utm_slide_
TRANSCRIPT
-
7/22/2019 UTM_Slide_
1/231
CIRCUIT BREAKER
Abdullah Asuhaimi Mohd.Zin
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
2/231
Introduction
A power system network needs a switchgearfor its switching and or isolation undernormal or abnormal operation conditions.
Two functions of switchgear :
1. To permit plant and distributors (transmission lines)
to be conveniently put into and taken out of service.2. To enable the same plant and lines when thesebecome faultyto be rapidly and safely isolated byautomatic means.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
3/231
Introduction
The function of a circuit breaker is to isolate
the faulty part of the power system in case of
abnormal conditions.A protective relay detects abnormal
conditions and sends a tripping signal to the
circuit breaker. After receiving the trip
command from the relay, the circuit breakerisolates the faulty part of the power system
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
4/231
Introduction
A circuit breaker has two contacts afixed contact and a moving contact.
Under normal conditions these twocontacts remain in closed position.
When the circuit breaker is required to
isolate the faulty part, the movingcontact moves to interrupt the circuit.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
5/231
Introduction
On the separation of the contacts, the
flow of current is interrupted, resulting in
the formation of arc between thecontacts, as shown in Figure 5.1. The
contacts are placed in a closed
chamber containing some insulatingmedium (liquid or gas) which
extinguishes the arc.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
6/231
Introduction
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.1 Separation of the contacts of circuit breaker
-
7/22/2019 UTM_Slide_
7/231
Arc Voltage
Figure 5.2 shows the wave shape of arc voltage. Thevoltage drop across the arc is called arc voltage.
As the arc path is purely resistive, the arc voltage isin phase with the arc current.
The magnitude of the arc voltage is very low,
amounting to only a few per cent of the rated voltage.A typical value may be about 3 per cent of the ratedvoltage.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
8/231
Arc Voltage
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.2 Short circuit current and arc voltage
-
7/22/2019 UTM_Slide_
9/231
Arc
Interruption
There are two methods of arc
interruption:
1. High Resistance Interruption
2. Current Zero Interruption
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
10/231
1. High Resistance
Interruption
In this method of arc interruption, itsresistance is increased so as to
reduce the current to a valueinsufficient to maintain the arc.
The arc resistance can be increasedby cooling, lengthening, constrainingand splitting the arc.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
11/231
1. High Resistance
Interruption
When current is interrupted the energyassociated with its magnetic field
appears in the form of electrostaticenergy.
A high voltage appears across thecontacts of the circuit breaker.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
12/231
1. High Resistance
Interruption
If this voltage is very high and more than
the withstanding capacity of the gap
between the contacts, the arc will strikeagain.
Therefore, this method is not suitable for a
large-current interruption. This can be
employed for low power arc and dc circuit
breakers.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
13/231
2. Current Zero
Interruption
This method is applicable only in caseof ac circuit breakers.
In case of ac supply, the current wavepasses through a zero point, 100
times per second at the supplyfrequency of 50 Hz.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
14/231
2. Current Zero
Interruption
This feature of ac is utilised for arc
interruption. The current is not interruptedat any point other than the zero current
instant, otherwise a high transient voltage
will occur across the contact gap. The
current is not allowed to rise again after azero current occurs.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
15/231
2. Current Zero
Interruption
There are two theories to explain the
zero current interruption of the arc.
1. Recovery rate theory (SlepainsTheory)
2. Energy balance theory (CassiesTheory)
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
16/231
2. Current Zero
Interruption
Recovery rate theory
The arc is a column of ionised gases.
To extinguish the arc, the electrons and ions are tobe removed from the gap immediately after thecurrent reaches a natural zero.
Ions and electrons can be removed either byrecombining them into neutral molecules or bysweeping them away by inserting insulatingmedium (gas or liquid) into the gap.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
17/231
2. Current Zero
Interruption
Recovery rate theory (cont.)
The arc is interrupted if ions are removed from thegap at a rate faster than the rate of ionisation.
In this method , the rate at which the gap recoversits dielectric strength is compared with the rate atwhich the restriking voltage (transient voltage)
across the gap rises.
.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
18/231
2. Current Zero
Interruption
Recovery rate theory (cont.)
If the dielectric strength increases more rapidlythan the restriking voltage, the arc is extinguished.
If the restriking voltage rises more rapidly than thedielectric strength, the ionization persists andbreakdown of the gap occurs, resulting in an arcfor another half cycle.
Figure 5.3 explains the principle of recovery ratetheory.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
19/231
2. Current Zero
Interruption
Recovery rate theory (cont.)
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.3 Recovery rate theory
-
7/22/2019 UTM_Slide_
20/231
2. Current Zero
Interruption
Energy balance theory
The space between the contacts contains some
ionised gas immediately after current zero andhence, it has a finite post-zero resistance.
At the current zero moment, power is zerobecause restriking voltage is zero.
When the arc is finally extinguished the poweragain becomes zero, the gap is fully de-ionisedand its resistance is infinitely high.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
21/231
2. Current Zero
Interruption
Energy balance theory (cont.)
In between these two limits, first the
power increases reaches a maximumvalue, then decreases and finallyreaches zero value as shown in Fig. 5.4.
Due to the rise of restriking voltage andassociated current, energy is generatedin the space between the contacts.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
22/231
2. Current Zero
Interruption
Energy balance theory (cont.)
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.4 Energy balance theory
-
7/22/2019 UTM_Slide_
23/231
2. Current Zero
Interruption
Energy balance theory (cont.)
The energy appears in the form of heat. Thecircuit breaker is designed to remove thisgenerated heat as early as possible by cooling thegap, giving a blast of air or flow of oil at highvelocity and pressure.
If the rate of removal of heat is faster than the rate
of heat generation the arc is extinguished. If therate of heat generation is more than the rate ofheat dissipation, the space breaks down againresulting in an arc for another half cycle.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
24/231
5.3 Restriking Voltage and Recovery Voltage
The voltage across the contacts of the circuit breaker is arcvoltage when the arc persists.
This voltage becomes the system voltage when the arc is
extinguished. The arc is extinguished at the instant of currentzero.
After the arc has been extinguished, the voltage across thebreaker terminals does not normalise instantaneously but itoscillates and there is a transient condition.
The transient voltage which appears across the breakercontacts at the instant of arc being extinguished is known asrestriking voltage.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
25/231
5.3 Restriking Voltage and Recovery Voltage (cont.)
The power frequency rms voltage,
which appears across the breaker
contacts after the arc is finallyextinguished and transient oscillations
die out is called recovery voltage.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
26/231
5.3 Restriking Voltage and Recovery Voltage (cont.)
The instantaneous recovery voltage at the instant ofarc extinction is called active recovery voltage.
The instantaneous recovery voltage is given by :
Var= kVm sin
Where k=1 if the three-phase fault is grounded andk=1.5 if the three-phase fault is isolated. Vm is peak
recovery voltage and is the power factor angle.
Figure 5.5 shows the restriking and recovery voltage.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
27/231
5.3 Restriking Voltage and Recovery Voltage (cont.)
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.5 Restriking and recovery voltage
-
7/22/2019 UTM_Slide_
28/231
5.3.1 Expression for Restriking Voltage and RRRV
Figure 5.6(a) shows a short circuit on a
feeder beyond the location of the circuit
breaker.
Figure 5.6(b) shows an equivalent electrical
circuit where L and C are the inductance and
capacitance per phase of the system up tothe point of circuit breaker location,
respectively.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
29/231
5.3.1 Expression for Restriking Voltage and RRRV
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.6 (a) Fault on a feeder near circuit breaker
(b) Equivalent electrical circuit for analysis of
restriking voltage
-
7/22/2019 UTM_Slide_
30/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
When the circuit breaker is closed, the shortcircuit current flows through R, L and thecontacts of the circuit breaker, the
capacitance C being short-circuited by thefault.
When the circuit breaker contacts are openedand the arc is extinguished, the current isdiverted through the capacitance C, resultingin a transient condition.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
31/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
The inductance and the capacitance form a
series oscillatory circuit. The voltage across
the capacitance which is restriking voltage,rises and oscillates, as shown in Fig. 5.5.
The natural frequency of oscillation is given
by
INSPIRING CREATIVE AND INNOVATIVEMINDS
LC2
1fn
-
7/22/2019 UTM_Slide_
32/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
The voltage across the capacitance
which is the voltage across the contacts
of the circuit breaker can be calculatedin terms of L, C, fnand system voltage.
