Ventilation
Technical DataOutdoor air processing unit, ventilation and air processing
EEDEN13-205
FXMQ-MF
-
• Ventilation • FXMQ-MF 1
• Indoor Unit • FXMQ-MF
TABLE OF CONTENTSFXMQ-MF
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Cooli ng/ Heati ng Capacity Tables 7
6 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Dimensi onal Drawings 10Dimensi onal Drawings wi th Accessor ies 12
7 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Wiring Diagrams - Single Phase 16
10 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Sound Pressure Spectrum 17
11 Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
12 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
-
• Indoor Unit • FXMQ-MF
1
2
1 Features
oor Unit ntilat Q-MF door air
Ind Ve FXM Out • 100% fresh air intake possible• Ideal solution for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings
• Operation range: -5°C to 43°C
• Up to 225Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas
• Drain pump kit available as accessory
• Ventilation • FXMQ-MF
-
3
2
• Indoor Unit • FXMQ-MF
2 Specifications
Standard Accessories : Clamps;Standard Accessories : Screws;Standard Accessories : Sealing pads;Standard Accessories : Installation and operation manual;Standard Accessories : Connection pipes;
2-1 Technical Specifications FXMQ125MF FXMQ200MF FXMQ250MFCooling capacity Nom. kW 14.0 (1) 22.4 (1) 28.0 (1)Heating capacity Nom. kW 8.9 (2) 13.9 (2) 17.4 (2)Connection ratio Outdoor units with
only ventilation units connected
Minimum
% 50
Maximum
% 100
Ventilation units when combined with VRV® indoor units
Maximum
% 30
Casing Material Galvanised steelDimensions Unit Height mm 470
Width mm 744 1,380Depth mm 1,100
Weight Unit kg 86 123Heat exchanger Rows Quantity 3
Stages Quantity 26Fin pitch mm 2.0Face area m² 0.28 0.65
Fan Type Sirocco fanExternal static pressure - 50Hz
High Pa 185 225 205
Fan motor Model D13/4G2DA1Output 50 Hz W 380Drive Direct drive
Operation range On coil temperature Cooling Max. °CDB 43 (13)Heating Min. °CDB -5
Refrigerant Control Electronic expansion valveType R-410A
Piping connections Liquid Type Flare connectionOD mm 9.52
Gas Type Flare connection Braze connectionOD mm 15.9 19.1 22.2
Drain PS1BSafety devices Item 01 Thermal potector for fan motor, fuse
2-2 Electrical Specifications FXMQ125MF FXMQ200MF FXMQ250MFPower supply Phase 1~
Frequency Hz 50Voltage V 220-240
Voltage range Min. % -10Max. % 10
Current Minimum circuit amps (MCA) A 1.9 3.3 3.8Maximum fuse amps (MFA) A 15Fan motor rated output kW 0.380Full load amps (FLA)
Fan motor A 1.5 2.6 3.0
• Ventilation • FXMQ-MF 3
-
• Indoor Unit • FXMQ-MF
2
4
2 Specifications
Notes
(1) Cooling: outdoor temp.: 33°CDB, 28°CWB (68%RH), discharge set temperature: 18°CDB, equivalent piping length 7.5m (horizontal) (2) Heating: outdoor temp. 0°CDB, -2.9°CWB (50%RH); discharge set temp. 25°CDB; equivalent piping length: 7.5m (horizontal) (3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (4) The air filter is not a standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method) 50% or more. (5) When connected to VRV water-cooled outdoor units a mix of ventilation units and VRV indoor units is not possible (6) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) Maximum allowable voltage range variation between phases is 2%. (8) MCA/MFA: MCA = 1.25 x FLA (9) MFA ≤ 4 x FLA (10) Next lower standard fuse rating minimum 15A (11) Select wire size based on the value of MCA (12) Instead of a fuse, use a circuit breaker (13) 45% Relative humidity
• Ventilation • FXMQ-MF
-
3
3
• Indoor Unit • FXMQ-MF
3 Safety device settings
• Ventilation • FXMQ-MF 5
-
• Indoor Unit • FXMQ-MF
4
6
4 Options
������� �� �
�
������������ ������������������������������� ��� ���������� ����������
�� ��������� �������������������!�� ���������� �����������"������������������������� ���������� ����������
��������
• Ventilation • FXMQ-MF
-
3
5
• Indoor Unit • FXMQ-MF
5 Capacity tables
5 - 1 Cooling/Heating Capacity Tables
• Ventilation • FXMQ-MF 7
-
• Indoor Unit • FXMQ-MF
5
8
5 Capacity tables
5 - 1 Cooling/Heating Capacity Tables
• Ventilation • FXMQ-MF
-
3
5
• Indoor Unit • FXMQ-MF
5 Capacity tables
5 - 1 Cooling/Heating Capacity Tables
• Ventilation • FXMQ-MF 9
-
• Indoor Unit • FXMQ-MF
6
10
6 Dimensional drawings
6 - 1 Dimensional Drawings
���������
�������
NOTES
� �#$%&'#(�#)�*('&+,�(%-.�/0%&.,1��#(&2#0�3#4�,*2)%$.5� #*(&�&6.�%'2�)'0&.2�%&�&6.�,*$&'#(�,'7.5�
89.0.$&�'&,�$#0#2'-.&6#7�8:2%;'&
-
3
6
• Indoor Unit • FXMQ-MF
6 Dimensional drawings
6 - 1 Dimensional Drawings
FXMQ200,250MF
3D045128A
Piping size (field supply)
