    California Title 24 2013Design Guide for Smart Lighting Controland Energy Solutions

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    2/4422

    Energy efficiency is more than a single system.It requires a whole building approach.

    The basic goal of Title 24 energy standards is the reduction of energy use. A simple and efficient strategyto improve energy efficiency is to automatically turn off lights and devices when they are not in use.

    Since lighting currently accounts for nearly 30 percent of Californias electricity use, the extensive useof lighting controls is essential and makes up one of the more significant changes to Title 24 2013.

    www.leviton.com/title24

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    3/44www.leviton.com/title24

    Design Guide for Title 24 CompliantLighting Control and Energy Solutions

    Small Office . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Open Office . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Conference Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Classroom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Stairwell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Common Area - Lobby. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Hallway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Parking Garage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    Site Lighting Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    Warehouse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Retail Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    Restaurant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    Hospitality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    Energy Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

    Leviton Solutions for California Title 24 2013 Code Compliance . . . . . . . . . . . . . . . .37

    Leviton Value Add Design Services and Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43

    Disclaimer:This document is for informational purposes only. Each project will have its own specific requirements for satisfyingTitle 24 code compliance based on a variety of factors. Other exceptions or details may apply. Review the code for specific requirements and/or con-sult with a professional advisor. Leviton Mfg. Co., Inc. is not responsible for any loss resulting from the use of any information found in this document.

    Solutions are subject to change without notice.For additional assistance, contact your local Leviton representative.

    www.leviton.com/title24

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    4/444 www.leviton.com/title244

    Small Office Control Solutionfeaturing Integrated Room Control (IRC)

    Section 130.1(a)- Area Controls

    - Manual ON/OFF Section 130.1(b)

    - Multi-Level Controls- Dimming- Task Tuning- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting,

    0-10V dimming, partial ON, partial OFF, and demandresponse capabilities in a stand-alone package

    Kitted with factory configured sensor, photocell,and 4-button switch

    Autocal automatic photocell calibration and LadderlessCommissioning

    Easy automatic closed or open loop multi-zone daylightharvesting control design

    Auto 100 hour burn-in

    List of Equipment

    IRC Kit for 2 Zones, 2 Relays - includes IRC,sensor, photocell, and control stationRCD20-102

    1

    IRC for 2 Zones, 2 RelaysMZD20-102

    Multi-Tech Ceiling MountOccupancy Sensor1000SF, OSC10-M0W

    Photocell, IndoorODC0P-00W

    Lighting Control StationRLVSW-4LW

    OPP20 Super Duty Power PackOPP20-0D1

    1

    Marked Controlled Receptacles5362-S1W

    5

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    5/44www.leviton.com/title24 www.leviton.com/title24

    Small Office Control Solutionfeaturing LevNet RFEnergy Harvesting Wireless Solutions

    Section 130.1(a)- Area Controls

    - Manual ON/OFF Section 130.1(b)

    - Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand ResponsePower Reduction Controls

    Section 130.5(d)

    - Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    LevNet RF Energy HarvestingSelf-Powered Wireless Solutions No wires to run and no batteries required - install in 1/4th

    the timeeliminating time and expense of control wiring

    Broad range of switches and control modules to meetvirtually any control need including a Receptacle andengraved cover plate to meet plug load controlcode requirements

    Enables rapid retrofit with minimal impact

    FEATURED LEVITON TITLE 24 SOLUTIONList of Equipment

    LevNet RF Self-Powered PIROccupancy SensorWSCxx-IRW

    1

    LevNet RF Self-Powered Light SensorWSCPC-00W

    1

    LevNet RF 0-10V DimmerWSD01-010

    2

    LevNet RF Self-Powered SwitchWSS0S-D0W

    1

    OPP20 Super Duty Power PackOPP20-0D1

    2

    Marked Controlled ReceptaclesCR020-1PW

    5

    LevNet RF LAN Access Point& Venergy UI SoftwareWSAP0-TIP

    1

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    6/446 www.leviton.com/title246

    List of Equipment

    Sector Bus Controller and Power SupplySBC00-000

    1

    Sector RelaySBCS0-L00

    2

    Sector Occupancy Sensor, Multi-Tech, 2000SFOSC20-MSW

    1

    Sector PhotocellODC0P-0SW

    1

    Sector 5-Button Digital SwitchSDS00-15W

    1

    Sector Low Voltage InterfaceSLIQS-000

    1

    Marked Controlled Receptacles16352-1PW

    5

    Small Office Control Solutionfeaturing SectorDistributed Lighting Control System

    Section 130.1(a)- Area Controls

    - Manual-ON/OFF Section 130.1(b)

    - Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

    SectorDistributed Lighting Control System Topology-free, polarity-free distributed control

    Combines all lighting management functions intoa single system with the fewest connection points,simplest installation, greatest flexibility, and simplespecification

    All components connect directly to the topology

    free 2-wire bus, not the ballast Relay controllers allow zone dimming and control

    for cost-effective system design

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    7/44www.leviton.com/title24 www.leviton.com/title24

    Open Office Control Solutionfeaturing Sensing and Plug Load Control

    Section 130.1(a)- Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    At least one controlled receptacle must be installed within6 ft. of each uncontrolled receptacle or a split duplexcan be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    Sensing Control Broadest range of sensors for any application

    Provolt integrates occupancy sensing, daylight

    harvesting, and manual-ON/auto-OFF override control ina single unit - no special control stations required

