First Draft 3-15-97 VA DESIGN GUIDE AMBULATORY CARE INVASIVE PROCEDURES SUITE CONTENTS - SECTION 3 Section 4 Design Guide Plates and Data Sheets: Operating Rooms Guide Plate Series Plate Number Ambulatory Surgery Operating Room (General & Topical Anesthesia) Functional Plan........................................ 4-1 Enlarged Functional Plan......................... 4-1 Equipment Plan ....................................... 4-1 Utility Plan ............................................... 4-1 Reflected Ceiling ..................................... 4-1 Design Standards .................................... 4-1 Equipment Guide List .............................. 4-1 Ambulatory Surgery Operating Room (Topical Anesthesia) Equipment & Utility Plan .......................... 4-2 Reflected Ceiling ..................................... 4-2 Design Standards .................................... 4-2 Equipment Guide List .............................. 4-2

Upload: motasem-nammora

Post on 31-Dec-2015

46 views

Category:

Documents


2 download

DESCRIPTION

VA guide-2009

TRANSCRIPT

Page 1: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE CONTENTS - SECTION 3

Section 4Design Guide Platesand Data Sheets:Operating Rooms

Guide Plate Series PlateNumber

Ambulatory Surgery Operating Room(General & Topical Anesthesia)

Functional Plan........................................4-1Enlarged Functional Plan.........................4-1Equipment Plan .......................................4-1Utility Plan ...............................................4-1Reflected Ceiling .....................................4-1Design Standards ....................................4-1Equipment Guide List ..............................4-1

Ambulatory Surgery Operating Room(Topical Anesthesia)

Equipment & Utility Plan..........................4-2Reflected Ceiling .....................................4-2Design Standards ....................................4-2Equipment Guide List ..............................4-2

Page 2: VA guide -2009
Page 3: VA guide -2009
Page 4: VA guide -2009
Page 5: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 4-1

Equipment Plan NotesAmbulatory Surgery Operating Room (General & Topical Anesthesia)

Note 1 The surgical light fixtures are (CC) unless the VAMC chooses to select a specific surgical light fixture duringdesign development. If the VAMC chooses the fixtures, they should be either (VV) or (CF). Coordinationinvolving structural support, utility connections, and other details are the responsibility of the designer.

Note 2 Nominal thickness of walls should be shown as 8 inches through design development. This is based uponthe need to accommodate a variety of panel boards, exhaust air ducts, and miscellaneous elements ofconstruction that require a thicker partition than in other areas of a clinic or hospital building. Partitions otherthan the operating room enclosure should be shown nominally as 6 inches through design developmentunless a special requirement dictates otherwise.

Note 3 Inclusion of x-ray shielding, consisting of a lead membrane in the partition, lead lined doors, and leadedglass observation windows, is determined on a project basis. The need for radiation protection is basedupon the degree to which portable x-ray equipment is to be used in each of the operating rooms, andcontinuous occupancy of adjacent spaces. Once it is determined that a lead membrane is required, theexact location of that membrane and details related to it are the designer's responsibility.

Note 4 An automatic door opener is to be provided in the corridor at the doors between the operating room and theperipheral corridor. A tread type of opener is permitted; however, a wall-mounted type of automatic dooropener is preferred.

Note 5 The ceiling mounted utility columns may be one of two types: articulating (as indicated on this guide plateseries), or retractable (telescoping). (See guide plate series Ambulatory Surgery Operating Room for agraphic representation of retractable utility columns used in a 450 square foot operating room.) The VAMCmust decide which type of utility column to use during the design development phase of the project. If achoice is made at this point, the utility columns may be (VV), (CF) or (CC). If the VAMC declines to make atimely decision, then the utility columns will be (CC). Coordination involving structural support, utilityconnections, and other details is the responsibility of the designer.

Note 6 Modular Casework - The VAMC has the option of choosing modular casework in lieu of built-in casework.However, this decision must be made during the design development phase of the project. If modularcasework that is wall mounted is selected by the VAMC, the partitions must be designed to support thecasework. It should be noted that the standard studs found in the master specifications are insufficient tocarry this added weight; therefore, the equipment manufacturer's recommendations for supporting partitionsshould be followed where appropriate.

Note 7 Clocks - For more information regarding clocks in the operating room see MCS, Division 16.

Note 8 See VA Handbook 7610 Chapter 286 of the Equipment Guide List for additional equipment not shown.

Page 6: VA guide -2009
Page 7: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 4-1

Utility Plan NotesAmbulatory Surgery Operating Room (General & Topical Anesthesia)

Note 1 Exhaust Air Grilles - Provide a minimum of two exhaust air grilles in this operating room. If only two grillesare provided, locate them opposite from each other. Where there are more than two exhaust grilles, centerthem on each of the walls of the operating room. The bottom of each exhaust air grille is to be seven inchesabove finished floor. See the HVAC Design Manual for additional information.

Note 2 Electrical Power/Ground Module - Place a separate power/ground module near the center of each wall ofthe operating room. Each power/ground module is to have 3 duplex power receptacles and 1 groundingreceptacles. These power/ground receptacles are to be located 18 inches above finished floor. See theElectrical Design Manual for additional information.

Note 3 Articulating Utility Column - Provide connections on each utility column as delineated in Chapter 286,Equipment Guide List.

Note 4 HVAC Controllers - Provide one of the two following systems for controlling room temperature and humidityin the design of the mechanical system. The first system is indicated on the utility plan .It involves locating athermostat, a humidistat, and a recorder in the operating room. The second system involves temperatureand humidity sensors located in the operating room, with a recorder located remotely. See the HVACDesign Manual for Hospital Projects and MCS, Division 15 for additional information.

Note 5 Video Monitors - The increasing use of fluoroscopy in surgical procedures has increased the need for videomonitors located in the vicinity of the "sterile field". With x-ray film soon to be replaced by digitized imagesdisplayed on a video screen, the use of these monitors in surgery will increase even further. This emergingtechnology is called "PACS" (Picture Archiving and Communications System). The VAMC has a choice tomake regarding these monitors. A set of video monitors can be mounted on a cart, or the set of videomonitors can be mounted on an articulating arm that is suspended from the ceiling. The latter concept isshown on these guideplates. In either case, the A/E is to determine utility requirements for the video systemselected by the VAMC and the VHA program official. These requirements include: power supply;provisions for grounding of the monitors; communications linkage to other areas of the clinic. See ReflectedCeiling Plan Note 9 for a concept that links the Frozen Section area of the clinical laboratory with the videomonitors in each of the operating rooms.

Note 6 Isolated Power Unit - Each of the isolated power units is to serve two adjacent walls. For this reason theunits are to be located near the corners of the room and diagonally opposite from each other. See ElectricalDesign Manual for Hospital Projects, Chapter 11, for more information regarding isolated power.

Note 7 Computer Terminal - Utility requirements for the in-room computer terminal are to be determined by theVAMC based upon the computer system to be used. This information is to be given to the A/E forincorporation into the construction documents. The printer for the in-room computer terminals is to belocated remotely.

Note 8 Laser Panel - It is understood that air cooled lasers are soon to replace water cooled lasers. For thisreason, the future impact of air cooled lasers on the design of the HVAC system must be considered by thedesigner. In spite of this anticipated change, water and drainage should be provided in operating roomswhere existing water cooled lasers are to be continued in use.

Note 9 Zone Valve Box - Provide a separate medical gas zone valve box for each operating room in accordancewith NFPA 99, Chapter 4. Locate this cabinet in the peripheral corridor near the door to the operating roomit serves. See MCS, Division 15 for a description.

Note 10 Nitrogen Control Panel - See NFPA 99, Chapter 4 and MCS, Division 15 for information regarding thispanel.

Page 8: VA guide -2009
Page 9: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 4-1

Reflected Ceiling Plan NotesAmbulatory Surgery Operating Room (General & Topical Anesthesia)

Note 1 Supply Air Outlet - Perforated panel centered over operating table with no obstructions. A/E is to design it.(Do not scale.) This outlet is to provide 30 percent of supply air for the operating room. Air distribution is tobe in a downward vertical direction. See the HVAC Design Manual for Hospital Projects.

Note 2 Supply Air Outlets - Stainless steel multiple slot panel diffusers to be located above the perimeter of the"clean air zone". (See Functional Plan.) A/E is to design them. (Do not scale.) These outlets are toprovide 70 percent of supply air for the operating room. This air is to be discharged in a vertical air streaminclined at an outward angle of fifteen degrees from the center of the room. See the HVAC Design Manualfor Hospital Projects.

Note 3 Mounting Plate for Articulating Utility Column - (Do not scale.) Size of mounting plate varies withmanufacturer. Exact size, type, and location are to be determined by the A/E in coordination with the VAMCand Central Office program officials.

Note 4 Surgical Light Fixture - Note that the location of the mounting plate is not to be placed directly over theoperating table. That zone must be kept unobstructed for the supply air outlet and the plenum serving itabove the ceiling. See the Electrical Design Manual, Chapter 6.

Note 5 Surgical Microscope - If VAMC chooses a ceiling-mounted microscope in lieu of a floor-mountedmicroscope, it must be supported by a fixed mounting plate. A ceiling track-mounted system is not to beused for the microscope due to concerns regarding asepsis. The exact size of the mounting plate dependsupon the microscope selection. (Do not scale the guideplate.) Coordinate details and utilities requirementswith the VAMC.

Note 6 Fluorescent Light Fixtures - General illumination. Only 2 x 4 recessed fixtures are to be used in theoperating room due to the fact that this size of fixture (with 6 lamps - Type D) is required in order to deliverenough ambient illumination while also producing color corrected light in the operating room. The design isnot to include 1 x 4 fluorescent fixtures. For more information see Electrical SD F-27.

Note 7 General Illumination on Emergency Power - 50 percent of the fluorescent light fixtures above the operatingtable are to be provided emergency power with battery backup. The fluorescent fixtures above the head ofthe patient (where the nurse anesthetist administers anesthesia and monitors the patient's vital signs) are tobe provided emergency power. (See CS 800-3.) Since the "head of the table" may be reversed onoccasions when the ceiling-mounted microscope is in use, fluorescent fixtures above both ends of the tableare to be put on emergency power.

Note 8 Mounting Plate for Video Monitors - If the VAMC chooses a suspended video system instead of a cart-mounted system, the mounting plate must be integrated into the ceiling layout. The exact size and locationof this plate must be determined. The equipment shown is similar to that found in a cardiac cath procedureroom; however, the mounting plate for the video monitors is not to be supported on tracks due to asepsisconsiderations.

Note 9 Video Monitors - A proposal to be considered is to provide a fiber-optic connection (enclosed in conduit)from the video monitors in the operating room to the microscope in the frozen section area of the clinicallaboratory. This would permit the surgical team in the operating room to see what the pathologist is talkingabout over the intercom while examining the biopsy specimen. This installation would reduce the need foranatomical pathologist to leave a contaminated area. Also, the surgical team would not have to wait for thepathologist to clean up, gown, and come to the operating suite to examine the tissue specimen.

Note 10 Sprinkler System - Coordinate the location of the sprinklers with other ceiling systems in accordance withMCS, Division 15 and Plumbing Design Manual, Medical Centers.

Note 11 Provide no ceiling tracks for intravenous solutions in the design. This restriction is based upon concerns forasepsis in the operating room.

Page 10: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 4-1

Design StandardsAmbulatory Surgery Operating Room (General & Topical Anesthesia)

ARCHITECTURAL Ceiling: Plaster Ceiling Ht: 2895 mm (9'-6")* Wall Finish: Plaster (SC) Paint Wainscot: -- Base: Welded Seamless Flooring Floor Finish: Welded Seamless Flooring Slab Depr: Notes: Additional 8” accessible space

above ceiling for microscope or 10”- 2”.

SPECIAL EQUIPMENTNone

LIGHTING General: 200 FC, (see Note 1) Special: Surgical Light (see Note 2) Emergency: 50% Gen Fluorescent (see Note 3) Notes: 1. Color improved lamps matching

color temperature of surgical light.2. (1) TYPE 840A, 1500 W3. Battery backup in (4) fixtures.

POWERGeneral: (1) Module each wallSpecial: (2) 7-1/2 KVA 12-Circuit IPUEmergency: Each IPU & X-Ray unit

(1) Film Processor per Suite

COMMUNICATIONSPatient Monitor: YesNurse Call: --Code One: --CCTV: Empty ConduitTelephone: Wall Mounted Hand FreeIntercom: Part of TelephonePub. Addr: Empty ConduitADP: --Radio: Empty Conduit

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 190 C( 68°F) Dry Bulb Temp Heating: 230C(75°F) Minimum % Outside Air: 100 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 55% Relative Humidity/Heating: 50% Minimum Air Changes/Hr.: 15 Occupied

8 Unoccupied Room Pressure: Positive AC Load Lights: 91W/m 2 (8.5W/SF) AC Load Equipment:1 19W/m 2 (11.1W/SF) Number of People: 12 Special Exhaust: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Nitrogen Oxide: Yes Nitrogen: Yes Anesthesia Evac: Yes

Page 11: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 4-1

Ambulatory Surgery Operating Room (General & Topical Anesthesia)

1 CC WINDOW, VIEWING, LEAD GLASS, FOR PATIENTOBSERVATION (PG-18-1, MCS 13091; PG-18-4, SD 24G)

20 CC RECEPTACLE, ELECTRICAL, SIMPLEX, 120 VOLT, 20 AMP,ONE GROUNDING JACK PER MODULE AND FOUR SIMPLEXSTRAIGHT BLADE, HOSPITAL GRADE RECEPTACLES ANDTWO GROUNDING RECEPTACLES IN EACH SURGICALCOLUMN (PG-18-1, MCS 16140; H-18-3, CS 801-3)

4 CC ILLUMINATOR, FILM, X-RAY, RECESSED, 120 VOLT, 20 AMP,356 mm X 432 mm (14" X 17") (INSTALLATION NOT TO BECOMBINED WITH IPU'S OR OTHER ELECTRICAL DEVICES)(PG-18-1, MCS 16510)

AR CC ILLUMINATION, GENERAL, RECESSED, WITH THREE LEVELCONTROL (PG-18-1, MCS 16510)

2 CC COLUMN, TELESCOPING OR ARTICULATING, CEILINGMOUNTED (PG-18-1, MCS 15491)

COLUMN A: LOCATE AT HEAD OF TABLE,1200 mm TO 1800 mm (48" TO72") FROM THE CENTERLINE AND 600 mm TO 1200 mm(24" TO 48") TO THE LEFT OF THE CENTERLINE OF THETABLE

COLUMN B: LOCATE AT THE FOOT OF THE TABLE,1200 mm TO 1800 mm(48" TO 72")FROM THE CENTERLINE AND 600mm TO 1200mm(24” TO 48”) TO THE RIGHT OF THE CENTERLINE OF THETABLE. EACH COLUMN CONTAINS THE FOLLOWING:2 INLETS, VACUUM (PG-18-1, MCS 15491)1 OUTLET, NITROUS OXIDE (PG-18-1, MCS 15491)2 OUTLET, OXYGEN (PG-18-1, MCS 15491)1 OUTLET, MEDICAL AIR (PG-18-1, MCS 15491)1 OUTLET, NITROGEN (PG-18-1, MCS 15491)1 INLET, VACUUM, DEDICATED ANESTHESIA GASEVACUATION (PG-18-1, MCS 15491)1 INLET, MASS SPECTROMETER (BLANK OUTLET)

2 CC ISOLATED POWER UNIT PROVIDES ISOLATED ELECTRICALPOWER, INCLUDES LINE ISOLATION MONITOR, ISOLATIONTRANSFORMER AND CIRCUIT BREAKERS (DETAILSAVAILABLE FROM ELECTRICAL SERVICE)

1 CF LIGHT, MAJOR, SURGICAL WITH VARIABLE INTENSITYCONTROL, SINGLE POINT SUSPENSION, CEILING MOUNTED(LOCATION INSTRUCTIONS AVAILABLE FROM ELECTRICALSERVICE) (PG-18-1, MCS 16515)

AR VV TABLE, OPERATING, MOBILE1 CC CLOCK, ELECTRIC WITH SWEEP SECOND HAND,

RECESSED (PG-18-1, MCS 10360)

SYMBOL QTY AI DESCRIPTION

Page 12: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 4-1

Ambulatory Surgery Operating Room (cont.) (General & Topical Anesthesia)

1 CC CLOCK, ELECTRIC TIME ELAPSED, RECESSED(PG-18-1, MCS 10360)

AR CC OUTLET, ELECTRICAL, 120 VOLT, 20 AMP,RECESSED FOR CLOCK

1 VV X-RAY, MOBILE UNIT, C-ARMAR CC SERVICE, ELECTRICAL, SPECIAL, AS REQUIRED FOR X-RAY

EQUIPMENTAR CC OUTLET BOX, LASER1 CC RECEPTACLE, ELECTRICAL, 208 VOLT, 30 AMP, SINGLE

PHASE, FOR LASERS (PG-18-1, MCS 16140; H-18-3, CS 801-3)AR VV MICROSCOPE, CEILING MOUNTEDAR VV MONITOR, VIDEO

SYMBOL QTY AI DESCRIPTION

Page 13: VA guide -2009
Page 14: VA guide -2009
Page 15: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 4-2

Design StandardsAmbulatory Surgery Operating Room (Topical Anesthesia)

ARCHITECTURAL Ceiling: Gypsum Wall Bd SC Ceiling Ht: 2900 mm (9'-6")* Wall Finish: SC Wainscot: -- Base: Resilient sheet flooring intergral base Floor Finish: Resilient sheet flooring Slab Depr: -- Notes: --

SPECIAL EQUIPMENTNone

LIGHTING General: 100 FC Special: Portable examining light Notes: 1. 600mm x 1200mm (2’x4’)

recessed fluorescent light fixture,acrylic prismatic lens, W/3-F32T8lamps, 4100°K CRI=85 (Minimum)

POWERGeneral: (540 W (receptacles)Special: --Emergency: --

COMMUNICATIONSADP: YesRadio: --Telephone: YesIntercom: --Pub. Addr: Empty Conduit

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C( 78°F) Dry Bulb Temp Heating: 22°C(72°F) Minimum % Outside Air: 100 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: SA + 15% AC Load Lights: -- AC Load Equipment:1 -- Number of People: 3 Special Exhaust: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes

Page 16: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE CARE SUITE GUIDE PLATE 4-2

Ambulatory Surgery Operating Room (Topical Anesthesia)

NOTE: BRACKET, VACUUM BOTTLE SLIDE, (PG-18-1, MCS 15991; PG-18-4, SD 336)

NOTE: INTERCOM, STATION (PG-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM(EMPTY CONDUIT SYSTEM; (PG-18-1, MCS 16111)

NOTE: OUTLET, WALL, MEDICAL AIR(PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: ELECTRICAL RECEPTACLES FOR CRASH CART TO BE ON EMERGENCY POWER.

1 VV BLOOD PRESSURE MONITOR1 VV CABINET, INSTRUMENTS, 900mm x 406mm x 1829mm

(36” x 16” x 72”) WITH GLAZED DOORS, SLOPING TOP1 VV CART, EMERGENCY, “CRASH CART”

APROX. 914mm x 533mm (36” x 21”)1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV ILLUMINATORS, FILM, X-RAY, 120 VOLT, 20 AMP, WALL

MOUNTED (1 BANK OF 3)1 CC PORTABLE EXAM LIGHT, 12O VOLTS, 20 AMPS, W/VARIABLE

INTENSITY CONTROLS APPROX. 455mm DIA. X 1905mm H(18”DIA x 75”H)

AR CF MODULAR CASEWORK1 VV MONITOR, CARDIAC - ON CART (FLOOR UNIT)1 VV MONITOR, EAR OXIMETER

P-418 1 CC LAVATORY, SENSOR CONTROL(PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VV BENCH, SOILED HAMPER2 VV STOOL, STEP, APPROX. 508mm x 406mm (20” x 16”)1 VV TABLE, TREATMENT

SYMBOL QTY AI DESCRIPTION

Page 17: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE CONTENTS - SECTION 5

Section 5Design Guide Platesand Data Sheets:Procedures Rooms

Guide Plate Series Plate Number

Cystoscopy RoomFunctional Plan...........................................5-1Equipment Plan ..........................................5-1Utility Plan ..................................................5-1Reflected Ceiling Plan.................................5-1Design Standards .......................................5-1Equipment Guide List .................................5-1

Special Procedures/Broncoscopy RoomEquipment & Utility Plan .............................5-2Reflected Ceiling Plan.................................5-2Design Standards .......................................5-2Equipment Guide List .................................5-2

EGD/Colonoscopy Procedures RoomEquipment & Utility Plan ............................5-3Reflected Ceiling Plan.................................5-3Design Standards .......................................5-3Equipment Guide List .................................5-3

Proctoscopy/Sygmoidoscopy RoomEquipment & Utility Plan .............................5-4Reflected Ceiling Plan.................................5-4Design Standards .......................................5-4Equipment Guide List .................................5-4

Gastric Motility StudiesEquipment & Utility Plan .............................5-5Reflected Ceiling Plan.................................5-5Design Standards .......................................5-5Equipment Guide List .................................5-5

Page 18: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE CONTENTS - SECTION 5

Section 5Design Guide Platesand Data Sheets:Procedures Rooms

Guide Plate Series Plate Number

Radiographic Film Processing RoomEquipment & Utility Plan .............................5-6Reflected Ceiling Plan.................................5-6Design Standards .......................................5-6Equipment Guide List .................................5-6

Scope Cleaning/Film StorageEquipment & Utility Plan .............................5-7Reflected Ceiling Plan.................................5-7Design Standards .......................................5-7Equipment Guide List .................................5-7

Page 19: VA guide -2009
Page 20: VA guide -2009
Page 21: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 5-1

Equipment Plan NotesCystoscopy RoomNote 1 The surgical light fixtures are to be (CC) unless the VAMC chooses to select a specific surgical light fixture

during the development of construction documents. If the VAMC chooses the fixtures, they may be either(CC), (CF), or (VC). All coordination Involving structural support, utility connections, and other detailsregarding these lights are the responsibility of the A/E.

Note 2 Nominal thickness of walls during design development should be shown as 8 inches thick by the A/E. Thisrequirement is based upon the need to accommodate a variety of panel boards, return air ducts, andmiscellaneous elements of construction that require a thicker partition than in other areas of a hospitalbuilding. Partitions other than the cystoscopy room enclosure should be shown nominally as 6 inches duringdesign development by the A/E unless some special requirement dictates otherwise.

Note 3 Provide x-ray shielding (see SD 24) consisting of a lead membrane in the partitions', lead lined doors; andleaded glass observation windows. The exact location of that membrane and details related to it are theA/E's responsibility.

Note 4 An automatic door opener is to be provided in the corridor at the doors between the cystoscopy room andthe peripheral corridor. A tread type of opener is permitted', however, a wall-mounted type of automatic dooropener with a push-plate Is preferred.

Note 5 The ceiling mounted utility column may be one of two types: articulating, or retractable (telescoping) (asindicated on this guide plate series). (See guideplates series General Operating Room for a graphicrepresentation of an articulating utility column used in a 450 square foot operating room.) The VAMC mustdecide which type of utility column to use during the design development phase of the project. If a choice Ismade at this point, the utility columns may be (W), (CF) or (CC). It the VAMC declines to make a timelydecision, then the utility columns will be (CC). Coordination involving structural support, utility connections,and other details is the responsibility of the designer.

Note 6 Modular Equipment - The VAMC has the option of choosing modular equipment in lieu of built-in casework.However, this decision must be made during the design development phase of the procurement. If wall-mounted modular casework is selected by the VAMC, the A/E must design the partitions to support thecasework. It should be noted that the standard studs found In the master specifications are Insufficient tocarry this added weight-, therefore, the equipment manufacturer's recommendations for supporting partitionsshould be followed where appropriate.

Note 7 Clocks - For more information regarding clocks in operating room, see MCS, Division 16.

Note 8 See Chapter 286 of the Equipment Guide List for additional equipment not shown.

Page 22: VA guide -2009
Page 23: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 5-1

Utility Plan NotesCystoscopy RoomNote 1 Exhaust Air Grilles - Provide a minimum of two exhaust air grilles in this operating room. If only two grilles

are provided, locate them opposite each other. Where there are more than two exhaust grilles, they are tobe centered on each of the walls of the operating room. The bottom of each exhaust air grille is to be seveninches above the finished floor. See the HVAC Design Manual for additional information

Note 2 Electrical Power/Ground Module - A separate power/ground module Is to be placed near the center of eachwall of the operating room. Each power/ground module is to have 3 duplex power receptacles and 1grounding receptacle, These power/ground receptacles are to be located 435mm (18 inches) above thefinished floor. See the Electrical Design Manual.

Note 3 Retractable Utility Column Provide connections on utility column as delineated in Chapter 286, EquipmentGuide List.

Note 4 HVAC Controllers - Provide one of the two following systems for controlling room temperature and humidity,in the design of the mechanical system. The first system is indicated on the utility plan below. It involveslocating a thermostat, a humidistat, and a recorder in the operating room. The second system involvestemperature and humidity sensors located in the operating room with a recorder located remotely. See theHVAC Design Manual for Hospitals and MCS, Division 15 for additional information.

Note 5 Nitrogen Control Panel - For information regarding this panel see NFPA 99, Chapter 4 and MasterSpecifications, Section 15491.

Note 6 Isolated Power Unit - Each of the isolated power units is to serve two adjacent walls. For this reason theunits are to be located near the corners of the room and diagonally opposite from each other. See ElectricalDesign Manual, Chapter 11, for more Information regarding isolated power.

Note 7 Computer terminal - Utility requirements for the in-room computer terminal are to be determined by theVAMC based upon the computer system to be used. This information is to be given to the A/E forincorporation into the construction documents, The printer for the in-room computer terminals is to belocated remotely.

Note 8 Laser Panel - It is understood that air-cooled lasers are soon to replace water cooled lasers. For thisreason, the future impact of air cooled lasers on the design of the HVAC system must be considered by thedesigner. In spite of this anticipated change, it is the policy of the VHA program official that water service isto be provided in any operating rooms where existing water cooled lasers are to be continued in use.

Note 9 Zone Valve Box - A separate zone valve box is to be provided for each operating room (anesthetizinglocation) in accordance with NFPA 99 - Chapter 4. This cabinet is to be located in the peripheral corridornear the door to the operating room it serves. See MCS. Division 15 for a description.

Page 24: VA guide -2009
Page 25: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE GUIDE PLATE 5-1

Reflected Ceiling Plan NotesCystoscopy RoomNote 1 Supply Air Outlet - Perforated panel centered over operating table with no obstructions. A/E Is to design it.

(Do not scale.) This outlet is to provide 30 percent of supply air for the operating room. Air distribution is tobe in a downward vertical direction. See the HVAC Design Manual for Hospital Projects.

Note 2 Supply Air Outlets - Stainless steel multiple slot panel diffusers to be located above the perimeter of the"clean air zone". (See Functional Plan.) A/E is to design them. (Do not scale.) These outlets are to provide70 percent of supply air for the operating room. This air Is to be discharged in a vertical air stream inclinedat an outward angle of fifteen degrees from the center of the room. See the HVAC Design Manual.

Note 3 Mounting Plate for Utility Column - (Do not scale.) Size of mounting plate varies with manufacturer. Exacttype, size, type, and location are to be determined by the A/E in coordination with the VAMC and CentralOffice program officials.

Note 4 Surgical Light Fixture - Note that the location of the mounting plate is not to be placed directly over theoperating table. That zone must be kept unobstructed for the supply air outlet and the plenum serving Itabove the ceiling. See the Electrical Design Manual, Chapter 6.

Note 5 Surgical Microscope - If VAMC chooses a ceiling-mounted microscope In lieu of a floor-mountedmicroscope, it must be supported by a fixed mounting plate. A ceiling track-mounted system is not to beused for the microscope due to concerns regarding asepsis. The exact size of the mounting plate dependsupon the microscope selection . (Do not scale the guideplate.) Coordinate details and utilities requirementswith the VAMC.

Note 6 Fluorescent Light Fixtures - General illumination. Only 2 x 4 recessed fixtures are to be used in theoperating room due to the fact that this size of fixture (with 6 lamps - Type D) is required in order to deliverenough ambient illumination while also producing color corrected light in the operating room. The design isnot to include 1 x 4 fluorescent fixtures. For more Information see Electrical SD F-27.

Note 7 General Illumination on Emergency Power - 50 percent of the fluorescent light fixtures above the operatingtable are to be provided emergency power with battery backup. The fluorescent fixtures above the head ofthe patient (where the nurse anesthetist administers anesthesia and monitors the patient's vital signs) areto be provided emergency power. (See CS 800-3.)

Note 8 Video Monitors (A proposal to be considered by the VAMC and the A/E) - Is to provide a fiber-opticconnection (enclosed in conduit) from the video monitors in the operating room to the microscope in thefrozen section area of the clinical laboratory. This would permit the surgical team in the operating room tosee what the pathologist is talking about over the intercom while examining the biopsy specimen. Thisinstallation would reduce the need for anatomical pathologist to leave a contaminated area. Also, thesurgical team would not have to wait for the pathologist to clean up, gown, and come to the operating suiteto examine the tissue specimen.

Note 9 Sprinkler System - Coordinate the location of the sprinklers with other ceiling systems in accordance withMCS, Division 15 and Plumbing Design Manual, Medical Centers.

Note 10 Provide no ceiling tracks for intravenous solutions in the design. This restriction is based upon concernsfor asepsis in the operating room.

Page 26: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-1

Design StandardsCystoscopy RoomARCHITECTURAL Ceiling: Plaster Ceiling Ht: 2900mm (9'-6")(see note 1) Wall Finish: Plaster Wainscot: -- Base: Welded Seamless Flooring Floor Finish: Welded Seamless Flooring Slab Depr: -- Notes: 1. Additional 8” accessible space

above ceiling for microscope or10’-2”

SPECIAL EQUIPMENTNone

LIGHTING General: 2152lx(200 fc)(see note 1) Special: Surgical Light(see note 2) Emergency: 50% Gen. Fluorescent(see note 3) Notes: 1. Color improved lamps matching

color temperature of surgical light.2. (1) TYPE 840A, 1500 W3. Battery backup in (4) fixtures.

POWERGeneral: (1) Module each wallSpecial: (2) 7-1/2 KVA 12-Circuit IPUEmergency: Each IPU & X-Ray unit

(1) Film Processor per Suite

COMMUNICATIONPatient Monitor: YesNurse Call: --Code One: --CCTV: Empty ConduitTelephone: Wall Mounted Hand FreeIntercom: Part of TelephonePub. Addr: Empty ConduitADP: Empty ConduitRadio: Empty Conduit

HEATING, VENTILATING AND AIRCONDITIONINGDry Bulb Temp Cooling: 190 C( 68°F) Dry Bulb Temp Heating: 230C(75°F) Minimum % Outside Air: 100 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 55% Relative Humidity/Heating: 50% Minimum Air Changes/Hr.: 15 Occupied

8 Unoccupied Room Pressure: Positive AC Load Lights: 91W/m 2 (8.5W/SF) AC Load Equipment:1 19W/m 2 (11.1W/SF) Number of People: 12 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Nitrogen Oxide: Yes Nitrogen: Yes Anesthesia Evac: Yes Notes: --

Page 27: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-1

Cystoscopy Room

1 VC TABLE, UROLOGICAL, RADIOGRAPHIC. MOTOR DRIVEN, WITHX-RAY TUBE SUPPORT

1 CC FLOOR DRAIN, AUTOMATIC FLUSHING TYPE(PG-18-1. MCS 15400. H-18-4. SD 305)

16 cc RECEPTACLE. ELECTRICAL, SIMPLEX, 120 VOLT. 20 AMP.HOSPITAL GRADE TYPE, STRAIGHT BLADE, 1 MODULE OF 3SIMPLEX RECEPTACLES ON EACH WALL WITH ONE GROUNDINGJACK B@DE. ONE MODULE OF THREE SIMPLEX RECEPTACLESON EACH WALL WITH ONE GROUNDING JACK PER MODULE ANDFOUR SIMPLEX STRAIGHT BLADE, HOSPITAL GRADE AND TWOGROUNDING RECEPTACLES IN THE SURGICAL COLUMN(PG-18-1. MCS 16140: H-18-3. CS 801-3)

1 VV RADIOGRAPHIC TUBE AND HIGH VOLTAGE CABLES, 500 MA.SINGLE PHASE

AR CC SERVICES, ELECTRICAL. SPECIAL AS REQUIRED FOR THEABOVE EQUIPMENT

4 CC ILLUMINATOR. FILM. X-RAY. RECESSED, 120 VOLT. 20 AMP.356mm x 432mm (14" x 17-) (INSTALLATION NOT TO BE COMBINEDWITH IPU'S OR OTHER ELECTRICAL DEVICES)(PG-18-1, MCS 16510)

1 CF LIGHT, MAJOR, SURGICAL WITH VARIABLE INTENSITY CONTROL,SINGLE POINT SUSPENSION, CEILING MOUNTED (LOCATIONINSTRUCTIONS AVAIL-ABLE FROM ELECTRICAL SERVICE)(PG-18-1. MCS 16515)

AR CC ILLUMINATION, GENERAL. RECESSED, WITH THREE LEVELCONTROL (PG-18-1. MCS 16510)

1 CC NURSE CALL. EMERGENCY STATION, ACTIVATED BY PUSHBUTTON ON WALL, WITH CORRIDOR SIGNAL LIGHT(PG-18-1, MCS 16761)

1 CC COLUMN, TELESCOPING UTILITY, CEILING MOUNTED (PG-18-1,MCS 15491) LOCATE AT HEAD OF TABLE 48" TO 72" FROM THECENTERLINE AND 24' TO 48' TO THE LEFT OF THE CENTERLINEOF THE TABLE COLUMN CONTAINS THE FOLLOWING:2 INLETS, MEDICAL VACUUM (PG-18-1. MCS 15491)1 OUTLET, NITROUS OXIDE (PG-18-1. MCS 15491)2 OUTLETS, OXYGEN (IT 08-1. MCS 15491)1 OUTLET, MEDICAL AIR (PG-18-1, MCS 15491)1 OUTLET. NITROGEN (PG-18-1, MCS 15491)1 INLET,DEDICATED ANESTHESIA GAS EVACUATION(PG-18-1, MCS 15491)1 INLET,MASS ATOMIC SPECTROMETER (BLANK OUTLET)

SYMBOL QTY AI DESCRIPTION

Page 28: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-1

Cystoscopy Room (cont.)

2 CC ISOLATED POWER UNIT PROVIDES ISOLATED ELECTRICALPOWER, INCLUDES LINE ISOLATION MONITOR, ISOLATIONTRANSFORMER AND CIRCUIT BREAKERS (DETAILS AVAILABLEFROM ELECTRICAL SERVICE)

1 CC CLOCK. ELECTRIC TIME ELAPSED, RECESSED(PG-18-1, MCS 10360)

1 CC CLOCK, ELECTRIC WITH SWEEP SECOND HAND, RECESSED(PG-18-1, MCS 10360)

AR CC OUTLET, ELECTRICAL, 120 VOLT. 20 AMP, RECESSED FORCLOCK

AR VV MONITOR. VIDEOT-14 AR CC CABINET, STORAGE, WITH SLOPING TOP, 2 HINGED PANEL

DOORS, LOCK AND 5 ADJUSTABLE SHELVES. 48”W x 22”D x 84”H(PG-18-1.MCS 12301; H-18-4, SD 70K)

1 VV CRT, COMPUTER SYSTEM, WITH KEYBOARD1 CC RECEPTACLE, ELECTRICAL, QUADRAPLEX. FOR COMPUTER

EQUIPMENT ITEMS (PG-18-1, MCS 16140, H-18-3. CS 866- 1)AR VV KICKBUCKETSAR VV STOOL. SURGICAL1 VV TABLE. SURGICAL INSTRUMENTAR VV CART,CASE1 CC INTERCOM, STATION (PG-18-1, MCS 16760)1 CC OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM)

(PG-18-1, MCS 16111)1 VV UNIT, ELECTROCAUTERY1 VV UNIT. HYPERIHYPOTHERMIA1 VV HAMPER, SOILED LINEN, WITH HINGED SELF CLOSING TOP,

20” DIA.1 VV CART, EMERGENCY,”CRASH CART" APPROX, 36"W X 2 I'D1 VV MACHINE. ANESTHESIA, PORTABLE1 VV CART, ANESTHESIA EQUIPMENT1 VV STAND, IV, MOBILE1 VV MACHINE, SUCTION

SYMBOL QTY AI DESCRIPTION

Page 29: VA guide -2009
Page 30: VA guide -2009
Page 31: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-2

Design StandardsSpecial Procedures / Bronchoscopy RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling Tile Ceiling Ht: 2900mm (9'-6") Wall Finish: Vinyl Wall Covering Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: --Notes: 1. 900mm (3’-0”) wide entry door

with200 mm x 250mm (8” x 10”)tempered glass view window.

SPECIAL EQUIPMENTNone

LIGHTING General: 70 FC Special: -- Notes: 1. 20mm x 1200mm (2’ x 4’)

recessed fluorescent light fixtures,acrylic prismatic lens, W/3-F32T8lamps, 3500°k, CRI+75(minimum)

2. Illumination level controlled bydimmer.

POWER General: 1200 W (receptacles) Emergency: 500 W (receptacles)Notes: 1. Special receptacle for mobile

fluoroscopy unit. (Coordinate withsystem supplier).

2. Receptacle for crash cart to be onemergency power.

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: Yes Pub. Addr: -- Notes: 1. Junction box for CCTV camera

with conduit to adjacent diagnosticroom.

2. Junction box for poly somnographcabling with conduit diagnosticroom.

3. Nurse call system.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Lighting: 86 w/sm (8w/sf) AC Load-Equipment: 22 w/sm (2w/sf) Number of People: 3 Special Exhaust: -- Notes: 1. Room exhaust shall be

accomplished via low level outlets.2. Provide a special hood and

exhaust for instrument cleaningfumes if instrument cleaning isdone here rather than a separateroom.

3. If Bronchoscopy room is used fortuberculosis patient exams min.air changes per hr. increases to12 and provide filtration as per TBCriteria in HVAC Design Manualfor Hospitals Projects.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes:

Page 32: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-2

Special Procedures / Bronchoscopy Room

NOTE: BRACKET, VACUUM BOTTLE SLIDE (PG-18-1, MCS 15491; PG-18-4, SO 336)

NOTE: INTERCOM, STA77ON (PG-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUITSYSTEM (PG-18-1, MCS 16111)

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLE7, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE. OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE.' ELECTRICAL RECEPTACLE FOR CRASH CART TO BE ON EMERGENCYPOWER.

1 VV BLOOD PRESSURE MONITOR3 VV BRONCHOSCOPES1 VV CABINET, INSTRUMENTS, 1219 MM X 406 MM X 1829 MM,

(48" X 16" X 72") WITH GLAZED DOORS, SLOPING TOP1 VV CART, EMERGENCY, "CRASH CART'APPROX.,

914 MM X 533 MM (36" X 21 ")1 VV CART, VIDEO, ENDOSCOPIC1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV ILLUMINATORS, FILM, X-RAY, 120 VOLT, 20 AMP, WALL

MOUNTED (1 BANK OF 4)1 VV LIGHT SOURCE, FIBER-OPTIC, ENDOSCOPIC WI CARTAR CF MODULAR CASEWORK1 VV MONITOR, CARDIAC - ON CART (FLOOR UNIT)1 VV MONITOR, EAR OXIMETER1 VV RECEPTACLE, WASTE, 330 MM (13")

N-2 1 CF SINK, CORROSION RESISTING STEEL, WITH END ORCORNER DRAIN OUTLET, 559 MM X 406 MM X 279 MM(22" X 16" X 11") (PG-1 8-1 & PG-1 8-6, MCS 11 602)

2 VV STOOL, STEP, APPROX., 508 MM X 406 MM (20" X 16")1 VV TABLE, EXAMINATION-PATIENT, X-RAY, TRANSLUCENT TOP1 VV X-RAY/FLUOROSCOPE (MOBILE UNIT & MONITOR)

SYMBOL QTY AI DESCRIPTION

Page 33: VA guide -2009
Page 34: VA guide -2009
Page 35: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-3

Design StandardsEGD / Colonoscopy Procedures RoomARCHITECTURAL Ceiling: Acoustic lay-in Ceiling Tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Paint

Ceramic Tile in Toilet Room Wainscot: -- Base: Resilient sheet flooring w/ integral base Floor Finish: Resilient sheet flooring

Ceramic Tile in Toilet Room Slab Depr: -- Notes: 1. 900mm (3’-0”) wide entry door.

SPECIAL EQUIPMENTNone

LIGHTING General: EGD & Colonoscopy Rm.: 100 FC

Toilet Rm.: 30 FC Special: -- Notes: 1. 50% of lighting on critical power.

2. 600 x 1200 mm (2'x4') recessedfluorescent light fixture, acrylicprismatic lens, W/3-F32T8 lamps,4100°K, CRI=85 (Minimum)

3. 300 x 1200 mm (1'x4') surfacemtd. fluorescent light fixture,acrylic prismatic lens, W/2-F32T8lamps, 4100°K, CRI=85(Minimum)

POWER General: 1000W (receptacles) Emergency: 200W (receptacles) Notes: --

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr -- Notes: 1. Nurse Call

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Negative AC Load Lighting: 30 w/sm (2.8 w/sf) AC Load-Equipment: 54 w/hr (5 w/hr) Number of People: 4 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: -- Notes:

Page 36: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-3

EGD / Colonoscopy Procedures Room

1 CC OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)1 CC OUTLET, WALL, MEDICAL AIR (PG-18-1,MCS 15491;H-18-3, CS 310-1)1 CC OUTLET, WALL, VACUUM (PG-18-1 MCS 15491; H-18-3. CS 310-1)1 CC VACUUM BOTTLE SLIDE (PG-18-1. MCS 3.5491; H-18-4. SD 336)

-OR-

1 CC COLUMN, TELESCOPING UTILITY, CEILING MOUNTED (PG-18-1,MCS 15491) LOCATED AT HEAD OF TABLE 1219mm TO 1829mm(4' TO 6') FROM THE CENTERLINE AND 610mm TO 1219mm(2’ TO 4') TO THE LEFT OF THE OF CENTERLINE OF THE TABLE

COLUMN CONTAINS THE FOLLOWING:

2 INLETS, VACUUM (PG-18-1, MCS 15491)1 OUTLET, NITROUS OXIDE (PG-18-1, MCS 15491)2 OUTLET, OXYGEN (PG-18-1,MCS 15491)1 OUTLET, MEDICAL AIR (PG-18-1, MCS 15491)1 OUTLET, NITROGEN (PG-18-1, MCS 15491)1 INLET, VACUUM, DEDICATED ANESTHESIA GAS

EVACUATION (PG-18-1, MCS 15491)1 INLET, MASS ATOMIC SPECTROMETER (BLANK OUTLET

NOTE: PROVIDE SPACE POR MEDICAL GAS CYLINDERS STRAPPED TO THE WALL-IF NEEDED.

1 VV HAMPER, SOILED LINEN, WITH HINGED SELF CLOSING TOP,508mm (20”) DIA.

AR VV STOOL, SURGICAL6 VV CABINET, GLAZED DOORS, SLOPING TOP,

610mm x 1829mm (24” x 72”)1 CF CABINET,.DRUG STORAGE, DOUBLE LOCKING DOORS, WALL

HUNG WITHOUT BASE, 610mm x 330mm x 762mm (24” x 13” x 30”)3 CC CABINET, WALL ABOVE COUNTER (PG-18-1, MCS 12302)1 CC COUNTER, APPROX. 2750mm (9’-0”) PLASTIC LAMINATE WITH

SINK, 508mm x 457mm x 203mm (20” x 18” x 8”) AND CABINETSUNDERNEATH (PG-18-1, MCS 12302)

1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV PRINTER, COMPUTER SYSTEM1 CC RECEPRACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT ITEMS (PG-18-1, MCS 16140, H-18-3, CS 866-1)1 VV CHAIR, OPERATOR'S, SWIVEL AND ADJUSTABLE HEIGHTS

N-2 1 CF SINK, CORROSION RESISTING STEEL, WITH END OR CORNER DRAINOUTLET, 559mm x 406mm x 279mm (22” x 16” x 11”) (PG-18-1 & PG-18-6,,MCS 11602);

1 VV DISPENSER. SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV RECEPTACLE, WASTE, 330mm (13') DIAMETER2 VV WASTE RECEPTACLE, MOBIL, DRY, 508mm (20”) DIA.1 VV CART, FOR VCR, APPROX., 914mm x 457mm (36” x 18”)

SYMBOL QTY AI DESCRIPTION

Page 37: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-3

EGD / Colonoscopy Procedures Room (cont.)

1 CC INTERCOM, STATION (PG-18-11 MCS 16760)1 VV TABLE, EXAMINATION, STAINLESS STEEL,

610mm x 1524mm (24” x 60”)1 CC TRACK, CURTAIN CUBICLS, CEILING TYPE, SURFACE MOUNTED

(PG-18-1, MCS 10152)1 VV CURTAIN, CUBICL1 VC POWER PEDESTAL1 VC RACK. MOBILE, FOR LIGHTSOURCE AND, ENDOSCOPE

INSTRUMENT1 VV CART, MOBILE, INSTRUMENT, 813mm x 406mm (32” x 16”)2 VV CART, UTILITY, 457mm x 914mm (18” x 36”)1 VV CART, EMERGENCY, “CRASH CART” APPROX.,

914mm x 533 mm (36” x 21”)1 VV CAUTERY DEVICE, ELECTRIC1 VC MONITOR, VISUAL, 610mm (24”) SCREEN MINIMUM, SUSPENDED

FROM THE CEILING1 CC OUTLET, WALL, EVACUATION (PG-18-1,MCS I5491, H-06-3, CS 310-1)1 CC OUTLET, INTERCOM (EMPTY CONTUIT SYSTEM)

(PG-18-1, MCS 16111)1 CC NURSE CALL, PANEL WITH CORRIDOR SIGNAL LIGHT

(PG-18-1,MCS 16761)1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP,

APPROX., 508mm x 1499mm (20” x 59”). 4 IN 11 VV CLOCK. BATTERY OPERATEDAR CC RECEPTACLE. ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: THE FOLLOWING EQUIPMENT WILL BE PROVIDED IN THE PATIENT TOILET AREA.

P-103 2 CC WATER CLOSET, (PG-18-1, MCS 1.5450; El-03-4, SD 4)1 CC BAR, GRAB FOR WATER CLOSET

(PG-18-1, MCS 10800, H-18-4, SD 12, 14B & 14F)1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL

(PG-18-1, MCS 10800; H-18-4, SD 12)P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450)

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 W RECEPTACLE, WASTE, 330mm (13”) DIAMETER

P-701 1 CC SHOWER, BATH FIXTUR, DETACHABLE, WALL MOUNTED,CONCEALED SUPPLIES (PG-18-1, MCS 15450; H-18-4, SD 13 & 382)

1 CC DRAIN, FLOOR (PG-18-1, MCS 15400)1 CC NURSE CALL, PANEL WITH CORRIDOR SIGNAL LIGHT

(PG-18-1, MCS 16761)

NOTE: THE FOLLOWING EQUIPMENT WILL BE PROVIDED IN THE GURNEY STORAGE AREA

AR VV WHEELCHAIR, STANDARDAR VV STRETCHER, APPROX., 762mm x 1981mm (30” X 78”)

SYMBOL QTY AI DESCRIPTION

Page 38: VA guide -2009
Page 39: VA guide -2009
Page 40: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-4

Design StandardsProctoscopy / Sigmoidoscopy RoomARCHITECTURAL Ceiling: Acoustic Lay-In Ceiling Tile

Gyp. Wall Bd. In Toilet Rm. Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint

Ceramic Tile in Toilet Room Wainscot: -- Base: Resilient sheet flooring w/ integral base Floor Finish: Resilient sheet flooring

Ceramic Tile in Toilet Room Slab Depr: -- Notes: 1. 900mm (3’-0”) wide entry door.

SPECIAL EQUIPMENTNone

LIGHTING General: Procto Rm :100 FC

Toilet: 30 FC Special: -- Notes: 1. Lighting control by area;

switch(es) at room entrance.2. 600mm x 1200mm (2' x 4')

recessed fluorescent light fixture,acrylic prismatic lens, W/3-F32T8lamps, 3500°K, CRI=75(minimum)

3. 600mm x 600mm (2' x 2')recessed fluorescent light fixture,acrylic prismatic lens, W/3-FB31lamps, 3500°K, CRI=75(minimum)

POWER General: 1000W (receptacles) Emergency: 200W (receptacles) Notes: 1. Special receptacle for laser

equipment. (Coordinate withsupplier).

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1.Nurse Call

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Negative AC Load Lighting: 30 w/sm (2.8 w/sf) AC Load-Equipment: 54 w/sm (5 w/sf) Number of People: 4 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: -- Notes: 1. Potential cold water is required for

laser equipment. (Coordinate withequipment supplier.)

Page 41: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-4

Proctoscopy/Sigmoidoscopy Room

P-418 1 CC LAVATORY, SENSOR CONTR0L(PG- 18-1) MCS 15450; VOL. 3 SD 380)

1 VV CABINET, INSTRUMENT AND TREATMENT, 36”W x 16"D x 78”HAR VV CART, ENDOSCOPIC1 VV CURTAIN, CUBICLEAR VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL,

1200 mm W x 760 mm D x 760 mm H (48”VV x 30"D x 30"H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV ELECTRO-CAUTERIZING UNIT, MOBILE,

APPROX. 535mmW x 600mmD(21”W x 24"D)1 VV HAMPER, SOILED LINEN, WITH HINGED SELF CLOSING TOP,

500 mm (20") DIA.AR VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR X RAY FILM, 120 VOLTS, 150 WATTS, WALL

MOUNTED, INDIVIDUAL SWITCH FOR TWO, 355 mm x 430 mm(14" x 17") RADIOGRAPHS, 790 mm W x 500 mm H (31'VV X 20"H)

1 VV LASER, CO2, MOBILEAR VV LIGHT, EXAMINING, PORTABLE, 120 VOLTS, 20 AMPS,

APPROX., 455 mm (18") DIAMETER X 75"H1 VV RECEPTACLE, WASTE, STEP ON TYPE,

APPROX. 305 mm (12") DIAMETER1 VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, PROCTOSCOPIC, ADJUSTABLE,HYDRAULICALLY

OPERATED.

SYMBOL QTY AI DESCRIPTION

Page 42: VA guide -2009
Page 43: VA guide -2009
Page 44: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-5

Design StandardsGastric Motility StudiesARCHITECTURAL Ceiling: Acoustic Lay-In Ceiling Tile Ceiling Ht: 2700 MM (9'-0") Wall Finish: Paint

Ceramic Tile in Toilet Room Wainscot: -- Base: Resilient sheet flooring w/ integral base

Ceramic Tile in Toilet Room Floor Finish: Resilient sheet flooring

Ceramic Tile in Toilet Room Slab Depr: -- Notes: 1. 900mm (3’-0”) wide entry door.

SPECIAL EQUIPMENTNone

LIGHTING General: 50 FC (ambient)/100 FC Task Special: -- Notes: 1. Dual-level switching provided

50/10 FC levels.2. 600 X 1200 MM (2'x4') recessed

fluorescent light fixture, acrylicprismatic lens, W/2-F32T8lamps, 3500°K, CRI=75 (Min.).

3. 600mm x 600mm (2' x 2')recessed fluorescent light fixture, acrylic prismatic lens, W/3-FB31 lamps, 3500°K, CRI=75 (minimum)

POWER General: 1400W (receptacles);1000W (dedicated recept./circuit for exam table) Emergency: -- Notes: --

COMMUNICATION ADP: Yes Radio: --Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating : 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Lighting: 19 w/sm (1.8 w/sf) AC Load-Equipment: 65 w/sm (6 w/sf) Number of People: 3 Special Exhaust: Yes Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 45: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-5

Gastric Motility Studies

P-418 1 CC LAVATORY, SENSOR CONTROL(PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VV CABINET, INSTRUMENT AND TREATMENT,910mm W x 405mm D x 1980mm H (36"W x 16"0 x 78"H)

1 VV CART, MEDICATION, W/IV POLEAR VV CART, MOBIL, INSTRUMENT, 910mm x 500mm (36” x 20”)1 VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITHOUTARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL,

1200mm W x 760mm D x 760mm H (48”W x 30"D x 30" H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV HAMPER, SOILED LINEN, V\NTH HINGED SELF CLOSING TOP

500mm (20") DIAMETERAR VV HOOK, CLOTHES, WALL MOUNTED1 VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 WATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,355mm x 430mm (14”x 17') RADIOGRAPHS,790 mm W x 500 mm H (31"W x 20"H)

AR VV LIGHT, EXAMINING, PORTABLE, 120 VOLTS, 20 AMPSAPPROX. 455 mm (1 8") DIAMETER x 1905 mm H (75"H)

1 VV MANOMETER, ESOPHAGEAL, W/ RECORDER1 VV OPHTHALMOSCOPE, WALL HUNG1 VV OTOSCOPE, WALL HUNG1 VV RECEPTACLE, WASTE, STEP-ON TYPE,

APPROX. 305 mm (12") DIAMETER1 VV SPHYGMOMANOMETER, WALL HUNGI VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, INSTRUMENT, DRESSING, CORROSION

RESISTING STEEL, 500 mm W x 910 mm L x 890 mm H(20"W x 36"L x 35"H)

I VV TABLE, EXAMINING AND TREATMENT, MOTORIZED

SYMBOL QTY AI DESCRIPTION

Page 46: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-5

Gastric Motility Studies - Toilet

P-103 1 CC WATER CLOSET, WALL HUNG (PG-18-1, MCS 15450; H-18-4)1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL

(PG-18-1,MCS 10800; H-18-4, SD 12)P-418 1 CC LAVATORY, SENSOR CONTROL

(PG-18-1, MCS 15450;VOL. 3 SD 380)T45 1 CC SHELF, CORROSION RESISTING STEEL, 305mm x 127mm

(1 2" x 5") (PG-18-1, MCS 10360; H-18-4, SD60H)1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED1 VV RECEPTACLE, WASTE, STEP-ON TYPE,

APPROX. 305 mm (12”) DIAMETERAR CC BAR, GRAB FOR WATER CLOSET

(PG-18-1, MCS 10800; H-18-4, SD 12)2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)1 CC MIRROR, WHEELCHAIR, 610 mm W x 910 mm H

(24”W x 36"H) (PG-18-1, MCS 10800; H-18-4, SD 15)

SYMBOL QTY AI DESCRIPTION

Page 47: VA guide -2009
Page 48: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-6

Design StandardsRadiographic Film Processing RoomARCHITECTURAL Ceiling: GWB Ceiling Ht: 2700 MM (9'-0") Wall Finish: Paint (SC) Wainscot: -- Base: Welded Seamless Flooring Floor Finish: Welded Seamless Flooring Slab Depr: -- Notes: --

SPECIAL EQUIPMENTNone

LIGHTING General: 0 -10 FC (incandescent) Special: Safety Light Notes: --

POWER General: 180W Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: --Telephone: -- Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating : 22°C (72°F) Minimum % Outside Air: 100 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 (SA) Room Pressure: Negative AC Load Lighting: None AC Load-Equipment: 81 w/sm (7.5 w/sf) Number of People: 3 Special Exhaust: Yes (see note 1)Notes: 1. 4” round duct for film processor.

Ducts require lead shielding.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Acid Waste: Yes Silver Recovery: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 49: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-6

Radiographic Film Processing Room

1 VC PROCESSOR, FILM. AUTOMATIC, 90 SECOND PROCESSINGCYCLE, THRU WALL

AR VC TANK, REPLENISHER, 25 GAL. CAPACITY AND CURBING, 2 FOREACH PROCESSOR

TOP 616A 1 CF COUNTER TOP. HIGH PRESSURE PLASTIC LAMINATE, ACIDRESISTANT COMPOSITION OVER PLYWOOD OR PARTICLEBOARD CORE. 1-1/4” THICK (PG-18-1 & H-08-6. MCS 11602)

AR VV BENCH, FILM LOADING AND STORAGE BINS1 VV ILLUMINATOR, X-RAY FILM, 120 VOLT. 150 WATTS, WALL

MOUNTED, INDIVIDUAL SWITCH FOR TWO, 14" X 17"RADIOGRAPHS. 31"W x 20"H

1 CC SAFELIGHT, CEILING TYPE, SWITCH ON WALL (H-18-4. SD E-D-3)AR CC DOOR, LIGHTPROOF OR LIGHT LOCK DOOR IF SPECIFIED

(PG-18-1, MCS 11471)1 CC CASSETTE TRANSFER CABINET. THRU WALL

(PG-18-1, MCS 13091; PG-18 4)P-516 1 CC SINK, SINGLE BOWL, SELF RIMMING

1 VV DISPENSER. SOAP. LIQUID, WALL MOUNTED1 VV DISPENSER. BIFOLD PAPER TOWEL, SURFACE MOUNTEDAR CC RECEPTACLE. ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140. H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 50: VA guide -2009
Page 51: VA guide -2009
Page 52: VA guide -2009

First Draft 3-15-97

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-7

Design StandardsScope Cleaning / Clean StorageARCHITECTURAL Ceiling: Acoustical ceiling tile Ceiling Ht: 2700 MM (9'-0") Wall Finish: High build glazed coating Wainscot: -- Base: Welded Seamless Flooring Floor Finish: Welded Seamless Flooring Slab Depr: -- Notes: 1. 900mm (3’-0”) wide entry doors

with tempered glass view window.

SPECIAL EQUIPMENTNone

LIGHTING General: 30 FC Special: -- Notes: 1. 600mm x 1200mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 3500°K,CRI=75 (Min.).

POWER General: 1800W (Receptacles) Emergency: -- Notes: 1. Special receptacle for

endoscopy washer, (coordinatewith supplier)

COMMUNICATION ADP: -- Radio: --Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating : 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: Scope Cleaning: 10

Clean Storage: 4 Room Pressure: Scope Cleaning: Negative

Clean Storage: Positive AC Load Lighting:

Scope Cleaning: 54 w/sm (5 w/sf)Clean Storage: 22 w/sm (2 w/sf)

AC Load-Equipment: Scope Cleaning: 13 w/sm (1.2 w/sf)

Clean Storage: 19 w/sm (1.8 w/sf) Number of People: 2 Special Exhaust: --Notes: 1. Provide counter top exhaust for

scope cleaning room.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: 1. Sink, drain pipe, waste and vent

from the sink located in thescope cleaning room needs tobe chemical resistant type.

Page 53: VA guide -2009

First Draft 3-15-97

Equipment Guide List

VA DESIGN GUIDEAMBULATORY CARE INVASIVE PROCEDURES SUITE PAGE 5-7

Scope Cleaning/Clean Storage

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18.3, CS 310-1)

NOTE:- OUTLE7, WALL VACUUM (PG-18-1, MCS 154 91; H-18-3, CS 310-1)

(A) Scope Cleaning

1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR CF MODULAR CASEWORK1 CF SINK, DOUBLE BOWL, SELF RIMMING, CRS3 VV WASHER, ENDOSCOPE

(B) Clean Scope Storage

AR CF MODULAR CASEWORKAR VV CABINET, ENDOSCOPE STORAGE

SYMBOL QTY AI DESCRIPTION

Page 54: VA guide -2009

FINAL DRAFT- 10/31/95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) CONTENTS - SECTION 3

Section 4Design Guide Platesand Data Sheets:Reception Area

Guide Plate Series Plate Number

Vital Sign StationEquipment & Utility Plan 4-1Reflected Ceiling Plan 4-1Design Standards 4-1Equipment Guide List 4-1

Page 55: VA guide -2009
Page 56: VA guide -2009
Page 57: VA guide -2009

FINAL DRAFT- 10/31/95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 4-1

Design StandardsVital Sign StationARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 50 FC Special: -- Notes: 1. Switching per station

2. 600 mm x 1200 mm (2'x4') recessed fluorescent light fixture, acrylic prismatic lens, with 2-F32T8 lamps 3500°K, CRI=75 (Minimum)

POWER General: 500W (Receptacles) Emergency: -- Notes:

COMMUNICATIONS ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting 17 W/m 2(1.6 W/sf) AC Load Equipment: 35 W/m 2 (3.2W/sf) Number of People: 4 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 58: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListVital Signs Station

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 4-1

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VV CABINET, INSTRUMENTAR VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATEDAR VV CRT, COMPUTER SYSTEM, WITH KEYBOARD1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETERAR VV SPHYGMOMANOMETER, WALL HUNG1 VV TABLE, APPROX. 815 mm W x 815 mm L x 760 mm H

(32"W X 32"L X 30"H)

Page 59: VA guide -2009

FINAL DRAFT- 10/31/95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) CONTENTS - SECTION 5

Section 5Design Guide Platesand Data Sheets:Emergency Care (ER)

Guide Plate Series Plate Number

Nurse/Communication StationEquipment & Utility Plan 5-1Reflected Ceiling Plan 5-1Design Standards 5-1Equipment Guide List 5-1

Life Support UnitEquipment & Utility Plan 5-2Reflected Ceiling Plan 5-2Design Standards 5-2Equipment Guide List 5-2

Observation and Treatment RoomEquipment & Utility Plan 5-3Reflected Ceiling Plan 5-3Design Standards 5-3Equipment Guide List 5-3

Toilet/Bath WheelchairEquipment & Utility Plan 5-4Reflected Ceiling Plan 5-4Design Standards 5-4Equipment Guide List 5-4

Page 60: VA guide -2009
Page 61: VA guide -2009
Page 62: VA guide -2009

FINAL DRAFT- 10/31/95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-1

Design StandardsNurse/Communication StationARCHITECTURAL Ceiling: Acoustic lay-in ceil ing tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint & wallcovering on

gypsum wallboard. Tackboard Wall Surface)

Wainscot: -- Base: Resilient base Floor Finish: Carpet Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC Special: Notes: 1. 600 mm x 600 mm (2'x2')

recessed fluorescent lightfixture, 9-cell parabolicreflector, with 3-FB31 lamps,3500°K, CRI=75 (Minimum)

2. Recessed fluorescent downlightwith 2-13 watt compactfluorescent lamps.

3. Switching is by separate zonesfor downlights, normal andcritical 600 mm x 600 mm(2'x2') lights.

POWER General: 1200W (receptacles) Emergency: 1600W (receptacles) Notes:

COMMUNICATION ADP: Yes Radio: Yes Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1.Nurse Call/Code One/EMS

recorder.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: 0 AC Load Lighting: 31 W/m 2(2.85 W/sf) AC Load-Equipment: 86 W/m 2 (8W/sf) Number of People: 5 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Recommended location for

medical gases zone valve box and local alarm panel.

Page 63: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListNurse/Communication Station

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-1

1 CC COUNTER, BETWEEN RECEPTIONIST’S OFFICE AND WAITING AREA, DRAWERS AND CABINETS UNDERNEATH ON OFFICE SIDE (PG-18-1, MCS 12302)

AR VV DESK, DOUBLE PEDESTAL, APPROX. 1524 mm x 762 mm x 749 mm (60” x 30” x 29-1/2”)

AR VV DESK, RIGHT OR LRFT, SINGLE PEDESTAL, 1524 mm x 762 mm x 749 mm (60” x 30” x 29-1/2”), L UNIT ATTACHMENT AT TYPEWRITER HEIGHT, 1016 mm x 457 mm x 660 mm (40” x 18” x 26”)

AR VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, ROTARY, WITHOUT ARMS1 VV HOOK, COAT, WALL MOUNTEDAR VV CABINET, STORAGE, METAL, 2 DOORS WITH LOCK,

1219 mm x 457 mm x 1981 mm (48” x 18” x 78”)1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV PRINTER, COMPUTER SYSTEM1 CC RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR

COMPUTER EQUIPMENT ITEMS (PG-18-1, MCS 16140;H-18-3, CS 866-1)

1 VV CLOCK, BATTERY OPERATED1 CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT,

20 AMP (PG-18-1, MCS 16140; H-08-3, CS 801-3)1 VV MACHINE, EMBOSSER, 120 VOLT, 20 AMP, TYPE AND

SIZE AS REQUIRED

Page 64: VA guide -2009
Page 65: VA guide -2009
Page 66: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-2

Design StandardsLife Support UnitARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile with

washable finish Ceiling Ht: 2700 mm (9'-0") Wall Finish: Veneer plaster with high-build

glazed coating Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. Provide 1200 mm (4’-0”)

automatic door and operatorwith remote push-plateoperation

SPECIAL EQUIPMENT None

LIGHTING General: Cubicle: 50FC ambient/100 FC task Special: --- Notes: 1. Dual switching for cubicle

lighting to provide 50/100 FClevels. Switches located onPBPU.

2. 600 mm x 1200 mm (2'x4')recessed fluorescent lightfixture, acrylic prismatic lens,W/3-F32T8 lamps, 3500°K,CRI=75 (Minimum)

3. 600 mm x 600 mm (2'x2')recessed fluorescent lightfixture, acrylic prismatic lens,W/2-FB31 lamps, 3500°K,CRI=75 (minimum)

POWER General: 1000W (Non-PBPU receptacles) Emergency: 500W (Crash cart receptacle) Notes:

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1.Nurse Call

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 25 100% Exhaust Air: -- Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 15 W/m 2(1.4 W/sf) AC Load-Equipment: 65 W/m 2 (6W/sf) Number of People: 6 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes:

Page 67: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListLife Support Unit

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-2

T1B 1 CC CABINET, ASSEMBLY, WITH 2 UNDERCOUNTER UNITS TO 1 DRAWER, I HINGED DOOR AND 1 ADJUSTABLE SHELF, SINK CABINENT TO HAVE 2 HINGED DOORS, TOTAL SIZE, 2130 mm W x 555 mm D x 910 mm H (84”W x22”D x 36”H), WALL CABINETS TO BE SLOPING TOP, 2 GLAZED SLIDING DOORS AND 2 ADJUSTABLE SHELVES, COUNTER TOP OF CORROSION RESISTING STEEL WITH INTERGAL SPLASHBACKS AND SINK, 450 mm x 510 mm x 190 mm (18” x 20” x 7-1/2” DEEP) WITH PLASTER TRAP, REMOVEABLE STRAINER AND SWING SPOUT FAUCET(PG-18-1,MCS 12301;PG-18-4P-418 1CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450 VOL. 3 SD 380)

AR CC MIRROR, 400 mm W x 500 mm H (16"W x 20"H), WITH INTREGAL SHELF, OVER LAVATORY (PG-18-1, MCS 10800; PG-18-4, SD15)

2 CC PREFABRICATED BEDSIDE PATIENT UNIT; TYPE 3B (PG-18-1, MCS 16685; PG-18-4, SD E-P-7, 8 & 9)(1) - RECEPTACLE, ELECTRICAL, FOR READING-

EXAM LIGHT, LOCATION OPTIONAL(1) - BRACKET, FOR STEM BASE READING-EXAM

LIGHT(1) - BUMPER, WRAPAROUND, PROTUDING(1) - LIGHT, READING-EXAM, STEM BASE (PG-18-4; SD

E-N-2)AR CC TRACK, CURTAIN, CUBICLE, CEILING TYPE, SURFACE

MOUNTED (PG-18-1, MCS 10800)2 CF BRACKET, MONITOR, WALL MOUNTED1 VV CABINET, INSTRUMENT, SURGICAL. 760 mm W x

405 mm D x 1830 mm H (30”W x 16”D x 72”H)1 VV CART, CARDIAC ARREST SUPPORT1 VV CLOCK, BATTERY OPERATEDAR VV CURTAIN, CUBICLE, 2750 mm x 2280 mm (108” x 90”)

(EACH STATION)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED2 VV MONITOR, PHYSIOLOGICAL, ECG, HRT, BP, OX1 VV MONITOR, DEFIBRILLATOR, MOBILE2 VV STRETCHER, RECOVERY

Page 68: VA guide -2009
Page 69: VA guide -2009
Page 70: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-3

Design StandardsObservation and Treatment RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile with

washable finish Ceiling Ht: 2700 mm (9'-0") Wall Finish: Veneer plaster with high-build

glazed coating Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1: Entrance doors to observation

and treatment area should bedouble doors with remote push-plate door operator.

SPECIAL EQUIPMENT None

LIGHTING General: Cubicle: 50/100 FC Special: -- Notes: 1. Dual-level switching per cubicle

to provide 50/100 FC level;switches located in PBPU;switching of general space byarea.

2. 600 mm x 1200 mm (2'x4')recessed fluorescent lightfixture, acrylic prismatic lens,W/4-F32T8 lamps, 3500°K,CRI=75 (Minimum)

3. 600 mm x 600 mm (2'x2')recessed fluorescent lightfixture, acrylic prismatic lens,W/2-FB31T8 lamps, 3500°K,CRI=75 (Minimum)

POWER General: 300W (non-PBPU receptacles) Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr -- Notes: 1. Nurse Call

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 25 100% Exhaust Air: -- Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 19 W/m 2 (1.8 W/sf) AC Load-Equipment: 65 W/m 2 (6W/sf) Number of People: 2 per Patient Bed Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes:

Page 71: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListObservation and Treatment Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-3

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

AR CC MIRROR, 400 mm W x 500 mm H (16"W x 20"H), WITH INTREGAL SHELF, OVER LAVATORY (PG-18-1, MCS 10800; PG-18-4, SD15)

AR CC PREFABRICATED BEDSIDE PATIENT UNIT; TYPE 1 (PG-18-1, MCS 16685; PG-18-4, SD E-P-1, 3 & 6)

AR CC TRACK, CURTAIN, CUBICLE, CEILING TYPE, SURFACE MOUNTED (PG-18-1, MCS 10800)

AR CF BRACKET, MONITOR, WALL MOUNTEDAR CF MODULAR CASEWORK, W/ OVERHEAD CABINENTS

AND WALL HANGER STRIPAR VV CART - “L”, W/ C -LOCKER1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, W/ KEYBOARD1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV LIGHT, EXAMINING, PORTABLE, 12 VOLTS, 20 AMPSAR VV MONITOR, PHYSIOLOGICAL, ECG, HRT, BP, OX1 VV RECEPTACLE, WASTE, STEP-ON TYPE, APPROX.

305 mm (12”) DIAMETER1 VV STRETCHER, RECOVERY

Page 72: VA guide -2009
Page 73: VA guide -2009
Page 74: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-4

Design StandardsToilet/Bath WheelchairARCHITECTURAL Ceiling: Gypsum Wallboard, paint Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: Ceramic Tile Base: Ceramic tile Floor Finish: Ceramic tile Slab Depr: 75 mm (3") depression to allow

entire floor area to slope todrain

Notes: 1. 1120 mm (3'-8") wide door

SPECIAL EQUIPMENT None

LIGHTING General: 30 FC Special: -- Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 3500°K,CRI=75 (Minimum), UL listedfor wet locations.