NOTES
1 Location of unit's name plates: Control box surface.2 Mount the air filter at the suction side.
(Select its colorimethod (gravity method) 50% or more).
Indoor unit Gas side Liquid sideFXMQ200MFV1 ø 19.1 attached piping ø 9.5FXMQ250MFV1 ø 22.2 attached piping ø 9.5
Nr Name Description1 Liquid pipe connection Flare connection2 Gas pipe connection Attendant piping connection3 Drain pipe connection PS1B Internal thread
Major dia. ø 33.349,Minor dia. ø 30.391
4 Control box5 Ground terminal M5 (Inside control box)6 Name plate Note 17 Power supply wiring connection8 Transmission wiring connection9 Hanger bracket M1010 Discharge companion flange11 Water supply port12 Attached piping Brazing
(All around)32 - ø 4.7 hole
(Service space)Inspection hole 600 or more
650 o
r more
11x1
00=1
100
1296
1380
(Serv
ice sp
ace)
1100 or more
1148
Appro
x. 15
0
Discharge side
A View
Suction side (Note 2)
3x10
0=30
0
1100760
613
470
50
A View
(All around)16 - M5 hole
12305x200=1000
250 3
60 330
200
(All around)32 - ø7 hole
12301200
11x100=1100
25
360
330
3x10
0=3 61
296 39
0
3025
0
1004
B View ( For FXMQ250MFV1)
(All around)16 - M5 hole
12305x200=1000
250 3
60 330
200
580
B View ( For FXMQ200MFV1)
B
24560
• Ventilation • FXMQ-MF 11
-
• Indoor Unit • FXMQ-MF
6
12
6 Dimensional drawings
6 - 2 Dimensional Drawings with Accessories
FXMQ125MF
3D046155
Nr Name Description1 VRV D.P. Unit C. duct type2 Filter chamber3 High-efficiency filter4 Long-life replacement filter5 Drain pump kit Built-in6 Drain pipe connection
(drain pump kit)VP25 (O.D. ø 32, I.D. ø 25)
7 Water supply port8 Drain hose Attached to drain pump kit
Inspection hole 600 or more
650 o
r more
5x10
0=50
074
4
(Serv
ice sp
ace)
1100
1148
Appro
x. 30
0
A
79529285
456
8
A View
5645x100=500 22
320
033
036
0
630600
5x100=500
(0~25
0)
360
330
3x10
0=30
0
300 or less
222 22
2~47
2
250
20 - ø4.7 hole(All around)
16 - ø8 hole(All around)
744
685
690 o
r more
(Serv
ice sp
ace)
222 3x10
0=30
0
594
20 - ø7 hole(All around)
• Ventilation • FXMQ-MF
-
3
6
• Indoor Unit • FXMQ-MF
6 Dimensional drawings
6 - 2 Dimensional Drawings with Accessories
FXMQ200-250MF
3D046154
Nr Name Description1 VRV D.P. Unit C. duct type2 Filter chamber3 High-efficiency filter4 Long-life replacement filter5 Drain pump kit Built-in6 Drain pipe connection
(drain pump kit)VP25 (O.D. ø 32, I.D. ø 25)
7 Water supply port8 Drain hose Attached to drain pump kit
Inspection hole 600 or more
650 o
r more
11x1
00=1
100
1380
(Serv
ice sp
ace)
1100
1148Ap
prox.