    Plug load control with OPP20 Super Duty Power Pack

    24V AC/DC input for integration with HVAC/BAS systems

    Industry leading layout and application services

    Plug Load Control Meets requirements for identifying receptacles that will

    automatically be de-energized as part of an overall plugload control program

    2014 NEC requires all 15A and 20A, 125V receptacles thatare automatically controlled to be marked with a specificsymbol ()

    Ideal for new construction and renovation applications

    Available in back and side wired, side wired standard,tamper-resistant and Decoraversions

    List of Equipment

    Ultrasonic Ceiling MountOccupancy SensorOSCxx-U0W

    2

    Photocell, 1-10V DimmingODC0P-D 0W

    1

    Illumatech DimmerIP710-xxx

    1

    Decora Rocker, 3-way05633-xxx

    1

    OPP20 Super Duty Power PackOPP20-RD4

    3

    Marked Controlled Receptacles16352-2PW

    5

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    8/448 www.leviton.com/title248

    Open Office Control Solutionfeaturing Integrated Room Control (IRC)

    Section 130.1(a)- Area Controls

    - Manual ON/OFF Section 130.1(b)

    - Multi-Level Controls- Dimming- Task Tuning- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installed within6 ft. of each uncontrolled receptacle or a split duplexcan be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting,

    0-10V dimming, partial ON, partial OFF, and demandresponse capabilities in a stand-alone package

    Kitted with factory configured sensor, photocell, and4-button switch

    Autocal automatic photocell calibration and LadderlessCommissioning

    Easy automatic closed or open loop multi-zone daylightharvesting control design

    Auto 100 hour burn-in

    FEATURED LEVITON TITLE 24 SOLUTION

    List of Equipment

    IRC Kit for 2 Zones, 2 Relays - includes IRC,

    sensor, photocell, and control stationRCD20-102

    1

    IRC for 2 Zones, 2 RelaysMZD20-102

    Multi-Tech Ceiling MountOccupancy Sensor, 1000SFOSC10-M0W

    Photocell, IndoorODC0P-00W

    Lighting Control StationRLVSW-4LW

    Multi-Tech Ceiling MountOccupancy Sensor, 1000SFOSC10-M0W

    1

    Lighting Control StationRLVSW-4LW

    3

    OPP20 Super Duty Power PackOPP20-0D1

    1

    Marked Controlled ReceptaclesCR020-1PW

    5

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    9/44www.leviton.com/title24 www.leviton.com/title24

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    Multi-Tech Ceiling Mount Occupancy SensorOSCxx-M0W

    2

    Photocell, IndoorPCIND-000

    1

    GreenMAX Digital SwitchRDGSW-xDW

    4

    Marked Controlled Receptacles16352-1PW

    5

    Open Office Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)- Area Controls

    - Manual-ON/OFF Section 130.1(b)

    - Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or asplit duplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    GreenMAXRelay Control System Integrates common sensing, dimming, switching, and

    advanced daylight harvesting applicationsfrom the same cabinet

    BACnet IP native in each cabinet for seamlessBMS integration

    Industry leading 25,000A Short Circuit Current Rating(SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control of eachload individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    10/4410 www.leviton.com/title2410

    List of Equipment

    Sector Bus Controller and Power SupplySBC00-000

    1

    Sector RelaySBCS0-L00

    6

    Sector Occupancy Sensor, Multi-Tech, 2000SFOSC20-MSW

    2

    Sector PhotocellODC0P-0SW

    1

    Sector 5-Button Digital SwitchSDS00-15W

    2

    Sector Low Voltage InterfaceSLIQS-000

    1

    Marked Controlled Receptacles5362-S1W

    5

    Open Office Control Solutionfeaturing SectorDistributed Lighting Control System

    Section 130.1(a)- Area Controls

    - Manual-ON/OFF Section 130.1(b)

    - Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    SectorDistributed Lighting Control System Topology-free, polarity-free distributed control

    Combines all lighting management functions into a singlesystem with the fewest connection points, simplestinstallation, greatest flexibility, and simple specification

    All components connect directly to the topology free2-wire bus, not the ballast

    Relay controllers allow zone dimming and control forcost-effective system design

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    11/44www.leviton.com/title24 www.leviton.com/title24

    Conference Room Control Solutionfeaturing Dimensions4000 Lighting Control System

    Section 130.1(a)

    - Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings larger than10,000SF

    At least one controlled receptacle must be installed within6 ft. of each uncontrolled receptacle or a split duplexcan be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    Dimensions4000Architectural Lighting Control System Offers both stand-alone and integrated room dimming

    and control

    LED compatible with power extender

    Complete multi-event scheduler and integratedastronomical time clock

    Interfaces with HVAC, emergency, time clock,and load shed auxiliary systems

    List of Equipment

    Dimensions D4206 Multi-ZoneArchitectural Lighting Control SystemD4206-1LW

    1

    PE300 Power ExtenderPE300-D0W

    2

    Multi-Technology Ceiling MountOccupancy SensorOSCxx-M0W

    1

    OPP20 Super Duty Power PackOPP20-0D1

    1

    Marked Controlled Receptacles5362-2PW

    5

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    12/4412 www.leviton.com/title2412

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    Sapphire LCD TouchscreenTS007-000 | TS007-C0E

    1

    Multi-Tech Ceiling Mount Occupancy SensorOSCxx-M0W

    1

    Marked Controlled Receptacles16352-1PW

    5

    Conference Room Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)- Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    GreenMAXRelay Control System Integrates common sensing, dimming, switching,

    and advanced daylight harvesting applications fromthe same cabinet

    BACnet IP native in each cabinet for seamless BMSintegration

    Industry leading 25,000A Short Circuit CurrentRating (SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control of

    each load individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    13/44www.leviton.com/title24 www.leviton.com/title24