The mathematical expression for
transient condition (neglectingresistance) is as follows.
INSPIRING CREATIVE AND INNOVATIVEMINDS
EdtiC1
dt
diL
-
7/22/2019 UTM_Slide_
33/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
Where E is the system voltage at the
instant of arc interruption. As the
transient oscillation is a fastphenomenon, E can be regarded as a
constant for a short duration.
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
34/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
Where vc= voltage across the capacitor
Therefore
INSPIRING CREATIVE AND INNOVATIVEMINDS
dt
)d(cv
dt
dqi c
-
7/22/2019 UTM_Slide_
35/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
Substituting these values in the equationgiven above, we get
Taking Laplace Transform of both sides ofthe equation, we get
Where (S) is the Laplace Transform of
INSPIRING CREATIVE AND INNOVATIVEMINDS
Evtd
vd
LC c2c
2
S
E)(v)(SLC c
2 SSvc
where vc(S) is the Laplace Transform of vc
-
7/22/2019 UTM_Slide_
36/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
Other terms are zero as initially q = 0 at t = 0,
or
, therefore
INSPIRING CREATIVE AND INNOVATIVEMINDS
LCwn
1 2
nLC
1
-
7/22/2019 UTM_Slide_
37/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
or
INSPIRING CREATIVE AND INNOVATIVEMINDS
)(S
(S
)S(S
E
(s)V 2n2
nn
2n
2
2
n
c
E
Taking the inverse Laplace, we get
t
0 nnc tsinE(t)V
t
0n
nnc
tcosE(t)V
-
7/22/2019 UTM_Slide_
38/231
5.3.1 Expression for Restriking Voltage and RRRV (cont.)
INSPIRING CREATIVE AND INNOVATIVEMINDS
As = 0 at t = 0, constant = 0
(t) = E(1cos wnt ) , or
= Restriking voltage
The maximum value of restriking voltage = 2 Epeak= 2 x peak value of the system voltage
The Rate of Rise of Restriking voltage (RRRV)
= (1 - cos wnt) = wn E sin wnt
The maximum value of RRRV = wnE
= wnEpeak
-
7/22/2019 UTM_Slide_
39/231
Assignment
INSPIRING CREATIVE AND INNOVATIVEMINDS
-
7/22/2019 UTM_Slide_
40/231
Example 5.1
INSPIRING CREATIVE AND INNOVATIVEMINDS
Example 5.1 For a 132 kV system, the reactance andcapacitance up to the location of the circuit breaker is 3 ohmsand 0.015 F, respectively. Calculate the following:
a. The frequency of transient oscillation.
b. The maximum value of restriking voltage across
the contacts of the circuit breaker
c. The maximum value of RRRV
-
7/22/2019 UTM_Slide_
41/231
Example 5.1
INSPIRING CREATIVE AND INNOVATIVEMINDS
Solution
(a)The frequency of transient oscillation
L = , f = 50, the system frequency
= 0.00954 H=
= =
=
= 13.291 kHz=
-
7/22/2019 UTM_Slide_
42/231
Example 5.1
INSPIRING CREATIVE AND INNOVATIVEMINDS
(b) The restriking voltage
= E [ 1 - cos wnt ]The maximum value of the restriking voltage = 2 Epeak
= 2 x
= 215.56 kV(c) maximum value of RRRV = wnEpeak
100023
1322 xxxf
n
V/sx10002x3
132x013.291x1002x
kV/9.01045V/s10x9010.45 6 sec
-
7/22/2019 UTM_Slide_
43/231
Example 5.2
INSPIRING CREATIVE AND INNOVATIVEMINDS
Example 5.2 : In a short circuit test on a 132kV 3-phase system, the breaker gave thefollowing result : p.f. of the fault 0.4, recoveryvoltage 0.95 of full line value, the breakingcurrent is symmetrical and the restriking
transient had a natural frequency of 16 kHz.Determine the rate of rise of restriking voltage.Assume the fault is grounded.
-
7/22/2019 UTM_Slide_
44/231
Example 5.2
INSPIRING CREATIVE AND INNOVATIVEMINDS
Solution :
The peak value of line to neutral voltage =
kV107.7523
132
kV93.850.916x102.4
0.4cossinxx107.750.95V 1ar
-
7/22/2019 UTM_Slide_
45/231
Example 5.2
INSPIRING CREATIVE AND INNOVATIVEMINDS
The maximum restriking voltage = 2 x 93.85
= 187.7 kV
sec16x2
10
2f
1twheret
VRRRV3
n
kV/V/6.0
kV/sec10x187.7x32
10
16x2x187.7RRRV 3
3-
sec
-
7/22/2019 UTM_Slide_
46/231
Determinat ion of Recovery Vol tage
The recovery voltage is an indication ofthe severity of the test.
Less than the normal system voltagedue to voltage drop.
A typical recovery voltage oscillogram is
shown in the figure
-
7/22/2019 UTM_Slide_
47/231
Determination of Recovery voltage
YELLOW PHASE V
-
7/22/2019 UTM_Slide_
48/231
In this oscillogram, Line LL is drawn through the pointof final arc extinction, this point being determinedfrom an examination of the three corresponding
current waveforms. Line MM and NN are drawn at half-cycle intervalsfrom LL.
The peak to peak recovery voltage (V1,V2, etc) aremeasured during the second complete half-cycle
after final arc extinction, that is between the lines MMand NN.
If a peak to peak voltage occurs exactly on theselines, it is measured on NN, as shown.
-
7/22/2019 UTM_Slide_
49/231
The above measurements are made during thesecond half-cycle so as to allow a reasonable time for
the high frequency restriking transients to disappear
and for the voltage recovery to commence. The rms recovery voltage for any phase is obtained
by dividing the peak to peak value by 22.
Average recovery line voltage for a three-phase
breaker is1 2 3( ) 3
2 2 3
V V V
x
-
7/22/2019 UTM_Slide_
50/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
To reduce the restriking voltage, RRRV and severity of
the transient oscillations, a resistance is connected
across the contacts of the circuit breaker.
This is known as resistance switching. The resistance is
in parallel with the arc.
A part of the arc current flows through this resistance
resulting in a decrease in the arc current and increase in
the deionization of the arc path and resistance of the
arc.
-
7/22/2019 UTM_Slide_
51/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
This process continues and the current through the
shunt resistance increases and arc current decreases.
Due to the decrease in the arc current, restriking voltage
and RRRV are reduced.
The resistance may be automatically switched in with
the help of a sphere gap as shown in Fig. 5.7.
The resistance switching is of great help in switching out
capacitive current or low inductive current.
-
7/22/2019 UTM_Slide_
52/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.7 Resistance switching
-
7/22/2019 UTM_Slide_
53/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
The analysis of resistance switching can be made to find
out the critical value of the shunt resistance to obtain
complete damping of transient oscillations. Figure 5.8
shows the equivalent electrical circuit for such ananalysis.
Figure 5.8 Circuitfor analysis of
resistance switching
-
7/22/2019 UTM_Slide_
54/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
The voltage equation is given by
RCC iiiandEdtiC
1
dt
diL
Therefore, the above equation become
Edt
)id(iL C
RC
Edt
diLdt
diL CRC
dt
)d(C
dt
dqi cC
-
7/22/2019 UTM_Slide_
55/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
Therefore,
2
c
2
2
c
2
c
dt
dC
dt
)(Cd
dt
di
dt
d
R
1
dt
/R)(d
dt
di ccR
Substituting these values in the main equation, we get
Edt
d
R
L
dt
dLC C
c
2
C2
-
7/22/2019 UTM_Slide_
56/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
Taking Laplace Transform, we get
Other terms are zero, as
-
7/22/2019 UTM_Slide_
57/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
For no transient oscillation, all the root of the equation should
be real. One root is zero, i.e. S = 0 which is real. For the
other two roots to be real, the roots of the quadratic equation
in the denominator should be real. For this, the followingcondition should be satisfied.
-
7/22/2019 UTM_Slide_
58/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
CL /
Therefore, if the value of the resistance connected across the
contacts of the circuit breaker is equal to or less than there will be no transient oscillation.
If R > there will be oscillation. R = is known as critical resistance.
