VACUUM CONTACTORS MEDIUM VOLTAGE

Upload: others

Post on 06-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • VACUUM CONTACTORSMEDIUM VOLTAGE

  • MV VACUUM CONTACTORS

    • Environment-Resistant: Ideal for use in high-dust areas. Switching arc is contained within the vacuum bottle, shielding the main contacts.

    • Reduced Maintenance: Vacuum bottle contacts have long life with virtually no maintenance required.

    • No External Surge Protection: Special main contact materials minimize chopping current. No surge suppressor is required.

    • Designed for Safety: High voltage and low voltage parts are completely separated by an insulated barrier (non-flammable molded frame).

    • Electronic Control Drive Unit: All contacts include electronic control of the operating coil, which offers a wide control voltage of 100 to 240 VAC and 100 to 250 VDC, anti-chopping feature, and reduced power consumption.

    • HCV-7HA (7200 V, 400 A) Contactor: New HCV-7HA(L) Contactor: Same dimensions as the HCV-5HA, but Includes Higher Performance Vacuum Interrupter. Higher Interrupting-Performance: Afford a Wide Margin of Protective Coordination with Any Type of Power Fuse Resulting in Increased Electrical Safety & Reliability .

    • Designed for Longer Wear: Unique vertical magnetic arc dispersion system. USA patents on HCV-1KAU, HCV-7HA, HCV-7HAL, HCV-6KAU, and HCV-6KALU.

    • Compact & Lightweight: Smaller than air break contactors of equivalent electrical performance.

    • Conformance to International Standards: Conforms to international industrial standards such as UL, CSA, AS, BS, NEMA, and IEC. Consult factory for each series.

    • Higher Interrupting Performance: Offers a wide margin of protective coordination with any type of power fuse, resulting in increased electrical safety and reliability.

    OFFON

    8.89

    10.36

    17.05

    0.38

    5.130.43

    7.251.37

    16.8115.31

    18.43

    6.30

    15.27

    0.75

    0.43 DIA. MOUNTING HOLES4 PLACES

    OFFON

    8.89

    10.36

    17.05

    0.38

    5.130.43

    7.251.37

    16.8115.31

    18.43

    6.30

    15.27

    0.75

    0.43 DIA. MOUNTING HOLES4 PLACES

    OFFON

    MOUNTING HOLES4 PLACES

    17.404.534.532.72

    5.04

    14.61

    1.22 11.81

    8.46

    4.88

    8.54

    0.43 DIA

    NP

    OFFON

    MOUNTING HOLES4 PLACES

    17.404.534.532.72

    5.04

    14.61

    1.22 11.81

    8.46

    4.88

    8.54

    0.43 DIA

    NP

    0.55 DIA. MOUNTINGHOLES 4 PLACES

    0.5119.68

    20.71

    22.24

    6.56.5

    5.75

    7.60.94

    12.59

    8.11

    9.250.59

    0.55 DIA. MOUNTINGHOLES 4 PLACES

    0.5119.68

    20.71

    22.24

    6.56.5

    5.75

    7.60.94

    12.59

    8.11

    9.250.59

    COMPACT DESIGN,ADVANCED TECHNOLOGY

    HCV-5HA/7HA

    HCV-6KAU

    CV-10H

  • MV VACUUM CONTACTORS MV VACUUM CONTACTORS

    P9 ASD

    Model HCV-5HA HCV-5HAL HCV-7HA HCV-7HAL HCV-6KAU HCV-6KALU CV-10HA(L) CV-10HB(L)

    Rated Supply Voltage(Rated Maximum Voltage)

    2.4 to 6.6 KV (7.2 kV)11 to 13.8 kV

    (15kV)11 to 12 kV(13.8 kV)*

    Operational Current 400 A 400 A 720 A 400 A

    Rated Thermal Current 450 A 450 A 800 A 450 A

    Interrupting Current7000 A @ 5 kV

    (4500 A @ 7.2 kV)7200 A 7200 A

    5000 A @ 12 kV (4000 A

    @ 15 kV)5000A **

    Peak Withstand Current 15.8 kA 20 kA 20 kA 12.5 kA

    Class E1 MVA29/60/54

    (2400 V/5000 V/6900 V)30/62/86

    (2400 V/5000 V/6900 V)30/62/86

    (2400 V/5000 V/6900 V)95/96

    (11 kV/13.8 kV)95

    (11 kV)

    Class E2 MVA200/400/600

    (2400 V/5000 V/6900 V)200/400/600

    (2400 V/5000 V/6900 V)200/400/600

    (2400 V/5000 V/6900 V)953/1195

    (11 kV/13.8 kV)

    Withstand Overload Current2400 A for 30 Seconds 2400 A for 30 Seconds 4320 A for 30 Seconds 2400 A for 30 Seconds

    6000 A for 1 Second 6000 A for 1 Second 10,800 A for 1 Second 8000 A for 1 Second

    Short Circuit Current (E2)50 kA (130 kA Peak)

    See Coordination Below50 kA (130 kA Peak)

    See Coordination Below50 kA (130 kA Peak)

    See Coordination Below50 kA (130 kA Peak)

    See Coordination Below

    Coordination W/Current Limiting Fuses

    Peak Let-Thru 65 kA Max. Peak Let-Thru 77 kA Max. Peak Let-Thru 85 kA Max. Peak let-Thru 36 kA Max.

