vegap three phase outdoor sf6 insulated pole mounted lbs fnal
DESCRIPTION
sfTRANSCRIPT
Three phase Outdoor SF6 insulated
pole mounted LBS
VEGA P
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 1/15
Three phase outdoor SF6 insulated
pole mounted LBS
The Pole Mounted switch disconnector for medium voltage application is a self supporting bent-press stainless 30/10 plate structure with a IP54 protection degree for horizontal mounting. It is manufactured to be assembled to the pole through a bracket and a steel strip. Each part of the structure is earth connected. The connection of the line to the earth is made by external conductors. The disconnector can be controlled in a manual or electrical mode and there is a mechanical fuorescent signal to show open and closed positions. The insulators could be made in silicone or epoxy resin and they are subjected to a quick aging test.
The switch disconnector types differ in relation to the required use and installation:
P Manual pole mounted switch PE Motorized pole mounted switch
Designed, manufactured and tested in accordance with IEC, CEI and ENEL applicable standards, such as:
� Switchboard and apparatus: IEC 62271-200 � bushings for alternative voltages above 1000 V: IEC 60137 � Alternating current disconnectors and earthing switches: IEC 62271-102
And also to ENEL specifications:
� DY 806/1 MATR.162071 (P model) � DY 806/2 MATR.162075 (PE model)
� Standard electrical, thermal, mechanical tests � Internal arc tested �
LBS
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 2/15
Three phase outdoor SF6 insulated
pole mounted LBS
Bare conductors
VegaP Technical data
VegaP Technical data Rated Voltage 12 kV 24 kV
Motorization 24Vdc ± 20%
Frequency 50 Hz 50 Hz
Max power consumption at nominal V 150 W
Transfer current 400 A 400 A
Temperature operating conditions -25°C - 40°C
630 A 630 A
Degree of protection IP54
Rated Current
400 A 400 A
Environment conditions 630 A 630 A
Operative temprerature -25°C - 50°C
Breaking capacity cosØ 0,7
400 A 400 A
Humidity 0% - 90% 630 A 630 A
Max Altitude 1000 m
Short time current withstand 1 second
12.5 kA 12.5 kA
Mechanical operations 1000
16 kA 16 kA
Close opening operations 100 20 kA 20 kA
Thickness and material of the tank 3 mm, stainless steel
25 kA 25 kA
Absolute rated filling pressure (20° C) 125 kPa Short time current withstand 3 seconds 18.5 kA 18.5 kA
Materials
Internal arc withstand current 1 second 12.5kA 12.5kA
Contacts Copper Silver plated
Peak current withstand
31,5 kA 31,5 kA
Arc estinguish chamber Polycarbonate
40 kA 40 kA
Bushing Silicon rubber 50 kA 50 kA
Terminals Copper
62.5 kA 62.5 kA
Degree of protection IP64 Short circuit making current 12.5 kA 12.5 kA
Estimated weight (kg)
16 kA 16 kA
LBS 113 kg
Rated making capacity on short-circuit fault (5 closing ops.)
31,5 kA 31,5 kA
LBS support 29 kg
40 kA 40 kA
Connecting shafts and one MT cable 11 kg Breaking capacity
Transmission system 7.5 kg
No Load cables 16,0 A 16,0 A
Motorization (TV and cable TV-UP) 39 kg No Load O.H. lines 10,0 A 10,0 A
Creepage distance and clearances
No Load Transformer 6,3 A 6,3 A
Between insulators 390 mm Power freq. withstand voltage
Phase to Phase 120 mm
Towards the ground and between phases 28 kV 50 kV
From insulator top to base 730 mm
Across the isolating distance 32 kV 60 kV Rated lighting impulse withstand voltage
Towards the ground and between phases 75 kV 125 kV
Across the isolating distance 85 kV 145 kV
M16
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 3/15
Three phase outdoor SF6 insulated
pole mounted LBS
Insulated conductors
Protection enclosures The whole external enclosure including the mechanism carter are in stainless steel. Ferrous material components of the operating mechanism are composed by hot dip zinc galvanised. The switch support and the transmission is hot dip zinc coated. Motorized operating mechanism The motorized operating mechanism is composed by a permanent magnet reductive motor. Characteristics: Following the on-off operation, in less than 4 seconds the LBS will complete the open or close operation during service. The maximum time for auxiliary power and LBS loading and operating is less than 7 seconds at the minimum supply voltage. DIMENSIONS
TYPE P Frontal view
M14
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 4/15
Three phase outdoor SF6 insulated
pole mounted LBS
Top view
INSPECTION, HANDLING AND STORAGE, ACCEPTANCE INSPECTION At the moment of the delivery of the switch, it is recommended to verify:
• The correspondence of delivery documents