Figure 5.9 shows the transient conditions for three different values of
R. The frequency of damped oscillation is given by
-
7/22/2019 UTM_Slide_
59/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.9 Transient oscillations for different value of R
-
7/22/2019 UTM_Slide_
60/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
Example 5.3 In a 220 kV system, the reactance and
capacitance up to the location of circuit breaker is 8
and 0.025 F, respectively. A resistance of 600 ohms
is connected across the contacts of the circuit breaker.
Determine the following:
1. Natural frequency of oscillation
2. Damped frequency of oscillation
3. Critical value of resistance which will give no
transient oscillation4. The value of resistance which will give damped
frequency of oscillation, one-fourth of the natural
frequency of oscillation.
-
7/22/2019 UTM_Slide_
61/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
f = 3.413 kHz
f =
(ii) Frequency of damped oscillation is given by
=
kHz413.3
9
10
36.6
10
2
1 1010
=
-
7/22/2019 UTM_Slide_
62/231
5.4 Resistance Switching
INSPIRING CREATIVE AND INNOVATIVEMINDS
(iii) The value of critical resistance
35.50410x0.025
0.02544
2
1
C
L
2
1R
6-
-
7/22/2019 UTM_Slide_
63/231
5.5 Current Chopping
INSPIRING CREATIVE AND INNOVATIVEMINDS
When low inductive current is being interrupted and
the arc quenching force of the circuit breaker is more
than necessary to interrupt a low magnitude of
current, the current will be interrupted before itsnatural zero instant.
In such a situation, the energy stored in the magnetic
field appears in the form of high voltage across thestray capacitance, which will cause restriking of the
arc.
-
7/22/2019 UTM_Slide_
64/231
5.5 Current Chopping
INSPIRING CREATIVE AND INNOVATIVEMINDS
The energy stored in the magnetic field is Li2, if i is the
instantaneous value of the current which is interrupted. This
will appear in the form of electrostatic energy equal to cv2.
As these two energies are equal, they can be related as
follows.
-
7/22/2019 UTM_Slide_
65/231
5.5 Current Chopping
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.10 shows the current chopping phenomenon.
If the value of v is more than the withstanding capacity of the
gap between the contacts, the arc appears again.
Since the quenching force is more, the current is again
chopped.
The phenomenon continues till the value of v becomes less
than the withstanding capacity of the gap.
The theoretical value of v is called the prospective value of the
voltage.
-
7/22/2019 UTM_Slide_
66/231
5.5 Current Chopping
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.10 Current chopping
-
7/22/2019 UTM_Slide_
67/231
5.5 Current Chopping
INSPIRING CREATIVE AND INNOVATIVEMINDS
Example 5.4A circuit breaker interrupts the magnetising
current of a 100 MVA transformer at 220 kV. The
magnetising current of the transformer is 5% of the full load
current. Determine the maximum voltage which may appearacross the gap of the breaker when the magnetising current
is interrupted at 53% of its peak value. The stray
capacitance is 2500 F. The inductance is 30H.
-
7/22/2019 UTM_Slide_
68/231
5.5 Current Chopping
INSPIRING CREATIVE AND INNOVATIVEMINDS
Solution
The full load current of the transformer
=
= 262.44 A
Magnetising current = x 262.44 = 34.44 A
Current chopping occurs at 0.53 x 34.44 = 25.83 A
-
7/22/2019 UTM_Slide_
69/231
5.6 Interruption Capacitive Current
INSPIRING CREATIVE AND INNOVATIVEMINDS
The interruption of capacitive current produces high voltage
transients across the gap of the circuit breaker.
This occurs when an unloaded long transmission line or a
capacitor bank is switched off.
Figure 5.11(a) shows an equivalent electrical circuit of a
simple power system. C represents stray capacitance of the
circuit breaker. CLrepresents line capacitance. The value ofCLis much more than C.
Figure 5.11(b) shows transient voltage across the gap of the
circuit breaker when capacitive current is interrupted
-
7/22/2019 UTM_Slide_
70/231
5.6 Interruption Capacitive Current
INSPIRING CREATIVE AND INNOVATIVEMINDS
(a)Electrical circuit of a simple power system
-
7/22/2019 UTM_Slide_
71/231
5.6 Interruption Capacitive Current
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.11 Interruption of capacitive current
-
7/22/2019 UTM_Slide_
72/231
5.6 Interruption Capacitive Current
INSPIRING CREATIVE AND INNOVATIVEMINDS
At the instant M, the capacitance current is zero and the
system voltage is maximum. If an interruption occurs, the
capacitors CL remains charged at the maximum value of the
system voltage. After instantM
, the voltage across the breakergap is the difference of Vcand VCL. At instant N, i.e. half-cycle
from A, the voltage across the gap is twice the maximum value
of Vc. At this moment, the breaker may restrike.
If the arc restrikes, the voltage across the gap becomespractically zero. Thus, the voltage across the gap falls from
2Vcmaxto zero. A severe high frequency oscillation occurs.
-
7/22/2019 UTM_Slide_
73/231
5.6 Interruption Capacitive Current
INSPIRING CREATIVE AND INNOVATIVEMINDS
The voltage oscillates about points between R and N, i.e.
between -3emaxand emax.
When restriking current reaches zero, the arc may be
interrupted again. At this stage, the capacitor CL remainscharged at the voltage -3emax.
At instant P, the system voltage reaches its positive
maximum shown by the point T in the figure, and at thismoment the voltage across the gap becomes 4emax. The
capacitive current reaches zero again and there may be an
interruption.
-
7/22/2019 UTM_Slide_
74/231
5.6 Interruption Capacitive Current
INSPIRING CREATIVE AND INNOVATIVEMINDS
If the interruption occurs at this moment, the transient
voltage oscillates between P (-3emax) and Q (+5emax).
In this way, the voltage across the gap goes on increasing.
But in practice, it is limited to 4 times the peak value of thesystem voltage.
Thus, it is seen that there is a problem of high transient of
high transient voltage while interrupting a capacitivecurrent.
-
7/22/2019 UTM_Slide_
75/231
5.7 Classification of Circuit Breaker
INSPIRING CREATIVE AND INNOVATIVEMINDS
The classification of circuit breakers has been made
on the basis of insulating medium employed in the
circuit breakers to extinguish the arc. Depending
on the arc quenching medium employed, thefollowing are important types of circuit breakers.
(i) Oil Circuit Breakers
(ii) Air Blast Circuit Breakers
(iii) Sulphur Hexafluoride (SF6)Circuit Breakers
(iv) Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
76/231
5.8 Oil Circuit Breaker
INSPIRING CREATIVE AND INNOVATIVEMINDS
Mineral oil has better insulating properties
than air. Due to this very reason it is
employed in many electrical equipment
including circuit breakers.
Oil has also good cooling property. In a
circuit breaker when arc is formed, itdecomposes oil into gases. Hence, the arc
energy is absorbed in decomposing the oil.
-
7/22/2019 UTM_Slide_
77/231
5.8 Oil Circuit Breaker
INSPIRING CREATIVE AND INNOVATIVEMINDS
The main disadvantage of oil is that it isinflammable and may pose a fire hazard.
Other disadvantages include the possibility of
forming explosive mixture with air and the
production of carbon particles in the oil due to
heating, which reduces its dielectric strength.
There are various types of oil circuit breakers
developed for use in different situations. Some
important types are discussed below.
-
7/22/2019 UTM_Slide_
78/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
In a plain-break oil circuit breaker there is a fixed and a
moving contact immersed in oil. The metal tank is strong,
weather tight and earthed.
Figure 5.12 shows a double break plain oil circuit breaker.
When contacts separate there is a severe arc which
decomposes the oil into gases. The gas obtained from
the oil is mainly hydrogen. The volume of gasesproduced is about one thousand times that of the oil
decomposed. Hence, the oil is pushed away from arc and
the gaseous medium surrounds the arc.
-
7/22/2019 UTM_Slide_
79/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.12 Plain-break oil circuit breaker
-
7/22/2019 UTM_Slide_
80/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The arc quenching factors are as follows:
(i) Elongation of the arc
(ii) Formation of gaseous medium in between the
fixed and moving contacts. This has a high
heat conductivity and high dielectric strength.
(iii) Turbulent motion of the oil, resulting from the
gases passing through it.
-
7/22/2019 UTM_Slide_
81/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
A large gaseous pressure is developed
because a large amount of energy is dissipated
within the tank.
Therefore, the tank of the circuit breaker is
made strong to withstand such a large
pressure.