300
A
79529285
456
8
A View
12005x200=1000 23
320
033
036
0
12301200
11x100=1100
(0~25
0)
360
330
3x100=
300
300 or less
222 22
2~47
2
250
32 - ø4.7 hole(All around)
16 - ø8 hole(All around)
1380
1296
690 o
r more
(Serv
ice sp
ace)
222
3x10
0=30
0
1230
32 - ø7 hole(All around)
• Ventilation • FXMQ-MF 13
-
• Indoor Unit • FXMQ-MF
7
14
7 Centre of gravity
������
�������
#7.0 �2#7*$&�-%,, �� �! �� �� �����������������
���C: ��� � � ��� ��� �����C: ��� �� � ��� ��� ������C: ��� �� � ��� ��� ���
• Ventilation • FXMQ-MF
-
3
8
• Indoor Unit • FXMQ-MF
8 Piping diagrams
• Ventilation • FXMQ-MF 15
-
• Indoor Unit • FXMQ-MF
9
16
9 Wiring diagrams
9 - 1 Wiring Diagrams - Single Phase
• Ventilation • FXMQ-MF
-
3
10
• Indoor Unit • FXMQ-MF
10 Sound data
10 - 1 Sound Pressure Spectrum
�������
�����
� ";.2��00�87!=18!A��A���',�%02.%7
-
• Indoor Unit • FXMQ-MF
11
18
11 Fan characteristics
���������
��������
����E��� ����E����4
&.2(%
0�,&%&
'$�/2.
,,*2.
�4&.2
(%0�,
&%&'$�
/2.,,
*2.
8--��"=��������8�%= 8--��"=��������8�%=
�'2�)0#B�8--'(= �'2�)0#B�8--'(=
�#B.2�0
'-'&�#)�
�9�
8,&%(7%
27��9�
=
�#B.2�0'
-'&�#)��
9�
8,&%(7%
27��9�=
• Ventilation • FXMQ-MF
-
3
11
• Indoor Unit • FXMQ-MF
11 Fan characteristics
FXMQ200MF
3D046266
220V-50Hz 240V-50HzEx
terna
l stat
ic pre
ssure
Exter
nal s
tatic
press
ure
(mmH2O) (Pa) (mmH2O) (Pa)
Air flow (m3/min) Air flow (m3/min)
Lower l
imit of
ESP
(standa
rd ESP)
Lower li
mit of E
SP
(standa
rd ESP)
��������
�������
����E��� ����E���
�4&.2
(%0�,
&%&'$�
/2.,,
*2.
�4&.2
(%0�,
&%&'$�
/2.,,
*2.
8--��"=��������8�%= 8--��"=��������8�%=
�'2�)0#B�8--'(= �'2�)0#B�8--'(=
�#B.2�0'
-'&�#)��
9�
8,&%(7%
27��9�=
�#B.2�0'-
'&�#)��9�
8,&%(7%27
��9�=
• Ventilation • FXMQ-MF 19
-
• Indoor Unit • FXMQ-MF
12
20
12 Operation range
���������
�������
NOTES
� �6.,.�)':*2.,�%,,*-.�&6.�)#00#B'(:�#/.2%&'(:�$#(7'&'#(,58�(7##2�%(7�#*&7##2�*('&,= �>*';%0.(&�/'/'(:�0.(:&61��5�- �.;.0�7')).2.($.1��-
� 1��6.�7',$6%2:.�%'2�&.-/.2%&*2.�-%
-
3
12
• Indoor Unit • FXMQ-MF
12 Operation range
�����
��
�������
NOTES
� �6.,.�)':*2.,�%,,*-.�&6.�)#00#B'(:�#/.2%&'(:�$#(7'&'#(,58�(7##2�%(7�#*&7##2�*('&,= �>*';%0.(&�/'/'(:�0.(:&61��5�- �.;.0�7')).2.($.1��-
� 1��6.�7',$6%2:.�%'2�&.-/.2%&*2.�-%
-
These products are not within the scope ofthe Eurovent certification program
EED
EN
13-2
05
07/
13 C
opyr
ight
Dai
kin
The
pres
ent p
ublic
atio
n su
pers
edes
EED
EN12
-205The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.has compiled the content of this leaflet to the best of its knowledge. Noexpress or implied warranty is given for the completeness, accuracy, re-liability or fitness for particular purpose of its content and the productsand services presented therein. Specifications are subject to changewithout prior notice. Daikin Europe N.V. explicitly rejects any liability forany direct or indirect damage, in the broadest sense, arising from or re-lated to the use and/or interpretation of this leaflet. All content is copy-righted by Daikin Europe N.V.
BARCODE Daikin products are distributed by:
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
VentilationTechnical DataFXMQ-MF
1 Features2 Specifications2-1 Technical Specifications2-2 Electrical Specifications
3 Safety device settings4 Options5 Capacity tables5 - 1 Cooling/Heating Capacity Tables
6 Dimensional drawings6 - 1 Dimensional Drawings6 - 2 Dimensional Drawings with Accessories
7 Centre of gravity8 Piping diagrams9 Wiring diagrams9 - 1 Wiring Diagrams - Single Phase
10 Sound data10 - 1 Sound Pressure Spectrum
11 Fan characteristics12 Operation range