 16.86220V 14.10 14.10 7.32 35.52

Option 2 380V 4.17 8.16 4.17 8.16 2.23 4.23 10.57 20.55440V 7.05 7.05 3.66 17.76

Plenum Box 220V 14.10 14.10 1.80 30.00Option 380V 4.17 8.16 4.17 8.16 0.45 1.04 8.79 17.36

440V 7.05 7.05 0.90 15.00

Maximum Operation Values Compressor 1 Compressor 2 Fan Motor CurrentFan Voltage CMO CMO CMO A

220V 19.80 19.80 5.18 44.78STD 380V 11.46 11.46 2.99 25.91

440V 9.90 9.90 2.59 22.39220V 19.80 19.80 6.91 46.51

Option 1 380V 11.46 11.46 3.99 26.91440V 9.90 9.90 3.46 23.26220V 19.80 19.80 9.15 48.75

Option 2 380V 11.46 11.46 5.28 28.20440V 9.90 9.90 4.58 24.38

Plenum Box 220V 19.80 19.80 2.25 41.85Option 380V 11.46 11.46 1.30 24.22

440V 9.90 9.90 1.13 20.93

Start-up Values Compressor 1 Compressor 2 Fan MotorFan Voltage LRA LRA LRA

220V 128.00 128.00 30.92STD 380V 74.11 74.11 17.85

440V 64.00 64.00 15.46220V 128.00 128.00 48.36

Option 1 380V 74.11 74.11 27.92440V 64.00 64.00 24.18220V 128.00 128.00 60.45

Option 2 380V 74.11 74.11 34.90440V 64.00 64.00 30.23

Plenum Box 220V 128.00 128.00 11.25Option 380V 74.11 74.11 6.50

440V 64.00 64.00 5.63

ElectricalData

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -1.5 CV.• Option 1 - evaporator fan motor -2 CV.• Option 2 - evaporator fan motor -3 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Size the electrical wiring using the maximum operation currents.

Page 45: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

45PKG-PRC006-EN

ElectricalData

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -2 CV.• Option 1 - evaporator fan motor -3 CV.• Option 2 - evaporator fan motor -4 CV.• Plenum box option - evaporator fan motor -0.5 CV.• Size the electrical wiring using the maximum operation currents.

Table ED-9 — Genius – Electrical Features - SAVE125Nominal Operation Values Compressor 1 Compressor 2 Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW A

220V 16.99 14.10 5.53 36.62STD 380V 5.68 9.84 4.17 8.16 1.64 3.19 11.49 21.19

440V 8.50 7.05 2.76 18.31220V 16.99 14.10 7.32 38.41

Option 1 380V 5.68 9.84 4.17 8.16 2.23 4.23 12.08 22.23440V 8.50 7.05 3.66 19.21220V 16.99 14.10 9.28 40.37

Option 2 380V 5.68 9.84 4.17 8.16 2.93 5.36 12.78 23.36440V 8.50 7.05 4.64 20.19

Plenum Box 220V 16.99 14.10 1.80 32.89Option 380V 5.68 9.84 4.17 8.16 0.45 1.04 10.30 19.04

440V 8.50 7.05 0.90 16.45

Maximum Operation Values Compressor 1 Compressor 2 Fan Motor CurrentFan Voltage CMO CMO CMO A

220V 24.98 19.80 6.91 51.69STD 380V 14.46 11.46 3.99 29.91

440V 12.49 9.90 3.46 25.85220V 24.98 19.80 9.15 53.93

Option 1 380V 14.46 11.46 5.28 31.20440V 12.49 9.90 4.58 26.97220V 24.98 19.80 11.60 56.38