When gas is formed around the arc, the oil is
displaced.
-
7/22/2019 UTM_Slide_
82/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
To accommodate the displaced oil, an aircushion between the oil surface and the tank is
essential.
The air cushion also absorbs the mechanicalshock produced due to upward oil movement.
It necessary to provide some form of vent fitted
in the tank cover for the gas outlet.
A sufficient level of oil above the contacts is
required to provide substantial oil pressure at
the arc
-
7/22/2019 UTM_Slide_
83/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Certain gap between the contacts must be createdbefore the arc interruption occurs.
To achieve this, the speed of the break should be as
high as possible.
The two breaks in series provide rapid arc elongation
without the need for a specially fast contact. The
double break also provides ample gap distance before
arc interruption.
But this arrangement has the disadvantage of unequal
voltage distribution across the breaks.
-
7/22/2019 UTM_Slide_
84/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.13 shows voltage distribution acrossbreaks. C is the capacitance between the fixed
contact and moving contact, C is thecapacitance between the moving contact and
earth. V1is the voltage across the first contact
and V2 across the second contact. Suppose
the fault current is i.
The voltages V1and V2will be expressed as follows :
-
7/22/2019 UTM_Slide_
85/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.13 Voltage
distribution across
breaks
-
7/22/2019 UTM_Slide_
86/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The capacitance between the moving contact and
earth Cis in parallel with C, the capacitance ofthe second break.
Taking C = 8 pF and C = 16 pF, we get
V1 + V2 = V = system voltage
V2 = 25% of the system voltage
and
V1 = 75% of the system voltage
-
7/22/2019 UTM_Slide_
87/231
5.8.1 Plain-break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
To equalise the voltage distribution across the breaks,
non-linear resistors are connected across each break.
The plain break circuit breakers are employed for breaking
of low current at comparatively lower voltages. They are
used on low voltage d.c. circuits and on low voltage a.c.
distribution circuits. Their size becomes unduly large for
higher voltages.
Also, they require large amount of transformer oil. They
are not suitable for autoreclosing. Their speed is slow.
They can be used up to 11 kV with an interrupting capacity
up to 250 MVA.
-
7/22/2019 UTM_Slide_
88/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
In this type of circuit-breakers, arc energy is
utilised to generate a high pressure in a
chamber known as explosion pot or pressure
chamber or arc controlling device.
The contacts are enclosed within the pot.
The pot is made of insulating material and it is
placed in the tank. Such breakers have high
interrupting capacity. The arcing time is
reduced.
-
7/22/2019 UTM_Slide_
89/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Since the pressure is developed by the arc itself, itdepends upon the magnitude of the current. Therefore,
the pressure will be low at low current and high at high
values of the current. This creates a problem in
designing a suitable explosion pot.
At low current, pressure generated should be sufficient
to extinguish the arc.
At heavy currents, the pressure should not be too high
so as to burst the pot. Various types of explosion pots
have been developed to suit various requirements. A
few of them have been discussed below.
-
7/22/2019 UTM_Slide_
90/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figured 5.14 shows a plain explosion pot.
This is the simplest form of an explosion pot.
When the moving contact separates a severe arc is
formed. The oil is decomposed and gas is produced. It
generates a high pressure within the pot because there
is a close fitting throat at the lower end of the pot.
The high pressure developed causes turbulent flow of
streams of the gas into the arc resulting in arc-
extinction.
Plain explosion pot
-
7/22/2019 UTM_Slide_
91/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Plain explosion pot (cont.)
Figure 5.14 Plain explosion pot
8 2 S lf d Oil Ci i B k
-
7/22/2019 UTM_Slide_
92/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
If the arc extinction does not occur within the pot, it occurs
immediately after the moving contact leaves the pot, due
to the high velocity axial blast of the gas which is released
through the throat.
Since the arc extinction in the plain explosion pot is
performed axially, it is also known as an axial extinction
pot. This type of a pot is not suitable for breaking of heavy
currents. The pot may burst due to very large pressure.
At low currents, the arcing time is more. Hence, type of an
explosion pot is suitable for the interruption of currents of
medium range.
Plain explosion pot (cont.)
5 8 2 S lf t d Oil Ci it B k
-
7/22/2019 UTM_Slide_
93/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.15 shows a cross-jet explosion pot.
It is suitable for high current interruptions. Arc splitters
are used to obtain an increased arc length for a givenamount of contact travel. When the moving contact is
separated from the fixed contact, an arc is formed, as
shown in Fig. 5.15(a).
The arc is pushed into the arc splitters as shown in Fig.
5.15(b), and finally it is extinguished, as in Fig. 5.15 (c).
In this type of a pot, the oil blast is across the arc and
hence it is known as a cross-jet explosion pot.
Cross-jet explosion pot
5 8 2 S lf t d Oil Ci it B k
-
7/22/2019 UTM_Slide_
94/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.15 Cross-jet
explosion pot
5 8 2 S lf t d Oil Ci it B k
-
7/22/2019 UTM_Slide_
95/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Self-compensated explosion pot
This type of a pot is a combination of a cross-jet explosion potand a plain explosion pot.
Figure 5.16 shows a self-compensated explosion pot. Its upper
portion is a cross-explosion pot, and the lower portion a plainexplosion pot.
On heavy currents the rate of gas generation is very high and
consequently, the pressure produced is also very high.
The arc extinction takes place when the first or second lateral
orifice of the arc splitter is uncovered by the moving contact.
The pot operates as a cross-jet explosion pot.
5 8 2 S lf t d Oil Ci it B k
-
7/22/2019 UTM_Slide_
96/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Self-compensated explosion pot (cont)
Figure 5.16 Self-compensated explosion pot
5 8 2 S lf t d Oil Ci it B k
-
7/22/2019 UTM_Slide_
97/231
5.8.2 Self-generated Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Self-compensated explosion pot (cont)
When the current is low, the pressure is also low in the
beginning. So the arc is not extinguished when the tip of the
moving contact is in the upper portion of the pot.
By the time the moving contact reaches the orifice at thebottom of the pot, sufficient pressure is developed.
The arc is extinguished by the plain explosion pot action.
Thus, it is seen that the pot is suitable for low as well as highcurrent interruptions.
5 8 3 D bl B k Oil Ci it B k
-
7/22/2019 UTM_Slide_
98/231
5.8.3 Double Break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
To obtain high speed arc interruption, particularly
at low currents, various improved designs of the
explosion pot have been presented.
Double break oil circuit breaker is also one of
them. It employs an intermediate contact
between the fixed and moving contact. When
the moving contact separates, the intermediate
contact also follows it.
5 8 3 Double Break Oil Circuit Breakers
-
7/22/2019 UTM_Slide_
99/231
5.8.3 Double Break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The arc first appears between the fixed contactand the intermediate contact. Soon after, the
intermediate contact stops and a second arc
appears between the intermediate contact and
the moving contact.
The second arc is extinguished quickly
employing gas pressure and oil momentumdeveloped by the first arc. Figure 5.17 (a) shows
an axial blast pot and Fig. 5.17(b) shows a cross
blast pot.
5 8 3 Double Break Oil Circuit Breakers
-
7/22/2019 UTM_Slide_
100/231
5.8.3 Double Break Oil Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.17 Double break oil circuit
breakers
5.8.4 Bulk Oil and Minimum Oil Circuit
-
7/22/2019 UTM_Slide_
101/231
Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
In bulk oil circuit breakers, oil performs twofunctions.
It acts as an arc extinguishing medium and it also
serves as insulation between the live terminals and
earth. The tank of a bulk oil circuit breaker is
earthed.
Its main drawback is that it requires a huge amount
of oil at higher voltages. Due to this very reason it is
not used at higher voltages.
5.8.4 Bulk Oil and Minimum Oil Circuit
-
7/22/2019 UTM_Slide_
102/231
Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
A minimum content oil circuit breaker does not employ asteel tank. Its container is made of porcelain or other
insulating material.
This type of a circuit breaker consists of two sections namelyan upper chamber and a lower chamber.
The upper chamber contains an arc control device, fixed and
a moving contact. The lower chamber acts as an insulating
support and it contains the operating mechanism.
These two chambers are filled with oil but they are physically
separated from each other.
5.8.4 Bulk Oil and Minimum Oil Circuit
-
7/22/2019 UTM_Slide_
103/231
Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The arc control device is placed in a resin bounded
glass fiber cylinder (or backelised paper encloser).