POWER General: -- Emergency: -- Notes:

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes: 1. Nurse Call

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: -- Relative Humidity/Heating: -- Minimum Air Changes/Hr.: 10 ac/hr exhaust Room Pressure: Negative AC Load Lighting: 15 W/m2 (1.4 Wsf) AC Load-Equipment: --- Number of People: 1 Special Exhaust: -- Notes:PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 75: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListToilet/Bath Wheelchair

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 5-4

AR CC BAR, GRAB FOR WATER CLOSET (PG-18-1, MCS 10800; PG-18-4, SD 12)

1 CC DISPENSER, PAPER TOWEL AND DISPOSAL COMBINATION UNITS (PG-18-1, MCS 10800

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL PG-18-1, MCS 10800; PG-18-4, SD 12)

2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450;

VOL. 3 SD 380)1 CC MIRROR, WHEELCHAIR, 610 mm W x 910 mm H (24"W X

36"H) (PG-18-1, MCS 10800; PG-18-4, SD 15)1 CC NURSE CALL, EMERGENCY STATION WITH CORRIDOR

SIGNAL LIGHT CONNECTED TO NEAREST NURSE CONTROL STATION (PG-18-1, MCS 16761)

P-103 1 CC WATER CLOSET, WALL HUNG (PG-18-1, MCS 15450 PG-18-4)1 VV DISPENSER, SOAP, LIQUID, WALL HUNG

P-703 1 CC SHOWER1 VV RECEPTACLE, WASTE, STEP-ON TYPE, APPROX.

305 mm (12”) DIAMETER

Page 76: VA guide -2009

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) CONTENTS - SECTION 6

Section 6Design Guide Platesand Data Sheets:Examination/ TreatmentModule(s)Guide Plate Series Plate Number

Multipurpose Examination RoomEquipment & Utility Plan 6-1Reflected Ceiling Plan 6-1Design Standards 6-1Equipment Guide List 6-1

ENT Examination RoomEquipment & Utility Plan 6-2Reflected Ceiling Plan 6-2Design Standards 6-2Equipment Guide List 6-2

Women's Health/GYN Examination RoomEquipment & Utility Plan 6-3Reflected Ceiling Plan 6-3Design Standards 6-3Equipment Guide List 6-3

MAS Reception/Control UnitEquipment & Utility Plan 6-4Reflected Ceiling Plan 6-4Design Standards 6-4Equipment Guide List 6-4

Medication RoomEquipment & Utility Plan 6-5Reflected Ceiling Plan 6-5Design Standards 6-5Equipment Guide List 6-5

Intake/Exit Interview RoomEquipment & Utility Plan 6-6Reflected Ceiling Plan 6-6Design Standards 6-6Equipment Guide List 6-6

Page 77: VA guide -2009

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) CONTENTS - SECTION 6 cont.

Section 6Design Guide Platesand Data Sheets:Examination/ TreatmentModule(s) - Cont’d.Guide Plate Series Plate Number

Gastroenterology (GI) Procedure/ Treatment RmEquipment & Utility Plan 6-7Reflected Ceiling Plan 6-7Design Standards 6-7Equipment Guide List 6-7

Screening Proctoscopy/Sigmoidoscopy RoomEquipment & Utility Plan 6-8Reflected Ceiling Plan 6-8Design Standards 6-8Equipment Guide List 6-8

Gastric (Esophageal) Motility Procedure RoomEquipment & Utility Plan 6-9Reflected Ceiling Plan 6-9Design Standards 6-9Equipment Guide List 6-9

Dermatology Procedure/Treatment RoomEquipment & Utility Plan 6-10Reflected Ceiling Plan 6-10Design Standards 6-10Equipment Guide List 6-10

Dermatology Medication Preparation Storage RmEquipment & Utility Plan 6-11Reflected Ceiling Plan 6-11Design Standards 6-11Equipment Guide List 6-11

Page 78: VA guide -2009

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) CONTENTS - SECTION 6 cont.

Section 6Design Guide Platesand Data Sheets:Examination/ TreatmentModule(s) - Cont’d.Guide Plate Series Plate Number

Phototherapy Treatment RoomPhototherapy Shower Room

Equipment & Utility Plan 6-12Reflected Ceiling Plan 6-12Design Standards 6-12Equipment Guide List 6-12Equipment Guide List 6-12

Orthopedic Clinic / Cast roomEquipment & Utility Plan 6-13Reflected Ceiling Plan 6-13Design Standards 6-13Equipment Guide List 6-13

Chemotherapy Treatment RoomEquipment & Utility Plan 6-14Reflected Ceiling Plan 6-14Design Standards 6-14Equipment Guide List 6-14

Chemotherapy Agent Preparation RoomEquipment & Utility Plan 6-15Reflected Ceiling Plan 6-15Design Standards 6-15Equipment Guide List 6-15

Aerosolized Pentamidine Procedure RoomEquipment & Utility Plan 6-16Reflected Ceiling Plan 6-16Design Standards 6-16Equipment Guide List 6-16

Page 79: VA guide -2009
Page 80: VA guide -2009
Page 81: VA guide -2009

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-1

Design StandardsMultipurpose Examination Room

ARCHITECTURAL Ceiling: Gypsum wallboard lay-in ceiling

panels Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. Provide STC partitions and

doors2. 900 mm (3'-0") wide door

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC ambient/100 FC task Special: -- Notes: 1. Dual-level switching provided

50/10 FC levels. 2. 600 mm X 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/4-F32T8 lamps, 3500°K,CRI=75 (Minimum)

POWER General: 1000W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating : 22°C (72°F) Minimum % Outside Air: 25 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 30 W/m 2(2.8 W/sf) AC Load-Equipment: 65 W/m 2 (6W/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 82: VA guide -2009

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListMultipurpose Exam Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-1

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

T45 1 CC SHELF, CORROSION RESISTING STEEL,305 mm W x 125 mm D (12"W X 5"D) (H-08-1, MCS 10360; PG-18-4,SD 60H)

1 VV CABINET, INSTRUMENT AND TREATMENT,760 mm W x 400 mm D x 1980 mm H (30"W X 16"D X78"H)

2 VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL, 1220 mm W x 760 mm D x

760 mm H (48"W X 30"D X 30"H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED2 VV HOOK, COAT, WALL MOUNTEDAR VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 WATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,355 mm x 420 mm (14" X 17") RADIOGRAPHS,790 mm W x 500 mm H (31"W X 20"H)

1 VV OTOSCOPE / OPHTHALMOSCOPE, WALL HUNG1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETERAR VV SCALE, PERSON WEIGHING, PLATFORM TYPE,

255 mm W x 330 mm L (10"W X 13"L),226.8 kg (500 LB.) CAPACITY WITH HEIGHT INDICATOR

1 VV SPHYGMOMANOMETER, WALL HUNG1 VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, EXAMINING, PADDED, ADJUSTABLE TOP,

APPROX. 1830 mm W x 535 mm D x 760 mm H (74"W X 21"D X 30"H)

SYMBOL QTY AI DESCRIPTION

Page 83: VA guide -2009
Page 84: VA guide -2009
Page 85: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-2

Design StandardsENT Examination RoomARCHITECTURAL Ceiling: Gypsum wallboard lay-in ceiling

panels Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. Provide STC partitions and door

2. 900 mm (3'-0") wide door

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC ambient/100 FC task Special: -- Notes: 1. Dual-level switching provides

50/100 FC levels.2. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/4-F32T8 lamps, 4100°K,CRI=85 (Minimum)

POWER General: 800W (receptacles); 1000W

(dedicated circuit for ENT chair).

Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting 30 W/m2 (2.8 W/sf) AC Load-Equipment: 65 W/m2 (6 W/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 86: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListENT Exam Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-2

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

T45 1 CC SHELF, CORROSION RESISTING STEEL,300 mm W x 125 mm D (12"W X 5"D) (PG-18-1, MCS 10360; PG-18-4,SD 60H)

1 VV BULLETIN BOARD,1200 mm W x 910 mm H (48"W X 36"H)1 VV CABINET, INSTRUMENT AND TREATMENT, 910 mm W x

405 mm D x 1950 mm H (36"W X 16"D X 78"H)1 VV CART, TREATMENT, ENT1 VV CHAIR, EXAMINING, SURGICAL, 120 VOLTS, 20 AMPS1 VV CHAIR, ROTARY, WITH ARMS1 VV CHAIR, STRAIGHT, WITH-OUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL, 1200 MM w x 760 mm D

760 mm H (48"W X 30"D X 30"H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED2 VV HOOK, COAT, WALL MOUNTED1 VV OTOSCOPE / OPHTHALMOSCOPE, WALL HUNG1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER1 VV STOOL, EXAMINING, ADJUSTABLE1 VV SCALE, PERSON WEIGHTING, PLATFORM TYPE,

255 mm W x 300 mm L (10” x 13”);226.8 kg (500lb) CAPACITY WITH HEIGHT INDICATOR

Page 87: VA guide -2009
Page 88: VA guide -2009
Page 89: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-3

Design StandardsWomen's Health GYN Examination RoomARCHITECTURAL Ceiling: Gypsum wallboard in toilet; lay-

in panels in exam room Ceiling Ht 2700 mm (9'-0") Wall Finish: Paint (Ceramic tile in toilet rm) Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. Provide STC 40 for partitions

and door2. 900 mm (3'-0") wide door

SPECIAL EQUIPMENT None

LIGHTING General: Exam Room: 50 FC

Toilet: 30 FC Special: -- Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/3-F32T8 lamps, 4100°K,CRI=85 (Minimum)

POWER General: 1400W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 15% 100% Exhaust Air: Toilet room only Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: Exam room is 0 Toilet is negativeAC Load Lighting: 15 W/m 2(1.4 W/sf) AC Load-Equipment: Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 90: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListWomen's Health / Gyn Exam Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-3

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

T45 1 CC SHELF, CORROSION RESISTING STEEL, 305 mm W x 125 mm D (12"W X 5"D)(PG-18-1, MCS 10360; PG-18-4,SD 60H)

1 CC TRACK, CURTAIN, CUBICLE, CEILING TYPE, SURFACE MOUNTED (PG-18-1, MCS 10152)

1 VV CABINET, INSTRUMENT AND TREATMENT,910 mm W x 405 mm D x 1980 mm H (36"W X 16"D X78"H)

1 VV CHAIR, ROTARY, WITH ARMS1 VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL, 1200 mm W x 760 mm D x

760 mm H (48"W X 30"D X 30"H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED2 VV HOOK, COAT, WALL MOUNTEDAR VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 WATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,355 mm x 430 mm (14" X 17") RADIOGRAPHS,790 mmW x 500 mm H (31"W X 20"H)

AR VV LIGHT, EXAMINING, PORTABLE, 120 VOLTS, 20 AMPS, APPROX., 455 mm DIAMETER x 1905 H(18" DIAMETER x 75"H)

1 VV OTOSCOPE / OPHTHALMOSCOPE, WALL HUNG1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER1 VV SPHYGMOMANOMETER, WALL HUNG1 VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, EXAMINING AND TREATMENT, MOTORIZED

Page 91: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListWomen's Health / Gyn Exam Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-3

P-103 1 CC WATER CLOSET, WALL HUNG (PG-18-1; PG-18-4)1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-18-1,

MCS 10800; PG-18-4, SD 12)P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450;

VOL. 3 SD 380)T45 1 CC SHELF, CORROSION RESISTING STEEL,

305 mm x 127 mm (12” x 5”) (PG-18-1, MCS 10360; PG-18-4, SD 60H)

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTEDAR VV DISPENSER, SANITARY NAPKINAR VV DISPOSAL, SANITARY NAPKIN1 VV RECEPTACLE, WASTE, STEP-ON TYPE, APPROX. 305

mm (12”) DIAMETER.AR CC BAR, GRAB FOR WATER CLOSET (PG-18-1, MCS 10800,

PG-18-4, SD 12)2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)1 CC MIRROR, WHEELCHAIR, 600 mm W x 910 mm H

(42” W x 36” H) (PG-18-1, MCS 10800, PG-18-4, SD 15)

Page 92: VA guide -2009
Page 93: VA guide -2009
Page 94: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-4

Design StandardsMAS Reception/Control UnitARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Vinyl fabric wall covering Wainscot: -- Base: Resilient base Floor Finish: Carpet Slab Depr: -- Notes: 1. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC Special: -- Notes: 1. Lighting control by area;

switches at room entries. 2. 600 mm x 1200 mm (2'x4')

recessed fluorescent light fixture, 8-cell parabolic louver, W/2-F32T8 lamps, 3500°K, CRI=75 (Minimum)

POWER General: 1000W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 30 W/m 2 (2.8 W/sf) AC Load-Equipment: 65 W/m 2 (6 W/sf) Number of People: 6 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 95: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListMAS Reception / Contol Unit

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-4

1 CC COUNTER, BETWEEN RECEPTIONIST'S OFFICE AND WAITING AREA, DRAWERS AND CABINETS UNDERNEATH ON OFFICE SIDE (PG-18-1, MCS 12302;

PG-18-4, SD 72K)AR VV CHAIR, ROTARY, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATEDAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD3 VV HOOK, COAT, WALL MOUNTED1 VV MACHINE, EMBOSSER, 120 VOLTS, 20 AMPS, TYPE

AND SIZE AS REQUIRED1 VV PRINTER, COMPUTER SYSTEMAR VV SHELVING, METAL, FREESTANDING

Page 96: VA guide -2009
Page 97: VA guide -2009
Page 98: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-5

Design StandardsMedication RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. 900 mm (3'-0") wide doors

SPECIAL EQUIPMENT None

LIGHTING General: 100 FC (ambient) Special: 50% of lights on critical power. Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent light fixture, acrylic prismatic lens, W/3-F32T8 lamps, 3500°K, CRI=75 (Minimum)

POWER General: 600W (receptacles) Emergency: -- Notes: 1.Junction box for 120V power

connection to T18C medication cabinet for alarm indication.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 78°F (25°C) Dry Bulb Temp Heating: 72°F (22°C) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 27 W/m 2 (2.6 W/sf) AC Load-Equipment: 32 W/m 2 (3 W/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 99: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListMedication Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-5

T18C 1 CC CABINET, MEDICATION, NURSES, CONSISTING OF BASE WITH BUILT-IN REFRIGERATOR STORAGE CABINET, COUNTER TOP WITH SINK, CABINETS WITH METAL DOORS OR ROLL-UP SHUTTER DOOR OVER NARCOTICS VAULT WITH SIGNAL LIGHT AND LIGHT OVER COUNTER, 635 mm D x 1220 mm L x 2050 mm H (25" D x 48” L x 80"H) (PG-18-1, MCS 12336; PG-18-4, SD 70P)

P-41B 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD380)

AR CF MODULAR CASEWORK, W/ OVERHEAD CABINETS AND WALL HANGER STRIPS

AR VV CART, MEDICATION APPROX. 555 mm W x 840 mm L x 1120 mm H (22"W X 33"L X 44"H)

1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED.

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER

Page 100: VA guide -2009
Page 101: VA guide -2009
Page 102: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-6

Design StandardsIntake/Exit Interview RoomARCHITECTURAL Ceiling: Gypsum wallboard lay-in ceiling

panel Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile or carpet Slab Depr: -- Notes: 1. Provide STC 40 partitions and

door.2. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC (Ambient) Special: -- Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 3500°K,CRI=75 (Minimum)

POWER General: 1000W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 15 W/m 2(1.4 W/sf) AC Load-Equipment: 65 W/m2 (6 W/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 103: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListIntake / Exit Interview

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-6

1 VV BOOKCASE, SECTIONAL (EACH SECTION, 840 mm W x 330 mm D x 380 mm H (33"W x 13"D x 15"H)) WITH255 mm (10") H BASE

1 VV CABINET, INSTRUMENT1 VV CHAIR, ROTARY, WITH ARMS2 VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV CRT, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, DOUBLE PEDESTAL, APPROX., 1525 mm W x

760 mm D x 710 mm H (60"W X 30"D X 29-1/2"H)1 VV SPHYGMOMANOMETER, WALL HUNG

Page 104: VA guide -2009
Page 105: VA guide -2009
Page 106: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-7

Design StandardsGastroenterology Procedure Treatment RoomARCHITECTURAL Ceiling: Gypsum wallboard lay-in ceiling

panel Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient sheet flooring integral

base Floor Finish: Resilient sheet flooring Slab Depr: -- Notes: 1. Provide STC 40 partitions and

door2. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC ambient/100 FC task Special: -- Notes: 1. 50% of lights on critical power

2. 600 mm x 1200 mm (2'x4')recessed fluorescent lightfixture, acrylic prismatic lens,W/4-F32T8 lamps, 3500°K,CRI=75 (Minimum)

POWER General: 1. 800W (receptacles) 2.1000W (dedicated circuit for

exam table. Emergency: 400W (receptacles) Notes: --

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Nurse call

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Lighting: 19 W/m 2 (1.8 W/sf) AC Load-Equipment: 65 W/m 2 (6W/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 107: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListGastroenterology Procedure Treatment Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-7

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VV CABINET, INSTRUMENT AND TREATMENT, 910 mm W x 405 mm D x 1980 mm H (36"W X 16"D X 78"H)

AR VV CART, MOBILE, INSTRUMENT,910 mm x 500 mm (36" X 20")

1 VV CHAIR, ROTARY, WITH ARMS1 VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL, 1200 mm W x 760 mm D x

760 mm H (48"W X 30"D X 30"H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HAMPER, SOILED LINEN, WITH HINGED SELF CLOSING

TOP, 500 mm (20") DIAMETERAR VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 WATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,355 mm x 430 mm (14" X 17") RADIOGRAPHS,790 mm W x 500 mm H (31"W X 20"H)

AR VV LIGHT, EXAMINING, PORTABLE, 120 VOLTS, 20 AMPS, APPROX., 455 mm (18") DIAMETER X 1905 mm (75"H)

1 VV OTOSCOPE / OPHTHALMOSCOPE, WALL HUNG1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER1 VV SPHYGMOMANOMETER, WALL HUNG1 VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, INSTRUMENT, DRESSING, CORROSION

RESISTING STEEL, 500 mm W x 910 mm L x 860 mm H (20"W X 36"L X 35"H)

1 VV TABLE, EXAMING AND TREATMENT, MOTORIZED

Page 108: VA guide -2009
Page 109: VA guide -2009
Page 110: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-8

Design StandardsScreening Proctoscopy/ Sigmoidoscopy RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile

Gyp Wall Bd in Toilet Rm. Ceiling Ht: 2700 MM (9'-0") Wall Finish: Paint

Ceramic Tile in Toilet Rm. Wainscot: -- Base: Resilient sheet flooring integral

base Floor Finish: Resilient sheet flooring

Ceramic Tile in Toilet Rm. Slab Depr: -- Notes: 1. 1200 MM (4'-0") wide doors.

SPECIAL EQUIPMENT None

LIGHTING General: Procto Rm:100 FC

Toilet: 30 FC Special: -- Notes: 1. 50% of lighting on critical

power.2. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/3-F32T8 lamps, 3500°K,CRI=75 (Minimum)

3. 600 mm x 600 mm (2'x2')recessed fluorescent lightfixture, acrylic prismatic lens,W/2-FB31 lamps, 3500°K,CRI=75 (minimum).

POWER General: 1000W (receptacles) Emergency: 200W (receptacle) Notes: 1. Special receptacle for laser

equipment. (Coordinate withsupplier.)

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Nurse call

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Negative AC Load Lighting: 30 W/m 2(2.8 W/sf) AC Load-Equipment: 54 W/m 2 (5W/sf) Number of People: 4 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: -- Notes: 1. Potential cold water is required

for laser equipment. (Coordi-nate with equipment supplier.)

Page 111: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListScreening Proctoscopy / Sigmoidoscopy Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-8

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VV CABINET, INSTRUMENT AND TREATMENT, 36"W X 16"D X 78"H

AR VV CART, ENDOSCOPIC1 VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL, 1200 mm W x 760 mm D x

760 mm H (48"W x 30"D x 30"H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV ELECTRO-CAUTERIZING UNIT, MOBILE, APPROX.

535 mm W x 600 mm D (21"W x 24"D)1 VV HAMPER, SOILED LINEN, WITH HINGED SELF CLOSING

TOP, 500 mm (20") DIA.AR VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 W ATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,355 mm x 430 mm (14" x 17") RADIOGRAPHS, 790 mm W x 500 mm H (31"W X 20"H)

1 VV LASER, CO2, MOBILEAR VV LIGHT, EXAMINING, PORTABLE, 120 VOLTS, 20 AMPS,

APPROX., 455 mm (18") DIAMETER X 75"H1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER1 VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, PROCTOSCOPIC, ADJUSTABLE,

HYDRAULICALLY OPERATED.

Page 112: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListScreening Proctoscopy / Sigmoidoscopy Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-8

P-103 1 CC WATER CLOSET, WALL HUNG (H-08-1, MCS 15450;H-08-4)

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL (H-08-1, MCS 10800; H-08-4, SD 12)

P-418 1 CC LAVATORY, SENSOR CONTROL (H-08-1, MCS 15450; VOL. 3 SD 380)

T-45 1 CC SHELF, CORROSION RESISTING STEEL, 305 mm x 127 mm (12” x 5”) (H-0801, MCS 10360; H-08-4,SD 60H)

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED1 VV RECEPTACLE, WASTE, STEP-ON TYPE, APPROX.

305 mm (12”) DIAMETERAR CC BAR, GRAB FOR WATER CLOSET (H-081, MCS 10800;

H-08-4, SD12)2 CC HOOK, CLOTHES (H-08-1, MCS 10800)1 CC MIRROR, WHEELCHAIR, 600 mm W x 910 mm H (24” W x

36” H) (H-08-1, MCS 10800; H-08-4, SD15)

Page 113: VA guide -2009
Page 114: VA guide -2009
Page 115: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-9

Design StandardsGastric (Esophageal) Motility Procedure RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint

Ceramic Tile in Toilet Rm. Wainscot: -- Base: Resilient sheet flooring integral

base/Ceramic Tile in Toilet Rm. Floor Finish: Resilient sheet flooring

Ceramic Tile in Toilet Rm. Slab Depr: -- Notes: 1. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC ambient/100 FC task Special: -- Notes: 1. Dual-switching provides 50/100

FC levels.2. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/3-F32T8 lamps, 3500°K,CRI=75 (minimum).

3. 600 mm x 600 mm (2’x2’)recessed fluorescent lightfixture, acrylic prismatic lens,W/2-FB31 lamps, 3500 ° KCRI=75 (minimum)

POWER General: 1400W (receptacles); 1000W

(dedicated recept./circuit forexam table).

Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes

HEATING VENTILATING & AIR CONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Lighting: 19 W/m 2(1.8 W/sf) AC Load-Equipment: 65 W/m 2 (6 W/sf) Number of People: 3 Special Exhaust: Yes Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 116: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListGastric (Esophegeal) Motility Procedure Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-9

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VV CABINET, INSTRUMENT AND TREATMENT, 910 mm W x 405 mm D x 1980 mm H (36”W x 16”D x 78”H)

1 VV CART, MEDICATION, W/IV POLEAR VV CART, MOBIL, INSTRUMENT, 910 MM X 500 MM

(36” X 20”)1 VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV DESK, SINGLE PEDESTAL, 1200 mm W x 760 mm D x

760 mm H (48”W x 30”D x 30” H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV HAMPER, SOILED LINEN, WITH HINGED SELF CLOSING

TOP 500 mm (20”) DIAMETERAR VV HOOK, CLOTHES, WALL MOUNTED1 VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 WATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,355 mm x 430 mm (14” x 17”) RADIOGRAPHS, 790 mm W x 500 mm H (31”W x 20”H)

AR VV LIGHT, EXAMINING, PORTABLE, 120 VOLTS, 20 AMPSAPPROX. 455 mm (18”) DIAMETER x 1905 mm H (75”H)

1 VV MANOMETER, ESOPHAGEAL, W/ RECORDER1 VV OPHTHALMOSCOPE, WALL HUNG1 VV OTOSCOPE, WALL HUNG1 VV RECEPTACLE, WASTE, STEP-ON TYPE, APPROX.

305 mm (12”) DIAMETER1 VV SPHYGMOMANOMETER, WALL HUNG1 VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, INSTRUMENT, DRESSING, SORROSION

RESISTING STEEL, 500 mm W x 910 mm L x 890 mm H (20”W x 36”L x 35”H)

1 VV TABLE, EXAMINING AND TREATMENT, MOTORIZED.

Page 117: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListGastric (Esophegeal) Motility Procedure Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-9

P-103 1 CC WATER CLOSET, WALL HUNG (PG-18-1, MCS 15450;H-08-4)

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-18-1, MCS 10800; PG-18-4)

P-418 1 CC LAVATORY, SENSOR CONTROL (HPG-18-1, MCS 15450; VOL. 3 SD 380)

T45 1 CC SHELF, CORROSION RESISTING STEEL, 305mm x 127mm (12” x 5”) (H-08-1, MCS 10360; PG-18-4, SD 60H)

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED1 VV RECEPTACLE, WASTE, STEP-ON TYPE, APPROX.

305 mm (12”) DIAMETERAR CC BAR, GRAB FOR WATER CLOSET (PG-18-1, MCS 10800;

PG-18-4, SD 12)2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)1 CC MIRROR, WHEELCHAIR, 610 mm W x 910 mm H

(24"W x 36"H) (PG-18-1, MCS 10800; PG-18-4, SD 15)

Page 118: VA guide -2009
Page 119: VA guide -2009
Page 120: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-10

Design StandardsDermatology Procedure Treatment RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. Provide STC 40 partitions and

door. 2. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 100 FC Special: -- Notes: 1. 50% of lighting on critical

power.2. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lensW/4-F32T8 lamps, 3500°K,CRI=75 (minimum).

POWER General: 600W (receptacles); 1000W

(dedicated receptacle/circuit forelectrocautery unit).

Emergency: 200W (receptacle) Notes: 1. Junction box for 120V power

connection to surgical light.

COMMUNICATIONS ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Nurse call

HEATING, VENTILATING AND AIR CONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: 0 AC Load Lighting: 19 W/m 2(1.8 W/sf) AC Load-Equipment: 65 W/m2 (6 W/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 121: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListDermatology Procedure Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-10

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

1 CF LIGHT, SMALL, SURGICAL WITH VARIABLE INTENSITY CONTROL, SINGLE POINT SUSPENSION, CEILING MOUNTED, TYPE 840B (LOCATION INSTRUCTION AVAILABLE FROM ELECTRICAL SERVICE)(PG-18-1, MCS 16515)

AR CF MODULAR CASEWORK, W/ OVERHEAD CABINETS AND WALL HANGER STRIP

1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV ELECTRO-CAUTERIZING UNIT, MOBILE, APPROX.

535 mm W x 610 mm D (21"W X 24"D)2 VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 WATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,355 mm x 450 mm (14" X 17") RADIOGRAPHS,750 mm W x 500 mm H (31"W X 20"H)

1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,305 mm (12") DIAMETER

1 VV TABLE, EXAMINING AND TREATMENT, MOTORIZED1 VV TABLE, INSTRUMENT, DRESSING, CORROSION

RESISTING STEEL, 500 mm W x 910 mm L x 840 mm H (20"W X 36"L X 35"H)

Page 122: VA guide -2009
Page 123: VA guide -2009
Page 124: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-11

Design StandardsDermatology Medication Preparation Storage RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. 900 mm (3'-0") wide doors

SPECIAL EQUIPMENTNone

LIGHTING General: 30 FC Special: -- Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 3500°K,CRI=75 (Minimum)

POWER General: 600W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 78 W/m 2(7 W/sf) AC Load-Equipment: 32 W/ m2 (3 W/sf) Number of People: 1 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 125: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListDermatology Medication Preparation Storage Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-11

T-22C 1 CC KITCHEN CABINET, CORROSION REISISTING STEEL, 910 mm x 610 mm x 2130 mm ( 3’-0” x 2’-0” x 7’-0”) (H-08-1, MCS 10360; PG-18-4, SD 71A)

T14A 2 CC CABINET, CORROSION REISISTING STEEL, 6 ADJUSTIBLE SHELVES, SLIDING DOORS, METAL SLOPED TOP 1220 mm x 555 mm x 2130 mm(4’-0” x 1’-10” x 7’-0”) ( PG-18-1 MCS 10360, PG-18-6 CAB TYPE 14A 12301-10)

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER

Page 126: VA guide -2009
Page 127: VA guide -2009
Page 128: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-12

Design StandardsPhototherapy Treatment Rm/Phototherapy Shower RmARCHITECTURAL - Treatment Room Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient sheet flooring integral

base Floor Finish: Resilient Slab Depr: -- Notes: 1. 900 mm (3'-0") wide door.

ARCHITECTURAL - Shower/Toilet Ceiling: Portland cement plaster Ceiling Ht: 2700 mm (9'-0") Wall Finish: Ceramic tile, full height Wainscot: -- Base: Ceramic tile Floor Finish: Ceramic tile Slab Depr: 75 mm (3") shower depression Notes: 1. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: Treat. Room 50 FC Toilet/shower 30 FC Special: -- Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/3-F32T8 lamps, 3500°K,CRI=75 (minimum).

2. 600 x 600 mm (2'x2') recessedfluorescent light fixture, acrylicprismatic lens, W/2-FB31lamps, 3500°K, CRI=75(minimum).

3. Recessed incandescent showerlight, drop opal lens, 150W-A21lamp, UL listed for wetlocations.

POWER General: 1000W (receptacles) Emergency: -- Notes: 1. Junction box for 208V power

connection to UV light boxes.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Nurse call in patient shower to

be mounted 1200 mm (48") AFF.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 100 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Lighting: 46 W/m2 (4.2 W/sf) AC Load-Equipment: (5 W/sf to10 W/sf) 54 W/sm - 109 W/smNumber of People: 3 Special Exhaust: Yes Notes: 1. Coordinate equipment heat gain

requirements with supplier.

PLUMBING AND MEDICAL GASES Cold Water Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 129: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListPhototherapy Treatment Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-12

2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450;

VOL. 3 SD 380)2 CC TRACK, CURTAIN, CUBICLE, CEILING TYPE, SURFACE

MOUNTED (PG-18-1, MCS 10152)1 VV CABINET, FILING (LETTER SIZE) 5 DRAWER, APPROX.

380 mm W x 6350 mm D x 1520 mm H(15"W x 25"D x60"H)1 VV CABINET, STORAGE, STEEL, FREESTANDING WITH, 2

DOORS, 5 ADJUSTABLE SHELVES AND LOCK, 36"W X 910 mm W x 455 mm D x 2130 mm H (18"D x 84"H)

1 VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITH ARMS1 VV CLOCK, BATTERY OPERATED1 VV DESK, DOUBLE PEDESTAL, 1520 mm W x 760 mm D x

800 mm D (60"W x 30"D x 29 -1/2"H)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HAND AND FOOT UV LIGHT BOX, ON MOBILE STAND,

220 VOLT, APPROX., 610 mm W x 610 mm D x 760 mm H (24"W X 24"D X 30"H)

1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 mm (12") DIAMETER

1 VV WHOLE BODY UV LIGHT BOX, 220 VOLT, APPROX.,100 mm (4') DIAMETER IN CLOSED POSITION

Page 130: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListPhototherapy Shower Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-12

1 CC BAR, TOWEL (PG-18-1, MCS 10800)AR CC BAR, GRAB FOR TUB OR SHOWER (PG-18-1,

MCS 10800; PG-18-4, SD 13)1 CC DISH, SOAP, SURFACE MOUNTED (PG-18-1,

MCS 10800)2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)

P-415 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)P-702 1 CC SHOWER, BATH FIXTURE, WALL MOUNTED,

CONCEALED SUPPLIES (PG-18-1, MCS 15450; PG-18-4, SD 13A)

AR CC BAR, GRAB FOR WATER CLOSET (PG-18-1 MCS 10800; PG-18-4, SD 12)

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-18-1, MCS 10800; PG-18-4, SD 12)

2 CC NURSE CALL, EMERGENCY STATION WITH CORRIDOR SIGNAL LIGHT CONNECTED TO NEAREST NURSE CONTROL STATION (PG-18-1, MCS 16761)

P-103 1 CC WATER CLOSET, WALL HUNG (PG-18-1, MCS 15450; PG-18-1, MCS 15450; PG-18-4)

1 VV DISPENSER, SOAP, LIQUID, WALL HUNG1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE,

APPROXIMATELY 305 mm (12”) DIAMETER

Page 131: VA guide -2009
Page 132: VA guide -2009
Page 133: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-13

Design StandardsOrthopedic Clinic/Cast RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Veneer plaster, paint Wainscot: -- Base: Resilient sheet flooring integral

base Floor Finish: Resilient sheet flooring Slab Depr: -- Notes: 1. 1200 mm (4'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: Cubicle: 100 FC Work Area: 50 FC Special: -- Notes: 1. Local switching by area/cubicle.

2. 600 mm x 1200 mm (2'x4')recessed fluorescent lightfixture, acrylic prismatic lens,W/4-F32T8 lamps, 3500°K,CRI=75 (minimum).

3. 600 mm x 1200 mm (2'x4')recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 3500°K,CRI=75 (minimum).

POWER General: 1400W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: -- Radio; -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 10 Room Pressure Negative AC Load Lighting: 26 W/m 2(2.4 W/sf) AC Load-Equipment: 54 W/m 2 (5 W/sf) Number of People: 4 Special Exhaust: Yes Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: -- Notes:

Page 134: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListOrthopedic Clinic/Cast Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-13

T1A 1 CC CABINET, BASE WITH 2 DRAWERS, 2 HINGED DOORS AND 1 ADJUSTABLE SHELF, 910 mm W x 555 mm D x 910 mm H (36"W X 22"D X 36"H), CORROSION RESISTING STEEL TOP AND SPLASHBACKS, WITH WALL CABINET ABOVE WITH SLOPING TOP, 2 GLAZED SLIDING DOORS AND 2 ADJUSTABLE GLASS SHELVES ( PG-18-1, MCS 12301; PG-18-6, 12301-5, 5A)

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

1 CC PEGBOARD, PERFORATED, HEAVY DUTY, WITH HANGERS, 1220 mm x 2440 mm (48" X 96") (PG-18-1,

MCS 06200)T45 1 CC SHELF, CORROSION RESISTING STEEL, 305 mm W x

125 mm D (12"W X 5"D) (PG-18-1, MCS 10360)P-507 1 CC SINK, PLASTER, SINGLE COMPARTMENT, CRS

DRAINBOARD WITHOUT CORRUGATIONS (PG-18-1,MCS 15450; PG-18-4, SD 4.1)

1 VV BULLETIN BOARD, 1220 mm W x 91 mm H (48"W X 36"H)1 VV CABINET, INSTRUMENT AND DRESSING, 760 mm W x

405 mm D x 1520 mm H (30"W x 16"D x 60"H)1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED2 VV HOOK, COAT, WALL MOUNTEDAR VV ILLUMINATOR, X-RAY FILM, 120 VOLTS, 150 WATTS,

WALL MOUNTED, INDIVIDUAL SWITCH FOR TWO,255 mm x 455 mm (14" X 17") RADIOGRAPHS, 790 mm W x 500 mm H (31"W X 20"H)

AR VV LIGHT, EXAMINING, PORTABLE, 120 VOLTS, 20 AMPS, APPROX., 455 mm DIAMETER x 1900 mm H (18" DIAMETER X 75"H)

1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 mm (12") DIAMETER

Page 135: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListOrthopedic Clinic/Cast Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-13

AR VV SHELVING, FLOORSTANDING, STEEL, 4 OR 5 ADJUSTABLE SHELVES, 910 mm W x 455 mm D x 2130 mm H (36"W X 18"D X 84"H)

1 VV STOOL, EXAMINING, ADJUSTABLE1 VV TABLE, ORTHOPEDIC, PORTABLE PLASTER TABLE,

HYDRAULIC BASE1 VV TABLE, WORK, CORROSION RESISTING STEEL TOP,

METAL FRAME, 1 DRAWER AND 1 SHELF, 1520 mm W x 760 mm D x 860 mm H (60"W X 30"D X 34"H)

Page 136: VA guide -2009
Page 137: VA guide -2009
Page 138: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-14

Design StandardsChemotherapy Treatment RoomARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile

with washable finish Ceiling Ht: 2700 mm (9'-0") Wall Finish: Veneer plaster, paint Wainscot: -- Base: Resilient sheet flooring integral

base Floor Finish: Resilient sheet flooring Slab Depr: -- Notes: 1. 1220 mm (3'-8") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 30 FC Special: --- Notes: 1. Cubicles have individual

switches for separate control ofup/down lights.

2. 600 mm x 600 mm (2'x2')recessed fluorescent lightfixture, acrylic prismatic lens,W/2-FB31 lamps, 3500°K,CRI=75 (minimum).

3. Wall-mounted fluorescentdirect/indirect fixture, acrylicprismatic lens, W/4-F32T8lamps, 2-up and 2-down,separately ballasted.

POWER General: 1000W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Lighting: 16 W/m 2(1.5 W/sf) AC Load-Equipment: 65 W/m 2 (6 W/sf) Number of People: 10 Special Exhaust: Yes Notes: Provide capability to maintain 29 0C (850 F) year round.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes:

Page 139: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListChemotherapy Treatment Room

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-14

AR CC BRACKET, MOUNTING, TELEVISION RECEIVER(PG-18-1, MCS 16781)

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

T45 1 CC SHELF, CORROSION RESISTING STEEL, 305 mm W x 125 D (12"W X 5"D) (H-08-1, MCS 103 60; H-08-4,SD 60H)

AR CC TRACK, CURTAIN, CUBICLE, CEILING TYPE, SURFACE MOUNTED (PG-18-1, MCS 10152)

AR CC TRACK, INTRAVENOUS, CEILING MOUNTED, CONTINUOUS LOOP TRACK AND VERTICAL ADJUSTMENT (ONE FOR EACH RECLINING CHAIR OR STRETCHER

AR CF MODULAR CASEWORK, W/ OVERHEAD CABINETS AND WALL HANGER STRIPS

AR VV CHAIR, RECLINING, UPHOLSTERED, 910 mm x 960 mm - 1830 mm (36" X 38"-72") (EXTENDED)

1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV HOOK, COAT, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETERAR VV STRETCHER, TREATMENTAR VV TELEVISION, COLOR, 230 mm (9")AR VV CHAIR, STRAIGHT, WITH ARMS

Page 140: VA guide -2009
Page 141: VA guide -2009
Page 142: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-15

Design StandardsChemotherapy Agent Preparation RoomARCHITECTURAL Ceiling: Veneer plaster, paint Ceiling Ht: 2700 mm (9'-0") Wall Finish: Veneer plaster, paint Wainscot: -- Base: Resilient sheet flooring integral

base Floor Finish: Resilient sheet flooring Slab Depr: -- Notes: 1. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC Special: -- Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/3-F32T8 lamps, 4100°K,CRI=85 (minimum).

POWER General: 800W (receptacles) Emergency: -- Notes: 1. Junction box for 120V critical

power connection torefrigerator.

2. Junction box for 120V powerconnection to biological safetycabinet.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 60% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 12 Room Pressure: Prep area is Positive

Ante is Negative with respect to adjacent areas.

AC Load Lighting: 16 W/m 2(1.5 W/sf) AC Load-Equipment: 54 W/m 2 (5 W/sf) Number of People: 6 Special Exhaust: Biological safety cabinet

exhaust.See HVACDesign Manual forHospital Projects.

Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: Yes Laboratory Vacuum: Yes Sanitary Drain: Chemical-resist. type. Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Provide one natural gas outlet.

2. All outlets need to be on the leftside of the biological safetycabinet.

Page 143: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListChemotherapy Agent Preparation Room

VA DESIGN GUIDEAMBULATORY CARE UNIT (Hospital Based) PAGE 6-15

P-418 2 CC LAVATORY, SENSOR CONTROL PG-18-1, MCS 15450; VOL. 3 SD 380)

1 CC BIOLOGICAL SAFETY CABINET H12B2-72 (LAMINAR FLOW), CLASS II; TYPE B-2, 100% DIRECT EXHAUSTED AIR THROUGH THE WORK-SPACE. 1200 mm x 815 mm x 1980 mm (48"W X 38"D X 72"H)

AR CF MODULAR CASEWORK, W/ OVERHEAD CABINETS AND WALL HANGER STRIP

1 CF REFRIGERATOR, BIOLOGICAL, PASS-THRU, W/ HINGEDGLASS DOORS, 760 mm W x 840 mm D x 2060 mm H (30"W X 33"D X 81"H)

1 VV CABINET, INTRAVENOUS (IV), VISUAL CLARITY INSPECTION, 760 mm W x 610 mm D (30"W X 24"D), 120 VOLTS 20 AMPS

AR VV CART, EXCHANGE, CRS WIRE2 VV CHAIR, ROTARY, WITH ARMS1 VV CLOCK, BATTERY OPERATEDAR VV CRT, COMPUTER SYSTEM, W/ KEYBOARD2 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE

MOUNTED2 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV RECEPTACLE, WASTE, STEP-ON TYPE, APPROX.,

300 mm (12") DIAMETERAR VV HOOK, COAT, WALL MOUNTED

Page 144: VA guide -2009
Page 145: VA guide -2009
Page 146: VA guide -2009

FINAL DRAFT 10-31-95REVISED January 1997

VA DESIGN GUIDEAMBULATORY CARE (Hospital Based) PAGE 6-16

Design StandardsAerosolized Pentamidine Procedure RoomARCHITECTURAL Ceiling: Gypsum wallboard lay-in panels Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint. Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. Provide STC 40 partitions and

door.2. 900 mm (3'-0") wide door.

SPECIAL EQUIPMENT None

LIGHTING General: 50 FC Special: -- Notes: 1. 600 mm x 1200 mm (2'x4')

recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 3500°K,CRI=75 (minimum).

POWER General: 1000W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 10 Room Pressure: Negative AC Load Lighting: 13 W/m 2 (1.2 W/sf) AC Load-Equipment 32 W/m 2 (3 W/sf) Number of People: Provide 3 Special Exhaust: Dedicated exhaust. Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: -- Oxygen: -- Notes:

Page 147: VA guide -2009

SYMBOL QTY AI DESCRIPTION

FINAL DRAFT- 10/31/95REVISED January 1997

Equipment Guide ListAerosolized Petamidine Treatment Room

VA DESIGN GUIDEAMBULATORY CARE UNIT (Hospital Based) PAGE 6-16

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450; VOL. 3 SD 380)

T45 1 CC SHELF, CORROSION RESISTING STEEL, 305 mm W x 125 mm D (12"W X 5"D) (PG-18-1, MCS 10360; PG-18-4,SD 60H)

1 VV CABINET, FLOORSTANDING, STEEL, 2 DOOR, WITH 5 ADJUSTABLE SHELVES, 1220 mm W x 600 mm D x 910 mm H (48"W X 24"D X 36"H)

1 VV CHAIR, RECLINING, UPHOLSTERED, 36" X 38" X 72" (EXTENDED)

1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED.1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED

Page 148: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY CONTENTS - SECTION 5

Section 5Design Guide Platesand Data Sheets:Support AreasGuide Plate Series Plate Number

Nurse StationEquipment & Utility Plan........................5 - 1Reflected Ceiling Plan ...........................5 - 1Design Standards..................................5 - 1Equipment Guide List ............................5 - 1

Consultation RoomEquipment & Utility Plan........................5 - 2Reflected Ceiling Plan ...........................5 - 2Design Standards..................................5 - 2Equipment Guide List ............................5 - 2

Changing Cubicles & Patient LockersEquipment & Reflected Ceiling Plan ......5 - 3Design Standards..................................5 - 3Equipment Guide List ............................5 - 3

Anesthesia Workroom & Equipment StorageEquipment & Utility Plan........................5 - 4Reflected Ceiling Plan ...........................5 - 4Design Standards..................................5 - 4Equipment Guide List ............................5 - 4

Clean Utility RoomEquipment & Utility Plan........................5 - 5Reflected Ceiling Plan ...........................5 - 5Design Standards..................................5 - 5Equipment Guide List ............................5 - 5

Soiled Utility RoomEquipment & Utility Plan........................5 - 6Reflected Ceiling Plan ...........................5 - 6Design Standards..................................5 - 6Equipment Guide List ............................5 - 6

Page 149: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY CONTENTS - SECTION 5

Section 5Design Guide Platesand Data Sheets:Support AreasGuide Plate Series Plate Number

Housekeeping Aids ClosetEquipment & Utility Plan........................5 - 7Reflected Ceiling Plan ...........................5 - 7Design Standards..................................5 - 7Equipment Guide List ............................5 - 7

Page 150: VA guide -2009
Page 151: VA guide -2009
Page 152: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-1

Design StandardsNurse StationARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient Base Floor Finish: Carpet Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 70FC Special: Recessed Downlights Notes: 1. 600 mm x 1200 mm (2’x4’)

recessed fluorescent light fixture,acryliclens,w/2-F32T8 lamps, 3500 deg. K, CRI=75 (Min.)

2. Illumination level controlled by dimmer.

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 (Note 1) 100% Exhaust Air: Yes Noise Criteria: 40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Equal AC Load-Equipment: 54W/m 2 (5W/SF) AC Load Lighting: 64W/m 2 (6W/SF) Number of People: 5 Special Exhaust: -- Notes:

1. See HVAC Design Manual forHospital Projects for othercosiderations.

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 153: VA guide -2009

Final Draft 10-18-96Revised February 1997

Equipment Guide List

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-1

Nurse Station

1 CC COUNTER, PLASTIC LAMINATED TOP, LENGTH AS REQUIREDx 1067 mm (42”) (PG-18-1, MCS 12302; PG-18-4, SD 27)

1 VV CABINET, FILING (LETTER SIZE) 5 DRAWER,APPROX., 381 mm x 635 mm x 1524 mm (15” x 25” x 60”)

AR VV CHAIR, ROTARY, WITHOUT ARMS1 VV BULLETIN BOARD, 914 mm x 1524 mm (36” x 60”)1 CC CALL, CODE ONE, CONTROL AND ALARM STATION CONNECTED

TO LIFE SUPPORT UNIT AND SWITCHBOARDAR VV COMPUTER SYSTEM (PC)AR VV PRINTER FOR COMPUTER SYSTEMAR CC RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT (PG-18-1, MCS 16140: H-18-3, CS 866-1)1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 154: VA guide -2009
Page 155: VA guide -2009
Page 156: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-2

Design StandardsConsultation RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient Base Floor Finish: Carpet Slab Depr: -- Notes: 1. Provide STC 40 PTNS & Door

2. 3’-0” Wide Door

SPECIAL EQUIPMENTNone

LIGHTING General: 30FC Special: -- Notes:

1. 600mm x 1200mm (2’ x 4’)recessed fluorescent light fixture,acrylic prismatic lens, with 2-F32T8 lamps, 3500 deg. K,CRI=75 (minimum).

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% (Note 1) Noise Criteria: 40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: Equal AC Load-Equipment: 43W/m2 (4W/SF) AC Load Lighting: 32W/m2 (3W/SF) Number of People: 3 Special Exhaust: -- Notes:

1. See HVAC Design Manual for HospitalProjects for other considerations.

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: --

Page 157: VA guide -2009

Final Draft 10-18-96Revised February 1997

Equipment Guide List

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-2

Consultation Room

1 VV DESK, DOUBLE PEDESTAL, APPROX., 1524mm x 762mm x 749mm(60” x 30” x 29 1/2”)

1 VV CHAIR, ROTARY. WITH ARMSAR VV CHAIR, STRAIGHT, WITH ARMSAR VV HOOK, COAT, WALL MOUNTED1 VV BOOKCASE, 2 ADJ. SHELVES, 900mm x 900mm x 300mm

(36” x 36” x 12”)1 VV COMPUTER SYSTEM (PC) WITH KEYBOARDAR CC RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT (PG-18-1, MCS 16140: H-18-3, CS 866-1)1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 158: VA guide -2009
Page 159: VA guide -2009
Page 160: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-3

Design StandardsChanging Cubicles & Patient LockersARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 30FC Special: -- Notes:

1. 300 mm x1200 mm (1’x4’) recessedfluorescent light fixture, acrylicprismatic lens.

2. 600mm x 600 mm (2’x2’) recessedfluorescent light fixture, acrylicprismatic lens.

3. Provide nurse call light in corridor.

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: --- 100% Exhaust Air: Yes Noise Criteria: 40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: Negative AC Load-Equipment: 1W/m2 (1W/SF) AC Load Lighting: 22W/m2 (2W/SF) Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 161: VA guide -2009

Final Draft 10-18-96Revised February 1997

Equipment Guide List

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-3

Changing Cubicles and Patient Lockers

AR CC CUBICLE, DRESSING WITH ROBE HOOK, CURTAIN ROD ANDWALL HUNG BENCH (PG-18-1, MCS 06200 & 10800)

AR VV CURTAIN & ROD FOR DRESSING BOOTHAR CC MIRROR, FULL LENGTH, HEAT TEMPERED GLASS,

500mm x 1220mm (20” x 48”)AR CC LOCKER, STEEL, WITH FLAT TOP SURFACE,

305mm x 533mm x 1220mm (12” x 21” x 48”)AR CC NURSE CALL, EMERGENCY STATION, ACTIVATED BY PUSH

BUTTON ON WALL, WITH CORRIDOR SIGNAL LIGHT(PG-18-1, MCS 16761)

SYMBOL QTY AI DESCRIPTION

Page 162: VA guide -2009
Page 163: VA guide -2009
Page 164: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-4

Design StandardsAnesthesia Workroom & Equipment StorageARCHITECTURAL Ceiling: Gwbd. Ceiling Ht: 2400 mm (8'-0") Wall Finish: Gwbd Paint (Special Coat) Wainscot: -- Base: Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 30FC Special: -- Notes: 1. 600 mm x 1200 mm (2’x4’)

recessed fluorscent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 35000K,CRI=75 (Min.)

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: --- 100% Exhaust Air: Yes Noise Criteria: 40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: -- Room Pressure Negative AC Load-Equipment: 32W/m 2(3W/SF) AC Load Lighting: 32W/m 2(3W/SF) Number of People: 3 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes:

Page 165: VA guide -2009

Final Draft 10-18-96Revised February 1997

Equipment Guide List

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-4

Anesthesia Workroom & Equipment Storage (cont.)

1 CC OUTLET, AUDIO EMERGENCY ALARM (PG-18-1, MCS 16761)1 CC CONDUIT FOR ABOVE EQUIPMENT TO RECOVERY BEDS

(PG-18-1, MCS 16111)AR CC RECEPTACLES, ELECTRICAL, DUPLEX, 120 VOLT, 15 AMP, STRIP

MOLD WITH OUTLETS, WIRED ALTERNATELY ON SEPARATECIRCUITS ON 600mm (24”) CENTERS ABOVE COUNTER(PG-18-1, MCS 16140, H-18-3, CS 801-3)

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED1 VV FLAME PHOTOMETER2 VV TABLE, CRT, APPROX. 900mm x 900mm (36” x 36”)1 VV MACHINE, BLOOD GAS ANALYSIS1 VV CART, ANESTHESIA EQUIPMENT1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(MCS 16140; CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 166: VA guide -2009
Page 167: VA guide -2009
Page 168: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-5

Design StandardsClean Utility RoomARCHITECTURAL Ceiling: SC Gwbd Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 1200 mm (4'-0") Wide door

SPECIAL EQUIPMENTNone

LIGHTING General: 30FC Special: -- Notes: 1. 600mm x 1200mm (2’ x 4’)

recessed fluorescent lightfixture, acrylic prismatic lens,with 2-F32T8 lamps, 3500 deg.K, CRI=75 (minimum).

POWER General: 80 w Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: Yes Noise Criteria: 40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: Positive AC Load-Equipment: 27W/m 2 (2.5W/SF) AC Load Lighting: 38W/m2 (3.5W/SF) Number of People: 2 Special Exhaust: --Notes: 1. See HVAC Design Manual for

Hospital Projects for otherconsiderations.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 169: VA guide -2009

Final Draft 10-18-96Revised February 1997

Equipment Guide List

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-5

Clean Utility Room

AR VV SHELVING, STORAGE, MOBILE, STEEL, ROD SHELF, OPEN STYLEWITH 5 ADJUSTABLE SHELVES

T-5B AR CC CABINET, WALL, WITH SLOPING TOP, 2 HINGED DOORS AND 2ADJUSTABLE SHELVES, 914mm x 559mm x 1067mm(36” x 22” x 42”) (PG-18-1, MCS 12301; PG-18-4, SD 70E)

AR VV CART, MOBIL WITH ADJUSTABLE SHELVES,686mm x 914mm x 965mm (27” x 36” x 38”)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP(PG-18-1,MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 170: VA guide -2009
Page 171: VA guide -2009
Page 172: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-6

Design StandardsSoiled Utility RoomARCHITECTURAL Ceiling: SC Gwbd Ceiling Ht: 400 mm (8'-0") Wall Finish: SC Paint Wainscot: -- Base: Resilient Base Floor Finish: Ceramic Tile Slab Depr: -- Notes: 1. Full height ceramic tile - 3 walls

SPECIAL EQUIPMENTNone

LIGHTING General: 30FC Special: -- Notes: 1. 600 mmx1200 mm (2’x4’)

recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 3500oK,CRI=75 (Minimum)

POWER General: 180 w Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air Yes Noise Criteria: 40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Negative AC Load-Equipment: 38W/m 2 (3.5W/SF) AC Load Lighting: 38W/m 2 (3.5W/SF) Number of People: -- Special Exhaust: -- Notes: 1. See HVAC Design Manual for

Hospital Projects for otherconsiderations.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 173: VA guide -2009

Final Draft 10-18-96Revised February 1997

Equipment Guide List

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-6

Soiled Utility Room

2 VV CART, UTILITY, CORROSION RESISTING STEEL,914mm x 762mm (36” x 18” x 30”)

P-418 1 CC LAVATORY, SENSOR CONTROL(PG-18-1, MCS 15450; PG-18-4, VOL. 3 SD 380)

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED

P-505 1 CC SINK, SERVICE, CLINIC, FLUSHING RIM, WALL HUNG(PG-18-1, MCS 15450; PG-18-4, SD 379)

AR VV CARTS, SOILED, LINEN1 CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1,MCS 16140; H-18-3, CS 801-3)AR VV CRASH CART1 VV RACK, BEDPAN AND URINAL, WALL MOUNTED

600 mm x 180 mm x 1040 mm (26” x 7” x 41”)

SYMBOL QTY AI DESCRIPTION

Page 174: VA guide -2009
Page 175: VA guide -2009
Page 176: VA guide -2009

Final Draft 10-18-96Revised February 1997

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-7

Design StandardsHousekeeping Aids ClosetARCHITECTURAL Ceiling: GWB Ceiling Ht: 400 mm (8'-0") Wall Finish: GWB SC Paint Wainscot: -- Base: Welded Seamless Flooring Floor Finish: Welded Seamless Flooring Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 30FC Special: -- Notes:

1. 600 mm x 1200 mm (2’x4’) recessedfluorescent light fixture, acrylic prismaticlens, W/2-F32T8 lamps, 3500oK,CRI = 75 (Minimum)

POWER General: 180 w Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air Yes Noise Criteria: 40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 10 Room Pressure: Negative AC Load-Equipment: 20W/m2 (1.8W/SF) AC Load Lighting: 27W/m2 (2.5W/SF) Number of People: -- Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 177: VA guide -2009

Final Draft 10-18-96Revised February 1997

Equipment Guide List

VA DESIGN GUIDEAMBULATORY SURGERY PAGE 5-7

Housekeeping Aids Closet

P-502 1 CC SINK, SERVICE, CORNER, FLOOR MOUNTED(PG-18-1, MCS 10360; PG-18-4, SD 64B & 66)

T-10 AR CC RACK, MOP, WALL MOUNTED(PG-18-1, MCS 10360; PG-18-4, SD 64B & 66)

T-7 AR CC SHELVING, WALL HUNG, CORROSION RESISTING STEEL, TWOFIXED SHELVES, TWO DOORS WITH LOCKS,914mm x 305 x 1219mm (36” x 12” x 48”), 1524mm (60”) ABOVEFINISHED FLOOR (PG-18-1, MCS 12301, PG-18-4, SD 60C & 66)

1 VV VACUUM CLEANER, BATTERY POWERED1 VV MACHINE, SCRUBBING, WALL, BATTERY POWERED1 VV CART, SUPPLIES, 610mm x 1220mm (24” x 48”)1 CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, WITH

GROUND FAULT INTERRUPTER(PG-18-1, MCS 16140, H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 178: VA guide -2009

DRAFT 7-6-95

VA Design GuideCommunity Based Outpatient Clinic SECTION 5

Section 5Design Guide Platesand Data Sheets:Examination/Treatment

Guide Plate Series Plate Number

Screening Room (Nurse Triage)Equipment & Utility Plan ................................ .. 5-1Reflected Ceiling Plan ................................ ..... 5-1Design Standards................................ ............ 5-1Equipment Guide List ................................ ...... 5-1

Nurse StationEquipment & Utility Plan ................................ .. 5-2Reflected Ceiling Plan ................................ ..... 5-2Design Standards................................ ............ 5-2Equipment Guide List ................................ ...... 5-2

Blood Specimen Collection RoomEquipment & Utility Plan ................................ .. 5-3Reflected Ceiling Plan ................................ ..... 5-3Design Standards................................ ............ 5-3Equipment Guide List ................................ ...... 5-3

Blood Specimen Collection Room (Mobil Lab Unit)Equipment & Utility Plan ................................ .. 5-4Reflected Ceiling Plan ................................ ..... 5-4Design Standards................................ ............ 5-4Equipment Guide List ................................ ...... 5-4

Office/Examination RoomEquipment & Utility Plan ................................ .. 5-5Reflected Ceiling Plan ................................ ..... 5-5Design Standards................................ ............ 5-5Equipment Guide List ................................ ...... 5-5

Examination RoomEquipment & Utility Plan ................................ .. 5-6Reflected Ceiling Plan ................................ ..... 5-6Design Standards................................ ............ 5-6Equipment Guide List ................................ ...... 5-6

Page 179: VA guide -2009

DRAFT 7-6-95

VA Design GuideCommunity Based Outpatient Clinic SECTION 5

Section 5Design Guide Platesand Data Sheets:Examination/Treatment

Guide Plate Series Plate Number

Multipurpose Procedure RoomEquipment & Utility Plan ................................ .. 5-7Reflected Ceiling Plan ................................ ..... 5-7Design Standards................................ ............ 5-7Equipment Guide List ................................ ...... 5-7

Patient Wheelchair ToiletEquipment & Utility Plan ................................ .. 5-8Reflected Ceiling Plan ................................ ..... 5-8Design Standards................................ ............ 5-8Equipment Guide List ................................ ...... 5-8

Clean Utility RoomEquipment & Utility ................................ .......... 5-9Reflected Ceiling Plan ................................ ..... 5-9Design Standards................................ ............ 5-9Equipment Guide List ................................ ...... 5-9

Soiled Utility RoomEquipment & Utility Plan ................................ 5-10Reflected Ceiling Plan ................................ ... 5-10Design Standards................................ .......... 5-10Equipment Guide List ................................ .... 5-10

Page 180: VA guide -2009
Page 181: VA guide -2009
Page 182: VA guide -2009

Draft 7-6-95

Design StandardsScreening Room (Nurse Triage)ARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") (see note 1) Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Sound Protection: Yes (see note 2) Notes: 1. Perimeter partitions full height

2. Acoustic blanket over ceilings

SPECIAL EQUIPMENT None

LIGHTING General: 70FC - 3.5W/SF Special: -- Notes:

POWER General: 1080 W RECEPT Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: Negitive AC Load-Equipment: 2.9W/SF AC Load-Lighting: 1.7W/SF Number of People: 3 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 -1

Page 183: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-1

Equipment Guide ListScreening Room (Nurse Triage)

SYMBOL AI QTY DESCRIPTION

VV 1 SPHYGMOMANOMETER, WALL HUNGVV 1 CABINET, INSTRUMENTVV 1 TABLE, APPROX., 813 MM X 813 MM X 762 MM

(32" X 32" X 30")VV 2 CHAIR, STRAIGHT, WITHOUT ARMSVV 1 CLOCK, BATTERY OPERATED

Page 184: VA guide -2009
Page 185: VA guide -2009
Page 186: VA guide -2009

Draft 7-6-95

Design StandardsNurse StationARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Carpet Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: 70FC - 3.5W/SF Special: -- Notes: 1. Downspots over counter

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: Yes Pub. Addr: Yes Code One: Yes Paging: Yes Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 3.4w/sf AC Load-Lighting: 2.5w/sf Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Other: AAP Notes:

PAGE 5 -2

Page 187: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-2

Equipment Guide ListNurse Station

SYMBOL AI QTY DESCRIPTION

CC 1 COUNTER, PLASTIC LAMINATE TOP, 3048 MM X 1067 MM (120" X 42")(H-08-1, MCS 12302; H-08-4, SD 27)

VV AR CHAIR, ROTARY, WITHOUT ARMSVV 1 BULLETIN BOARD, 1524 MM X 914 MM (60" X 36")VV AR CART, MOBILE, 457 MM X 762 MM X 914 MM (18" X 30" X 36")CC 1 NURSE CALL, AUDIO/VISUAL, POWER AND CONTROL UNIT (H-08-1

MCS 16761)VV 2 CRT, COMPUTER SYSTEM, WITH KEYBOARDVV 1 PRINTER, COMPUTER SYSTEMCC 3 RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT ITEMS (H-08-1, MCS 16140; H-08-3, CS 866-1)VV 1 CLOCK, BATTERY OPERATED

Page 188: VA guide -2009
Page 189: VA guide -2009
Page 190: VA guide -2009

Draft 7-6-95

Design StandardsBlood Specimen Collection RoomARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: 1080 W Special: -- Notes:

POWER General: 1080 W Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 3.0 W/SF AC Load-Lighting: 1.7 W/SF Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 -3

Page 191: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-3

Equipment Guide ListBlood Specimen Collection Room

SYMBOL AI QTY DESCRIPTION

BLOOD SPECIMEN COLLECTION/MAILOUT ROOMTOP 10A CF 1 COUNTER TOP, HIGH PRESSURE PLASTIC LAMINATE,

DECORATIVE, OVER PLYWOOD OR PARTICLE BOARD CORE, 1-1/4" THICK (H-08-1 & H-08-6, MCS 11602)

VL4 CF 1 CABINET, UNDERCOUNTER, WITH 2 DRAWERS, 2 HINGED DOORSAND 1 ADJUSTABLE SHELF, 914 MM X 559 MM X 787 MM, (36" X22" X 31") FOR FLOOR MOUNTED ADD, 127 MM (5") TOE BASE (H-08-1 & H-08-6, MCS 12345)

VL5 CF 1 CABINET, UNDERCOUNTER, WITH 4 DRAWERS, 1 HINGED DOORAND 2 ADJUSTABLE SHELVES, 914 MM X 559 MM X 787 MM, (36" X22" X 31") FOR FLOOR MOUNTED ADD, 127 MM (5") TOE BASE (H-08-1 & H-08-6, MCS 12345)

VL25 CF 1 CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORSAND 2 ADJUSTABLE SHELVES, 914 MM X 330 MM X 762 MM (36" X13" X 30") (H-08-1 & H-08-6, MCS 12345)

CC 2 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, OVERCOUNTER (H-08-1, MCS 16140; H-08-3, CS 801-3)

P-414 CC 1 LAVATORY, STRAIGHT BACK (H-08-1, MCS 15450)VV 1 DISPENSER, SOAP, LIQUID, WALL MOUNTEDVV 1 DISPENSER, PAPER TOWEL, SURFACE MOUNTEDVV 1 RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 MM (12")

DIAMETERVV 1 CHAIR, BLOOD COLLECTING, APPROX. 27-1/2"W X 21-1/2"D X 32"HVV 1 BULLETIN BOARD, 762 MM X 1067 MM (30" X 42")VV 1 LITTER, APPROXIMATELY, 610 MM X 1829 MM (24" X 72")VV 1 REFRIGERATOR/FREEZER, 120 VOLT, 20 AMP, DOMESTIC,

APPROX., 787 MM X 711 MM X 1676 MM (31" X 28" X 66")VV 1 CENTRIFUGE, NON-REFRIGERATED, BENCH MODEL, 120 VOLT,

20 AMP, APPROX., 610 MM X 610 MM (24" X 24")VV 1 CLOCK, BATTERY OPERATED

Page 192: VA guide -2009
Page 193: VA guide -2009
Page 194: VA guide -2009

Draft 7-6-95

Design StandardsBlood Specimen Collection Room (Mobil Lab Unit)ARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: 50FC - 2.5 W/SF Special: -- Notes:

POWER General: 1080 W Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 3.0 W/SF AC Load-Lighting: 1.7 W/SF Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 - 4

Page 195: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-4

Equipment Guide ListBlood Specimen Collection Room (Mobile Lab Unit)

SYMBOL AI QTY DESCRIPTION

BLOOD SPECIMEN COLLECTION/MAILOUT ROOMTOP 10A CF 1 COUNTER TOP, HIGH PRESSURE PLASTIC LAMINATE,

DECORATIVE, OVER PLYWOOD OR PARTICLE BOARD CORE, 1-1/4" THICK (H-08-1 & H-08-6, MCS 11602)

VL4 CF 1 CABINET, UNDERCOUNTER, WITH 2 DRAWERS, 2 HINGED DOORSAND 1 ADJUSTABLE SHELF, 914 MM X 559 MM X 787 MM, (36" X22" X 31") FOR FLOOR MOUNTED ADD, 127 MM (5") TOE BASE (H-08-1 & H-08-6, MCS 12345)

VL5 CF 1 CABINET, UNDERCOUNTER, WITH 4 DRAWERS, 1 HINGED DOORAND 2 ADJUSTABLE SHELVES, 914 MM X 559 MM X 787 MM, (36" X22" X 31") FOR FLOOR MOUNTED ADD, 127 MM (5") TOE BASE (H-08-1 & H-08-6, MCS 12345)

VL25 CF 1 CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORSAND 2 ADJUSTABLE SHELVES, 914 MM X 330 MM X 762 MM (36" X13" X 30") (H-08-1 & H-08-6, MCS 12345)

CC 2 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, OVERCOUNTER (H-08-1, MCS 16140; H-08-3, CS 801-3)

P-414 CC 1 LAVATORY, STRAIGHT BACK (H-08-1, MCS 15450)VV 1 DISPENSER, SOAP, LIQUID, WALL MOUNTEDVV 1 DISPENSER, PAPER TOWEL, SURFACE MOUNTEDVV 1 RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 MM (12")

DIAMETERVV 1 CHAIR, BLOOD COLLECTING, APPROX. 27-1/2"W X 21-1/2"D X 32"HVV 1 BULLETIN BOARD, 762 MM X 1067 MM (30" X 42")VV 1 LITTER, APPROXIMATELY, 610 MM X 1829 MM (24" X 72")VV 1 REFRIGERATOR/FREEZER, 120 VOLT, 20 AMP, DOMESTIC,

APPROX., 787 MM X 711 MM X 1676 MM (31" X 28" X 66")VV 1 MOBILE LAB UNITVV 1 COMPUTER SYSTEM, WITH KEYBOARDVV 1 CLOCK, BATTERY OPERATED

Page 196: VA guide -2009
Page 197: VA guide -2009
Page 198: VA guide -2009

Draft 7-6-95

Design StandardsOffice/Examination RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") (see note 1) Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Sound Protection: Yes (see note 2) Slab Depr: -- Notes: 1. Perimeter partitions full height

2. Acoustic blanket over ceilings

SPECIAL EQUIPMENT None

LIGHTING General: 70FC-3.5W/SF Special: -- Notes:

POWER General: 1200 W Emergency: -- Notes: --

COMMUNICATION ADP: Empty Conduit Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Nurse Call: Yes Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 2.9 W/SF AC Load-Lighting: 2.0 W/SF Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 - 5

Page 199: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-5

Equipment Guide ListOffice/Examination Room

SYMBOL AI QTY DESCRIPTION

VV 1 DESK, SINGLE PEDESTAL, 1219 MM X 762 MM X 762 MM (48" X 30"X 30")

VV 1 CHAIR, ROTARY, WITH ARMSVV 1 BOOKCASE, SECTIONAL, EACH SECTION, 838 MM X 330 MM X 381

MM (33" X 13" X 15") WITH 254 MM (10") BASEVV 3 HOOK, COAT, WALL MOUNTEDVV 1 RECEPTACLE, WASTE, 330 MM (13") DIAMETERVV 1 CRT, COMPUTER SYSTEM, WITH KEYBOARDCC 1 RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT ITEMS (H-08-1, MCS 16140; H-08-3, CS 866-1)P-418 CC 1 LAVATORY, SENSOR CONTROL (H-08-1, MCS 15450; H-08-4, VOL.

3 SD 380)T45 CC 1 SHELF, CORROSION RESISTING STEEL, 305 MM X 127 MM (12" X

5") (H-08-1, MCS 10360; H-08-4, SD 60H)VV 1 DISPENSER, SOAP, LIQUID, WALL MOUNTEDVV 1 DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTEDVV 1 TABLE, EXAMINING, PADDED, ADJUSTABLE TOP, APPROX., 1880

MM X 533 MM X 762 MM (74" X 21" X 30")VV 1 STOOL, EXAMINING, ADJUSTABLEVV 1 OPHTHALMOSCOPE, WALL HUNGVV 1 OTOSCOPE, WALL HUNGVV 1 SPHYGMOMANOMETER, WALL HUNGVV AR ILLUMINATOR, X-RAY FILM, 120 VOLT, 150 WATTS, WALL

MOUNTED, INDIVIDUAL SWITCH FOR TWO, 356 MM X 432 MM (14"X 17") RADIOGRAPHS, 787 MM X 508 MM (31" X 20")

VV 1 CABINET, INSTRUMENT AND TREATMENT, 914 MM X 406 MM X1981 MM (36" X 16" X 78")

VV 1 RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 MM (12")DIAMETER

VV AR LIGHT, EXAMINING, PORTABLE, 120 VOLT, 20 AMP, APPROX., 457MM (18") DIAMETER X 1905 MM (75")

VV 2 CHAIR, STRAIGHT, WITHOUT ARMSVV 1 BULLETIN BOARD, 1219 MM X 914 MM (48" X 36")VV 1 CLOCK, BATTERY OPERATED

Page 200: VA guide -2009
Page 201: VA guide -2009
Page 202: VA guide -2009

Draft 7-6-95

Design StandardsExamination RoomARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0") (see note 1) Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Sound Protection: Yes (see note 2) Slab Depr: -- Notes: 1. Perimeter partitions full height

2. Acoustic blanket over ceilings

SPECIAL EQUIPMENT None

LIGHTING General: 70FC-3.5W/SF Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: Empty Conduit Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Nurse Call: Yes Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 2.9 W/SF AC Load-Lighting: 2.0 W/SF Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 - 6

Page 203: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-6

Equipment Guide ListExamination Room

SYMBOL AI QTY DESCRIPTION

P-418 CC 1 LAVATORY, SENSOR CONTROL (H-08-1, MCS 15450; H-08-4, VOL. 3SD 380)

T45 CC 1 SHELF, CORROSION RESISTING STEEL, 305 MM X 127 MM (12" X5") (H-08-1, MCS 10360; H-08-4, SD 60H)

VV 1 DISPENSER, SOAP, LIQUID, WALL MOUNTEDVV 1 DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTEDVV 1 TABLE, EXAMINING, PADDED, ADJUSTABLE TOP, APPROX., 1880

MM X 533 MM X 762 MM (74" X 21" X 30")VV 2 HOOK, COAT, WALL MOUNTEDVV 1 RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 MM (12")

DIAMETERVV 1 LIGHT, EXAMINING, PORTABLE, 120 VOLT, 20 AMP, APPROX., 457

MM (18") DIAMETER X 1905 MM (75")VV 2 CHAIR, STRAIGHT, WITHOUT ARMSVV 1 DESK, SINGLE PEDESTAL, 1219 MM X 762 MM X 762 MM (48" X 30"

X 30")VV 1 CRT, COMPUTER SYSTEM, WITH KEYBOARDCC 1 RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT ITEMS (H-08-1, MCS 16140; H-08-3, CS 866-1)VV 1 CLOCK, BATTERY OPERATED

Page 204: VA guide -2009
Page 205: VA guide -2009
Page 206: VA guide -2009

Draft 7-6-95

Design StandardsMultipurpose Procedure RoomARCHITECTURAL Ceiling: GWB Ceiling Ht: 2895 mm (9'-6") (see note 1) Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Sound Protection: Yes (see note 2) Slab Depr: -- Notes: 1. Perimeter partitions full height

2. Acoustic blanket over ceilings3. Bulletin Board

SPECIAL EQUIPMENT None

LIGHTING General: 50-100FC (see note 1) Special: -- Notes: 1. 2.5-5.0 W/SF, Fluor lamp of

deluxe color improved type.2. 18” DIA portable examination

light, 120V.