Option 2 380V 14.46 11.46 6.70 32.62440V 12.49 9.90 5.80 28.19

Plenum Box 220V 24.98 19.80 2.25 47.03Option 380V 14.46 11.46 1.30 27.22

440V 12.49 9.90 1.13 23.52

Start-up Values Compressor 1 Compressor 2 Fan MotorFan Voltage LRA LRA LRA

220V 171.00 128.00 48.36STD 380V 99.00 74.11 27.92

440V 85.50 64.00 24.18220V 171.00 128.00 60.45

Option 1 380V 99.00 74.11 34.90440V 85.50 64.00 24.18220V 171.00 128.00 87.00

Option 2 380V 99.00 74.11 50.23440V 85.50 64.00 43.50

Plenum Box 220V 171.00 128.00 11.25Option 380V 99.00 74.11 6.50

440V 85.50 64.00 5.63

Page 46: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN46

ElectricalData

• To know which ventilation option should be used, consult the behavior of theventilation options.

• CNO = Nominal operation current (A).• CMO = Maximum operation current.• LRA = Locked rotor amps.• STD Option - evaporator fan motor -3 CV.• Option 1 - evaporator fan motor -4 CV.• Option 2 - evaporator fan motor -5 CV.• Plenum box option - evaporator fan motor -1 CV.• Size the electrical wiring using the maximum operation currents.

Table ED-10 — Genius – Electrical Features - SAVE150Nominal Operation Values Compressor 1 Compressor 2 Fan Motor Consumption CurrentFan Voltage KW CNO KW CNO KW CNO KW A

220V 16.99 16.99 7.32 41.30STD 380V 5.68 9.84 5.68 9.84 2.23 4.23 13.59 23.91

440V 8.50 8.50 3.66 20.66220V 16.99 16.99 9.28 43.26

Option 1 380V 5.68 9.84 5.68 9.84 2.93 5.36 14.29 25.04440V 8.50 8.50 4.64 21.64220V 16.99 16.99 11.61 45.59

Option 2 380V 5.68 9.84 5.68 9.84 3.54 6.70 14.90 26.38440V 8.50 8.50 5.80 22.80

Plenum Box 220V 16.99 16.99 3.04 37.02Option 380V 5.68 9.84 5.68 9.84 0.83 1.76 12.19 21.44

440V 8.50 8.50 1.52 18.52

Maximum Operation Values Compressor 1 Compressor 2 Fan Motor CurrentFan Voltage CMO CMO CMO A

220V 24.98 24.98 9.15 59.11STD 380V 14.46 14.46 5.28 34.20

440V 12.49 12.49 4.58 29.56220V 24.98 24.98 11.60 61.56

Option 1 380V 14.46 14.46 6.70 35.62440V 12.49 12.49 5.80 30.78220V 24.98 24.98 14.51 64.47

Option 2 380V 14.46 14.46 8.38 37.30440V 12.49 12.49 7.26 32.24

Plenum Box 220V 24.98 24.98 3.80 53.76Option 380V 14.46 14.46 2.19 31.11

440V 12.49 12.49 1.90 26.88

Start-up Values Compressor 1 Compressor 2 Fan MotorFan Voltage LRA LRA LRA

220V 171.00 171.00 60.45STD 380V 99.00 99.00 34.90

440V 85.50 85.50 30.23220V 171.00 171.00 87.00

Option 1 380V 99.00 99.00 50.23440V 85.50 85.50 43.50220V 171.00 171.00 110.55

Option 2 380V 99.00 99.00 63.83440V 85.50 85.50 55.28

Plenum Box 220V 171.00 171.00 21.96Option 380V 99.00 99.00 12.68

440V 85.50 85.50 10.98

Page 47: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

47PKG-PRC006-EN

Dimensions

01 - Plenum box with optional supply screen02 - Resistor box for heating (optional) (control and power panel for external heating)03 - Double [intake / exhaust] (evaporator) Centrifugal fan04 - Supply motor05 - Evaporating coil06 - Return screen (optional)07 - Filters08 - Spacing for energy intake wire f 46.5 (right/left)09 - Scroll compressor10 - Drain f 1/2” BSP (left)11 - Spacing for remote thermostat wire f 46.512 - Water intake and outlet (left/right)13 - Electric panel for electric control model 100/125/150 (optional)14 - Electric panel15 - Electric panel for electric control model 050/075 (optional)16 - Shell and tube condenser