    List of Equipment

    Sector Bus Controller and Power SupplySBC00-000

    1

    Sector Relay

    SBCS0-L00

    3

    Sector Occupancy Sensor, PIR, 450SFOSC04-ISW

    1

    Sector 5-Button Digital SwitchSDS00-15W

    2

    Sector Low Voltage InterfaceSLIQS-000

    1

    Marked Controlled ReceptaclesCR020-1PW

    5

    Conference Room Control Solutionfeaturing SectorDistributed Lighting Control System

    Section 130.1(a)- Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    If required by presence of windows or skylights, addphotocell to comply with 130.1(d) Daylighting

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    SectorDistributed Lighting Control System Topology-free, polarity-free distributed control

    Combines all lighting management functions into a singlesystem with the fewest connection points, simplestinstallation, greatest flexibility, and simple specification

    All components connect directly to the topology free2-wire bus, not the ballast

    Relay controllers allow zone dimming and control forcost-effective system design

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    14/4414

    Classroom Control Solutionfeaturing Integrated Room Control (IRC)

    Section 130.1(a)

    - Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming- Task Tuning- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control(optional in classrooms)

    Notes:

    Demand response required in all buildingslarger than 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    www.leviton.com/title2414

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting,

    0-10V dimming, partial ON, partial OFF, and demandresponse capabilities in a stand-alone package

    Kitted with factory configured sensor, photocell, and4-button switch

    Autocal automatic photocell calibration and LadderlessCommissioning

    Easy automatic closed or open loop multi-zone daylightharvesting control design

    Auto 100 hour burn-in

    List of Equipment

    IRC Kit for 2 Zones, 2 Relays - includes IRC,sensor, photocell, and control stationRCD20-102

    1

    IRC for 2 Zones, 2 RelaysMZD20-102

    Multi-Tech Ceiling MountOccupancy Sensor, 1000SFOSC10-M0W

    Photocell, IndoorODC0P-00W

    Lighting Control Station

    RLVSW-4LW

    Lighting Control StationRLVSW-4LW

    1

    Decora Rocker56081-0xx

    1

    OPP20 Super Duty Power PackOPP20-0D1

    2

    Marked Controlled Receptacles5362-2SW

    5

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    15/44www.leviton.com/title24 www.leviton.com/title24

    Classroom Control Solutionfeaturing LevNet RF Energy Harvesting Wireless Solutions

    Section 130.1(a)- Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control(optional in classrooms)

    Notes:

    Demand response required in all buildings larger than10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    LevNet RF Energy HarvestingSelf-Powered Wireless Solutions No wires to run and no batteries required - install in

    1/4th the timeeliminating time and expense ofcontrol wiring

    Broad range of switches and control modules to meetvirtually any control need including a Receptacle and

    engraved cover plate to meet plug load controlcode requirements

    Enables rapid retrofit with minimal impact

    List of Equipment

    LevNet RF Self-Powered PIROccupancy SensorWSCxx-IRW

    1

    LevNet RF Self-Powered Light SensorWSCPC-00W

    1

    LevNet RF 0-10V DimmerWSD01-010

    3

    LevNet RF Self-Powered Wall SwitchWSS0S-D0W

    1

    OPP20 Super Duty Power PackOPP20-0D1

    3

    Marked Controlled Receptacles5362-1PW

    5

    LevNet RF LAN Access Point& Venergy UI SoftwareWSAP0-TIP

    1

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    16/4416 www.leviton.com/title2416

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    Multi-Tech Ceiling Mount Occupancy Sensor

    OSCxx-M0W

    1

    Photocell, IndoorPCIND-000

    1

    GreenMAX Digital SwitchRDGSW-xDW

    2

    Marked Controlled Receptacles5362-S1W

    5

    Classroom Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)

    - Receptacle Control/Plug Load Control(optional in classrooms)

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    GreenMAXRelay Control System Integrates common sensing, dimming, switching, and

    advanced daylight harvesting applications from thesame cabinet

    BACnet IP native in each cabinet for seamlessBMS integration

    Industry leading 25,000A Short Circuit Current Rating(SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control of each

    load individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    17/44www.leviton.com/title24 www.leviton.com/title24

    List of Equipment

    Sector Bus Controller and Power SupplySBC00-000

    1

    Sector RelaySBCS0-L00

    3

    Sector Occupancy Sensor, Multi-Tech, 2000SFOSC20-MSW

    1

    Sector PhotocellODC0P-0SW

    1

    Sector 5-Button Digital SwitchSDS00-15W

    1

    Sector Low Voltage InterfaceSLIQS-000

    1

    Marked Controlled Receptacles5362-2PW

    5

    Classroom Control Solutionfeaturing SectorDistributed Lighting Control System

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)

    - Receptacle Control/Plug Load Control(optional in classrooms)

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    SectorDistributed Lighting Control System Topology-free, polarity-free distributed control

    Combines all lighting management functions into a singlesystem with the fewest connection points, simplestinstallation, greatest flexibility, and simple specification

    All components connect directly to the topology free2-wire bus, not the ballast

    Relay controllers allow zone dimming and control for cost-effective system design

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    18/4418 www.leviton.com/title2418

    Stairwell Control Solutionfeaturing Integrated Room Control (IRC)