POWER General: 1200 W Emergency: -- Notes: --

COMMUNICATION ADP: Empty Conduit Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 100% 100% Exhaust Air Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load-Equipment: 8.0 W/SF AC Load-Lighting: 2.7 W/SF Number of People: 5 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 - 7

Page 207: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-7

Equipment Guide ListMultipurpose Procedure Room

SYMBOL AI QTY DESCRIPTION

VV 1 TABLE, TREATMENT, HI-LO, ELECTRICAL, 120 VOLT, 20 AMP, 762MM X 1981 MM X 813 MM (30" X 78" X 32")

VV 1 CABINET, INSTRUMENT AND TREATMENT, 914 MM X 406 MM X 1981MM (36" X 16" X 78")

VV 1 LIGHT, EXAMINING, PORTABLE, 120 VOLT, 20 AMP, APPROX., 457MM (18") DIAMETER X 1905 MM (75")

P-418 CC 1 LAVATORY, SENSOR CONTROL (H-08-1, MCS 15450; H-08-4, VOL. 3SD 380)

VV 1 DISPENSER, SOAP, LIQUID, WALL MOUNTEDVV 1 DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTEDVV 1 RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 MM (12")

DIAMETERVV 1 BULLETIN BOARD, 1524 MM X 914 MM (60" X 36")VV 1 ILLUMINATOR, X-RAY FILM, 120 VOLT, 150 WATTS, WALL

MOUNTED, INDIVIDUAL SWITCH FOR TWO, 356 MM X 432 MM (14" X17") RADIOGRAPHS, 787 MM X 508 MM (31" X 20")

VV 1 OPHTHALMOSCOPE, WALL HUNGVV 1 OTOSCOPE, WALL HUNGVV 1 SPHYGMOMANOMETER, WALL HUNGVV 1 CLOCK, BATTERY OPERATED

Page 208: VA guide -2009
Page 209: VA guide -2009
Page 210: VA guide -2009

Draft 7-6-95

Design StandardsPatient Wheelchair ToiletARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0")(see note 1) Wall Finish: CT Wainscot: -- Base: CT Floor Finish: CT Sound Protection: Yes (see note 2) Slab Depr: -- Notes: 1. Perimeter partitions full height

2. Acoustic blanket over ceilings

SPECIAL EQUIPMENT None

LIGHTING General: 30FC - 1.5 W/SF Special: -- Notes:

POWER General: 180 W Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Nurse Call: Yes Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: -- Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 100% 100% Exhaust Air Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: -- Relative Humidity/Heating: -- Minimum Air Changes/Hr.: 10 Room Pressure: Negative AC Load-Equipment: -- AC Load-Lighting: -- Number of People: -- Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 - 8

Page 211: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-8

Equipment Guide ListPatient Wheelchair Toilet

SYMBOL AI QTY DESCRIPTION

P-103 CC 1 WATER CLOSET, WALL HUNG (H-08-1, MCS 15450; H-08-4, SD 4)CC 1 DISPENSER, TOILET TISSUE, DOUBLE ROLL (H-08-1, MCS 10800;

H-08-4, SD 12)CC AR BAR, GRAB FOR WATER CLOSET (H-08-1, MCS 10800; H-08-4, SD

12, 14B & 14F)P-414 CC 1 LAVATORY, STRAIGHT BACK (H-08-1, MCS 15450)

CC 1 MIRROR, 610 MM X 914 MM, (24" X 36") OVER WHEELCHAIRLAVATORY (H-08-1, MCS 10800; H-08-4, SD 15)

CC 1 SHELF, STAINLESS STEEL, WALL HUNG, 152 MM X 457 MM (6" X18") (H-08-1, MCS 10360; H-08-4, SD 15)

CC 1 LIGHT, OVER MIRROR (H-08-1, MCS 16510; H-08-4, SD E-F-15)VV 1 DISPENSER, SOAP, LIQUID, WALL MOUNTEDVV 1 DISPENSER, PAPER TOWEL, SURFACE MOUNTEDVV 1 RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 MM (12")

DIAMETERCC 1 NURSE CALL, EMERGENCY STATION, WITH VESTIBULE SIGNAL

LIGHT, PROVIDE PULL CORD BY WATER CLOSET (H-08-1, MCS16761)NOTE: PROVIDE ONLY WHEN CLINIC HAS A LABORATORY.

CC 1 WINDOW, PASS-THRU, TO GENERAL LAB (H-08-1, MCS 08110)

Page 212: VA guide -2009
Page 213: VA guide -2009
Page 214: VA guide -2009

Draft 7-6-95

Design StandardsClean Utility RoomARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 4’-0” Door

SPECIAL EQUIPMENT None

LIGHTING General: 30FC - 1.5 W/SF Special: -- Notes:

POWER General: 180 w Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: Positive AC Load-Equipment: 2.0 w/sf AC Load-Lighting: 4.5 w/sf Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 - 9

Page 215: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-9

Equipment Guide ListClean Utility Room

SYMBOL AI QTY DESCRIPTION

VV AR SHELVING, STORAGE, MOBILE, STEEL, ROD SHELF, OPEN STYLEWITH 5 ADJUSTABLE SHELVES

VV AR CABINET, WALL, WITH SLOPING TOP, 2 HINGED DOORS AND 2ADJUSTABLE SHELVES, APPROX., 914 MM X 559 MM X 1067 MM(36" X 22" X 42")

VV AR SHELVING, FLOORSTANDING, STEEL, 4 OR 5 ADJUSTABLESHELVES, 914 MM X 457 MM X 2134 MM (36" X 18" X 84")

VV 1 CART, CRASH, 914 MM X 914 MM (36" X 36")

Page 216: VA guide -2009
Page 217: VA guide -2009
Page 218: VA guide -2009

Draft 7-6-95

Design StandardsSoiled Utility RoomARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB (see note 1) Wainscot: -- Base: 4” Resilient Base (see note 2) Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. CT full height on fixture wall

2. RB on three (3) walls

SPECIAL EQUIPMENT

None

LIGHTING General: (30fc) Special: -- Notes:

POWER General: 180 w Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Negative AC Load-Equipment: (3.3 w/sf) AC Load-Lighting: (2.5w/sf) Number of People: 1 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 5 - 10

Page 219: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 5-10

Equipment Guide ListSoiled Utility Room

SYMBOL AI QTY DESCRIPTION

VV 2 CART, UTILITY, CORROSION RESISTING STEEL, 914 MM X 457 MMX 762 MM (36" X 18" X 30")

P-418 CC 1 LAVATORY, SENSOR CONTROL (H-08-1, MCS 15450; H-08-4, VOL. 3SD 380)

VV 1 DISPENSER, SOAP, LIQUID, WALL MOUNTEDVV 1 DISPENSER, PAPER TOWEL, SURFACE MOUNTED

P-505 CC 1 SINK, SERVICE, CLINIC, FLUSHING RIM, WALL HUNG (H-08-1, MCS15450; H-08-4, SD 379)

VV AR CARTS, SOILED, LINEN

Page 220: VA guide -2009

DRAFT 7-6-95

VA Design GuideCommunity Based Outpatient Clinic SECTION 6

Section 6Design Guide Platesand Data Sheets:Support Areas

Guide Plate Series Plate Number

General LaboratoryEquipment & Utility Plan................................... 6-1Reflected Ceiling Plan...................................... 6-1Design Standards ............................................ 6-1Equipment Guide List....................................... 6-1

Pharmacy - Basic ServiceEquipment & Utility Plan................................... 6-2Reflected Ceiling Plan...................................... 6-2Design Standards ............................................ 6-2Equipment Guide List....................................... 6-2

Pharmacy - Expanded ServiceEquipment & Utility Plan................................... 6-3Reflected Ceiling Plan...................................... 6-3Design Standards ............................................ 6-3Equipment Guide List....................................... 6-3

Radiology - General Purpose RoomEquipment & Utility Plan................................... 6-4Reflected Ceiling Plan...................................... 6-4Design Standards ............................................ 6-4Equipment Guide List....................................... 6-4

Radiology - Film Processing RoomEquipment & Utility Plan................................... 6-5Reflected Ceiling Plan...................................... 6-5Design Standards ............................................ 6-5Equipment Guide List....................................... 6-5

Page 221: VA guide -2009

DRAFT 7-6-95

VA Design GuideCommunity Based Outpatient Clinic SECTION 6

Section 6Design Guide Platesand Data Sheets:Support Areas

Guide Plate Series Plate Number

Radiology - Dressing RoomEquipment/Utility/Reflected Ceiling Plan ......... 6-6Design Standards................................ ............ 6-6Equipment Guide List ................................ ...... 6-6

Radiology - Storage, Unexposed Film & ChemicalsEquipment & Utility Plan ................................ .. 6-7Reflected Ceiling Plan ................................ ..... 6-7Design Standards................................ ............ 6-7Equipment Guide List ................................ ...... 6-7

Page 222: VA guide -2009
Page 223: VA guide -2009
Page 224: VA guide -2009

Draft 7-6-95

Design StandardsGeneral LaboratoryARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: (70fc) Special: -- Notes:

POWER General: 4800 w Receptacles Emergency: 2000 w - 208 V Special: Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 100% 100% Exhaust Air Yes Noise Criteria: NC-45 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 12 (SA) Room Pressure: Negative AC Load-Equipment: (3.9w/sf) AC Load-Lighting: (3.0w/sf) Number of People: 5 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 6 - 1

Page 225: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-1

Equipment Guide ListGeneral Laboratory

SYMBOL AI QTY DESCRIPTION

TOP 13/13A CF AR COUNTER TOP, EPOXY, RESIN, WITH DRIP GROOVE, 1-1/4" THICK(H-08-1 & H-08-6, MCS 11602)-OR-

TOP 6/6A CF AR COUNTER TOP, HIGH PRESSURE PLASTIC LAMINATE, ACIDRESISTANT COMPOSITION OVER PLYWOOD OR PARTICLE BOARDCORE, 32 MM (1-1/4") THICK (H-08-1 & H-08-6, MCS 11602)

VL20/20A CF 1 TOILET, STAFF-OR-

VL21/21A CF 1 CABINET, UNDERCOUNTER, SINK UNIT, 1 DOOR, AVAILABLEWIDTHS - 457 MM, 610 MM; (18", 24") DEPTH - 559 MM; (22")HEIGHTS - 787 MM, 635 MM, (31", 25") FOR FLOOR MOUNTED ADD127 MM (5") TOE BASE (H-08-1 & H-08-6, MCS 12345)

VL23/23A CF 1 CABINET, UNDERCOUNTER, END SINK UNIT, 2 HINGED PANELDOORS, AVAILABLE WIDTHS - 1372 MM, 1524 MM; (54", 60") DEPTH -559 MM; (22") HEIGHTS - 787 MM, 635 MM, (31", 25") FOR FLOORMOUNTED ADD 127 MM (5") TOE BASE (H-08-1 & H-08-6, MCS 12345)

S-3 CF 1 SINK, MOLDED, RESIN WITH END OR CORNER DRAIN OUTLET, 635MM X 457 MM X 406 MM (25" X 18" X 16") DEEP (H-08-1 & H-08-6,MCS 11602)

F-3 CF 1 SINK, MOLDED, RESIN WITH END OR CORNER DRAIN OUTLET, 18"X 15" X 8" DEEP (H-08-1 & H-08-6, MCS 11602)

VL54 CF 1 PEGBOARD, 32 PEGS, 508 MM X 762 MM (20" X 30") OR 53 PEGS,813 MM X 762 MM (32" X 30") (H-08-1 & H-08-6, MCS 11602)

VL50/50A CF AR CABINET, UNDERCOUNTER, CORNER UNIT, FLOOR MOUNTED,WITH 127 MM (5") TOE BASE, SINGLE DOOR, FIXED SHELF, 813 MM(32") ALONG WALLS, HEIGHTS - 787 MM, 635 MM (31", 25") (H-08-1 &H-08-6, MCS 12345)

VL4/4A CF AR RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305 MM (12")DIAMETER

VL1/1A CF AR CABINET, UNDERCOUNTER, WITH 4/3 DRAWERS, AVAILABLEWIDTHS - 457 MM, 610 MM, 914 MM, 1219 MM; (18", 24", 36", 48")DEPTH - 559 MM; (22") HEIGHTS - 787 MM, 635 MM, (31", 25") FORFLOOR MOUNTED ADD 127 MM (5") TOE BASE (H-08-1 & H-08-6,MCS 12345)

VL8/8A CF AR CABINET, UNDERCOUNTER, WITH 1 DRAWER, 1 DOOR AND 1ADJUSTABLE SHELF, AVAILABLE WIDTHS - 305 MM, 457 MM, 610MM; (12", 18", 24") DEPTH - 559 MM; (22") HEIGHTS - 787 MM, 635MM, (31", 25") FOR FLOOR MOUNTED ADD 127 MM (5") TOE BASE(H-08-1 & H-08-6, MCS 12345)

Page 226: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-1

Equipment Guide ListGeneral Laboratory (cont.)

SYMBOL AI QTY DESCRIPTION

VL3/3A CF AR CABINET, UNDERCOUNTER, WITH 5/4 DRAWERS, AVAILABLEWIDTHS - 457 MM, 610 MM, 914 MM, 1219 MM; (18", 24", 36", 48")DEPTH - 559 MM; (22") HEIGHTS - 787 MM, 635 MM, (31", 25") FORFLOOR MOUNTED ADD 127 MM (5") TOE BASE (H-08-1 & H-08-6,MCS 12345)

VL14 CF AR TABLE FRAME, WITH DRAWER(S), KNEE SPACE UNIT, AVAILABLEWIDTHS - 457 MM, 610 MM, 762 MM, 914 MM, 1067 MM, 1219 MM;(18", 24", 30", 36", 42", 48") DEPTH - 559 MM; (22") HEIGHT - 787 MM(31") (H-08-1 & H-08-6, MCS 12345)

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 15 AMP, STRIPMOLD WITH OUTLETS, WIRED ALTERNATELY ON SEPARATECIRCUITS ON 610 MM (24") CENTERS ABOVE COUNTER (H-08-1,MCS 16140; H-08-3, CS 801-3)

VL25 CF AR CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORSAND 2 ADJUSTABLE SHELVES, AVAILABLE WIDTHS - 762 MM, 914MM, 1067 MM, 1219 MM; (30", 36", 42", 48") DEPTH - 330 MM; (13")HEIGHT - 762 MM (30") (H-08-1 & H-08-6, MCS 12345)

VL26 CF AR CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORSAND 2 ADJUSTABLE SHELVES, AVAILABLE WIDTHS 30", 36", 42",48"; DEPTH 16"; HEIGHT 48" (H-08-1 & H-08-6, MCS 12345)

P-706 CC 1 EMERGENCY SHOWER (H-08-1, MCS 15450)P-708 CC 1 EMERGENCY EYE AND FACE WASH, WALL MOUNTED, (H-08-1, MCS

15450)-OR-

P-707 CC 1 EMERGENCY SHOWER, EYE AND FACE WASH IN LIEU OF P-706AND P-708 (H-08-1, MCS 15450)

VV 1 REFRIGERATOR, DOMESTIC TYPE, .42 M3, (15 CU. FT.) 120 VOLT,20 AMP, APPROX., 787 MM X 711 MM X 1676 MM (31" X 28" X 66")

VV 1 REFRIGERATOR, 4 TO 10 DEGREES C., 25 CU. FT., 120 VOLT, 20AMP, REACH-IN TYPE, DOUBLE DOOR, WITH SHELVES

VV AR CHAIR, LABORATORY, SEMI-HYDRAULIC, ADJUSTABLE HEIGHT TO787 MM (31")

VV 1 BULLETIN BOARD, 762 MM X 1067 MM (30" X 42")VV 1 FREEZER, REACH-IN TYPE, -20 DEGREES TO -70 DEGREES C, .42

M3, (15 CU. FT.) 120 VOLT, 20 AMP, SINGLE DOOR, WITH SHELVESVV AR CENTRIFUGE, NON-REFRIGERATED, BENCH MODEL, 120 VOLT, 20

AMP, APPROX., 610 MM X 610 MM (24" X 24")VV 1 CLOCK, BATTERY OPERATEDCC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (H-08-1,

MCS 16140; H-08-3, CS 801-3)

Page 227: VA guide -2009
Page 228: VA guide -2009
Page 229: VA guide -2009

Draft 7-6-95

Design StandardsPharmacy - Basic ServiceOffice, Pharmacist/Consultation RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 3’-4” doors

SPECIAL EQUIPMENT None

LIGHTING General: -- Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: -- Dry Bulb Temp Heating: -- Minimum % Outside Air: -- 100% Exhaust Air -- Noise Criteria: -- Steam: -- Relative Humidity/Cooling: -- Relative Humidity/Heating: -- Minimum Air Changes/Hr.: -- Room Pressure: -- AC Load-Equipment: -- AC Load Lighting: -- Number of People: -- Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 6 - 2

Page 230: VA guide -2009

Draft 7-6-95

Design StandardsPharmacy - Basic ServiceStorage & PacksARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") (see note 1) Wall Finish: CMU Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. Full Height Partitions

SPECIAL EQUIPMENT None

LIGHTING General: -- Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: -- Dry Bulb Temp Heating: -- Minimum % Outside Air: -- 100% Exhaust Air -- Noise Criteria: -- Steam: -- Relative Humidity/Cooling: -- Relative Humidity/Heating: -- Minimum Air Changes/Hr.: -- Room Pressure: -- AC Load-Equipment: -- AC Load Lighting: -- Number of People: -- Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 6 - 2

Page 231: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-2

Equipment Guide ListPharmacy - Basic Service

SYMBOL AI QTY DESCRIPTION

NOTE: EQUIPMENT TO BE DETERMINED BY PHARMACY SERVICE,VACO FOR EACH PROJECT.

Page 232: VA guide -2009
Page 233: VA guide -2009
Page 234: VA guide -2009

Draft 7-6-95

Design StandardsPharmacy - Expanded ServiceARCHITECTURAL Ceiling: GWB Ceiling Ht: 2400 mm (8'-0") Wall Finish: GWB (see note 1) Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. Perimeter wall full height 6”

CMU-P.2. Perimeter barricade wall special locks, entry doors

SPECIAL EQUIPMENT None

LIGHTING General: 2x4 flour Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: (5.1w/sf) AC Load-Lighting: (2.4w/sf) Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 6 - 3

Page 235: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-3

Equipment Guide ListPharmacy - Expanded Service

SYMBOL AI QTY DESCRIPTION

NOTE: EQUIPMENT TO BE DETERMINED BY PHARMACY SERVICE,VACO FOR EACH PROJECT.

Page 236: VA guide -2009
Page 237: VA guide -2009
Page 238: VA guide -2009

Draft 7-6-95

Design StandardsRadiology - General Purpose RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: -- Wall Finish: -- Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 4’-0” lead lined entry door

2. Lead lined partitions

SPECIAL EQUIPMENT None

LIGHTING General: -- Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 5.0 w/sft (see note 1) AC Load Lighting: 2.6 w/sft Number of People: 2 Special Exhaust: -- Notes: 1. Check with the equipment

manufacturer for heat dissipationinto the room.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 6 - 4

Page 239: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-4

Equipment Guide ListRadiology - General Purpose Room

SYMBOL AI QTY DESCRIPTION

VC 1 RADIOGRAPHIC UNIT - CONSISTS OF THE FOLLOWINGCOMPONENTS:

VC 1 STARTER, TUBE, HIGH SPEEDVC 1 MODULE, POWERVC 1 TRANSFORMER, HIGH TENSION, X-RAYVC 1 TABLE, RADIOGRAPHIC, FLAT BUCKY

-OR-VC 1 TABLE, TILT, 90 DEGREE VERTICAL, 15 DEGREE TRENDELENBURGVC 1 TABLE, FLAT, MODIFIED WITH TRAY FOR MULTICASSETTES FOR

BODY SECTIONAL TECHNIQUE (PROVIDE ONLY WHEN APPROVEDFOR A SPECIFIC PROJECT)

VC 1 TUBE CARRIAGE, CEILING MOUNTEDVC 1 RAILS, CEILING FOR TUBE CARRIAGE, UNIVERSAL MOUNTVC 1 ATTACHMENT, BODY SECTION (PROVIDE WHEN APPROVED FOR A

SPECIFIC PROJECT)VC 1 BUCKY, TILT, WALL MOUNTEDVC 1 CONTROL, ATTACHMENT, BODY SECTION (PROVIDE ONLY WHEN

APPROVED FOR A SPECIFIC PROJECT)VC 1 HEADSTAND, RADIOGRAPHICVC 1 CHANGER, CASSETTE

NOTE: OPTIONAL COMPONENTS TO BE DETERMINED BYVETERANS HEALTH ADMINISTRATION)NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT

CC AR SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAYEQUIPMENT, IN ACCORDANCE WITH (H-18-1, MCS 13091, CS 64-1;H-18-4, SD 24 THRU 24K AND NCRP REPORT NO.33, 35 AND 36)

P-403 CC 1 LAVATORY, STRAIGHT BACK, FOOT PEDAL CONTROL (H-18-1, MCS15450)

CC 1 DISPENSER, SOAP, WALL MOUNTED WITH FOOT CONTROL (H-18-1,MCS 10800)

VV 1 DISPENSER, PAPER TOWEL, SURFACE MOUNTEDVV 1 RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305mm (12”)

DIAMETER, PROVIDE ONLY WHEN APPROVED FOR A SPECIFICPROJECT (OXYGEN, AIR, VACUUM OUTLET AND BRACKET)

CC 1 OUTLET, WALL, OXYGEN (H-18-1, MCS 15491; H-18-3, CS 310-1)CC 1 OUTLET, WALL, MEDICAL AIR (H-18-1, MCS 15491; H-18-3, CS 310-1)CC 1 OUTLET, WALL, VACUUM (H-18-1, MCS 15491; H-18-3, CS 310-1)CC 1 BRACKET, VACUUM BOTTLE SLIDE (H-18-1, MCS 15491; H-18-4, SD

336) NOTE: OUTLETS TO BE ON THE WALL, NEAR HEAD END OF X-RAY TABLE, 1524mm (60”) ABOVE THE FLOOR.

Page 240: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-4

Equipment Guide ListRadiology - General Purpose Room (cont.)

SYMBOL AI QTY DESCRIPTION

CC 1 CASSETTE PAS BOX TO DARK ROOM AS APPROVED FOR ASPECIFIC PROJECT

CC AR RECEPTACLES, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (H-18-1,MCS 16140; H-18-3, CS 801-3)

VV 1 CLOCK, BATTERY OPERATEDVV AR ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508 mm x 1499 mm (20” x 59”), 4 IN 1CF 1 CABINET, STORAGE, WALL MOUNTED, 254 mm (10”) ABOVE

FINISHED FLOOR, 5 SHELVES ANF FOLDING DOOR, APPROX., 610mm x 406 mm x 1575 mm (24” x 16” x 62”)

VV 1 HOOK, COAT, WALL MOUNTEDVV 1 RACK, APRON, WALL MOUNTEDVV 1 DISPOSAL, NEDLES, WALL MOUNTED

Page 241: VA guide -2009
Page 242: VA guide -2009
Page 243: VA guide -2009

Draft 7-6-95

Design StandardsRadiology - Film Processing RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: Painted GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: -- Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 100% 100% Exhaust Air Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load-Equipment: (7.5w/sf) AC Load-Lighting: (1.6w/sf) Number of People: 1 Special Exhaust: -- Notes: 1. Requires special exhaust min.

4” round duct with lead shieldingfor film processing.

2. Maintain negative pressure by exhausting 15% more air than supply air.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Chemical resistant pipe for

sanitary.

PAGE 6 - 5

Page 244: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-5

Equipment Guide ListRadiology - Film Processing Room

SYMBOL AI QTY DESCRIPTION

VC 1 PROCESSOR, FILM, AUTOMATIC, 90 SECOND PROCESSING CYCLECC 2 SAFELIGHT (H-18-4, SD E-D-4)CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (H-18-1,

MCS 16140; H-18-3, CS 801-3)CC AR DOORS, LIGHTPROOF OR LIGHT LOCK DOOR IF SPECIFIED (H-18-1,

MCS 11471)VV AR ILLUMINATOR, X-RAY FILM, WALL MOUNTED, 120 VOLT, 150

WATTS, INDIVIDUAL SWITCH FOR TWO, 14” x 17” RADIOGRAPHS,31” W x 20” H

P-516 CC 1 SINK, CORROSION RESISTING STEEL, SINGLE COMPARTMENT,WALL HUNG (H-18-1, MCS 15450)

CC 1 DISPENSER, PAPER TOWEL AND DISPOSAL COMBINATION UNITS(H-18-1. MCS 10800)

CC 1 SWITCH, DISCONNECT FOR FILM PROCESSOR (H-18-1, MCS 16170)

Page 245: VA guide -2009
Page 246: VA guide -2009

Draft 7-6-95

Design StandardsRadiology - Dressing RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: Painted GWB Wainscot: -- Base: 4” Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: -- Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: -- Dry Bulb Temp Heating: -- Minimum % Outside Air: -- 100% Exhaust Air -- Noise Criteria: -- Steam: -- Relative Humidity/Cooling: -- Relative Humidity/Heating: -- Minimum Air Changes/Hr.: -- Room Pressure: -- AC Load-Equipment: -- AC Load Lighting: -- Number of People: -- Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 6 - 6

Page 247: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-6

Equipment Guide ListRadiology - Dressing Room

SYMBOL AI QTY DESCRIPTION

CC AR CUBILCE, DRESSING, WITH ROBE HOOK, CURTAIN ROD AND WALLHUNG BENCH (H-18-1, MCS 06200 & 10800)

CC 1 MIRROR, FULL LENGTH, HEAT TEMPERED GLASS, 508mm x1219mm (20” x 48”) (H-18-1, MCS 10800)

CC 1 NURSE CALL EMERGENCY STATION, ACTIVATED BY PUSHBUTTON ON WALL, WITH CORRIDOR SIGNAL LIGHT (H-18-1, MCS16761)

Page 248: VA guide -2009
Page 249: VA guide -2009
Page 250: VA guide -2009

Draft 7-6-95

Design StandardsRadiology - Storage, Unexposed Film & ChemicalsARCHITECTURAL Ceiling: -- Ceiling Ht: -- Wall Finish: -- Wainscot: -- Base: -- Floor Finish: -- Slab Depr: -- Notes:

SPECIAL EQUIPMENT None

LIGHTING General: -- Special: -- Notes:

POWER General: -- Emergency: -- Notes: --

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes:

VA Design GuideCommunity Based Outpatient Clinic

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 100% 100% Exhaust Air Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: Negative AC Load-Equipment: None AC Load-Lighting: (1.3w/sf) Number of People: 0 Special Exhaust: -- Notes: 1. Maintain negative pressure

by exhausting.2. 15% more air than supply

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

PAGE 6 - 7

Page 251: VA guide -2009

Draft 7-6-95

VA Design GuideCommunity Based Outpatient Clinic PAGE 6-7

Equipment Guide ListRadiology - Storage, Unexposed Film & Chemicals

SYMBOL AI QTY DESCRIPTION

STORAGENOTE: LOCATE CONVIENIENT TO COMMON VIEWING ROOM

T9 CC AR BINS, FILING, X-RAY FILM, 914mm x 2286mm (36” x 90’) (H-18-1, MCS10671; H-18-4, SD 65B)

UNEXPOSED FILM & CHEMICALSNOTE: PROVIDE AIR CONDITION REQUIREMENTS AS PER HVACDESIGN MANUAL

VV AR PALLETS (SIZE AS REQUIRED)

Page 252: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC CONTENTS - SECTION 4

Section 4Design Guide Platesand Data Sheets:Patient Care Areas

Guide Plate Series Plate Number

Office, Eye Care ProviderLow Vision Exam & Traning Room

Equipment & Utility Plan ..........................4-1Reflected Ceiling Plan..............................4-1Design Standards ....................................4-1Equipment Guide List ..............................4-1

Examination/Treatment RoomEquipment & Utility Plan ..........................4-2Reflected Ceiling Plan..............................4-2Design Standards ....................................4-2Equipment Guide List ..............................4-2

Visual Fields Room and Photography RoomEquipment & Utility Plan ..........................4-3Reflected Ceiling Plan..............................4-3Design Standards ....................................4-3Equipment Guide List ..............................4-3

Pretesting, Fitting and Dispensing Room andConsulting/Viewing Room

Equipment & Utility Plan ..........................4-4Reflected Ceiling Plan..............................4-4Design Standards ....................................4-4Equipment Guide List ..............................4-4

Page 253: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC CONTENTS - SECTION 4 (cont.)

Section 4Design Guide Platesand Data Sheets:Patient Care Areas

Guide Plate Series Plate Number

Laser Room and Ultrasound RoomEquipment & Utility Plan ..........................4-5Reflected Ceiling Plan..............................4-5Design Standards ....................................4-5Equipment Guide List ..............................4-5

Eye Procedure RoomEquipment & Utility Plan ..........................4-6Reflected Ceiling Plan..............................4-6Design Standards ....................................4-6Equipment Guide List ..............................4-6

Page 254: VA guide -2009
Page 255: VA guide -2009
Page 256: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC PAGE 4-1

Design StandardsOffice, Eye Care ProviderLow Vision Exam & Training RoomARCHITECTURAL

Ceiling: Gypsum wallboard lay-in ceiling panels Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 50 FC (1.4 W/sf) - Ambient100 FC (/2.8 W/sf) - Task

Special: -- Notes: 1. 600 mm x 1200 mm (2’x4’)

recessed fluorescent light fixture,acrylic prismatic lens on top andbottom, W/4-F32T8 lamps, 4100deg. K, CRI=85 (min.)

POWER

General: 800W (receptacles) Emergency: -- Notes: --

COMMUNICATIONS

ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 25 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: -- AC Load Lighting 30 W/m2 (2.8 W/sf) AC Load Equipment: 97 W/m2 (1.76 W/sf) Number of People: 2 each rm Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 257: VA guide -2009

First Draft 6-28-97

Equipment Guide List

VA DESIGN GUIDEEYE CLINIC PAGE 4-1

Low Vision Examination And TrainingOffice, Eye Care Provider

LOW VISION EXAMINATION AND TRAINING ROOM

VV DESK, DOUBLE PEDESTAL,APPROX., I524mm x 762mm x 749mm (60” x 30” x 29 ”)

1 VV CHAIR, ROTARY, WITH ARMS1 VV TABLE. 1067mm x 610mm x 749mm (42” x 24” x 29 ”)1 VV CHAIR, PATIENT, WITH ARMSAR VV CABINET, STORAGE OF VISION AIDS DISPENSED TO PATIENTS.

WITH SLIDING GLASS DOORS, FREE STANDING,1524mm x 610mm x 1829mm (60” x 24” x 72”)

1 VV LAMP, FLOOR, WITH GOOSENECK FOR ADJUSTMENTS,HIGH INTENSITY (LUXO)

2 VV ILLUMINATED CHARTS (NEAR & FAR)455mm x 300mm (18”H x 12”W)

1 VV CLOCK, BATTERY OPERATED1 VV RECEPTACLE, WASTE, 300mm (12”) DIAMETERAR CC RECEPTACLE. ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 8Ol-3)

OFFICE, EYE CARE PROVIDER

1 VV DESK, DOUBLE PEDESTAL,APPROX., 1524mm x 762mm x 749mm (60” x 30” x 29 ”)

1 VV CHAIR, ROTARY, WITH ARMS2 VV CHAIR, STRAIGHT, WITH ARMS2 VV BOOKCASE, SECTIONAL,. EACH SECTION,

836mm x 330mm x 381mm (33” x 13” x 15”) WITH 254mm (10”) BASE-OR-

1 VV MODULAR FURNITURE WITH SHELVES/CABINETS ABOVE ANDBELOW WITH CHAIR, EXECUTIVE, ROTARY

1 VV RECEPTACLE, WASTE 330mm (13*) DIAMETER1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD

(TOP OF WORKSURFACE)1 VV PRINTER, FOR COMPUTER SYSTEM1 VV TABLE, FOR COMPUTER1 CC RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT (PG-18-1, MCS 16140; H-18-3, CS 866-1)1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 258: VA guide -2009
Page 259: VA guide -2009
Page 260: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC PAGE 4-2

Design StandardsExamination/Treatment RoomARCHITECTURAL

Ceiling: Gypsum wallboard lay-in ceiling panels Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 50 FC (1.4 W/sf) - Ambient100 FC (/2.8 W/sf) - Task

Special: -- Notes: 1.Provide dimmer controls for

Opthamolic stands.2.600 mm x 1200 mm (2’ x 4’)

recessed fluorescent light fixture,acrylic prismatic lens, W/4-F32T8lamps, 4100 deg. K, CRI=8.5(min.)

POWER

General: 800W (receptacles) Emergency: -- Notes --

COMMUNICATION

ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 25 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 30 W/m2 ( 4 W/sf) AC Load-Equipment: 65 W/m2 (6 W/sf) Number of People: 3 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 261: VA guide -2009

First Draft 6-28-97

Equipment Guide List

VA DESIGN GUIDEEYE CLINIC PAGE 4-2

Examination/Treatment Room

1 VV CHAIR/TABLE, PATIENT, EXAM, FULLY POWERED, HEIGHTADJUSTED

1 VV STAND, OPHTHALMIC INSTRUMENT STAND WITH SWINGINGAND PIVOTING ARMS CONTINUING:• PHOROPTOR• SLIT LAMP• KERATOMETER• LAMP-TOP OF OPHTHALMIC COLUMN

1 VV DESK, REFRACTION, WITH RETRACTABLE LENS DRAWER ANDCONTROLS AND DIMMER CONTROLS, POWER WELLSCONTAINS OPHTHALMOSCOPE, RETINOSCOPE ANDTRANSILLUMINATOR

1 VV CHART, PROJECTOR - TOP OF THE DESK1 VV SINK, MODULE1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED2 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED1 VV RECEPTACLE, WASTE, 330mm (23”) DIAMETER1 VV DISPENSER, GLOVES. WALL MOUNTED1 VV CABINET, SLOPING TOP, GLAZED DOORS,

457mm x 381mm x 1829mm (18” x I5” x 72”)AR VV HOOK, COAT, WALL MOUNTEDAR VV MIRROR, SET - 2, REFLECTING, ADJUSTABLE (SPECIAL

OPTOMETRIST)AR VV SCREEN, REFLECTING, ADJUSTABLE (SPECIAL OPTOMETRIST)1 VV TABLE, COMPUTER EQUIPMENT,(600mm x 1200mm (24” x 48”)1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV PRINTER, FOR COMPUTER SYSTEM1 CC RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

EQUIPMENT ITEMS (PG-18-1, MCS 16140; H-18-3, CS 866-1)1 VV CABINET, FILING (LETTER SIZE) 5 DRAWER,

APPROX., 381mm x 635mm x 1524mm (15” x 25” x 60”)1 VV CHAIR, OPEPATOR'S WITHOUT ARMS, SWIVEL AND

ADJUSTABLE HEIGHTS1 VV CHAIR, STRAIGHT, WITH ARMSAR CC SWITCH, DIMMER CONTROL (PG-18-1, MCS 16510)

NOTE: PROVIDE DUAL POINT CONTROL FOR LIGHTS1 VV CLOCK, BATTERY OPERATED1 VV RECEPTACLE, WASTE, 300mm (12”) DIAMETERAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG18-1, MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 262: VA guide -2009
Page 263: VA guide -2009
Page 264: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC PAGE 4-3

Design StandardsVisual Fields Room and Photography RoomARCHITECTURAL

Ceiling: Gypsum wallboard lay-in ceiling panels Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 50 FC (1.4 W/sf) - Ambient100 FC (/2.8 W/sf) - Task

Special: -- Notes: 1. 600 mm x 1200 mm (2’x4’)

recessed fluorescent light fixture,acrylic prismatic lens on top andbottom, W/4-F32T8 lamps, 4100deg. K, CRI=85 (min.)

POWER

General: 800W (receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 25% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 30 W/m2 (2.8 W/sf) AC Load-Equipment: 19 W/m2 (1.76 W/sf) Number of People: 2 each rm Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 265: VA guide -2009

First Draft 6-28-97

Equipment Guide List

VA DESIGN GUIDEEYE CLINIC PAGE 4-3

Visual Fields Room and Photography Room

VISUAL FIELDS ROOM(S)

1 VV VISUAL FIELDS INSTRUMENT(S)1 VV LENS SET, TRIAL, OPHTHALMIC2 VV CHAIR, WITH BACK SUPPORT, ADJUSTABLE HEIGHTS, SWIVEL

AND WHEEL BRAKES1 VV CHAIR, ROTARY, EXECUTIVE

NOTE: PROVIDE SPACE FOR WHEELCHAIRS2 VV BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140, H-18-3, CS 801-3)

PHOTOGRAPHY ROOM

1 VV CAMERA RETINAL2 VV CAMERA, ANTERIOR SEGMENT2 VV CAMERA, HAND HELD FOR EXTERNAL PHOTOS2 VV CHAIR, STRAIGHT, WITH ARMS2 VV CHAIR, OPERATOR'S WITHOUT ARMS, SWIVEL AND

ADJUSTABLE HEIGHTS1 VV CABINET, SLOPING TOP AND GLAZED DOORS,

914mm x 381mm x 1829mm (36” x 15” x 72")1 VV CART, VIDEO, .1016mm x 508mm (40” x 20”)

P-418 1 CC LAVATORY, SENSOR CONTROL,(PG-18-1, MCS 15450, VOL S, SD 380)

1 VV DISPENSER, SOAP. LIQUID, WALL MOUNTED1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED1 VV RECEPTACLE, WASTE, 330mm (13”) DIAMETER1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL., DUPLEX, 120 VOLT, 20 AMP

(PG-18-1. MCS 16140, H-18-3, CS 801-3)NOTE: PROVIDE DIMMER SWITCH FOR ROOM LIGHTING.

SYMBOL QTY AI DESCRIPTION

Page 266: VA guide -2009
Page 267: VA guide -2009
Page 268: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC PAGE 4-4

Design StandardsPretesting, Fitting & Dispensing Room andConsultation/Viewing RoomARCHITECTURAL

Ceiling: Gypsum wallboard lay-in ceiling panels Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 50 FC (1.4 W/sf) - Ambient100 FC (/2.8 W/sf) - Task

Special: -- Notes: 1. 600 mm x 1200 mm (2’x4’)

recessed fluorescent light fixture,acrylic prismatic lens on top andbottom, W/4-F32T8 lamps, 4100deg. K, CRI=85 (min.)

POWER

General: 800W (Receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 25% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 AC Load Lighting: 30 W/m2 (2.8 W/sf) AC Load-Equipment: 19 W/m2 (1.76 W/sf)Number of People: 2 each room Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 269: VA guide -2009

First Draft 6-28-97

Equipment Guide List

VA DESIGN GUIDEEYE CLINIC PAGE 4-4

Pretesting, Fitting and Dispensing Room andConsulting/Viewing Room

PRERESTING, FITTING AND DISPENSING ROOM

1 VV SCREENING CENTER WITH TABLE INCORPORATINGFOLLOWING INSTRUMENTS:• AUTO REFRACTOR• AUTO LENSOMETER• AUTO TONOMETER• AUTO BIOMETRY AND KERATOMETER

2 VV CHAIR, PATIENT, WITHOUT ARMS1 VV CHAIR, TECHNICIAN, WITHOUT ARMS1 VV DISPLAY, GLASSES-FRAME, APPROX., 1219mm (48”) LONG1 VV TABLE, KNEE SPACE UNDER, 1524mm x 610mm (60” x 24”)1 VV CHAIR, STRAIGHT WITHOUT ARMSAR VV MIRROR1 VV CABINET, STORAGE FOR CONTACT LENSES,

457mm x 610mm x 1829mm (18” x 24” x 72”)1 CC BENCH, REPAIR, 762mm x 2438mm WITH 152mm

(30” WIDE x 96” LONG WITH 6” WIDE) TOOL SHELF ABOVE,152mm (6”) DEEP DRAWERS UNDER AND KNEE SPACE

1 CC SINK, STAINLESS STEEL, BUILT INTO COUNTER,457mm x 356mm x 203mm (18” x 14” x 8”)

1 VV STOOL, OPERATOR’S, SWIVEL AND ADJUSTABLE HEIGHTS2 VV CABINET, WALL MOUNTED, 762mm (30”) WIDE1 VV CART, UTILITY, CORROSION RESISTING STEEL,

914mm x 457mm x 762mm (36” x 18” x 30”)1 VV CLOCK, BATTERY OPERATED1 CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 270: VA guide -2009

First Draft 6-28-97

Equipment Guide List

VA DESIGN GUIDEEYE CLINIC PAGE 4-4

Pretesting, Fitting and Dispensing Room andConsulting/Viewing Room (cont.)

CONSULTATION/VIEWING ROOM

1 VV TABLE, CONFERENCE,914mm x 1829mm x 762mm (36” x 72” x 30”)

4 VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV BOOKCASE, SECTIONAL

838mm x 330mm x 381mm (33” x 13” x I5”) WITH 254mm (10”) BASE1 VV BULLETIN/ERASER BOARD, COMBINATION,

1219mm x 914mm (48” x 36”)1 CC SCREEN, PROJECTION, CEILING OR WALL MOUNTED,

RETRACTABLE (PG-18-1, MCS 11131)AR VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 1499mm (20” x 59”), 4 IN 11 VV PROJECTION, APPARATUS, 610mm x 610mm (24” x 24”)1 VV RECEPTACLE, WASTE, 330mm (13”) DIAMETER1 VV PC, COMPUTER SYSTEM, WITH KEYBOARD, WITH MONITOR

(TOP OF WORK SURFACE)1 VV PRINTER, COMPUTER SYSTEM1 CC RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER

ITEMS (PG-18-1, MCS 16140; H-18-3, CS 866-1)1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1,MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 271: VA guide -2009
Page 272: VA guide -2009
Page 273: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC PAGE 4-5

Design StandardsLaser Room & Ultrasound RoomARCHITECTURAL

Ceiling: Gypsum wallboard lay-in ceiling panels Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile; Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 50 FC (1.4 W/sf) - Ambient100 FC (/2.8 W/sf) - Task

Special: -- Notes: 1. 600 mm x 1200 mm (2’x4’) recessed

fluorescent light fixture, acrylicprismatic lens, W/4-F32T8 lamps,4100 deg K, CRI-85 (minimum)

POWER

General: 800W (receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 25% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 30 W/m2 (2.8 W/sf) AC Load Equipment: 19 W/m2 (1.76 W/sf) Number of People: 2 each rm Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 274: VA guide -2009

First Draft 6-28-97

Equipment Guide List

VA DESIGN GUIDEEYE CLINIC PAGE 4-5

Laser Room and Ultrasound Room

LASER ROOM

1 VV LASER, YAG, AIR COOLED2 VV LASER, ARGON-KRYPTON DYE, WATER HOOK-UP FOR

COOLENT1 VV LASER, PROTECTIVE GOGGLE HOLDERAR CC CONNECTIONS, PLUMBINC;, ELECTRICAL OR MECHANICAL AS

REQUIRED1 VV CHAIR, PATIENT, WITH ARMS1 VV CHAIR, OPERATOR’S WITHOUT ARMS, SWIVEL AND

ADJUSTABLE HEIGHTS1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, 208 VOLT, 30 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

ULTRASOUND ROOM1 VV MACHINE, ULTRA SOUND ON CARTAR VV ULTRASOUND BIOMICROSCOPE, INSTRUMENT1 VV TABLE, EXAMINATION WITH PAPER ROLL DISPENSER AT THE

FOOT OF THE TABLE2 VV CHAIR, STRAIGHT, WITHOUT ARMS1 VV DESK, DOUBLE PEDESTAL.

APPROX., 1524mm x 762mm x 749mm (60” x 30” x 29 ”)1 VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 MP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 275: VA guide -2009
Page 276: VA guide -2009
Page 277: VA guide -2009

First Draft 6-28-97

VA DESIGN GUIDEEYE CLINIC PAGE 4-6

Design StandardsEye Procedure RoomARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2400 mm (8'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 50 FC (1.4 W/sf) - Ambient100 FC (/2.8 W/sf) - Task

Special: -- Notes: 1. Provide dimmer controls for

fluorescent lights2. 600 mm x 1200 mm (2’ x 4’)

recessed fluorescent light fixture,acrylic prismatic lens, W/4-F32T8lamps, 4100 deg. K, CRI=85.

3. Light, major surgical.

POWER

General: 800W (Receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 25% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 30 W/m2 (2.8 W/sf) AC Load-Equipment: 19 W/m2 (1.76 W/sf) Number of People: 2 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes:--

Page 278: VA guide -2009

First Draft 6-28-97

Equipment Guide List

VA DESIGN GUIDEEYE CLINIC PAGE 4-6

Eye Procedure Room

1 VV CHAIR, OPHTHALMIC, VARIABLE POSITIONS, ADJUSTABLEHEIGHTS

1 VV STOOL, SURGEON1 VV CART, UTILITY, CORROSION RESISTING STEEL,

914mm x 457mm x 762mm (36” x 18” x 30”)1 VV LASER, PROTECTIVE GOGGLE HOLDER1 VV I.V. POLE1 CC OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491, H-18-3, CS 310-1)1 CC OUTLET, WALL, MEDICAL AIR

(PG-18-1, MCS 15491, H-18-3, CS 310-1)1 CC OUTLET, WALL, VACUUM

(PG-18-1, MCS 15491, H-18-3, CS 310-1)1 CC BRACKET, VACUUM BOTTLE SLIDE

(PG-18-1, MCS 15491; PG-18-4, SD 336)1 VV CABINET, FOR DILATION AND IRRIGATION EQUIPMENT,

SLOPING TOP, 914mm x 457mm x 1829mm (36” x 15” x 72”)1 VV CABINET, INSTRUMENTS, GLAZED DOORS, SLOPING TOP,

914mm x 457mm x 1829mm (36” x 15” x 72”)1 VV DEFIBRILLATOR, ON CART1 VV CART, EMERGENCY, “CRASH CART”

APPROX., 914mm x 533mm (36” x 21”)1 VV CABINET, SUPPLIES, GLAZED DOORS, SLOPING TOP,

914mm x 457mm x 1829mm (36” x 15” x 72”)P-520 1 CC SINK, SURGEONS, SCRUB-UP, SENSOR CONTROL

(PG-18-1, MCS 15450; PG-18-4. SD 392)1 CC DISPENSER, SOAP, WITH FOOT CONTROL, WALL MOUNTED

OVER SINK (PG-18-1, MCS 10800)1 CC DRYER, HAND. FORCED AIR, TOUCHLESS TYPE,

120 VOLT, 20 AMP (PG-18-1, MCS 10800)1 VV DISPENSER, GLOVES, WALL MOUNTED1 CP LIGHT, MAJOR, SURGICAL WITH VARIABLE INTENSITY

CONTROL, SINGLE POINT SUSPENSION, CEILING MOUNTED,(PG-18-1, MSC 16515)

1 VV MONITOR, CEILING SUSPENDED1 VV UNIT, CRYOSURGICAL1 VV MACHINE, CAUTERYAR CC SWITCH, DIMMER CONTROL (PG-18-1, MCS 16510)1 VV HEAD MOUNT. LASER SYSTEMAR VV RECEPTACLE, WASTE, 330mm (13”) DIAMETERAR CC RECEPTACLE, ELECTRICAL. DUPLEX, 120 VOLT, 20 AMP

(PG-18-1. MCS 16140; H-18-3, CS 801-3)

SYMBOL QTY AI DESCRIPTION

Page 279: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Contents - Section 4

Section 4Design Guide Plates:Laboratories

GuidePlateSeries

4 - 1 ............. Single Module LaboratoryEquipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List

4 - 2 ............. Single Module Laboratory (Accessible)Equipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List (same as 4-1)

4 - 3 ............. Double Module Laboratory IEquipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List (same as 4-1)

4 - 4 ............. Double Module Laboratory IIEquipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List (same as 4-1)

4 - 5 ............. Double Module Laboratory IIIEquipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List (same as 4-1)

Page 280: VA guide -2009
Page 281: VA guide -2009
Page 282: VA guide -2009

September 30, 1995

Guide Plate 4-1 VA Design Guide — Research Laboratory

Design StandardsSingle Module Laboratory

ARCHITECTURALFloor Area 28 m² (300 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9’-0”) min* Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

*2850 mm (9'-6") preferred

SPECIAL EQUIPMENTH7-72 Fume Hood

Lighting ELECTRICAL PowerGeneral 550 lx(50 fc) General -

Special 1100 lx (100 fc) task Special **

Emergency - Emergency fume hood(s)***

Louvered deep cell parabolic fixtures, T-8 lamps **Recep: 5000 W, 208 V, 1Ø; Recep: 3000 W, 120 V

***Fume hood recep: 1200 W, 120 V dedicated circuit

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 1050 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 52 W/m² (4.8 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 3 Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 12 100% Exhaust Air yes

Steam - Special Exhaust yes****

****H7: 0.65 m³/s (1375 cfm), 60 Pa (0.24 inches of water), 724 mm (28½") sash opening

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water yes

Fuel Gas yes Laboratory Air yes

Nitrogen - Laboratory Vacuum yes

Page 283: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Guide Plate 4-1

Equipment Guide ListLaboratories, Generalqty symbol ai description

NOTE: IN ADDITION TO VL (FIXED) CASEWORK SHOWN ON THE EQUIPMENTGUIDE LIST; MODULAR CASEWORK MAY ALSO BE SELECTED.

1 H7-72 CC FUME HOOD, AIR BY-PASS, 1829 MM X 787 MM X 2438 MM, (72” X 31” X 96”) WITHCUP SINK, LAB AIR, FUEL GAS, LAB VACUUM, AND COLD WATER OUTLETS, 120VOLT, 20 AMP, RECEPTACLES (DEDICATED CIRCUIT) (PG-08-1 & PG-08-6, MCS11610)

AR H12B2-48

CC CABINET, BIOLOGICAL SAFETY (LAMINAR FLOW), CLASS II, TYPE B2, 100% DIRECTEXHAUSTED AIR THROUGH THE WORKSPACE, WITH FUEL GAS, LAB AIR AND LABVACUUM OUTLET, 120 VOLT, 20 AMP, RECEPTACLE (PG-08-1 & PG-08-6, MCS11604)

NOTE: THE TYPE (A, B1, B2 OR B3) OF CLASS II BIOLOGICAL SAFETY CABINETREQUIRED FOR ANY GENERAL LABORATORY MODULE WILL BE DETERMINED ONAN INDIVIDUAL PROJECT BASIS BY RESEARCH SERVICE AT THE MEDICALCENTER. REFER TO GENERAL INFORMATION 16.

AR CC CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

AR TOP13/13A

CF COUNTER TOP, EPOXY, RESIN, WITH DRIP GROOVE, 25 MM (1”) THICK, 762 MM(30”) DEEP ALONG WALL (PG-08-1 & PG-08-6, MCS 11602)

AR S-3 CF SINK, MOLDED, RESIN WITH END OR CORNER DRAIN OUTLET, 635 MM X 457 MM X406 MM (25” X 18” X 16”) (PG-08-1 & PG-08-6, MCS 11602)

AR VL1/1A CF CABINET, UNDERCOUNTER, WITH 4/3 DUST SEAL DRAWERS, WIDTH - 762 MM(30"); DEPTH - 559 MM (22"); HEIGHT - 787 MM (31"); FOR FLOOR MOUNTED ADD127 MM (5") TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

AR VL3/3A CF CABINET, UNDERCOUNTER, WITH 5/4 DUST SEAL DRAWERS, WIDTH - 914 MM(36"); DEPTH - 559 MM (22"); HEIGHT - 787 MM (31"); FOR FLOOR MOUNTED ADD127 MM (5") TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

AR VL4/4B CF CABINET, UNDERCOUNTER, WITH 2 DUST SEAL DRAWERS, 2 HINGED DOORS AND1 ADJUSTABLE SHELF, AVAILABLE WIDTHS - 762 MM, 914 MM, 1219 MM (30”, 36”,48”); DEPTH - 559 MM (22”); HEIGHTS - 787 MM, 635 MM (31”, 25”); FOR FLOORMOUNTED ADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

AR VL5/5B CF CABINET, UNDERCOUNTER, WITH 4/3 DUST SEAL DRAWERS, 1 HINGED DOOR AND2/1 ADJUSTABLE SHELVES, WIDTH - 914 MM (36”); DEPTH - 559 MM (22”); HEIGHT -635 MM (25”); FOR FLOOR MOUNTED ADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

AR VL8/8A CF CABINET, UNDERCOUNTER, WITH 1 DRAWER, 1 DOOR AND 1 ADJUSTABLE SHELF,WIDTH - 914 MM (36”); DEPTH - 559 MM (22”); HEIGHT - 787 MM (31”); FOR FLOORMOUNTED ADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

Page 284: VA guide -2009

September 30, 1995

Guide Plate 4-1 VA Design Guide — Research Laboratory

Equipment Guide ListLaboratories, Generalqty symbol ai description

AR VL14 CF TABLE FRAME, WITH DRAWER(S), KNEE SPACE UNIT, WIDTHS - 914 MM, 1067 MM(36”, 42”); DEPTH - 559 MM (22”); HEIGHT - 635 MM (25”) (PG-08-1 & PG-08-6, MCS12345)

AR VL20/20B

CF CABINET, UNDERCOUNTER, SINK UNIT, 2 HINGED PANEL DOORS, WIDTH - 914 MM(36”); DEPTH - 559 MM (22”); HEIGHT - 635 MM (25”); FOR FLOOR MOUNTED ADD127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

AR VL25 CF CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORS AND 2ADJUSTABLE SHELVES, WIDTH - 914 MM (36”); DEPTH - 330 MM (13”); HEIGHT - 762MM (30”) (PG-08-1 & PG-08-6, MCS 12345)

AR VL32 CF CABINET, WALL, OPEN WITH SLOPING TOP AND 2 ADJUSTABLE SHELVES, WIDTH -914 MM (36”); DEPTH - 330 MM (13”); HEIGHT - 762 MM (30”) (PG-08-1 & PG-08-6,MCS 12345)

AR VL54 CF PEGBOARD, EPOXY, 53 PEGS, 813 MM X 762 MM (32” X 30”) (PG-08-1 & PG-08-6,MCS 11602)

AR CC OUTLETS, ONE EACH, LAB AIR, FUEL GAS AND LAB VACUUM GROUPED OVERCOUNTER (PG-08-1 & PG-08-6, MCS 11602)

AR CC FAUCET, REAGENT GRADE OR MINERAL FREE WATER (PG-08-1, MCS 11602)

1 CC OUTLET, ADP (EMPTY CONDUIT SYSTEM) (SEE ELECTRICAL ENGINEERINGSERVICE GUIDE LINES)

AR CC RECEPTACLE, ELECTRICAL, 208 VOLT, 20 AMP, 1 PHASE, ON WALL,WEATHERPROOF (PG-08-1, MCS 16140; H-08-3, CS 801-3)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, 610 MM (24”) ONCENTERS ON FREE WALLS (PG-08-1, MCS 16140; H-08-3, CS 801-3)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, STRIP MOLD WITHOUTLETS ON 610 MM (24”) CENTERS, 229 MM (9”) ABOVE COUNTER (PG-08-1, MCS16140; H-08-3, CS 801-3)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 30 AMP, DEDICATED CIRCUIT (PG-08-1, MCS 16140)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 285: VA guide -2009
Page 286: VA guide -2009
Page 287: VA guide -2009

September 30, 1995

Guide Plate 4-2 VA Design Guide — Research Laboratory

Design StandardsLaboratory (Accessible)

ARCHITECTURALFloor Area 28 m² (300 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) min* Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

*2850 mm (9'-6") preferred

SPECIAL EQUIPMENTH7-72 Fume Hood

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special 1100 lx (100 fc) task Special **

Emergency - Emergency fume hood(s)***

Louvered deep cell parabolic fixtures, T-8 lamps **Recep: 5000 W, 208 V, 1Ø; Recep: 3000 W, 120 V

***Fume hood recep: 1200 W, 120 V dedicated circuit

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 1050 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 52 W/m² (4.8 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 2 Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 12 100% Exhaust Air yes

Steam - Special Exhaust yes****

****H7: 0.65 m³/s (1375 cfm), 60 Pa (0.24 inches of water),, 724 mm (28½") sash opening

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water yes

Fuel Gas yes Laboratory Air yes

Nitrogen - Laboratory Vacuum yes

Page 288: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 4-2

Equipment Guide ListLaboratories, Generalqty symbol ai description

See Guide Plate 4-1.

Page 289: VA guide -2009
Page 290: VA guide -2009
Page 291: VA guide -2009

September 30, 1995

Guide Plate 4-3 VA Design Guide — Research Laboratory

Design StandardsDouble Module Laboratory I

ARCHITECTURALFloor Area 58 m² (615 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) min* Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

*2850 mm (9'-6") preferred

SPECIAL EQUIPMENTH7-72 Fume Hood

H12 B2-48 Laminar Flow Hood

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special 1100 lx (100 fc) task Special **

Emergency - Emergency fume hood(s)***

Louvered deep cell parabolic fixtures, T-8 lamps **Recep: 5000 W, 208 V, 1Ø; Recep: 8000 W, 120 V

***Fume, flow hoods: 1200 W, 120 V dedicatedcircuit each

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 1995 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 75 W/m² (7.0 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 6 Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 12 100% Exhaust Air yes

Steam - Special Exhaust yes****

****H7: 0.65 m³/s (1375 cfm), 60 Pa (0.24 inches of water), 724 mm (28½") sash openingH12 B2: 0.40 m³/s (840 cfm), 523 Pa (2.10 inches of water), requires dedicated exhaust system

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water yes

Fuel Gas yes Laboratory Air yes

Nitrogen - Laboratory Vacuum yes

Page 292: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Guide Plate 4-3

Equipment Guide ListLaboratories, Generalqty symbol ai description

See Guide Plate 4-1.

Page 293: VA guide -2009
Page 294: VA guide -2009
Page 295: VA guide -2009

September 30, 1995

Guide Plate 4-4 VA Design Guide — Research Laboratory

Design StandardsDouble Module Laboratory II

ARCHITECTURALFloor Area 58 m² (615 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) min* Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

*2850 mm (9'-6") preferred

SPECIAL EQUIPMENTH7-72 Fume Hood

H12 B2-48 Laminar Flow Hood

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special 1100 lx (100 fc) task Special **

Emergency - Emergency fume hood(s)***

Louvered deep cell parabolic fixtures, T-8 lamps **Recep: 5000 W, 208 V, 1Ø; Recep: 8000 W, 120 V

***Fume, flow hoods: 1200 W, 120 V dedicatedcircuit each

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 1995 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 75 W/m² (7.0 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 6 Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 12 100% Exhaust Air yes

Steam - Special Exhaust yes****

****H7: 0.65 m³/s (1375 cfm), 60 Pa (0.24 inches of water), 724 mm (28½") sash openingH12 B2: 0.40 m³/s (840 cfm), 523 Pa (2.10 inches of water), requires dedicated exhaust system

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water yes

Fuel Gas yes Laboratory Air yes

Nitrogen - Laboratory Vacuum yes

Page 296: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Guide Plate 4-4

Equipment Guide ListLaboratories, Generalqty symbol ai description

See Guide Plate 4-1.

Page 297: VA guide -2009
Page 298: VA guide -2009
Page 299: VA guide -2009

September 30, 1995

Guide Plate 4-5 VA Design Guide — Research Laboratory

Design StandardsDouble Module Laboratory III

ARCHITECTURALFloor Area 58 m² (615 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) min* Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

*2850 mm (9'-6") preferred

SPECIAL EQUIPMENTH7-72 Fume Hood

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special 1100 lx (100 fc) task Special **

Emergency - Emergency fume hood(s)***

Louvered deep cell parabolic fixtures, T-8 lamps **Recep: 5000 W, 208 V, 1Ø; Recep: 3000 W, 120 V

***Fume hood recep: 1200 W, 120 V dedicated circuit

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 2100 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 75 W/m² (7.0 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 6 Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 12 100% Exhaust Air yes

Steam - Special Exhaust yes****

****H7: 0.65 m³/s (1375 cfm), 60 Pa (0.24 inches of water), 724 mm (28½") sash opening

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water yes

Fuel Gas yes Laboratory Air yes

Nitrogen - Laboratory Vacuum yes

Page 300: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Guide Plate 4-5

Equipment Guide ListLaboratories, Generalqty symbol ai description

See Guide Plate 4-1.

Page 301: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Contents - Section 5

Section 5Design Guide Plates:Specialized Areas

GuidePlateSeries

5 - 1 ............. Fluorescent Activated Cell Sorter Room(FACS)Equipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List

5 - 2 ............. Nuclear Magnetic Resonance Room(NMR)Equipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List

5 - 3 ............. Polymerase Chain Reactor Suite (PCR)5 - 3a ........... Polymerase Chain Reactor Room

(PCR)5 - 3b ........... Electrophoresis Room

Equipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List

5-4 ............... Confocal Microscope RoomEquipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List

5-5 ............... Cell Irradiator RoomEquipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List

Page 302: VA guide -2009
Page 303: VA guide -2009
Page 304: VA guide -2009

September 30, 1995

Guide Plate 5-1 VA Design Guide — Research Laboratory

Design StandardsFluorescent Activated Cell Sorter Room (FACS)

ARCHITECTURALFloor Area 14 m² (148 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

Lighting ELECTRICAL PowerGeneral 750 lx (70 fc) General -

Special - Special -

Louvered deep cell parabolic fixtures, T-8 lamps Emergency -

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 630 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 86 W/m² (8.0 W/ft²)* Dry Bulb Temp Heating 22°C (72°F)

Number of People 2 Relative Humidity - Cooling 50%

Noise Criteria NC-40 Relative Humidity - Heating 30%

Room Pressure (0) Minimum % Outside Air 100

Min Air Changes per Hour 6 100% Exhaust Air yes

Steam - Special Exhaust -

*Based on water cooled laser generators

PLUMBING AND LABORATORY GASESSanitary Drain yes Cold Water yes

Acid Waste - Hot Water yes

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 305: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 5-1

Equipment Guide ListFluorescent Activated Cell Sorter Room (FACS)qty symbol ai description

1 VV MACHINE, FLUORESCENT ACTIVATED CELL SORTER (FACS), 1778 MM X 1422 MM(70” X 56”) WITH 457 MM (18”) CLEARANCE ON ALL SIDES

1 VV CRT, COMPUTER SYSTEM, WITH KEYBOARD

1 VV TABLE, COMPUTER, APPROX., 762 MM X 762 MM X 660 MM (30” X 30” X 26”)

1 VV PRINTER, COMPUTER SYSTEM

1 VV STAND, COMPUTER PRINTER, APPROX., 610 MM X 610 MM X 660 MM (24” X 24” X26”)

AR CC OUTLET, ADP (EMPTY CONDUIT SYSTEM) (SEE ELECTRICAL ENGINEERINGSERVICE GUIDE LINES)

1 CC RECEPTACLE, ELECTRICAL, QUADRUPLEX, FOR COMPUTER EQUIPMENT ITEMS(PG-08-1, MCS 16140; H-08-3, CS 866-1)

1 VV CHAIR, ROTARY, WITH ARMS

1 VL20/20A

CF CABINET, UNDERCOUNTER, SINK UNIT, 2 HINGED PANEL DOORS, WIDTH - 762 MM(30”); DEPTH - 559 MM (22”); HEIGHT - 787 MM (31”); FOR FLOOR MOUNTED ADD127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

1 L-3 CF SINK, MOLDED, RESIN WITH END OR CORNER DRAIN OUTLET, 457 MM X 381 MM X279 MM (18” X 15” X 11”) (PG-08-1 & PG-08-6, MCS 11602)

1 VL4/4A CF CABINET, UNDERCOUNTER, WITH 2 DUST SEAL DRAWERS, 2 HINGED DOORS AND1 ADJUSTABLE SHELF, WIDTH, 762 MM (30”); DEPTH - 559 MM (22”); HEIGHT 787MM (31”); FOR FLOOR MOUNTED ADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6,MCS 12345)

1 VV CLOCK, BATTERY OPERATED

2 CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 30 AMP, DEDICATED CIRCUIT (PG-08-1, MCS 16140)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 306: VA guide -2009
Page 307: VA guide -2009
Page 308: VA guide -2009

September 30, 1995

Guide Plate 5-2 VA Design Guide — Research Laboratory

Design StandardsNuclear Magnetic Resonance Room (MNR)

ARCHITECTURALFloor Area 42 m² (457 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft)* Floor Finish vct

RFI Shielding yes Slab Depression -

Soundproofing - Floor Load -

*4100 mm (13'6") min over magnet 1.5 m² (16 ft²) min

SPECIAL EQUIPMENTNuclear magnetic resonance machine

Lighting ELECTRICAL PowerGeneral 750 lx (70 fc) General -

Special - Emergency ventilation system

Direct current, non-ferrous, incandescent fixtures withPAR38 halogen flood lamps on dimmer switches

Copper cladding on wiring

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 2760 W Dry Bulb Temp Cooling 23°C (74°F)

AC Load Equipment 70 W/m² (6.5 W/ft²)** Dry Bulb Temp Heating 22°C (72°F)

Number of People 3 Relative Humidity - Cooling 50%

Noise Criteria NC-40 Relative Humidity - Heating 30%

Room Pressure (0) Minimum % Outside Air 100

Min Air Changes per Hour 6 100% Exhaust Air yes

Steam - Special Exhaust yes***

**Minimum requirement

***Use only copper piping and aluminum or PVC ductwork inside the room.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water -

Fuel Gas yes Laboratory Air yes

Nitrogen - Laboratory Vacuum yes

Additional Notes:1. Utility requirements for magnets vary greatly among manufacturers. There are different kinds of magnets withspecific utility requirements. Requirements also vary if gradient power supply and gradient coils are used, andwhether they are air-cooled or water-cooled. A water-cooled system, consisting of a closed loop water supply withwater-to-water heat exchanger to a refrigerator type heat exchanger, is recommended for gradient power supplyand gradient coils. The water must be filtered to protect equipment. Provide domestic water back-up for coolingwater in case of emergency.

Page 309: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 5-2

Equipment Guide ListNuclear Magnetic Resonance Room (NMR)qty symbol ai description

1 VC MACHINE, NUCLEAR MAGNETIC RESONANCE (NMR)

1 VC CONSOLE, CONTROL

1 VL20/20A

CF CABINET, UNDERCOUNTER, SINK UNIT, 2 HINGED PANEL DOORS, WIDTH - 914 MM(36”); DEPTH - 559 MM (22”); HEIGHT 787 MM (31”); FOR FLOOR MOUNTED ADD 127MM (5”) TOW BASE (PG-08-1 & PG-08-6, MCS 12345)

1 S-3 CF SINK, MOLDED, RESIN WITH END OR CORNER DRAIN OUTLET, 635 MM X 457 MM X406 MM (25” X 18” X 16”) (PG-08-1 & PG-08-6, MCS 11602)

1 TOP 13/13A

CF COUNTER TOP, EPOXY, RESIN, WITH DRIP GROOVE, 25 MM (1”) THICK (PG-08-1 &PG-08-6, MCS 11602)

1 CC OUTLETS, ONE EACH, LAB AIR, FUEL GAS AND LAB VACUUM GROUPED OVERCOUNTER (PG-08-1 & PG-08-6, MCS 11602)

1 CC RECEPTACLE, ELECTRICAL, 208 VOLT, 20 AMP, 1 PHASE, DEDICATED CIRCUIT (PG-08-1, MCS 16140)

NOTE: PROVIDE COOLING FOR MAGNET, COMPRESSED AIR OR NITROGEN ASREQUIRED.

Additional Notes (continued):2. Superconducting magnets use liquid cryogens (helium and nitrogen). Due to quenching and to prevent

explosion due to overpressure in the magnet, excess pressure is relieved through rupture discs. Dischargefrom these discs must be relieved to the outside through vents. Also, a separate emergency exhaust system isrequired with a minimum of 12 air changes per hour to exhaust above the roof any accidental gas spillage insidethe room. The emergency exhaust system shall be activated by an oxygen sensor. Also, provide emergencymake-up supply air from the normal supply system whenever the emergency exhaust air is activated.

3. Some manufacturers do not recommend blowing air directly at magnets.

Page 310: VA guide -2009
Page 311: VA guide -2009
Page 312: VA guide -2009

September 30, 1995

Guide Plate 5-3a VA Design Guide — Research Laboratory

Design StandardsPolymerase Chain Reactor Room (PCR)

ARCHITECTURALFloor Area 10 m² (112 ft²)* Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

*Floor area may change depending on suite layout.

Lighting ELECTRICAL PowerGeneral 750 lx (70 fc) General -

Special 1100 lx (100 fc) task Special -

Louvered deep cell parabolic fixtures, T-8 lamps Emergency -

COMMUNICATIONSTelephone yes ADP -

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 315 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 32 W/m² (3.0 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 1 Relative Humidity - Cooling 50%

Noise Criteria NC-40 Relative Humidity - Heating 30%

Room Pressure positive** Minimum % Outside Air 100

Min Air Changes per Hour 4 100% Exhaust Air yes

Steam - Special Exhaust -

**Maintain positive pressure with respect to air lock by exhausting 15% less than supply air.

Maintain positive pressure in air lock with respect to corridor and PCR Prep Lab.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water -

Acid Waste - Hot Water -

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 313: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 5-3b

Design StandardsElectrophoresis Room

ARCHITECTURALFloor Area 11 m² (118 ft²)* Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

*Floor area may change depending on suite layout.