SAVE

Model A B C D E F G H J K ø L050 38 (960) 9 (230) 13 (333) – – 16 (397) 5 (127) 11 (289) 10 (263) 5 (113) 1”075 47 (1190) 15 (367) 16 (396) – – 17 (427) 2 (57) 13 (341) 10 (263) 5 (113) 1”100 59 (1500) 7 (175) 13 (333) 9 (230) 13 (333) 17 (429) 5 (127) 11 (289) 8 (213) 4 (111) 1 1/2”125 67 (1700) 8 (210) 16 (396) 10 (255) 16 (396) 17 (443) 2 (57) 13 (341) 8 (213) 4 (111) 1 1/2”150 67 (1700) 8 (210) 16 (396) 10 (255) 16 (396) 17 (443) 2 (57) 13 (341) 8 (213) 4 (111) 1 1/2”

All dimensions are in

Page 48: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN48

01 - Plenum box with optional supply screen02 - Resistor box for heating (optional) (control and power panel for external heating)03 - Double [intake / exhaust] (evaporator) Centrifugal fan04 - Supply motor05 - Evaporating coil06 - Return screen (optional)07 - Filters08 - Spacing for energy intake wire f 46.5 (right/left)09 - Double [intake / exhaust] (condenser) Centrifugal fan10 - Scroll compressor11 - Drain f 1/2” BSP (left)12 - Spacing for remote thermostat wire f 46.513 - Electric panel for electric control model 100/125/150 (optional)14 - Electric panel15 - Electric panel for electric control model 050/075 (optional)16 - Shell and tube condenser

Dimensions SRVE

Model A B C D E F G H J K L M050 38 (960) 9 (230) 13 (333) – – 16 (397) 5 (127) 11 (289) 5 (120) 47 (1180) 10 (258) 36 (920)075 47 (1190) 15 (367) 16 (396) – – 17 (427) 2 (57) 13 (341) 5 (120) 47 (1180) 10 (258) 45 (1150)100 59 (1500) 7 (175) 13 (333) 9 (230) 13 (333) 17 (429) 5 (127) 11 (289) 9 (230) 48 (1210) 10 (247) 58 (1460)125 67 (1700) 8 (210) 16 (396) 10 (255) 16 (396) 17 (443) 2 (57) 13 (341) 16 (400) 50 (1280) 9 (240) 65 (1660)150 67 (1700) 8 (210) 16 (396) 10 (255) 16 (396) 17 (443) 2 (57) 13 (341) 16 (400) 59 (1510) 9 (240) 65 (1660)

All dimensions are in

Page 49: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

49PKG-PRC006-EN

Dimensions SIVE

01 - Plenum box with optional supply screen02 - Resistor box for heating (optional) (control and power panel for external heating)03 - Double [intake / exhaust] (evaporator) Centrifugal fan04 - Supply motor05 - Evaporating coil06 - Return screen (optional)07 - Filters08 - Spacing for energy intake wire f 46.5 (right/left)09 - Scroll compressor10 - Drain f 1/2” BSP (left)11 - Spacing for remote thermostat wire f 46.512 - Electric panel for electric control model 100/125/150 (optional)13 - Electric panel14 - Electric panel for electric control model 050/075 (optional)15 - Prep for spacing for f 46.5 (right/left) lines

Model A B C D E F G H J K D1 D2 L1 L2050 38 (960) 9 (230) 13 (333) – – 16 (397) 5 (127) 11 (289) – – 5/8” – 1/2” –075 47 (1190) 15 (367) 16 (396) – – 17 (427) 2 (57) 13 (341) – – 3/4” – 1/2” –100 59 (1500) 7 (175) 13 (333) 9 (230) 13 (333) 17 (429) 5 (127) 11 (289) 6 (150) 8 (205) 5/8” 5/8” 1/2” 1/2”125 67 (1700) 8 (210) 16 (396) 10 (255) 16 (396) 17 (443) 2 (57) 13 (341) 6 (150) 8 (205) 3/4” 5/8” 1/2” 1/2”150 67 (1700) 8 (210) 16 (396) 10 (255) 16 (396) 17 (443) 2 (57) 13 (341) 6 (150) 8 (205) 3/4” 3/4” 1/2” 1/2”