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting, 0-10V

    dimming, partial ON, partial OFF, and demand responsecapabilities in a stand-alone package

    Kitted with factory configured sensor, photocell, and4-button switch

    Autocal automatic photocell calibration and LadderlessCommissioning

    Easy automatic closed or open loop multi-zone daylightharvesting control design

    Auto 100 hour burn-in

    Section 130.1(a)

    - Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Notes:

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    List of Equipment

    IRC for 2 Zones, 2 RelaysMZD20-102

    1

    PIR Wall/Corner Mount Occupancy

    Sensor, Wide ViewOSWWV-I0W 2

    Lighting Control StationRLVSW-4LW

    1

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    19/44www.leviton.com/title24 www.leviton.com/title24

    Common Area Control Solutionfeaturing Integrated Room Control (IRC)

    List of Equipment

    IRC Kit for 2 Zones, 2 Relays - includes IRC,sensor, photocell, and control stationRCD20-102

    1

    IRC for 2 Zones, 2 RelaysMZD20-102

    Multi-Tech Ceiling MountOccupancy Sensor, 1000SFOSC10-M0W

    Photocell, IndoorODC0P-00W

    Lighting Control StationRLVSW-4LW

    Lighting Control StationRLVSW-4LW

    1

    OPP20 Super Duty Power PackOPP20-0D1

    1

    Marked Controlled Receptacles5362-1PW

    5

    Section 130.1(a)

    - Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming- Task Tuning- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)

    - Demand Response Power Reduction Controls Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings larger than10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting,

    0-10V dimming, partial ON, partial OFF, and demandresponse capabilities in a stand-alone package

    Kitted with factory configured sensor, photocell,and 4-button switch

    Autocal automatic photocell calibration andLadderless Commissioning

    Easy automatic closed or open loop multi-zonedaylight harvesting control design

    Auto 100 hour burn-in

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    20/4420

    Common Area Control Solutionfeaturing 1-10V Dimming Photocell

    Section 130.1(a)- Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    List of Equipment

    Photocell, 1-10V DimmingODC0P-D0W

    1

    Multi-Tech Ceiling Mount Occupancy SensorOSCxx-M0W

    1

    Illumatech DimmerIP710-xxx

    1

    Decora Rocker, 3-way

    05633-xxx

    1

    OPP20 Super Duty Power PackOPP20-0D1

    2

    Marked Controlled Receptacles16352-1PW

    5

    1-10V Dimming Photocell Ideal for open and closed loop daylight harvesting

    applications

    Autocal automatic photocell calibration

    www.leviton.com/title2420

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    21/44www.leviton.com/title24

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    Multi-Tech Ceiling Mount Occupancy SensorOSCxx-M0W

    1

    Photocell, IndoorPCIND-000

    1

    GreenMAX Digital SwitchRDGSW-xDW

    2

    Marked Controlled Receptacles16352-1PW

    5

    Common Area Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)- Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    GreenMAXRelay Control System Integrates common sensing, dimming, switching,

    and advanced daylight harvesting applications fromthe same cabinet

    BACnet IP native in each cabinet for seamless BMSintegration

    Industry leading 25,000A Short Circuit CurrentRating (SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control ofeach load individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

    www.leviton.com/title24

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    22/4422 www.leviton.com/title2422

    List of Equipment

    Sector Bus Controller and Power SupplySBC00-000

    1

    Sector RelaySBCS0-L00

    3

    Sector Occupancy Sensor, PIR, 450SFOSC04-ISW

    1

    Sector PhotocellODC0P-0SW

    1

    Sector 5-Button Digital SwitchSDS00-15W

    2

    Sector Low Voltage InterfaceSLIQS-000

    1

    Marked Controlled Receptacles5362-1PW

    5

    Common Area Control Solutionfeaturing SectorDistributed Lighting Control System

    Section 130.1(a)- Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control- Partial-ON/OFF

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.5(d)

    - Receptacle Control/Plug Load Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    At least one controlled receptacle must be installedwithin 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    SectorDistributed Lighting Control System Topology-free, polarity-free distributed control

    Combines all lighting management functions intoa single system with the fewest connection points,simplest installation, greatest flexibility, andsimple specification

    All components connect directly to the topologyfree 2-wire bus, not the ballast

    Relay controllers allow zone dimming and control forcost-effective system design

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    23/44www.leviton.com/title24 www.leviton.com/title24

    Hallway Control Solutionfeaturing Integrated Room Control (IRC)

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting,

    0-10V dimming, partial ON, partial OFF, and demandresponse capabilities in a stand-alone package

    Kitted with factory configured sensor, photocell,and 4-button switch

    Autocal automatic photocell calibration andLadderless Commissioning

    Easy automatic closed or open loop multi-zonedaylight harvesting control design

    Auto 100 hour burn-in

    Section 130.1(a)- Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(e)- Demand Response Power Reduction Controls

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    If required by presence of windows or skylights,add photocell to comply with 130.1(d) Daylighting

    Add VerifEye Submetering Solutions to meetSection 130.5(a)- Service Metering, Disaggregation of Electrical Circuits

    Meets the Following Title 24 Requirements

    List of Equipment

    IRC for 2 Zones, 2 RelaysMZD20-102

    1

    PIR Ceiling Mount Occupancy SensorOSCxx-I0W

    2

    Lighting Control StationRLVSW-4LW

    2

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    24/4424 www.leviton.com/title2424