Lighting ELECTRICAL PowerGeneral 750 lx (70 fc) General -

Special 1100 lx (100 fc) task Special -

Louvered deep cell parabolic fixtures, T-8 lamps Emergency -

COMMUNICATIONSTelephone yes ADP -

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 420 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 32 W/m² (3.0 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 1 Relative Humidity - Cooling 50%

Noise Criteria NC-40 Relative Humidity - Heating 30%

Room Pressure positive** Minimum % Outside Air 100

Min Air Changes per Hour 4 100% Exhaust Air yes

Steam - Special Exhaust -

**Maintain positive pressure with respect to air lock to air lock by exhausting 15% less than supply air.

Maintain positive pressure in air lock with respect to corridor and PCR Prep Lab.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 314: VA guide -2009

September 30, 1995

Guide Plate 5-3 VA Design Guide — Research Laboratory

Equipment Guide ListPolymerase Chain Reaction Suite (PCR)qty symbol ai description

AR VV CYCLERS, DNA THERMAL, 305 MM X 610 MM (12"" X 24"")"

NOTE: FOR EQUIPMENT REQUIREMENTS SEE (LABORATORIES, GENERAL) LISTEDIN GUIDE PLATE 4-1

1 VV POWER PACK

1 VV COOLING DEVICE

1 VV ELECTROPHORESIS CHAMBER

Page 315: VA guide -2009
Page 316: VA guide -2009
Page 317: VA guide -2009

September 30, 1995

Guide Plate 5-4 VA Design Guide — Research Laboratory

Design StandardsConfocal Microscope Room

ARCHITECTURALFloor Area 14 m² (147 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

Lighting ELECTRICAL PowerGeneral 325 lx (30 fc) General -

Special - Special -

Incandescent fixtures with PAR38 halogen flood lamps ondimmer switch

Emergency -

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 600 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 48 W/m² (4.5 W/ft²)* Dry Bulb Temp Heating 22°C (72°F)

Number of People 3 Relative Humidity - Cooling 50%

Noise Criteria NC-40 Relative Humidity - Heating 30%

Room Pressure positive Minimum % Outside Air 100

Min Air Changes per Hour 6 100% Exhaust Air yes

Steam - Special Exhaust -

*Based on water cooled laser generator. See note 1 below.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water see below

Acid Waste - Hot Water -

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Additional Notes:1. Use of water-cooled laser generators is preferred as air-cooled generators dissipate excessive heat into the

room. Tie into a common closed circuit cooler for all water-cooled equipment in the Research Facility. Providedomestic water backup for cooling water in case of emergency.

Page 318: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 5-4

Equipment Guide ListConfocal Microscope Roomqty symbol ai description

1 VV MICROSCOPE, CONFOCAL AND ANCILLARY EQUIPMENT

1 VV TABLE, VIBRATION FREE, 1219 MM X 914 MM (48” X 36”)

1 VV TANK, NITROGEN STORAGE

1 VV TABLE, COMPUTER, 1219 MM X 914 MM (48” X 36”)

1 VL36 CF CABINET, FULL HEIGHT, WITH SLOPING TOP, 2 GLAZED SLIDING DOORS AND 5ADJUSTABLE SHELVES, WIDTH - 914 MM (36”); DEPTH - 406 MM (16”); HEIGHT -2134 MM (84”) (PG-08-1 & PG-08-6, MCS 12345)

1 VV CHAIR, ROTARY, WITH ARMS

AR VV CHAIR, ROTARY, WITHOUT ARMS

1 VV CLOCK, BATTERY OPERATED

1 CC RECEPTACLE, ELECTRICAL, 208 VOLT, 20 AMP 1 PHASE (PG-08-1, MCS 16140; H-08-3, CS 801-3)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 319: VA guide -2009
Page 320: VA guide -2009

September 30, 1995

Guide Plate 5-5 VA Design Guide — Research Laboratory

Design StandardsCell Irradiator Room

ARCHITECTURALFloor Area 6.6 m² (71 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special - Special -

Louvered deep cell parabolic fixtures, T-8 lamps Emergency -

COMMUNICATIONSTelephone - ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 105 W Dry Bulb Temp Cooling 24°C (76°F)

AC Load Equipment 97 W/m² (9.0 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 1* Relative Humidity - Cooling 50%

Noise Criteria NC-40 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 6 100% Exhaust Air yes

Steam - Special Exhaust -

*This room intended for short occupancy.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water -

Acid Waste - Hot Water -

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 321: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 5-5

Equipment Guide ListCell Irradiator Roomqty symbol ai description

1 VV IRRADIATOR, GAMMA CELL, 610 MM X 610 MM (24” X 24”)

1 VV CART, SPECIMEN

1 VV HOLDER, FOR LOG BOOK, WALL MOUNTED

1 VV CRT, COMPUTER SYSTEM, WITH KEYBOARD

1 VV PRINTER, COMPUTER SYSTEM

1 VV TABLE, COMPUTER AND PRINTER

AR CC OUTLET, ADP (EMPTY CONDUIT SYSTEM) (SEE ELECTRICAL ENGINEERINGSERVICE GUIDE LINES)

1 CC RECEPTACLE, ELECTRICAL, QUADRUPLEX, FOR COMPUTER EQUIPMENT ITEMS(PG-08-1, MCS 16140; H-08-3, CS 866-1)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 322: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Contents - Section 6

Section 6Design Guide Plates:Laboratory Support

GuidePlateSeries

6 - 1 ............. Cold Procedure RoomEquipment & Utility PlanDesign StandardsEquipment Guide List

6 - 2 ............. Glassware Washing and SterilizationRoomEquipment & Utility PlanReflected Ceiling PlanDesign StandardsEquipment Guide List

6 - 3 ............. Tissue Culture LaboratoryEquipment & Utility PlanDesign StandardsEquipment Guide List

6 - 4 ............. Gas Cylinder Storage RoomEquipment & Utility PlanDesign StandardsEquipment Guide List

6 - 5 ............. Acid Storage RoomEquipment & Utility PlanDesign StandardsEquipment Guide List

6 - 6 ............. Flammable Storage RoomEquipment & Utility PlanDesign StandardsEquipment Guide List

6 - 7 ............. Ultralow Freezer RoomEquipment & Utility PlanDesign StandardsEquipment Guide List

Page 323: VA guide -2009
Page 324: VA guide -2009

September 30, 1995

Guide Plate 6-1 VA Design Guide — Research Laboratory

Design StandardsCold Procedure Room

ARCHITECTURALFloor Area 7.5 m² (81 ft²)* Wall Finish prefab

Ceiling prefab Base -

Ceiling Height - Floor Finish prefab

RFI Shielding - Slab Depression yes

Soundproofing - Floor Load -

*Prefabricated, see PG-08-1 MCS 13062, H-08-3 CS 643-1

Lighting ELECTRICAL PowerGeneral 750 lx (70 fc) General GFI

Special - Special -

Incandescent fixtures Emergency -

COMMUNICATIONSTelephone - ADP -

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights - Dry Bulb Temp Cooling 4°C (40°F)

AC Load Equipment - Dry Bulb Temp Heating -

Number of People - Relative Humidity - Cooling - %

Noise Criteria - Relative Humidity - Heating - %

Room Pressure - Minimum % Outside Air -

Min Air Changes per Hour - 100% Exhaust Air -

Steam - Special Exhaust -

Provide minimum 42 m³/s (25 cfm) supply and exhaust air.

PLUMBING AND LABORATORY GASESSanitary Drain yes Cold Water yes

Acid Waste - Hot Water yes

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 325: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Guide Plate 6-1

Equipment Guide ListCold Procedure Roomqty symbol ai description

AR CC COLD PROCEDURE ROOM, PREFABRICATED WALK-IN, SIZE AS SPECIFIED BYRESEARCH SERVICE, TEMP. RANGE, 0 DEGREES C TO 4 DEGREES C (PG-08-1,MCS 11615)

AR CC SHELVING, ADJUSTABLE, ALUMINUM OR STAINLESS STEEL, PERFORATED, 457 MM(18”) DEEP (PG-08-1, MCS 11615)

1 CC DRAIN, FLOOR (PG-08-1, MCS 15400)

1 TOP 5 CF COUNTER TOP, CORROSION RESISTING (STAINLESS) STEEL, RAISED RIM, WITHINTEGRAL SINK AND SPLASHBACKS (PG-08-1 & PG-08-6, MCS 11602)

1 R-2 CF SINK, CORROSION RESISTING STEEL, WITH END OR CORNER DRAIN OUTLET, 457MM X 457 MM X 406 MM (18” X 18” X 16”) (PG-08-1 & PG-08-6, MCS 11602)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, WITH GROUND FAULTINTERRUPTER (PG-08-1, MCS, 16140; H-08-3, CS 801-3)

Page 326: VA guide -2009
Page 327: VA guide -2009
Page 328: VA guide -2009

September 30, 1995

Guide Plate 6-2 VA Design Guide — Research Laboratory

Design StandardsGlassware Washing and Sterilization Room

ARCHITECTURALFloor Area 38 m² (406 ft²) Wall Finish cmu/sc

Ceiling at (sp) Base erf

Ceiling Height 2700 mm (9 ft) Floor Finish erf

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

SPECIAL EQUIPMENTHW517 Glassware washing machine VS260 Sterilizer

DW 911 Still K3010 Ice Machine

Lighting ELECTRICAL PowerGeneral 750 lx (70 fc) General -

Special 1100 lx (100 fc) task Special -

Louvered deep cell parabolic fixtures, T-8 lamps Emergency -

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 1120 W Dry Bulb Temp Cooling 27 C (80°F)

AC Load Equipment 65 W/m² (6.0 W/ft²) Dry Bulb Temp Heating 21 C (70°F)

Number of People 2 to 3 Relative Humidity - Cooling 60%

Noise Criteria NC-40 Relative Humidity - Heating - %

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 15 100% Exhaust Air yes

Steam 275 kPa (40-60 psig) Special Exhaust yes

See PG-08-6 for steam, heat gain, & exhaust capacities. See PG-08-4 Volume 3 Section II for Type ‘B’ hooddetails.

Provide a dedicated exhaust system with liquid-tight stainless steel ductwork.

Limit temp rise in service area to 8.3°C (15°F) above disassembling area.

PLUMBING AND LABORATORY GASESSanitary Drain yes Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water yes

Fuel Gas - Laboratory Air yes

Nitrogen - Laboratory Vacuum -

Page 329: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 6-2

Equipment Guide ListGlassware Washing and Sterilization Roomqty symbol ai description

1 HW517 CC WASHING MACHINE, LABORATORY GLASSWARE AND UTENSILS, RECESSED, 660MM X 483 MM (26” X 19”), BASKET OR SPINDLE HEADER OR PIPETTE HEADER,WITH HEADER TRANSFER DOLLY, 1143 MM X 1067 MM X 2286 MM (45” X 42” X 90”)(PG-08-1 & PG-08-6, MCS 11714)

1 DW911 VV STILL, WATER, HIGH PURITY, 19 L (5 GAL.) PER HOUR, COUNTER MOUNTED, 635MM X 406 MM X 1143 MM (25” X 16” X 45”), 208 VOLT, 40 AMP, SINGLE PHASE (PG-08-1, MCS 11612)

1 CC UTILITIES FOR ELECTRIC STILL, ELECTRIC OUTLET, 208 VOLT, 50 AMP, 1 PHASE,WATER AND WASTE FROM ADJACENT SINK

1 VS260 CC STERILIZER, LABORATORY, RECESSED, CHAMBER SIZE: 610 MM X 914 MM X 1219MM/.68 M3 (24” X 36” X 48”/24 CU. FT.), (PG-08-1 & PG-08-6, MCS 11710)

AR CC HOOD, EXHAUST, OVER STERILIZER DOOR (PG-08-1, MCS 15840)

AR VV OVEN, DRYING, FLOOR MOUNTED, 208 VOLT, 3000 WATT

1 CC SINK, CORROSION RESISTING STEEL, 2 COMPARTMENT, EACH SINK 559 MM X 406MM X 279 MM (22” X 16” X 11”), WITH FAUCET AND RINSE HOSE ASSEMBLY (PG-08-1, MCS 11602)

1 VL20/20A

CF CABINET, UNDERCOUNTER, SINK UNIT, 2 HINGED PANEL DOORS, WIDTH - 1219MM (48”); DEPTH - 559 MM (22”); HEIGHT - 787 MM (31”); FOR FLOOR MOUNTEDADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

AR CF COUNTER TOP, CORROSION RESISTING STEEL, 32 MM (1-1/4”) THICK

AR VL1/1A CF CABINET, UNDERCOUNTER, WITH 4/3 DRAWERS, WIDTH - 914 MM (36”); DEPTH -559 MM (22”); HEIGHTS - 787 MM (31”); FOR FLOOR MOUNTED ADD 127 MM (5”) TOEBASE (PG-08-1 & PG-08-6, MCS 12345)

-OR-

AR VL4/4A CF CABINET, UNDERCOUNTER, WITH 2 DRAWERS, 2 HINGED DOORS AND 1ADJUSTABLE SHELF, WIDTH - 1219 MM (48”); DEPTH - 559 MM (22”); HEIGHT - 787MM (31”); FOR FLOOR MOUNTED ADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6,MCS 12345)

AR VL7/7A CF CABINET, UNDERCOUNTER, WITH 2 HINGED DOORS AND 2/1 ADJUSTABLESHELVES, WIDTHS - 914 MM (36”); DEPTH - 559 MM (22”); HEIGHTS - 787 MM (31”);FOR FLOOR MOUNTED ADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

AR VL14 CF TABLE FRAME, WITH DRAWER(S), KNEE SPACE UNIT, WIDTH - 1067 MM (42”);DEPTH - 559 MM (22”); HEIGHT - 787 MM (31”) (PG-08-1 & PG-08-6, MCS 12345)

AR VL29 CF CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORS AND 2ADJUSTABLE SHELVES, WIDTH - 914 MM (36”,); DEPTH - 406 MM (16”); HEIGHT - 762MM (30”) (PG-08-1 & PG-08-6, MCS 12345)

Page 330: VA guide -2009

September 30, 1995

Guide Plate 6-2 VA Design Guide — Research Laboratory

Equipment Guide ListGlassware Washing and Sterilization Roomqty symbol ai description

AR VV TABLE, WORK, 864 MM X 1524 MM X 762 MM (34” X 60” X 30”)

1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED

1 K3010 CC MACHINE, ICE MAKING (CRUSHED) AND DISPENSING, AUTOMATIC, FLOORMOUNTED, 45 KG (100 LB.), BIN, 120 VOLT, 20 AMP, 710 MM X 658 MM X 2108 MM(28” X 25” X 82”) (PG-08-1 & PG-08-6, MCS 11415)

1 CC DRAIN, FLOOR (PG-08-1, MCS 15400)

1 VV CLOCK, BATTERY OPERATED

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 15 AMP, STRIP MOLD WITHOUTLETS, WIRED ALTERNATELY ON SEPARATE CIRCUITS ON 610 MM (24”)CENTERS ABOVE COUNTER (PG-08-1, MCS 16140; H-08-3, CS 801-3)

AR CC RECEPTACLE, ELECTRICAL, 208 VOLT, 20 AMP, 1 PHASE, ON WALL,WEATHERPROOF (PG-08-1, MCS 16140; H-08-3, CS 801-3)

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 331: VA guide -2009
Page 332: VA guide -2009
Page 333: VA guide -2009

September 30, 1995

Guide Plate 6-3 VA Design Guide — Research Laboratory

Design StandardsTissue Culture Laboratory

ARCHITECTURALFloor Area 9 m² (97 ft²) Wall Finish gwb

Ceiling at Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

SPECIAL EQUIPMENTH12-78 Laminar Flow Hood

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special 1100 lx (100 fc) task Special -

Louvered deep cell parabolic fixtures, T-8 lamps Emergency -

COMMUNICATIONSTelephone yes ADP yes

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 420 W Dry Bulb Temp Cooling 25°C (78°F)

AC Load Equipment 36 W/m² (3.6 W/ft²) Dry Bulb Temp Heating 22°C (72°F)

Number of People 1 Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure positive Minimum % Outside Air 100

Min Air Changes per Hour 12 100% Exhaust Air yes

Steam - Special Exhaust -

See PG-08-10 HVAC for exhaust requirements for specific laminar flow hood type.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water yes

Acid Waste yes Hot Water yes

Other - Reagent Grade Water yes

Fuel Gas yes Laboratory Air yes

Nitrogen - Laboratory Vacuum yes

Page 334: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 6-3

Equipment Guide ListTissue Culture Laboratoryqty symbol ai description

1 H12-54/78

CC CABINET, AIR FLOW, BIOLOGICAL WITH LAB AIR, FUEL GAS AND LAB VACUUMOUTLETS, 120 VOLT, 20 AMP, RECEPTACLE (PG-08-1 & PG-08-6, MCS 11604)

1 VL32 CF CABINET, WALL, OPEN WITH SLOPING TOP AND 2 ADJUSTABLE SHELVES, WIDTHS- 1219 MM (48”); DEPTH - 330 MM (13”); HEIGHT - 762 MM (30”) (PG-08-1 & PG-08-6,MCS 12345)

1 VL3/3A CF CABINET, UNDERCOUNTER, WITH 5/4 DUST SEAL DRAWERS, WIDTH - 610 MM (24”);DEPTH - 559 MM (22”); HEIGHTS - 787 MM (31”); FOR FLOOR MOUNTED ADD 127MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

1 VL20/20A

CF CABINET, UNDERCOUNTER, WITH 5/4 DUST SEAL DRAWERS, AVAILABLE WIDTHS -914 MM (36”); DEPTH - 559 MM (22”); HEIGHTS - 787 MM (31”); FOR FLOORMOUNTED ADD 127 MM (5”) TOE BASE (PG-08-1 & PG-08-6, MCS 12345)

1 S-3 CF SINK, MOLDED, RESIN WITH END OR CORNER DRAIN OUTLET, 635 MM X 457 MM X406 MM (25” X 18” X 16”) (PG-08-1 & PG-08-6, MCS 11602)

1 TOP 13/13A

CF COUNTER TOP, EPOXY, RESIN, WITH DRIP GROOVE, 25 MM (1”) THICK, 762 MM(30”) DEEP ALONG WALL (PG-08-1 & PG-08-6, MCS 11602)

1 VV TABLE, BALANCE

1 VL53 VV INCUBATOR, BACTERIOLOGICAL, 120 VOLT, 1.5 KW

1 VV CLOCK, BATTERY OPERATED

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 335: VA guide -2009
Page 336: VA guide -2009

September 30, 1995

Guide Plate 6-4 VA Design Guide — Research Laboratory

Design StandardsGas Cylinder Storage Room

ARCHITECTURALFloor Area 9 m² (97 ft²) Wall Finish cmu

Ceiling gwb Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish c (treated)

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

Lighting ELECTRICAL PowerGeneral 325 lx (30 fc) General -

Special - Special -

Emergency - Emergency -

COMMUNICATIONSTelephone - ADP -

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 140 W Dry Bulb Temp Cooling 26°C (78°F)

AC Load Equipment - Dry Bulb Temp Heating 22°C (72°F)

Number of People - Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour * 100% Exhaust Air yes

*Min 4 air changes per hour or 0.005 m³/s per m² (1 cfm per ft²) of floor area.

NFPA 55 requirements must be met.

Provide continuous gas detection system with ECC alarm and local alarm at continuously attended location.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water -

Acid Waste - Hot Water -

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 337: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 6-4

Equipment Guide ListGas Cylinder Storage Roomqty symbol ai description

NOTE: CONSTRUCTION TO COMPLY WITH NFPA 68, CHAPTER 4.

AR CC RACK, CYLINDER, 711 MM X 559 MM X 1930 MM (28” X 22” X 76”) (PG-08-1, MCS10360; H-08-4, SD 64C)

AR CC RACK, CHAIN (PG-08-1, MCS 10360; H-08-4, SD 64C)

2 VV CART, CYLINDER, 610 MM X 762 MM (24” X 30”)

Page 338: VA guide -2009
Page 339: VA guide -2009

September 30, 1995

Guide Plate 6-5 VA Design Guide — Research Laboratory

Design StandardsAcid Storage Room

ARCHITECTURALFloor Area 9 m² (97 ft²) Wall Finish cmu

Ceiling gwb Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish c (treated)

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special - Special -

Emergency - Emergency -

COMMUNICATIONSTelephone - ADP -

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 140 W Dry Bulb Temp Cooling 26°C (78°F)

AC Load Equipment - Dry Bulb Temp Heating 22°C (72°F)

Number of People - Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 4 100% Exhaust Air yes

Steam - Special Exhaust yes

Provide dedicated exhaust system for room, with acid resistant epoxy coating on exhaust fan.

Ductwork to be fiberglass reinforced polyester resin self-extinguishing material, or galvanized plastic coated (PVC)acid-resistant material.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water -

Acid Waste - Hot Water -

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 340: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 6-5

Equipment Guide ListAcid Storage Roomqty symbol ai description

NOTE: PROVIDE ADEQUATE VENTILATION AND TEMPERATURE CONTROL ASREQUIRED.

AR VV CABINET, STORAGE, LIQUID

AR T-7D CC SHELVING, WALL HUNG, STAINLESS STEEL, STANDARD AND BRACKET TYPE, 4ADJUSTABLE SHELVES, 914 MM X 457 MM X 1219 MM (36” X 18” X 48”), WITH LIPEDGES (PG-08-1, MCS 10671; H-08-4, SD 60D)

NOTE: P-707, EMERGENCY SHOWER, EYE AND FACE WASH TO BE LOCATEDIMMEDIATELY OUTSIDE OF ACID STORAGE ROOM.

Page 341: VA guide -2009
Page 342: VA guide -2009

September 30, 1995

Guide Plate 6-6 VA Design Guide — Research Laboratory

Design StandardsFlammable Storage Room

ARCHITECTURALFloor Area 9 m² (97 ft²) Wall Finish cmu/gwb

Ceiling gwb Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish c (treated)

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

Lighting ELECTRICAL PowerGeneral 325 lx (30 fc) General -

Special - Special -

Explotion proof incandescent fixtures with PAR38 halogenflood lamps on dimmer switch

Seal conduit in rigid steel

COMMUNICATIONSTelephone - ADP -

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 600 W Dry Bulb Temp Cooling 26°C (78°F)

AC Load Equipment - Dry Bulb Temp Heating 22°C (72°F)

Number of People - Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating 30%

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour * 100% Exhaust Air yes

Steam - Special Exhaust yes

*Min 6 air changes per hour or 0.005 m³/s per m² (1 cfm per ft²) of floor area, or 0.067 m³/s (150 cfm) exhaust.

NFPA 30 requirements must be met.

Provide a dedicated exhaust system for room.

Provide explosion-proof motor & spark-proof fan.

PLUMBING AND LABORATORY GASESSanitary Drain yes Cold Water yes

Acid Waste - Hot Water yes

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 343: VA guide -2009

September 30, 1995

VA Design Guide -- Research Laboratory Guide Plate 6-6

Equipment Guide ListFlammable Storage Roomqty symbol ai description

NOTE: PROVIDE ADEQUATE VENTILATION AND TEMPERATURE CONTROL ASREQUIRED.

AR VV RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

AR T-7D CC SHELVING, WALL HUNG, STAINLESS STEEL, STANDARD AND BRACKET TYPE, 4ADJUSTABLE SHELVES, 914 MM X 457 MM X 1219 MM (36” X 18” X 48”), WITH LIPEDGES (PG-08-1, MCS 10671; H-08-4, SD 60D)

AR T-6A CC SHELVING, FLOORSTANDING, STEEL, WITH SLOPING TOP AND 4 OR 5ADJUSTABLE SHELVES, 914 MM X 457 MM X 2134 MM (36” X 18” X 84”) (PG-08-1,MCS 12301; H-08-4, SD 60B)

1 VL25 CF CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORS AND 2ADJUSTABLE SHELVES, AVAILABLE WIDTHS - 762 MM (30”); DEPTH - 330 MM (13”);HEIGHT - 762 MM (30”) (PG-08-1 & PG-08-6, MCS 12345)

1 TOP 13/13A

CF COUNTER TOP, EPOXY, RESIN, WITH DRIP GROOVE, 25 MM (1”) THICK (PG-08-1 &PG-08-6, MCS 11602)

1 S-3 CF SINK, MOLDED, RESIN WITH END OR CORNER DRAIN OUTLET, 635 MM X 457 MM X406 MM (25” X 18” X 16”) (PG-08-1 & PG-08-6, MCS 11602)

1 VV EMERGENCY EYE AND FACE WASH, MOUNTED ON GOOSENECK FAUCET

Page 344: VA guide -2009
Page 345: VA guide -2009
Page 346: VA guide -2009

September 30, 1995

Guide Plate 6-7 VA Design Guide — Research Laboratory

Design StandardsUltralow Freezer Room

ARCHITECTURALFloor Area 18.5 m² (198 ft²) Wall Finish cmu (sc)

Ceiling gwb Base rb

Ceiling Height 2700 mm (9 ft) Floor Finish vct

RFI Shielding - Slab Depression -

Soundproofing - Floor Load -

Lighting ELECTRICAL PowerGeneral 550 lx (50 fc) General -

Special - Special -

Emergency - Emergency -

COMMUNICATIONSTelephone yes ADP -

HEATING, VENTILATING AND AIR CONDITIONINGAC Load Lights 420 W Dry Bulb Temp Cooling 22°C (72°F)

AC Load Equipment 161 W/m² (15.0 W/ft²) Dry Bulb Temp Heating -

Number of People - Relative Humidity - Cooling 50%

Noise Criteria NC-45 Relative Humidity - Heating - %

Room Pressure negative Minimum % Outside Air 100

Min Air Changes per Hour 30 100% Exhaust Air yes

Steam - Special Exhaust yes

Freezers have air-cooled compressors. Freezer temperature -62.2°C (-80°F).

Provide heat recovery system, if cost effective based on life cycle cost, to apply to an appropriate system in thebuilding. See PG-08-10 HVAC for type of heat recovery system that may be employed.

PLUMBING AND LABORATORY GASESSanitary Drain - Cold Water -

Acid Waste - Hot Water -

Other - Reagent Grade Water -

Fuel Gas - Laboratory Air -

Nitrogen - Laboratory Vacuum -

Page 347: VA guide -2009

September 30, 1995

VA Design Guide — Research Laboratory Guide Plate 6-7

Equipment Guide ListUltralow Freezer Roomqty symbol ai description

AR VV FREEZER, ULTRALOW, UPRIGHT

AR VV FREEZER, LIQUID NITROGEN, 1219 MM X 914 MM (48” X 36”)

AR VV TANK, LIQUID NITROGEN, 610 MM (24”) DIAMETER

AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 30 AMP, DEDICATED CIRCUIT (PG-08-1, MCS 16140)

AR CC RECEPTACLE, ELECTRICAL, 208 VOLT, 20 AMP, 1 PHASE, ON WALL,WEATHERPROOF (PG-08-1, MCS 16140; H-08-3, CS 801-3)

NOTE: PROVIDE MONITORING SYSTEM IF CARBON DIOXIDE IS USED.

Page 348: VA guide -2009

Department of Veterans AffairsVeterans Health AdministrationOffice of Facilities Management

Facilities Quality OfficeStandards Service

202 565 6775

VA Design Guide

Magnetic ResonanceImaging (MRI)

28 September 1995

Final Draft

UPDATED 7 NOV. 96

Page 349: VA guide -2009

FINAL DRAFT 9/28/95

DEPARTMENT OF VETERANS AFFAIRS VETERANS HEALTH ADMINISTRATIONOFFICE OF FACILITIES MANAGEMENT STANDARDS SERVICE 202.565.6775

VA DESIGN GUIDEMAGNETIC RESONANCEIMAGING

Page 350: VA guide -2009

FINAL DRAFT 9/28/95

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING FOREWORD

.

ForewordThe material contained in the Magnetic

Resonance Imaging Design Guide is theculmination of a partnering effort by theDepartment of Veterans Affairs Veterans HealthAdministration and the Facilities Quality Office. The goal of the Design Guide is to ensure thequality of VA facilities while controllingconstruction and operating costs.

This document is intended to be used as aguide and as a supplement to current technicalmanuals and other VA criteria in the planning ofMagnetic Resonance Imaging. The DesignGuide is not to be used as a standarddesign, and use of this Design Guide doesnot limit the project Architect’s andEngineer’s responsibilities to develop acomplete and accurate project design thatbest meets the user’s needs and theapplicable code requirements.

Lloyd H. Siegel, FAIADirector, Facilities Quality Office

Page 351: VA guide -2009

FINAL DRAFT 9/28/95

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING CONTENTS

Contents

Section 1.........................................IntroductionAcknowledgments

AbbreviationsLegend of Symbols

Section 2.............................................Narrative

Section 3........................ Relationship Diagrams

Section 4.........Design Guide Plates and Design Standards: Patient Care Areas

Page 352: VA guide -2009

FINAL DRAFT 9/28/95

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING SECTION 1

Section 1Introduction,Acknowledgments,Abbreviations, andLegend of Symbols

Page

Introduction .................................................1 - 1

Acknowledgments .......................................1 - 2

Abbreviations ..............................................1 - 3

Legend of Symbols .....................................1 - 4

Page 353: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingIntroduction

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 1-1

The Magnetic Resonance Imaging (MRI)Service Design Guide is intended to be agraphic consolidation of existing Department ofVeterans Affairs standards and criteria. Itcontains data from the following sources:

PG-18-1 Master Construction Specifications

H-18-3 Construction Standards

PG-18-4 Standard Details

PG 7610 Equipment Guide List

PG-18-6 List of Equipment Symbols

PG 7610 Space Planning Criteria

PG-18-13 Barrier-Free Design Handbook

PG-18-14 Room Finish and Door HardwareSchedule

Various Technical Criteria (Design Manuals)pertaining to Architectural, HVAC, Plumbing,and Electrical.

Consensus information from various VAmedical centers.

MRI Service Program Division

The Design Guide refers to the abovementioned sources when data is either toodetailed or too broad to be included in this guide.

The Design Guide for MRI was developed as adesign tool to assist the medical center staff andthe contracting officers in better understandingthe choices that designers ask them to make,and to help designers understand the functionalrequirements necessary for proper operation ofthe MRI.

The Guide Plate contained in the MRI DesignGuide is intended to illustrate VA's furniture,equipment and personnel space needs. It is notmeant to limit design opportunities.

This Design Guide is not intended to be project-specific. While it does contain spaces requiredin MRI, it is not possible to foresee futurerequirements. The project-specific spaceprogram is the basis for an individual projectdesign. It is important to note that the guideplate is a generic graphic representation only.

Equipment manufacturers should be consultedfor actual dimensions and utility and shieldingrequirements. Use of this Design Guide doesnot supersede the project architects' andengineers' responsibilities to develop a completeand accurate design that meets the user's needsand appropriate code requirements.

Page 354: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingAbbreviations

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 1-3

A AmperesAC/HR Air Changes per HourADA Americans with Disabilities ActAFF Above Finished FloorAI Acquisition and InstallationA&MM Acquisitions and Material

ManagementAR As RequiredAT Acoustical Ceiling TileC Degrees CelsiusCC Contractor Furnished and Installed,

Construction FundsCF Construction Funds, VA Furnished,

Installed by VA or ContractorCFM Cubic Feet per MinuteCLG CeilingCM Construction Management OfficeCMU Concrete Masonry UnitCP Carpet (without cushion broadloom)CS Construction StandardCT Ceramic TileDISC SW Disconnect SwitchEtO Ethylene Oxide GasEPO Emergency Power OffEXH ExhaustF Degrees FahrenheitFC Foot-candleFD Floor DrainFIXT FixtureFLUOR FluorescentHAC Housekeeping Aids ClosetHVAC Heating, Ventilation, and Air

ConditioningHP HorsepowerHR HourICU Intensive Care UnitKW KilowattLB Pound/PoundsLLTS Lounge, Lockers, Toilets, and

ShowersMCS Master Construction SpecificationsMTD MountedNA Not Procured with Activation FundsNFPA National Fire Protection AssociationNSF Net Square FeetNSM Net Square MetersOSD Open Site DrainPCP Portland Cement PlasterPH PhasePL Plaster

PREP PreparationPSIG Pounds per Square Inch GaugeQT Quarry TileRB Resilient BaseSC Special Coating (High Build Glazed

Coating)SD Standard DetailSF Square Feet, Square FootSPD Supply, Processing, and DistributionSOPC Satellite Outpatient ClinicSS Stainless SteelTELEC TelecommunicationsUFAS Uniform Federal Accessibility

StandardsV VoltsVA Department of Veterans AffairsVACO Veterans Affairs Central OfficeVAMC Veterans Affairs Medical CenterVC VA Furnished and Contractor

Installed - Medical CareAppropriation for Equipment andConstruction Appropriations forInstallation

VCT Vinyl Composition TileVHA Veterans Health AdministrationVV VA Furnished and Installed-VHA

AppropriationW WattsW/SF Watts per Square Feet

Page 355: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingAcknowledgments

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 1-2

Credit is due to the following individuals whose guidance, advice, and effort made this publicationpossible:

CONSTRUCTION MANAGEMENT OFFICE

C.V. Yarbrough Chief Facilities Management Officer

Robert L. Neary, Jr. Deputy Chief Facilities Management Officer

Lloyd H. Siegel, FAIA Director Facilities Quality Office

Leo A. Phelan, AIA Director, Standards Service

Mark G. Hall Design Guide Developer Architect

William J. Leahy Architect

Wesley C. Wheeler Jr. Architect

Jim D. Holtschulte Landscape Architect

Jennifer S. Webb Intern Architect

Sheila C. Jackman Program Support Assistant

Frances C. Wells Secretary

Satish Sehgal Mechanical Engineer

E.T. Minter Plumbing & Sanitary Engineering

CRITERIA, POST OCCUPANCY EVALUATIONAND PLANNING SUPPORT SERVICE

Fred Amthor Chief, Criteria Division

John Sibenik Criteria Division

Francis Kernan Chief Planning Support Division

Al Wong Equipment Criteria

MRI PROGRAM DIVISION

Roger H. Shannon, M.D. DirectorRadiology Service (114)

Michael Hughes Chief Technology Division (114)

PRIVATE SECTOR CONSULTANTS

Kevin D. Carter, A.I.A. Smith Hinchman &Grylls

Associates

Page 356: VA guide -2009
Page 357: VA guide -2009
Page 358: VA guide -2009
Page 359: VA guide -2009

FINAL DRAFT 9/28/95

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING SECTION 2

Section 2Narrative

Page

General Considerations...............................2 - 1

Functional Considerations ...........................2 - 1

Technical Consideration ..............................2 - 5

Page 360: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-1

I. General Considerations

A. Overview

1. Current Direction

Magnetic Resonance Imaging (MRI) is aspecialized diagnostic imaging toolemploying a strong magnetic field and theapplication of a radio frequency pulse tomeasure vector deflection of selectedatomic nuclei.

MRI is particularly useful in providingimages of soft tissues.

MRI is contra-indicated for patients withcardiac pacemakers or ferro-magneticaneurysmal clips.

The emitted magnetic field can effectCRT's and information systems. Therefore,great care must be employed in selecting asite location for the MRI.

Patient volume can be anticipated to beprimarily 80-90% outpatient volume.

When shared among multiple medicalcenters, mobile MRI units (docked to areaswith appropriate patient and staff spaces)may be a viable alternative to fixed MRIunits.

2. Trends

Magnetic Resonance Angiographytechnology is increasingly used.

MRI in combination with computed AxialTomography (CT) for comprehensivescreening of diseases that are difficult todiagnose in early stages (such as multiplesclerosis) is also increasingly used.

II.Functional Considerations

A. Operations

1. Services

Magnetic Resonance Imaging is a programunder Radiology Service. MRI should becoordinated with associated andcomplimentary diagnostic services toassure coordination of patient care.

a. Imaging Process

MRI is performed on inpatients andoutpatients on a regular and scheduledbasis. Services are also performed on anunscheduled basis for emergency patients.

MRI uses strong magnetic fields to inducemolecular resonance which creates radiofrequencies. These frequencies allow acomputer image to be created by theanalysis of measurements of frequenciesemitted by resonating cell structures.

The image is electronically enhanced,recorded on video, stored on tape or opticaldisk and reproduced as a laser image. Theimage can also be outputted to paper orfilm copy.

2. Patient Care Concept

MRI remains a centralized function due tothe high cost of the technology, the highlyspecialized space criteria (dictated bypermanently installed equipment), and thespecialized staffing requirements.

Page 361: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-2

3. Level of Care

A single MRI will most often be HospitalBased, as this location provides the mostuniversal and hopefully convenient location.

4. Patient Base

VA MRI Facilities need to demonstrate anability to generate sufficient workload tojustify the substantial cost. This is basedon a cost benefit analysis.

VA MRI facilities are focused upon servingthe Veteran, and may participate in sharingagreements, joint ventures, and referrals. Also, efforts are made to include theveteran’s family and the general public.

5. Medical Records

Diagnostic evaluations generated within thedepartment become part of the veteran’sConsolidated Health Record (CHR) withactual films and/or electronic data storedlocally within the MRI Facility or inRadiology Film Storage.

Evaluations are also communicated to theordering physician in either hard copy orelectronic form (as required).

Image manipulation, interpretation,archiving, retrieval and distributionprocedures may occur within the MRIFacility or may be consolidated withRadiology. These techniques includevarying levels of electronic and film recordstorage requirements and will effect finalspace requirements.

6. Patient Protocol

Outpatient and inpatient procedures areordered by physicians and scheduled bythe department during regular businesshours.

Unscheduled and off-hour procedures willdepend on the level of care to be provided.

7. Special Requirements

Teaching facilities will require moretechnical support space, including spacesfor small observation groups, interpretationareas, and image manipulation areas.

Coordination with related departments,facilities, and program missions is requiredto verify space needs. These may includeprep, recovery, exam, and stretcher holdingspaces.

Such departments may include:• Hospital-Nursing Care;• Long Term Care Facilities;• Ambulatory Services;• Emergency;• Surgery; and• Satellite Facilities.

B. Space Planning Issues

1. Flexibility

Certain technical space requirementsimpose special constraints on the siting anddesign of MRI facilities. These mayinclude:• Magnetic field generated by MRI

magnets;• The sensitivity of Imaging process to

radio frequencies (RF’s);• The size and weight of the magnet;• cryogen service; and• Venting requirements.

Page 362: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-3

Although specialized facilities are required,generic guidelines should be applied toaccommodate a wide range of MRItechnology to maximize equipmentselection options.

2. Efficiency

Economies of shared functions, facilities,and staff are increasingly facilitated by MRIsystems. “Self shielded” magnets allow MRItechnology to be located near operationswhich are sensitive to magnetic fields andnear fixed and moving metallic objectssuch as building structure, elevators andvehicular traffic.

3. Human Factors

Patient dignity and self-determination areaccommodated while consideringoperational efficiencies.

Patient's vulnerability to stress fromnoise, lack of privacy, poor lighting andother causes can have harmful effects onthe healing process. This is a well knownand documented phenomenon.

An inherent opportunity exists in thedesign of Magnetic Resonance ImagingFacilities to address these issues and putforth creative solutions that enhancepatient comfort and contribute to positiveoutcomes.

A prime objective should be tode-emphasize the institutional image oftraditional health care facilities and tosurround the patient (and familymembers) with architectural finishes andfurnishings that are familiar andnon-threatening.

Good planning and design appeal to thespirit and sensibilities of patients andcare providers alike.

Magnetic Resonance Imaging facilitiesshould be healing environments thatallow the building itself to become a partof the therapy. The technicalrequirements should be addressed in anintegrated manner to support theseconcepts.

Patient privacy is to be accommodatedwithout sacrificing facility utilization.

Security is addressed by planning,design, and detail considerations.

Handicapped access is accommodatedby the application of UFAS and ADAdesign standards to space and fixedequipment layouts.

4. Technical and Environmental

MRI shielding considerations includecontrol of magnetic fields and the isolationfrom external radio frequency interference.

Magnetic Shielding and Magnetic Fieldsiting considerations will vary with magneticfield strength and with the features of theequipment and manufacturer selected.

The environment effects on fieldhomogeneity and the effects of MagneticField on other technologies and surroundingmust be considered.

Employment of a registered health physicistshould be undertaken when the program isput together, as his/her recommendationswill determine shielding of equipment,thickness of walls, etc.

Page 363: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-4

C. Functional Space Relationships

1. Work Flow

a. Patient

Provide a single point of control forinpatients and outpatients.

b. Staff and Administrative Functions

Staff and Administrative areas are locatedoutside of patient traffic areas.

Staff functions may be located within thedepartment or in a convenient locationshared with another department (usuallyRadiology Service).

c. Patient Records and Work Orders

Patient records and Work Orders shouldmove among the administrative, filmprocessing, viewing, and interpretativefunctions should be separated from thepatient traffic wherever possible.

d. Clean and Soiled Materials

Locate Clean and Soiled Utility Functionsclose to the Patient areas that they supportand also away from patient traffic.

2. Organizational Concepts

a. Functional Plan

Reception is strategically located to controlaccess to the patient areas and to securethe MRI from unauthorized access

The MRI Control Area and the ElectronicsRoom need to be Adjacent to the MRIProcedure Room

b. Building Systems Integration

Coordinate locations of depressed slabsand structure for equipment, electricalaccess, and magnetic and/or radiofrequency shielding.

Evaluate need for computer access flooringon a project basis.

Consider size and weight of magnet whenestablishing locations. This could relegatelocations on the lower or the lowest floors ofthe facility.

The radiation problem must also beconsidered in relation to adjacent areas.

c. Organization To Minimize MagneticShielding and Field Constraints

Both magnetically shielded and unshieldedMRI systems require consideration ofmagnetic fields when establishing room andequipment layouts.

Steel-support structures arranged in afashion not symmetrical to the magneticfield impose special requirements forshielding.

Installation within multiple story facilitiesmay impose planning and structuralrestrictions on spaces above and below.

3. Location / External Relationships

a. Patient Access / Wayfinding

MRI Facilities should be located convenientto parking, ambulatory care, and inpatientaccess.

Location with other diagnostic facilitiesassists in wayfinding and coordination ofpatient services.

Page 364: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-5

b. Functional Adjacencies

The MRI facility benefits from a locationnear Radiology as they may share staff andfacilities

c. Service Access

Magnet installation and replacementrequires crane access and a direct route formagnet passage.

Cryogen venting during quenching isaccomplished by a direct vent to outdoors.

Cryogen replenishment is accomplished viacryogen dewars which may be stored onsite. Access is required around and abovethe magnet for cryogen service.

III. Technical Considerations

A. Architectural

1. Interior Materials and Finishes

a. Partitions

Interior partitions should primarily bepainted gypsum wallboard on metalstuds. Partitions around physicianoffices, exam rooms and treatmentrooms should have sound attenuationbatts between the studs in accordancewith VA Construction Standard H-18-3and Standard 34-1, “Noise TransmissionControl”.

Partitions and doors around the MRIGantry Room should provide radiofrequency (RF) shielding and beconstructed of non-magnetic materials.

Coordinate RF Shielding requirementswith the equipment manufacturer andhave them reviewed by a registeredhealth physicist.

b. Floors

Floors in offices, conference rooms andwaiting areas should be carpet with a 100mm (4”) high resilient base.

Floors in toilet rooms should be ceramictile with a ceramic tile base. If metaltoilet stalls are used, be certain they areremotely located

Floors in most other spaces should bevinyl composition tile with a 100 mm (4”)high resilient base.

Floors in MRI Gantry Rooms require a 40mm (1-1/2”) deep depression toaccommodate the RF shielding.

Page 365: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-6

A computer/access floor system may berequired in the MRI computer room andpart of the Gantry Room. The accessfloor system should be of non-magneticmaterials.

c. Ceilings

Ceilings should be primarily lay-inacoustic ceiling tile. The ceilingsuspension system in the MRI GantryRoom should also be of non-magneticmaterials.

Non-magnetic materials should be usedin the vicinity of the gantry room.

d. Protection

Wall and corner guards should be usedin corridors and other areas where walldamage from cart traffic is anticipated.

2 Interior Doors and Hardware

Interior doors should be 45 mm (1 3/4")thick, solid-core, flush-panel wood doorsor non-magnetic hollow metal doors andhollow metal frames.

Doorjambs should have hospital typesanitary stops that stop 200 mm (8”) fromthe floor to facilitate mopping. Hollowmetal doors should be used where highimpact is a concern and where fire rateddoors are required. Non-magnetic kick /mop plates should generally be applied toboth sides of the doors. Handicappedaccessible hardware should be usedthroughout.

All metal in the vicinity of the gantry roomshall be non-magnetic.

Refer to VA Program Guide PG-08-14,“Room Finishes, Door and HardwareSchedule” for additional information.

B. Equipment

1. Casework

Casework systems should be chosento provide flexibility in planning andutilization purposes.

Casework systems should incorporatecomponents dimensioned for ease ofmultiple re-use installationapplications.

Casework systems should be plannedwithout corner installations and fillerpanels.

2. Information Management Systems

Information Management Systems shallinclude elements such as:

• image retrieval• processing / storage• treatment planning• patient registrations• patient charges• physician’s order entry• patient/staff movement

They also may require additionalshielding.

These systems’ elements will requireaccess to the main facility’s “informationbackbone” as well as the departmentalLocal Area Network (LAN). Allcomponents should be planned forcompatibility.

3. Therapy Systems

Imaging systems’ requirements will varyfor each facility and the technology maybe deferred in selection/procurement. Design requirements will be as instructedby the Contracting Officer.

Page 366: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-7

4. Film Processing

Film processing requirements will vary foreach facility. Design criteria for “digitallaser” and the integrated use of PictureArchiving and Communications Systems(PACS), will be as instructed by theContracting Officer.

C. Heating, Ventilation and AirConditioning

1. Operation

Air conditioning systems should beprovided to heat, cool and ventilate theindividual space, as required to satisfythe VA design criteria. Follow TB Criteriain the HVAC Design Manual for hospitalprojects.

The air conditioning systems serving theMRI area should be designed to operateat full capacity which will be determinedby local conditions. A dedicatedcomputer-type AC unit should beconsidered to cool and heat the computerequipment room. Theengineers/designers should verify the ACrequirements with equipment supplier.

Client requirements must coordinate withthe final system.

All ductwork downstream of the radiofrequency shielding (RF) shall be non-ferrous type and should be equipped withradio frequency dampers. Provide adedicated vent line located above themagnet isocenter.

2. Capacities

The number of people and the airconditioning load noted on the roomdesign standard sheet establishes a basefor the design guide and its use inplanning.The engineers/designers shouldverify the actual number of people andthe air conditioning load to agree with theproject requirements.

Similarly, engineers/designers shouldverify equipment AC loads shown or peractual equipment furnished on a project.

The percent of outside air should bebased on the space’s total supply airquantities.

3. Air Quality and Distribution

Corridors should not be used to supply orto exhaust/return air from rooms. Corridor air may be used to ventilatetoilet rooms, and small electrical ortelephone closets opening directly oncorridors. Exfiltration / infiltration frompositive/ negative pressure roomsadjacent to a corridor should beconsidered in balancing air flow..

The transferred air should be more than2.8m3/min (100cfm) per undercut door.

Care should be taken to minimize theshort-circuiting of air between supply andreturn and or/exhaust openings in interiorrooms.

The MRI Gantry Room shall be providedwith duct-mounted temperature andrelative humidity sensors with remoteadjustment capability. The sensors shallbe located in the return air duct.

Page 367: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-8

4. Exhaust System

Provide a dedicated exhaust system toemergency exhaust the cryogendischarge into the room. The fan shall beactivated via an oxygen sensor locatedinside the MRI Gantry Room.

5. Seismic

Where required, install the HVACsystems with seismic provisions asoutlined in the VA HVAC Design Manualfor Hospital Projects.

Refer to VA Construction StandardHandbook PG-18-03 (CD-54), “NaturalDisaster Resistive Design Non-Structural” for additional information.

6. Noise Level

Select HVAC equipment, ductwork andair distribution devices to achieve noiselevels listed in the VA HVAC DesignManual for Hospital Projects.

D. Plumbing

1. Water and Waste Systems

The plumbing systems should beprovided to satisfy the departmentalplumbing needs.

The department’s domestic cold watershould be piped to all plumbing fixturesand equipment requiring this utility. A hotwater return system should be providedto ensure the design temperature at thefarthestoutlet.

The department’s plumbing fixtures anddrains should be drained by gravitythrough soil, waste, and vent stacks. Inaddition, the department’s special wasteshould be drained through corrosion-resistant, flame- retardant piping intoeither a local or centralized acid dilutiontank.

2. Medical Gas Systems

The department’s medical gas outletsare shown to establish a base for thedesign guide and its use in planning. Theengineers/designers shall verify themedical gas location and quantities forindividual projects.

All equipment shall be non-magnetic.

3. Seismic

Where required, the plumbing andmedical gas systems should be installedwith seismic provisions, as outlined in theVA Plumbing Design Manual for HospitalProjects.

Refer to VA Handbook H-18-03 (CD-54),“Natural Disaster Resistive Design Non-Structural” for additional information.

4. Fire Protection

The recommended fire protection for theMRI Gantry and Computer EquipmentRooms are either preaction or dry pipesystems in lieu of the standard wetsystem.

Page 368: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-9

E. Electrical

1. Illumination

Illumination is typically provided utilizingrecessed fluorescent luminaries withacrylic prismatic lenses. The fixturestypically use F32T8 lamps in compliancewith the National Energy Policy Act of1992. Lamps have a minimum colorrendering index (CRI) of 85 and a colortemperature of 4100 degrees Kelvin (K),which is close to the "cool white" colortemperature of 4150 degrees K.

Lighting intensities conform to the VAdesign criteria, the IES LightingHandbook and IES publication CP-29,"Lighting for Health Care Facilities". IESCP-29 is currently being updated and willbe replaced by IES

Recommended Practice RP-29 in thefuture.

Lighting is typically controlled by wall-mounted switches located at theentrance to the room. Larger spacesmay utilize multiple switching by separateswitches for lighting of individual zones orareas.

Power load densities for lighting arelisted by use for the mechanical HVACload calculation purposes. Loaddensities should be verified for the actualdesign, as they may vary depending onthe room configuration, fixture types,lamps and ballasts used.

2. Power

MRI power requirements have to becoordinated with the equipmentmanufacturer.

General purpose duplex receptacles aretypically provided on each wall of a roomor space.

Workstations with personal computers(PC's) are typically provided withquadraplex receptacles for the PC,monitor, and printer.

Junction boxes are provided forequipment requiring a hardwiredconnection. Provide non-magnetic boxesin the gantry room.

Certain modular casework units areprovided with a utility access module withsurface-mounted electrical strip moldwhich also provides a chase for wiring. Conduits and junction boxes are providedto connect to the utility access module forpower wiring.

Duplex receptacles on the critical branchof the emergency power system areprovided for selected pieces ofequipment (such as refrigerators) to allowfor limited operation during a poweroutage.

F. Life Safety

1. Purpose

The life safety program should bedeveloped to provide a reliable system toprotect the building occupants, fire-fighting personnel, building contents,building structure, and building function.

This can be accomplished by limiting thedevelopment and spread of a fireemergency to the area of origin andthereby reduce the need for totaloccupant evacuation.

Page 369: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-10

The design aspects of the facility whichrelate to the fire and life safety include:

• Structural fire resistance;• Building compartmentalization;• Fire detection, alarm and

suppression;• Smoke control and exhaust;• Firefighter access and facilities; and• Emergency power.

New hospital construction and renovatedareas of existing facilities are required tobe fully protected by an automatic firesuppression system.

The minimum width of corridors andpassageways in MRI areas is 1100 mm(44”) in areas to be used only by staff. The minimum width of corridors in areasthat will also be used by inpatients is2400 mm (96”).

Provide handrails on both sides of thecorridors in patient areas.

Nurses’ stations are permitted to be opento the corridor.

Waiting areas are also permitted to beopen to the corridors.

Refer to the latest editions of NFPA 101“Life Safety Code”, the Uniform BuildingCode and additional standards publishedby the National Fire ProtectionAssociation (NFPA).

G. Energy Conservation

1. Air Conditioning

All air conditioning systems that areconsidered should be compared to abasic system with respect to both lifecycle cost and energy usage. The basicsystem should be that system having thelowest cost. The systems with the lowestlife cycle cost should be selected.

Coordinate the selected system with theVA HVAC Design Manual for Hospitalprojects for additional information.

H. Communications

1. Telephone

Telephone outlets are typically providedat each workstation or in each room. Desk outlets are 450 mm (18”) AFF andwall phone outlets are 1200 mm (48”)AFF.

Certain modular casework units areprovided with a utility access module thathouses communication outlets andprovides a chase for cabling. Conduitsand junction boxes are provided toconnect to the utility access module fortelephone service.

2. Automatic Data Processing (ADP)

ADP, or computer outlets, are typicallyprovided at each workstation with apersonal computer (PC) and/or printer.Desk outlets are 450 mm (18”) AFF.

Page 370: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-11

Certain modular casework units areprovided with a utility access module thathouses communication outlets andprovides a chase for cabling. Conduitsand junction boxes are provided toconnect to the utility access module forADP service.

3. Public Address

The MRI department will not have anindependent public address (PA) system.The department will be included as partof the hospital-wide PA system.Speakers are typically located incorridors and public spaces. The actualsystem configuration will depend on theoverall design layout and the functionalrequirements.

I. Waste Management

1. Medical Waste

Medical waste is generated in exam andtreatment spaces where it is bagged,collected, and transported to the soiledutility rooms. Then it is held in separatecontainers pending transport to themedical waste handling facility.

2. General Waste

General Waste is generated in all spacesand is held in containers for collectionand sorting into carts or it is bagged andplaced in a waste chute and transportedto the waste handling facility.

3. Recycling

Methods for sorting, collecting,transporting and disposing of recyclableproducts must be specifically analyzedfor each facility and location.

The optional use of disposable andreusable products should be considered.

4. Soiled Linen

Soiled reusable linens are generated inexam rooms, treatment spaces, andpatient and staff gowning areas. Theyare collected in carts or hampers(depending on volume) in the soiled utilityrooms; or they are bagged andtransported to (a) central collectionarea(s) via soiled linen chutes or carts.

Disposable linens are included with eithergeneral recyclable waste or medicalwaste as appropriate.

5. Utensils

Reusable utensils include bed pans,urinals, emesis basins and otherstainless steel items, which are used inexam and treatment areas. Then theyare transported to the soiled utility roomwhere they are reprocessed (if steamwashers are available) or collected forreprocessing and transported to theSterile Processing Department.

6. Space Requirements

Space requirements will vary with theselection of waste collection andrecycling methods/systems. Spacerequirements need to be analyzed foreach optional method or systemconsidered for new and existing facilities.

Page 371: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-12

While space needs are determined byPG 7610 on a departmental basis, spaceprovisions for waste collection needs tobe distributed and dedicated to a varietyof uses in order to accommodate theimplementation of the system andmethod selected.

J.Transportation

1. Patient

Gowning areas with lockers for inpatientand outpatient and control of ferrousmaterials should be provided.

a. Outpatient

Convenient access from patient parkingand primary care entrance should beconsidered.

Passenger elevator access to MRIfacilities should be located off mainentrance levels.

Techniques like clear access routes,public spaces, landmarks, and signagefacilitate wayfinding.

b. Inpatient

Stretcher and wheelchair patients shouldbe provided access from inpatient areas.

Inpatient and outpatient traffic should beseparated where possible.

Inpatient access from hospital serviceelevators is required.

Inpatients arrive at a control pointcommon with outpatients.

Inpatients access patient holding througha dedicated route, which is separatedfrom outpatient waiting.

2. Staff

Staff access should be separated frompatient waiting and holding areas.

Staff lounge and locker areas should belocated away from inpatient andoutpatient traffic and gantry rooms.

3. Records

MRI utilizes digital imaging and retrievaltechniques which may reduce the needfor storage and retrieval of films.

Viewing, interpretation and video imagemanipulation areas should have datacommunication access.

MRI film records, which should beaccessible by cart traffic, are usuallycombined with radiology records.

4. Specimens

Specimens are normally not drawn in thisdepartment.

5. Pharmaceuticals

Pharmaceuticals, including narcotics, aretransported by pharmacy personal to thedepartment in locked carts.

Narcotics are delivered to a narcoticslocker which is usually located in a cleansupply or patient prep area and isremotely alarmed to the nearest nursingstation.

6. Materials

Clean supplies are transported byexchange carts which are stored in theClean Supply Room.

Page 372: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingNarrative

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING PAGE 2-13

Supplies are transported by ServiceElevator and through hospital corridorsseparated from patient traffic wherepossible.

Deliveries are scheduled during hourswhen patient visits are not scheduled.

7. Linen

Disposable linens are delivered as partof clean supplies.

8. Sterile Supplies

The use of sterile supplies is minimaland is accommodated by prepackaged ordisposable items delivered with cleansupplies.

9. Food

Meal and Nourishment deliveries to MRIare not required.

10. Waste

Waste is collected by housekeeping staffand transported to the Soiled UtilityRoom where it is disposed of asindicated by the Waste Managementnarrative on page 2-10.

Page 373: VA guide -2009

FINAL DRAFT 9/28/95

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING SECTION 3

Section 3Relationship Diagrams

Page

Magnetic Resonance Imaging .....................3 - 1

Page 374: VA guide -2009
Page 375: VA guide -2009

FINAL DRAFT 9/28/95

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING SECTION 4

Section 4Design Guide Platesand Data Sheets:Patient Care AreasGuide Plate Series Plate Number

Magnetic Resonance Imaging SystemEquipment & Utility Plan..............................4 - 1Reflected Ceiling Plan .................................4 - 1Design Standards........................................4 - 1Equipment Guide List ..................................4 - 1

Page 376: VA guide -2009
Page 377: VA guide -2009
Page 378: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingDesign Standards

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING 4-1

ARCHITECTURAL

Ceiling: Acoustic Ceiling TileCeiling Ht: Coordinatew/ Equipment

Manufacturer up to 3130mm (13’)Wall Finish: PaintWainscot: ---Base: Resilient BaseFloor Finish: Vinyl Composition TileSlab Depr: Access Floor System 40 mm (1-1/2”) slab depression for RF

Shielding in Gantry RoomNotes: 1. 1200 mm (4’-0”) wide RF door

into Gantry Room coordinatedradio frequency and magneticshielding requirements withequipment manufacturer

SPECIAL EQUIPMENTNone

ELECTRICAL LIGHTING

General: Control Room: 30 fc - 1.0 W/sf Remote Viewing: 30 fc-1.5W/sf Control Room: 30 fc -.90 W/sf Gantry Room: 30 fc - 2.5 W/sf

Notes: 1. 600 mm x 1200 mm (2’x4’)recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 4100 deg.k, CRI-85 (minimum).

2. Recessed, lensedincandescent down light with100w, A-21 lamp.

POWER

General: 3200W (receptacles)Emergency:Notes: 1. 480v, 3P, flush-mounted circuit

breaker with shunt trip for MRIsystem. Coordinate rating withsystem supplier.

2. 480v, 3P, flush mounted circuitbreaker with shunt trip forcomputer room’s A/C unit (whenprovided). Coordinate ratingwith system supplier.

3. DC power supply (rectifier) forMRI Gantry Room lighting.Rating as required for roomlighting load.

COMMUNICATIONS

ADP: ---Radio: ---Telephone: YesIntercom: YesPublic Addr: ---Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 21 0C (700 F) for computer room,24 0C (76 0F)all others

Dry Bulb Temp Heating: 21 0C (70 0F) for computer room,

25 0C (780 F) all others

Minimum % Outside Air: 15% 100% Exhaust Air: Required only in

emergency for MRI Gantry

Noise Criteria NC 35 in GantryNC 40 in others

Steam: Yes Relative Humidity/Cooling: 50% Relative Humidity/Heating: 45%

40% +/- 5 in computer room Minimum Air Changes/Hr.: 12 for MRI Gantry

4 for all others Room Pressure: Positive for Gantry Rm

Equal for all othersAC Load-Equipment: 4400W (15,000 Btu/hr)

for Gantry 2400W (8000 Btu/hr)

all others AC Load Lighting: 27 W/m2 (2.5 W/sf)

Gantry 17 W/m2 (1.5 W/sf)

all others Number of People: 6 for MRI, 3 for all others Special Exhaust: --- Notes: 1. The HVAC system serving the

Gantry Room needs to becapable of handling 100% O.A.

Page 379: VA guide -2009

FINAL DRAFT 9/28/95

Magnetic Resonance ImagingDesign Standards

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING 4-1

HEATING, VENTILATING AND AIRCONDITIONING (cont’d)

Notes: 2. Provide temperature andhumidity sensor in the returnexhaust ductwork with remoteadjustment capabilities for theGantry Room.

3. Provide a dedicated AC unit toserve the Computer Room. .

4. Provide 2 low level exhaustoutlets located 175 mm (7”)above finished floor in thegantry room.

5. Provide nonferrous piping,ductwork, and hangers materialinside the shielding enclosure,as well as in all associateddampers.

6. Provide an automaticemergency 100% exhaustsystem in the Gantry Room.

7. Provide separate vent frommagnet to outside for cryogenboil-off.

8. Provide chilled water supply andreturn to the building centralchilled water system forenvironmental and computerroom units

9. Provide a dedicated air cooledclosed loop water coolingequipment for backup to theenvironmental and computer ACunits.

10. Provide local and central hightemperature alarms for thecomputer equipment.

11. Provide wave guide damper forall ductwork penetrating the RFshielding enclosure

PLUMBING AND MEDICAL GASCold Water: YesHot Water: YesLaboratory Air: ---Laboratory Vacuum: ---Sanitary Drain: YesReagent Grade Water: ---Medical Air: YesMedical Vacuum: YesOxygen: YesNotes: 1. Provide nonferrous piping and

hangers material inside theshielding enclosure.

Page 380: VA guide -2009

FINAL DRAFT 11/7/96

Magnetic Resonance ImagingEquipment Guide List

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING 4-1

General NotesNOTE: ALL MATERIALS INSTALLED, LOCATED WITHIN OR INTENDED TO ENTER THE GANTRY AREA, MUST BE NON-MAGNETIC EXCEPT FOR RECOMMENDED MAGNET SHIELDING MATERIALS ON OR IN WALLS, FLOORS OR CEILINGS.

NOTE: ALL PENETRATIONS (THROUGH THE RF SHIELDED ROOM FOR PLUMBING, ELECTRICAL, MECHANICAL) OR ANY CONDUCTIVE BUILDING MATERIAL SHALL BE ELECTRICALLY ISOLATED AND RFI FILTERED IN ACCORDANCE WITH MANUFACTURERS STANDARDS.

NOTE: CONDUCTIVE CONNECTIONS ARE TO BE MADE OUTSIDE THE RF ROOM.

NOTE: PROVIDE NON-MAGNETIC MATERIAL FOR AIR, OXYGEN AND VACUUM OUTLETS FROM PORTABLE SUPPLY, ONLY WHEN APPROVED FOR A SPECIFIC PROJECT BY VHA.

Gantry Room

NOTE: INTERCOM STATION, CONNECTED TO STATION IN THE CONTROL ROOM.

NOTE: INTERCOM, STATION, NON-MAGNETIC MATERIAL (PG-18-1, MCS 16760

NOTE: COMPUTER/ACCESS FLOORING, NON-MAGNETIC MATERIALS)

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: LIGHTING SYSTEM, DC, FOR INCANDESCENT LIGHT FIXTURES, NON-MAGNETIC MATERIAL, MULTI-CIRCUIT LIGHT FIXTURES

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG 18-1, MCS 16111)

NOTE: RADIO FREQUENCY COPPER GROUND PLANES, LOCATED ON THE FINISHED FLOOR SURFACE, FROM THE MAGNET TO THE ELECTRONIC CABINETS

NOTE: SHIELDING, MAGNETIC (ACTIVE OR PASSIVE)

NOTE: SHIELDING, RADIO FREQUENCY (RF)

NOTE: SYSTEM EMERGENCY OFF BUTTON PANEL, GUARD COLLAR, FLUSH MOUNTED, LOCATED NEAR EXIT FROM GANTRY ROOM, APPROX., 1524 MM (60") ABOVE FINISHED FLOOR

AR CC MODULAR CASEWORKAR VC GANTRY, MAGNET, PATIENT COUCH, SIZES AS REQUIRED1 VC OXYGEN MONITOR AND ALARM, WALL MOUNTED,

APPROX., 279 MM X 178 MM X 229 MM (11" X 7" X 9") LOCATED APPROX., 1524 MM (60") ABOVE FINISHED FLOOR

SYMBOL QTY AI DESCRIPTION

Page 381: VA guide -2009

FINAL DRAFT 11/7/96

Magnetic Resonance ImagingEquipment Guide List

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING 4-1

Control RoomNOTE: PROCESSOR, UTILITIES SERVICE INCLUDING MECHANICAL AND ELECTRICAL

SERVICES, MAINSWITCH, PER MANUFACTURER STANDARDS.

NOTE: COMPUTER/ACCESS FLOORING, AS REQUIRED.

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: INTERCOM, STATION PG-18-1, MCS 16760)

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: SYSTEM EMERGENCY OFF BUTTON PANEL, GUARD COLLAR, WALL MOUNTED, LOCATED NEAR EXIT FROM CONTROL ROOM, APPROX., 1524 MM (60") ABOVE FINISHED FLOOR

1 VV CHAIR, ROTARY, WITH ARMS1 VC CONSOLE, OPERATOR'S WITH COMPUTER TERMINAL AND

IMAGE DISPLAY MONITORS, FOR CONTROLLING ACQUISTION, PROCESSING, DISPLAY AND MANIPULATION OF DATA

1 VV BULLETIN BOARD, 914 MM X 610 MM (36" X 24")AR CF MODULAR CASEWORK1 VV RECEPTACLE, WASTE, 330 MM (13") DIAMETER

Computer / Equipment RoomNOTE: VARIOUS CABINETS, DISTRIBUTION SYSTEMS AS REQUIRED BY MANUFACTURER.

NOTE: COMPUTER/ACCESS FLOORING, AS REQUIRED.

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: SHUNT TRIP CIRCUIT BREAKER, AS REQUIRED.

NOTE: SYSTEM EMERGENCY OFF BUTTON PANEL, GUARD COLLAR, WALL MOUNTED, LOCATED NEAR EXIT FROM COMPUTER/EQUIPMENT ROOM, APPROX., 1524 MM (60") ABOVE FINISHED FLOOR

AR VV COMPUTER, SYSTEM HARDWARE

SYMBOL QTY AI DESCRIPTION

Page 382: VA guide -2009

FINAL DRAFT 11/7/96

Magnetic Resonance ImagingEquipment Guide List

VA DESIGN GUIDEMAGNETIC RESONANCE IMAGING 4-1

Remote Viewing RoomNOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED.

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG -18-1, MCS 16510).

AR VV CHAIR, ROTARY, WITH ARMS1 VV CLOCK, BATTERY OPERATEDAR VC CONSOLE, WITH COMPUTER TERMINAL AND IMAGE DISPLAY

MONITORS (AS APPROVED ON PROJECT BASIS BY VHA)1 VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508 MM X 1499 MM (20" X 59")1 VV RECEPTACLE, WASTE, 330 MM (13") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 383: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE CONTENTS- SECTION 5

Section 5Design Guide Platesand Data Sheets:Technical Support Areas

Guide Plate Series Plate Number

Computer-Image and Data Processing AreaEquipment & Utility Plan........................5 - 1Reflected Ceiling Plan...........................5 - 1Design Standards .................................5 - 1Equipment Guide List............................5 - 1

Non-Imaging Procedure RoomEquipment & Utility Plan........................5 - 2Reflected Ceiling Plan...........................5 - 2Design Standards .................................5 - 2Equipment Guide List............................5 - 2

Non-Imaging Procedure Room(Alternate Exercise Room)

Equipment & Utility Plan........................5 - 3Reflected Ceiling Plan...........................5 - 3Design Standards .................................5 - 3Equipment Guide List............................5 - 3

Radioimmunoassay UnitEquipment & Utility Plan........................5 - 4Reflected Ceiling Plan...........................5 - 4Design Standards .................................5 - 4Equipment Guide List............................5 - 4

Employee Biosafety RoomsEquipment & Utility Plan........................5 - 5Reflected Ceiling Plan...........................5 - 5Design Standards .................................5 - 5Equipment Guide List............................5 - 5

Page 384: VA guide -2009
Page 385: VA guide -2009
Page 386: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Design StandardsComputer Image and Data Processing Area

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-1

ARCHITECTURALCeiling: Acoustical ceiling tileCeiling Ht: 2700 mm (9’-0”)Wall Finish: PaintWainscot: ---Base: Resilient BaseFloor Finish: Vinyl composition tileSlab Depr.: ---Notes: 1050 mm (3’-6”) wide door with tempered-glass view window

SPECIAL EQUIPMENT ---

ELECTRICAL LIGHTINGGeneral: 30FCNotes: 1. 600 mm x 1200 mm (2’ x 4’)

recessed fluorescent lightfixture, 18 parabolic louver,W/3-F32T8 lamps, 4100 deg. K,CRI=85 (minimum).

POWERGeneral: 2200 W (receptacles)Emergency: ---Notes: ---

COMMUNICATIONS ADP: Yes Radio: --- Telephone: Yes Intercom: --- Public Addr: --- Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling : 25 0 C (78 0 F) Dry Bulb Temp Heating : 22 0 C (72 0 F) Minimum % Outside Air: 15% 100% Exhaust Air: --- Noise Criteria: NC-40 Steam: --- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 2 Room Pressure: 0 AC Load-Equipment: 160 w/m2 (15 w/sf) AC Load-Lighting: 20 w/m 2(1.8 w/sf) Number of People: 6 Special Exhaust: --- Notes: 1. Verify equipment AC load as

per actual equipment used.

PLUMBING AND MEDICAL GAS Cold Water: --- Hot Water: --- Laboratory Air: --- Laboratory Vacuum: --- Sanitary Drain: --- Reagent Grade Water: --- Medical Air: --- Medical Vacuum: --- Oxygen: -- Notes: ---

Page 387: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-1

Computer Image and Data Processing Area

NOTE: RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER EQUIPMENT ITEMS(PG-18-1, MCS 16140

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-18-1, MCS 16140; )

1 VV BULLETIN BOARD, 1220 mm X 910 mm (48" X 36")AR VV CHAIR, ROTARY, WITH ARMS1 VV CLOCK, BATTERY OPERATED1 VV PRINTER, COMPUTER SYSTEM, LASER1 VV PRINTER, COMPUTER SYSTEM, COLOR2 VV STAND, COMPUTER PRINTER, APPROX., 610 mm X 610 mm

X 660 mm (24" X 24" X 26")4 VV WORKSTATION, IMAGE PROCESSING, NUC. MEDICINE

SYMBOL QTY AI DESCRIPTION

Page 388: VA guide -2009
Page 389: VA guide -2009
Page 390: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Design StandardsNon-Imaging Procedure Room

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-2

ARCHITECTURAL Ceiling: Acoustical ceiling tile Ceiling Ht: 2890 mm (9’-6") Wall Finish: Paint Wainscot: --- Base: Integral welded seam sheet flooring base Floor Finish: Welded seam sheet flooring Slab Depr.: 1220 mm (4’) Notes: 1150 mm (3’-10”) wide door

SPECIAL EQUIPMENT ---

ELECTRICAL LIGHTING General: --- Notes: 1. 600 mm x 600 mm (2’ x 2’)

recessed fluorescent lightfixtures, acrylic prismaticlens, W/2- R32T8 lamps,4100 deg K, CRI-85 (min).