All dimensions are in

Page 50: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

PKG-PRC006-EN50

Dimensions CRCB

01 - Double [intake / exhaust] Centrifugal fan02 - Terminal box03 - Service panel04 - Motor05 - Condensing coil06 - Spacing for ø 27 energy intake wire07 - Refrigeration connections (only one setting)

Model A B C D E F G H I J L M N P Q R ø L1 ø D1 ø L2 ø D2050 39 25 35 12 16 – – 13 30 28 4 41 21 5 – – 1/2” 5/8” – –

(987) (631) (890) (295.5) (396) (341) (762) (711) (110) (1029) (521) (132)075 49 25 35 17 16 – – 13 40 32 4 51 21 5 – – 1/2” 3/4” – –

(1241) (631) (890) (422.5) (396) (341) (1016) (816.5) (110) (1283) (521) (132)100 49 25 37 9 13 9 13 11 45 34 4 55 21 6 8 10 1/2” 5/8” 1/2” 5/8”

(1341) (631) (941) (212.5) (333) (230) (333) (289) (1143) (863.5) (97) (1383) (521) (159) (200) (255)125 65 28 40 12 16 10 16 13 58 37 3 67 24 9 8 10 1/2” 3/4” 1/2” 5/8”

(1646) (714) (1018) (299.5) (396) (255) (396) (341) (1473) (940) (84) (1688) (604) (236) (200) (255)150 65 28 49 12 16 10 16 13 58 46 3 67 24 9 8 10 1/2” 3/4” 1/2” 5/8”

(1646) (714) (1247) (299.5) (396) (255) (396) (341) (1473) (1168) (84) (1688) (604) (236) (200) (255)

All dimensions are in

Page 51: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

51PKG-PRC006-EN

MechanicalSpecifications

CabinetManufactured of galvanized steel plate,it is painted with anticorrosive primerand high resistance synthetic enamel.The cabinet is constructed with anbottom tray, structural laterals, frontscreen and cover and back cover. Theremote condenser cabinet is paintedwith epoxy primer and high resistanceenamel and is also constructed ofgalvanized steel plate.

For frontal access to the evaporatorunits, just loosen four screws to removethe cover and the screen.

Return ScreenScreen of anodized aluminum profilewith vertical flanges. Vertical screensprovide excellent air distribution in thecoil. This option is recommended forhulls in which the machine is visible inthe zone to be air-conditioned.

Plenum BoxThe style of the plenum box is similar tothat of the cabinet and is sized toguarantee silent operation. The plenumbox screen has a slight angle that allowsthe air flow to be directed in a vertical orlateral direction. A specific fan arrayexists for use of the Genius unit withplenum box (consult the general factstables).

This plenum should only be used whenthe discharge from the unit is free intothe atmosphere. In the case of dischargeinto a duct network, this option shouldnot be used.

CoilsAll the coils (evaporator and condenser)use tubes with 3/8” external diameterand high efficiency aluminum flange,Trane Wavy 3B model, mounted on theevaporator coil with 132 fins per foot,and on the condenser with 168 flangesper foot.

The copper tubes are expandedmechanically to guarantee perfectcontact between fin and tube. All thecoils are tested for leaks. Evaporatorcoils are tested at a pressure of 300PSIG, and the condensers at 400 PSIG.

The tray for condensation water wasdesigned according to the interior airquality standards of ASHRAE.

Copper-Copper CoilsFor applications where greaterresistance against corrosion isnecessary, coils with copper tubes andfins can be manufactured. Offer asspecial design.