This cylinder is also filled with oil. The fibre glasscylinder is then placed in a porcelain cylinder. The
annular space between the fibre-glass cylinder and
the porcelain insulator is also filled with oil.
Minimum oil circuit breakers arc available in the
voltage range of 3.3 kV to 420 kV. Now-a-days they
are superseded by SF6circuit breakers
5.8.4 Bulk Oil and Minimum Oil Circuit
-
7/22/2019 UTM_Slide_
104/231
Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
One of the important advantages that the bulk
oil circuit breaker has over both the low
content oil circuit breakers and air blast circuitbreakers is that the protective current
transformers can be accommodated on the
bushings instead of being supplied as aseparate piece of apparatus
5.8.4 Bulk Oil and Minimum Oil Circuit
-
7/22/2019 UTM_Slide_
105/231
Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The number of interrupter units contained in a tankdepends upon the fault current to be interrupted,
and the system voltage. Up to 11kV voltage, the
minimum oil circuit breakers generally employ a
single interrupter per phase.
The typical figures for higher voltages are, two per
phase at 132 kV, and six per phase at 275 kV. Eachinterrupter has a provision of resistance switching (a
typical value being 1200 , linear wire wound
resistor) to damp restriking voltage.
5 9 Air Blast Circuit Breakers
-
7/22/2019 UTM_Slide_
106/231
5.9 Air Blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
In air blast circuit breakers, compressed air at a pressure of10-30 kg/cm2is employed as an arc quenching medium.
Air blast circuit breakers are suitable for operating voltages of
132 kV and above. They have also been used in 11kV-33 kVrange for certain applications.
At present, SF6 circuit breakers are preferred for 132 kV and
above. Vacuum circuit breakers are preferred for 11 kV33kV range.
Therefore, the air blast circuit breakers are becoming
obsolete.
5 9 Air Blast Circuit Breakers
-
7/22/2019 UTM_Slide_
107/231
5.9 Air Blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The advantages of air blast circuit breakers over oil circuit
breakers are:
1. Cheapness and free availability of the interrupting
medium, chemical stability and inertness of air.2. High speed operation
3. Elimination of fire hazard
4. Short and consistent arcing time and therefore, less
burning of contacts.5. Less maintenance
6. Suitability for frequent operation
7. Facility for high speed reclosure
5 9 Air Blast Circuit Breakers
-
7/22/2019 UTM_Slide_
108/231
5.9 Air Blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The disadvantages of an air blast circuit breaker are as
follows.
1. An air compressor plant has to be installed andmaintained.
2. Upon arc interruption the air blast circuit breaker
produces a high-level noise when air is discharged to the
open atmosphere. In residential areas, silencers need to
be provided to reduce the noise level to an acceptablelevel.
3. Problem of current chopping
4. Problem of restriking voltage
5 9 Air Blast Circuit Breakers
-
7/22/2019 UTM_Slide_
109/231
5.9 Air Blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Switching resistors and equalising capacitors aregenerally connected across the interrupters. The
switching resistors reduce transient overvoltages
and help arc interruption. Capacitors are employed
to equalise the voltage across the breaks.
The number of breaks depends upon the system
voltages. For example, there are 2 for 66 kV, 2 to 4for 132 kV, 2 to 6 for 220 kV, 4 to 12 for 400 kV, 8 to
12 for 750 kV.
5 9 Air Blast Circuit Breakers
-
7/22/2019 UTM_Slide_
110/231
5.9 Air Blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
The breaking capacities are, 5000 MVA at 66
kV, 10,000 MVA at 132 kV, 20,000 MVA at
220 kV; 35000 MVA at 400 kV, 40,000 MVA at
500 kV; 60,000 MVA at 750 kV.
Circuit breakers for higher interruptingcapacity have also been designed for 1000
kV and 1100 kV systems.
5 9 Air Blast Circuit Breakers
-
7/22/2019 UTM_Slide_
111/231
5.9 Air Blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
An air-blast circuit breaker may be either of
the following two types.
1. Cross-blast Circuit Breakers
2. Axial-blast Circuit Breakers
5 9 1 Cross-blast Circuit Breakers
-
7/22/2019 UTM_Slide_
112/231
5.9.1 Cross blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
In a cross-blast type circuit breaker, a high-pressure blast ofair is directed perpendicularly to the arc for its interruption.
Figure 5.18 (a) shows a schematic diagram of a cross-blast
type circuit breaker.
The arc is forced into a suitable chute. Sufficient lengthening
of the arc is obtained, resulting in the introduction of
appreciable resistance in the arc itself. Therefore, resistance
switching is not common in this type of circuit breakers.
Cross-blast circuit breakers are suitable for interrupting high
current (up to 100 kA) at comparatively lower voltages.
5.9.1 Cross-blast Circuit Breakers
-
7/22/2019 UTM_Slide_
113/231
5.9.1 Cross blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.18 (a) Cross-blast circuit breaker (b) Single blast type axial-blast
circuit breaker (c) Double blast type ( or radial-blast type) axial-blast circuit
breaker
5.9.1 Axial-blast Circuit Breakers
-
7/22/2019 UTM_Slide_
114/231
5.9.1 Axial blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
In an axial-blast type breaker, a high-pressure
blast of air is directed longitudinally, i.e. in line
with the arc. Figure 5.18 (b) and (c) show
axial-blast type circuit breakers.
Figure 5.18(b) shows a single blast type.
Whereas Fig. 5.18(c) shows a double blasttype or radial blast type.
5.9.1 Axial-blast Circuit Breakers
-
7/22/2019 UTM_Slide_
115/231
5.9.1 Axial blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.18(d) : axial-
blast type
circuit
breakers.
5.9.1 Axial-blast Circuit Breakers
-
7/22/2019 UTM_Slide_
116/231
5.9.1 Axial blast Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Axial blast circuit breakers are suitable for EHV and
super high voltage application. This is because
interrupting chambers can be fully enclosed in
porcelain tubes. Resistance switching is employedto reduce the transient overvoltages.
The number of breaks depends upon the system
voltage, for example, 4 at 220 kV and 8 at 750 kV.
Air-blast circuit breakers have also been
commissioned for 1100 kV system.
5.10 Air-break Circuit Breakers
-
7/22/2019 UTM_Slide_
117/231
5.10 Air break Circuit Breakers
INSPIRING CREATIVE AND INNOVATIVEMINDS
Oil circuit breakers are not suitable for heavy
current interruption at low voltages due to
carbonisation of oil, whereas air-break circuit
breakers are quite suitable for high currentinterruption at low voltages.
In this type of a circuit breaker, air atatmospheric pressure is used as an arc
extinguishing medium.
5.10 Air-break Circuit Breakers
-
7/22/2019 UTM_Slide_
118/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.19 shows an air-break circuit breaker. Itemploys two pairs of contacts main contacts andarcing contacts.
The main contacts carry current when the breaker is inclosed position. They have low contact resistance.
When contacts are opened, the main contacts separate
first, the arcing contacts still remain closed. Therefore,the current is shifted from the main contacts to the
arcing contacts. The arcing contacts separate later on
and the arc is drawn between them.
5.10 Air-break Circuit Breakers
-
7/22/2019 UTM_Slide_
119/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.19 Air-break
circuit breaker
5.10 Air-break Circuit Breakers
-
7/22/2019 UTM_Slide_
120/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.19 Air-break
circuit breaker
5.10 Air-break Circuit Breakers
-
7/22/2019 UTM_Slide_
121/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
In air-break circuit breakers, the principle ofhigh resistance is employed for arc
interruption. The arc resistance is increased
by lengthening, splitting and cooling the arc.The arc length is rapidly increased employing
arc runners and arc chutes. The arc moves
upward by both electromagnetic and thermal
effects. It moves along the arc runner and
then it is forced into a chute. It is splitted by
arc splitters.
5.10 Air-break Circuit Breakers
-
7/22/2019 UTM_Slide_
122/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
A blow-out coil is employed to provide
magnetic field to speed up arc movement and
to direct the arc into arc splitters. The blow-
out coil is not connected in the circuitpermanently. It comes in the circuit by the arc
automatically during the breaking process.
The arc interruption is assisted by currentzero in case of ac air break circuit breakers.
High resistance is obtained near current zero.
5.10 Air-break Circuit Breakers
-
7/22/2019 UTM_Slide_
123/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
AC air-break circuit breakers are available in thevoltage range 400 to 12 kV. They are widely
used in low and medium voltage system.