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx | RHDU1-xxx | RELAY-xxx

    1

    Multi-Tech Ceiling Mount Occupancy SensorOSCxx-M0W

    2

    GreenMAX Digital SwitchRDGSW-xDW

    2

    Hallway Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)- Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(e)- Demand Response Power Reduction Controls

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    GreenMAXRelay Control System Integrates common sensing, dimming, switching,

    and advanced daylight harvesting applications fromthe same cabinet

    BACnet IP native in each cabinet for seamlessBMS integration

    Industry leading 25,000A Short Circuit CurrentRating (SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control ofeach load individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    25/44www.leviton.com/title24

    Parking Garage Control Solutionfeaturing Integrated Room Control (IRC)

    Section 130.1(b)- Multi-Level Controls- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    List of Equipment

    IRC for 2 Zones, 2 RelaysMZD20-102

    1

    PIR Ceiling Mount Occupancy SensorOSCxx-I0W

    x

    Photocell, OutdoorPCOUT-000

    x

    Lighting Control StationRLVSW-4LW

    2

    www.leviton.com/title24

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting,

    0-10V dimming, partial ON, partial OFF, and demandresponse capabilities in a stand-alone package

    Kitted with factory configured sensor, photocell, and4-button switch

    Autocal automatic photocell calibration andLadderless Commissioning

    Easy automatic closed or open loop multi-zone daylightharvesting control design

    Auto 100 hour burn-in

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    26/4426

    Parking Garage Control Solutionfeaturing EZ-MAXPlus Stand-Alone Relay Control System

    Section 130.1(b)

    - Multi-Level Controls- Partial-ON/OFF

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Notes:

    Demand response required in all buildings larger than10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Solution features bi-level HID lighting

    Meets the Following Title 24 Requirements

    EZ-MAXPlus Stand-Alone Relay Control System Centralized building lighting control and daylight harvesting

    in a contractor-friendly, quick to install, simple to configurecompact enclosure

    Low voltage inputs allow connection of photocells,occupancy sensors, low-voltage switches, and digitalswitches for a comprehensive yet easily installed energy

    management solution Built-in astronomical time clock and scheduler

    Auto-detection and auto-assign of installed network switches

    List of Equipment

    EZ-MAX Plus Stand-Alone Relay SystemR08BD-L08

    1

    PIR Ceiling Mount Occupancy SensorOSCxx-I0W

    x

    Photocell, OutdoorPCOUT-000

    x

    Low Voltage Switch, 5-Button00LVS-05W

    2

    www.leviton.com/title2426

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    27/44www.leviton.com/title24 www.leviton.com/title24

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    Multi-Tech Ceiling Mount Occupancy SensorOSCxx-M0W

    x

    Photocell, OutdoorPCOUT-000

    x

    GreenMAX Digital SwitchRDGSW-xDW

    2

    Parking Garage Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Partial-OFF Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Power packs required as needed

    GreenMAXRelay Control System Integrates common sensing, dimming, switching, and

    advanced daylight harvesting applications from thesame cabinet

    BACnet IP native in each cabinet for seamless BMSintegration

    Industry leading 25,000A Short Circuit Current Rating(SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control of eachload individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    28/4428 www.leviton.com/title2428

    Site Lighting Control Solutionfeaturing EZ-MAXPlus Stand-Alone Relay Control System

    Section 130.2(c)

    - Outdoor Lighting Controls- Schedule Based Control

    Notes:

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    No dimming required for the following exceptions:- Pole lights > 24- Non-pole site lighting < 30 Watts- Pole site lighting < 75 Watts- Linear lighting < 4 Watts

    EZ-MAXPlus Stand-Alone Relay Control System Centralized building lighting control and daylight harvesting

    in a contractor-friendly, quick to install, simple to configurecompact enclosure

    Low voltage inputs allow connection of photocells,occupancy sensors, low-voltage switches, and digitalswitches for a comprehensive yet easily installed energymanagement solution

    Built-in astronomical time clock and scheduler

    Auto-detection and auto-assign of installednetwork switches

    List of Equipment

    EZ-MAX Plus Stand-Alone Relay SystemR24BD-L24

    1

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    29/44www.leviton.com/title24 www.leviton.com/title24

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    Outdoor Motion SensorPS200-10W

    4

    Site Lighting Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.2(c)

    - Outdoor Lighting Controls- Schedule Based Control- Partial-OFF Motion Sensing

    Section 130.1(e)- Demand ResponsePower Reduction Controls

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    No dimming required for the following exceptions:- Pole lights > 24- Non-pole site lighting < 30 Watts- Pole site lighting < 75 Watts- Linear lighting < 4 Watts

    GreenMAX Relay Control System Integrates common sensing, dimming, switching, and

    advanced daylight harvesting applications from thesame cabinet

    BACnet IP native in each cabinet for seamless BMSintegration

    Industry leading 25,000A Short Circuit Current Rating(SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control of eachload individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    30/4430 www.leviton.com/title2430

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    PIR High Bay Fixture Mount SensorOSFHU-ITW

    x

    Photocell, IndoorPCIND-000

    3

    GreenMAX Digital SwitchRDGSW-xDW

    2

    Warehouse Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Partial-OFF Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Additional power supply may be needed for sensors

    GreenMAXRelay Control System Integrates common sensing, dimming, switching, and

    advanced daylight harvesting applications from thesame cabinet

    BACnet IP native in each cabinet for seamless BMSintegration

    Industry leading 25,000A Short Circuit Current Rating(SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control of eachload individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    31/44www.leviton.com/title24 www.leviton.com/title24

    Retail Space Control Solutionfeaturing Dimensions4000 Lighting Control System

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.2(c)