Water-cooled condenserWater-cooled condensers are “Shell &Tube” type. They are manufactured withcopper tubes with integrated flanges,expanded in steel mirrors, with groovedholes, mounted in a steel casing andcast iron covers, which are removablefor easy cleaning. The casing and coversare protected with finishing paint.

Designed, constructed and testedaccording to ASME standards, for workpressure of 300 PSIG on the refrigerantside and 150 PSIG on the water side.

FansSirocco type centrifugal fans,constructed of galvanized steel platewith static and dynamically balancedrotors. The evaporator array is sized toovercome up to 1.6 inches of externalstatic pressure.

FiltersThe standard unit is furnished withpermanent washable filters ofelectrostatic fabric.

Also Available:Metallic permanent filters (standard)Disposable fiberglass filters of 1”thicknessCombination in series of the twoprevious filters

Scroll CompressorAll compressors of the Genius line arescroll type. They are of high efficiencyusing ports instead of valves, whicheliminates possible breakdowns. Theyhave 64% fewer moveable parts than areciprocating compressor of the samecapacity. Their operation is extremelysmooth and silent.

Page 52: Vertical Self-Contained Air Conditioning - Trane · Vertical Self-Contained Air Conditioning Air and Water Cooled 5 - 15 Tons 50 Hz ... the comfort of knowing that our self-contained

The Trane Company3600 Pammel Creek RoadLa Crosse, WI 54601-7599www.trane.com

An American Standard CompanySince The Trane Company has a policy of continuous product improvement, it reserves the right to changedesign and specifications without notice.

Literature Order Number

File Number

Supersedes

Stocking Location

Regulating points for high and low pressure pressurestats Stop - PSIG Start-up - PSIGMachines with water condensation 275 +/- 15 185 +/-15Machines with air condensation 395 +/- 15 280 +/- 20Machines with water and air condensation 25 +/- 8 80 +/- 12

MechanicalSpecifications

Line diameter Suction line Discharge line Liquid line5 TR circuit 7/8” 5/8” 1/2”7.5 TR circuit 1 1/8” 3/4” 1/2”10 TR circuit 1 1/8” 7/8” 5/8”

Safety and Protection DevicesThe equipment is protected by high andlow pressure pressurestats withautomatic resets and fixed calibration,internal thermostat with automatic reset

Cooling ComponentsIn the suction and discharge linesRotalock type service valves areavailable. The liquid line has a 1/4” SAESchrader valve.

A drying filter is installed in the liquidline. For the SIVE model the drying filter

ControlsUnits are provided with a controlthermostat. This thermostat can beinstalled remotely or in the equipment,depending on the needs of the client.

As Option:Programmable ThermostatUCP Microprocessor Control

Service ValveService valve for the liquid line.

Condensation Pressure ControllerA set with pressurestatic valves tocontrol the condensation pressure inmachines with air-cooled condensers.

in the compressor, current overloadrelay for the compressor and overloadthermal relay for the fan motors.

Water-cooled condensers are protectedby a fusible top.

has a screw connection. For the SAVEand SRVE models, the filter is welded.

The following table shows therefrigerant tube diameters relative tothe equipment cooling circuits.

High pressure pressurestat with manualreset

Liquid TankOnly for the SIVE model.

Liquid ViewerAuxiliary maintenance component,indicates the existence of humidityinside the equipment.

Solenoid ValveAuxiliary component that allowsconfinement of the refrigerant in thecondenser for later extraction.

Supply Voltage 380V, triphasic, 50 HZ.

Electric HeatingIncludes heating resistors, stainless steeltubes, a contact unit, fuses, a controlthermostat and safety thermostat, allproperly installed.

The control scheme considers the use ofheating resistors.

TestsGenius line equipment are shipped fullytested from the factory. The standardtests consist of visual inspections, leaktests, fan start-up followed by start-upand operation of the unit.

Trane offers the following factory tests:Basic production test with inspector.Performance test.Complete test with or without aninspector present.

PKG-PRC006-EN

PL-UN-PKG-000-PRC006-EN-100

New

La Crosse