    Switching Frequency 1200/Hr 300/Hr 1200/Hr 300/Hr 600/Hr 300/Hr 300/Hr 120/Hr

    Mechanical Life 2.5 Million 0.25 Million 2.5 Million 0.25 Million 1 Million 0.20 Million 0.25 Million

    Electrical Life 0.25 Million 0.25 Million 0.20 Million 0.10 Million

    Impulse Withstand 60 kV 75 kV (95 kV)****

    Dielectric Strength 18.2kV, 1 Minute 18.2kV, 1 Minute 18.2kV, 1 Minute 35.75 kV (42 kV)***, 1 Minute

    Pick-up Voltage 85% Hot to 70% Cold AC or DC

    Drop-out Voltage 70% Hot to 60% Cold AC or DC

    Tripping Voltage 60% or Less of Coil Rating DC (Cold)

    Control Voltage

    Standard 120 VAC, 50/60 Hz115 to 240 VAC/ 125 to 250 VDC

    100 to 240 VAC/ 125 to 250 VDC

    Optional ^ 240 VAC/125 VDC/250 VDC - -

    Tripping -24, 32, 48, 125,

    250 VDC-

    24, 32, 48, 125, 250 VDC

    -24, 32, 48, 125,

    250 VDC- 125 VDC

    Control Circuit Burden

    Closing5.4 A Peak @ 120 VAC

    670 VA (AC), 700 W (DC)6 to 7.0 A @ 120 VAC

    840 VA (AC), 875 W (DC)7.2 A Peak @ 120 VAC

    864 VA (AC), 900 W (DC)

    Holding0.12 A Avg. @ 120 VAC85 VA (AC), 85 W (DC)

    0.8 to 1 A @ 120 VAC48 VA

    0.16 A Avg. @ 120 VAC80 VA (AC), 90 W (DC)

    Tripping^^ 4.8 A Peak @125 VDC

    Auxiliary Contact Ratings

    Arrangement 3NO-3NC 2NO-2NC 3NO-3NC 2NO-2NC 3NO-3NC 2NO-2NC 4NO-2NC 2NO-1NC

    Current 10 A (A600)

    Voltage 600 V Maximum, 48 V Minimum

    AC 720 VA (P.F. 0.35)

    DC 60 W (L/R 150 ms)

    Application Conditions

    Altitude w/o Derating

    Lower than 3300 ft (1000 m)

    Ambient -5° to 40°C

    Relative Humidity

    45 to 85%

    Vibration Maximum 20 Hz to 1 G

    Shock Maximum 30 G

    Weight in lbs. (kg) 43 (19.5) 44 (20.0) 44 (19.5) 45 (20.0) 60 (27) 62 (28) 88 (40) 91 (41)

    Notes: * 13.8 kV maximum for capcitor switching (5000 kVAR max. with a 6% series reactor)** The rated inerrupting current was tested at 12 kV*** Special withstand voltage (42 kV for 1 minute) available by request**** 95kV BIL with Station Class Arresters. Consult factory for further details

    SPECIFICATIONS

    Notes:^ Adjustable via switch settings on the electronic drive unit^^ Trip circuit burden applies to all latched type contactors only

  • MV VACUUM CONTACTORS

    © 2018 Toshiba International Corporation • Motors & Drives Division • 13131 West Little York Road • Houston, Texas 77041 USA • Tel +713-466-0277 US 1-800-231-1412 • Rev. 180418

    www.toshiba.com/tic

    MEDIUM VOLTAGE APPLICATIONS

    Model NumberHCV-5HA(L) HCV-7HA(L)

    (400 A)

    CV-10HA(L) (400 A)

    CV-10HB(L) (320 A Continuous,

    230 A Breaking)

    HCV-6KA(L) U (720 A)

    0.8 PF Induction/ Synchronous Motor

    2.2 to 2.5 kV 1750 HP —

    N/A

    2500 HP3 to 3.3 kV 2250 HP — 3000 HP4 to 5 kV 3000 HP — 4500 HP

    6 to 6.6 kV 4500 HP — 6000 HP6.9 to 7.2 kV — 3500 HP —11 to 12 kV — 5500 HP —

    13.8 kV — 7000 HP —

    1.0 PF Synchronous Motor

    2.2 to 2.5 kV 2000 HP —

    N/A

    2500 HP3 to 3.3 kV 2500 HP — 3000 HP4 to 5 kV 3500 HP — 4500 HP

    6 to 6.6 kV 5000 HP — 6000 HP6.9 to 7.2 kV — 4000 HP —11 to 12 kV — 6000 HP —

    13.8 kV — 7500 HP —

    Three-Phase Transformer

    2.2 to 2.5 kV 1500 kVA —

    N/A

    2500 kVA3 to 3.3 kV 2000 kVA — 3500 kVA4 to 5 kV 3000 kVA — 4500 kVA

    6 to 6.6 kV 4000 kVA — 7000 kVA6.9 to 7.2 kV — 3000 kVA —11 to 12 kV — 5500 kVA —

    13.8 kV — 6500 kVA —

    Three-Phase Capacitor

    2.2 to 2.5 kV 1500 kVAR

    N/A

    1500 kVAR 2000 kVAR3 to 3.3 kV 2000 kVAR 2000 kVAR 2000 kVAR4 to 5 kV 2000 kVAR 2000 kVAR 2000 kVAR

    6 to 6.6 kV 2000 kVAR 3000 kVAR 2000 kVAR6.9 to 7.2 kV — 3000 kVAR —10 to 13.8 kV — 5000 kVAR —11 to 12 kV — — —

    13.8 kV — — —

    APPLICABLE INDUSTRIES• Aggregate• Mining• Oil & Gas• Pulp & Paper

    • Steel• Utility/Power Generation• Water/Wastewater

    APPLICABLE APPLICATIONS• Pumps• Conveyors• Transformers

    TOSHIBA MOTORS & DRIVES DIVISION• Adjustable Speed Drives • Motors • Motor Controls