They are extensively used with electric furnaces,with large motors requiring frequent starting, in a
place where chances of fire hazard exist, etc.
Air-break circuit breakers are also used in dc
circuit up to 12 kV.
5.11 SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
124/231
6
INSPIRING CREATIVE AND INNOVATIVEMINDS
Suphur hexafluoride (SF6) has good dielectricstrength and excellent arc quenching property.
It is an inert, nontoxic, nonflammable and heavy
gas.
At atmospheric pressure, its dielectric strength is
about 2.5 times that of air.
At 3 atmospheric pressure its dielectric strength is
equal to that of transformer oil.
5.11 SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
125/231
6
INSPIRING CREATIVE AND INNOVATIVEMINDS
It is an electronegative gas, i.e. it has high affinity for
electrons.
When a free electron comes in collision with a neutralgas molecule, the electron is absorbed by the neutral
gas molecule and a negative ion is formed.
As the negative ions so formed are heavy they do notattain sufficient energy to contribute to ionization of the
gas. The property gives a good dielectric property.
5.11 SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
126/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Besides good dielectric strength, the gas has an
excellent property of recombination after the
removal of the source which energizes the arc.
This gives an excellent arc quenching property.
The gas has also an excellent heat transferproperty. Its thermal time constant is about 1000
times shorter than that of air.
5.11 SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
127/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Under normal conditions, SF6 is chemically inert and it doesnot attack metals or glass. However, it decomposes to SF4,
SF2, S2, F2, S and F at temperatures of the order of 1000oC.
After arc extinction, the products of decomposition recombine
in a short time, within about 1 microsecond.
In the presence of moisture, the decomposition products can
attack contacts, metal parts and rubber sealings in SF6circuit
breakers. Therefore, the gas in the breaker must bemoisture-free. To absorb decomposition products, a mixture
of soda line (NaOH + CaO) and activated alumina can be
placed in the arcing chamber.
5.11 SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
128/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
One major disadvantage of SF6 is its condensation at low
temperature.
The temperature at which SF6changes to liquid depends onthe pressure. At 15 atm. Pressure, the gas liquefies at a
temperature of about 100C.
Hence, SF6 breakers are equipped with thermostaticallycontrolled heaters wherever such low ambient temperatures
are encountered.
5.11 SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
129/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
SF6 circuit breakers are manufactured in the voltage range
3.6 kV to 765 kV. However, they are preferred for voltages
132 kV and above.
The dielectric strength of SF6gas increases rapidly after final
current zero. SF6 circuit breakers can withstand severe
RRRV and are capable of breaking capacitive current without
restriking. Problems of current chopping are minimised.
Electrical clearances are very much reduced due to high
dielectric strength of SF6.
5.11.1 Types of SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
130/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
This is the early design of SF6circuit breakers. Its operating
principle is similar to that of air-blast circuit breakers.
In this type of a circuit breaker, the gas from a high-pressurecompartment is released to the low pressure compartment to
extinguish the arc.
Because of its complicated design and construction, and itsneed for various auxiliaries such as gas compressors, filters
and control devices, this type of circuit breakers have
become obsolete.
Double-pressure SF6circuit breakers
5.11.1 Types of SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
131/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
This type of circuit breakers are also sometimes
called single-pressure or impulse type SF6circuit
breakers.
In this type of breakers, gas is compressed by a
moving cylinder system and is released througha nozzle to quench the arc. This type is
available in the voltage range 3.6 kV to 765 kV.
Puffer-type SF6circuit breakers
5.11.1 Types of SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
132/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.20 (a) shows a puffer-type breaker in
closed position. The moving cylinder and the
moving contact are coupled together.
When the contacts separate and the moving
cylinder moves, the trapped gas is compressed.
The trapped gas is released through a nozzle andflows axially to quench the arc as shown in Fig.
5.20(b).
Puffer-type SF6circuit breakers (cont.)
5.11.1 Types of SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
133/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Figure 5.20 Puffer-type SF6circuit breaker
5.11.1 Types of SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
134/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
There are two types of tank designs. Live
tank design and dead tank design.
In live tank design, interrupters are supported
on porcelain insulators. In the dead tank
design, interrupters are placed in SF6 filled-tank which is at earth potential. Live tank
design is preferred for outdoor substations.
Puffer-type SF6circuit breakers (cont.)
5.11.1 Types of SF6Circuit Breakers
-
7/22/2019 UTM_Slide_
135/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
A number of interrupters (connected in series) on
insulating supports are employed for EHV systems up to
765 kV. Two interrupters are used in a 420 kV system.Breaking time of 2 to 3 cycles can be achieved.
In the circuit breaker the steady pressure of the gas is
kept at 5 kg/cm2. The gas pressure in the interruptercompartment increases rapidly to a level much above its
steady value to quench the arc.
Puffer-type SF6circuit breakers (cont.)
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
136/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
The dielectric strength and arc interrupting ability of high
vacuum is superior to those of porcelain, oil, air and SF6at
atmospheric pressure.
SF6 at 7 atm. pressure and air at 25 atm. pressure have
dielectric strengths higher than that of high vacuum. The
pressure of 10-5mm of mercury and below is considered to
be high vacuum.
Low pressures are generally measured in terms of torr; 1 torr
being equal to 1 mm of mercury. It has now become
possible to achieve pressures as low as 10-8torr.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
137/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
When contacts separate in a gas, arc is formed due to the
ionized molecules of the gas.
The mean free path of the gas molecules is small and the
ionization process multiplies the number of electrons to form
an electron avalanche. In high vacuum, of the order of 10-5
mm of mercury, the mean free path of the residual gasmolecules becomes very large. It is of the order of a few
meters.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
138/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
Therefore, when contacts are separated by a few
mm in high vacuum, an electron travels in the gap
without collision. The formation of arc in high
vacuum is not possible due to the formation of
electron avalanche.
In vacuum arc electrons and ions do not come fromthe medium in which the arc is drawn but they come
from the electrodes due to the evaporation of their
surface material.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
139/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
The breakdown strength is independent of gas
density. It depends only on the gap length and
surface condition and the material of the electrode.
The breakdown strength of highly polished and
thoroughly degassed electrodes is higher. Copper-
bismuth, silver-bismuth, silver-lead and copper-leadare good materials for making contacts of the
breaker
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
140/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
The breakdown strength is independent of gas
density. It depends only on the gap length and
surface condition and the material of the
electrode.
The breakdown strength of highly polished and
thoroughly degassed electrodes is higher.Copper-bismuth, silver-bismuth, silver-lead and
copper-lead are good materials for making
contacts of the breaker
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
141/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
When contacts are separated in high vacuum,
an arc is drawn between them. The arc does
not take place on the entire surface of thecontacts but only on a few spots.
The contact surface is not perfectly smooth.
It has certain microprojections. At the time of
contact separation, these projections form the
last points of separation.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
142/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
The current flows through these points of
separation resulting in the formation of a few
hot spots.
These hot sports emit electrons and act as
cathode spots. In addition to thermalemission, electrons emission may be due to
field emission and secondary emission.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
143/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Figure 5.21 shows the schematic diagram of a vacuumcircuit breaker. Its enclosure is made of insulating
material such as glass, porcelain or glass fibre
reinforced plastic.
The vapour condensing shield is made of synthetic
resin. This shield provided to prevent metal vapour
reaching the insulating envelope.
As the interrupter has a sealed construction a stainless
metallic bellows is used to allow the movement of the
lower contact.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
144/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Figure 5.21 Vacuum
circuit breaker
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
145/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
One of its end is welded to the moving contact.
Its other end is welded to the lower end flange.
Its contacts have large disc-shaped faces.
These faces contain spiral segments so that the
arc current produces axial magnetic field.
This geometry helps the arc to move over the
contact surface.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
146/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The movement of arc over the contact surface
minimises metal evaporation, and hence erosion
of the contact due to arc.
Two metal end flanges are provided. They
support the fixed contact, outer insulating
enclosure, vapour condensing shield and themetallic bellows. The sealing technique is
similar to that used in electronic valves
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
147/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The vacuum circuit breaker is very simple inconstruction compared to other types of circuit breaker.
The contact separation is about 1 cm which is adequate
for current interruption in vacuum. As the breaker isvery compact, power required to close and open its
contacts is much less compared to other types of
breaker.