POWER General: --- Emergency: --- Notes: ---

COMMUNICATIONS ADP: --- Radio: --- Telephone: --- Intercom: -- Public Addr: --- Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling : 25 0 C(78 0 F) Dry Bulb Temp Heating : 22 0 C(72 0 F) Minimum % Outside Air: --- 100% Exhaust Air: Yes Noise Criteria: NC 40 Steam: --- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 12 Room Pressure: Negative AC Load-Equipment: 195 w/m 2 (18 w/sf) AC load-Lighting: 20 w/m 2(1.75w/sf) Number of People: 6 Special Exhaust: Yes Notes: 1. Check minimum air changes

per hour with minmum hoodexhaust requirements.

2. Design H3 hood exhaustrequirements for constantvelocity control and notconstant CFM.

3. Verify equipment AC as peractual equiment furnished.

PLUMBING AND MEDICAL GAS Cold Water: Yes Hot Water: Yes Laboratory Air: Yes Laboratory Vacuum: Yes Sanitary Drain: Yes Reagent Grade Water: Check with Medical

Center Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: 1. Sanitary waste and vent

needs to be chemicalresistant type.

2. Natural gas is required forfume hood.

Page 391: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-3

Non-Imaging Procedure Room

NOTE: INTERCOM, STATION, HANDS FREE, WALL MOUNTED (PG-18-1, MCS 16760)

NOTE: OUTLETS, AIR, GAS AND VACUUM, GROUPED, 1220 mm (48") ON CENTER ABOVECOUNTER (PG-18-1 & PG-18-6, MCS 11602)

NOTE: OUTLETS, EMERGENCY ALARM BUTTON , (PG-18-1 , MCS 16761)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 15 AMP, STRIP MOLD WITHOUTLETS, WIRED ALTERNATELY ON SEPARATE CIRCUITS ON 610 mm (24") CENTERSABOVE COUNTER (PG-18-1, MCS 161403)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, (PG-18-1, MCS 16140;

NOTE:COUNTER TOPS OF MODULAR CASEWORK ARE TO BE IMPENETRABLE, SEAMLESS SURFACES WITH RIMS AND DRIP GROOVES AT EDGES.(PG-18-1, MCS 11620 PG-18-5)

AR VV CENTRIFUGE, REFRIGERATED, 120 VOLT, 20 AMP,910mm X 1220mm (36” X 48”)

1 VV CLOCK, BATTERY OPERATEDAR CF COUNTER TOP, CORROSION RESISTING STEEL,

32 mm (1-1/4”) THICK1 CC DISPENSER, SOAP, WALL-MOUNTED WITH FOOT CONTROL

(PG-18-1, MCS 10800)1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE-MOUNTED1 VV DISPENSER, GLOVES, WALL-MOUNTEDAR VV REFRIGERATOR, 4 TO 10 DEGREES CELCIUS, 71 CUBIC M.

(25 CUBIC FT.), 120 VOLT, 20 AMP, REACH-IN TYPE, DOUBLE DOOR, WITH SHELVES

1 VV FREEZER, 4 TO 10 DEGREES CELCIUS, CAPACITY AS REQUIRED,120 VOLT, 20 AMP, REACH-IN TYPE

H3-72 1 CC FUME HOOD, RADIOISOTOPE, STAINLESS STEEL INTERIOR WITH CABINET BASE, 2 EACH, WA-- AIR, GAS, VACUUM, ELECTRIC DUPLEX OUTLETS AND CUP SINKS, BASE TO SUPPORT SUPERSTRUCTURE PLUS 9.58 KPA (200 POUNDS PER SQUARE FOOT), 1830mm X 910mm X 2130mm(72” X 36” X 84”) (PG-18-1 & PG-18-6, MCS 11610)

SEE HVAC DESIGN MANUAL FOR HOSPITAL PROJECTS.AR CF MODULAR LABORATORY CASEWORK1 VV MONITOR, RADIATION, MOBILE1 VV RECEPTACLE, WASTE, BIOHAZARD TYPE, 762mm (30”) DIA.,

ON WHEELS WITH FOOT-OPERATED LIDP-512 1 CC SINK, CORROSION-RESISTING STEEL, SINGLE

COMPARTMENT WITH DRAINBOARD, WALL-HUNG 1,MCS 15450)

SYMBOL QTY AI DESCRIPTION

Page 392: VA guide -2009
Page 393: VA guide -2009
Page 394: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Design StandardsNon-Imaging Procedure Room (Alternate Exercise Room)

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-3

ARCHITECTURAL Ceiling: Acoustical ceiling tile Ceiling Ht: 2890 mm (9’-6") Wall Finish: Paint Wainscot: --- Base: Integral welded seam sheet flooring base Floor Finish: Welded seam sheet flooring Slab Depr.: 1220 mm (4’) Notes: 1150 mm (3’-10”) wide door

SPECIAL EQUIPMENT ---

ELECTRICAL LIGHTING General: --- Notes: 1. 600 mm x 600 mm (2’ x 2’)

recessed fluorescent lightfixtures, acrylic prismaticlens, W/2- R32T8 lamps,4100 deg K, CRI-85 (min).

POWER General: --- Emergency: --- Notes: ---

COMMUNICATIONS ADP: --- Radio: --- Telephone: --- Intercom: --- Public Addr: --- Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling : 25 0 C(78 0 F) Dry Bulb Temp Heating : 22 0 C(72 0 F) Minimum % Outside Air: --- 100% Exhaust Air: Yes Noise Criteria: NC 40 Steam: --- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 12 Room Pressure: Negative AC Load-Equipment: 195 w/m 2 (18 w/sf) AC load-Lighting: 20 w/m 2(1.75w/sf) Number of People: 6 Special Exhaust: Yes

Notes: 1. Verify equipment AC as peractual equiment furnished.

PLUMBING AND MEDICAL GAS Cold Water: Yes Hot Water: Yes Laboratory Air: Yes Laboratory Vacuum: Yes Sanitary Drain: Yes Reagent Grade Water: Check with Medical Center Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: 1. Sanitary waste and vent

needs to be chemicalresistant type.

2. Natural gas is required forfume hood.

Page 395: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-3

Non-Imaging Procedure Room (Alternate Exercise Room)

NOTE: INTERCOM, STATION, (PG-18-1, MCS 16760)

NOTE: OUTLETS, AIR, GAS AND VACUUM, GROUPED, 1219 mm (48") ON CENTER ABOVECOUNTER (PG-18-1 & PG-18-6, MCS 11602)

NOTE: OUTLET, EMERGENCY ALARM BUTTON (PG-18-1, MCS 16761)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491, H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491, H-18-3, CS 310-1)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 15 AMP, STRIP MOLD WITHOUTLETS, WIRED ALTERNATELY ON SEPARATE CIRCUITS ON 610 mm (24") CENTERSABOVE COUNTER (PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, (PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: RECEPTACLE, ELECTRICAL, FOR CRASH CART TO BE ON EMERGENCY POWER

1 VV CART, EMERGENCY, “CRASH CART” APPROX. 910mm X 530mm (36” X 21”)

1 VV CHAIR, STRAIGHT1 CC CLOCK, ELECTRIC TIME ELAPSED, RECESSED (PG-18-1,

MCS 10360)1 VV DESK 1520mm X 610mm (60” X 24”)1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV EXERCISER, BICYCLE

P-414 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)1 VV MACHINE, TREADMILL WITH CONTROLS, 120 VOLT, 20 AMP,

APPROX. 1830mm X 760mm (72” X 30”)1 VV MACHINE, TWELVE (12) LEADS “ECG”1 VV PC AND PRINTER1 VV RECEPTACLE, WASTE, 330mm (13”) DIA.

SYMBOL QTY AI DESCRIPTION

Page 396: VA guide -2009
Page 397: VA guide -2009
Page 398: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Design StandardsRadioimmunoassay Unit

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-4

ARCHITECTURAL Ceiling: Acoustical ceiling tile Ceiling Ht: 2700 mm (9’-0") Wall Finish: Paint Wainscot: --- Base: Integral welded seam sheet flooring base Floor Finish: Welded seam sheet flooring Slab Depr.: --- Notes: 1220 mm (4’-0”) wide doors

SPECIAL EQUIPMENT ---

ELECTRICAL LIGHTING General: 50FC Notes: 1. Lighting control by area;

switch(ex) at room entrance.

2. 600 mm x 1200 mm (2’ x 4’)recessed fluorescent lightfixtures, acrylic prismatic lens,W/2-=F32T8 lamps, 4100 deg.K, CRI-85 (minimum).

POWER General: 3000 W (receptacles on electrical

strip mold on modular casework) Emergency: Notes: 1. Junction box for 120V

power/connection to electricalstrip/mold on modularcasework.

2. Junction box for biologicalsafety cabinet on emergencypower.

COMMUNICATIONS ADP: Yes Radio: --- Telephone: Yes Intercom: Yes Public Addr: --- Notes: 1. Communications cabling routed

via modular casework utilityaccess lab module to outletson casework.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25 0 C (78 0 F) Dry Bulb Temp Heating: 22 0 C (72 0 F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: --- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 12 Room Pressure: Negative AC Load-Equipment: 195 w/sm (18 w/sf) AC Load Lighting: 22.5 w/sm (2.1 w/sf) Number of People: 12 Special Exhaust: Provide safety cabinet

exhaust

Notes 1. Verify equipment AC load asper actual equipment used.

PLUMBING AND MEDICAL GAS Cold Water: Yes Hot Water: Yes Laboratory Air: Yes Laboratory Vacuum: Yes Sanitary Drain: YesReagent Grade Water: Yes

Medical Air: ---- Medical Vacuum: ---- Oxygen: ---- Notes: 1. Waste and vent needs to be

chemical resistant type.

2. Natural gas is required forbiohazard safety cabinet.

Page 399: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-4

Radioimmunoassay Unit

NOTE: INTERCOM, STATION, HANDS FREE, WALL MOUNTED (PG-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: OUTLET, SINK, REAGENT GRADE WATER (PG-18-1, MCS 11602)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, STRIP MOLD, ON 610 mm(24") CENTERS ABOVE COUNTER (PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, (PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: RECEPTACLE, ELECTRICAL, QUADRAPLEX, FOR COMPUTER EQUIPMENT ITEMS(PG-18-1, MCS 16140; H-18-3, CS 866-1)

NOTE:COUNTER TOPS OF MODULAR CASEWORK ARE TO BE IMPENETRABLE,SEAMLESS SURFACES WITH RIMS AND DRIP GROOVES AT EDGES. (PG-18-1, MCS 11620PG-18-5)

RECEIVING, PREP, DATA REDUCTION & REPORTING AREA

AR VV BULLETIN BOARD, 760 mm X 1070 mm (30" X 42")AR VV CHAIR, LABORATORY, SEMI-HYDRAULIC, ADJUSTABLE

HEIGHT TO 790 mm (31")1 VV CLOCK, BATTERY OPERATED1 VV COMPUTER TERMINAL, WITH KEYBOARD1 VV DISPENSER, GLOVES, WALL MOUNTED1 VV DISPOSAL, NEEDLES, WALL MOUNTEDAR CF MODULAR LABORATORY CASEWORK

VL54 1 CF PEGBOARD, 53 PEGS, 810 mm X 760 mm (32" X 30")(PG-18-1 & PG-18-6, MCS11602)

J-2 1 CF SINK, CORROSION RESISTING STEEL, WITH CENTER DRAIN OUTLET, 460 mm X 380 mm X 200 mm ( 18” X 15” X 8”)( PG-18-1& PG-18-6, MCS 11602)

1 VV RECEPTACLE, WASTE, BIOHAZARD TYPE, 760 mm (30") DIA., ON WHEELS WITH FOOT OPERATED LID

ASSAY PREPARATION

AR VV BULLETIN BOARD, 760 mm X 1070 mm (30" X 42")AR VV CENTRIFUGE, LAB, BENCH MODEL, 120 VOLT, 20 AMP,

APPROX., 610 mm X 610 mm (24" X 24")1 VV CENTRIFUGE, REFRIGERATED, 120 VOLT, 20 AMP,

910 mm X 1220 mm (36" X 48")AR VV CHAIR, LABORATORY, SEMI-HYDRAULIC, ADJUSTABLE

HEIGHT TO 790 mm (31")1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE MOUNTED

SYMBOL QTY AI DESCRIPTION

Page 400: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-4

Radioimmunoassay Unit (cont’d)

ASSAY PREPARATION (CONT’D)

1 VV DISPENSER, GLOVES, WALL MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPOSAL, NEEDLES, WALL MOUNTED

VL84 1 CC EMERGENCY EYE AND FACE WASH, RETRACTABLE, HAND HELD, COUNTER MOUNTED (PG-18-1, MCS 11602)

AR CF MODULAR LABORATORY CASEWORKVL54 1 CF PEGBOARD, 53 PEGS, 810 mm X 760 mm (32" X 30")

(PG-18-1 &PG-18-6, MCS11602)J-2 1 CF SINK, CORROSION RESISTING STEEL, WITH CENTER DRAIN

OUTLET, 460 mm X 380 mm X 200 mm ( 18” X 15” X 8”)( PG-18-1& PG-18-6, MCS 11602)

BIOHAZARD PREPARATION

H12B2-72 1 CC BIOLOGICAL SAFETY CABINET (LAMINAR FLOW), CLASS II, TYPE B2, 100% DIRECT EXHAUSTED AIR THROUGH THE WORK SPACE. 1830mm X 910mm X 2134mm(72” X 36” X 84”). SEE HVAC DESIGN MANUAL FOR HOSPITAL PROJECTS.

AR VV CENTRIFUGE, LAB, BENCH MODEL, 120 VOLT, 20 AMP, APPROX., 610 mm X 610 mm (24" X 24")

AR VV CHAIR, LABORATORY, SEMI-HYDRAULIC, ADJUSTABLE HEIGHT TO 790 mm (31")

1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, GLOVES, WALL MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPOSAL, NEEDLES, WALL MOUNTED

VL84 1 CC EMERGENCY EYE AND FACE WASH, RETRACTABLE, HAND HELD, COUNTER MOUNTED (PG-18-1, MCS 11602)

AR CF MODULAR LABORATORY CASEWORKVL54 1 CF PEGBOARD, 53 PEGS, 810 mm X 760 mm (32" X 30")

(PG-18-1 &PG-18-6, MCS11602)J-2 AR CF SINK, CORROSION RESISTING STEEL, WITH CENTER DRAIN

OUTLET, 460 mm X 380 mm X 200 mm (18" X 15" X 8")(PG-18-1 & PG-18-6, MCS 11602)

SYMBOL QTY AI DESCRIPTION

Page 401: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-4

Radioimmumoassay Unit (cont’d)

SAMPLE COUNTING AREA

AR VV CHAIR, LABORATORY, SEMI-HYDRAULIC, ADJUSTABLE HEIGHT TO 790 mm (31")

1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, GLOVES, WALL MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR CF MODULAR LABORATORY CASEWORK1 VV SAMPLE COUNTER, BENCH MODEL1 VV SAMPLE COUNTER, LARGE VOLUME, FLOOR MOUNTEDAR VV BULLETIN BOARD, 760 mm x 1070 mm (30”x42”)

SYMBOL QTY AI DESCRIPTION

Page 402: VA guide -2009
Page 403: VA guide -2009
Page 404: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Design StandardsEmployee Biosafety Room - Lounge

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-5

ARCHITECTURAL Ceiling: Acoustical ceiling tile Ceiling Ht: 2740 mm (9’-0”) Wall Finish: Vinyl wall covering Wainscot: --- Base: Resilient base Floor Finish: Carpet Slab Depr.: --- Notes: ---

SPECIAL EQUIPMENT ---

ELECTRICAL LIGHTING General: 30FC Notes: 1. 600 mm x 1200 mm (2’ x 4’)

recessed fluorescent lightfixtures, acrylic prismatic lens,W/2-=F32T8 lamps, 4100 deg.k, CRI-85 (minimum)

POWER General: 100W (receptacles on electrical

strip mold on modular casework) Emergency: --- Notes: ---

COMMUNICATIONS ADP: --- Radio: --- Telephone: Yes Intercom: Yes Public Addr: Yes Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25 0 C (78 0F) Dry Bulb Temp Heating: 22 0 C (72 0 F) Minimum % Outside Air: --- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: --- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Negative AC Load-Equipment: 22w/m2 (2 w/sf) AC Load Lighting: 22.5 w/m2 (2.1 w/sf) Number of People: 12 Special Exhaust: --- Notes: ---

PLUMBING AND MEDICAL GAS Cold Water: Yes Hot Water: Yes Laboratory Air: --- Laboratory Vacuum: --- Sanitary Drain: --- Reagent Grade Water: --- Medical Air: --- Medical Vacuum: --- Oxygen: --- Notes: ---

Page 405: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Design StandardsEmployee Biosafety Room - Toilet and Lockers

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-5

ARCHITECTURAL Ceiling: Acoustical ceiling tile Ceiling Ht: 2740 mm (9’-0") Wall Finish: Ceramic tile Wainscot: --- Base: Ceramic tile Floor Finish: Ceramic tile Slab Depr.: --- Notes: Plaster ceiling in shower

SPECIAL EQUIPMENT ---

ELECTRICAL LIGHTING General: 30FC Notes: 1. 600 mm x 1200 mm (2’ x

4’) recessed fluorescent lightfixtures, acrylic prismatic lens,W/2-=F32T8 lamps, 4100 deg.k, CRI-85 (minimum).

POWERGeneral: 100 W (receptacles

on electrical strip moldon modular casework)

Emergency: --- Notes: ---

COMMUNICATIONS ADP: --- Radio: --- Telephone: Yes Intercom: --- Public Addr: Yes Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25 0 C (78 0 F) Dry Bulb Temp Heating: 22 0 C (72 0 F) Minimum % Outside Air: --- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: --- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 10 Room Pressure: Negative AC Load-Equipment: 11 w/m 2(1 w/sf) AC Load Lighting 11 w/m2(1 w/sf) Number of People: 6-8 Special Exhaust: --- Notes: ---

PLUMBING AND MEDICAL GAS Cold Water: Yes Hot Water: Yes Laboratory Air: --- Laboratory Vacuum: --- Sanitary Drain: --- Reagent Grade Water: --- Medical Air: --- Medical Vacuum: --- Oxygen: --- Notes: ---

Page 406: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-5

Employee Biosafety Room

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, (PG-18-1, MCS 16140; H-18-3)

LOUNGE

AR VV CHAIR, LOUNGEAR VV CHAIR, STRAIGHT, WITH ARMS1 VV CLOCK, BATTERY OPERATED

T-B AR CC LOCKER, STEEL, SLOPING TOP, 310mm X 530mm X 1830mm(12” X 21” X 72”) (PG-18-1, MCS 10500; PG-18-4, SD 61)

1 VV MICROWAVEAR CF MODULAR CASEWORK1 VV RECEPTACLE, WASTE, 330mm (13”) DIA.1 VV REFRIGERATOR, UNDER COUNTER.

P-528 1 VV SINK, SINGLE COMPARTMENT, CORROSION RESISTING STEEL, WITH CENTER DRAIN OUTLET, 530 mm X 560 mm(21” X 22”) (PG-18-1, MCS 15450)

AR VV SOFA, 3 SEAT, UPHOLSTERED, APPROX., 1830mm X 840mm 710mm (72” X 26” X 28”)

AR VV TABLE, APPROX. 1830mm X 810mm X 760mm (72” X 32” X 30”)AR VV TABLE, END, PLASTIC LAMINATE TOP, METAL FRAME

TOILETS AND LOCKERS

AR CC BAR, GRAB FOR SHOWER (PG-18-1, MCS 10800; PG-18-4,SD13.1)

AR CC BAR, GRAB FOR WATER CLOSET (PG-18-1, MCS 10800;PG-18-4, SD 12, 14B & 14F)

1 CC BAR, TOWEL (PG-18-1, MCS 10800)1 VV CURTAIN, SHOWER1 CC DISH, SOAP, RECESSED (PG-18-1, MCS 10800; PG-18-4, SD12)1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-18-1,

MCS 10800; PG-18-4, SD 12)2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)

P-414 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)1 CC LIGHT, OVER LAVATORY (PG-18-1, MCS 16510; PG-18-4,

SD 919)1 CC LOCKER, PATIENT, HALF HEIGHT

SYMBOL QTY AI DESCRIPTION

Page 407: VA guide -2009

FINAL DRAFT 9/6/95UPDATED NOV. 1996

Equipment Guide List

VA DESIGN GUIDENUCLEAR MEDICINE SERVICE 5-5

Employee Biosafety Room- (cont’d)

TOILETS AND LOCKERS (cont’d)

1 CC MIRROR, WHEELCHAIR, 610mm X 910mm (24” X 36”)(PG-18-1, MCS 10800; PG-18-4, SD 15)

1 CC ROD, FOR SHOWER CURTAIN (PG-18-1, MCS 10800; H-8-4,SD 14)

1 CC SHELF, STAINLESS STEEL, WALL HUNG, 150mm X 460mm(6” X 18”) (PG-18-1. MCS 10360; PG-18-4, SD 15)

P-701 1 CC SHOWER, BATH FIXTURE, DETACHABLE, WALL MOUNTED,(PG-18-1, MCS 15450; PG-18-4, SD 13 & 382)

1 CC STALL, SHOWER, 1220mm X 1190mm (48” X 46-3/4”)(PG-18-1, MCS 10170; PG-18-4, SD 13)

P-104 1 CC WATER CLOSET, WALL HUNG (PG-18-1, MCS 15450;PG-18-4, SD 389)

SYMBOL QTY AI DESCRIPTION

Page 408: VA guide -2009

First Draft 8-14-96Revised June 97

VA DESIGN PRIMEROUTPATIENT PHARMACY CONTENTS - SECTION 4

Section 4Design Guide Platesand Data Sheets:Pharmacy SpecializedProgram

Guide Plate Series Plate Number

Drug Information ServiceEquipment & Utility Plan ..........................4-1Reflected Ceiling Plan..............................4-1Design Standards ....................................4-1Equipment Guide List ..............................4-1

Page 409: VA guide -2009
Page 410: VA guide -2009
Page 411: VA guide -2009

First Draft 8-14-96Revised June 97

VA DESIGN PRIMEROUTPATIENT PHARMACY PAGE 4-1

Design StandardsDrug Information ServiceARCHITECTURAL

Ceiling: Acoustic Lay-In Ceiling Tile Ceiling Ht: 2740 MM (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Resilient base Floor Finish: Carpet or Vinyl Composition Tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 1.7 w/sf538 lx (50 FC) Special: -- Notes: 1. Dual-level switching provided

50/15 FC levels.

2.600 x 1200mm (2'x4') recessedfluorescent light fixture, paraboliclouver lens, W/3-F32T8 lamps,3500°K, CRI=75 (Minimum)

POWER

General: 1200W (receptacles) Emergency: -- Notes:

COMMUNICATION

ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating : 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 18 w/sm (1.7 w/sf) AC Load-Equipment: 43 w/hr (4 w/hr) Number of People: 3 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 412: VA guide -2009

First Draft 8-14-96Revised June 97

Equipment Guide ListDrug Information Service

VA DESIGN PRIMEROUTPATIENT PHARMACY PAGE 4 - 1

SYMBOL QTY AI DESCRIPTION

AR CC SHELVING, FREESTANDING STEEL, LIBRARY, SINGLEFACED UNITS, WITH ADJUSTABLE SHELVES,915mm W x 255mm D x 2285mm H (36"W X 10"D X 90"H)(PG-18-1, MCS 11052; PG-18-4)

AR CC SHELVING, SINGLE FACED UNITS, PERIODICAL, WITHSLOPING AND ADJUSTABLE SHELVES,915mm W x 305mm D x 2285mm H (36"W X 12"D X 90"H)(PG-18-1, MCS 11052; PG-18-4)

AR VV BOOKCASE, SECTIONAL (EACH SECTION,315mm W x 330mm D x 380mm H (33"W X 13"D X 15"H))WITH 255mm H (10"H) BASE

1 VV BULLETIN BOARD, APPROX., 915mm W x 915mm H (36"W X 36"H)AR VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITH ARMS1 VV CHALKBOARD/TACKBOARD COMBINATION,

1525mm W x 1220mm H (60"W x 48"H)AR VV CLOCK, BATTERY OPERATEDAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV TABLE, OCCASIONAL, 1220mm (48”) DIA.AR CF CABINET, UNDERCOUNTER, 3 DRAWER,

395mm W x 555mm D x 760mm H (15”W x 22”D x 30”H)AR CF COUNTER, TOP, HIGH PRESSURE LAMINATED, DECORATIVE

760mm W x 1525m L (30”W x 60”L)1 CC RECEPTACLE, ELECTRICAL, QUADAPLEX FOR COMPUTER

EQUIPMENT ITEMS (PG-18-1, MCS 16140, H18-3, CS 866-1)AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLTS, 20 AMPS

(PG-18-1, MCS 16140: H-18-3, CS 801-3)

Page 413: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE CONTENTS - SECTION 4

Section 4Design Guide Platesand Data Sheets:Inpatient Pharmacy

Guide Plate Series Plate Number

Dispensing Station - Unit Dose and Ward StockEquipment & Utility Plan ..........................4-1Reflected Ceiling .....................................4-1Design Standards ....................................4-1Equipment Guide List ..............................4-1

Medication Assignment Area and Stat CounterEquipment & Utility Plan ..........................4-2Reflected Ceiling .....................................4-2Design Standards ....................................4-2Equipment Guide List ..............................4-2

Controlled Substance Vault andSecured Dispensing Area

Equipment & Utility Plan ..........................4-3Reflected Ceiling Plan..............................4-3Design Standards ....................................4-3Equipment Guide List ..............................4-3

Receiving AreaEquipment & Utility Plan ..........................4-4Reflected Ceiling Plan..............................4-4Design Standards ....................................4-4Equipment Guide List ..............................4-4

Page 414: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE CONTENTS - SECTION 4 (cont.)

Section 4Design Guide Platesand Data Sheets:Inpatient Pharmacy

Guide Plate Series Plate Number

Extemporaneous Repackaging andExtemporanous Compounding

Equipment & Utility Plan ..........................4-5Reflected Ceiling Plan..............................4-5Design Standards ....................................4-5Equipment Guide List ..............................4-5

Intravenous Admixture and Aseptic TransferEquipment & Utility Plan ..........................4-6Reflected Ceiling Plan..............................4-6Design Standards ....................................4-6Equipment Guide List ..............................4-6

Oncology DrugsEquipment & Utility Plan ..........................4-7Reflected Ceiling Plan..............................4-7Design Standards ....................................4-7Equipment Guide List ..............................4-7

Page 415: VA guide -2009
Page 416: VA guide -2009
Page 417: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 1

Design StandardsUnit Dose and Ward StockARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 100 FC Special: -- Notes: 1. Lighting control by area;

switch(es) at room entrance.2. 600 x 1200 mm (2'x4') recessed

fluorescent light fixture, acrylicprismatic lens, W/2-F32T8 lamps,3500° K CRI=75 (minimum)

POWER General: 3000W (Receptacles on electrical

strip mold on modular casework) Emergency: -- Notes: 1. Junction box for 120V power

connection to electrical strip moldon modular casework

2.Junction box for dose dispensingmachine to be ceiling-mounted

COMMUNICATIONS ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Communications cabling routed

via modular casework utilityaccess module to outlets oncasework.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Equipment: 54 w/sm (5W/SF) AC Load Lighting: 32 w/sm (3 W/SF) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 418: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListUnit Dose and Ward Stock

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 1

SYMBOL QTY AI DESCRIPTION

AR CF MODULAR CASEWORK , W/ OVERHEAD CABINETS, GRAVITYFEED SHELVES AND UTILITY ACCESS MODULE

AR VV CHAIR, ROTARY, WITH ARMSAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARDAR VV DOSE DISPENSING MACHINE, PATIENT SPECIFIC

Page 419: VA guide -2009
Page 420: VA guide -2009
Page 421: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 2

Design StandardsMedication Assignment Area and Stat CounterARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile or Carpet Slab Depr: -- Notes:

SPECIAL EQUIPMENTThis space will have immediate access to amaterial transport system.

LIGHTING General: 50 FC Special: -- Notes: 1. Lighting control by area;

switch(es) at room entrance.2. 600 x 1200 mm (2'x4')recessed

fluorescent light fixture, acrylicprismatic lens, W/2-F32T8 lamps,3500° K CRI=75 (Min.)

POWER General: 600W (Receptacles on electrical

strip mold on modular casework) Emergency: -- Notes: 1. Junction box for 120V power

connection to electrical strip moldon modular casework

COMMUNICATIONS ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Communications cabling routed

via modular casework utilityaccess module to outlets oncasework.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 18 w/sm (1.7 w/sf) AC Load Equipment: 54 w/sm (5 w/hr) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 422: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListMedication Assignment and Stat Counter

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 2

SYMBOL QTY AI DESCRIPTION

AR CF CABINET, FULL HEIGHT, DRUG DISPENSING, 1 FIXED SHELF,1 ADJUSTABLE SHELF AND 8 DISPENSING SHELVES WITHGRAVITY FEED TRAYS, 910mm W x 405mm D x 2130mm H(36"W X16"D X 84"H)

AR CF MODULAR CASEWORK , W/ OVERHEAD CABINETS AND UTILITY ACCESS MODULE

AR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARDAR VV TELECOPIER, FACSIMILE RECEIVER/FAX MACHINE

Page 423: VA guide -2009
Page 424: VA guide -2009
Page 425: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 3

Design StandardsControlled Substance Vault & Secured DispensingAreaARCHITECTURAL Ceiling: 1. Acoustic Tile in Secured Dispensing

2. Painted Gypsum Wallboard Ceiling Ht: 2740 mm (9'-0") Wall Finish: Paint Masonry & GWBD Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: -- Notes: 1. Vault Construction: Reinforced

concrete or reinforced CMU walls;concrete slab "roof".

2. Vault door and day gate: Refer toVA Construction Standard H-08-3,CD-49 for additional securitycriteria.

SPECIAL EQUIPMENTNone

LIGHTING General: Secured dispensing = 100 FC

Vault = 20 FC Notes: 1. Single switch per room controls

lighting2. 300mm x 1200mm (1' x 4') surface

mounted fluorescent light fixture,wrap-around acrylic lens, W/2-F32T8 lamps, 3500°K, CRI=75(minimum)

3. 600mm x 1200mm (2' x 4')recessed fluorescent light fixtures,acrylic prismatic lens, W/2F32T8lamps, 3500°K, CRI=75(minimum)

POWER General: 1000W (Receptacles) Emergency: -- Notes: 1. Junction box for power and signal

connections to electronic accessreader (2 locations)

COMMUNICATIONS ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Conduit and junction boxes

required for electronic accesssecurity system.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: Vault Area 11 w/sm (1 w/sf) Secured Area 32 w/sm (3 w/sf) AC Load Equipment: Vault Area43 w/sm (4 w/sf)

Secured Area 54 w/sm (5 w/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 426: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListControlled Substance Vault & Secured DispensingArea

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 3

SYMBOL QTY AI DESCRIPTION

AR CF MODULAR CASEWORK , W/ OVERHEAD CABINETS AND WALLHANGER STRIP

1 CF REFRIGERATOR, UNDER COUNTER, 5 CU. FT., 120 VOLTS, 20AMPS, 600mm W x 600mm D x 960mm H (24"W X 24"D X 38"H)

AR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARDAR VV CABINET, FULL HEIGHT OPEN SHELVES, 5 ADJUSTABLE, 1 FIXED

SHELF, 900mm W x 405mm D x 2130mm H (36”x16”x84”)

Page 427: VA guide -2009
Page 428: VA guide -2009
Page 429: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 4

Design StandardsReceiving AreaARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 1120mm (3’-8”) Wide Door

SPECIAL EQUIPMENTNone

LIGHTING General: 30 FC Special: -- Notes: 1. Lighting control by area; switching

2. 600 x 1200 mm (2'x4')recessedfluorescent light fixture, acrylicprismatic lens, W/2-F32T8 lamps,3500° K CRI=75 (minimum)

POWER General: 500 W (Receptacles) Emergency: -- Notes: --

COMMUNICATIONS ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0AC Load Lighting: 13 w/sm (1.2 W/sf) AC Load Equipment: 32 w/sm (3W/sf) Number of People: 6 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 430: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListReceiving Area

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 4

SYMBOL QTY AI DESCRIPTION

AR CF MODULAR CASEWORK , W/ OVERHEAD CABINETS AND WALL HANGER STRIP

AR CF CABINET, FULL HEIGHT, BIN TYPE, ADJUSTABLE SHELVES, WITH 60 REMOVEABLE BINS, 910mm W x 305mm D x 2130mm H(36"W X 12"D X 84"H)

AR CF CABINET, FULL HEIGHT, OPEN SHELVES, 5 ADJUSTABLE AND 1 FIXED SHELF, AVAILABLE WIDTHS, 915mm (36"), 1200mm (48"); DEPTH 405mm (16"), HEIGHT 2130mm (84")

AR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD

Page 431: VA guide -2009
Page 432: VA guide -2009
Page 433: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 5

Design StandardsExtemporaneous Repackaging & ExtemporanousCompoundingARCHITECTURAL Ceiling: Acoustic lay-in ceiling Tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Resilient Base Floor Finish: Vinyl Composition Tile or Carpet Slab Depr: -- Notes: --

SPECIAL EQUIPMENTNone

LIGHTING General: 100 FC Special: -- Notes: 1.Lighting control by area;

switch(es) at room entrance.2.600 x 1200 mm (2'x4') recessed

fluorescent light fixture, acrylicprismatic lens, W/3-F32T8 lamps,3500° K CRI=75 (Min.).

POWER General: 2400W (Receptacles on electrical

strip mold on modular casework) Emergency: -- Notes: 1.Junction box for 120V power

connection to electrical strip moldon modular casework

2.Junction box for 120V powerconnection to tablet and capsulecounting machine.

3.Junction box for 120V powerconnection to unit dose packermachine.

COMMUNICATIONS ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1.Communications cabling routed

via modular casework utilityaccess lab module to outlets oncasework.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 32 w/sm (3 w/sf) AC Load Equipment: 64 w/sm (5 w/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: Yes Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Drain and vent need to be

chemical resistant type.

Page 434: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListExtemporaneous Repackaging & ExtemporaneousCompounding

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 5

SYMBOL QTY AI DESCRIPTION

AR CF MODULAR CASEWORK , W/ OVERHEAD BINS,UTILITY ACCESS MODULE AND WALL HANGER STRIP

AR CF SINK, CORROSION RESISTING STEEL, 555mm x 405mm x 205mm (22" X 16" X 8")

AR CF PEGBOARD, 405mm W x 600mm H (16"W X 24"H)AR VV CABINET, FILING, UNDER COUNTER, 380mm W x 635mm D

(15"W X 25"D)AR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV MACHINE, COUNTING,TABLET AND CAPSULE, 910mm W x 600mmD

(36"W X 24"D)AR VV MACHINE, UNIT DOSE PACKER, STRIP PACKAGING, 910mm W x

600mm D (36"W X 24"D), 120 VOLTS, 20 AMPSAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD

Page 435: VA guide -2009
Page 436: VA guide -2009
Page 437: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListIntravenous Admixture & Aseptic Transfer

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 6

SYMBOL QTY AI DESCRIPTION

P-418 1 CC LAVATORY, WALL HUNG (PG-18-1, MCS 15450; VOL. 3 SD 380)AR CF MODULAR CASEWORK , W/ OVERHEAD CABINETS AND WALL

HANGER STRIPAR CF REFRIGERATOR, UNDER COUNTER, 5 CU. FT., 120 VOLTS, 20

AMPS, 600mm W x 600mm D x 960mm H (24"W X 24"D X 38"H)AR VV CABINET, INTRAVENOUS (IV), VISUAL CLARITY INSPECTION, 120

VOLTS, 20 AMPS, 760mm W x 600mm D (30"W X 24"D)AR VV CART, STAINLESS STEEL, HEAVY DUTY, WIRE,

1525mm L x 600mm D x 2086mm H (60"L X 24"D X 70"H),205mm (8") CASTERS W/ BRAKE, HORIZONTAL SHELVING

AR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV COMPOUNDER, HIGH SPEED FOR PARENTAL NUTRITION,

ELECTRIC, 120 VOLTS, 20 AMPS1 VV DISPENSER, BIFOLD PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV HOOK, COAT, WALL MOUNTEDAR VV LAMINAR FLOW CLEAN WORK STATION, 1830 LINEAR mm

(72 LINEAR INCHES) OF WORK SPACE, 815mm D x 2050mm H(32"D X 80"H), PROVIDE 120 VOLTS, 20 AMPS

AR VV MACHINE, COUNTING, TABLET AND CAPSULE,915mm W x 600mm D (36"W X 24"D)

1 VV REFRIGERATOR, SELF CONTAINED, PASS-THRU,.90cm (65 CU. FT.), DISPLAY WITH GLASS DOORS,1060mm W x 740mm D x 2060mm H (42"W X 33"D X 81"H),120/208 VOLTS, SINGLE PHASE, 20 AMPS

AR VV SCANNER, LASER, HAND HELD, ELECTRIC, 120 VOLTS, 20 AMPSAR VV SCANNER, LASER, HAND HELD, ELECTRONIC, 120 VOLTS, 20

AMPSAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD

Page 438: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 6

Design StandardsIntravenous Admixture and Aseptic TransferARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile with

washable surface Ceiling Ht: 2740 mm (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Ceramic Tile Floor Finish: Ceramic Tile Slab Depr: -- Notes: 1120 (3”-8”) Wide Door

SPECIAL EQUIPMENTNone

LIGHTING General: 50 FC - 1.6 W/SF Special: -- Notes: 1.Lighting control by area;

switch(es) at room entrance.2.600 x 1200 mm (2'x4') recessed

fluorescent light fixture, acrylicprismatic lens, W/3-F32T8 lamps,3500° K CRI=75 (minimum)

POWER General: 1600 W (Receptacles) Emergency: 2000 W (Refrigerators) Notes: 1. Junction box for 120V power

connection to visual clarityinspection cabinet.

2. Junction box for 120V powerconnection to laminar flow workstation on emergency power.

3. Junction box for 120V powerconnection to pass-throughrefrigerator station on emergencypower.

. Junction box for 120V powerconnection to tablet and capsulecounting machine.

COMMUNICATIONS ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 100 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 10 Room Pressure: See notes below AC Load Equipment: anteroom 32 w/sm (3 w/sf)

buffer room 64 w/sm(6 w/sf) Number of People: 8 Special Exhaust: -- Notes: 1. Maintain admixture (buffer room) under

positive pressure with respect to Ante Room.2. Maintain Ante Room under positive pressure

with respect to Corridor.3. AC load due to equipment is based on use of

water-cooled pass-through refrigerator. If air-cooled refrigerator is used increase heat loadcorrespondingly.

4. HVAC System for Buffer Room (Risk Level II)to be based on 100% outdoor air, HEPAfiltered supply air with 100% exhaust from theroom.

5. Laminar flow clean work station is self-contained and does not require exhaust tooutside the building

6. Provide minimum 12 air changes per hour forBuffer Room and Ante Room

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: Yes Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Sanitary drain and vent need to be

the chemical resistant type.

Page 439: VA guide -2009
Page 440: VA guide -2009
Page 441: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 7

Design StandardsOncology DrugsARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Integral welded seam sheet flooring base Floor Finish: Welded seam sheet flooring Slab Depr: -- Notes: 1. 1060mm (3’-6”) Wide Door

SPECIAL EQUIPMENTNone

LIGHTING General: 70 FC Special: -- Notes: 1.600 x 1200 mm (2'x4')recessed

fluorescent light fixture, acrylicprismatic lens, W/2-F32T8 lamps,4100° K CRI=85 (minimum)

2. 300mm x 1300mm (1’x4”)recessed fluorescent light fixture,acrylic prismatic lens, W/1-F32T8lamps, 4100° K

POWER General: 2800W (Receptacles) Emergency: 2000W (Receptacles) Notes: 1.Junction box for Laminar Flow

Hood on emergency power.

COMMUNICATIONS ADP: Yes Radio: -- Telephone: Yes Intercom: Yes Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: -- 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 12 (Prep Area) Room Pressure: Negative for Prep Area

Equal for reference areawith respect to corridor

AC Load Lighting: 22 w/sm (2 w/sf) both rooms AC Load Equipment: 194 w/sm (18 w/sf) Number of People: 4 per room Special Exhaust: Provide dedicated exhaust

system for Laminar FlowH12-B2 hood. See HVAC Design

Manual for Hospital Projects. Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 442: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListOncology Drugs

VA DESIGN GUIDEPHARMACY SERVICE PAGE 4 - 7

SYMBOL QTY AI DESCRIPTIONREFERENCE AREAP-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1: MCS 15450, VOL3,

SD 380)1 VV WORK STATION, MODULAR1 VV CHAIR, ROTARY, WITH ARMS1 VV CABINET, FILING (LETTER SIZE) 5 DRAWER,

APPROX. 381mm x 635mm x 1524mm (15” x 25” x 60”)1 VV BOOKCASE, SECTIONAL, EACH SECTION,

838mm x 330mm x 381mm (33” x 13” x 15”) WITH 254mm (10”) BASE1 VV BULLETIN BOARD, APPROX. 914mm x 914mm (36” x 36”)AR VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140, H-18-3, CS 801 3)1 VV DISPENSER, PAPER POWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP-ON TYPE,

APPROX. 305mm (12”) DIAMETERAR VV HOOK, COAT, WALL MOUNTED

PREPARATION AREAH7-48 AR CC BIOLOGICAL SAFETY CABINET (LAMINAR FLOW) CLASS II, TYPE

B2 100% DIRECT EXHAUSTED AIR THROUGH WORK SPACE,1219mm x 787mm x 2438mm (48” x 31” x 96”), WITH CUP SINK, AIR,VACUUM AND COLD WATER OUTLETS, 120 VOLTS, 20 AMPRECEPTACLES, GAS OUTLETS NOT REQUIRED(PG-18-1 & PG-18-6, MCS 11610)

1 VV CHAIR, ROTARY, WITH ARMSJ-2 1 CF SINK, CORROSION RESISTING STEEL,

555mm x 405mm x 205mm (22”x16”x8”)AR CF MODULAR CASEWORK, W/OVERHEAD CABINETS AND WALL

HANGER STRIPAR CF REFRIGERATOR, .14 m3 (5 CU. FT), 120 VOLT, 20 AMP,

UNDERCOUNTER, 610mm x 955mm (24” x 38”)AR VV CLOCK, BATTERY OPERATEDAR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140, H-18-3, CS 801 3)AR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD

Page 443: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE CONTENTS - SECTION 5

Section 5Design Guide Platesand Data Sheets:Outpatient Pharmacy

Guide Plate Series Plate Number

Prescription ReceivingEquipment & Utility Plan .............................5-1Reflected Ceiling Plan.................................5-1Design Standards .......................................5-1Equipment Guide List .................................5-1

Filing and AssemblyEquipment & Utility Plan .............................5-2Reflected Ceiling Plan.................................5-2Design Standards .......................................5-2Equipment Guide List .................................5-2

DispensingEquipment & Utility Plan ............................5-3Reflected Ceiling Plan.................................5-3Design Standards .......................................5-3Equipment Guide List .................................5-3

Prepacking & Extemporaneous CompoundingEquipment & Utility Plan .............................5-4Reflected Ceiling Plan.................................5-4Design Standards .......................................5-4Equipment Guide List .................................5-4

Page 444: VA guide -2009
Page 445: VA guide -2009
Page 446: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5-1

Design StandardsPrescription ReceivingARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Fabric (Tackboard Wall Surface) Wainscot: -- Base: Resilient base Floor Finish: Carpet Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 50 FC Special: -- Notes: 1. Single switch per station controls

station lighting. As an alternate,lighting may be controlled by areawith switch(es) located at roomentrance.

2. 600mm x 1200mm (2' x 4')recessed fluorescent light fixture,parabolic louver, W/2-F32T8lamps, 3500°K, CRI=75(minimum)

POWER General: 1000W (receptacles) Emergency: -- Notes:

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1.Nurse Call/Code One/EMS

recorder.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 22 w/sm (2 w/sf) AC Load-Equipment: 54 w/sm (w/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 447: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListPrescription Receiving

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5 - 1

SYMBOL QTY AI DESCRIPTION

AR CF CABINET, UNDER COUNTER, 3 DRAWER,395mm W x 55mm D x 760mm H (15"W X 22"D X 30"H)

AR CF COUNTER TOP, HIGH PRESSURE PLASTIC LAMINATEDECORATIVE

AR VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITH ARMSAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD

Page 448: VA guide -2009
Page 449: VA guide -2009
Page 450: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5-2

Design StandardsFiling and AssemblyARCHITECTURAL Ceiling: Acoustic lay-in ceiling Tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Resilient base Floor Finish: Carpet Slab Depr: -- Notes: --

SPECIAL EQUIPMENTNone

LIGHTING General: 30 FC (ambient) Special: -- Notes: 1. Lighting control by area;

switch(es) at room entrance.2. 600mm x 1200mm (2' x 4')

recessed fluorescent light fixture,acrylic prismatic lens, w/2-F32T8lamps, 4100°k, CRI=75(minimum)

3. Coordinate height of rotary filewith lighting layout.

POWER General: 200 W (receptacles) Emergency: -- Notes: 1. Junction box for 120V power

connection to electric rotary file

COMMUNICATION ADP: -- Radio: -- Telephone: -- Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 18 w/sm (1.7w/sf) AC Load-Equipment: 32 w/sm (3 w/sf) Number of People: 2 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 451: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListFiling and Assembly

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5 - 2

SYMBOL QTY AI DESCRIPTION

AR CF CABINET, UNDER COUNTER, 3 DRAWER,395mm W x 555mm D x 760mm H) 15"W X 22"D X 30"H

AR CF COUNTER TOP, HIGH PRESSURE PLASTIC LAMINATEDECORATIVE

AR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV FILE, ROTARY, MECHANICAL POWER, ELECTRIC, 120 VOLTS,

20 AMPS ( See 5-2 Lighting Note # 3)

Page 452: VA guide -2009
Page 453: VA guide -2009
Page 454: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5-3

Design StandardsDispensingARCHITECTURAL Ceiling: Acoustic lay-in Ceiling Tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Painted Gypsum Wallboard on

reinforced masonry sub-wall. Wainscot: -- Base: Resilient base Floor Finish: Carpet Slab Depr: -- Notes: 1. Refer to VA Construction

Standard CD-49 for securitycriteria

SPECIAL EQUIPMENTNone

LIGHTING General: 100 FC Special: -- Notes: 1. Lighting controlled by area;

switch(es) located at roomentrance.

2. 600 x 1200 mm (2'x4') recessedfluorescent light fixture, acrylicprismatic lens, W/3-F32T8 lamps,4100°K, CRI=85 (Minimum)

POWER General: 500W (receptacles) Emergency: -- Notes: 1. Junction box for 120V power

connection to electronic tabletcounting machine.

2. Junction box(es) for 120Vpower and signal connections topatient notification monitor.

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr -- Notes: 1. Conduit and junction boxes

required for patient notificationmonitor system.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 32 w/sm (3 w/sf) AC Load-Equipment: 54 w/hr (5 w/hr) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 455: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListDispensing

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5 - 3

SYMBOL QTY AI DESCRIPTION

AR CC SERVICE WINDOW, BULLET RESISTIVE, ONE WINDOW ATWHEELCHAIR HEIGHT AND ONE CONVENTIONAL HEIGHT WITHPACKAGE TRANSFER BOX (PG-18-1, MCS 11022; PG-18-4, SD 67B)

AR CF BELT, CONVEYOR, 1 TO 5 BELTS AS REQUIRED (WHENAPPROVED BY VHA)

AR CF MODULAR CASEWORK, W/ OVERHEAD CABINETS AND WALLHANGER STRIP

CF NOTE: DISPENSING SYSTEMS SHALL BE AS DIRECTED BY VHAAR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV COMPUTER, PRINTERAR VV CRT, COMPUTER SYSTEM, WITH KEYBOARDAR VV MACHINE, COUNTING TABLET, ELECTRONIC, 120 VOLTS,

20 AMPS, 600mm W x 600mm D (24"W X 24"D)AR VV MONITORS, HIGH RESOLUTION, PATIENT NOTIFICATION SYSTEM,

BLACK AND WHITE, 685mm (27")

Page 456: VA guide -2009
Page 457: VA guide -2009
Page 458: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5-4

Design StandardsPrepacking & Extemporaneous CompoundingARCHITECTURAL Ceiling: Acoustic Lay-In Ceiling Tile Ceiling Ht: 2740 mm (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Resilient Base Floor Finish: Vinyl Composition Tile or Carpet Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 100 FC Special: -- Notes: 1.Lighting control by area;

switch(es) at room entrance.2.600mm x 1200mm (2' x 4')

recessed fluorescent light fixture,acrylic prismatic lens, W/3-F32T8lamps, 3500°K, CRI=75(minimum)

POWER General: 1000W (receptacles on electrical

strip mold on modular casework). Emergency: -- Notes: 1. Junction box for 120V power

connection to electrical strip moldon modular casework.

2. Junction box for 120V powerconnection to tablet and capsulecounting machine.

3. Junction box for 120V powerconnection to unit dose packer.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Communications cabling routed

via modular case-work utilityaccess lab module to outlets oncasework.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 32 w/sm (3 w/sf) AC Load-Equipment: 54 w/sm (3 w/sf) Number of People: 3 Special Exhaust: -- Notes:

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Sanitary drain and vent need to be

chemical resistant type.

Page 459: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListPrepacking & Extemporaneous Compounding

VA DESIGN GUIDEPHARMACY SERVICE PAGE 5 - 4

SYMBOL QTY AI DESCRIPTION

AR CF MODULAR CASEWORK , W/ OVERHEAD BINS, UTILITY ACCESSMODULE AND WALL HANGER STRIP

AR CF SINK, CORROSION RESISTING STEEL, 555mm x 405mm x 205mm(22" X 16" X 8")

AR CF PEGBOARD, 405mm W x 600mm H (16"W X 24"H)AR VV CABINET, FILING, UNDER COUNTER, 380mm W x 635mm D

(15"W X 25"D)AR VV CHAIR, ROTARY, WITH ARMSAR VV CLOCK, BATTERY OPERATEDAR VV MACHINE, COUNTING, TABLET AND CAPSULE,

910mm W x 610mm D (36"W X 24"D)AR VV MACHINE, UNIT DOSE PACKER, STRIP PACKAGING,

910mm W x 610mm D (36”W x 24”D)AR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD

Page 460: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE CONTENTS - SECTION 6

Section 6Design Guide Platesand Data Sheets:Pharmacy SpecializedProgramsGuide Plate Series Plate Number

Drug Information ServiceEquipment & Utility Plan........................6-1Reflected Ceiling Plan ...........................6-1Design Standards .................................6-1Equipment Guide List............................6-1

Page 461: VA guide -2009
Page 462: VA guide -2009
Page 463: VA guide -2009

Final Draft 11-30-95Revised March 1997

VA DESIGN GUIDEPHARMACY SERVICE PAGE 6-1

Design StandardsDrug Information ServiceARCHITECTURAL Ceiling: Acoustic Lay-In Ceiling Tile Ceiling Ht: 2740 MM (9'-0") Wall Finish: Painted Gypsum Wallboard Wainscot: -- Base: Resilient base Floor Finish: Carpet or Vinyl Composition Tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENTNone

LIGHTING General: 75 FC (ambient) Special: -- Notes: 1. Dual-level switching provided

50/10 FC levels. 2. 600 X 1200 MM (2'x4') recessed

fluorescent light fixture, acrylicprismatic lens, W/2-F32T8lamps, 3500°K, CRI=75 (Min.).

POWER General: 1000W (receptacles) Emergency: -- Notes: --

COMMUNICATION ADP: Yes Radio: --Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 22°C (72°F) Dry Bulb Temp Heating : 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 32 w/sm (3 w/sf) AC Load-Equipment: 54 w/sm (5 w/sf) Number of People: 3 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 464: VA guide -2009

Final Draft 11-30-95Revised March 1997

Equipment Guide ListDrug Information Service

VA DESIGN GUIDEPHARMACY SERVICE PAGE 6 - 1

SYMBOL QTY AI DESCRIPTION

AR CC SHELVING, FREESTANDING STEEL, LIBRARY, SINGLEFACED UNITS, WITH ADJUSTABLE SHELVES,915mm W x 255mm D x 2285mm H (36"W X 10"D X 90"H)(PG-18-1, MCS 11052; PG-18-4)

AR CC SHELVING, SINGLE FACED UNITS, PERIODICAL, WITHSLOPING AND ADJUSTABLE SHELVES,915mm W x 305mm D x 2285mm H (36"W X 12"D X 90"H)(PG-18-1, MCS 11052; PG-18-4)

AR VV BOOKCASE, SECTIONAL (EACH SECTION,315mm W x 330mm D x 380mm H (33"W X 13"D X 15"H))WITH 255mm H (10"H) BASE

1 VV BULLETIN BOARD, APPROX., 915mm W x 915mm H (36"W X 36"H)AR VV CHAIR, ROTARY, WITH ARMSAR VV CHAIR, STRAIGHT, WITH ARMS1 VV CHALKBOARD/TACKBOARD COMBINATION,

1525mm W x 1220mm H (60"W x 48"H)AR VV CLOCK, BATTERY OPERATEDAR VV COMPUTER, PRINTERAR VV PC, COMPUTER SYSTEM, WITH KEYBOARD1 VV TABLE, OCCASIONAL, 1220mm (48”) DIA.AR CF CABINET, UNDERCOUNTER, 3 DRAWER,

395mm W x 555mm D x 760mm H (15”W x 22”D x 30”H)AR CF COUNTER, TOP, HIGH PRESSURE LAMINATED, DECORATIVE

760mm W x 1525m L (30”W x 60”L)

Page 465: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE SECTION 4

Section 4Design Guide Platesand Data Sheets:Administration Space

Guide Plate Series Plate Number

Viewing Room\Library\AV Studies

Equipment & Utility Plan....................4 - 1

Reflected Ceiling Plan.......................4 - 1

Design Standards..............................4 - 1

Equipment Guide List........................4 - 1

Page 466: VA guide -2009
Page 467: VA guide -2009
Page 468: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Viewing Room/Library/AV StudiesDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 4-1

ARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2700 mm (9'-0")

Wall Finish: Vinyl wall covering

Wainscot: ---

Base: Resilient Base

Floor Finish: Carpet

Slab Depr: ---

Notes: 1. 900 mm (3”-0”) wide doorwith tempered glass viewwindow.

2. See VA constructionstandard 34-1, “NoiseTransmission Control”.

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 30 FC

Notes: 1. 600 mm x 1200 mm (2' x4') recessed fluorescentlight fixtures, acrylicprismatic lens, W/2-F32T8lamps, 3500°k, CRI=75(minimum)

POWER

General: 1000 W (Receptacles)

Emergency: ---

Notes: ---

COMMUNICATIONS

ADP: Yes

Radio: ---

Telephone: Yes

Intercom: ---

Public Addr: Yes

Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25 0 C(780 F)

Dry Bulb Temp Heating: 22 0 C (72 0 F)

Minimum % Outside Air: 15%

100% Exhaust Air: ---

Noise Criteria: NC-35

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr.: 4

Room Pressure: 0

AC Load-Equipment: 75 W/sm (7 W/sf)

AC Load-Lighting: 11 W/sm (1 W/sf)

Number of People: 6

Special Exhaust: ---

Notes: ---

Page 469: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Viewing Room/Library/AV StudiesDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 4-1

PLUMBING AND MEDICAL GAS

Cold Water: ---

Hot Water: ---

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: ---

Reagent Grade Water: ---

Medical Air: ---

Medical Vacuum: ---

Oxygen: ---

Notes: ---

Page 470: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Viewing Room/ Library/ AV StudiesEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 4-1

NOTE: THIS ROOM IS NOT REQUIRED IF CINE FILM VIEWING AND STORAGE ROOM IS AVAILABLE CONVENIENTLY CLOSE BY IN CARDIOLOGY LABORATORIES.

1 VV BULLETIN BOARD, 1524 MM X 914 MM (60" X 36")1 VV CART, UTILITYAR VV CHAIR, STRAIGHT, WITH ARMS1 VV CLOCK, BATTERY OPERATEDAR CC COUNTER, WITH KNEE SPACE, 787 MM (31") HIGH

(PG-18-1, MCS 12301 OR 12302)1 VV DRY MARKER BOARD, 1524 MM X 914 MM (60” X 36”)AR VV ILLUMINATORS, FILM, X-RAY, 120 VOLT, 20 AMP, WALL

MOUNTED (1 BANK OF 4)1 VV MONITOR, COLOR, 19”1 VV PERSONAL COMPUTER/ PRINTER1 VV PROJECTION, APPARATUS, 610 MM X 610 MM (24" X 24")1 VV RECEPTACLE, WASTE, 330 MM (13") DIA.1 VV RECORDER / PLAYER, VIDEO CASSETTE (VCR)1 VV TABLE, OFFICE, 1524 MM X 762 MM X 749 MM

(60" X 30" X 29-1/2")1 VV TAPE STORAGE SHELVING, SECTIONAL, EACH

SECTION, 838 MM X 330 MM X 381 MM (33" X 13" X 15") WITH 254 MM (10") BASE

1 VV TELEVISION SET

SYMBOL QTY AI DESCRIPTION

Page 471: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE SECTION 5

Section 5Design Guide Platesand Data Sheets:Patient Care Areas

Guide Plate Series Plate Number

Ventilatory Test Room / SpirometryEquipment & Utility Plan....................5 - 1Reflected Ceiling Plan.......................5 - 1Design Standards..............................5 - 1Equipment Guide List........................5 - 1

Blood Gas Analysis RoomEquipment & Utility Plan....................5 - 2Reflected Ceiling Plan.......................5 - 2Design Standards..............................5 - 2Equipment Guide List........................5 - 2

Exercise Room w/Patient Toilet & ShowerEquipment & Utility Plan....................5 - 3Reflected Ceiling Plan.......................5 - 3Design Standards..............................5 - 3Equipment Guide List........................5 - 3

Special Procedures/Bronchoscopy RoomEquipment & Utility Plan....................5 - 4Reflected Ceiling Plan.......................5 - 4Design Standards..............................5 - 4Equipment Guide List........................5 - 4

Sleep Study Suite w/ Patient Toilet & ShowerEquipment & Utility Plan....................5 - 5Reflected Ceiling Plan.......................5 - 5Design Standards..............................5 - 5Equipment Guide List........................5 - 5

Sleep Study Suite / Diagnostic RoomEquipment & Utility Plan....................5 - 6Reflected Ceiling Plan.......................5 - 6Design Standards..............................5 - 6Equipment Guide List........................5 - 6

Page 472: VA guide -2009
Page 473: VA guide -2009
Page 474: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Ventilatory Test Room/SpirometryDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-1

ARCHITECTURAL

Ceiling: Acoustical Ceiling Tile

Ceiling Ht: 2700 mm (9'-0")

Wall Finish: Vinyl wall covering

Wainscot: ---

Base: Resilient Base

Floor Finish: Vinyl composition tile

Slab Depr: ---

Notes: 1. 1120 mm (3’-8”) wide door with tempered glass view window.

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 30 FC - 75 FC levels in stations.

Notes: 1. Dual-level switching provides50/100 FC levels in stations.

2. 600 mm x 1200 mm (2’x4’) recessed fluorescent light fixtures, acrylic prismatic lens, W/4-F32T8 lamps, 3500°k, CRI=75 (minimum)

POWER

General: 1400 W (receptacles)

Emergency: 500 W (crash cart receptacle)

Notes: ---

COMMUNICATIONS

ADP: ADP needs direct interface of all PET equipment with DHCP, a printer and workstation(s) separate for Spirometry, DLCO, and Diffusing Capacity analysis stations

Radio: ---

Telephone: Yes

Intercom: Yes

Public Addr: ---

Notes: ---

HEATING, VENTILATING, AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24 0C (76 0 F)

Dry Bulb Temp Heating: 25 0C (78 0 F)

Minimum % Outside Air: 15%

100% Exhaust Air: Should be considered for medical centers withhigh tuberculosis cases

Noise Criteria: NC 35

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr.: 6

Room Pressure: 0

AC Load-Equipment: 75 W/sm (7 w/sf)

AC Load-Lighting: 26 W/sm (2.4 W/sf)

Number of People: 8

Note: Provide 12 air changes per hour for Medical Centers with high TB cases.

Page 475: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Ventilatory Test Room/SpirometryDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-1

HEATING, VENTILATING, AND AIRCONDITIONING (cont’d)

Notes: 1. At least two (2) low level grilles should be considered especially for Medical Centers with high

cases of tuberculosis.

PLUMBING AND MEDICAL GAS

Cold Water: Yes

Hot Water: Yes

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: Yes

Reagent Grade Water: Yes

Medical Air: Yes

Medical Vacuum: Yes

Oxygen: Yes

Notes: 1. Central supply for medical gas should be considered.

Page 476: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Ventilatory Test Room/SpirometryEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-1

(A) VENIPUNCTURE STATION

AR VV CART, UTILITY, CORROSION RESISTING STEEL,914 MM X 457 MM X 762 MM (36" X 18" X 30")

1 VV CHAIR, BLOOD-DRAW1 VV CLOCK, BATTERY OPERATED1 VV RECEPTACLE, WASTE, 330 MM (13") DIAMETER1 VV SCALE, PATIENT

(B) SPIROMETRY STATION

NOTE: OUTLET, WALL, MEDICAL AIR, (PG-18-1, MCS 15311; H-18-3, CS 317-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: THE ABOVE OUTLETS TO BE GROUPED TOGETHER.

2 VV CHAIR, STRAIGHT, WITH ARMS1 VV COMPUTER AND PRINTER1 VV MACHINE, SPIROMETRY WITH RECORDER AND

MEDICAL GAS CYLINDERS

(C) PLETHYSMOGRAPHY STATION

NOTE: OUTLET, WALL, MEDICAL AIR, (PG-18-1, MCS 15311; H-18-3, CS 317-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: THE ABOVE OUTLETS TO BE GROUPED TOGETHER.

1 VV CHAIR, STRAIGHT WITH ARMS1 VV PLETHYSMOGRAPH WITH SEPARATE MEDICAL GAS

CYLINDERS

SYMBOL QTY AI DESCRIPTION

Page 477: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Ventilatory Test Room/SpirometryEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-1

(D) DIFFUSION STATION

NOTE: OUTLET, WALL, MEDICAL AIR, (PG-18-1, MCS 15311; H-18-3, CS 317-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: THE ABOVE OUTLETS TO BE GROUPED TOGETHER.

1 VV CHAIR, STRAIGHT WITH ARMSAR VV UNIT, DIFFUSION

(E) SUPPORT SPACE

NOTE: INTERCOM, STATION (PG-18-1, MCS 16760)

NOTE: CC OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: ELECTRICAL RECEPTACLE FOR CRASH CART TO BE ON EMERGENCY POWER.

1 VV BAROMETER, WALL, 1219 MM (48") HIGH1 VV BLANKET, FIRE, ON THE WALL1 VV CART, EMERGENCY, "CRASH CART" APPROX., 914 MM X

533 MM (36" X 21")1 VV CHAIR, STRAIGHT, WITH ARMSAR CC COUNTER, WITH KNEE SPACE & SHELVING ABOVE1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED

P-418 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)1 VV RECEPTACLE, WASTE, 330 MM (13") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 478: VA guide -2009
Page 479: VA guide -2009
Page 480: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Blood Gas Analysis RoomDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-2

ARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2700 mm (9'-0")

Wall Finish: Paint

Wainscot: ---

Base: Resilient Base

Floor Finish: Vinyl composition tile

Slab Depr: --- Notes: 1. 900 mm (3’-0” ) wide door with

tempered glass view window.

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 100 FC

Special: ---

Notes: 1. 600 mm x 1200 mm (2' x 4') recessed fluorescent light fixture, acrylic prismatic lens, W/3-F32T8 lamps, 3500°k, CRI=75 (min.)

POWER

General: 1000 W (Receptacles)

Emergency: ---

Notes: ---

COMMUNICATIONS

ADP: ADP needs direct interface of all ABG equipment with DHCP, a printer, and a personal computer.

Radio: ---

Telephone: Yes

Intercom: ---

Public Addr: ---

Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 22 0 C(72 0F)

Dry Bulb Temp Heating: 22 0C (72 0F)

Minimum % Outside Air: 15%

100% Exhaust Air: Yes

Noise Criteria: NC-40

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr.: 6

Room Pressure: Negative

AC Load-Equipment: 129 W/sm (12 W/sf)

AC Load-Lighting: 27 W/sm (2.5 W/sf)

Number of People: 4

Special Exhaust: ---

Notes: ---

PLUMBING AND MEDICAL GAS

Cold Water: Yes

Hot Water: Yes

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: Yes

Reagent Grade Water: ---

Medical Air: ---

Medical Vacuum: ---

Oxygen: --- Notes: 1.Waste and vent piping

material needs to be chemical resistant type.

Page 481: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Blood Gas Analysis RoomEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-2

2 VV ANALYZER, BLOOD GAS1 VV CHAIR, STRAIGHT, WITH ARMS1 VV CHAIR, STRAIGHT1 VV CLOCK, BATTERY OPERATED1 VV COOXIMETER1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, GLOVE, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPOSAL, NEEDLEAR CF MODULAR CASEWORK1 VV PERSONAL COMPUTER AND PRINTERAR VV RECEPTACLE, WASTE, 330 MM (13") DIAMETER

N-2 1 CF SINK, CORROSION RESISTING STEEL, WITH END OR CORNER DRAIN OUTLET, 559 MM X 406 MM X 279 MM (22" X 16" X 11") (PG-18-1 & PG-18-6, MCS 11602)

1 VV TONOMETER

SYMBOL QTY AI DESCRIPTION

Page 482: VA guide -2009
Page 483: VA guide -2009
Page 484: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Exercise Room w/Patient Toilet & ShowerDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-3

ARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2700 mm (9'-0")

Wall Finish: Paint

Wainscot: ---

Base: ---

Floor Finish: Vinyl composition tile

Slab Depr: 75 mm (3”) @ shower Notes: 1. 1120 mm (3’-8” )wide door

with tempered glass view window in exercise room.

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 30 FC

Notes: 1. Recessed lensed incandescent shower light with 150W A-21 lamp, U.L. listed for wet locations.

2. 600 mm x 1200 mm (2' x4') recessed fluorescent light fixture, acrylic prismatic lens, W/2-F32T8 lamps, 3500°k, CRI=75 (min)U.L. listed for wetlocations.

3. 600 mm x 1200 mm (2’x 4’) recessed fluorescent light fixture, acrylic prismatic lens, W/2-F32T8 lamps, 3500 deg. K, CRI=75 (min.)

POWER

General: 1200W (Receptacles)

Emergency: 500W (crash craft receptacle)

Notes: 1. Junction boxes for elapsed time clock and controls as required.

2. 220 VACv usually required for treadmills.

COMMUNICATIONS

ADP: needs direct interface of all AGBequipment with DHCP, a printer, and a

workstation

Radio: ---

Telephone: Yes

Intercom: Yes

Public Addr: ---

Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24 0 C (760 F)

Dry Bulb Temp Heating: 25 0 C (780 F)

Minimum % Outside Air: 15%

100% Exhaust Air: Yes

Noise Criteria: NC 40

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr 10 (See Notes)

Room Pressure: Negative

AC Load-Equipment: 32 W/sm (3 W/sf)

(Exercise Room)

Page 485: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Exercise Room w/Patient Toilet & ShowerDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-3

HEATING, VENTILATING, AND AIRCONDITIONING (cont’d)

AC Load-Lighting: toilet:27 W/sm (2.5W/sf)exercise: 13W/sm (1.2W/sf)

Number of People: 6 for exercise;1 for toilet

Special Exhaust: ---

Notes: 1.Heat gain from occupant shall be higher than normal

in exercise room.

2.Minimum 10 Air Changes per hour of supply air in

exercise room and minimum of 10 air changes

per hour of exhaust air in shower/ toilet room.

PLUMBING AND MEDICAL GAS

Cold Water: Yes

Hot Water: Yes

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: Yes

Reagent Grade Water: ---

Medical Air: Yes

Medical Vacuum: Yes

Oxygen: Yes

Notes: ---

Toilet and Shower

ARCHITECTURAL

Ceiling: Plaster

Ceiling Ht: (2700 mm) 9’-0”

Wall Finish: Ceramic Tile

Wainscot: ---

Base: Ceramic Tile

Floor Finish: Ceramic Tile

Slab Depr: 75 mm (3”) @ shower

Notes:

Page 486: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Exercise Room with Patient Toilet and ShowerEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-3

(A) Exercise RoomNOTE: INTERCOM, STATION (PG-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: ELECTRICAL RECEPTACLE FOR CRASH CART TO BE ON EMERGENCY POWER.

1 VV CART, EMERGENCY, "CRASH CART" APPROX., 914 MM X 533 MM (36" X 21")

1 VV CHAIR, STRAIGHT1 CC CLOCK, ELECTRIC TIME ELAPSED, RECESSED

(PG-18-1, MCS 10360)1 VV CRT AND PRINTER1 VV DESK 1520 MM X 610 MM (60” X 24”) DESK1 VV DISPENSER, BI-FOLD PAPER TOWEL,

SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV EXERCISER, BICYCLE

P-414 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)1 VV MACHINE, TREADMILL, WITH CONTROLS, 120 VOLT, 20

AMP, APPROX., 1829 MM X 762 MM (72" X 30")1 VV MACHINE, TWELVE (12) LEADS "ECG"1 VV METABOLIC CART1 VV RECEPTACLE, WASTE, 330 MM (13") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 487: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Exercise Room with Patient Toilet and ShowerEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-3

(B) Patient Toilet and Shower

NOTE: NURSE CALL, EMERGENCY STATION WITH CORRIDOR SIGNAL LIGHT CONNECTED TO NEAREST NURSE CONTROL STATION (PG-18-1, MCS 16761)

NOTE: THE ABOVE NURSE CALL-EMERGENCY STATION IS IN ADDITION TO THE BATH EMERGENCY SYSTEM.