    - Outdoor Lighting Controls- Schedule Based Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Dimensions4000Architectural Lighting Control System Offers both stand-alone and integrated room dimming

    and control

    LED compatible with power extender

    Complete multi-event scheduler and integratedastronomical time clock

    Interfaces with HVAC, emergency, time clock, and loadshed auxiliary systems

    List of Equipment

    Dimensions D4206 Multi-ZoneArchitectural Lighting Control SystemD4206-1LW

    1

    Track Light Limiting Panel (TLLP)Gxxxx-1xx

    1

    Photocell, 1-10V DimmingODC0P-D0W

    1

    Power ExtenderPE300-D0W

    4

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    32/4432 www.leviton.com/title2432

    Retail Space Control Solutionfeaturing EZ-MAXPlus Stand-Alone Relay Control System

    Section 130.1(a)

    - Area Controls- Manual ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    Meets the Following Title 24 Requirements

    EZ-MAXPlus Stand-Alone Relay Control System Centralized building lighting control and daylight harvesting

    in a contractor-friendly, quick to install, simple to configurecompact enclosure

    Low voltage inputs allow connection of photocells,occupancy sensors, low-voltage switches, and digitalswitches for a comprehensive yet easily installed energymanagement solution

    Built-in astronomical time clock and scheduler

    Auto-detection and auto-assign of installed network switches

    List of Equipment

    EZ-MAX Plus Stand-Alone Relay SystemR24BD-L24

    1

    Track Light Limiting Panel (TLLP)Gxxxx-1xx

    1

    Renoir II DimmerAWSMT-7xx

    2

    Photocell, IndoorPCIND-000

    1

    Low Voltage Switch, 5-Button00LVS-05W

    2

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    33/44www.leviton.com/title24 www.leviton.com/title24

    List of Equipment

    GreenMAX Relay Control SystemRxxTC-100 | RPMxx-xxx | Rxxxx-xxx| RHDU1-xxx | RELAY-xxx

    1

    Track Light Limiting Panel (TLLP)Gxxxx-1xx

    1

    Photocell, IndoorPCIND-000

    1

    GreenMAX Digital SwitchRDGSW-xDW

    3

    Retail Space Control Solutionfeaturing GreenMAXRelay Control System

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Section 130.1(e)- Demand Response Power Reduction Controls

    Section 130.2(c)- Outdoor Lighting Controls- Schedule Based Control

    Notes:

    Demand response required in all buildings largerthan 10,000SF

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    GreenMAXRelay Control System Integrates common sensing, dimming, switching, and

    advanced daylight harvesting applications from thesame cabinet

    BACnet IP native in each cabinet for seamlessBMS integration

    Industry leading 25,000A Short Circuit Current Rating(SCCR) at 277V

    Integrated 0-10V dimming/switching relay Built-in override switch allows manual control of each

    load individually

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    34/4434 www.leviton.com/title2434

    Restaurant Control Solutionfeaturing Dimensions 4000 Lighting Control System

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.1(d)- Daylighting

    Notes:

    Add VerifEye Submetering Solutions tomeet Section 130.5(a) - Service Metering,

    Disaggregation of Electrical Circuits

    Power Extenders required for 0-10V LED lighting

    Dimensions4000Architectural Lighting Control System Offers both stand-alone and integrated room

    dimming and control

    LED compatible with power extender

    Complete multi-event scheduler and integratedastronomical time clock

    Interfaces with HVAC, emergency, time clock,and load shed auxiliary systems

    List of Equipment

    Dimensions D4206 Multi-ZoneArchitectural Lighting Control SystemD4206-1LW

    1

    Multi-Technology Ceiling MountOccupancy SensorOSCxx-M0W

    1

    Low Voltage Switch, 5-Button00LVS-05W

    2

    Photocell, 1-10V DimmingODC0P-D0W

    2

    Power ExtenderPE300-D0W

    2

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    35/44www.leviton.com/title24 www.leviton.com/title24

    Hospitality Control Solutionfeaturing LevNet RF Energy Harvesting Wireless Solutions

    Section 130.1(a)

    - Area Controls- Manual-ON/OFF

    Section 130.1(b)- Multi-Level Controls- Dimming

    Section 130.1(c)- Shut-Off Requirements- Occupancy Control

    Section 130.5(d)- Receptacle Control/Plug Load Control

    Notes:

    At least one controlled receptacle must be installed

    within 6 ft. of each uncontrolled receptacle or a splitduplex can be used

    Add VerifEye Submetering Solutions to meet Section130.5(a) - Service Metering, Disaggregation ofElectrical Circuits

    List of Equipment

    LevNet RF 902 MHz ThermostatWS0TH-L9W

    1

    Key Card SwtchHKSWP-0DX

    1

    LevNet RF 902 MHz Wall Switch ReceiverWSS20-N9N

    1

    LevNet RF 902 MHz Relay ReceiverWSP20-9D0

    1

    LevNet RF 902 MHz ReceptacleWSG15-x9W

    2

    Decora PIR Wall Switch Sensor withLED NightlightOSSNL-IDW

    1

    LevNet RF Energy HarvestingSelf-Powered Wireless Solutions No wires to run and no batteries required - install in

    1/4th the timeeliminating time and expense ofcontrol wiring

    Broad range of switches and control modules to meetvirtually any control need including a Receptacle andengraved cover plate to meet plug load controlcode requirements

    Enables rapid retrofit with minimal impact

    Meets the Following Title 24 Requirements

    FEATURED LEVITON TITLE 24 SOLUTION

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    36/4436 www.leviton.com/title2436

    Energy Metering Solutionfeaturing VerifEye Submetering Solutions

    Section 130.5(a)- Service Metering, Disaggregation

    of Electrical Circuits

    Notes:

    Contact your local Leviton Lighting Control Specialistfor Title 24 compliant design assistance.