• The integrity of packaging and of the switch In case of transport damages, contact us within 30 days. Storage If not immediately used, store the switch in a well protected, dry and ventilated place, positioning them according to the instructions on packaging. Do not absolutely lift the load break switch through insulators. Handling Be careful when handling switch, avoiding bumps and accidental solicitations especially on isolators of both switch and VT (when included and in case it is mounted on switch before the pole mounting) and, in the case of use of fork lift, put it on the forks according to the right position as shown on packaging. Do not absolutely lift the load break switch through insulators. Installation and use
• Before installing, verify the integrity of the switch
Removal of mechanism carter: 1) Unscrew exclusively the central M8 screw on the drive shaft (1) and extract the shaft (2). 2) Remove the mechanism carter (3) unscrewing the 12 M6 nuts
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 5/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 1
When completed, re position the mechanism carter and the bar paying attention to the coupling between the hub shaft and the related position on the drive shaft. Connections:
Switch Function UP 1 +M Power Supply (+24 Vcc) 1 2 -M Power Supply (-24 Vcc) 2 3 +A Power commands (+24 Vcc) 3 4 -A Power commands (-24 Vcc) 4 5 89CX Remote locking 5 6 89AX Remote Opening 6 7 89ccx Remote signal closed switch 7 8 89cax Remote signal open switch 8
Fixing the support:
Place the LBS support at a height of about 2,55 meters from the pole top (figure 2) and fix 1 according to the instructions reported in figure 3 with a stainless steel tape (type 19 DS3230/2) and fastening clip (type 19 DS3240/2) checking that the tape is passing through the holes “A”, ”B”, ”C”, ”D” (figure 2).
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 6/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 2
Fixing the switch to the support: Place the pole switch on the support and fix it with the screws and nuts kit provided in the positions indicated in figure 3. The switch will be oriented with the shaft near the pole.
Figure 3
N.B: the bracket has to be mounted on the opposite side of the support (as in figure). a) 180 degree bending with a strong lock clamp. Avoid hammering to prevent material hardening. b) 180 degree bending only with a gear puller. Avoid hammering to prevent material hardening. During this operation, loose the pilling a bit and gradually as you proceed to fold the tape in order to avoid excessive cuts. c) Re-bent slot d) 180 degree bending with a clamp and light hammer.
“A” detail
“A” detail
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 7/15
Three phase outdoor SF6 insulated
pole mounted LBS
Transmission system positioning:
Figure 4
1) Connect two or three bars for each side of the LBS according to the pole height (figure 5,6,7). Mounting transmission shafts for a pole with 10 meter height Connect the shafts using the four holes Ø9 fixing them with: n° 4 screws M8x25 UNI 5739 n° 4 nuts M8 UNI 5588 n° 8 washers Ø8,4 UNI 6892 n° 4 growers Ø8,4 UNI 1751 for each side of the LBS N°2 shafts for each side of the LBS coupled at half the length.
M12 fixing pin for grounding
Connection cable UP
Fixing points
Connection cable TV
UP
Operating shaft
Fixing points with: 4 screws M12x30 UNI5739 4 washers UNI 6592 4 grower UNI 1751
TV fixing points with: 4 screws M10x40 UNI5739 4 washers UNI 6592 4 grower UNI 1751
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 8/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 5
Mounting transmission shafts for a pole with 11 meter height Connect the shafts using the two holes Ø9 fixing them with: n° 2 screws M8x25 UNI 5739 n° 2 nuts M8 UNI 5588 n° 4 washers Ø8,4 UNI 6892 n° 2 growers Ø8,4 UNI 1751 for each side of the LBS N°2 shafts for each side of the LBS coupled at the whole length.
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 9/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 6
Mounting transmission shafts for a pole with 12 meter height Connect the shafts using the four holes Ø9 fixing them with: n° 4 screws M8x25 UNI 5739 n° 4 nuts M8 UNI 5588 n° 8 washers Ø8,4 UNI 6892 n° 4 growers Ø8,4 UNI 1751 for each side of the LBS N°3 shafts for each side of the LBS coupled at the whole length.
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 10/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 7
2) Fix the transmission shafts in proximity of the Ø13 holes on the operating lever pins of the load break switch with two cotter Ø5 pin holes supplied (figure 8).
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 11/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 8
3) Fix the transmission shafts in proximity of the Ø13 holes on the operating lever pins of the transmission with two cotter pin holes Ø5 supplied (figure 9).
Figure 9
4) Locate the transmission system previously connected to the transmission shafts on the pole and fixing according to the instructions detailed in figure 3 with the stainless steel tape (type 19 DS3230/2) and the fixing hooks (type 19 DS3240/2) in relation of the two holes of the system itself (figure 10).