AR CC BAR, GRAB FOR SHOWER (PG-18-1, MCS 10800;PG-18-4, SD 13.1)

AR CC BAR, GRAB FOR WATER CLOSET PG-18-1, MCS 10800; PG-18-4, SD 12,14G)

1 CC BAR, TOWEL (PG-18-1, MCS 10800)1 VV CURTAIN, SHOWER1 CC DISH, SOAP, RECESSED (PG-18-1, MCS 10800)1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL

(PG-18-1, MCS 10800; PG-18-4, SD 12)1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR CC HOOK, CLOTHES (PG-18-1, MCS 10800)

P-418 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)1 CC LIGHT, OVER LAVATORY

(H-08-1, MCS 16510; H-08-4, SD 919)2 CC LOCKER, PATIENT, FULL HEIGHT1 CC MIRROR, WHEELCHAIR, 610 MM X 914 MM (24" X 36")

(PG-18-1, MCS 10800; PG-18-4, SD 15)1 CC ROD, FOR SHOWER CURTAIN

(PG-18-1, MCS 10800; PG-18-4, SD 14)1 CC SHELF, STAINLESS STEEL, WALL HUNG,

152 MM X 457 MM (6" X 18") (PG-18-1, MCS 10360;PG-18-4, SD 15)

P-701 1 CC SHOWER, BATH FIXTURE, DETACHABLE, WALL MOUNTED, CONCEALED SUPPLIES (PG -18-1, MCS 15450; PG-18-4, SD 13 & 382)

1 CC STALL, SHOWER, 1219 MM X 1187 MM (48" X 46 -3/4") (PG-18-1, MCS 10170; PG-18-4, SD 13)

P-104 1 CC WATER CLOSET, WALL HUNG, WITH BED PAN WASHER (PG-18-1, MCS 15450; PG-18-4, SD 389)

SYMBOL QTY AI DESCRIPTION

Page 488: VA guide -2009
Page 489: VA guide -2009
Page 490: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Special Procedures/Bronchoscopy RoomDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-4

ARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2890 mm (9'-6")

Wall Finish: Vinyl wall covering

Wainscot: ---

Base: Resilient Base

Floor Finish: Vinyl composition tile

Slab Depr: ---

Notes: 1. 1200 mm (4’-0”) wide door with 200 mm x 250 mm (8” x 10”) tempered glass view window.

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 70 FC

Notes: 1. 600 mm x 1200 mm (2' x 4') recessed fluorescent light fixtures, acrylic prismatic lens, W/3-F32T8 lamps, 3500°k,CRI=75 (minimum)

2. Illumination level controlled by dimmer.

POWER

General: 1200 W (Receptacles)

Emergency: 500 W (Receptacles)

Notes: 1. Special receptacle for mobile fluoroscopy unit. (Coordinate with system supplier).

2. Receptacle for crash cart to be on emergency power.

COMMUNICATIONS

ADP: Yes

Radio: ---

Telephone: Yes

Intercom: Yes

Public Addr: ---

Notes: 1.Junction box for CCTV camera with conduit to adjacent diagnostic room.

2.Junction box for poly somnograph cabling with conduit diagnostic room.

3.Nurse call system.

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24 0 C (76 0 F)

Dry Bulb Temp Heating: 25 0 C (78 0 F)

Minimum % Outside Air: ---

100% Exhaust Air: Yes

Noise Criteria: NC-40

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr.: 8

Room Pressure: Negative

AC Load-Equipment: 86 W/sm (8 W/sf)

AC Load-Lighting: 22 W/sm (2 W/sf)

Number of People: 3

Special Exhaust: ---

Page 491: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Special Procedures/Bronchoscopy RoomDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-4

HEATING, VENTILATING, AND AIRCONDITIONING (cont’d)

Notes: 1. Room exhaust shall be accomplished via low level outlets.

2. Provide a special hood and exhaust for instrument cleaning fumes if instrument cleaning is done here rather than in separate room.

3. If Bronchoscopy room is used for tuberculosis patient exams min. air changes perhr. increases to 12 and provide filtration as per TB Criteria in HVAC Design Manual for Hospital Projects.

PLUMBING AND MEDICAL GAS

Cold Water: Yes

Hot Water: Yes

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: Yes

Reagent Grade Water: ---

Medical Air: Yes

Medical Vacuum: Yes

Oxygen: Yes

Notes: ---

Page 492: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Special Procedures / Bronchoscopy RoomEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-4

NOTE: BRACKET, VACUUM BOTTLE SLIDE (PG-18-1, MCS 15491; PG-18-4, SD 336)

NOTE: INTERCOM, STATION (PG-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: ELECTRICAL RECEPTACLE FOR CRASH CART TO BE ON EMERGENCYPOWER.

1 VV BLOOD PRESSURE MONITOR3 VV BRONCHOSCOPES1 VV CABINET, INSTRUMENTS, 1219 MM X 406 MM X 1829 MM,

(48" X 16" X 72") WITH GLAZED DOORS, SLOPING TOP1 VV CART, EMERGENCY, "CRASH CART" APPROX.,

914 MM X 533 MM (36" X 21")1 VV CART, VIDEO, ENDOSCOPIC1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR VV ILLUMINATORS, FILM, X-RAY, 120 VOLT, 20 AMP, WALL

MOUNTED (1 BANK OF 4)1 VV LIGHT SOURCE, FIBER-OPTIC, ENDOSCOPIC W/ CARTAR CF MODULAR CASEWORK1 VV MONITOR, CARDIAC - ON CART (FLOOR UNIT)1 VV MONITOR, EAR OXIMETER1 VV RECEPTACLE, WASTE, 330 MM (13")

N-2 1 CF SINK, CORROSION RESISTING STEEL, WITH END OR CORNER DRAIN OUTLET, 559 MM X 406 MM X 279 MM (22" X 16" X 11") (PG-18-1 & PG-18-6, MCS 11602)

2 VV STOOL, STEP, APPROX., 508 MM X 406 MM (20" X 16")1 VV TABLE, EXAMINATION-PATIENT, X-RAY, TRANSLUCENT

TOP1 VV X-RAY/FLUOROSCOPE (MOBILE UNIT & MONITOR)

SYMBOL QTY AI DESCRIPTION

Page 493: VA guide -2009
Page 494: VA guide -2009
Page 495: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Sleep Study SuiteDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-5

BedroomARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2700 mm ( 9'-0")

Wall Finish: Paint/ceramic tile

Wainscot: ---

Base: Resilient base

Floor Finish: Vinyl composition tile

Slab Depr: Slope bathroom floor

Notes: ---

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 30 FC

Notes: 1. Wall mounted fluorescent bed light. VA STD. detail E-F-18.

2. Wall mounted night light fixture mounted 450 mm (18”) AFF.

3. Provide electric for infra-red lights.

4. Provide Faraday type shielding for bedrooms and diagnostic rooms.

POWER

General: 1000 W (Receptacles)

Emergency: ---

Notes: 1. All power to bedroomswill be controlled from Diagnostic Rooms.

COMMUNICATIONS

ADP: ---

Radio: ---

Telephone: Yes

Intercom: Microphone and outlets

Public Addr: ---

Notes: 1. Provide closed circuit TV cameras and receivers.

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24 0 C (76 0 F)

Dry Bulb Temp Heating: 25 0 C (78 0 F)

Minimum % Outside Air: 15%

100% Exhaust Air: ---

Noise Criteria: NC-35

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr: 4

Room Pressure: 0

AC Load Equipment: 29 W/sm (2.7 W/sf)

AC Loading Lighting: 11 W/sm (1.0 W/sf)

Number of People: 3

Special Exhaust: ---

Notes: 1. See HVAC Design Manual forHospital Projects for air balance

requirements betweenbedroom and the toilet /shower

Page 496: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Sleep Study SuiteDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-5

PLUMBING AND MEDICAL GAS

Cold Water: ---

Hot Water: ---

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: ---

Reagent Grade Water: ---

Medical Air: ---

Medical Vacuum: Yes

Oxygen: Yes

Notes: Yes

Toilet and ShowerARCHITECTURAL

Ceiling: Plaster

Ceiling Ht: (2700 mm) 9'-0"

Wall Finish: Ceramic tile

Wainscot: ---

Base: Ceramic tile

Floor Finish: Ceramic tile

Slab Depr: 75 mm (3”) @ shower

Notes: ---

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 30 FCshower: 11 W/m2 (1.0 W/sf)toilet: 20 W/m2 (1.8 W/sf)

Notes: 1. Recessed lens incandescent shower light with 150 W A-21 lamp, U.L. listed for wet locations.

2. 300 mm x 1200 mm (1’ x 4’) recessed fluorescent light fixtures, acrylic prismatic lens, W/2-F32T8 lamps, 4100 deg. k, CRI=85 (min.), U.L. listed for wet locations.

POWER

General: 1000 W (Receptacles) Emergency: ---

Notes: 1. All power to bedroomswill be controlled from Diagnostic Rooms.

COMMUNICATIONS

ADP: --- Radio: --- Telephone: --- Intercom: Yes Public Addr: --- Notes: ---

PLUMBING AND MEDICAL GAS

Cold Water: Yes Hot Water: Yes Laboratory Air: --- Laboratory Vacuum: --- Sanitary Drain: Yes Reagent Grade Water --- Medical Air: --- Medical Vacuum: --- Oxygen: --- Notes: ---

Page 497: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Sleep Study SuiteEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-5

(A) Patient Bedroom

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

1 VV BED, RESIDENTIAL DOUBLE BED1 VV CABINET, BEDSIDE, 470 MM X 464 MM X 876 MM

(18-1/2" X 19" X 34-1/2")1 VV CAMERA, CCTV SYSTEM, WALL MTD.1 VV CHAIR, STRAIGHT, WITH ARMS1 VV CHAIR, STRAIGHT

P-413 1 CC LAMINATED PLASTIC SHELF WITH DRAWER610 MM X 914 MM (24” X 36”)

1 VV TABLE, OVER-BED, ADJUSTABLE HEIGHT,838 MM X 356 MM (33" X 14") ON CASTERS

1 VV VIDEO TAPE PLAYER

(B) Patient Toilet/Shower

NOTE: NURSE CALL, EMERGENCY STATION WITH CORRIDOR SIGNAL LIGHT CONNECTED TO NEAREST NURSE CONTROL STATION (PG-18-1, MCS 16761)

NOTE: PROVIDE INTERCOM BETWEEN SUITE AND DIAGNOSTIC ROOM

NOTE: THE ABOVE NURSE CALL-EMERGENCY STATION IS IN ADDITION TO THE BATH EMERGENCY SYSTEM.

AR CC BAR, GRAB SHOWER (PG-18-1, MCS 10800; PG-18-4,SD 13,13.1)

AR CC BAR, GRAB FOR WATER CLOSET (PG -18-1, MCS 10800; PG-18-4, SD 12, 146)

1 CC BAR, TOWEL (PG-18-1, MCS 10800)1 VV CURTAIN, SHOWER1 CC DISH, SOAP, RECESSED (PG-18-1, MCS 10800)1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED

SYMBOL QTY AI DESCRIPTION

Page 498: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Sleep Study SuiteEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-5

(B) Patient Toilet/Shower (cont’d)

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG -18-1, MCS 10800; PG-18-4, SD 12)

2 CC HOOK, CLOTHES (PG-18-1, MCS 10800)P-414 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)

1 CC LIGHT, OVER LAVATORY (PG-18-1, MCS 16510; PG-18-4,SD 919)

1 CC MIRROR, WHEELCHAIR, 610 MM X 914 MM (24" X 36") (PG-18-1, MCS 10800; PG-18-4, SD 15)

1 CC ROD, FOR SHOWER CURTAIN (PG-18-1, MCS 10800; PG-18-4, SD 14)

1 CC SHELF, STAINLESS STEEL, WALL HUNG, 152 MM X 457 MM (6" X 18") (H-08-1, MCS 10360; PG-18-4, SD 15)

P-701 1 CC SHOWER, BATH FIXTURE, DETACHABLE, WALL MOUNTED, CONCEALED SUPPLIES (PG -18-1, MCS 15450; PG-18-4, SD 13 & 382)

1 CC STALL, SHOWER, 910 MM X 910 MM (36" X 36") (PG-18-1, MCS 10170; PG-18-4, SD 13)

P-104 1 CC WATER CLOSET, WALL HUNG, WITH BED PAN WASHER (PG-18-1, MCS 15450; PG-18-4, SD 389)

SYMBOL QTY AI DESCRIPTION

Page 499: VA guide -2009
Page 500: VA guide -2009
Page 501: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Sleep Study Suite/Diagnostic RoomDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-6

ARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2700 mm (9'-0")

Wall Finish: Paint

Wainscot: ---

Base: Resilient Base

Floor Finish: Vinyl composition tile

Slab Depr: ---

Notes: ---

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 30 FC

Notes: 1. 600 mm x 1200 mm (2' x 4') recessed fluorescent light fixtures, acrylic prismatic lens, W/2-F32T8 lamps, 3500°k, CRI=75 (minimum).

POWER

General: 1000 W (Receptacles)

Emergency: 500 W (crash cart receptacle)

Notes: ---

COMMUNICATIONS

ADP: Yes

Radio: ---

Telephone: Yes

Intercom: Yes

Public Addr: ---

Notes: 1.Junction box for CCTVsystem with conduit fromadjacent patient bedroom

2.Junction box forpolysomnograph cablingwith conduit from adjacentpatient bedroom.

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24 deg C (76 deg F)

Dry Bulb Temp Heating: 25 deg C (78 deg F)

Minimum % Outside Air: 15%

100% Exhaust Air: ---

Noise Criteria: NC-35

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr.: 4

Room Pressure: 0

AC Load-Equipment: 75 W/sm (7 W/sf)

AC Load-Lighting: 22 W/sm (2 W/sf)

Number of People: 3

Special Exhaust: ---

Notes: ---

Page 502: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Sleep Study Suite/Diagnostic RoomDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 5-6

PLUMBING AND MEDICAL GAS

Cold Water: Yes

Hot Water: Yes

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: ---

Reagent Grade Water: ---

Medical Air: ---

Medical Vacuum: ---

Oxygen: ---

Notes: ---

Page 503: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Sleep Study Diagnostic RoomEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 5-6

NOTE: ELECTROMAGNETIC INTERFERENCE (EMI) EMI., SHIELDING PROVIDED IF THE LOCAL CONDITIONS DO NOT MEET CRITERIA ENUMERATED IN VA STANDARD 58-1 OF H-18-3, DATED JUNE 23, 1989.

NOTE: ELECTRICAL RECEPTACLE FOR CRASH CART TO BE ON EMERGENCY POWER.

NOTE: PROVIDE INTERCOM BETWEEN SUITE AND DIAGNOSTIC ROOM.

NOTE: ONE POLYSOMNOGRAPH MACHINE PER EACH PATIENT'S BED ROOM.

NOTE: INTEGRAL BLINDS (ADJUSTABLE - ON/OFF) (PG-18-1, MCS 12513)

1 VV BOOKSHELF 610 MM X 305 MM X 910 MM (24” X 12” X 36”)1 VV CART, EMERGENCY, "CRASH CART" APPROX., 914 MM X

533 MM (36" X 21") -IN ADJACENT CORRIDORAR CC COUNTER, WITH KNEE SPACE, 787 MM (31") HIGH

(PG-18-1, MCS 12301 OR 12302)2 VV CHAIR, POSTURE-TYPE, SWIVEL1 VV CLOCK, BATTERY OPERATED2 VV CONTROL CONSOLE, CCTV SYSTEM1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV ELECTRICAL TUBE DRYING RACK

P-414 1 VV LAVATORY, STRAIGHT BACK (PG-18-1; MCS 15450)2 VV MACHINE, POLYSOMNOGRAPH, WITH TWELVE (12)

CHANNELS CAPABILITY2 VV MONITORS, 230 MM (9”), CCTV2 VV RECEPTACLE, WASTE, 330 MM (13") DIAMETER2 VV RECORDER, VIDEO, CCTV SYSTEM1 VV SUPPLY CABINET, FIRE PROOF CAB. 910 MM X 435 MM

X 1830 MM (36” X 18” X 72”)

SYMBOL QTY AI DESCRIPTION

Page 504: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

VA DESIGN GUIDEPULMONARY MEDICINE SERVICESECTION 6

Section 6Design Guide Platesand Data Sheets:Support Spaces

Guide Plate Series Plate Number

Equipment Storage RoomEquipment & Utility Plan...................6 - 1Reflected Ceiling Plan......................6 - 1Design Standards.............................6 - 1Equipment Guide List.......................6 - 1

Scope Cleaning / Clean StorageEquipment & Utility Plan...................6 - 2Reflected Ceiling Plan......................6 - 2Design Standards.............................6 - 2Equipment Guide List.......................6 - 2

Page 505: VA guide -2009
Page 506: VA guide -2009
Page 507: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Equipment Room Storage/Supply/Clean-up/Repair/Testing

Design Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 6-1

ARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2700 mm (9'-0")

Wall Finish: Paint

Wainscot: ---

Base: Resilient Base

Floor Finish: Vinyl composition tile

Slab Depr: ---

Notes: 1. 1120 mm (3’-8” ) wide doors with tempered glass view windows.

SPECIAL EQUIPMENT

None

ELECTRICAL

General: 20 FC

storage/supply: 50 FC

clean-up/repair: 30 FC

equipment storage: 20 FC

Notes: 1. 600 mm x 1200 mm (2' x 4') recessed fluorescent light fixtures, acrylic prismatic lens, W/2-F32T8 lamps, 3500°k, CRI=75 (minimum)

POWER

General: 2800 W (Receptacles)

Emergency: ---

Notes: ---

COMMUNICATIONS

ADP: ---

Radio: ---

Telephone: Yes

Intercom: ---

Public Addr: ---

Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25 0 C (78 0 F)

Dry Bulb Temp Heating: 22 0 C (72 0 F)

Minimum % Outside Air: 15%

100% Exhaust Air: For clean-up room only

Noise Criteria: NC-40

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr.: 10-clean-up room

4 for all others

Room Pressure: Negative

AC Load-Equipment: 32 W/sm (3 W/sf)

AC Load-Lighting:

(A)storage: 11 W/sm ( 1 W/sf)

(B)clean-up: 27 W/sm (2.5 W/sf)

(C)equip./storage: 29 W/sm (2.7 Wsf)

Number of People: 3 per room

Special Exhaust: ---

Notes: 1.Provide counter top exhaustfor clean-up/repair room

Page 508: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Equipment Room Storage/Supply/Clean-up/Repair/Testing

Design Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 6-1

PLUMBING AND MEDICAL GAS

Cold Water: Yes

Hot Water: Yes

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: Yes

Reagent Grade Water: ---

Medical Air: Yes

Medical Vacuum: Yes

Oxygen: Yes

Notes: 1. Sink drain pipe, waste and ventlocated in the clean-up repairroom needs to be chemicalresistant type.

Page 509: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Equipment Room Storage/Supply/Clean-Up/Repair/TestingEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 6-1

(A) Storage/Supply Room

T-37 AR CC SHELVING, FLOOR-STANDING, STEEL, WITH SLOPING TOP AND 6 ADJUSTABLE SHELVES,914 MM X 457 MM X 2134 MM (36" X 18" X 84") (PG -18-1, MCS 10671; PG-18-4)

(B) Clean-Up/Repair/Testing RoomNOTE: ELECTRICAL, STRIP MOLDING, 120 VOLT, 20 AMP (FOR WORK COUNTER) (PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE MOUNTED

1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR CF MODULAR CASEWORK

N-2 1 CF SINK, CORROSION RESISTING STEEL, WITH END OR CORNER DRAIN OUTLET, 559 MM X 406 MM X 279 MM (22" X 16" X 11") (PG-18-1 & PG-18-6, MCS 11602)

1 VV BENCH, WORK, KNEE-SPACE UNDER. 2 SHELVES, OPEN, ABOVE BENCH1829 MM X 305 MM X 762 MM(72" X 12" X 30")

AR VV STOOL, ADJUSTABLE HEIGHT, WITHOUT ARMS

(C) Equipment Storage

T-37 AR CC SHELVING, FLOOR-STANDING, STEEL, WITH SLOPING TOP AND 6 ADJUSTABLE SHELVES,914 MM X 457 MM X 2134 MM (36" X 18" X 84") (PG -18-1, MCS 10671; PG-18-4)

SYMBOL QTY AI DESCRIPTION

Page 510: VA guide -2009
Page 511: VA guide -2009
Page 512: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Scope Cleaning/Clean StorageDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 6-2

ARCHITECTURAL

Ceiling: Acoustical ceiling tile

Ceiling Ht: 2700 mm (9'-0")

Wall Finish: High build glazed coating

Wainscot: ---

Base: Integral welded seam

Floor Finish: Welded seam sheet flooring

Slab Depr: --- Notes: 1. 900 mm (3’-0”) wide doors

with tempered glass view windows.

SPECIAL EQUIPMENTNone

ELECTRICAL

General: 30 FC

Special: ---

Notes: 1.600 mm x 1200 mm (2'x 4') recessed fluorescent light fixtures, acrylic prismatic lens, W/2-F32T8 lamps,3500°k, CRI=75 (min.)

POWER

General: 1800 W (Receptacles)

Emergency: ---

Notes: 1.Special receptacle for endoscope washer, coordinate with supplier.

COMMUNICATIONS

ADP: ---

Radio: ---

Telephone: Yes

Intercom: ---

Public Addr: ---

Notes: ---

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25 0 C (78 0 F)

Dry Bulb Temp Heating: 22 0 C (72 0 F)

Minimum % Outside Air: ---

100%Exhaust Air: Yes

Noise Criteria: NC 40

Steam: ---

Relative Humidity/Cooling: 50%

Relative Humidity/Heating: 30%

Minimum Air Changes/Hr.: 10- scope cleaning

4 clean storage

Room Pressure: Negative for scope cleaning

positive for clean storage

AC Load-Equipment:

scope cleaning 54 W/sm (5 W/sf)

clean storage 22 W/sm (2W/sf)

AC Load-Lighting:

scope cleaning 13W/sm (1.2W/sf)

clean storage 19W/sf (1.8W/sf)

Number of People: 3 per room

Special Exhaust: ---

Notes: 1.Provide counter to exhaust for scope cleaningroom.

Page 513: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Scope Cleaning/Clean StorageDesign Standards

VA DESIGN GUIDEPULMONARY MEDICINE SERVICE PLATE 6-2

PLUMBING AND MEDICAL GAS

Cold Water: Yes

Hot Water: Yes

Laboratory Air: ---

Laboratory Vacuum: ---

Sanitary Drain: Yes

Reagent Grade Water: ---

Medical Air: Yes

Medical Vacuum: Yes

Oxygen: Yes

Notes: 1.Sink, drain pipe, waste and vent from the sink located in the scope cleaning room needs to be chemical resistant type.

Page 514: VA guide -2009

FINAL DRAFT 9-26-95REVISED FEBRUARY 1997

Scope Cleaning/Clean StorageEquipment Guide List

VA DESIGN GUIDE PULMONARY MEDICINE SERVICE PLATE 6-2

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL VACUUM (PG-18-1, MCS 154 91; H-18-3, CS 310-1)

(A) Scope Cleaning

1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE

MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTEDAR CF MODULAR CASEWORK1 CF SINK, DOUBLE BOWL, SELF RIMMING, CRS4 VV WASHER, ENDOSCOPE

(B) Clean Scope Storage

AR CF MODULAR CASEWORKAR VV CABINET, ENDOSCOPE STORAGE

SYMBOL QTY AI DESCRIPTION

Page 515: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE CONTENTS - SECTION 4

Section 4Design Guide Platesand Data Sheets:Patient Care Areas

Guide Plate Series PlateNumber

General Purpose Radiographic Rm. w/ControlEquipment & Utility Plan ..........................4-1Reflected Ceiling Plan..............................4-1Design Standards ....................................4-1Equipment Guide List ..............................4-1

Dedicated Chest RoomEquipment & Utility Plan ..........................4-2Reflected Ceiling Plan..............................4-2Design Standards ....................................4-2Equipment Guide List ..............................4-2

Radiographic Fluoroscopic Rm. w/ControlEquipment & Utility Plan ..........................4-3Reflected Ceiling Plan..............................4-3Design Standards ....................................4-3Equipment Guide List ..............................4-3

Special Procedure Rm. (non-affiliated ControlRoom)

Equipment & Utility Plan ..........................4-4Reflected Ceiling Plan..............................4-4Design Standards ....................................4-4Equipment Guide List ..............................4-4

CT Suite - Mid-Level Imaging SystemEquipment & Utility Plan ..........................4-5Reflected Ceiling Plan..............................4-5Design Standards ....................................4-5Equipment Guide List ..............................4-5

Page 516: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE CONTENTS - SECTION 4 (cont.)

Section 4Design Guide Platesand Data Sheets:Patient Care Areas

Guide Plate Series PlateNumber

Ultrasound RoomEquipment & Utility Plan ..........................4-6Reflected Ceiling Plan..............................4-6Design Standards ....................................4-6Equipment Guide List ..............................4-6

Mammography RoomEquipment & Utility Plan ..........................4-7Reflected Ceiling Plan..............................4-7Design Standards ....................................4-7Equipment Guide List ..............................4-7

Automated Radiographic w/ControlEquipment & Utility Plan ..........................4-8Reflected Ceiling Plan..............................4-8Design Standards ....................................4-8Equipment Guide List ..............................4-8

Page 517: VA guide -2009
Page 518: VA guide -2009
Page 519: VA guide -2009
Page 520: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-1

Design StandardsGeneral Purpose Radiographic Room w/ControlARCHITECTURAL

Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2890 mm (9'-6") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: 100 mm (4”) Notes: 1200mm (4’-0”) wide door. See VA

Construction Standard 64-1,X-RayRadiation Shielding and Special Control”.

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FC Special: -- Notes: 1. Continuous fluorescent

direct/indirect wall mountedfixture, acrylic prismatic lens ontop and bottom, W/2-F32T8lamps, 3500 deg. K, CRI=75(min.)

2. Illumination level controlled bydimmer.

3. Recessed lensed incandescentdown light W/100W, A-21 lamps

POWER

General: -- Emergency: -- Notes: 1. The electrical plan as shown is to

be used as a guide only. Equipmentlocations, dimensions and wiringrequirements to be per the x-raysystem suppliers equipment installationdrawings.

2. Electrical trades shall providenecessary conduit, openings, bushings,nipples, flexible conduit etc., asrequired at the various junction boxes,duct and conduit terminations to allowproper connections of the x-rayequipment and related accessories.

POWER (cont.)Notes: 3. 480V., 3P., 150A., adjustable trip

flush mounted circuit breaker with shunt trip. Run empty 600 mm (2’) C.from circuit breaker to x-ray duct above finished ceiling.

4. 250 mm x 140 mm (10” x 5-½”) deepflush vertical wall duct with 300 mm(12”) wide screw-on cover. Connectto x-ray duct above finished ceiling andterminate at finished floor.

5. 250 mm x 140 mm (10” x 5-½”) deepx-ray duct above finished ceiling with250 mm (10”) wide screw-on cover.Connect to vertical wall duct.

6. Emergency Power Off (EPO) push button station. Connect to shunt trip circuit breakers.

7. Run 13 mm (½”) C. from door switchto junction box at x-ray controller.Connect door switch so t that ifdoor is opened the x-ray system willbe shut off.

COMMUNICATIONS

ADP: -- Radio: Yes Telephone: -- Intercom: -- Pub. Addr: --Notes:

Page 521: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-1

Design StandardsGeneral Purpose Radiographic Room w/ControlHEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24°C (75°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: No Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: 0 AC Load Lighting 40 W/m 2 (3.7 W/sf) AC Load Equipment: 97 W/m2 (9 W/sf) Number of People: 6 Special Exhaust: -- Notes: 1. See HVAC Design Manual for

Hospital Projects for leadwrapping of ductwork penetratinglead lined walls.

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: Possible Medical Air: -- Medical Vacuum: Yes Oxygen: Yes Notes: 1. Check with the Medical Center

regarding Silver RecoverySystem.

Page 522: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-1

General Purpose Radiographic Room w/Control

NOTE: OPTIONAL COMPONENTS TO BE DETERMINED BY VETERANS HEALTH ADMINISTRATION

NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (OXYGEN, AIR, VACUUM OUTLET AND BRACKET).

NOTE: OUTLETS TO BE ON THE WALL, NEAR HEAD END OF X-RAY TABLE, 1524mm (60") ABOVE THE FLOOR.

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491;H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT.

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP (PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (PG-18-1, MCS 13091; H-18-3, CS 64-1; PG-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

1 CC DISPENSER, SOAP, WALL MOUNTED WITH FOOT CONTROL (PG-18-1, MCS 10800)

P-418 1 CC LAVATORY, STRAIGHT BACK, SENSOR CONTROL(PG-18-1, MCS 15450 VOL3 SD 380)

1 CF CABINET, STORAGE, WALL MOUNTED, 254mm (10") ABOVE FINISHED FLOOR, 5 SHELVES AND FOLDING DOOR, APPROX., 610mm x 406mm x 1575mm (24" x 16" x 62")

1 VC X-RAY UNIT, RADIOGRAPHIC AND FLUOROSCOPIC CONSISTS OF THE FOLLOWING COMPONENTS:

1 VC BUCKY, TILT, WALL MOUNTED(USE IN TYPE R-F #2 AND TYPE R-F #3)

1 VC CAMERA UNIT, CINE, FOR USE WITH IMAGE INTENSIFIER (OPTIONAL)

1 VC CAMERA, SPOT, 100 OR 105mm (USE IN TYPE R-F #3)1 VC CAMERA, TV (FOR USE WITH IMAGE INTENSIFIER) (OPTIONAL)1 VC CONTROL, CINE CAMERA1 VC IMAGE INTENSIFIER, 152mm, 229mm (6", 9"), OR DUAL TYPE TO

BE DETERMINED ON PROJECT BASIS1 VC MODULE, POWERAR VC MONITOR, FOR USE WITH IMAGE INTENSIFIER

SYMBOL QTY AI DESCRIPTION

Page 523: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-1

General Purpose Fluoroscopic Room w/Control

1 VC RAILS, CEILING FOR TUBE CARRIAGE, UNIVERSAL MOUNT1 VC RECORDER, TV TAPE1 VC STARTER, TUBE, HIGH SPEED1 VC TABLE, 90 DEGREE - 15 DEGREE TRENDELENBURG R&F,

WITH SPOT FILM DEVICE (TWO-WAY OR FOUR WAY TABLE TOP AND SIZE OF SPOT FILM DEVICE TO BE DETERMINED ON PROJECT BASIS)

1 VC TABLE, TILT, 90 DEGREE - 90 DEGREE R&F, WITH SPOT FILM DEVICE (TWO-WAY OR FOUR WAY TABLE TOP AND SIZE OF SPOT FILM DEVICE TO BE DETERMINED ON PROJECT BASIS)

1 VC TRANSFORMER, HIGH TENSION, X-RAY1 VC TUBE CARRIAGE, CEILING MOUNTED1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPOSAL, NEEDLES, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 787mm (20" x 31"), 2 IN 12 VV RACK, GLOVE/APRON, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305mm (12") DIAMETER

General Purpose Fluoroscopic Control Area

NOTE: PROVIDE INTERCOM STATION IN CONTROL BOOTH CONNECTED TO REMOTE STATION IN X-RAY ROOM, WHEN CONTROL BOOTH IS SEPARATED FROM X-RAYROOM.

NOTE: INCANDESCENT, DIMMING SYSTEM (PG-18-1, MCS 16510)

NOTE: INTERCOM, STATION (PG-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: WINDOW, LEAD GLASS, MINIMUM 457mm x 610mm (18" x 24") (PG-18-1, MCS 13091; PG-18-4,)

1 VC CONSOLE, CONTROL, X-RAY, FOR RADIOGRAPIC UNIT (CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

Page 524: VA guide -2009
Page 525: VA guide -2009
Page 526: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-2

Design StandardsDedicated Chest RoomARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2890 mm (9'-6") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: 100 mm (4”) Notes: 1. 1200 mm (4’-0”) wide door. See

VA Construction Standard 64-1,X-Ray Radiation Shielding andSpecial Control”.

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FC Special: -- Notes: 1.Continuous fluorescent

direct/indirect wall mounted lightfixture, acrylic prismatic lens on topand bottom, W/2-F32T8 lamps,3500 deg. K, CRI=75 (min.)

2. Recessed, lensed incandescent downlight with 100W, A-21 lamp.

3. Down light illumination level controlled by dimmer.

POWER

General: 1000W (Non-PBPU receptacles) Emergency: -- Notes: 1. The electrical plan as shown is to

be used as a guide only.Equipment locations, dimensionsand wiring requirements to be perthe x-ray system suppliersequipment installation drawings.

2. Electrical trades shall providenecessary conduit, openings,bushings, nipples, flexible conduitetc., as required at the variousjunction boxes, duct and conduitterminations to allow properconnections of the x-ray equipmentand related accessories.

POWER (cont.)Notes: 3. 480V., 3P., 150A., adjustable trip flush

mounted circuit breaker with shunttrip. Run empty 50 mm (2” C.) fromcircuit breaker to x-ray duct abovefinished ceiling.

4. 240V, 2P., 30A flush MTD. circuitbreaker for film processor.

5. 250 mm x 140 mm (10’ x 5-½”) deepflush vertical wall duct with 300 mm(12”) wide screw-on cover. Connect tox-ray duct above finished ceiling andterminate at finished floor.

6. 250 mm x 140 mm (10’ x 5-½”) deepx-ray duct above finished ceiling with250 mm (10”) wide screw-on cover.Connect to vertical wall duct.

7. Emergency Power Off (EPO) pushbutton station. Connect to shunt tripcircuit breakers.

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1.Nurse Call

Page 527: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-2

Design StandardsDedicated Chest RoomHEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 15 100% Exhaust Air: -- Noise Criteria: NC-35 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load Lighting: 43 W/m ( 4 W/sf) AC Load-Equipment: 65 W/m (6 W/sf) Number of People: 6 Special Exhaust: -- Notes: 1. See HVAC Design Manual for

Hospital Projects for lead wrapping ofductwork penetrating lead lined walls.

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: --

Page 528: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-2

Dedicated Chest Room

NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO SILVER RECOVERY SYSTEM, IF REQUIRED.

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT.

NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (OXYGEN, AIR, VACUUM OUTLET AND BRACKET).

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: FLOOR DRAIN, NEAR FILM PROCESSING UNITS (PLUMBING DESIGN CRITERIA AND INSTRUCTIONS)

NOTE: FLOOR DRAIN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN CRITERIA & INSTRUCTIONS)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (PG-18-1, MCS 13091; H-18-3, CS 64-1; PG-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

1 CC DISPENSER, SOAP, WALL MOUNTED WITH FOOT CONTROL (PG-18-1, MCS 10800)

P-802 1 CC HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED, CONCEALED SUPPLY PIPES(PG-18-1, MCS 15450; PG-18-4, SD 4.2)

1 CC FLOOR DRAIN, NEAR FILM PROCESSORP-418 1 CC LAVATORY, STRAIGHT BACK, SENSOR CONTROL

(PG-18-1, MCS 15450 VOL3, STD 380)1 VC AUTOMATED CHEST UNIT - CONSISTS OF THE FOLLOWING

COMPONENTS:1 VC CABINET, RACK1 VC CALCULATOR, HEAT ANODE1 VC MODULE, POWER1 VC PROCESSOR, FILM, AUTOMATED (TYPE OF FILM

PROCESSOR-TOP OR END FILM DISCHARGE TO BE DETERMINED ON PROJECT BASIS)

1 VC RAILS, TUBE, CEILING MOUNTED1 VC STAND, TUBE, CEILING MOUNTED1 VC STAND, UNIT, CHEST1 VC STARTER, TUBE, HIGH SPEED

SYMBOL QTY AI DESCRIPTION

Page 529: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-2

Dedicated Chest Room (cont’d)

1 VC TANK, REPLENISHER, 95 L (25 GAL.) CAPACITY AND CURBING,2 FOR EACH PROCESSOR

1 VC TRANSFORMER, HIGH TENSION, X-RAY1 VC UNIT, CHEST, LESS TUBE STAND1 VC UNIT, FORCED EXTINCTION1 VC UNIT, TRANSPORT, FILM1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPOSAL, NEEDLES, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV RACK, GLOVE/APRON, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305mm

(12") DIAMETER

Dedicated Chest Room - Control Area

NOTE: INCANDESCENT, DIMMING SYSTEM (PG-18-1, MCS 16510)

NOTE: WINDOW, LEAD GLASS, MINIMUM 457mm x 610mm (18" x 24") (PG-18-1, MCS 13091; PG-18-4,)

1 VC CONSOLE, CONTROL, X-RAY, FOR AUTOMATED CHEST UNIT (CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED, APPROX., 508mm x 787mm (20" x 31"), 2 IN 1

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

Page 530: VA guide -2009
Page 531: VA guide -2009
Page 532: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-3

Design StandardsRadiographic Fluoroscopic Room w/ControlARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2890 mm (9'-6") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: 100 mm (4”) Notes: 1200 mm (4’-0”) wide door. See VA

Construction Standard 64-1, X-RayRadiation Shielding and SpecialControl”.

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FC - 2.0W/sf Special: 10FC - 3.0W/sf- Notes: 1. Continuous fluorescent

direct/indirect wall mounted fixture,acrylic prismatic lens on top andbottom, W/1-F32T8 lamp 3500deg. K, CRI=75 (min.)

2. “X-ray in use DO NOT ENTER”sign fixture.

3. Recessed, lensed incandescentdownlight with 100W, A-21 lamp.

4. Provide dimmers for down lightIllumination.

POWER

General: 1000W (Receptacles) Emergency: -- Notes: 1.The electrical plan as shown is to be

used as a guide only. Equipmentlocations, dimensions and wiringrequirements to be per the x-raysystem suppliers equipmentinstallation drawings.

2.Electrical trades shall providenecessary conduit, openings,bushings, nipples, flexible conduitetc., as required at the variousjunction boxes, duct and conduitterminations to allow properconnections of the x-ray equipmentand related accessories.

POWER (cont.) Notes: 3. 480V., 3P., 150A., adjustable trip

flush mounted circuit breaker withshunt trip. Run empty 600 mm (2’)C. from circuit breaker to x-rayduct above finished ceiling.

4. 240V, 2P., 30A flush MTD. circuitbreaker for film processor.

5. 250 mm x 140 mm (10” x 5-½”)deep flush vertical wall duct with300mm (12”) wide screw-oncover. Connect to floor duct andto x-ray duct above finishedceiling.

6. 250 mm x 140 mm (10” x 5-½”)deep flush vertical wall duct with300 mm (12”) wide screw-oncover. Connect to x-ray ductabove finished ceiling andterminate at finished floor.

7. 250 mm x 140 mm (10” x 5-½”)deep x-ray duct above finishedceiling with 250 mm (10”) widescrew-on cover. Connect tovertical wall duct.

8. Emergency Power Off (EPO)push button station. Connect toshunt trip breakers.

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: Yes Pub. Addr -- Notes: 1. Nurse Call in toilet room to

annunciate at reception desk.

Page 533: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-3

Design StandardsRadiographic Fluoroscopic Room w/ControlHEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24°C (75°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: radiographic supply: 6

Toilet exhaust: 10Room Pressure: negative for radiographic:

Toilet: negative AC Load Lighting: 35 W/m 2 (3.2 W/sf) AC Load-Equipment:

Radiographic: 97 W/sm (9 W/sf Number of People: 6 Special Exhaust: -- Notes: 1. See HVAC Design Manual for

Hospital Projects for lead wrapping ofductwork penetrating lead lined walls.

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: --

Page 534: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-3

Radiographic Fluoroscopic Room w/Control

NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO SILVER RECOVERY SYSTEM, IF REQUIRED.

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT.

NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (OXYGEN, AIR, VACUUM OUTLET AND BRACKET)

.NOTE: OUTLETS TO BE ON THE WALL, NEAR HEAD END OF X-RAY TABLE, 1524mm (60") ABOVE THE FLOOR.

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

NOTE: SHADES, EXTERIOR WINDOWS (PG-18-1, MCS 12513)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (PG-18-1, MCS 13091; H-18-3, CS 64-1; PG-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

1 CC DISPENSER, SOAP, WALL MOUNTED WITH FOOT CONTROL (PG-18-1, MCS 10800)

P-418 1 CC LAVATORY, SENSOR CONTROL (PG-18-1, MCS 15450, VOL. 3SD 380)

1 CF CABINET, STORAGE, WALL MOUNTED, 254mm (10") ABOVE FINISHED FLOOR, 5 SHELVES AND FOLDING DOOR, APPROX., 610mm x 406mm x 1575mm (24" x 16" x 62")

1 VC X-RAY UNIT, RADIOGRAPHIC AND FLUOROSCOPIC CONSISTS OF THE FOLLOWING COMPONENTS:

1 VC BUCKY, TILT, WALL MOUNTED (USE IN TYPE R-F #2 AND TYPER-F #3)

1 VC CAMERA UNIT, CINE, FOR USE WITH IMAGE INTENSIFIER (OPTIONAL)

1 VC CAMERA, SPOT, 100mm OR 105mm (USE IN TYPE R-F #3)1 VC CAMERA, TV (FOR USE WITH IMAGE INTENSIFIER) (OPTIONAL)1 VC CHANGER, CASSETTE1 VC CONTROL, CINE CAMERA1 VC IMAGE INTENSIFIERM 152mm, 229mm (6”, 9”), OR DUAL TYPE TO

BE DETERMINED ON PROJECT BASIS

SYMBOL QTY AI DESCRIPTION

Page 535: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-3

Radiographic Fluoroscopic Room w/Control

1 VC MODULE, POWERAR VC MONITOR, FOR USE WITH IMAGE INTENSIFIER1 VC RAILS, CEILING FOR TUBE CARRIAGE, UNIVERSAL MOUNT1 VC RECORDER, TV TAPE1 VC STARTER, TUBE, HIGH SPEED1 VC TABLE, 90 DEGREE - 15 DEGREE TRENDELENBURG R&F, WITH

SPOT FILM DEVICE (TWO-WAY OR FOUR WAY TABLE TOP AND SIZE OF SPOT FILM TO BE DETERMINED ON PROJECT BASIS)

1 VC TABLE, TILT, 90 DEGREE - 90 DEGREE R&F, WITH SPOT FILM DEVICE (TWO-WAY OR FOUR WAY TABLE TOP AND SIZE OF SPOT FILM TO BE DETERMINED ON PROJECT BASIS)

1 VC TRANSFORMER, HIGH TENSION, X-RAY1 VC TUBE CARRIAGE, CEILING MOUNTED1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPOSAL, NEEDLES, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 790mm (20" x 31"), 2 IN 11 VV RACK, GLOVE/APRON, WALL MOUNTED

Radiographic Fluoroscopic Room - Control Area

NOTE: PROVIVE INTERCOM STATION IN CONTROL BOOTH CONNECTED TO REMOTE STATION IN X-RAY ROOM, WHEN CONTROL BOOTH IS SEPERATED FROM X-RAY ROOM.

NOTE: INCANDESCENT, DIMMING SYSTEM (PG-18-1, MCS 16510)

NOTE: INTERCOM, STATION (PG-18-1, MCS 16510)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: WINDOW, LEAD GLASS, MINIMUM 457mm x 610mm (18" x 24") (PG-18-1, MCS 13091; PG-18-4, SD 24G)

1 VC CONSOLE, CONTROL, X-RAY, FOR X-RAYUNIT (CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

Page 536: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-3

Radiographic Fluoroscopic Room - Toilet Room

AR CC BAR, GRAB FOR WATER CLOSET (PG-18-1, MCS 10800; PG-18-4, SD 12)

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL(PG-18-1, MCS 10800; PG-18-4, SD 12)

P-418 1 CC LAVATORY, SENSOR CONTROL(PG-18-1, MCS 15450; VOL. 3 SD380)

1 CC MIRROR, 600mm x 910mm (24” x 36”) OVER WHEELCHAIR LAVATORY (PG-18-1, MCS 10800; PG-18-4, SD 15)

P-103 1 CC WATER CLOSET, WALL HUNG (PG-08-1, MCS 15450)1 VV DISPENSER, BI-FOLD PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV RECEPTACLE, WASTE 330mm (13”) DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 537: VA guide -2009
Page 538: VA guide -2009
Page 539: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-4

Design StandardsSpecial Procedures (non-affiliated Control Room)ARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: Coordinate/ with equipment

Manufacturer Wall Finish: Painted veneer plaster Wainscot: -- Base: Integral welded seam sheet

flooring base Floor Finish: Welded seam sheet flooring Slab Depr: 100 mm (4”) Notes: 1. 1200 mm (4’-0”) wide door. See VA

Construction Standard 64-1, X-RayRadiation Shielding and SpecialControl”.

SPECIAL EQUIPMENT

None

LIGHTING

General: 50 FC (Procedure) Special: 10 FC (Control) Notes: 1. X-ray in use DO NOT ENTER sign

fixture2. Continuous fluorescent direct/indirect

wall mounted light fixture, acrylicprismatic lens on top and bottom,W/2-F32T8 lamps, 3500 deg. K,CRI=75 (minimum.)

3. Recessed, lensed incandescentdownlight with 100W, A-21 lamp.

4. 600 mm x 1200 mm (2’x4’) recessedfluorescent light fixture, acrylicprismatic lens, W/3-F32T8 lamps,3500 deg. K, CRI-75 (minimum).

5. Down light illumination levelcontrolled by dimmers.

POWER

General: 1000W (Receptacles) Emergency: -- Notes: 1. The electrical plan as shown is to be

used as a guide only. Equipmentlocations, dimensions and wiringrequirements to be per the x-raysystem suppliers equipmentinstallation drawings.

POWER (cont.)

Notes: 2. Electrical trades shall providenecessary conduit, openings,bushings, nipples, flexible conduitetc., as required at the variousjunction boxes, duct and conduitterminations to allow properconnections of the x-ray equipmentand related accessories.

3. 480V., 3P., 150A., adjustable tripflush mounted circuit breaker withshunt trip. Run empty 50mm (2”) C.from circuit breaker to x-ray ductabove finished ceiling.

4. 300 mm x 140 mm (12’ x 5-½”) deepflush floor duct with screw-on cover.Connect to x-ray wall duct.

5. 250 mm x 140 mm (10” x 5-½”) deepflush vertical wall duct with 305mm(12”) wide screw-on cover. Connectto floor duct and to x-ray duct abovefinished ceiling.

6. 250 mm x 140 mm (10” x 5-½”) deepflush vertical wall duct with 300 mm(12”) wide screw-on cover. Connectto x-ray duct above finished ceilingand terminate at finished floor.

7. 250 mm x 140 mm (10” x 5-½”) deepx-ray duct above finished ceiling with255mm (10”) wide screw-on cover.Connect to vertical wall duct.

8. Emergency Power Off (EPO) pushbutton station. Connect to shunt tripcircuit breakers.

Page 540: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-4

Design StandardsSpecial Procedures (non-affiliated Control Room)COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: Yes Pub. Addr: -- Notes: 1. Nurse Call in toilet room to

annunciate at reception desk.

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: -- Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.:

Special Procedures: 8Control Room: 4

Room Pressure: Special Procedures: NegativeAll Others: 0

AC Load Lighting: forSpecial Procedures: 39 W/sm (3.6 W/sf)

Control Room: 26 W/sm (2.4 W/sf) AC Load-Equipment:

Special Procedures: 65 W/sm (6W/sf)Control Room: 13,000 Btu/hr - 3752W)

Number of People: 6 for Procedure;All Others: 3

Special Exhaust: -- Notes: 1. Provide a dedicated AC unit for

computer room sized to handle aminimum of 3 tons of cooling. Verifycooling capacity and other specificrequirements with the equipmentmanufacturer on a specific project.

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: --

Page 541: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-4

Special Procedure Room (non-affiliated Control Room)

NOTE: THE FOLLOWING X-RAY EQUIPMENT TO BE DETERMINED ON PROJECT BASIS BY VETERANS HEALTH ADMINISTRATION.

NOTE: SHOULD VETERANS HEALTH ADMINISTRATION INDICATE A SINGLE PLANE ANGIOGRAPHIC FILM CHANGER, THE RADIOGRAPHIC UNIT FOR THE SECOND PLANE WILL BE OMITTED.

NOTE: OPTIONAL COMPONENTS TO BE DETERMINED BY VETERANS HEALTH ADMINISTRATION.

NOTE: OUTLET, WALL, EVACUATION (PG-18-1, MCS 15491; H-18-3, CS 310-1))

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, NITROUS OXIDE (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLETS TO BE ON THE WALL, NEAR HEAD END AND OPPOSITE END OF X-RAY TABLE, 1524mm (60") ABOVE THE FLOOR.

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT.

NOTE: ISOLATED POWER UNIT PROVIDES ISOLATED ELECTRICAL POWER, INCLUDES LINE ISOLATION MONITOR, ISOLATION TRANSFORMER AND CIRCUIT BREAKERS (DETAILS AVAILABLE FROM ELECTRICAL SERVICE)

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (PG-18-1, MCS 13091; H-18-3, CS 64-1; PG-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

AR CF MODULAR CASEWORKJ-2 1 CF SINK, CORROSION RESISTING STEEL, WITH CENTER DRAIN

OUTLET, 457mm x 381mm 203mm (18” x 15” x 8”)(PG-18-1 & PG-18-6, MCS 11602)

1 VC X-RAY UNIT, RADIOGRAPHIC AND FLUOROSCOPIC CONSISTS OF THE FOLLOWING COMPONENTS:

1 VC CAMERA, 35/100 OR 105mm, USE WITH IMAGE INTENSIFIER (OPTIONAL)

1 VC CAMERA, TV (FOR USE WITH IMAGE INTENSIFIER) (OPTIONAL)1 VC CARRIAGE, TUBE, CEILING MOUNTED, WITH TWO TUBE CRANES1 VC CHANGER, FILM, ANGIOGRAPHIC, BI-PLANE1 VC CHANGER, FILM, DUAL RAPID1 VC CONTROL, CINE CAMERA

SYMBOL QTY AI DESCRIPTION

Page 542: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-4

Special Procedure Room (non-affiliated Control Room) (cont.)

1 VC IMAGE INTENSIFIER, 152mm, 229mm (6", 9"), OR DUAL TYPE TO BE DETERMINED ON PROJECT BASIS

1 VC MODULE, POWER1 VC MONITOR, FOR USE WITH IMAGE INTENSIFIER1 VC RECORDER, TV TAPE1 VC STARTER, TUBE, HIGH SPEED1 VC SYRINGE, ANGIOGRAPHIC, AUTOMATIC, MOBILE1 VC TABLE, TILT, 90 DEGREE - 90 DEGREE R&F, WITH SPOT FILM

DEVICE (TWO-WAY OR FOUR WAY TABLE TOP AND SIZE OF SPOT FILM DEVICE TO BE DETERMINED ON PROJECT BASIS)

1 VC TRANSFORMER, HIGH TENSION, X-RAY1 VC TRANSFORMER, HIGH TENSION, X-RAY1 VC X-RAY UNIT, RADIOGRAPHIC, FOR SECOND PLANE OF

ANGIOGRAPHIC FILM CHANGER, 480 VOLT, 3 PHASE 60 CYCLE1 VV BULLETIN BOARD, 914mm x 610mm (36" x 24")AR VV CART, MOBILE, 610mm x 1219mm x 914mm (24" x 48" x 36")1 VV CLOCK, BATTERY OPERATED1 VV DISPOSAL, NEEDLES, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, 4 PANEL, SURFACE MTD.2 VV RACK, APRON, WALL MOUNTED2 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305mm

(12") DIAMETER

Special Procedure Rm (non-affiliated Control Rm)- Control Area

NOTE: PROVIDE INTERCOM STATION IN CONTROL BOOTH CONNECTED TO REMOTE STATION IN X-RAY ROOM, WHEN CONTROL BOOTH IS SEPARATED FROM X-RAY ROOM.

NOTE: INCANDESCENT, DIMMING SYSTEM (PG-18-1, MCS 16510)

NOTE: INTERCOM, STATION (PG-18-1, MCS 16760)

NOTE: LIGHT, WARNING (DO NOT ENTER) OVER DOOR (PG-18-4, SD E-D-2)

NOTE: WINDOW, LEAD GLASS, 1397mm x 1219mm (55" x 48") (PG-18-1, MCS 13091)

1 VC CONSOLE, CONTROL, X-RAY, FOR X-RAY UNIT (CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

1 VC SELECTOR, PROGRAM, ANGIOGRAPHIC, FOR FILM CHANGER

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

Page 543: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-4

Special Procedure Rm (non-affiliated Control Rm) - Scrub Room

NOTE: WINDOW, LEAD GLASS, 760mm X 1200mm (30” X 48”,PG-18-1, MCS-13)

AR CC DISPENSER, SOAP, WITH FOOT CONTROL, WALL MOUNTED OVER SINK (PG-18-1, MCS 10800)

P-520 AR CC SINK, SURGEONS, SCRUB-UP, SENSOR CONTROL(PG-18-1, MCS 15450; PG-18-4,)

1 VV CLOCK, BATTERY OPERATEDAR VV DISPENSER, BRUSH, SCRUBAR VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV RECEPTACLE, WASTE, 330mm (13") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 544: VA guide -2009
Page 545: VA guide -2009
Page 546: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-5

Design StandardsCT Suite - Mid-Level Imaging SystemARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2890 mm (9'-6") Wall Finish: -- Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile;

Access Floor System inComputer and Control Rooms

Slab Depr: 100mm (4”) Notes: 1. 1200 mm (4’-0”) wide door. See VA

Construction Standard 64-1, X-RayRadiation Shielding and SpecialControl”.

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FC (CT Gantry Room)30 FC (Control Room)

Special: 30 FC (Computer Room) Notes: 1. 600 mm x 1200 mm (2’x4’) recessed

fluorescent light fixture, acrylicprismatic lens, W/3-F32T8 lamps,3500 deg K, CRI-75 (minimum)

2. Recessed, lensed incandescentdownlight with 100W, A-21 lamp.

3. Down light illumination levelcontrolled by dimmer.

POWER

General: 1000W (Receptacles) Emergency: -- Notes: 1. The electrical plan as shown is to be

used as a guide only. Equipmentlocations, dimensions and wiringrequirements to be per the x-raysystem suppliers equipmentinstallation drawings.

POWER (cont.)

Notes: 2. Electrical trades shall providenecessary conduit, openings,bushings, nipples, flexible conduitetc., as required at the variousjunction boxes, duct and conduitterminations to allow properconnections of the x-ray equipmentand related accessories.

3. 480V., 3P., 150A., adjustable tripflush mounted circuit breaker withshunt trip. Run empty 50 mm (2’) C.from circuit breaker to x-ray ductabove finished ceiling.

4. 300 mm x 140 mm (12’ x 5-½”) deepflush floor duct with screw-on cover.Connect to x-ray wall duct.

5. Run 13 mm (½”) C. from door switchto junction box at x-ray controller.Connect door switch so that if door isopened the x-ray system will be shutoff.

COMMUNICATION

ADP: Yes Radio: -- Telephone: Yes Intercom: Yes Pub. Addr: -- Notes: 1. Junction box for CCTV camera with

conduit to adjacent control room.2. Junction box for CCTV monitor.

Page 547: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-5

Design StandardsCT Suite - Mid-Level Imaging SystemHEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: for

CT Gantry and Computer Room: 45%All Others: 30%

Minimum Air Changes/Hr.:CT Gantry and Computer Room: 8

All Others: 4 Room Pressure: 0 AC Load-Equipment:

CT Gantry: 2930 W (10,000 Btu/hr)Control Room: 1400 W (4800 Btu/hr)

Viewing Room: 43 W /sm (4 W/sf) AC Load Lighting:

CT Gantry: 26 W/sm (2 W/sf)Computer Room: 14W/sm (1.3W/sf

Control and Viewing Room: 22 W/sm (2.W/sf) Number of People: Procedure: 6

All Others: 3 Special Exhaust: -- Notes: 1. Provide a dedicated AC unit for

computer room sized to handle aminimum of 3 tons of cooling. SeeHVAC Design Manual for HospitalProjects for CT Suite requirements

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: --

Page 548: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-5

CT Suite (Mid-Level Imaging System) - Gantry Room

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT.

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

NOTE: OUTLETS TO BE ON THE WALL, NEAR HEAD END OF X-RAY TABLE, 1524mm (60") ABOVE THE FLOOR.

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491; H-18-3, CS 310-1)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (PG-18-1, MCS 13091; H-18-3, CS 64-1; PG-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

AR CF MODULAR CASEWORKJ-2 1 CF SINK, CORROSION RESISTING STEEL, WITH CENTER DRAIN

OUTLET, 457mm x 381mm x 203mm (18" x 15" x 8")(PG-18-1 & PG-18-6, MCS 11602)

1 VC GANTRY AND MOUNTING FRAME1 VC TABLE, PATIENT AND MOUNTING FRAME1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV DISPOSAL, NEEDLES, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV RACK, APRON, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP-ON TYPE APPROX 305mm (12”)

DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 549: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-5

CT Suite (Mid-Level Imaging System) - Control Area

NOTE: INCANDESCENT, DIMMING SYSTEM (PG-18-1, MCS 16510)

NOTE: LIGHT, WARNING (DO NOT ENTER) OVER DOOR (PG-18-4, SD E-D-2)

NOTE: OUTLET, MONITOR, CLOSED CIRCUIT TELEVISION, (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: WINDOW, LEAD GLASS, 1397mm x 1219mm (55" x 48") (PG-18-1, MCS 13091)

1 VC CONSOLE, OPERATORS, FOR SCANNER TABLE AND GANTRY (CAPACITY OF GENERATOR TO BE DETERMINE ON PROJECT BASIS)

AR VC IMAGER, HARD LINEAR VC PRINTER, LINE1 VV CAMERA, LASER, IMAGER,APPROX.,1295mm x 660mm x 1194mm

(51" x 26" x 47")1 VV CHAIR, OPERATOR'S1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 760mm (20" x 30"), 2 IN 1

CT Suite (Mid-Level Imaging System) - Computer Room

AR VC AIR COOLERAR VC COMPUTER CABINET, AUXILIARYAR VC COMPUTER CABINET, MAINAR VC HEAT EXCHANGER (WATER/WATER)1 VC POWER CABINET1 VC POWER LINE PROTECTOR1 VC TRANSFORMER, HIGH VOLTAGEAR VC UNIT, DISC DRIVE STORAGE1 VC UNIT, POWER DISTRIBUTION

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

Page 550: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-5

CT Suite (Mid-Level Imaging System) - Physicians Viewing Rm

SYMBOL QTY AI DESCRIPTION

AR VV CONSOLE, PHYSICIAN’SAR VV CHAIR, ROTARY, WITH ARMS2 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 1499mm (20" x 59"), 4 IN 12 CC COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED,

762mm (30”) ABOVE FINISHED FLOOR, APPROX., 1524 mm x 457mm (60” x 18”), PROVIDE UNDER ILLUMINATOR(PG-18-1, MCS 12302)

3 VV HOOK, COAT, WALL MOUNTED1 VV BULLETIN BOARD, 914mm x 610mm (36” x 24”)1 VV RECEPTACLE, WASTE, 330mm (13”) DIAMETER1 VV MONITOR, TV, REMOTE VIEWING FOR COMPUTERIZED

TOMOGRAPHIC (CT)1 VV CLOCK, BATTERY OPERATED1 CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140; H-18-3, CS 801-3)

Page 551: VA guide -2009
Page 552: VA guide -2009
Page 553: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-6

Design StandardsUltrasound RoomARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: -- Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 1200 mm (4’-0”) wide door

SPECIAL EQUIPMENT

None

LIGHTING

General: Scanning Room: 30 FCToilet Room: 30FC

Special: -- Notes: 1. Wall mounted fluorescent fixture,

acrylic prismatic lens on bottom,W/2-F32T8 lamps, 3500 deg. K,CRI=75 (min.)

2. 600 mm x 1200 mm (2’ x 4’)recessed fluorescent light fixture,acrylic prismatic lens, W/3-F32T8lamps, 3500 deg. K, CRI=75.

3. Recessed, lensed incandescentdownlight with 100W, A-21 lamp.

4. Down light illumination levelcontrolled by dimmer.

POWER

General: 1000W (Receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: Yes Pub. Addr: -- Notes: 1. nurse call for toilet room

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: See Note 1 AC Load Lighting:

Ultrasound: 54 W/m 2(5W/sf) AC Load-Equipment:

Ultrasound 2700 W(9200 Btu/hr)Number of People: 3 Special Exhaust: -- Notes: 1. Negative pressure in Toilet and equal

pressure in Ultrasound with respectto Corridor.

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes:--

Page 554: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-6

Ultrasound Room

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

1 CC COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED, 762mm (30") ABOVE FINISHED FLOOR, APPROX., 1524mm x 457mm (60" x 18"), PROVIDE UNDER ILLUMINATOR(PG-18-1, MCS 12302)

1 CC DISPENSER, SOAP, WALL MOUNTED WITH FOOT CONTROL (PG-18-1, MCS 10800)

P-418 1 CC LAVATORY, SENSOR CONTROL(PG-18-1, MCS 15450; VOL. 3 SD 380)

AR VV STRETCHER, RECOVERY APPROX., 762mm x 2032mm (30" x 80")1 VV BULLETIN BOARD, 914mm x 610mm (36" x 24")AR VV CART, SUPPLIES, 610mm x 1219mm (24" x 48")AR VV CHAIR, ROTARY, WITHOUT ARMS1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTEDAR VV HAMPER, SOILED LINEN, WITH HINGED SELF CLOSING TOP,

508mm (20") DIA.1 VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 1499mm (20" x 59"), 4 IN 12 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305mm

(12") DIAMETERAR VV SCANNER, ULTRASONIC, MOBILE

SYMBOL QTY AI DESCRIPTION

Page 555: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-6

Ultrasound Room - Patient Toilet

NOTE: LIGHT, OVER MIRROR (PG-18-1, MCS 16510; PG-18-4, SD E-F-15)

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, WITH GROUND FAULT INTERRUPTER, ADJACENT TO LAVATORY (PG-18-1, MCS 16140; H-18-3, CS 801-3)

AR CC BAR, GRAB FOR WATER CLOSET(PG-18-1, MCS 10800; PG-18-4, SD 12)

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL(PG-18-1, MCS 10800; PG-18-4, SD 12)

P-414 1 CC LAVATORY, STRAIGHT BACK (PG-18-1, MCS 15450)1 CC MIRROR, 610mm x 914mm (24" x 36"), OVER WHEELCHAIR

LAVATORY (PG-18-1, MCS 10800; PG-18-4, SD 15)1 CC SHELF, STAINLESS STEEL, WALL HUNG, 152mm x 457mm

(6" x 18") (PG-18-1, MCS 10360; PG-18-4, SD 15)P-103 1 CC WATER CLOSET, WALL HUNG (PG-18-1, MCS 15450; PG-18-4)

1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED

SYMBOL QTY AI DESCRIPTION

Page 556: VA guide -2009
Page 557: VA guide -2009
Page 558: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-7

Design StandardsMammography RoomARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: -- Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 1100 mm (3’-8”) wide door

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FC Special: -- Notes: 1. 600 mm x 1200 mm (2’ x 4’)

recessed fluorescent light fixture,acrylic prismatic lens, W/3-F32T8lamps, 3500 deg. K, CRI=75.

POWER

General: 1000W (Receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: -- Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 54 W/sm (5W/sf) AC Load Lighting: 22 W/sm (2 W/sf) Number of People: 3 Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

Page 559: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-7

Mammography Room

1 CC COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED, 760mm (30") ABOVE FINISHED FLOOR, APPROX., 1524mm x 455mm (48" x 18"), PROVIDE UNDER ILLUMINATOR (PG-18-1, MCS 12302) (PG-18-1, MCS 10800)

P-418 1 CC LAVATORY, SENSOR CONTROL(PG-18-1, MCS 15450; VOL. 3 SD 380)

1 VC UNIT, MAMMOGRAPHY WITH CHAIR1 VV BULLETIN BOARD, 914mm x 610mm (36" x 24")2 VV CHAIRS, STRAIGHT, WITH ARMS1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 787mm (20" x 31"), 2 IN 11 VV RACK, GLOVE & APRON, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX., 305mm

(12") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 560: VA guide -2009
Page 561: VA guide -2009
Page 562: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-8

Design StandardsAutomated Radiographic Room w/ControlARCHITECTURAL

Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2890 mm (9'-6") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: 100 mm (4”) Notes: 1. 200 mm (4’-0”) wide door. See VA

Construction Standard 64-1, X-RayRadiation Shielding and SpecialControl”.

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FCSpecial: --Notes: 1. “X-ray in use -DO NOT ENTER”

warning sign fixture.2. Continuous fluorescent direct/indirect

wall mounted fixture, acrylic prismaticlens on top and bottom, W/2-F32T8lamps, 3500 deg. K, CRI=75 (min.)

3. Illumination level controlled bydimmer.

POWER

General: 1200W (receptacles) Emergency: 1600W (receptacles) Notes: 1. The electrical plan as shown is to be

used as a guide only. Equipmentlocations, dimensions and wiringrequirements to be per the x-raysystem suppliers equipmentinstallation drawings.

2. Electrical trades shall providenecessary conduit, openings,bushings, nipples, flexible conduitetc., as required at the variousjunction boxes, duct and conduitterminations to allow properconnections of the x-ray equipmentand related accessories.

POWER (cont.)

Notes: 3. 480V., 3P., 150A., adjustable tripflush mounted circuit breaker withshunt trip. Run empty 600 mm (2” C.from circuit breaker to x-ray ductabove finished ceiling.

4. 300 mm x 140 mm (12” x 5-½”) deepflush floor duct with screw-on cover.Connect to vertical wall duct.

5. 250 mm x 140 mm (10” x 5-½”) deepflush vertical wall duct with 300 mm(12”) wide screw-on cover. Connectto floor duct and to x-ray duct abovefinished ceiling.

6. 250 mm x 140 mm (10” x 5-½”) deepflush vertical wall duct with 300 mm(12”) wide screw-on cover. Connectto x-ray duct above finished ceilingand terminate at finished floor.

7. 250 mm x 140 mm (10” x 5-½”) deepx-ray duct above finished ceiling with250 mm (10”) wide screw-on cover.Connect to vertical wall duct.

8. Emergency Power Off (EPO) pushbutton station. Connect to shunt tripcircuit breakers.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: --

Page 563: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-8

Design StandardsAutomated Radiographic Room w/ControlHEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 24°C (75°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15 100% Exhaust Air: No Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 6 Room Pressure: Negative AC Load Lighting: 40 W/m 2 (3.7 W/sf) AC Load-Equipment: 50/70 W (17300 Btu/hr) Number of People: 6 Special Exhaust: -- Notes: 1. Provide at least two level exhaust

outlets.2. Provide at least 150 mm (6”) duct to

each processor balanced to 80CFM each.

3. See HVAC Design Manual forHospital Projects for lead wrapping ofductwork penetrating lead lined walls.

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: 1. Provide piping connection from

processors to Silver RecoverySystem, if required.

Page 564: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 4-8

Automated Radiographic Room

NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO SILVER RECOVERY SYSTEM, IF REQUIRED.

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT

NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (OXYGEN, AIR, VACUUM OUTLET AND BRACKET)

NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491)

NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491)

NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491)

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: FLOOR DRAIN, NEAR FILM PROCESSING UNITS (PLUMBING DESIGN CRITERIA AND INSTRUCTIONS)

NOTE: FLOOR DRAIN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN CRITERIA & INSTRUCTIONS)

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (PG-18-1, MCS 16510)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH PG-18-1, MCS 13091; PG-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

AR CC COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED, 760mm (30") ABOVE FINISHED FLOOR, APPROX., 1525mm x 457mm (60" x 18"), PROVIDE UNDER ILLUMINATOR(PG-18-1, MCS 12302)

1 CC DISPENSER, SOAP, WALL MOUNTED WITH FOOT CONTROL (PG18-1, MCS 10800)

P-802 1 CC HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED, CONCEALED SUPPLY PIPES(PG-18-1, MCS 15450, PG-08-4, SD VOL. 3 SD 380)

P-418 1 CC LAVATORY, SENSOR CONTROL(PG-18-1, MCS 15450; VOL. 3 SD 380)

1 CF CABINET, FOR EQUIPMENT MANUAL, WALL MOUNTED, APPROX., 1220mm x 405mm x 405mm (48” x 16” x 16”)

1 CF CABINET, STORAGE, WALL MOUNTED, 255mm (10”) ABOVE FINISHED FLOOR, 5 SHELVES AND FOLDING DOOR, APPROX. 610mm x 405mm x 1575mm (24” x 16” x 62”)

SYMBOL QTY AI DESCRIPTION

Page 565: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-1

Section 5Design Guide Platesand Data Sheets:Technical Support AreasGuide Plate Series PlateNumber

Darkroom (2-processors)Equipment & Utility Plan ..........................5-1Reflected Ceiling Plan..............................5-1Design Standards ....................................5-1Equipment Guide List ..............................5-1

Radiology Film Records RoomEquipment & Utility Plan ..........................5-2Reflected Ceiling Plan..............................5-2Design Standards ....................................5-2Equipment Guide List ..............................5-2

Patient Gowning (for 4 Diag. Rms)Equipment & Utility Plan ..........................5-3Reflected Ceiling Plan..............................5-3Design Standards ....................................5-3Equipment Guide List ..............................5-3

Daylight Processor AreaEquipment & Utility Plan ..........................5-4Reflected Ceiling Plan..............................5-4Design Standards ....................................5-4Equipment Guide List ..............................5-4

Page 566: VA guide -2009
Page 567: VA guide -2009
Page 568: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-1

Design StandardsDarkroom (2 Processors)ARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Integral welded seam sheet flooring base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 900 mm (3’-0”) wide door with light

seals

SPECIAL EQUIPMENT

None

LIGHTING

General: Darkroom: 30 FCWork Area: 30FC

Special: -- Notes: 1. 600 mm x 1200 mm (2’ x 4’)

recessed fluorescent light fixture,acrylic prismatic lens, W/3-F32T8lamps, 3500 deg. K, CRI=75(minimum).

2. Recessed incandescent safe lightfixture.

POWER

General: 1600W (Receptacles) Emergency: -- Notes: 1. 240V, 2P.,30A, flush mounted circuit

breaker for film processor (coordinaterequirements with system supplier).

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: For Darkroom Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 for Work Area

8 for Darkroom Room Pressure: 0 for Work Area

Negative for Darkroom AC Load-Equipment: Darkroom: 65W/sm (6W/sf)

Open Area: 43 W/sm (4 W/sf)AC Load Lighting: Darkroom: 24 W/sm (2.2 W/sf)

Open Area: 26 W/sm (2.4 W/sf) Number of People: 3 for Darkroom

6 for Open Area Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Provide piping connection from

processors to Silver RecoverySystem, if required.

2. Waste and vent piping need to bechemical resistant type.

Page 569: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-1

Darkroom (2 Processors) - Open Work Area

NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO SILVER RECOVERY SYSTEM, IF REQUIRED.

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: FLOOR DRAIN, NEAR FILM PROCESSING UNITS (PLUMBING DESIGN CRITERIA AND INSTRUCTIONS)

NOTE: FLOOR DRAIN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN CRITERIA & INSTRUCTIONS)

AR CC COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED, 762mm (30") ABOVE FINISHED FLOOR, APPROX., 3660mm x 600mm (144" x 24"), PROVIDE UNDER ILLUMINATOR(PG-18-1, MCS 12302)

P-516 1 CC SINK, CORROSION RESISTING STEEL, SINGLE COMPARTMENT, WALL HUNG (PG-18-1, MCS 15450)

AR VC PORTABLE DARKROOM (REMOVING UNPROCESSED FILM FROM DISPENSER)

AR VC PROCESSOR, FILM, AUTOMATIC, 90 SECOND PROCESSING CYCLE, THRU WALL

AR VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED, APPROX., 508mm x 1499mm (20" x 59"), 4 IN 1

SYMBOL QTY AI DESCRIPTION

Page 570: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-1

Darkroom (2 Processors) - Darkroom

NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO SILVER RECOVERY SYSTEM, IF REQUIRED.