    Meets the Following Title 24 Requirements

    VerifEye Submetering Solutions Comprehensive line of submeters, communication

    products, and software solutions

    Simple installation in new or existing facilities

    Measurement & Verification (M&V) capabilities withdata collection and storage

    Ideal for real-time energy monitoring andtenant billing

    Integrate with Building Management Systems forenergy efficiency and savings

    Meets separation of load requirements with theability to measure various loads

    FEATURED LEVITON TITLE 24 SOLUTION

    Series 8000 Multi-PointHigh Density Meter

    EMH+ All-in-OneMeter and Hub

    LAN

    BillSuiteTenant BillingSoftware

    BMO 2.0Energy Monitoring Software

    Energy ManagerEnergy Monitoring Software

    Cloud

    List of Equipment

    Series 8000 Phase Config Multi-PointHigh Desnsity MeterS8xxx-xxx*

    1

    EMH+ All-in-One Meter and HubA8814-xxx*

    1

    *Series 8000 Multi-Point High Density Meter and EMH+ All-in-One Meterand Hub are available in multiple configurations.See data sheets for more information.

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    37/44www.leviton.com/title24 www.leviton.com/title24

    Leviton Solutions for Title 24 Code Compliance

    Partial List of Title 24 2013 Requirements

    LevitonSolutions A

    reaControl

    EgressLighting

    EmergencyLigh

    ting

    (UL924)

    Multi-Level

    LightingContro

    ls

    AutomaticShut

    -Off

    Display/Retail

    Lighting

    Daylighting

    DemandRespon

    se

    ExteriorLight

    Control

    SignLighting

    Controls

    HVACOccupanc

    y

    Controls

    ReceptacleCon

    trol

    (PlugLoadCont

    rol)

    EnergyMetering

    Residential

    Dimmers X - Xd X - Xb - - - - - - -

    Vacancy Sensors - X Xd X X - - - - - X X -

    Occupancy Sensors X X Xd X X - - - - - X X -

    Humidity Sensors - - - - X - - - - - X - -

    Programmable Timer Switch X - - - X - - - X - - - -

    Non-Residential

    Vacancy Sensors - X Xd X X - - - - - X X -

    Occupancy Sensors X X Xd X X - - - - - X X -

    Dimmers X - Xd X - Xb - - - - - - -

    Dimensions4000Lighting Controls

    X - Xd X Xa - - X X X - - -

    Dimensions8000Lighting Controls

    X - Xd X Xa - - X X X - - -

    a-2000Dimming Cabinets X X Xd X Xa Xb - X X X - X -

    LevNet RFEnergy Harvesting

    Wireless Controls

    X Xe - Xe Xe - Xe - X X X Xe -

    Integrated Room Control(IRC)

    X Xb Xd X Xa X Xb X X X X Xb -

    EZ-MAXPlus Stand-AloneRelay System

    X Xb Xd X Xa Xb Xc - X X X Xb -

    GreenMAXRelayControl Systems

    X Xb Xd X Xa Xb Xb X X X X Xb -

    Track Light Limiting Panel (TLLP) - - - - - X - - - - - - -

    SectorFlex X Xb Xd X Xa Xb Xb X X X X Xb -

    SectorDistributedLighting Control

    X Xb Xd X Xa Xb Xb X X X X Xb -

    VerifEye Submetering

    Solutions- - - - - - - X - - - - X

    Marked ControlledReceptacles

    - - - - - - - - - - - X -

    X = Solutions help spaces comply with the code requirement when used appropriatelyXa = Use with Leviton occupancy sensorXb = Use with Leviton daylight sensorXc = Use with Leviton daylight sensor (switched dimming only)Xd = Use with Leviton Emergency luminaire control (UL924)Xe = Use with Leviton LevNet RF Occupancy Sensor and/or Daylight Sensor

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    38/4438 www.leviton.com/title24

    Leviton Solutions Interface Method

    Integrated Room Control (IRC)* Interface is through contact closure

    GreenMAX* Interface is through contact closure

    Sector* Interface is through contact closure.

    Dimensions D4200 controls Use KCLCM to provide contact closure type interface

    Dimensions D8000 controls Use KCLCM to provide contact closure type interface

    a-2000 ** Demand response interface would be dependent on the controls used

    Other Dimmer Cabinets ** Demand response interface would be dependent on the controls used

    *Leviton solution requires the device that would receive the Demand Response Signal from the utility to be supplied by other. The demand response interfacedevice must have the capability to provide a contact closure or control signal to a Class C relay that can be used to provide contact closure to the Levitonlighting control system.

    ** Leviton solutions might require the device that would receive the Demand Response Signal from the utility to be supplied by other. The demand responseinterface device must have the capability to provide a contact closure or control signal to a Class C relay that can be used to provide contact closure to theLeviton lighting control system.