It is capable of interrupting capactive and small inductive
current, without producing excessive transient
overvoltages.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
148/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Vacuum circuit breakers have other
advantages like suitability for repeatedoperations, least maintenance, silent
operation, long life, high speed of
dielectric recovery, less weight of movingparts, etc..
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
149/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
In a.c., when the current decreases, vapour emission
decreases. Near current zero, the rate of vapour emission
tends to zero.
Immediately after current zero, the remaining vapour
condenses and the dielectric strength increases rapidly.
At current zero, cathode spots extinguish within 10-8
second.The rate of dielectric recovery is many times higher than that
obtained in other types of circuit breakers. Its typical value
may be as high as 20 kV/s.
5.12 Vacuum Circuit Breakers
-
7/22/2019 UTM_Slide_
150/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Vacuum circuit breakers have nowbecome popular for voltage ratings
up to 36 kV. Up to 36 kV they
employ a single interrupter.
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
151/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
To open and close the contacts of a
circuit breaker, one of the
following mechanisms isemployed
(i) Spring(ii) Solenoid
(iii) Compressed Air
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
152/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Opening and closing of a circuit breaker should be quick
and reliable. Closing is slow compared to opening.
For reliability, both operations should be independent
of the main supply.
The force for the opening of a circuit breaker may be
applied by spring or compressed air. When spring is
used for opening, it is precharged, i.e. compressed .The precharging may be done by hand or a motor or
by the closing mechanism. The closing mechanism
may be spring, solenoid or compressed air.
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
153/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
If the system uses spring for both opening as well as closing,the closing spring has a higher energy level and is
charged by motor-driven gears. Two separate springs
are employed, one for closing and the other for opening.
The force of the closing spring is utilized for closing the
breaker and also for charging the spring which is used for
opening. The closing mechanism also latches the moving
contact in the closed position.
When the tripping signal is received, a small solenoid is
energised, which releases the latch and permits the
spring to exert its force to open the contact.
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
154/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
For large oil circuit breakers, solenoid is used for
closing and a spring is used for opening.
For medium size breakers, where provision ofbattery for solenoid is uneconomical, spring is
employed for closing as well as opening.
In EHV oil circuit breakers, compressed air is used
for closing and a spring is used for opening. The
spring is charged during the closing stroke.
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
155/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
In air blast circuit breakers, compressed air is used for both
closing and opening.
In some cases of air blast circuit breakers, the moving
contact is held in closed position by a spring.
When compressed air enters the arc chamber and its
pressure exceeds the spring force, the contacts
automatically come in the closed position by the springaction when the supply of compressed air is stopped.
Therefore, the supply of compressed air must be
maintained till the auxiliary circuit breaker switch is
opened.
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
156/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
In SF6 circuit breaker, compressed air may be used for
closing and a spring for opening or compressed air for
both closing as well as opening.
In vacuum circuit breakers, a solenoid or spring mechanism
is fixed to the lower end to move a metallic bellows
upward or downward inside the chamber during closing
or opening the contacts.
The closing mechanism must be tripfree, i.e. if a tripping
signal comes during the closing operation, the circuit
breaker must trip immediately
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
157/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Spring are very good for opening as their force is large in the
beginning and gradually decreases as the distance of
travel of the moving contact increases. But it is not
suitable for closing because the closing operation mustbe a smart one. However, in circuit breakers of small
capacity, it is also used for closing.
The spring which is used for closing is charged by hand or a
motor. In small circuit breakers, the spring can becharged by hand. For large ones, it is charged by means
of a motor. The spring which is used for opening is
charged by the closing mechanism.
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
158/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Solenoids are very good for closing. The force of attraction
increases when the distance between the contacts
decreases. They are not suitable for opening because
they are slow in action.
Compressed air is suitable for both closing as well as
opening as its force remains almost constant even when
the distance between the contacts increases or
decreases.
Figure 5.22 shows the characteristics of the opening and
closing mechanisms.
5.13 Operating Mechanism
-
7/22/2019 UTM_Slide_
159/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Figure 5.22 Characteristics of operating mechanism
5.14 Selection of Circuit Breakers
-
7/22/2019 UTM_Slide_
160/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Table 5.1 shows the summary of
various types of circuit breakers,
their voltage ranges and arcquenching medium they employ.
Table 5.2 shows the choice of circuitbreakers for various voltage
ranges.
5.14 Selection of Circuit Breakers
-
7/22/2019 UTM_Slide_
161/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Type Arc Quenching Medium Voltage Range and BreakingCapacity
Miniature circuit breaker Air at atmospheric pressure 400-600 V; for small currentrating
Air-break circuit breaker Air at atmospheric pressure 400 V11 kV; 5-750 MVA
Minimum oil circuit breaker Transformer oil 3.3 kV220 kV;15025000 MVA
Vacuum circuit breaker Vacuum 3.3 kV33 kV;2502000 MVA
SF6circuit breaker SF6at 5kg/cm2pressure 3.3765 kV;
100050,000 MVA
Air blast circuit breaker Compressed air at high pressure(20-30 kg/cm2)
6.6 kV1100 kV;250060,000 MVA
TABLE 5.1 Types of circuit breaker
5.14 Selection of Circuit Breakers
-
7/22/2019 UTM_Slide_
162/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Rated Voltage Choice of Circuit Breakers Remark
Below 1 kV Air-break CB
3.3 kV33 kV Vacuum CB, SF6CB, minimum oil CB Vacuum preferred
132 kV220 kV SF6CB, air blast CB, minimum oil CB SF6preferred
400 kV760 kV SF6CB, air blast CB SF6is preferred
TABLE 5.2 Selection of Circuit Breakers
5.14 Selection of Circuit Breakers
-
7/22/2019 UTM_Slide_
163/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Earlier oil circuit breakers were preferred in the
voltage range of 3.3 kV - 66kV.
Between 132 kV and 220 kV, either oil circuitbreakers or air blast circuit breakers were
recommended.
For voltages 400 kV and above, air blast circuit
breakers were preferred.
5.14 Selection of Circuit Breakers
-
7/22/2019 UTM_Slide_
164/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The present trend is to recommend vacuum or SF6circuit breakers in the voltage range 3.3 kv 33kV.
For 132 kV and above, SF6 circuit breakers arepreferred. Up to kV, air break circuit breakers are
used.
Air blast circuit breakers are becoming obsolete and
oil circuit breakers are being superseded by SF6
and vacuum circuit breakers.
5.15 High Voltage DC Circuit Breakers
-
7/22/2019 UTM_Slide_
165/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
At present, HVDC transmission lines are used for point
to point transmission of large power over long
distance.
Such lines have many advantages over ac transmission
lines such as lower cost, less stability problems, less
corona loss and less radio interference, etc.
HVDC circuit breakers are not essential for single HVDC
transmission lines which are used for point to point
transmission.
5.15 High Voltage DC Circuit Breakers
-
7/22/2019 UTM_Slide_
166/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The current in HVDC lines is controlled by controlling
the firing circuits of the thyristors employed in
rectifiers and inverters.
Switching operations are performed from ac side with
the help of ac circuit breakers.
If HVDC circuit breakers are available, parallel HVDClines, HVDC lines with a tap-off line, closed loop
circuit, etc. can also be planned and designed.
5.15 High Voltage DC Circuit Breakers
-
7/22/2019 UTM_Slide_
167/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The additional circuit creates artificial current zeros which
are utilised for arc interruption as shown in Fig. 5.23.
Figure 5.23 Artificial current zeros in DC
5.15 High Voltage DC Circuit Breakers
-
7/22/2019 UTM_Slide_
168/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Figure 5.24 shows the schematic diagram of a
HVDC circuit breaker.
It is consists of a main circuit breaker MCB
and a circuit to produce artificial current zero
and to suppress transient voltage.
The main circuit breaker MCB may either be
an SF6or vacuum circuit breaker.
5.15 High Voltage DC Circuit Breakers
-
7/22/2019 UTM_Slide_
169/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Figure 5.24 HVDC circuit breaker
5.15 High Voltage DC Circuit Breakers
-
7/22/2019 UTM_Slide_
170/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
R and C are connected in parallel with the main circuitbreaker to reduce dv/dt after the final current zero.
L is a saturable reactor in series with the main circuit
breaker. It is used to reduce di/dt before current zero.
Cp and Lp are connected in parallel to produce artificial
current zero after the separation of the contacts in the
main circuit breaker MCB.