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: FLOOR DRAIN, NEAR FILM PROCESSING UNITS (PLUMBING DESIGN CRITERIA AND INSTRUCTIONS)

NOTE: FLOOR DRAIN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN CRITERIA & INSTRUCTIONS)

AR CF DARKROOM CASEWORK2 CF CABINET, CASSETTE TRANSFER, FOUR DOOR, W/ AUDIO1 CC EYEWASH, WALL MTD.2 VC SILVER RECOVERY SYSTEM1 VC TANK, REPLENISHER, 95 L (25 GAL.) CAPACITY AND

CURBING, 2 FOR EACH PROCESSORP-802 1 CC HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED,

CONCEALED SUPPLY PIPES(PG-18-1, MCS 15450; PG-18-4, SD 4.2)

SYMBOL QTY AI DESCRIPTION

Page 571: VA guide -2009
Page 572: VA guide -2009
Page 573: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-2

Design StandardsRadiology Film Records RoomARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile/Carpet

in Viewing Area Slab Depr: -- Notes: 1. 1060 mm (3’-6”) wide doors in film

library.2. 1 hour fire resistant rated

construction around film library. Coordinate floor loadingrequirements in film library withStructural Engineer.

SPECIAL EQUIPMENT

None

LIGHTING

General: Common Viewing: 30 FCMulti Viewing: 30FC

Film Library: 50FC Special: -- Notes: 1. 600 mm x 1200 mm (2’ x 4’)

recessed fluorescent light fixture,acrylic prismatic lens, W/2-F32T8lamps, 3500 deg. K, CRI=75(minimum).

POWER

General: 2600W (Receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% Exhaust Air: 100% Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment:

Common & Mulit Viewing: 43 W/sm(4W/sf) Film Lab: 16W/sm (1.5W/sf)

AC Load Lighting:Common & Mulit Viewing: 11 W /sm(.1 W/sf)

Film Lab: 15 W/m 2 (1.4 W/sf)Number of People: Film Library: 3

Multi-Viewing: 4Common Viewing: 6

Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 574: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-2

Radiology Film Records Room - Common Viewing Room

NOTE: WHEN CONFERENCE ROOM IS NOT PROVIDED, ADD THE FOLLOWING TO THIS ROOM:

NOTE: OUTLET, CAMERA, CLOSED CIRCUIT TELEVISION (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: OUTLET, MONITOR, CLOSED CIRCUIT TELEVISION, 457mm (18") ABOVE FINISHED FLOOR (EMPTY CONDUIT SYSTEM) (PG-18-1, MCS 16111)

NOTE: OUTLET, PROJECTOR, FILM, X-RAY (PG-18-1, MCS 16140)

NOTE: OUTLET, TV MONITOR (X-RAY TV CHAIN)

AR CC COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED, 762mm (30") ABOVE FINISHED FLOOR, APPROX., 455mm (18") LENGTH AS REQUIRED, PROVIDE UNDER ILLUMINATORS(PG-18-1, MCS 12302)

AR VV CHAIR, ROTARY WITH ARMS1 VV CLOCK, BATTERY OPERATEDAR VV ILLUMINATORS, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APPROX., 508mm x 1500mm (20" x 59"), 4 IN 1

Radiology Film Records Room - Multi-Viewing Area

AR VV CHAIR, ROTARY, WITH ARMS1 VV CLOCK, BATTERY OPERATEDAR VV MULTI-VIEWER, AUTOMATIC, 120 VOLT, 20 AMP, APPROX.,

1725mm x 610mm x 1980mm (68" x 24" x 78")AR CC COUNTERTOP, PLASTIC LAMINATE, 455mm (18”) LENGTH AS

REQUIRED

Radiology Film Records Room - Film Library

T9 AR CC BINS, FILING, X-RAY FILM, 914mm x 2286mm (36" x 90") (PG-18-1, MCS 10671; PG-18-4, SD 65B)

AR CC SHELVING, OPEN, AS DETERMINED BY VETERANS HEALTH ADMINISTRATION

AR CF MODULAR CASEWORK1 VV BULLETIN BOARD, 914mm x 610mm (36" x 24")1 VV CART, UTILITYAR VV CHAIR, ROTARY W/ ARMS1 VV CLOCK, BATTERY OPERATED

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

Page 575: VA guide -2009
Page 576: VA guide -2009
Page 577: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-3

Design StandardsPatient Gowning (for 4 Diagnostic Rooms)ARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base

Ceramic Tile in Toilet Room Floor Finish: Vinyl Composition Tile

Ceramic Tile in Toilet Room Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FC Special: -- Notes: 1. 600 mm x 600 mm (2’ x 2’) recessed

fluorescent light fixture, acrylicprismatic lens, W/2-FB31 lamps,3500 deg. K, CRI=75 (minimum).

POWER

General: 1600W (Receptacles) Emergency: -- Notes: --

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: Yes Notes: 1. Nurse call system in toilet room to

annunciate at reception area.

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15%100% Exhaust Air: For Toilet Room Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr. Toilet Room exhaust 10

All Others: 4 Room Pressure: Toilet Room: Negative

All Others: 0 AC Load-Equipment: 26 W/m2 (2.4W/sf) AC Load Lighting:

Toilet Room: 15W/m2 (1.4 W/sf)All Others: 26W/m2 (2.4 W/sf)

Number of People: Dressing & Toilet Rm: 1Waiting Area: 6

Special Exhaust: -- Notes: --

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: --

Page 578: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-3

Patient Gowning (for 4 Diagnostic Rms) - Waiting Space

NOTE: SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL, HOSPITAL RADIO SYSTEM (PG-18-1, MCS 16771)

AR CC LOCKER, PATIENT, HALF-HEIGHT 330mm x 460mm x 980mm(1’-3” x 1’-6” x 3’-0”)

AR VV CHAIR, STRAIGHT, WITHOUT ARM, PADDED SEAT AND BACK1 VV CLOCK, BATTERY OPERATEDAR VV TABLE, END, PLASTIC LAMINATE TOP, METAL FRAME

Patient Gowning (for 4 Diagnostic Rms) - Dressing Room

NOTE: NURSE CALL, EMERGENCY STATION, ACTIVATED BY PUSH BUTTON ON WALL, WITH CORRIDOR SIGNAL LIGHT (PG-18-1, MCS 16761)

AR CC WALL HUNG BENCH1 CC MIRROR, FULL LENGTH, HEAT TEMPERED GLASS, 508mm x

1219mm (20" x 48") (PG-18-1, MCS 10800)AR CC TRACK, CUBICAL CURTAIN2 VV HOOK, COAT, WALL MOUNTED

SYMBOL QTY AI DESCRIPTION

SYMBOL QTY AI DESCRIPTION

Page 579: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-3

Patient Gowning (for 4 Diagnostic Rms) - W/ Toilet Rm.

NOTE: WHEELCHAIR WATER CLOSETS WILL BE IN ACCORDANCE WITH THE APPROPRIATE SPACE PROGRAM, P-103 WILL BE USED FOR BOTH CONVENTIONAL AND WHEELCHAIR INSTALLATIONS.

NOTE: RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP, WITH GROUND FAULTINTERRUPTER, ADJACENT TO LAVATORY (PG-18-1, MCS 16140; H-18-3, CS 801-3)

NOTE: STATION, CALL, EMERGENCY (LIGHT AND SOUND SIGNAL IN RECEPTIONISTS OFFICE, SIGNAL LIGHT OVER TOILET ROOM DOOR) (PG-18-1, MCS 16761)

1 CC BAR, GRAB FOR WATER CLOSET (PG-18-1, MCS 10800; PG-18-4, SD 12)

1 CC DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-18-1, MCS 10800; PG-18-4, SD 12)

1 CC HOOK, CLOTHES (PG-18-1, MCS 10800)P-418 1 CC LAVATORY, STRAIGHT BACK SENSOR CONTROL (PG-18-1,

MCS 15450; VOL 3 SD 380)1 CC MIRROR, 610mm x 914mm (24" x 36) (PG-18-1, MCS 10800;

PG-18-4, SD 15)1 CC SHELF, STAINLESS STEEL, WALL HUNG, 152mm x 457mm

(6" x 18") (PG-18-1, MCS 10360; PG-18-4, SD 15)P-103 1 CC WATER CLOSET, WALL HUNG (PG-18-1, MCS 15450; PG-18-4, SD4)

1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP-ON TYPE

SYMBOL QTY AI DESCRIPTION

Page 580: VA guide -2009
Page 581: VA guide -2009
Page 582: VA guide -2009

Final Draft 12-31-95Revised May 1997

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-4

Design StandardsDaylight Processor AreaARCHITECTURAL

Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2700 mm (9'-0") Wall Finish: Paint on Gypsum Wallboard Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: --

SPECIAL EQUIPMENT

None

LIGHTING

General: 30 FC - 1.5w/sf Special: -- Notes: 1. 600 mm x 1200 mm (2’ x 4’)

recessed fluorescent light fixture,acrylic prismatic lens, W/2-F32T8lamps, 3500 deg. K, CRI=75(minimum).

2. Recessed incandescent safe lightfixture.

POWER

General: 1200W (Receptacles) Emergency: -- Notes: 1. 240V, 2P., 30A, flush mounted circuit

breaker for film processor (coordinaterequirements with system supplier).

COMMUNICATION

ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: --

HEATING, VENTILATING AND AIRCONDITIONING

Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 100%100% Exhaust Air: Yes Noise Criteria: NC-50 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: Room Pressure: Negative AC Load-Equipment: 65 W/sm (6W/sf) AC Load Lighting: 16 W/m 2 (1.5 W /sf) Number of People: 6 Special Exhaust: -- Notes: 1. Provide an exhaust duct connection

to each processor.

PLUMBING AND MEDICAL GASES

Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Check with film processor supplier

regarding water quality supplied toeach processor.

2. Provide piping connection fromprocessors to silver recovery system.if required.

Page 583: VA guide -2009

Final Draft 12-31-95Revised May 1997

Equipment Guide List

VA DESIGN GUIDERADIOLOGY SERVICE PAGE 5-4

Daylight Processor Area

NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO SILVER RECOVERY SYSTEM, IF REQUIRED.

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: FLOOR DRAIN, NEAR FILM PROCESSING UNITS (PLUMBING DESIGN CRITERIA AND INSTRUCTIONS)

NOTE: FLOOR DRAIN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN CRITERIA & INSTRUCTIONS)

2 CC COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED, 762mm (30”) ABOVE FINISHED FLOOR, 610mm W(24”) LENGTH AS REQUIRED (PG-18-1, MCS 12302)

AR CC FLOOR RECEPTOR, FOR REPLENISHER SYSTEMP-802 1 CC HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED,

CONCEALED SUPPLY PIPES(PG-18-1, MCS 15450; PG-18-4, SD 4.2)

P-516 1 CC SINK, CORROSION RESISTING STEEL, SINGLE COMPARTMENT, WALL HUNG (PG-18-1, MCS 15450)

AR VC PROCESSOR, FILM, AUTOMATIC, 90 SECOND PROCESSING CYCLE

AR VC MODULAR DAYLIGHT FILM HANDLING SYSTEMCONSISTING OF THE FOLLOWING COMPONENTS:

1 BASE MODULE1 LOADING / UN-LOADING MODULE6 FILM DISPENSING MODULE1 CHEMICAL REPLENISHER SYSTEM1 WATER FILTRATION / SOLENOID SYSTEM1 BREAKER PANELAR VV ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED,

APROX., 508mm x 1499mm (20” x 59”), 4 PANEL

SYMBOL QTY AI DESCRIPTION

Page 584: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

VA DESIGN GUIDERADIATION THERAPY SERVICE

Section 4Design Guide Platesand Data Sheets:Patient Care Areas

Guide Plate Series Plate Number

Treatment Planning UnitEquipment & Utility Plan 4-1Reflected Ceiling Plan 4-1Design Standards 4-1Equipment Guide List 4-1

Superficial Therapy UnitEquipment & Utility Plan 4-2Reflected Ceiling Plan 4-2Design Standards 4-2Equipment Guide List 4-2

Orthovoltage Therapy UnitEquipment & Utility Plan 4-3Reflected Ceiling Plan 4-3Design Standards 4-3Equipment Guide List 4-3

Supervoltage UnitEquipment & Utility Plan 4-4Reflected Ceiling Plan 4-4Design Standards 4-4Equipment Guide List 4-4

Megavoltage UnitEquipment & Utility Plan 4-5Reflected Ceiling Plan 4-5Design Standards 4-5Equipment Guide List 4-5

CONTENTS - SECTION 4

Page 585: VA guide -2009
Page 586: VA guide -2009
Page 587: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsTreatment Planning UnitARCHITECTURAL Ceiling: Acoustic lay-in ceiling tile Ceiling Ht: 2895 mm (9'-6") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl composition tile Slab Depr: Coordinate with

equipment manufacturer Notes: 1220mm (4’-0”) wide door. See VA

Construction Standard 64-1,X-RayRadiation Shielding and Special Control”.

SPECIAL EQUIPMENTNone

LIGHTING General: Control Room: 30fc-1.6 w/sf

Simulator Room: 0-30fc-3.5w/sf Special: -- Notes: 1. “X-ray in use- Do Not Enter”

warning sign fixture.2. Recessed, lensed incandescent

down light with 100w, A-21 lamp.3. Continuous fluorescent

direct/indirect wall mountedfixture, acrylic prismatic lens ontop and bottom, W/2-F32T8lamps, 4100 deg. K, CRI=85(min.)

4. 600mm (2’-4”) recessedfluorescent light fixture, acryliclens, w/2-F32T8 lamps, 41000deg. K, CRI=85 (minimum)

POWERGeneral: 1600w (receptacles)Emergency: --Notes: 1. 480V, 3P flush mounted circuit breaker

with shunt trip for simulator system. Coordinate rating with system supplier.

2. Emergency power off (EPO) pushbutton station connect to shunt tripcircuit breakers.

VA DESIGN GUIDERADIATION THERAPY SERVICE

COMMUNICATIONSADP: --Radio: --Telephone: YesIntercom: YesPub. Addr: --Notes: 1. Junction box for CCTV Camera with

conduit to Control Room.2. Junction box for CCTV Monitor cabling.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: Yes Relative Humidity/Cooling: 50% Relative Humidity/Heating: 45% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Equipment: 4400w (15,000 Btu/hr) Number of People: 6 Special Exhaust: -- Notes: 1. Provide booster humidifier

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: Possible Medical Air: Yes Medical Vacuum: Yes Oxygen: Yes Notes: 1. Verify with the equipment supplier reguarding sanitary floor drain requirement. 2. Verify with the equipment supplier reguarding cold water and compressed air requirements.

GUIDE PLATE 4-1

Page 588: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-1

Treatment Planning Unit

NOTE: THE FOLLOWING SIMULATOR EQUIPMENT TO BE DETERMINED ON A PROJECT BASIS BY VETERANS HEALTH SERVICES AND RESEARCH

ADMINISTRATION

NOTE: LIGHT FIXTURE, WARNING, 120 VOLT, 20 AMP, RECESSED MOUNTED WITH 2-15 WATT, T-6, 145 VOLT (FURNISHED) AND WITH "IN USE" INSCRIPTION

(H-18-4, SD E-D-1)

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (H-18-1, MCS 16510)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (H-18-1, MCS 13091; H-18-3, CS 64-1; H-18-4, SD 24 THRU

24K AND NCRP REPORT NO. 33, 35 AND 49)

NOTE: OUTLET, WALL, OXYGEN, (H-18-1, MCS15491; H-18-3, CS 310-1)

NOTE: OUTLET, WALL, VACUUM, (H-18-1, MCS15491; H-18-3, CS 310-1)

NOTE: THE ABOVE OUTLETS GROUPED TOGETHER

NOTE: INTERCOM STATION (H-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (H-18-1, MCS 16111)

AR CF MODULAR CASEWORKJ-2 1 CF SINK, CORROSION RESISTING STEEL, WITH CENTER

DRAIN OUTLET, 457 mm X 381 mm X 203 mm(18" X 15" X 8") (H-18-1 & H-18-6, MCS 11602)

AR VC CONTROL CABINET1 VC SIMULATOR GANTRYAR VC SIMULATOR, POSITIONING LIGHTS, LASER1 VC TABLE, SIMULATOR1 VC TRANSFORMER, HIGH VOLTAGEAR VC X-RAY CONTROL AND POWER UNIT2 VV CAMERA, CCTV SYSTEM, WALL MTD.1 VV CHAIR, PATIENT1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 589: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-1

Treatment Planning Unit - Film Processing

1 VC PROCESSOR, FILM, AUTOMATIC, THRU-THE-WALL TYPE, CAPACITY 120 FILMS PER HOUR,

490mm W x 1035mm L x 600mm H (32”W x 35”L x 48”H)1 VC TANK, REPLENISHER, 25 GAL. CAPACITY, 2 FOR EACH

PROCESSOR1 VV ILLUMINATOR, FILM, X-RAY 355mm x 430mm (14” x 17”),

SURFACE MOUNTED, 120 VOLT, 20 AMP1 CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140: PG-18-3, CS 801-3)1 CC SINK, CORROSION RESISTING STEEL, SINGLE

COMPARTMENT, WALL HUNG, APPROX. 760mm x 430mm x 205mm D (30” x 20” x 8”D) WITH 305mm (12”) SLPLASHBACK (PG-18-1, MCS 15450)

1 CC HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED TO CONCEALED SUPPLY PIPES (PG-18-1, MCS 15450)

1 CC FLOOR DRAIN, NEAR FILM PROCESSING UNITS. (PLUMBIMG DESIGN CRITERIA AND INSTRUCTIONS)

1 CC FLOOR DRIAN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN CRITERIA & INSTRUCTIONS)

AR CC CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

AR CF COUNTER TOP, LENGTH AS REQUIRED x 600mmD x 940mmH (24”D x 37”H)(PG-18-1, MCS 11602, PG-18-6, ES 511)

1 VV DISPENSER, PAPERTPWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED

Treatment Planning Unit - Dark Room

1 CC DARK ROOM, CASSETTE PASS BOX AS DETERMINED BY VETERANS HEALTH SERVICES AND RESEARCH ADMINISTRATION (PG-18-4, SC 24H)

1 CC DOORS, LIGHTPROOF OR LIGHT LOCK DOOR IF SPECIFIED (PG-18-1, MCS 11471)

1 CC SAFELIGHT (PG-18-4, SD E-D-4)AR CC RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP

(PG-18-1, MCS 16140, PG-18-3, CS 801-3)AR CC ILLUMINATION, GENERAL

(FOR CONTROL SEE PG-18-4, SD E-S-T)AR VV UNITS, SILVER RECOVERYAR CC CONNECTIONS, PLUMBING, ELECTRICAL OR

MECHANICAL AS REQUIRED

SYMBOL QTY AI DESCRIPTION

Page 590: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-1

Treatment Planning Unit - Control Area, Simulator

NOTE: INCANDESCENT, DIMMING SYSTEM (H-18-1, MCS 16510)

NOTE: WINDOW, LEAD GLASS, MINIMUM 457 mm X 610 mm (18" X 24") (H-18-1,

MCS 13091; H-18-4, SD 24G)

1 CC RACK, APRON AND GLOVE, WALL MTD.1 VC CONSOLE, CONTROL, FOR SIMULATOR UNIT (CAPACITY

OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

1 VV CLOCK, BATTERY OPERATED1 VV ILLUMINATOR, 2 PANEL, SURFACE MTD.

SYMBOL QTY AI DESCRIPTION

Page 591: VA guide -2009
Page 592: VA guide -2009
Page 593: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsSuperficial Therapy UnitARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2745 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile or Carpet Slab Depr: Coordinate with

equipment manufacturer Notes: 1. 1200 mm (4’-0”) wide automatic

door. See VA ConstructionStandard 64-1,X-Ray RadiationShielding and Special Control”.

SPECIAL EQUIPMENTNone

LIGHTING General: 0-30 fc - 1.3 w/sf Special: ---

Notes: 1. “Beam On” and “Beam Ready” warning sign fixture.2. Recessed, lensed incandescent

downlight with 100W, A-21 lamp.

POWER General: 1800W (receptacles) Emergency: Notes: 1. 480V, 3P flush mounted circuit

breaker with shunt trip for linearaccelerator system. Coordinaterating with system supplier.

2. Emerency power off (EPO) pushbutton station. Connect to shunttrip curcuit breaker.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: Yes Pub. Addr: Yes Notes: 1. Junction box for CCTV camera with conduit to control room.

2. Junction box for CCTV monitor cabling.

VA DESIGN GUIDERADIATION THERAPY SERVICE

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: Yes Relative Humidity/Cooling: 50% Relative Humidity/Heating: 45% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load Lighting: Therapy: 14 w/sm (1.3 w/sf)

Control: 28w/sm (2.6w/sf) AC Load-Equipment:

Therapy: 12,505w (42,675 Btu/hr) Control: 2,520w (8,600 Btu/hr)

Number of People: 6 Special Exhaust: Yes Notes: 1. Route all ductwork over door to avoid radiation scatter.

2. Coordinate coolant water requirement with equipment supplier. The use of

city water is not permitted.

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: As Required Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Provide a line of compressed air

capable of providing minimum of 1 CFM at 5 psig.

2. Dry preaction system is recommended for fire protection

system.3. Some local potable water supplies

could cause excessive corrosion and frequent replacement of the internal equipment heat exchange. Consult equipment manufacturer regarding water treatment requirements.

GUIDE PLATE 4-2

Page 594: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-2

Superficial Therapy Unit

NOTE: THE FOLLOWING X-RAY EQUIPMENT TO BE DETERMINED ON PROJECT BASIS BY VETERANS HEALTH ADMINISTRATION.

1 VC THERAPY UNIT, X-RAY, HIGH FREQUENCY1 VC POWER UNIT DEVICE2 VC COOLER, WATER1 VC STABILIZER

INSTALL POWER UNIT DEVICE, WATER COOLER AND STABILIZER IN AN ENCLOSED SPACE NOT LESS THAN, 154mm x 3048mm (5’-0” x 10’-0”) WITH VENTILATION TO DISSIPATE HEAT GENERATED, AMOUNT OF

EQUIPMENT VARIES WITH MANUFACTURER.

NOTE: SERVICES, ELECTRICAL & PLUMBING, AS REQUIRED FOR EQUIPMENT.

1 VV TABLE, THERAPY, HYDRAULIC, MOBILE1 CC DOOR, POWER OPERATED, WITH ELECTRIC SAFETY

INTERLOCK TIED INTO CONTROL PANEL WITH LEAD GLASS WINDOW (PG-18-1, MCS 13091; PG18-4, SD 24G)

1 CC WINDOW, VIEWING, LEAD GLASS, FOR PATIENT OBSERVATION (PG-18-1, MCS 13091; PG-18-4, SD 25G)

AR CC SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (PG-18-1, MSC 13091, H-18-3, CS 64-1; PG-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

1 CC SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL, HOSPITAL RADIO SYSTEM (PG-18-1, MCS 16771)

SYMBOL QTY AI DESCRIPTION

Page 595: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-2

Superficial Therapy Unit, Control Area

1 VV CABINET, CONTROL FOR THERAPY UNIT (LOCATE ON SHELF DIRECTLY BELOW DIRECTLY BELOW LEAD GLASS VIEWING WINDOW) (CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

AR CC INCANDESCENT, DIMMING SYSTEM (PG-18-1, MCS 16510)1 CC INTERCOM, STATION (PG-18-1, MCS 16760)1 CC OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-18-1,

MCS 16111)

SYMBOL QTY AI DESCRIPTION

Page 596: VA guide -2009
Page 597: VA guide -2009
Page 598: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsOrthovoltage Therapy UnitARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2895 mm (9'-6") Wall Finish: Painted Concrete Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile or Carpet Slab Depr: Coordinated with equipment

manufacturer Notes: 1200mm (4’-0”) wide automatic

door. See VA Construction Standard 64-1, X-Ray Radiation Shielding and Special Control”.

SPECIAL EQUIPMENTNone

LIGHTING General: 30 FC - 3.2 W/SF Special: -- Notes: 1. “Beam On” and “Beam Ready”

warning sign fixture.2. Continuous fluorescent

direct/indirect fixture, acrylicprismatic lens on top and bottom,with 2-F32T8 lamps, 4100 deg. KCRI=85.

3. 600mm x 1200mm (2’x4’)recessed fluorescent lightfixtures, acrylic prismatic lens,w/2-F32T8 lamps, 4100 deg. K,CRI-85 (minimum).

4. 600mm x 600mm (2’x2’)recessed fluorescent light fixture,acrylic prismatic lens, w/2 FB31lamps, 4100 deg. K, CRI-85

5. Recessed, lensed incandescentdownlight with 100W, A-21 lamp.

POWER General: 1000W (Receptacles) Emergency: -- Notes: 1. 480V, 3P flush mounted circuit

breaker with shunt trip for linearaccelerator system. Coordinaterating with system supplier.

2. Emergency power off (EPO)push button station. Connect toshunt trip circuit breaker.

VA DESIGN GUIDERADIATION THERAPY SERVICE

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: Yes Pub. Addr Yes Notes: 1. Route all ductwork in vault down

maze and over door to avoidradiation scatter.

2. Coordinate coolant waterrequirement with equipmentsupplier. The use of city wateris not permitted.

3. Provide dedicated exhaustsystem to biological safetycabinet (if required).

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: Yes Relative Humidity/Cooling: 50% Relative Humidity/Heating: 45% Minimum Air Changes/Hr.: 8 Room Pressure: negative AC Load-Equipment:

Therapy Room: 12,505 w (42,675 Btu/hr)Control Room: 2,520 w (8,600 Btu/hr)

AC Load Lighting: Therapy Room: 14 w/sm (1.3 w/sf)Control Room: 28 w/sm (2.6 w/sf)

Number of People: 6 Special Exhaust: Yes Notes: --

GUIDE PLATE 4-3

Page 599: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsOrthovoltage Therapy UnitPLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: As Required Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Provide a line of compressed air

capable of providing minimum of1 CFM at 5 psig.

2. Dry preaction system isrecommended for fire protectionsystem.

3. Some local potable watersupplies could cause excessivecorrosion and frequentreplacement of the internalequipment heat exchange. consult equipment manufac-turer regarding water treatmentrequirements.

VA DESIGN GUIDERADIATION THERAPY SERVICE

GUIDE PLATE 4-3

Page 600: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-3

Orthovoltage Therapy Unit

NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (AIR, OXYGEN, VACUUM OUTLET AND BRACKET).

NOTE: SERVICES, ELECTRICAL & PLUMBING, AS REQUIRED FOR EQUIPMENT.

NOTE: THE FOLLOWING ORTHOVOLTAGE EQUIPMENT TO BE DETERMINED ON PROJECT BASIS BY VETERANS HEALTH ADMINISTRATION (VHA).

NOTE: DOOR, POWER OPERATED, WITH ELECTRIC SAFETY INTERLOCK TIED INTO CONTROL PANEL WITH LEAD GLASS WINDOW (H-18-1, MCS 08721)

NOTE: LIGHT FIXTURE, WARNING, 120 VOLT, 20 AMP, RECESSED MOUNTED WITH 2-15 WATT, T-6, 145 VOLT (FURNISHED) AND WITH "IN USE" INSCRIPTION(H-18-4, SD E-D-1)

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (H-18-1, MCS 16510)

NOTE: SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT, IN ACCORDANCE WITH (H-18-1, MCS 13091; H-18-3, CS 64-1; H-18-4, SD 24 THRU 24K AND NCRP REPORT NO. 33, 35 AND 49)

NOTE: SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL, HOSPITAL RADIO SYSTEM (H-18-1, MCS 16771)

AR CF MODULAR CASEWORKJ-2 AR CF SINK, CORROSION RESISTING STEEL, WITH CENTER

DRAIN OUTLET, 457 mm X 381 mm X 203 mm(18" X 15" X 8") (H-18-1 & H-18-6, MCS 11602)

AR VC CAMERA, TV, CLOSED CIRCUIT (FOR PATIENT OBSERVATION)

1 VC THERAPY UNIT1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV MONITOR, RADIATION, BATTERY POWERED, WALL

MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 601: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-3

Control Area, Orthovoltage Therapy Unit

NOTE: PROVIDE INTERCOM STATION IN CONTROL BOOTH CONNECTED TO REMOTE STATION IN THERAPY ROOM, WHEN CONTROL BOOTH IS SEPARATED FROM THERAPY ROOM.

NOTE: INTERCOM, STATION (H-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (H-18-1, MCS 16111)

NOTE: SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL, HOSPITAL RADIO SYSTEM (H-18-1, MCS 16771)

1 VC CONTROL UNIT, FOR THERAPY UNIT, LOCATED ON COUNTER (CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

1 VC MONITOR, CLOSED CIRCUIT TV - FOR PATIENT OBSERVATION

SYMBOL QTY AI DESCRIPTION

Page 602: VA guide -2009
Page 603: VA guide -2009
Page 604: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsSupervoltage UnitARCHITECTURAL Ceiling: Acoustic Ceiling Tile Lay-In Ceiling Ht: 2895 mm (9'-6") Wall Finish: Painted Concrete Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile or Carpet Slab Depr: Coordinate with equipment

manufacturer Notes: 1200mm (4’-0”) wide automatic

neutron shielded door. See VAConstruction Standard 64-1, “X-Ray Radiation Shielding andspecial Control”.

SPECIAL EQUIPMENTNone

LIGHTINGGeneral:

Megavoltage Rm: 0-30 fc = 1.3 w/sfControl Room: 0-30fc=2.6 w/sf

Special: --Notes: 1. “Beam On” and “Beam Ready”

warning sign fixture.2. Continuous fluorescent

direct/indirect fixture, acrylicprismatic lens on top and bottom,with 2-F32T8 lamps, 4100 deg. KCRI=85.

3. 600mm x 1200mm (2’x4’)recessed fluorescent lightfixtures, acrylic prismatic lens,w/2-F32T8 lamps, 4100 deg. K,CRI-85 (minimum).

4. 600mm x 600mm (2’x2’)recessed fluorescent light fixture,acrylic prismatic lens, w/2 FB31lamps, 4100 deg. K, CRI-85

5. Recessed, lensed incandescentdownlight with 100W, A-21 lamp

POWER General: 1000W (Receptacles) Emergency: -- Notes: 1. 480V, 3P flush mounted circuit

breaker with shunt trip for linearaccelerator system. Coordinaterating with system supplier.

VA DESIGN GUIDERADIATION THERAPY SERVICE

POWER (cont.)2. Emergency power off (EPO) push

button station. Connect to shunt tripcircuit breaker.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: Yes Public Addr: Yes Notes: 1.Junction box for CCTV camera with

conduit to control room.2. Junction box for CCTV monitor

cabling.

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: Yes Relative Humidity/Cooling: 50% Relative Humidity/Heating: 45% Minimum Air Changes/Hr.: 8 Room Pressure: Negative AC Load-Equipment:

Therapy Rm: 12,505 w (42,675 Btu/hr)Control Room: 2,520 w (8,600 Btu/hr)

AC Load Lighting:Therapy Rm: 14 w/sm (1.3 w/sf)Control Room: 28 w/sm (2.6 w/sf)

Number of People: 6 Special Exhaust: Yes Notes: 1. Route all ductwork in vault down

maze and over door to avoidradiation scatter.

2. Coordinate coolant waterrequirement with equipmentsupplier. The use of city water isnot permitted.

3. Provide dedicated exhaust systemto biological safety cabinet (ifrequired).

GUIDE PLATE 4-4

Page 605: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsSupervoltage UnitPLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: As Required Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Provide a line of compressed air

capable of providing minimum of 1CFM at 5 psig.

2. Dry preaction system isrecommended for fire protectionsystem.

3. Some local potable water suppliescould cause excessive corrosionand frequent replacement of theinternal equipment heat exchange. consult equipment manufac-turerregarding water treatmentrequirements.

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-4

Page 606: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-4

Supervoltage Unit

NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (AIR, OXYGEN, VACUUM OUTLET AND BRACKET).

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT.

NOTE: STATIONARY THERAPY UNIT MAY BE SUBSTITUTED IF APPROVED FOR A SPECIFIC PROJECT.

NOTE: THE FOLLOWING X-RAY EQUIPMENT TO BE DETERMINED ON PROJECT BASIS BY VETERANS HEALTH ADMINISTRATION.

NOTE: DOOR, POWER OPERATED, WITH ELECTRIC SAFETY INTERLOCK TIED INTO CONTROL PANEL WITH LEAD GLASS WINDOW (H-18-1, MCS 08721)

NOTE: LIGHT FIXTURE, WARNING, 120 VOLT, 20 AMP, RECESSED MOUNTED WITH 2-15 WATT, T-6, 145 VOLT (FURNISHED) AND WITH "IN USE" INSCRIPTION(H-18-4, SD E-D-1)

NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL FLUORESCENT ILLUMINATION SYSTEM (H-18-1, MCS 16510)

NOTE: PROTECTION, RADIATION - TO BE PRESCRIBED BY A REGISTERED RADIOLOGICAL PHYSICIST APPROVED BY THE AMERICAN BOARD OF RADIOLOGY IN ACCORDANCE WITH STANDARDS AND REGULATIONS OF NCRP REPORT 49 AND 50 AS APPROPRIATE

NOTE: SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL, HOSPITAL RADIO SYSTEM (H-18-1, MCS 16771)

AR CF MODULAR CASEWORKJ-2 AR CF SINK, CORROSION RESISTING STEEL, WITH CENTER

DRAIN OUTLET, 457 mm X 381 mm X 203 mm(18" X 15" X 8") (H-18-1 & H-18-6, MCS 11602)

1 VC CAMERA, TV, CLOSED CIRCUIT (FOR PATIENT OBSERVATION)

1 VC SUPERVOLTAGE THERAPY UNITAR VC POSITIONING LIGHTS, LASER1 VC TABLE, THERAPY, HYDRAULIC, MOBILE1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV MONITOR, RADIATION, BATTERY POWERED, WALL

MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 607: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-4

Control Area, Supervoltage Therapy Unit

NOTE: PROVIDE INTERCOM STATION IN CONTROL BOOTH CONNECTED TO REMOTE STATION IN COBALT ROOM WHEN CONTROL BOOTH IS SEPARATED

FROM COBALT ROOM.

NOTE: INTERCOM, STATION (H-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (H-18-1, MCS 16111)

NOTE: SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL, HOSPITAL RADIO SYSTEM (H-18-1, MCS 16771)

1 VC CABINET, CONTROL FOR THERAPY UNIT, LOCATE ON COUNTER (CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT BASIS)

1 VC MONITOR, CLOSED CIRCUIT TV - FOR PATIENT OBSERVATION

SYMBOL QTY AI DESCRIPTION

Page 608: VA guide -2009
Page 609: VA guide -2009
Page 610: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsMegavoltage UnitARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2895 mm (9'-6") Wall Finish: Painted Wainscot: -- Base: Resilient base Floor Finish: Vinyl Composition Tile or Carpet Slab Depr: Coordinate with equipment

manufacturer Notes: 1200mm (4’-0”) wide automatic

door. See VA Construction Standard 64-1, X-Ray Radiation Shielding and Special Control”.

SPECIAL EQUIPMENTNone

LIGHTING General: Control Rm: 0-30fc=1.3w/sf

Megavoltage Rm: 0-30fc=2.6w/sf Special: -- Notes: 1. “Beam On” and “Beam Ready”

warning sign fixture.2. Continuous fluorescent

direct/indirect fixture, acrylicprismatic lens on top and bottom,with 2-F32T8 lamps, 4100 deg. KCRI=85.

3. 600mm x 1200mm (2’x4’)recessed fluorescent lightfixtures, acrylic prismatic lens,w/2-F32T8 lamps, 4100 deg. K,CRI-85 (minimum).

4. 600mm x 600mm (2’x2’)recessed fluorescent light fixture,acrylic prismatic lens, w/2 FB31lamps, 4100 deg. K, CRI-85

5. Recessed, lensed incandescentdownlight with 100W, A-21 lamp

VA DESIGN GUIDERADIATION THERAPY SERVICE

POWER General: 1800w (Receptacles) Emergency: -- Notes: 1. 480V, 3P flush mounted circuit

breaker with shunt trip for linearaccelerator system. Coordinaterating with system supplier.

2. Emergency power off (EPO) pushbutton station. Connect to shunt tripcircuit breaker.

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: Yes Public Addr: Yes Notes: 1. Junction box for CCTV camera with

conduit to control room.2. Junction box for CCTV monitor

cabling.

GUIDE PLATE 4-5

Page 611: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsMegavoltage UnitHEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 24°C (76°F) Dry Bulb Temp Heating: 25°C (78°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: Yes Relative Humidity/Cooling: 50% Relative Humidity/Heating: 45%Minimum Air Changes/Hr.: 8Room Pressure: NegativeAC Load-Equipment:

Therapy Rm: 12,505w (42,675 Btu/hr)Control Room: 2,520w (8,600 Btu/hr)

AC Load Lighting:Therapy Rm: 14w/sm (1.3 w/sf)Control Rm: 28 w/sm (2.6w/sf)

Number of People: 6 Special Exhaust: Yes Notes: 1. Route all ductwork in vault down

maze and over door to avoidradiation scatter.

2. Coordinate coolant waterrequirement with equipmentsupplier. The use of city wateris not permitted.

3. Provide dedicated exhaustsystem to biological safetycabinet (if required).

VA DESIGN GUIDERADIATION THERAPY SERVICE

PLUMBING AND MEDICAL GASES Cold Water: Yes Hot Water: Yes Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: Yes Reagent Grade Water: As Required Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Provide a line of compressed air

capable of providing minimum of1 CFM at 5 psig.

2. Dry preaction system isrecommended for fire protectionsystem.

3. Some local potable watersupplies could cause excessivecorrosion and frequentreplacement of the internalequipment heat exchange. consult equipment manufac-turer regarding water treatmentrequirements.

GUIDE PLATE 4-5

Page 612: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-5

Megavoltage Unit

NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (AIR, OXYGEN, VACUUM OUTLET AND BRACKET).

NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT.

NOTE: THE FOLLOWING X-RAY EQUIPMENT TO BE DETERMINED ON PROJECT BASIS BY VETERANS HEALTH ADMINISTRATION.

NOTE: DOOR, POWER OPERATED, WITH ELECTRIC SAFETY INTERLOCK TIED INTO CONTROL PANEL WITH LEAD GLASS WINDOW (H-18-1, MCS 08721)

NOTE: INDIRECT, FLUORESCENT, DIMMED LIGHTING SYSTEM (H-18-1, MCS 16510)

NOTE: LIGHT FIXTURE, WARNING, 120 VOLT, 20 AMP, RECESSED MOUNTED WITH 2-15 WATT, T-6, 145 VOLT (FURNISHED) AND WITH "IN USE" INSCRIPTION(H-18-4, SD E-D-1)

NOTE: PROTECTION, RADIATION - TO BE PRESCRIBED BY A REGISTERED RADIOLOGICAL PHYSICIST APPROVED BY THE AMERICAN BOARD OF RADIOLOGY IN ACCORDANCE WITH STANDARDS AND REGULATIONS OF NCRP REPORT 49 AND 50 AS APPROPRIATE

NOTE: SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL, HOSPITAL RADIO SYSTEM (H-18-1, MCS 16771)

AR CC CUSTOM STORAGE CASEWORKAR CF MODULAR CASEWORK

J-2 AR CF SINK, CORROSION RESISTING STEEL, WITH CENTER DRAIN OUTLET, 457 mm X 381 mm X 203 mm(18" X 15" X 8") (H-18-1 & H-18-6, MCS 11602)

AR VC ACCELERATOR POSITIONING LIGHTS, LASER1 VC ACCELERATOR, LINEAR2 VC CAMERA, TV, CLOSED CIRCUIT (FOR PATIENT

OBSERVATION)1 VV MONITOR, RADIATION, BATTERY POWERED, WALL

MOUNTED1 VV TABLE, THERAPY, HYDRAULIC, MOBILE1 VV CLOCK, BATTERY OPERATED1 VV DISPENSER, PAPER TOWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED1 VV HOOK, COAT, WALL MOUNTED1 VV RECEPTACLE, WASTE, STEP ON TYPE, APPROX.,

305 mm (12") DIAMETER

SYMBOL QTY AI DESCRIPTION

Page 613: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 4-5

Control Area, Megavoltage Unit

NOTE: PROVIDE INTERCOM STATION IN CONTROL BOOTH CONNECTED TO REMOTE STATION IN THERAPY ROOM, WHEN CONTROL BOOTH IS SEPARATED FROM THERAPY ROOM.

NOTE: INTERCOM, STATION (H-18-1, MCS 16760)

NOTE: OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (H-18-1, MCS 16111)

1 VC CABINET, CONTROL, FOR LINEAR ACCELERATOR (CAPACITY OF)

1 VC MONITOR, CLOSED CIRCUIT TV - FOR PATIENT OBSERVATION

SYMBOL QTY AI DESCRIPTION

Page 614: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

VA DESIGN GUIDERADIATION THERAPY SERVICE

Section 5Design Guide Platesand Data Sheets:Technical Support AreasGuide Plate Series Plate Number

Mold RoomEquipment & Utility Plan 5 - 1Reflected Ceiling Plan 5 - 1Design Standards 5 - 1Equipment Guide List 5 - 1

Treatment Planning Computer RoomEquipment & Utility Plan 5 - 2Reflected Ceiling Plan 5 - 2Design Standards 5 - 2Equipment Guide List 5 - 2

CONTENTS - SECTION 5

Page 615: VA guide -2009
Page 616: VA guide -2009
Page 617: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsMold RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2745 mm (9'-0") Wall Finish: PaintGWB Wainscot: -- Base: Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes:

SPECIAL EQUIPMENTNone

LIGHTING General: 50fc - 2.4w/sf Special: -- Notes: 1. 600mm x 1200mm (2’ x 4’)

recessed fluorescent lightfixture, acrylic prismatic lens,W/2-F32T8 lamps, 4100 deg. K,CRI=85 (minimum).

POWER General: 1200w (Duplex Receptacles) Emergency: -- Notes: 1. Provide exhaust hood over

power tools..

COMMUNICATION ADP: -- Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes: 1. Conduit and junction boxes

required for electronic access security system.

VA DESIGN GUIDERADIATION THERAPY SERVICE

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% 100% Exhaust Air: Yes Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 10 Room Pressure: Negative AC Load-Equipment: 162w/sm (15w/sf) AC Load Lighting: 2.6 w/sm (2.4 w/sf) Number of People: 4 Special Exhaust: Yes Notes: --

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes: 1. Shop compressed air might be

required. 2. Plaster trap might be required.

GUIDE PLATE 5-1

Page 618: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 5-1

Mold Room

NOTE: CEILING LIGHTING SHOULD BE LOCATED TO SUIT BENCH LOCATIONS AND ORIENTATIONS.

NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED

NOTE: RECEPTACLE, ELECTRICAL, PROVIDE BOTH 120 & 208 VOLT SERVICE, STRIP, MULTIPLE, HEAVY DUTY, 1067 mm (42") ABOVE FINISHED FLOOR ON

WALLS W/OUTLET AT 914 mm (36") INTERVALS (H-18-1, MCS 16140; H-18-3, CS 801-3)

AR CC HOOD, CANOPY, EXHAUST, PROVIDED OVER POWER TOOLS AND MELTING POWER AREAS, DIMENSIONS TO BE INDICATED ON DRAWINGS (H-18-1, MCS 15822)

1 CC SINK, CORROSION RESISTING STEEL, DOUBLE COMPARTMENT, ELBOW CONTROLS

AR CF MODULAR CASEWORK1 VV DRILL PRESS, BENCH MOUNTED1 VV DUST COLLECTOR, MOBILE1 VV GRINDER, BENCH MOUNTED1 VV ILLUMINATOR, X-RAY FILM, 2 PANEL, SURFACE MTD.1 VV MILL, COMPENSATOR1 VV PROJECTOR, COMPENSATOR1 VV PUMP, SUCTION, MOBILE1 VV SAW, BAND, BENCH TYPEAR VV STOOL, ADJUSTABLE HEIGHT, WITHOUT ARMS1 VV STYROFOAM CUTTER1 VV TABLE, BLOCK COOLINGAR VV WORK BENCH, WOOD TOP WITH STORAGE

UNDERNEATH, APPROX., 1219 mm (48") X LENGTH AS REQUIRED X 762 mm (30")

1 VV DISPENSER, PAPERTPWEL, SURFACE MOUNTED1 VV DISPENSER, SOAP, LIQUID, WALL MOUNTED

SYMBOL QTY AI DESCRIPTION

Page 619: VA guide -2009
Page 620: VA guide -2009
Page 621: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Design StandardsTreatment Planning Computer RoomARCHITECTURAL Ceiling: Acoustic Ceiling Tile Ceiling Ht: 2745 mm (9'-0") Wall Finish: Paint Wainscot: -- Base: Resilient Base Floor Finish: Vinyl Composition Tile Slab Depr: -- Notes: 1. 3'-0" Wide door with tempered

glass view window

SPECIAL EQUIPMENTNone

LIGHTING General: 50fc - 1.3 w/sf Special: -- Notes: 1. 600mm x 1200mm (2’ x 4’)

recessed fluorescent lightfixture, acrylic prismatic lens,W/3-F32T8 lamps, 4100 deg. K,CRI=75 (minimum).

POWER General: 1400w (Receptacles) Emergency: -- Notes: --

COMMUNICATION ADP: Yes Radio: -- Telephone: Yes Intercom: -- Pub. Addr: -- Notes:

VA DESIGN GUIDERADIATION THERAPY SERVICE

HEATING, VENTILATING AND AIRCONDITIONING Dry Bulb Temp Cooling: 25°C (78°F) Dry Bulb Temp Heating: 22°C (72°F) Minimum % Outside Air: 15% Noise Criteria: NC-40 Steam: -- Relative Humidity/Cooling: 50% Relative Humidity/Heating: 30% Minimum Air Changes/Hr.: 4 Room Pressure: 0 AC Load-Equipment: 140w/sm (13w/sf) AC Load Lighting: 26w/sm (2.4w/sf) Number of People: 4 Special Exhaust: -- Notes:

--

PLUMBING AND MEDICAL GASES Cold Water: -- Hot Water: -- Laboratory Air: -- Laboratory Vacuum: -- Sanitary Drain: -- Reagent Grade Water: -- Medical Air: -- Medical Vacuum: -- Oxygen: -- Notes:

GUIDE PLATE 5-2

Page 622: VA guide -2009

FINAL DRAFT 2-29-96Revised 10/96

Equipment Guide List

VA DESIGN GUIDERADIATION THERAPY SERVICE GUIDE PLATE 5-2

Treatment Planning Computer Room

NOTE: THE DEDICATED COMPUTER EQUIPMENT FOR RADIATION THERAPY PLANNING TO BE DETERMINED ON PROJECT BASIS BY VETERANS HEALTH

ADMINISTRATION (VHA).

NOTE: OUTLETS, RADIATION THERAPY PLANNING COMPUTER SYSTEM (EMPTY CONDUIT SYSTEM) (SEE ELECTRICAL ENGINEERING SERVICE GUIDE LINES)

2 VV CHAIR, ROTARY, WITH ARMS2 VV WORKSTATION, TREATMENT PLANNING COMPUTER, W/

MAG TAPE, DISK SERVER, PRINTER/PLOTTER, DIGITIZER

SYMBOL QTY AI DESCRIPTION

Page 623: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Contents - Section 4

Section 4Design Guide Platesand Data Sheets:General Rooms

GuidePlateSeries

4 - 1.......Administrative OfficesEquipment & Utility Plan

4-1a....... Chief of SPDDesign StandardsEquipment Guide List

4-1b....... Assistant Chief of SPDDesign StandardsEquipment Guide List

4-1c....... Clerical StaffDesign StandardsEquipment Guide List

4 - 2.......Lockers, Toilet, & Shower Room(Soiled Area, Unisex)Equipment & Utility PlanDesign StandardsEquipment Guide List

4 - 3.......Lockers, Toilet, & Shower Room(Clean Area, Women)Equipment & Utility PlanDesign StandardsEquipment Guide List

4 - 4.......Lockers, Toilet, & Shower Room(Clean Area, Men)Equipment & Utility PlanDesign StandardsEquipment Guide List

Page 624: VA guide -2009
Page 625: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-1a

Design StandardsChief of SPD

ARCHITECTURALCeiling AT Wainscot -

Ceiling Height 2700 (9'-0") Base RB

Wall Finish GWB/W/PL (SC) Floor Finish CP/VCT

Notes: Slab Depression -

SPECIAL EQUIPMENT

ELECTRICALLighting PowerGeneral 70 FC - 4 W/SF General 2000 W RECEPTACLES

Special - Emergency -

Notes:

COMMUNICATIONSADP YES Telephone YES

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling 50%

Dry Bulb Temp Heating F 72 Relative Humidity/Heating 30%

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure (0)

Noise Criteria NC 40 AC Load - Equipment 0.4645 W/SM

Steam - Number of People 5

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water - Sanitary Drain -

Hot Water - Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 626: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-1a

Equipment Guide ListChief of SPDSYMBOL AI QUANTITY DESCRIPTION

A B C D

OFFICE, CHIEF, SPD

VV 1 DESK, DOUBLE PEDESTAL, APPROX., 1524 MM X 762MM X 749 MM (60" X 30" X 29-1/2")

VV 1 CHAIR, ROTARY, WITH ARMS

VV 3 CHAIR, STRAIGHT, WITH ARMS

VV 1 BOOKCASE, SECTIONAL, EACH SECTION, 838 MM X 330MM X 381 MM (33" X 13" X 15") WITH 254 MM (10") BASE

VV 1 TABLE, OFFICE, 1524 MM X 762 MM X 749 MM (60" X 30"X 29-1/2")

VV 1 HOOK, COAT, WALL MOUNTED

VV 1 CRT, COMPUTER SYSTEM, WITH KEYBOARD

VV 1 PRINTER, COMPUTER SYSTEM

VV 1 STAND, COMPUTER PRINTER, APPROX., 610 MM X 610MM X 660 MM (24" X 24" X 26")

CC 1 RECEPTACLE, ELECTRICAL, QUADRAPLEX, FORCOMPUTER EQUIPMENT ITEMS (PG-08-1, MCS 16140;H-08-3, CS 866-1)

VV 1 CLOCK, BATTERY OPERATED

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 627: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-1b

Design StandardsAssistant Chief of SPD

ARCHITECTURALCeiling AT Wainscot -

Ceiling Height 2700 (9'-0") Base RB

Wall Finish GWB/W/PL (SC) Floor Finish CP/VCT

Notes: Slab Depression -

SPECIAL EQUIPMENT

ELECTRICALLighting PowerGeneral 70 FC - 4 W/SF General 2000 W RECEPTACLES

Special - Emergency -

Notes:

COMMUNICATIONSADP YES Telephone YES

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling 50%

Dry Bulb Temp Heating F 72 Relative Humidity/Heating 30%

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure (0)

Noise Criteria NC-40 AC Load - Equipment 0.4645 W/SM

Steam - Number of People 5

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water - Sanitary Drain -

Hot Water - Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 628: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-1b

Equipment Guide ListAssistant Chief of SPDSYMBOL AI QUANTITY DESCRIPTION

A B C D

OFFICE, ASSISTANT CHIEF, SPD

VV 1 DESK, DOUBLE PEDESTAL, APPROX., 1524 MM X 762MM X 749 MM (60" X 30" X 29-1/2")

VV 1 CHAIR, ROTARY, WITH ARMS

VV 1 CHAIR, STRAIGHT, WITH ARMS

VV 1 BOOKCASE, SECTIONAL, EACH SECTION, 838 MM X 330MM X 381 MM (33" X 13" X 15") WITH 254 MM (10") BASE

VV 1 HOOK, COAT, WALL MOUNTED

VV 1 CRT, COMPUTER SYSTEM, WITH KEYBOARD

VV 1 PRINTER, COMPUTER SYSTEM

VV 1 STAND, COMPUTER PRINTER, APPROX., 610 MM X 610MM X 660 MM (24" X 24" X 26")

CC 1 RECEPTACLE, ELECTRICAL, QUADRAPLEX, FORCOMPUTER EQUIPMENT ITEMS (PG-08-1, MCS 16140;H-08-3, CS 866-1)

VV 1 CLOCK, BATTERY OPERATED

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 629: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-1c

Design StandardsClerical Staff

ARCHITECTURALCeiling AT Wainscot -

Ceiling Height 2700 (9'-0") Base RB

Wall Finish GWB/W/PL (SC) Floor Finish CP/VCT

Notes: Slab Depression -

SPECIAL EQUIPMENT

ELECTRICALLighting PowerGeneral 70 FC - 4 W/SF General 2000 W RECEPTACLES

Special - Emergency -

Notes:

COMMUNICATIONSADP YES Telephone YES

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling 50%

Dry Bulb Temp Heating F 72 Relative Humidity/Heating 30%

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure (0)

Noise Criteria NC-40 AC Load - Equipment 0.4645 W/SM

Steam - Number of People 5

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water - Sanitary Drain -

Hot Water - Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 630: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-1c

Equipment Guide ListClerical StaffSYMBOL AI QUANTITY DESCRIPTION

A B C D

CLERICAL STAFF

VV 2 1 1 DESK, TYPEWRITER, DOUBLE PEDESTAL

VV 1 DESK, DOUBLE PEDESTAL, APPROX., 1524 MM X 762MM X 749 MM (60" X 30" X 29-1/2")

VV 1 CHAIR, ROTARY, WITH ARMS

VV 2 1 1 CHAIR, ROTARY, WITHOUT ARMS

VV 4 3 2 CHAIR, STRAIGHT, WITHOUT ARMS

VV 3 2 1 CABINET, FILING (LETTER SIZE) 5 DRAWER, APPROX.,381 MM X 635 MM X 1524 MM (15" X 25" X 60")

VV 2 1 1 CABINET, FILING (LEGAL SIZE) 5 DRAWER, 457 MM X635 MM X 1524 MM (18" X 25" X 60")

VV 1 HOOK, COAT, WALL MOUNTED

VV 1 CRT, COMPUTER SYSTEM, WITH KEYBOARD

VV 1 PRINTER, COMPUTER SYSTEM

VV 1 STAND, COMPUTER PRINTER, APPROX., 610 MM X 610MM X 660 MM (24" X 24" X 26")

CC 1 RECEPTACLE, ELECTRICAL, QUADRAPLEX, FORCOMPUTER EQUIPMENT ITEMS (PG-08-1, MCS 16140;H-08-3, CS 866-1)

VV AR CLOCK, BATTERY OPERATED

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 631: VA guide -2009
Page 632: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-2

Design StandardsLockers, Toilet, & Shower Room (Soiled Area)

ARCHITECTURALCeiling PCP/AT Wainscot CT 1200 (4'-0")*

Ceiling Height 2700 (9'-0") Base CT

Wall Finish CT/GWB Floor Finish CT/VCT

Notes: Slab Depression -

UNISEX FACILITY, ENCLOSED TOILET

*WAINSCOT FOR TOILET AREA ONLY

ELECTRICALLighting PowerGeneral 30 FC - 2 W/SF General 400 W

Special - Emergency -

Notes:

COMMUNICATIONSADP - Telephone -

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling -

Dry Bulb Temp Heating F 72 Relative Humidity/Heating -

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure NEGATIVE

Noise Criteria NC-40 AC Load - Equipment 0.0929 W/SM

Steam - Number of People 1

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES

Hot Water YES Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 633: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-2

Equipment Guide ListLockers, Toilet, & Shower Room (Soiled Area)SYMBOL AI QUANTITY DESCRIPTION

A B C D

LOCKERS, LOUNGE, TOILET AND SHOWER FACILITIES- MALE

NOTE: CONTIGUOUS TO SOILED RECEIVING AND DECONTAMINATION AREA.

T-B CC AR LOCKER, STEEL, SLOPING TOP, 12"W X 21"D X 72"H(PG-08-1, MCS 10500; H-08-4, SD 61)

P-415 CC 1 2 2 1 LAVATORY, STRAIGHT BACK (PG-08-1, MCS 15450; H-08-4, SD 53)

CC 1 2 2 1 MIRROR, 406 MM X 508 MM (16" X 20"), WITH INTEGRALSHELF, OVER LAVATORY (PG-08-1, MCS 10800; H-08-4,SD 15)

VV 1 2 2 1 DISPENSER, SOAP, LIQUID, WALL MOUNTED

CC 1 2 2 1 DISPENSER, PAPER TOWEL AND DISPOSALCOMBINATION UNITS (PG-08-1, MCS 10800)

CC 1 2 2 1 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP, WITH GROUND FAULT INTERRUPTER, ADJACENTTO LAVATORY (PG-08-1, MCS 16140; H-08-3, CS 801-3)

WHEELCHAIR WATER CLOSETS WILL BE INACCORDANCE WITH THE APPROPRIATE SPACEPROGRAM, P-103 WILL BE USED FOR BOTHCONVENTIONAL AND WHEELCHAIR INSTALLATIONS.

P-103 CC 1 WATER CLOSET, WALL HUNG (PG-08-1, MCS 15450; H-08-4, SD 4)

CC 1 ENCLOSURE, TOILET, CEILING HUNG (PG-08-1, MCS10162; H-08-3, CD 13; H-08-4, SD 12)

CC 1 BAR, GRAB FOR WATER CLOSET (PG-08-1, MCS 10800;H-08-4, SD 12, 14B & 14F)

CC 1 DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-08-1,MCS 10800; H-08-4, SD 12)

P-201 CC 1 URINAL, WALL HUNG (PG-08-1, MCS 15450; H-08-4, SD4)

CC 1 STALL, SHOWER (PG-08-1, MCS 10170; H-08-4, SD 13A)

P-702 CC 1 SHOWER, BATH FIXTURE, WALL MOUNTED,CONCEALED SUPPLIES (PG-08-1, MCS 15450; H-08-4,SD 13A)

CC 1 ROD, CURTAIN, TUB OR SHOWER (PG-08-1, MCS 10800)

CC 1 DISH, SOAP, SURFACE MOUNTED (PG-08-1, MCS 10800)

CC 1 2 2 1 HOOK, TOWEL (PG-08-1, MCS 10800)

CC 1 HOOK, CLOTHES (PG-08-1, MCS 10800)

VV 1 HAMPER, SOILED LINEN, WITH HINGED SELF CLOSINGTOP, 20" DIA.

VV 1 RECEPTACLE, WASTE, WITH SWINGING TOP, 16" X 16"

Page 634: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-2

Equipment Guide ListLockers, Toilet, & Shower Room (Soiled Area)SYMBOL AI QUANTITY DESCRIPTION

A B C D

LOCKERS, LOUNGE, TOILET AND SHOWER FACILITIESFEMALE

NOTE: CONTIGUOUS TO SOILED RECEIVING AND DECONTAMINATION AREA.

T-B CC AR LOCKER, STEEL, SLOPING TOP, 12"W X 21"D X 72"H(PG-08-1, MCS 10500; H-08-4, SD 61)

P-415 CC 1 2 2 1 LAVATORY, STRAIGHT BACK (PG-08-1, MCS 15450; H-08-4, SD 53)

CC 1 2 2 1 MIRROR, 406 MM X 508 MM (16" X 20"), WITH INTEGRALSHELF, OVER LAVATORY (PG-08-1, MCS 10800; H-08-4,SD 15)

VV 1 2 2 1 DISPENSER, SOAP, LIQUID, WALL MOUNTED

CC 1 2 2 1 DISPENSER, PAPER TOWEL AND DISPOSALCOMBINATION UNITS (PG-08-1, MCS 10800)

CC 1 2 2 1 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP, WITH GROUND FAULT INTERRUPTER, ADJACENTTO LAVATORY (PG-08-1, MCS 16140; H-08-3, CS 801-3)

WHEELCHAIR WATER CLOSETS WILL BE INACCORDANCE WITH THE APPROPRIATE SPACEPROGRAM, P-103 WILL BE USED FOR BOTHCONVENTIONAL AND WHEELCHAIR INSTALLATIONS.

P-103 CC 1 WATER CLOSET, WALL HUNG (PG-08-1, MCS 15450; H-08-4, SD 4)

CC 1 ENCLOSURE, TOILET, CEILING HUNG (PG-08-1, MCS10162; H-08-3, CD 13; H-08-4, SD 12)

CC 1 BAR, GRAB FOR WATER CLOSET (PG-08-1, MCS 10800;H-08-4, SD 12, 14B & 14F)

CC 1 DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-08-1,MCS 10800; H-08-4, SD 12)

CC 1 STALL, SHOWER (PG-08-1, MCS 10170; H-08-4, SD 13A)

P-702 CC 1 SHOWER, BATH FIXTURE, WALL MOUNTED,CONCEALED SUPPLIES (PG-08-1, MCS 15450; H-08-4,SD 13A)

CC 1 ROD, CURTAIN, TUB OR SHOWER (PG-08-1, MCS 10800)

CC 1 DISH, SOAP, SURFACE MOUNTED (PG-08-1, MCS 10800)

CC 1 2 2 1 HOOK, TOWEL (PG-08-1, MCS 10800)

CC 1 HOOK, CLOTHES (PG-08-1, MCS 10800)

VV 1 HAMPER, SOILED LINEN, WITH HINGED SELF CLOSINGTOP, 20" DIA.

VV 1 RECEPTACLE, WASTE, WITH SWINGING TOP, 16" X 16"

Page 635: VA guide -2009
Page 636: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-3

Design StandardsLockers, Toilet, & Shower Room (Clean Area)

ARCHITECTURALCeiling PCP/AT Wainscot CT 1200 (4'-0")

Ceiling Height 2700 (9'-0") Base CT

Wall Finish CT/GWB Floor Finish CT/VCT

Notes: Slab Depression -

SEPARATE FACILITIES FOR MEN AND WOMEN

ENCLOSED TOILET

ELECTRICALLighting PowerGeneral 30 FC - 2 W/SF General 400 W

Special - Emergency -

Notes:

COMMUNICATIONSADP - Telephone -

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling -

Dry Bulb Temp Heating F 72 Relative Humidity/Heating -

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure NEGATIVE

Noise Criteria NC-40 AC Load - Equipment 0.0929 W/SM

Steam - Number of People 2

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES

Hot Water YES Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 637: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-3

Equipment Guide ListLockers, Toilet, & Shower Room (Clean Area)SYMBOL AI QUANTITY DESCRIPTION

A B C D

LOCKERS, LOUNGE, TOILET AND SHOWER FACILITIESFEMALE

NOTE: CONTIGUOUS TO SOILED RECEIVING AND DECONTAMINATION AREA.

T-B CC AR LOCKER, STEEL, SLOPING TOP, 12"W X 21"D X 72"H(PG-08-1, MCS 10500; H-08-4, SD 61)

P-415 CC 1 2 2 1 LAVATORY, STRAIGHT BACK (PG-08-1, MCS 15450; H-08-4, SD 53)

CC 1 2 2 1 MIRROR, 406 MM X 508 MM (16" X 20"), WITH INTEGRALSHELF, OVER LAVATORY (PG-08-1, MCS 10800; H-08-4,SD 15)

VV 1 2 2 1 DISPENSER, SOAP, LIQUID, WALL MOUNTED

CC 1 2 2 1 DISPENSER, PAPER TOWEL AND DISPOSALCOMBINATION UNITS (PG-08-1, MCS 10800)

CC 1 2 2 1 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP, WITH GROUND FAULT INTERRUPTER, ADJACENTTO LAVATORY (PG-08-1, MCS 16140; H-08-3, CS 801-3)

WHEELCHAIR WATER CLOSETS WILL BE INACCORDANCE WITH THE APPROPRIATE SPACEPROGRAM, P-103 WILL BE USED FOR BOTHCONVENTIONAL AND WHEELCHAIR INSTALLATIONS.

P-103 CC 1 WATER CLOSET, WALL HUNG (PG-08-1, MCS 15450; H-08-4, SD 4)

CC 1 ENCLOSURE, TOILET, CEILING HUNG (PG-08-1, MCS10162; H-08-3, CD 13; H-08-4, SD 12)

CC 1 BAR, GRAB FOR WATER CLOSET (PG-08-1, MCS 10800;H-08-4, SD 12, 14B & 14F)

CC 1 DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-08-1,MCS 10800; H-08-4, SD 12)

CC 1 STALL, SHOWER (PG-08-1, MCS 10170; H-08-4, SD 13A)

P-702 CC 1 SHOWER, BATH FIXTURE, WALL MOUNTED,CONCEALED SUPPLIES (PG-08-1, MCS 15450; H-08-4,SD 13A)

CC 1 ROD, CURTAIN, TUB OR SHOWER (PG-08-1, MCS 10800)

CC 1 DISH, SOAP, SURFACE MOUNTED (PG-08-1, MCS 10800)

CC 1 2 2 1 HOOK, TOWEL (PG-08-1, MCS 10800)

CC 1 HOOK, CLOTHES (PG-08-1, MCS 10800)

VV 1 HAMPER, SOILED LINEN, WITH HINGED SELF CLOSINGTOP, 20" DIA.

VV 1 RECEPTACLE, WASTE, WITH SWINGING TOP, 16" X 16"

Page 638: VA guide -2009
Page 639: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-4

Design StandardsLockers, Toilet, & Shower Room (Clean Area)

ARCHITECTURALCeiling PCP/AT Wainscot CT 1200 (4'-0")

Ceiling Height 2700 (9'-0") Base CT

Wall Finish CT/GWB Floor Finish CT/VCT

Notes: Slab Depression -

SEPARATE FACILITIES FOR MEN AND WOMEN

ENCLOSED TOILET

ELECTRICALLighting PowerGeneral 30 FC - 2 W/SF General 400 W

Special - Emergency -

Notes:

COMMUNICATIONSADP - Telephone -

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling -

Dry Bulb Temp Heating F 72 Relative Humidity/Heating -

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure NEGATIVE

Noise Criteria NC-40 AC Load - Equipment 0.0929 W/SM

Steam - Number of People 2

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES

Hot Water YES Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 640: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 4-4

Equipment Guide ListLockers, Toilet, & Shower Room (Clean Area)SYMBOL AI QUANTITY DESCRIPTION

A B C D

LOCKERS, LOUNGE, TOILET AND SHOWER FACILITIES- MALE

NOTE: CONTIGUOUS TO SOILED RECEIVING AND DECONTAMINATION AREA.

T-B CC AR LOCKER, STEEL, SLOPING TOP, 12"W X 21"D X 72"H(PG-08-1, MCS 10500; H-08-4, SD 61)

P-415 CC 1 2 2 1 LAVATORY, STRAIGHT BACK (PG-08-1, MCS 15450; H-08-4, SD 53)

CC 1 2 2 1 MIRROR, 406 MM X 508 MM (16" X 20"), WITH INTEGRALSHELF, OVER LAVATORY (PG-08-1, MCS 10800; H-08-4,SD 15)

VV 1 2 2 1 DISPENSER, SOAP, LIQUID, WALL MOUNTED

CC 1 2 2 1 DISPENSER, PAPER TOWEL AND DISPOSALCOMBINATION UNITS (PG-08-1, MCS 10800)

CC 1 2 2 1 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP, WITH GROUND FAULT INTERRUPTER, ADJACENTTO LAVATORY (PG-08-1, MCS 16140; H-08-3, CS 801-3)

WHEELCHAIR WATER CLOSETS WILL BE INACCORDANCE WITH THE APPROPRIATE SPACEPROGRAM, P-103 WILL BE USED FOR BOTHCONVENTIONAL AND WHEELCHAIR INSTALLATIONS.

P-103 CC 1 WATER CLOSET, WALL HUNG (PG-08-1, MCS 15450; H-08-4, SD 4)

CC 1 ENCLOSURE, TOILET, CEILING HUNG (PG-08-1, MCS10162; H-08-3, CD 13; H-08-4, SD 12)

CC 1 BAR, GRAB FOR WATER CLOSET (PG-08-1, MCS 10800;H-08-4, SD 12, 14B & 14F)

CC 1 DISPENSER, TOILET TISSUE, DOUBLE ROLL (PG-08-1,MCS 10800; H-08-4, SD 12)

P-201 CC 1 URINAL, WALL HUNG (PG-08-1, MCS 15450; H-08-4, SD4)

CC 1 STALL, SHOWER (PG-08-1, MCS 10170; H-08-4, SD 13A)

P-702 CC 1 SHOWER, BATH FIXTURE, WALL MOUNTED,CONCEALED SUPPLIES (PG-08-1, MCS 15450; H-08-4,SD 13A)

CC 1 ROD, CURTAIN, TUB OR SHOWER (PG-08-1, MCS 10800)

CC 1 DISH, SOAP, SURFACE MOUNTED (PG-08-1, MCS 10800)

CC 1 2 2 1 HOOK, TOWEL (PG-08-1, MCS 10800)

CC 1 HOOK, CLOTHES (PG-08-1, MCS 10800)

VV 1 HAMPER, SOILED LINEN, WITH HINGED SELF CLOSINGTOP, 20" DIA.