Detail of transmission shaft mounting on operating lever
with cotter pin hole Ø 5
Operating lever
Transmission shaft
Detail of transmission shaft mounting on transmission operating lever with cotter pin Ø 5 hole
Transmission
operating lever
Transmission shaft
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 12/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 10
Main connections Main electrical connections: In order to correctly fix the main electrical connections, when tightening the connection bolts always use two wrenches at the same time in order not to stress the insulating parts. Grounding connections: Figure 11 shows the grounding points of the system. The grounding connections need to be made with the minimum possible resistance; it is thus necessary that the surfaces of the connections are perfectly clean and degreased. Pay
particular attention to the TV grounding connection.
IMPORTANT: the connection cables between TV and UP and between LBS and UP have to be fixed diametrically opposed along the pole slope (figure 4).
Figure 11
Steel tape
Screw for grounding
Screw for grounding
Screw for grounding
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 13/15
Three phase outdoor SF6 insulated
pole mounted LBS
Instruction for LBS use The LBS status is reported by the letters “A” (black written on a green background) and “C” (black written on a red background) visible on the base of the mechanism carter. LBS electrical mechanism remotely controlled (PE version): Opening/Closing: At the beginning of the LBS closing operations, the operating mechanism will charge loading springs and will automatically make the LBS open/close in less than 7 second at the minimum operating voltage. Manual local operations Opening/Closure The manual operation to open/close the LBS is performed operating the transmission lever with the foil pulling it down (figure 12); at the beginning of the operation also the power supply of the motorization will stop (for PE version)
Figure 12
Lockable function: In order to guarantee the LBS open status, the transmission system is provided by a lockable pin that will lock LBS in open position. In case of motorized mechanism, the device will allow also the current cut of the motor (thus avoiding the start by remote systems). To obtain the lockable function, the following operations are required:
• Set the LBS on OPEN
• Rotate the operating lever downward of few degrees in order to allow the entering of the pin into the shaft hole (moving part) and in those of the transmission system (fixed part) (figure 13).
• Block the pin with a locker in order to avoid the pin unplugging.
Close Open
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 14/15
Three phase outdoor SF6 insulated
pole mounted LBS
Figure 13
Motorized operating mechanism change (PE version) BVV
Figure 14
Lever in “OPEN LBS” position
Hole to insert lockable pin
Lockable pin
LBS status Micro-switch (electrical
OPEN/CLOSE signal)
n. 3 screws M6 to unscrew for the
system change
Lever in lockable position
Micro-switch for motor supply cut in case of manual operation Micro-switch for electrical
interblock
Elettropicena Sud s.r.l. Delta Systems s.r.l.
Ancarano (TE), Italy Bergamo, Italy Tel.: +390861870172, Fax: +390861870901 Tel.: +390350296740, Fax: +390355095732 www.elettropicenasud.it www.delta-systems.net
Page 15/15
Three phase outdoor SF6 insulated
pole mounted LBS
In order to change the motorized operating mechanism, the following operations need to be performed:
1) Unscrew the screw on the command shaft (1) and disconnect the transmission shaft (2) (ref. Figure 1); 2) Remove the mechanism carter (3) (figure 1) 3) Unplug the motor connector; 4) Remove the three screws M6 shown in figure 14;
When clamping the three M6 screws (after the system change) pay attention to the the coupling between the motor and the mechanism shaft greasing the two dented wheels.
Maintenance The system does not need any maintenance operation for the first 36 months. Lubricate the gear and LBS operating parts with a greasy spray. Open and close the LBS several times.
End of life gas recover To recover LBS end of life gas, the following operations are required:
- Unscrew the screws and remove the protection cover “I” - Remove the lock; - Unscrew and remove cover “2”. Now the access to valve “3” is allowed. - Push the support “4” to cause the gas coming out.
Part numbering information
Ex. M-SG-VEGAP-PE-24kV-630A-25kA
Part number (p/n)
Product class: "M"
Subclass / Sottoclasse:
PA Primary air insulated
SA Secondary air insulated
PG Primary gas insulated
SG Secondary gas insulated
PM Primary gas/air insulated
SM Secondary gas/air insulated
Product Type / Tipo: VegaP
Product Subtype / Sotto Tipo: P,PE
Rated voltage in kV
Rated current in A
Withstand current (1 sec) in kA
Standard accessories
Earth connectors
Optional Accessories
Bracket and support
Auxiliary contacts
Auxiliary VT
Remote control system
Key interlock
Hanging brackets
Silicone rubber insulators
Lifting bolts
Operating lever
UP Peripheral unit
Elettropicena Sud s.r.l.
Ancarano (TE), Italy
Tel.: +390861870172, Fax: +390861870901
www.elettropicenasud.it
Delta Systems s.r.l.
Bergamo, Italy
Tel.: +390350296740, Fax: +390355095732
www.delta-systems.net