A non-linear resistor is used to suppress the transient
overvoltage which may be produced across the contacts
of the main circuit breaker.
5.15 High Voltage DC Circuit Breakers
Switch S which is a triggered vacuum gap is switched
-
7/22/2019 UTM_Slide_
171/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Switch S, which is a triggered vacuum gap, is switched
immediately after the opening of the contacts of the main
circuit breaker.
The capacitor Cpis precharged in the direction as shown
in the figure.
When S is closed, the precharged capacitor Cp
discharges through the main circuit breaker and sends a
current in opposition to the main to the main circuit
current.
This will force the main circuit current to become zero
with a few oscillations. The arc is interrupted at a current
zero
5.16 Rating of Circuit Breakers
-
7/22/2019 UTM_Slide_
172/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
A circuit breaker has to perform the
following major duties under short-circuit
conditions.
(i) To open the contacts to clear the fault
(ii) To close the contacts onto a fault
(iii) To carry fault current for a short time
while another circuit breaker is clearingthe fault
5.16 Rating of Circuit Breakers
-
7/22/2019 UTM_Slide_
173/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Therefore, in addition to the rated voltage,current and frequency, circuit breakers
have the following important ratings.
(i) Breaking Capacity
(ii) Making Capacity
(iii) Short-time Capacity
5.16.1 Breaking Capacity
-
7/22/2019 UTM_Slide_
174/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The breaking capacity of a circuit
breaker is of two types
(i) Symmetrical breaking capacity
(ii) Asymmetrical breaking capacity
5.16.1 Breaking Capacity
-
7/22/2019 UTM_Slide_
175/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Symmetrical breaking capacity
It is the rms value of the accomponent of the fault current that the
circuit breaker is capable of breaking
under specified conditions of recoveryvoltage.
5.16.1 Breaking Capacity
-
7/22/2019 UTM_Slide_
176/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Asymmetrical breaking capacity
It is the rms value of the total current
comprising of both ac and dccomponents of the fault current that
the circuit breaker can break under
specified conditions of recoveryvoltage.
5.16.1 Breaking Capacity
-
7/22/2019 UTM_Slide_
177/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Figure 5.25 shows a short-circuit current wave.
The short-circuit current contains a dc
component which dies out gradually as shown in
the figure.
In the beginning, the short-circuit current is
asymmetrical due to the dc component.
When dc dies out completely, the short-current
becomes symmetrical.
5.16.1 Breaking Capacity
-
7/22/2019 UTM_Slide_
178/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Figure 5.25
Short-circuitcurrent
waveform
5.16.1 Breaking Capacity
-
7/22/2019 UTM_Slide_
179/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The line X-X indicates the instant of contact separation.
AB is the peak value of the ac component of the current
at this instant.
Therefore, the symmetrical breaking current which is therms value of the ac component of the current at the
instant of contact separation is equal to current AB/2.
The section BC is the dc component of the short-circuitcurrent at this instant. Therefore, asymmetrical breaking
current is given by 2
2
asym. BC2
ABI
5.16.1 Breaking Capacity
Th b ki it f i it b k i ll
-
7/22/2019 UTM_Slide_
180/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The breaking capacity of a circuit breaker is generally
expressed in MVA. For a three-phase circuit breaker, it isgiven by
Breaking capacity = 3 x rated voltage in kV x rated
current in kA.The breaking capacity will be symmetrical if the rated
current in the above expression is symmetrical (British
practice).
The breaking capacity will be asymmetrical if the ratedcurrent is asymmetrical (American practice). The rated
breaking current is taken by designer as 1.6 times the
rated symmetrical current.
5.16.2 Making Capacity
-
7/22/2019 UTM_Slide_
181/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
The possibility of a circuit breaker to be closed on short-circuit is also considered.
The rated making current is defined as the peak value of
the current (including the component) in the first cycle atwhich a circuit breaker can be closed onto a short-circuit.
Ipin Fig. 5.25 is the making current.
The capacity of a circuit breaker to be closed onto ashort-circuit depends upon its ability to withstand the
effects of electromagnetic forces.
5.16.2 Making Capacity
-
7/22/2019 UTM_Slide_
182/231
INSPIRING CREATIVE AND INNOVATIVE MINDS
Making current = 2 x 1.8 x symmetrical breakingcurrent.
The multiplication by 2 is to obtain the peakvalue and again by 1.8 to take the dc component
into account.
Making capacity = 2 x 1.8 x symmetrical breakingcapacity=2.55 x symmetrical breaking capacity
5.16.3 Short-time Current Rating
-
7/22/2019 UTM_Slide_
183/231
INSPIRING CREATIVE ANDINNOVATIVE
MINDS
The short-time current rating is based on thermal and
mechanical limitations.
The circuit breaker must be capable of carrying short-
circuit current for a short period while another circuitbreaker (in series) is clearing the fault.
The rated short-time current is the rms value (total
current, both a.c and d.c components) of the current thatthe circuit breaker can carry safely for a specified short
period.
5.16.3 Short-time Current Rating
-
7/22/2019 UTM_Slide_
184/231
INSPIRING CREATIVE ANDINNOVATIVE
MINDS
According to British standard, the time is 3 seconds if the
ratio of symmetrical breaking current to rated normal
current is equal to or less than 40 and 1 second if this
ratio is more than 40.
According to ASA there are two short-time ratings; one is
the current which the circuit breaker can withstand for 1
second or less. Another is rated 4-second current which
is the current that the circuit breaker can withstand for aperiod longer than 1 second but not more than 4 seconds.
5.16.4 Rated Voltage, Current and
Frequency
In a power system the voltage level at all points
-
7/22/2019 UTM_Slide_
185/231
INSPIRING CREATIVE ANDINNOVATIVE
MINDS
In a power system, the voltage level at all points
is not the same. It varies, depending upon thesystem operating conditions. Due to this reason
manufacturers have specified a rated maximum
voltage at which the operation of the circuit
breaker is guaranteed. The specified voltage is
somewhat higher than the rated nominal voltage.
The rated current is the rms value of the currentthat a circuit breaker can carry continuously
without any temperature rise in excess of its
specified limit.
5.16.4 Rated Voltage, Current and
Frequency
-
7/22/2019 UTM_Slide_
186/231
INSPIRING CREATIVE AND INNOVATIVEMINDS
The rated frequency is also mentioned bythe manufacturer. It is the frequency at
which the circuit breaker has been
designed to operate.The standard frequency is 50 Hz.
If a circuit breaker is to be used at a
frequency other than its rated frequency, its
effects should be taken into consideration.
Example 5 5
-
7/22/2019 UTM_Slide_
187/231
Example 5.5The rating of a circuit breaker are as follows : 3-phase, 1500amp, 100 MVA, 3.3 kV, 3 seconds. Calculate symmetricalbreaking current, making current and short-time current rating.
Solution :
Given Rated voltage = 3.3 kV Rated normal current = 1500 ampSo, Rated symmetrical breaking current (rms) = = 17.5 kA
Rated making current = 17.5 x 1.8 x 2 = 44.62 kA Short-time current rating is 17.5 kA for 3 seconds.
3.33
100
x
Example 5 6
-
7/22/2019 UTM_Slide_
188/231
Example 5.6
The portion of the test oscillograms which wereobtained during a make-break test on a circuitbreaker is shown in the figure. Given A = 20kV, B =30kA, X = 21kA and Y = 12kA. Determine:-
a) The line voltage rating of the breakerb) The peak making current for the red phase only.
c) The AC and DC components of breaking current atthe instant of contact separation for yellow phase
only. Hence determine whether the test issymmetrical or asymmetrical, and estimate thebreaking current.
-
7/22/2019 UTM_Slide_
189/231
Solution
-
7/22/2019 UTM_Slide_
190/231
a) Peak to peak phase system voltage = A = 20 kV.rms phase system voltage = 20/(22) = 7.07 kV
line voltage rating of breaker = 3 * 7.07 = 12.25kV
b) Peak making current = B = 30 kA.
c) AC component of making current = 21 kA.
DC component of making current = 12 kA.
Y/X = 12/21 = 0.578, therefore the test isasymmetrical. (Note : greater than 0.5)
asymmetrical breaking current :
5.16.5 Rated Operating Duty
The operating duty of a circuit breaker prescribes its
-
7/22/2019 UTM_Slide_
191/231
IN