VV 1 RECEPTACLE, WASTE, WITH SWINGING TOP, 16" X 16"

Page 641: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Contents - Section 5

Section 5Design Guide Platesand Data Sheets:Areas Specific toSPD

GuidePlateSeries

5 - 1 .......Soiled Receiving &Decontamination AreaEquipment & Utility PlanDesign StandardsEquipment Guide List

5 - 2 .......Preparation, Assembly &Sterilization AreaEquipment & Utility PlanDesign StandardsEquipment Guide List

5 - 3 .......EtO Sterilizer/Aerator RoomEquipment & Utility PlanDesign StandardsEquipment Guide List

GuidePlateSeries

5 - 4.......Manual Equipment Wash AreaEquipment & Utility PlanDesign StandardsEquipment Guide List

5 - 5.......Equipment Storage & TestingRoomEquipment & Utility PlanDesign StandardsEquipment Guide List

5 - 6.......Dispatcher's Control StationEquipment & Utility PlanDesign StandardsEquipment Guide List

Page 642: VA guide -2009
Page 643: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-1

Design StandardsSoiled Receiving & Decontamination AreaARCHITECTURALCeiling PL (SC) Wainscot -

Ceiling Height 2700 (9'-0") Base QT

Wall Finish PL (SC) Floor Finish QT

Slab Depression -

SPECIAL EQUIPMENTVS-503: WASHER/STERILIZER

VS-210: STEAM STERILIZERS

HW-546: AUTOMATIC CART WASH

ELECTRICALLighting PowerGeneral 30 FC - 2 W/SF General *

Special - Emergency *

Notes: *VS-210: POWER DOOR - 15A, 120V; CONTROL - 1.0A, 120V

*VS-503: CONTROL - 10A, 120V; PUMP - 10A, 208V, 3 PH;

*COMPRESSOR - 3/4 HP, 208V, 3 PH

*HW-546: 20A, 480V, 3PH, 3 WIRE

COMMUNICATIONSADP - Telephone -

Radio YES** Intercom EMPTY CONDUIT

Notes: Public Address -

**CONNECT TO HOSPITAL SYSTEM

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling 50%

Dry Bulb Temp Heating F 72 Relative Humidity/Heating 30%

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure NEGATIVE

Noise Criteria NC-40 AC Load - Equipment 0.5574 W/SM

Steam YES*** Number of People 3

Notes: Special Exhaust YES***

***VS EQUIP: SEE PG-08-6 FOR STEAM, HEAT GAIN, EXHAUST CAPACITY

HW-546: 1400 CFM EXH; 30-60 PSIG, 40 LB/HR STEAM

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES

Hot Water YES Reagent Grade Water YES

Laboratory Air YES Laboratory Vacuum -

Notes: ****FOR VS EQUIP Other SHOP AIR****

Page 644: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-1

Equipment Guide ListSoiled Receiving & Decontamination AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

SOILED RECEIVING AND DECONTAMINATION AREA

TOP 5A CC 1 COUNTER TOP, CORROSION RESISTING (STAINLESS)STEEL, 32 MM (1-1/4") THICK (PG-08-1 & PG-08-6, MCS11602)

S-2 CF 3 SINK, CORROSION RESISTING STEEL, WITH END ORCORNER DRAIN OUTLET, 635 MM X 457 MM X 406 MM(25" X 18" X 16") DEEP, INTEGRAL WITH TOP 5A (PG-08-1 & PG-08-6, MCS 11602)

-AND/OR-

CC 1 SINK, DOUBLE, CORROSION RESISTING STEEL, WITHEND OR CORNER DRAIN OUTLET, EACH SINK, 635 MMX 457 MM X 406 MM (25" X 18" X 16") DEEP, INTEGRALWITH TOP 5A (PG-08-1 & PG-08-6, MCS 11602)

VL20 CC 3 CABINET, UNDERCOUNTER, SINK UNIT, 2 HINGEDPANEL DOORS, AVAILABLE WIDTHS - 762 MM, 914 MM,1067 MM, 1219 MM; (30", 36", 42", 48") DEPTH - 559 MM;(22") HEIGHT - 787 MM, (31") FOR FLOOR MOUNTED,ASSEMBLED WITH TOP 5A AND SINK S-2 (PG-08-1 &PG-08-6, MCS 12345)

-AND/OR-

VL23 CC 1 CABINET, UNDERCOUNTER, SINK UNIT, DOUBLECOMPARTMENT, 2 HINGED PANEL DOORS, AVAILABLEWIDTHS - 1372 MM, 1524 MM; (54", 60") DEPTH - 559MM; (22") HEIGHT - 787 MM, (31") FOR FLOORMOUNTED, ASSEMBLED WITH TOP 5A AND DOUBLESINK (PG-08-1 & PG-08-6, MCS 12345)

CC 1 OUTLET, LABORATORY AIR, OVER COUNTER, WITHIN36" OF SINK (PG-08-1, MCS 15488)

VL86 CC 1 MANIFOLD, TUBE WASHING (PG-08-1 & PG-08-6, MCS11602)

CC 1 FAUCET, REAGENT GRADE OR MINERAL FREE WATER(PG-08-1, MCS 11602)

VV AR WASHER, ROTARY, FOR WASHINGRESPIRATORY/ANESTHESIA TUBING ANDACCESSORIES, E.G., OLYMPIC TYPE

CC 1 DOOR, ACCESS, LAUNDRY CHUTE (PG-08-1, MCS14560)

VS-504 CC 1 WASHER/STERILIZER, SURGICAL INSTRUMENT,SINGLE DOOR, CABINET ENCLOSED, (CHAMBER SIZE:16" X 16" X 26"/3.8 CU. FT.), PROVIDE STEAM, WATER,COMPRESSED AIR, DRAIN, ELECTRIC AND EXHAUSTAS REQUIRED (PG-08-1 & PG-08-6, MCS 11710)

Page 645: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-1

Equipment Guide ListSoiled Receiving & Decontamination AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

-OR-

VS503 CC 1 WASHER/STERILIZER, SURGICAL INSTRUMENT,SINGLE DOOR, RECESSED THROUGH ONE WALL,(CHAMBER SIZE: 16" X 16" X 26"/3.8 CU. FT.), PROVIDESTEAM, WATER, COMPRESSED AIR, DRAIN, ELECTRICAND EXHAUST AS REQUIRED (PG-08-1 & PG-08-6, MCS11710)

VV 1 TABLE, TRANSFER, CRS, MOBILE FORWASHER/STERILIZER, WITH (CHAMBER SIZES: 16" X16" X 26")

VC 1 CLEANER, ULTRASONIC, WITH RINSER AND DRYER,TYPE DETERMINED ON INDIVIDUAL PROJECT BASIS

CC AR HOOD, EXHAUST, PROVIDE ONE HOOD OVER THEENTIRE WASHER AND LOADING DOOR (PG-08-1, MCS15822)

VV AR TABLE, WORK, PORTABLE, CORROSION RESISTINGSTEEL, 24" X 48" X 36"H

VV 2 2 1 CART, UTILITY, CORROSION RESISTING STEEL, 36"W X18"D X 30"H

P-418 CC 1 LAVATORY, STRAIGHT BACK, SENSOR CONTROL (PG-08-1, MCS 15450; H-08-4, SD 380)

P-505 CC 2 1 1 SINK, SERVICE, CLINIC, FLUSHING RIM, WALL HUNG(PG-08-1, MCS 15450; H-08-4, SD 379)

P-708 CC 1 EMERGENCY EYE AND FACE WASH, WALL MOUNTED,(PG-08-1, MCS 15450)

CC 1 2 1 1 DISPENSER, SOAP, WITH FOOT CONTROL, WALLMOUNTED OVER SINK (PG-08-1, MCS 10800)

VV 1 2 1 1 DISPENSER, BIFOLD PAPER TOWEL, SURFACEMOUNTED

VV 1 DRIER, TUBING, 120 VOLT, 20 AMP

VV 1 BULLETIN BOARD, APPROX., 1219 MM X 914 MM (48" X36")

CC AR STATION, SOILED RETURN FROM AUTOMATIC EJECTAT DOWN CONVEYOR (PG-08-1, MCS 14125)

P-802 CC AR HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED,CONCEALED SUPPLY PIPES (PG-08-1, MCS 15450; H-08-4, SD 4.2)

CC AR DRAIN, FLOOR (PG-08-1, MCS 15400)

NOTE: PROVIDE FLOOR DRAIN ONLY IN AREAHOUSING THE STERILIZERS AND NOT IN THERECEIVING-DECONTAMINATION AREA

Page 646: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-1

Equipment Guide ListSoiled Receiving & Decontamination AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

VV 7 5 3 RECEPTACLE, WASTE, WITH SWINGING TOP, 16" X 16"

CC 1 SPEAKER, WALL WITH VOLUME CONTROL,CONNECTED TO STATION RADIO SYSTEM (TO BEDETERMINED BY VETERANS HEALTH ADMINISTRATIONFOR EACH PROJECT WHEN THERE IS NOT ANEXISTING PUBLIC ADDRESS AND/OR RADIO SYSTEM)(PG-08-1, MCS 16771)

VS-508 CC AR WASHER/STERILIZER, AUTOMATED, PROVIDE STEAM,WATER, COMPRESSED AIR, MINERAL FREE-WATER,FLOOR DRAIN, ELECTRIC AND EXHAUST AS REQUIRED(PG-08-1 & PG-08-6, MCS 11710)

-OR-

VS-505 CC 2 2 1 WASHER/STERILIZER, SURGICAL INSTRUMENT,DOUBLE DOOR, RECESSED THROUGH ONE WALL,(CHAMBER SIZE: 16" X 16" X 26"/3.8 CU. FT.), PROVIDESTEAM, WATER, COMPRESSED AIR, DRAIN, ELECTRICAND EXHAUST AS REQUIRED (PG-08-1 & PG-08-6, MCS11710)

CC AR MODULAR WALL, ENCLOSURE PANELS, CRS, FROMFLOOR TO FINISHED CEILING, WITH EXHAUST LOUVERIN MODULAR PANEL ABOVE DOORS OF STERILIZERS(PG-08-1 & PG-08-6, MCS 11710)

CC AR RACK/BASKET RETURN, PASS-THRU, CONVEYOR ORFLOOR LEVEL, SPRING-LOADED BI-SWING DOORS (PG-08-1, MCS 11710)

CC AR CART, LOADING, FOR USE WITH PASS THRUSTERILIZERS, CHAMBER SIZES: 610 MM X 914 MM X1219 MM/1524 MM (24" X 36" X 48"/60") (PG-08-1, MCS11710)

CC AR CARRIAGE, TRANSFER, FOR USE WITH PASS-THRUSTERILIZERS, CHAMBER SIZES: 610 MM X 914 MM X1219 MM/1524 MM (24" X 36" X 48"/60") (PG-08-1, MCS11710)

VV 1 REAGENT GRADE OR MINERAL FREE WATER SYSTEM,SIZE AND TYPE DETERMINED ON INDIVIDUAL PROJECTBASIS

CC 1 OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-08-1, MCS 16111)

CC 1 MASTER STATION, FOR INTRASERVICE INTERCOM(PG-08-1, MCS 16760)

VV 1 CLOCK, BATTERY OPERATED

Page 647: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-1

Equipment Guide ListSoiled Receiving & Decontamination AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 15AMP, STRIP MOLD WITH OUTLETS, WIREDALTERNATELY ON SEPARATE CIRCUITS ON 610 MM(24") CENTERS ABOVE COUNTER (PG-08-1, MCS 16140;H-08-3, CS 801-3)

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP, 2 PER WALL, MINIMUM (PG-08-1, MCS 16140; H-08-3, CS 801-3)

SYMBOL AI QUANTITY DESCRIPTION

A B C D

AUTOMATIC CART WASHNOTE: VAPOR REMOVAL, DRYING CAPABILITIES ANDTILT RAMP.

CC AR GRATE, FLOOR, CRS, PROVIDE ON EXIT END OF CARTWASHER (PG-08-1, MCS 05500)

HW-546 CC AR NOTE: VAPOR REMOVAL, DRYING CAPABILITIES ANDTILT RAMP.

CC AR HOOD, EXHAUST, PROVIDE ONE HOOD OVER THEENTIRE WASHER AND LOADING DOOR (PG-08-1, MCS15822)

Page 648: VA guide -2009
Page 649: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-2

Design StandardsPreparation, Assembly & Sterilization Area

ARCHITECTURALCeiling AT (SP) Wainscot -

Ceiling Height 2700 (9'-0") Base QT

Wall Finish PL (SC) Floor Finish QT*

Notes: Slab Depression -

*EXTEND QT 10' BEYOND STERILIZERS

SPECIAL EQUIPMENT

ELECTRICALLighting PowerGeneral 50 FC - 3 W/SF General 1800 W RECEPTACLES

Special - Emergency -

Notes:

COMMUNICATIONSADP - Telephone -

Radio YES Intercom EMPTY CONDUIT

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling 50%

Dry Bulb Temp Heating F 72 Relative Humidity/Heating 30%

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure POSITIVE

Noise Criteria NC-40 AC Load - Equipment 0.4645.W/SM

Steam - Number of People 2

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES

Hot Water YES Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 650: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-2

Equipment Guide ListPreparation, Assembly & Sterilization AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

PREPARATION, ASSEMBLY AND STERILIZATION

NOTE: PROVIDE EMERGENCY POWER SYSTEM FOR THE STEAM AND ETO STERILIZERS,WASHER/STERILIZERS, ETO EXHAUST AND ETO MONITORING EQUIPMENT.

VV AR TABLE, WORK, PORTABLE, CORROSION RESISTINGSTEEL, 42"W X 72"L X 36"H

CC AR CABINET, WITH PLASTIC LAMINATE TOP, DRAWERSWITH ADJUSTABLE DIVIDERS (PG-08-1, MCS 12301)

P-418 CC 2 LAVATORY, STRAIGHT BACK, SENSOR CONTROL (PG-08-1, MCS 15450; H-08-4, SD 380)

CC 2 DISPENSER, SOAP, WALL MOUNTED WITH FOOTCONTROL (PG-08-1, MCS 10800)

VV 2 DISPENSER, PAPER TOWEL, SURFACE MOUNTED

VV AR RECEPTACLE, WASTE, WITH SWINGING TOP, 16" X 16"

VV 1 BULLETIN BOARD, APPROX., 1219 MM X 914 MM (48" X36")

VV AR STOOL, REVOLVING, APPROX., 330 MM (13") DIA. SEAT,495 MM (19-1/2") BASE

VV AR CART, WIRE, ADJUSTABLE SHELVES, 4 SWIVELCASTERS, 24"W X 72"L X 72"H

VV 1 CENTRIFUGE, LABORATORY, FOR THERMOMETERPREPARATION

VV 1 HAMPER, SOILED LINEN, WITH HINGED SELF CLOSINGTOP, 20" DIA.

VV AR HANDCART, WITH 2 REMOVABLE BASKETS, 38" X 24" X42-1/2"

CC 1 OUTLET, CENTRAL PAGING OR BROADCAST SYSTEM TOBE DETERMINED BY VHA FOR EACH PROJECT WHENTHERE IS NOT AN EXISTING PUBLIC ADDRESS AND/ORRADIO SYSTEM) (PG-08-1, MCS 16770)

VS-351 CC 2 3 AERATOR, ETHYLENE OXIDE, CABINET ENCLOSED,(CHAMBER SIZE: 24" X 36" X 48"/60"), PROVIDEELECTRIC AND EXHAUST AS REQUIRED (PG-08-1 & PG-08-6, MCS 11710)

-OR-

VC 1 AERATOR, FOR 100% ETHYLENE OXIDE GASSTERILIZER, SINGLE DOOR, RECESSED THROUGH ONEWALL OR FREE STANDING UNIT, FOR RECESSED UNITPROVIDE MOUNTING RACK, FOR FREE STANDING UNITPROVIDE STACKING RACK, PROVIDE ELECTRIC ANDEXHAUST AS REQUIRED

Page 651: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-2

Equipment Guide ListPreparation, Assembly & Sterilization AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

CC AR ENCLOSURE PLENUM, CRS, BETWEEN TOP OFAERATOR AND CEILING, PROVIDE EXHAUST LOUVER INPLENUM ENCLOSURE PANEL ABOVE DOOR (PG-08-1,MCS 11710)

VS-325 CC 2 STERILIZER/AERATOR, ETHYLENE OXIDE GAS, SINGLEDOOR, RECESSED THROUGH ONE OR TWO WALLS,(CHAMBER SIZE: 24" X 36" X 48"/24 CU. FT.), PROVIDESTEAM, WATER, DRAIN, ELECTRIC AND EXHAUST ASREQUIRED (PG-08-1 & PG-08-6, MCS 11710)

VC 2 STERILIZER/AERATOR, 100% ETHYLENE OXIDE GAS,SINGLE DOOR, RECESSED THROUGH ONE WALL ORFREE STANDING UNIT, FOR RECESSED UNITS PROVIDEMOUNTING RACK, FOR FREE STANDING UNIT PROVIDESTACKING RACK, PROVIDE COMPRESSED AIR,ELECTRIC AND EXHAUST AS REQUIRED

VS-360 CC AR ETHYLENE OXIDE DISPOSER SYSTEM, 838 MM X 889 MMX 2083 MM (33" X 35" X 82"), PROVIDE ELECTRIC ANDEXHAUST AS REQUIRED (PG-08-1 & PG-08-6, MCS 11710)

VV 1 CONTINUOUS MONITORING DEVICE, ETHYLENE OXIDEGAS WITH ADDITIONAL SENSORS/ALARMS, ETOSPECIFIC TO .01 PARTS-PER-MILLION

NOTE: PROVIDE ONE EMISSION CONTROL DEVICE FORNO MORE THAN TWO ETO STERILIZER

VS-203 CC 2 3 STERILIZER, MECHANICAL AIR REMOVAL, SINGLEDOOR, RECESSED THROUGH ONE WALL, CHAMBERSIZE: 610 MM X 1219 MM X 914 MM/ .68 M3, (24" X 36" X48"/24 CU. FT.) PROVIDE STEAM, WATER, COMPRESSEDAIR, DRAIN, ELECTRIC AND EXHAUST AS REQUIRED(PG-08-1 & PG-08-6, MCS 11710)

-OR-

VS-210 CC 2 3 STERILIZER, MECHANICAL AIR REMOVAL, DOUBLEDOOR, RECESSED THROUGH TWO WALLS, (CHAMBERSIZE: 24" X 36" X 48"/24 CU. FT.), PROVIDE STEAM,WATER, COMPRESSED AIR, DRAIN, ELECTRIC ANDEXHAUST AS REQUIRED (PG-08-1 & PG-08-6, MCS 11710)

-AND/OR-

VS-205 CC AR STERILIZER, MECHANICAL AIR REMOVAL, SINGLEDOOR, RECESSED THROUGH ONE WALL, CHAMBERSIZE: 610 MM X 914 MM X 1524 MM/.85 M3(24" X 36" X60"/30 CU. FT.), PROVIDE STEAM, WATER,COMPRESSED AIR, DRAIN, ELECTRIC AND EXHAUST ASREQUIRED (PG-08-1 & PG-08-6, MCS 11710)

-OR-

Page 652: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-2

Equipment Guide ListPreparation, Assembly & Sterilization AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

VS-211 CC AR STERILIZER, MECHANICAL AIR REMOVAL, DOUBLEDOOR, RECESSED THROUGH TWO WALLS, CHAMBERSIZE: 610 MM X 914 MM X 1524 MM/.85 M3(24" X 36" X60"/30 CU. FT.), PROVIDE STEAM, WATER,COMPRESSED AIR, DRAIN, ELECTRIC AND EXHAUST ASREQUIRED (PG-08-1 & PG-08-6, MCS 11710)

CC AR MODULAR WALL, ENCLOSURE PANELS, CRS, FROMFLOOR TO FINISHED CEILING, WITH EXHAUST LOUVERIN MODULAR PANEL ABOVE DOORS OF STERILIZERS(PG-08-1 & PG-08-6, MCS 11710)

CC AR CART, LOADING, FOR USE WITH AERATOR AND PASS-THROUGH/RECESSED STERILIZERS, CHAMBER SIZES:610 MM X 914 MM X 1219 MM/1524 MM (24" X 36" X48"/60") (PG-08-1, MCS 11710)

CC AR CARRIAGE, TRANSFER, FOR USE WITH AERATORS ANDPASS-THROUGH/RECESSED STERILIZERS, CHAMBERSIZES: 610 MM X 914 MM X 1219 MM/1524 MM (24" X 36"X 48"/60") (PG-08-1, MCS 11710)

VV 1 MESSAGE BOARD, PLASTIC LAMINATE, 914 MM X 610MM (36" X 24")

CC 1 OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-08-1, MCS 16111)

CC 1 MASTER STATION, FOR INTRASERVICE INTERCOM (PG-08-1, MCS 16760)

VV 1 CLOCK, BATTERY OPERATED

CC AR 8 7 6 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP(PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 653: VA guide -2009
Page 654: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-3

Design StandardsEtO Sterilizer/Aerator RoomARCHITECTURALCeiling PCP Wainscot -

Ceiling Height 2700 (9'-0") Base -

Wall Finish PRE-FAB PANEL Floor Finish C

Slab Depression -

SPECIAL EQUIPMENTVS-325: ETO STERILIZER

VS-360: ETO DISPOSER SYSTEM

ELECTRICALLighting PowerGeneral 50 FC - 3 W/SF* General ***

Special 30 FC-2 W/SF** Emergency ***

Notes: *LOBBY

**SERVICE AREA

***VS-325: POWER DOOR - 17A, 120V; CONTROL - 3A, 120V; VS-360: 40A, 208V, 3 PH

***VACUUM PUMP - 8A, 208V, 3 PH; RECEPTACLES: 800 W

COMMUNICATIONSADP - Telephone -

Radio - Intercom -

Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling -

Dry Bulb Temp Heating F 72 Relative Humidity/Heating -

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure NEGATIVE

Noise Criteria NC-40 AC Load - Equipment 2.0438 W/SM

Steam - Number of People 0

Notes: Special Exhaust YES****

****DEDICATED ETO EXHAUST SYSTEM PER HVAC DESIGN MANUAL

VS-360 WHERE REQ'D TO MEET STATE CODES

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES*****

Hot Water - Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other SHOP AIR****** Oxygen -

Notes: *****4" OSD FOR EACH STERILIZER

******FOR VS EQUIP

Page 655: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-3

Equipment Guide ListEtO Sterilizer/Aerator RoomEquipment Guide List for this area reprinted from 5-2 Preparation, Assembly & Sterilization Area.

SYMBOL AI QUANTITY DESCRIPTION

A B C D

NOTE: PROVIDE EMERGENCY POWER SYSTEM FOR THE ETO STERILIZER/AERATOR, ETO EXHAUST ANDETO MONITORING EQUIPMENT.

VC 1 AERATOR, FOR 100% ETHYLENE OXIDE GASSTERILIZER, SINGLE DOOR, RECESSED THROUGH ONEWALL OR FREE STANDING UNIT, FOR RECESSED UNITPROVIDE MOUNTING RACK, FOR FREE STANDING UNITPROVIDE STACKING RACK, PROVIDE ELECTRIC ANDEXHAUST AS REQUIRED

CC AR ENCLOSURE PLENUM, CRS, BETWEEN TOP OFAERATOR AND CEILING, PROVIDE EXHAUST LOUVER INPLENUM ENCLOSURE PANEL ABOVE DOOR (PG-08-1,MCS 11710)

VS-325 CC 2 STERILIZER/AERATOR, ETHYLENE OXIDE GAS, SINGLEDOOR, RECESSED THROUGH ONE OR TWO WALLS,(CHAMBER SIZE: 24" X 36" X 48"/24 CU. FT.), PROVIDESTEAM, WATER, DRAIN, ELECTRIC AND EXHAUST ASREQUIRED (PG-08-1 & PG-08-6, MCS 11710)

VC 2 STERILIZER/AERATOR, 100% ETHYLENE OXIDE GAS,SINGLE DOOR, RECESSED THROUGH ONE WALL ORFREE STANDING UNIT, FOR RECESSED UNITS PROVIDEMOUNTING RACK, FOR FREE STANDING UNIT PROVIDESTACKING RACK, PROVIDE COMPRESSED AIR,ELECTRIC AND EXHAUST AS REQUIRED

VS-360 CC AR ETHYLENE OXIDE DISPOSER SYSTEM, 838 MM X 889 MMX 2083 MM (33" X 35" X 82"), PROVIDE ELECTRIC ANDEXHAUST AS REQUIRED (PG-08-1 & PG-08-6, MCS 11710)

VV 1 CONTINUOUS MONITORING DEVICE, ETHYLENE OXIDEGAS WITH ADDITIONAL SENSORS/ALARMS, ETOSPECIFIC TO .01 PARTS-PER-MILLION

NOTE: PROVIDE ONE EMISSION CONTROL DEVICE FORNO MORE THAN TWO ETO STERILIZERS

CC AR MODULAR WALL, ENCLOSURE PANELS, CRS, FROMFLOOR TO FINISHED CEILING, WITH EXHAUST LOUVERIN MODULAR PANEL ABOVE DOORS OF STERILIZERS(PG-08-1 & PG-08-6, MCS 11710)

CC AR CART, LOADING, FOR USE WITH STERILIZER/AERATOR,CHAMBER SIZES: 610 MM X 914 MM X 1219 MM/1524 MM(24" X 36" X 48"/60") (PG-08-1, MCS 11710)

CC AR CARRIAGE, TRANSFER, FOR USE WITH STERILIZER/AERATOR, CHAMBER SIZES: 610 MM X 914 MM X 1219MM/1524 MM (24" X 36" X 48"/60") (PG-08-1, MCS 11710)

Page 656: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-3

Equipment Guide ListEtO Sterilizer/Aerator RoomEquipment Guide List for this area reprinted from 5-2 Preparation, Assembly & Sterilization Area.

SYMBOL AI QUANTITY DESCRIPTION

A B C D

CC AR 8 7 6 RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20 AMP(PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 657: VA guide -2009
Page 658: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-4

Design StandardsManual Equipment Wash Area

ARCHITECTURALCeiling PCP Wainscot -

Ceiling Height 2700 (9'-0") Base QT

Wall Finish CT* Floor Finish QT

Notes: Slab Depression -

*MOUNT CT ON CONCRETE BACKER BOARD

ELECTRICALLighting PowerGeneral 50 FC - 3 W/SF General 800 W RECEPTACLES

Special - Emergency -

COMMUNICATIONSADP - Telephone -

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F - Relative Humidity/Cooling -

Dry Bulb Temp Heating F - Relative Humidity/Heating -

Minimum % Outside Air - Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure NEGATIVE

Noise Criteria NC-40 AC Load - Equipment -

Steam YES Number of People 0

Notes: Special Exhaust YES**

**DEDICATED EXHAUST SYSTEM, SS CONSTRUCTION, FOR SATURATED WET EXHAUST AIR

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES***

Hot Water YES Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other SHOP AIR**** Oxygen -

Notes:

***DRAIN AT ROOM CENTER; SLOPE FLOOR AT 1/8" PER FT

****TO ROOM

Page 659: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-4

Equipment Guide ListManual Equipment Wash AreaSYMBOL AI QUANTITY DESCRIPTION

A B C D

MANUAL EQUIPMENT WASH

P-802 CC 1 HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED,CONCEALED SUPPLY PIPES (PG-08-1, MCS 15450; H-08-4, SD 4.2)

CC 1 CONNECTION, HOSE, STEAM (MECHANICAL DESIGNCRITERIA AND INSTRUCTIONS)

CC 1 CONNECTION, HOSE, SHOP AIR (PLUMBING DESIGNCRITERIA AND INSTRUCTIONS)

CC 1 DRAIN, FLOOR (PG-08-1, MCS 15400)

VV 1 GUN, STEAM PACKAGE, STEAM/WATER MODEL, WALLHUNG WITH DETERGENT TANK ANDDETERGENT/STEAM HOSES

P-505 CC 1 SINK, SERVICE, CLINIC, FLUSHING RIM, WALL HUNG(PG-08-1, MCS 15450; H-08-4, SD 379)

VV 1 TABLE, STAINLESS STEEL, 29"W X 60"L, WITH 4" HIGHBACKSPLASH

Page 660: VA guide -2009
Page 661: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-5

Design StandardsEquipment Storage & Testing Room

ARCHITECTURALCeiling AT (SP) Wainscot -

Ceiling Height 2700 (9'-0") Base RB

Wall Finish AT (SP) Floor Finish VCT

Notes: Slab Depression -

0.35 X STERILE/NONSTERILE STORAGE

MUST BE SITUATED CLOSE TO PREP AREA

SPECIAL EQUIPMENT

ELECTRICALLighting PowerGeneral 50 FC - 3 W/SF General 2000 W RECEPTACLES

Special - Emergency -

Notes:

COMMUNICATIONSADP - Telephone YES

Radio - Intercom -

Notes: Public Address -

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling 50%

Dry Bulb Temp Heating F 72 Relative Humidity/Heating 30%

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure (0)

Noise Criteria NC-40 AC Load - Equipment 0.0929 W/SM

Steam - Number of People 2

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water YES Sanitary Drain YES

Hot Water YES Reagent Grade Water -

Laboratory Air - Medical Air YES

Laboratory Vacuum - Medical Vacuum YES

Other - Oxygen YES

Notes:

Page 662: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-5

Equipment Guide ListEquipment Storage & Testing RoomSYMBOL AI QUANTITY DESCRIPTION

A B C D

EQUIPMENT STORAGE AND TESTING ROOM

CC AR PEGBOARD, HEAVY DUTY, WALL HUNG (FOR HANGINGBED RAILS, ORTHOPEDIC EQUIPMENT, ETC.) (PG-08-1,MCS 06200)

VV AR EQUIPMENT ASSEMBLY/INSPECTION STATION, WOOD,STORAGE DRAWERS, 762 MM X 1524 MM X 914 MM (30"X 60" X 36") WITH 203 MM (8") BACKSPLASH

CC 1 OUTLET, MEDICAL VACUUM (PG-08-1, MCS 15491

CC 1 OUTLET, OXYGEN, (PG-08-1, MCS 15491)

CC 1 OUTLET, MEDICAL AIR (PG-08-1, MCS 15491)

P-418 CC 1 LAVATORY, STRAIGHT BACK, SENSOR CONTROL (PG-08-1, MCS 15450; H-08-4, SD 380)

VV 1 DISPENSER, PAPER TOWEL, SURFACE MOUNTED

VV AR RECEPTACLE, WASTE, WITH SWINGING TOP, 16" X 16"

CC 1 DISPENSER, SOAP, WALL MOUNTED WITH FOOTCONTROL (PG-08-1, MCS 10800)

VV 1 DESK, SINGLE PEDESTAL, APPROX., 1219 MM X 762MM X 749 MM (48" X 30" X 29-1/2")

VV 1 CHAIR, ROTARY, WITHOUT ARMS

VV AR CABINET, STORAGE, SMALL PARTS

VV 1 CLOCK, BATTERY OPERATED

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 663: VA guide -2009
Page 664: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-6

Design StandardsDispatcher's Control Station

ARCHITECTURALCeiling AT Wainscot -

Ceiling Height 2700 (9'-0") Base RB

Wall Finish PL (SC) Floor Finish VCT

Notes: Slab Depression -

0.1 X STERILE/NONSTERILE STORAGE

SPECIAL EQUIPMENT

ELECTRICALLighting PowerGeneral 70 FC - 4 W/SF General 2000 W RECEPTACLES

Special - Emergency -

Notes:

COMMUNICATIONSADP - Telephone -

Radio - Intercom EMPTY CONDUIT

Notes: Public Address YES*

*CONNECT TO HOSPITAL SYSTEM

HEATING, VENTILATING AND AIR CONDITIONINGDry Bulb Temp Cooling F 76 Relative Humidity/Cooling 50%

Dry Bulb Temp Heating F 72 Relative Humidity/Heating 30%

Minimum % Outside Air 100 Minimum Air Changes/Hr 10

100% Exhaust Air YES Room Pressure (0)

Noise Criteria NC-40 AC Load - Equipment 2.2296 W/SM

Steam - Number of People 2

Notes: Special Exhaust -

PLUMBING AND MEDICAL GASESCold Water - Sanitary Drain -

Hot Water - Reagent Grade Water -

Laboratory Air - Medical Air -

Laboratory Vacuum - Medical Vacuum -

Other - Oxygen -

Notes:

Page 665: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Guide Plate 5-6

Equipment Guide ListDispatcher's Control StationSYMBOL AI QUANTITY DESCRIPTION

A B C D

DISPATCHER'S CONTROL STATION/OFFICE

VV 1 DESK, DOUBLE PEDESTAL, APPROX., 1524 MM X 762MM X 749 MM (60" X 30" X 29-1/2")

VV AR CHAIR, ROTARY, WITHOUT ARMS

VV 1 CHAIR, ROTARY, WITH ARMS

CC AR STATION, CLEAN TRANSPORT, SIZE AND TYPE TO BEDETERMINED FOR EACH PROJECT, COMPATIBLE WITHSOILED RETURN LIFT (PG-08-1, MCS 14125)

VV 1 BULLETIN BOARD, 40"W X 30"H

CC 1 OUTLET, CENTRAL PAGING OR BROADCAST SYSTEMTO BE DETERMINED BY VHA FOR EACH PROJECTWHEN THERE IS NOT AN EXISTING PUBLIC ADDRESSAND/OR RADIO SYSTEM) (PG-08-1, MCS 16770)

VV AR BOXES, TOTE FOR CONVEYOR SYSTEM

VV AR SHELVING, STORAGE, MOBILE, STEEL, ROD SHELF,OPEN STYLE WITH 5 ADJUSTABLE SHELVES

CC 1 OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM) (PG-08-1, MCS 16111)

CC 1 MASTER STATION, FOR INTRASERVICE INTERCOM(PG-08-1, MCS 16760)

VV 1 CRT, COMPUTER SYSTEM, WITH KEYBOARD

VV 1 PRINTER, COMPUTER SYSTEM

VV 1 STAND, COMPUTER PRINTER, APPROX., 610 MM X 610MM X 660 MM (24" X 24" X 26")

CC 1 RECEPTACLE, ELECTRICAL, QUADRAPLEX, FORCOMPUTER EQUIPMENT ITEMS (PG-08-1, MCS 16140;H-08-3, CS 866-1)

VV 1 CLOCK, BATTERY OPERATED

CC AR RECEPTACLE, ELECTRICAL, DUPLEX, 120 VOLT, 20AMP (PG-08-1, MCS 16140; H-08-3, CS 801-3)

Page 666: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Contents - Section 6

Section 6Satellite OutpatientClinic

Page

Recommended Space Criteria for SPD .......................................6 - 1

Page 667: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Page 6-1

Satellite Outpatient Clinic (SOPC)

Recommended Space Criteriafor SPD

Supply, Processing, and Distribution (SPD)is responsible for the processing and issuing ofmedical and surgical supplies and equipmentused in the delivery of patient care. An SPDsection may be required for a stand-alone SOPCthat operates as an off-site satellite facility that isadministratively attached to a VAMC. In somecases, depending on the distance and frequencyof supply deliveries, the VAMC may consider iteconomically sound to use the parent facility'sSPD rather than duplicating the function at theSOPC.

Soiled Receiving

• Decontamination Area: Minimum 18.6 NSM(200 NSF), 12.3 NSM (132 NSF) eachadditional sterilizers; Max. 46.5 NSM (500NSF) Space in this area is based on thenumber of sterilizers required to processreusable supplies and equipment. Theminimum of 18.6 NSM (200 NSF) providesspace for loading zone/access to 3 pass-through sterilizers (1 washer/ sterilizer/sanitizer, 1 steam, and 1 ethylene oxide[EtO] sterilizer) and 1 ultrasonic washer andsink.

• Manual Equipment Wash: 7.4 NSM (80NSF) This room is used to decontaminatecarts and equipment used in delivery ofpatient care.

• Housekeeping Aids Closet: 3.7 NSM (40NSF) For safety reasons this HAC will beused only for the decontamination area.

• Locker, Toilet, Shower: 7.4 NSM (80 NSF).Space provided will accommodate twolockers and a bench (2.3 NSM, 25 NSF),toilet with lavatory and water closet (2.8NSM, 30 NSF), and a shower at 2.3 NSM

(25 NSF). This area is to be used bypersonnel assigned to the Soiled Receivingand Decontamination Area.

Clean Areas

• Preparation Area: Minimum 18.6 NSM (200NSF), Add 12.3 NSM (132 NSF) for eachadditional sterilizer, Maximum 46.5 NSM(500 NSF) As in the decontamination area,space is based on the number of sterilizersneeded to process reusable supplies andequipment. The minimum of 18.6 NSM (200NSF), will provide space for loadingzone/access to 3 pass-through sterilizers (1washer/ sterilizer/ sanitizer, 1 steam, andone EtO gas sterilizer) and an ultrasonicwasher and sink.

• Ethylene Oxide Gas Cylinder Storage: 2.8NSM (30 NSF) If all 100% EtO sterilizers(which use a cartridge), are to be used,space for cylinder storage is unnecessary.

• Sterile/Clean Storage Area: Minimum 22.3NSM (240 NSF) Maximum 46.5 NSM (500NSF) Total annual SOPC visits (notincluding psychiatric visits) x .0035 + 200

• Clean Receiving and Bulk Storage Area: 7.4NSM (80 NSF) This space is provided forreceipt, breakdown, and temporary holdingof bulk sterile/clean supplies.

• Dispatch Area: The issuing and control ofmedical-surgical supplies and equipment isaccomplished in this area. A visual register(quantity and location) of issued suppliesand equipment is maintained in theDispatcher's Control Station/Office. Spacefor this area should be computed as follows:

A) Sterile/Clean Area x 0.1

PLUS

B) Dispatcher's Control Station/Office: 6.5NSM (70 NSF)

Page 668: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Page 6-2

PLUS (Include only if they will use computerizeddata handling equipment)

C) Work Station: 7.8 NSM (84 NSF) Thisenclosed area will accommodate thecomputerize data handling equipment andpersonnel. A running inventory of allsupplies entering and leaving SPD and theinitiation of the reordering process will beaccomplished at this work station.

• Equipment Storage and Testing Room:Maximum 7.4 NSM (80 NSF) Equipment,after decontamination, is tested and storedin this room. This equipment is used forpatient care and is assigned and stored inSPD as opposed to equipment used inpatient care that is permanently assigned toother areas. This area will also,accommodate SPD and Surgical case carts.

• Housekeeping Aids Closet: 3.7 NSM (40NSF) A separate HAC for the clean area isnot needed if another one (in addition to theone in the decontamination area) is locatedin the immediate area.

Page 669: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Contents - Section 7

Section 7Miscellaneous

Page

Glossary of Terms.............................7 - 1

Example Layout for SPD...................7 - 3

Page 670: VA guide -2009

September 30, 1994

VA Design Guide — Supply, Processing, & Distribution Page 7-1

GLOSSARY OF TERMS

AERATOR: A machine designed to speed up theremoval of EtO residues from sterilizeditems by subjecting them to warm,circulating air.

BIOBURDEN: The number and types of viablemicroorganisms with which an item iscontaminated. When measured, bioburdenis expressed as the total count of bacterialand fungi colony-forming units per singleitem.

CENTRAL SERVICE: A department in thehospital that provides supplies andequipment to patients and medical staff.Another name for SPD.

CLEANING: The physical removal of debris. Ithas two major effects. First, it results in areduction in the number of microorganismspresent. Second, it removes organic matter,such as blood and tissue, and other debris,which may interfere with sterilization ordisinfection.

DECONTAMINATION: The process of renderingcontaminated items safe for handling.

DISINFECTION: A process that destroys mostforms of microorganisms on inanimatesurfaces. The three levels of disinfectionare high-level, intermediate-level and low-level.

ETHYLENE OXIDE GAS STERILIZER (EtO):Sterilization at relatively low temperaturespossible with ethylene oxide gas. Using aheated unit at 49C (120F), sterilization canbe achieved in 2 - 3 hours.

PRIMARY STOCK: Medical supplies storedwithin the confines of the SPD Department

SECONDARY STOCK: Medical supplies storedin user areas such as wards, clinics, nursingcare units, and intensive care units.

STERILIZATION: The process which destroysall types and forms of microorganisms,including viruses, bacteria, fungi, andbacterial endospores.

Page 671: VA guide -2009
Page 672: VA guide -2009

First Draft 4-15-97

VA DESIGN GUIDETUBERCULOSIS PRIMER CONTENTS - SECTION 4

Section 4Enclosures

Enclosure Title

Program & Facility Planning Guidance for TBPrograms ................................................ Encl 1

Standard Technical Summaries............... Encl 2

Page 673: VA guide -2009

1

Department of Veterans AffairsVeterans Health Administration

Program and Facility Planning Guidancefor Tuberculosis Programs

August 18, 1995

OVERVIEW

Over the last several years, the issue of tuberculosis (TB) has been prominent in both the medicalliterature and the national press. This has been emphasized in the last year coincident with an increasedpubic awareness of emerging and re-emerging pathogens on the national and global level. Finally, andafter much work, the actual number of new cases of active tuberculosis disease is decreasing nationallywith the most notable decrease in the New York area. However, the TB epidemic continues particularlyalong the coast of the United States. No section of the country has been completely spared, however, ascases of tuberculosis have been identified in all VHA Regions.

To effectively plan and implement a tuberculosis program facilities must obtain information on currentand projected TB workload, evaluate and define missions related to TE, and develop integrated plans forpatient care, employee healtf4.and enhance facility controls. This TB program guidance will provide aconsistent framework for such VA TB program planning,

This planning document is organized in a format that prioritizes overall guidance for TB control based onclinical and epidemiologic priorities. It specifies infection control practices and regulatory requirements,while incorporating work practice controls, engineering, controls, and personal protective equipment intothe overall guidance. This is not designed to be a regulatory compliance document, but rather tointegrate the various components of tuberculosis control strategies into the medical facility culture.

CHARACTERISTICS OF A TB PROGRAM

I. Assign Responsibility

While all programs within VA Medical Centers are the ultimate responsibility of the Medical CenterDirector, it is appropriate to assign the responsibility for the tuberculosis program to a specific qualifiedperson or group of people within the facility. Each facility is to have a coherent, practical andimplementable program. Then the program must be implemented, monitored, and evaluated. Theprogram will also ensure that a mechanism will be established to identify responsible parties. forcomponents of the program, establish the program structure, and define the hierarchy of responsibilityfrom TB program officials to the facility Director. Included in this group should be representation fromInfection Control, Medical Staff (Infectious Diseases and Pulmonary Medicine if available), Nursing,Occupational Health, Safety/Industrial Hygiene, and Engineering, thus assuring the availability ofexpertise in all areas of TB control as well as ownership of the program through a multidisciplinary inputprocess.

Page 674: VA guide -2009

2

II. Risk Assessment, Tuberculosis Plan and Periodic Reassessment

An initial facility risk assessment must be undertaken. This includes gathering data regarding thefollowing: tuberculosis in the community, tuberculosis within the facility, skin test conversions within thefacility, and other evidence, if any, of person-to-person transmission of TB within the local health caresetting. A specific level of risk can be assigned for purposes of planning and monitoring or evaluating'intervention strategies to be incorporated into the written facility tuberculosis plan. The plan shouldinclude all components of the tuberculosis control strategies for the facility in a format that is concise yetcomprehensive. It should be located in a single document or group of documents that are easilyaccessible by hospital employees. Fragmentation of the tuberculosis control plan with multiple non-centralized documents should be avoided.

This risk assessment will need to be redefined at intervals appropriate to the risk- of transmission oftuberculosis as defined by disease/infection prevalence in the community and the facility. Specifically,changes in case rates for the facility or the community, clusters of skin test conversions, or other evidencesuspicious for facility TB mission will necessitate immediate reevaluation of the facility risk. The repeatrisk assessment should also include evaluation of the effectiveness of the extant, local methodologies forprevention of TB transmission.

III. Identification, Evaluation, and Treatment of Patients with Tuberculosis

The most important factors in preventing transmission of Mycobacterium tuberculosis are the earlyidentification of patients who may have infectious TB, prompt implementation of TB precautions for suchpatients, and prompt initiation of effective treatment for those who are likely to have TB.

For patients presenting to the health care facility for care, screening for signs and symptoms of TB shouldbe done in the initial triage locale. The detail and extent of this screening process should be determinedbased on the facility risk category. An example of a suitable screening methodology would bequestioning the patient regarding cough lasting greater than three weeks, weight loss, night-sweats andmalaise. A facility should individualize its screening methodology in the most appropriate manner for itsown risk stratum based on perceived risk to other patients and employees. As patients present for care inhigh or moderate risk areas, the issue of initial triage is extremely critical. Consideration should be givento speed of triage, traffic patterns as patients move about in admissions area, clinic assignments, and riskto employees performing administrative functions. Any triage system must be designed to preventpatients with suspected or known infectious tuberculosis (S/KI TB) from moving about the facility in anunprotected manner.

Tuberculin skin testing for high risk patients (methodology to meet most current CDC Guidelines) isdesigned to identify patients who are infected with Mycobacterium tuberculosis before they developsymptoms (cough, fever, sweats, weight loss) of active disease and become infectious.

For long-term care facilities, screening prior to admission should include PPD testing (following mostrecent CDC and VA guidance) and/or chest x-ray as appropriate (routine screening chest x-rays shouldonly be implemented based on local risk assessment), and include a focused physical examina6on. Inhigh or moderate risk areas this should be done prior to admission to the long-term care facility. Inminimal or low risk areas, this screening may be completed within 72 hours of admission if adequatetriage is accomplished.

Page 675: VA guide -2009

3

A. Patient Masks

When any patients are identified as having S/KI TB, they should wear a surgical mask and be placed inrooms meeting identified engineering controls 'or S/KI TE patients as noted later in this document.

B. Tuberculin Skin Test (TST) for High Risk Patients

Screening for high risk individuals must be a hospital-wide policy. This includes, but is not limited to,timely ongoing screening of HIV-positive patients, dialysis patients, the homeless, substance abusepatients and patients in other high risk special programs such as Hospital Based Home Care (HBHC) andothers as identified by the facility. All these screening programs should use the most current CDC-defined methodology for TST. If a patient has signs or symptoms suggestive of tuberculosis disease, afull evaluation must be conducted.

C. Laboratory Assessment

It is critical to expedite the evaluation and treatment of patients with S/KI TB. This includes access tocurrent laboratory technology for acid fast bacteria (AFB) smears, cultures, and susceptibility testing.

1. AFB smears, the following is necessary:

a. Available five days per week and reported within 24 hours of specimen receiptb. Consideration should be given to seven days per week for areas with a high

incidence of TBc. One sputum per patient per day should be sufficient

2. Cultures for Mycobacterium tuberculosis, the following is needed:

a. Available five days per weekb. Rapid identification methodology

Smears and culture results should be reported immediately to designated person(s). This must include thecare provider and should be reported to the Infection control function.

3. Susceptibility testing for Mycobacterium tuberculosis, the following, is appropriate:

a. First isolateb. Additional isolates if:

(1) failure to convert cultures within three months of beginning therapy(2) clinical evidence of failure to respond to therapy(3) other specific circumstances may dictate additional susceptibility testing.

It is not required that all of these activities be done on station. It is the facility’s responsibility to assurethat rapid, current diagnostic laboratory testing for Mycobacterium tuberculosis is readily available tothe clinicians. The guidance above should be used as a basis for individual station decision-makingregarding specific time frames and location for each of the studies noted above based on patient careneeds. These decisions should be documented in writing in the facility tuberculosis control plan to ensurefacility-wide consensus by the process stakeholders on these critical clinical testing issues.

Page 676: VA guide -2009

4

D. Patient Management

If the patient has been identified as having active tuberculosis disease, initiation of therapy shouldbe prompt using the most current CDC guidelines.

After a patient has been identified as having S/KI TB, the patient should be placed in a room meeting theengineering control guidelines noted below in this document. Enablers may be necessary to assure thatthe patient remains in this controlled environment, since patients cannot be allowed to wander about thehospital in an unprotected manner. Enablers, such a-s television sets, telephones, bathing facilities, andrecreational activities may be important to maintain these precautionary measures. In order to maintainproper directional air flow in the rooms, the doors must remain closed. If the patient must be out of theroom for clinical purposes, the patient should wear a surgical mask and administrative arrangementsmade to expedite the return of the patient to the negative pressure room. Discharge and follow-upplanning should be initiated as soon as possible in order to assure seamless transition between the hospitalsetting and outpatient care. This will likely involve the VHA outpatient clinic system and thegovernmental health department from which the patient may receive follow-up. As part of this process,immediate reporting of tuberculosis patients to the health department consistent with VA rules andregulations is necessary.

E. Visitors

Visitors to patients who have S/KI TB should be given respirators to wear while in the isolation rooms,and they should be given general instructions on how to use their respirators (CDC Guidelines MMWR,October 28, 1994, Vol. 43, No.RR- 13, p28).

F. Discontinuation of AFB Precautions

The following criteria must be used for discontinuing precautions for patients in the Medical Center withS/KI TB:

1. The patient is found not to have tuberculosis or

2. The patient is on appropriate therapy; (it should be noted that appropriate therapyneeds to be defined at the local level based on community incidence of multi-drugresistant tuberculosis, tuberculosis susceptibility testing of facility isolates, and thespecific known susceptibilities of the patient's organism) and A positive clinicalresponse to therapy and Three consecutive negative A.FB smears collected on separatedays

IV. Engineering Controls

A. General Guidelines

The CDC guidelines are the minimum acceptable level, and should be increased where required to satisfyother mandated criteria or engineering requirements. Where current VA criteria exceed the CDCguidance, the use of VA criteria is recommended. However, if existing configuration or cost do not allowcompliance to more stringent VA criteria, then the CDC guidance is the minimum acceptable.

Page 677: VA guide -2009

5

1. Six total air changes per hour are likely to reduce the concentration of bacteria the room. Forthe purposes of reducing the concentration of droplet nuclei, TB bedrooms and treatment rooms inexisting health care facilities should have an airflow of greater than or equal to six air changes per hour.Where feasible, this airflow rate should be increased to greater than or equal to 12 air changes per hour.New construction or renovation of existing health care facilities should be designed so that TB bedroomsachieve an airflow of greater than or equal to 12 air changes per hour.

2. Air from TB bedrooms and treatment rooms for S@ TB patients should be exhausted to theoutside. The air should be exhausted in a manner and location so that it is not pulled into intake louversor windows without significant dilution. At a minimum, the exhaust shall be 25 feet from any air intake.However, other factors, such as wind direction, wind velocity, stack effect, system sizes, and height ofbuildings must be evaluated and location of intake and exhaust outlets adjusted as required. If, in someinstances, recirculation of air into the general ventilation system from such rooms is unavoidable, high-efficiency particulate air (HEPA) filters should be installed in the exhaust leading from the room to thegeneral ventilation system. Air from TB bedrooms and treatment rooms in new or renovated facilitiesshould not be recirculated into the general ventilation system.

3. Exhaust air quantity must be 10% greater than the supply air. It is further recommended thatthe exhaust system should serve only the TB rooms and not be part of the general exhaust system. If thisis not practical, then use of the general exhaust system is acceptable provided appropriate precautions aretaken to assure that these systems are adequately designed, installed, balanced and maintained. Theserequirements result in providing additional outside air through the air handling system which then impactsheating and cooling capacities for both air side and primary equipment. In all applications, thermal loadcalculations or occupancy of the space may require a higher air change rate.

4. Rooms should be under negative pressure with respect to adjacent areas when occupied by apatient with SIKI TB.

5. Anterooms are not necessary for SIKI TB patient bedrooms.

6. The direction of the air-flow for TB rooms shall be monitored daily when an S/KI TB patientis occupying the room. When not in use by S/KI TB patients, the directional allow will be checkedmonthly. The method of testing for directional airflow in the S/KI TB rooms is at the discretion of thefacility, but must be of an acceptable standard. This would include such methodologies as smoke tubetesting or an airflow gauge.

7. The number of air changes per hour in these rooms should be checked yearly at aminimum. This may need to be more frequent based on facility risk assessment and recommendations ofthe Environmental and Infection Control Committee. In addition, the number of air chances per hourshould be checked after any maintenance to the airflow system.

8. In rooms where patient turnover is expected, use CDC guidelines ( MMWR, October28,1994,Vol.43,No.RR-13) for airchanges per hour to determine time required for removal of airbornecontaminants before the next patient occupies the room vacated by a patient with S/KI TB.

Page 678: VA guide -2009

6

9. When in use by SIKI TB patients, doors in negative pressure rooms must remain closed,except for entering or exiting the room. Proper airflow and pressure differentials between areas aredifficult to control because of open doors, movement of patients and staff, temperature, and the effect ofvertical openings. Air pressure differentials can only be maintained in completely closed rooms. An opendoor reduces or eliminates the desired effect of negative pressure rooms. Whether windows are needed indoors to S/KI TB patient bedrooms is a local decision.

10. Medical Centers and outpatient clinics should consider providing emergency power toexhaust systems serving inpatient TB rooms and to some of the ambulatory care rooms designated formanagement of S/KI TB patients. The potential risks to patients and staff, available emergency powersystem capacity, and relative priority of other functions covered by emergency power should be carefullyevaluated when considering costly emergency power system emergency expansion.

B. Medical, Surgical, and Neurological (MS&M) Nursing Acute Care Units

To determine the number- of TB rooms, use the following formulae to determine number of patientbedrooms for cases of S/KI TB:

1. Current need: (Identify the maximum number of patients requiring respiratory precautionsfor S/KI TB at any one time within the past 12 months,) x (change in incidence of TB in community overthe past year).

2. Projected Need: Using the estimated change in the population in the facility, DistributedPopulation Planning Base (DPPB) for any Future year, calculate future needs based on current estimateas determined above multiplied by this population change ratio.

EXAMPLE 1 - All specific numbers are for illustrative purposes only.

15.0 - Maximum number of patients requiring AFB precautions at one time (e.g., 15)

x 1. 05 - Change in community incidence (this represents a 5% increase in community incidence)

15.75 - Need for TB beds based on changes in TB incidence in community

x 10.85 - Correct for future anticipated changes in veteran population (this represents a 15% decrease in expected veteran population)

13.38 - Projected no. of AFB precaution beds needed corrected for calculated changes in veteran population and community incidence

C. Nursing Unit Organization

1. High Incidence Area or Referral Center:

Medical Centers with sufficient workload or those assigned the mission of referral center may choose toconcentrate all TB bedrooms on an existing MS&N nursing unit designated for TB inpatient care. Or,they may designate bedrooms to be used for TB care throughout their facility. In establishing groups ofTB bedrooms on an MS&N nursing unit, a Medical Center should renovate a contiguous sub-set of thebedrooms on the unit to meet HVAC and bathroom requirements; not necessarily the entire ward. The

Page 679: VA guide -2009

7

number of bedrooms included in the sub-set would be based on anticipated workload determined for thatfacility. The following facility requirements must be met:

a. All one-bed rooms designated for TB must meet CDC guidelines for S/KI TB

b. Each one-bed room must have a private bathroom and should have a shower wherepossible. Safe shower facilities are to be available, however, if the bedroom for S/KI TB . patients doesnot offer these facilities

c. Anterooms are not required for the negative pressure rooms designated for S/KI TB

d. For S/KI TB patients, examination/treatment rooms and any other special treatmentrooms where sputum induction, aerosol treatments and/or cough or aerosol-generating procedures areperformed should meet CDC requirements for infectious TB with the additional requirement of 12 orgreater air changes per hour. Ultraviolet germicidal irradiation (UVGI) may be used as an enhancementto the recommended engineering controls.

2. Low Incidence Areas

For those facilities anticipating a low S/KI TB workload, little or no chance to existing nursing units-maybe required. Existing VA space planning criteria for MS&N nursing units (see Planning Criteria for VAFacilities, Handbook 7610 Chapter 100.04) requires two isolation suites per nursing unit. These roomswill be capable of providing negative or positive pressure and have an anteroom and attached privatebathroom. Minimum air changes are 8 per hour with 100% outside exhaust through a HEPA filter. Ifthese rooms are not currently provided or if additional rooms are needed for S/KI TB patients then theseadditional rooms must meet CDC guidance for S/KI TB and have a private bathroom. An existing 2-bedroom which has appropriate ventilation airflow and bathroom facilities meeting, at a minimum, currentCDC guidance for S/KI TB, may be scheduled for use by a single TB patient as a low cost alternative toconstructing or renovating an additional 1-bed room.

Sputum induction, aerosol treatments and/or cough or aerosol-generating procedures should be performedeither in TB bedrooms or other rooms that meet CDC guidance for S/KI T'B.

D. MH&BS Nursing Units (Mental Health and Behavioral Sciences)

In general, no rooms should be required for S/KI TB patients as they should be transferred to anappropriate MS&N nursing unit for diagnosis and treatment as needed until they are no longer infectious.

E. Intensive Care Units (ICUs)

1. Existing ICUs should meet cur-rent VHA space planning criteria (see Planning Criteria forVA Facilities, Handbook 7610 Chapter 102.05) for the number of isolation suites and at a minimum meetCDC criteria for ventilation for S/KI TB.

2. All ICUs which utilize return air systems shall have the return air HEPA filtered.Installation of ultraviolet (UV) lamps may be considered in ICUs which there is a high risk for TBtransmission. All ICU rooms housing S/KI TB patients must, at a minimum, meet the current CDCguidance for S/KI TB.

Page 680: VA guide -2009

8

F. Post Anesthesia Recovery Units (PARUs)

Medical Centers should have at le one recovery room within the PARU meeting at a minimum CDCventilation criteria for S/KI TB. As an option, especially in low-incidence areas, Medical Centers mayrecover surgical patients with S/KI TB in an ICU isolation suite or room that meets CDC guidance forS/KI TB.

G. Surgical Suite (See MMWR, October 28, 1994, Vol. 43, No. RR- 13, p. 50-51 for details)

1. Existing VHA facility criteria (see HVAC Design Manual) and standards for surgery areappropriate for surgical care of S/KI TB patients. Current VHA criteria exceed the CDC guidelines.Typically, no changes will be required unless return air is used in the OR. VA criteria have notsanctioned the use of return air in ORs for many years.

2. Traffic patterns should be designed to reduce unnecessary movement throughout thesurgical suite, hallways and other associated areas when surgery on a patient with S/KI TB is performed.

3. Appropriate scheduling and other controls are necessary for surgery on S/KI TB patientssince positive pressure allow is used in operating rooms.

H. Long Term Care

In general, no rooms are required for S/KI TB patients as they should be transferred to an appropriateMS&N nursing unit for diagnosis and treatment as needed until they are no longer infectious.

I. Ambulatory Care

1. Determining the Number of TB Rooms:

Determining the number of TB rooms 'in the Ambulatory Care setting should be in alignment with thefacility risk assessment. Specifically, facilities in the lowest risk assessment category may not needrooms with specific tuberculosis engineering controls at all, but rather a written plan for dealing with thepossible event of a S/KI TB patient reaching the facility. For facilities above the minimal risk category,the following is a suggested method for determining the number of exam/treatment or special treatmentrooms designated for S/KI TB patients in unscheduled ambulatory care areas (hospital-based, satellite,and independent OPCs):

a. Obtain the estimated eligible veteran population for the facility from DPPB for anyspecified future year and the current eligible veteran population for the facility.

b. Each facility should generate the estimated number of potential unscheduled S/KI TBpatient visits per year.

Page 681: VA guide -2009

9

c. Calculate the projected number of potential unscheduled S/KI TB Patient visits peryear using the following formula:

A = Estimated eligible veteran population for the facility from the DPPB for any specified future year

B = Current eligible veteran population for the facility from DPPBC = Current number of potential unscheduled S/KI TB patient visits

D = Projected potential unscheduled S/KI TB patient visits per year

(A ÷ B)x C = D

EXAMPLE 2 - All specific numbers are for illustrative purposes only.

(A)400,000 - Estimated population for a future year (e.g., 400,000 for the year 2000)

(B)÷ 450,000 - Current veteran population )e.g., 450,000)

÷ 0.88 - Result of A B

(C)480 = Current number of unscheduled S/KI TB patient visits per year (e.g., year 2000)

(D)422.4 - Results of A B x C which is the estimated number of unscheduled visits of S/KI

TB patients for future year (e.g., year 2000)

d. Provide the number of designated TB exam/treatment or special procedure rooms asdetermined below using the potential SIM TB patient visit estimated generated in 1. I.c. above.

CALCULATED POTENTIAL UINSCHEDULEDS/KI TB PATIENTS VISITS (PER YEAR)

DESIGNATED TB EXAM/TREATMENTROOMS

500 OR LESS Use emergency area isolation room

501-1000 One additional TB room

Each additional 1000 One additional room

Designated TB rooms determined above may be located in the walk-in clinic module and/or in othermodules to meet local operating procedures and needs.

Page 682: VA guide -2009

10

2. Facility/air:

a. Meet at a minimum current CDC guidelines for unscheduled areas and high riskclinics.

b. Meet a minimum current CDC guidelines for ventilation and airflow for S/KI TB:

(1) Emergency area Isolation room(s) (anteroom not required)

(2) ENT room(s)

(3) Aerosolized pentamidine room(s)

(4) Designated exam/treatment/procedure room(s)

3. Unscheduled areas

All unscheduled ambulatory care areas and associated waiting- areas should have ventilation designedand maintained to reduce the risk of tuberculosis transmission. Germicidal UV lamps and/or HEPAfilters may provide additional benefit when used to supplement ventilation, particularly in facilitieslocated in areas of high incidence for TB.

4. Scheduled areas (clinics)

All scheduled areas serving patients who are at high risk for TB transmission should be designed toreduce the risk of TB transmission. Air from clinics serving patients at high risk for TB should not be re-circulated unless it is first passed through an effective high-efficiency filtration system (HEPA filters arecurrently the effective high-efficiency filtration system available).

5. Designated exam/treatment rooms for S/KI TB

VHA ambulatory care programs in Medical Centers and in satellite/independent outpatient clinic musthave some facilities that are adequate to deal with S/KI TB patients. These TB rooms can beexam/treatment rooms and/or special procedures rooms that are designated for use with S/KI TB patients.These rooms should meet CDC guidance for S/KI TB with the additional requirement that a minimum of12 air changes per hour must be exhausted (See IV.A.2). These rooms would normally be located 'm ornear the walk-in clinic module.

J. High Risk Areas

1. Potential Aerosol Producing Procedure Areas:

a. The pulmonary function laboratory (including spirometry and exercise rooms),bronchoscopy area(s), pulmonary function treatment rooms, and sputum induction areas and any otherspecial procedure room (e.g., ENT) in which cough inducing procedures are done on patients who mayhave infectious TB must meet CDC guidelines for S/KI TB with the additional requirement that aminimum of 12 air changes per hour must be exhausted. Additionally, airflow rates should be calculatedon expected patient turnover in these treatment areas based on the most recent CDC guidance.

Page 683: VA guide -2009

11

b. Any room (e.g. examination/treatment room procedure room) in the health care facilityin which aerosolized pentamidine (AP) procedures are performed on patients who may have infectious TBmust meet CDC guidelines for infectious TE with the additional requirement that a minimum of 12 airchanges per hour must be exhausted (See IV .A-2). Additionally, airflow rates should be calculated onexpected patient turnover in these treatment areas based on the most recent CDC guidance. If a booth orother containment entity is used for any potential aerosol producing procedure, booth airflow and exhaustshould meet CDC guidelines.

K. Radiology

At least one radiology room with chest x-ray capabilities should meet CDC guidance for S/KI TB. Bothambulatory care and in-patient programs can share this negative pressure radiology room if feasible.This specialized room with these engineering controls may not be necessary in facilities in the minimalrisk category.

L. Anatomic Pathology:

The morgue must meet at a minimum CDC guidance for infectious TB and follow current VA criteriawith a minimum of 12 air changes per hour with 100% exhaust to the outside through a HEPA filter.

M. Dental

At referral centers and at facilities in which emergency dental care is provided, at least one dentaloperators should meet CDC guidance for S/KI TB. Other health care Facilities may send S/KI TBpatients for dental. care to referral centers based on workload and travel distance.

N. HIV-related Issues

No, specific heating, ventilation and air conditioning (HVAC) considerations are necessary for patientswith HIV infection.

O. Dialysis Program

A room which meets at a minimum current CDC ventilation and airflow guidelines for S/KI TB must beavailable for dialysis of S/KI TB patients. The location of this area is at the discretion of the facility.Based on local need this area may be in the dialysis unit or ICU, or other area in the Medical Centerbased on patient need and efficient use of resources.

V. Respiratory Protection

A. General Criteria

Performance criteria for respiratory protective devices as outlined in the most recent CDC guidance are tobe met. This requires a respiratory protection program that follows the regulatory requirements of theOccupational Safety and Health Administration (OSHA) as well as American National StandardsInstitute (AINSI) Standards.

Page 684: VA guide -2009

12

B. Respiratory Protective Devices

Respiratory protection is required for persons entering rooms in which patients with S/KI TB are beinghoused, for persons present during cough-inducing, aerosol-generating procedures performed on suchpatients, and for persons in other settings where administrative and engineering controls are not likely toprotect them from inhaling, infectious airborne droplet nuclei. These other settings include transportingpatients who may have S/KI TB in emergency transport vehicles, and providing urgent surgical or dentalcare to pa6ents who have S/KI TB before determination has been made that the patient is non-infectious.These settings may also include home based health care programs, where patients with S/KI TB are beingseen in the home setting.

In the Mycobacteriology Laboratory, routine use of respiratory protective devices should not benecessary. However, if the laboratorian is working with significantly amplified Mycobacteriurntuberculosis cultures in liquid media, or performing specific procedures where aerosolization is expected,the use of respiratory protective equipment, gloves and gowns may be appropriate. The most recentstandards for laboratory practices should be followed.

VI. Healthcare Worker Training

All health care workers are to receive periodic TB education appropriate for their work responsibilitiesand duties and should include epiderniology of TB in the facility, mode of transmission, pathogenesis,diagnosis, and occupational risk for tuberculosis. The training should also describe work practices thatreduce the likelihood of transmitting Mycobacterium tuberculosis in the healthcare setting. The trainingmust be given to all those who work at the VA Medical Center who are at risk for the transmission oftuberculosis. All training is to follow the latest written regulatory requirements of valid oversight bodiessuch as OSHA.

VII. Healthcare Worker Counseling And Screening

All healthcare workers should be counseled regarding tuberculosis disease and tuberculosis infection.This should include information about the increased risk to immunocompromised persons for developingactive tuberculosis disease.

VIU. Personnel Health

A. TB Screening using most current CDC methodology

1. Prior to employment, TST results are required for covered employees who work in theVHA- For any TST done outside the Personnel Health Unit on station, appropriate written documentationmust be provided as detained by the Personnel Health Physician.

2. Interval TST screening as detained by risk assessment as outlined in the most recent CDCguidance should be conducted.

3. TST is recommended at the time of separation for all employees

4. Follow all pertinent VACO Directives and Manual references related to TB screening

Page 685: VA guide -2009

13

B. Record keeping

1. Record keeping is critical for the long term needs of the employee, station, and regulatorycompliance

2. Record keeping to comply with VHA directives, manuals, and valid regulatory agencies'requirements

C. Return to work clearance for health care workers with S/KI TB

1. At a minimum, return to work clearance should follow current CDC guidelines

2. Employees must be monitored for lack of infectiousness

D. Healthcare Worker TST Conversions

The facility must track and evaluate TST conversions in order to document possible episodes oftransmission of tuberculosis in the healthcare setting, to define the facility risk assessment category and toidentify facility TST conversion rates.

IX. Coordination with Health Department

It is critical that VA facilities coordinate all phases of tuberculosis control with appropriate healthdepartment authorities. Prompt reporting to public health authorities is a critical component of TBcontrol. It is most critical that the discharge planning for individual patients be done in close alignmentwith community health officials.

X. Child Day Care

For facilities with child day care facilities state and local guidelines regarding tuberculosis screeningand/or tuberculosis control programs should be followed.

XI. References

1. VHA Directive 10-93 -094, Supplement No. 1. TB (Tuberculosis) Control Responsibilities of VA (Department of Veterans Affairs) Facilities. July 25, 1994.

2. VHA Directive 10-94-104. Administration of Aerosolized Pentamidine to HumanImmunodeficiency (HIV) Positive Patients. October 17, 1994.

3. MP-5, Part I, Chapter 792, Change 7, Health Services. June 30, 1990.

4. M-1, Pan III, Chapter 4. Services and Benefits Available to Volunteers. October 24, 1934.

5. M-2, Part I, Chapter 23, Change 1, Formed Consent. February 21, 1991.

6. M-1, Part 1, Chapter 9, Release of Medical Information. November 30, 1990.

7. 5 United States Code, Section 552A, Privacy Act.

Page 686: VA guide -2009

14

8. Title 38, United States Code, Committees on Veterans Affairs - Patient Rights January 31, 1992.

9. Title 38, United States Code, Committees on Veterans Affairs - Records. January 31, 1992.

10.VA Regulations, Title 38 Code of Federal Regulations, Part 1, General Trans. Sheet 177,Safeguarding personal Information in VA Records. May 9, 1986.

11. Handbook 7610, Planning Criteria for VA Facilities. Chapter 1, 100, 102, 212, 240, 262, 276, and 316.

12. HVAC Design Manual for Hospital Projects. February, 1997.

13. M-5, Part IV. Geriatrics & Extended Care, Domiciliary Care. December 6, 1990.

14. CDC. Core Curriculum on Tuberculosis. Third Edition, 1994.

15.CDC. Typhoid immunization recommendations of the immunization practices advisory committee (ACIP) and prevention and control of tuberculosis in facilities providing long-term care to the elderly. Recommendations of the Advisory Committee for Elimination of Tuberculosis. MMWR, May 18, 1990, Vol. 39, No. RR-10).

16.Prevention and control of tuberculosis in U.S. communities with at-risk minority populations and prevention and control of tuberculosis among homeless persons. Recommendations of the Advisory Council for the Elimination of tuberculosis. MMWR, .April 17, 1992, Vol. 41, No.RR-5).

17.CDC. Screening for tuberculosis and tuberculosis infection in high-risk populations and theuse of prevention therapy for tuberculosis infection in the United States. Recommendations of the Advisory Committee for Elimination of Tuberculosis. MMWR, May 18, 1990, Vol. 39, No. RR-8.

18. CDC. Guidelines for preventing the transmission of Mycobacterium tuberculosis in healthcare facilities. MMWR, October 28, 1994, Vol. 43, No.RR-13.

19.M-2, Part IV, Chapter 6, Infectious Diseases. April 29, 1994.

20. American Thoracic Society. Treatment of Tuberculosis and Tuberculosis Infection in Adults and Children. Am J Resp Crit Care Med 1994; 149:1359-1374.

21.CDC/National Institutes of Health. Agent: Mycobacterium tuberculosis, M. bovis. In: Biosafety in microbiological and biomedical laboratories. Atlanta: US Department of Health and Human Services, Public Health Service, 1993:95, EDHHCS publication no. (CDC) 93-8395.

22- Shinnick, TM and Good. RC. Tuberculosis commentary. CID, 1995; 21:291-9.

Page 687: VA guide -2009

Contact Satish Sehgal @ 202-565-5032, Kurt Knight @ 202-565-4980, Sat Gupta @ 202-565-5268, WilburWright @ 202-565-5227, or Fred Lisi @ 202-565-6273 for additional information.

May 1997

HVAC REQUIREMENTS IN TB ISOLATION ROOM SUITE(NEW CONSTRUCTION)SEE VA PRIMER OF MAY,1997, FOR GRAPHIC INFORMATION

1. Indoor Design Conditions:Area Summer

Degree C (Degree F)Winter

Degree C (Degree F)HVAC DesignManual Ref.

Bed Room 24 (76) - 50%RH 25 (78) - 30% RH Application. A36

Ante Room (If provided) 25 (78) -50% RH 22 (72) - 30% RH “

Bathroom & Toilet 25 (78) 22 (72) “

2. Minimum Air Changes per Hour:Area Air Changes HVAC Design Manual

Ref.

Bed Room 12 Application. A36

Ante Room (If provided) 12 “

Bathroom & Toilet 10 (No supply) Para. 3.5

3. The use of Ante room is not mandatory, however, its need should bediscussed with the facility.

Application. A36

4. All air from bed room, ante room (if provided), bathroom & toilet should beexhausted to outside through a dedicated exhaust system.

5. Maintain negative pressure in bed room with respect to ante room. Maintainnegative pressure in ante room with respect to corridor. Maintain negativepressure in bath room & toilet with respect to bed room.

6. The supply air to the bed room and ante room shall be constant volume withterminal reheat.

7. Provide an individual air flow control valve in each individual space exhaustbranch for control reason. See VA standard detail 15900-7 and 7A, butcontrols should be set up for isolation room Mode 1 only, and NOT MODE 2FOR REVERSE ISOLATION.

8. The use of HEPA filters in the 100% exhaust from the TB isolation suite isnot necessary, but its use should be considered wherever exhaust air couldpossibly reenter the system.

CDC Guidelines

9. Negative pressure in the bed room should be monitored daily while the roomis occupied.

Application A36

10. Exhaust fan for TB isolation suite is not required to be on emergency power.Consult facility staff..