    Leviton Solutions for Demand Response Capabilities

    38

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    39/44www.leviton.com/title24 www.leviton.com/title24

    Leviton Residential Solutions for Title 24 Code Compliance

    Universal Dimming Control Designed to optimize performance with all classes of lamps

    dimmable LED, dimmable CFL, and incandescent

    Smooth operation for precise dimming, low-level starting, and flicker-free operation

    Universal Sensing Control Manual-ON or Auto-ON options for vacancy and occupancy sensors

    Universal dimming sensor

    Humidity sensor and fan control detects excess humidity in a room and automaticallyactivates the ventilation fan to reduce excess condensation

    Leviton Non-Residential Solutions for Title 24 Code Compliance

    Sensing Control Broadest range of sensors for any application

    Provolt integrates occupancy sensing, daylight harvesting, and manual-ON/auto-OFFoverride control in a single unit - no special control stations required

    Plug load control with OPP20 Super Duty Power Pack

    24V AC/DC input for integration with HVAC/BAS systems Industry leading layout and application services

    RenoirII Commercial Architectural Wall Box Dimmers Universal voltage 120-277V, 60Hz

    Supports virtually all common load types without power extenders

    Multi-location dimming up to 5-way dimming

    Low voltage dimming control for LEDs

    Patented Super-Silent Fan Control Technology (SST)

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    40/4440 www.leviton.com/title2440

    Sapphire Architectural Lighting Controls Modern touchscreen user interface integrates with multiple Leviton lighting control systems

    Online and offline configuration

    Supports multiple interfaces - LumaCAN, Ethernet, A/V, HVAC,wireless (LevNet RF), and analog systems

    Software update through USB interface behind front panel

    DimensionsD4000 and D8000 D4000 controls offer both stand-alone and integrated room dimming and control

    D8000 systems provide distributed control of up to one thousand channels plus

    LED compatible with power extender

    Complete multi-event scheduler and integrated astronomical time clock

    Interfaces with HVAC, emergency, time clock, and load shed auxiliary systems

    a-2000Dimming Cabinets Single dimming source for a broad range of loads

    Plug-in dimmer modules for easy maintenance

    Rugged dual-SCR dimmer circuitry for superior dimming performance and reliability

    Contractor-friendly design with a large wiring space for easy installation Communication inputs include DMX512, Luma-Net III, RS-485, full bright, emergency,

    and +0-10VDC analog for versatility

    LevNet RF Energy Harvesting Wireless Solutions No wires to run and no batteries required - install in 1/4th the timeeliminating time and

    expense of control wiring

    Broad range of switches and control modules to meet virtually any control need

    Enables rapid retrofit with minimal impact

    Integrated Room Control (IRC) Combines occupancy sensing, daylight harvesting, 0-10V dimming, partial ON,

    partial OFF, and demand response capabilities in a stand-alone package

    Kitted with factory configured sensor, photocell, and 4-button switch Autocal automatic photocell calibration and Ladderless Commissioning

    Easy automatic closed or open loop multi-zone daylight harvesting control

    Auto 100 hour burn-in

    EZ-MAXPlus Stand-Alone Relay System Centralized building lighting control and daylight harvesting in a contractor-friendly,

    quick to install, simple to configure compact enclosure

    Low voltage inputs allow connection of photocells, occupancy sensors, low-voltage switches,and digital switches for a comprehensive yet easily installed energy management solution

    Built-in astronomical time clock and scheduler Auto-detection and auto-assignof installed network switches

    Leviton Non-Residential Solutions for Title 24 Code Compliance

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    41/44www.leviton.com/title24 www.leviton.com/title24

    Leviton Non-Residential Solutions for Title 24 Code Compliance

    Track Light Limiting Panel (TLLP) Prevents overloaded circuits

    Provides tamper-proof current limiting protection for track lighting

    Sets a fixed power consumption limit for designer lighting installations by usingthe volt amperage rating of the breaker instead of watts per linear feet

    Factory configured to customer specifications arrives ready to install Reduces installation costs

    No programming required

    GreenMAXRelay Control System Integrates common sensing, dimming, switching, and advanced

    daylight harvesting applications from the same cabinet

    BACnet IP native in each cabinet for seamless BMS integration

    Industry leading 25,000A Short Circuit Current Rating (SCCR) at 277V

    Integrated 0-10V dimming/switching relay

    Built-in override switch allows manual control of each load individually

    Programming is done with preset Behaviors via the industry-exclusiveHandheld Display Unit (HDU)

    SectorDistributed Lighting Control System Topology-free, polarity-free distributed control

    Combines all lighting management functions into a single system with the fewestconnection points, simplest installation, greatest flexibility, and simple specification

    High performance Sector ballasts offer 1% dimming performance

    All components connect directly to the topology free 2-wire bus, not the ballast

    Relay controllers allow zone dimming and control for cost-effective system design

    VerifEye Submetering Solutions Comprehensive line of submeters, communication products, and software solutions

    Simple installation in new or existing facilities

    Measurement & Verification (M&V) capabilities with data collection and storage

    Ideal for real-time energy monitoring and tenant billing

    Integrate with Building Management Systems for energy efficiency and savings

    Meets separation of load requirements with the ability to measure various loads

    Marked Controlled Receptacles Meets requirements for identifying receptacles that will automatically be de-energized

    as part of an overall plug load control program

    2014 NEC requires all 15A and 20A, 125V receptacles that are automatically controlledto be marked with a specific symbol ()

    Ideal for new construction and renovation applications

    Available in back and side wired, side wired standard, tamper-resistant and Decoraversions

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    42/444242 www.leviton.com/title24

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    43/44www.leviton.com/title24 www.leviton.com/title24

    Service and Support During Every Step of the Process

    There is much more to making lighting more energy efficient than just installing a simple device or two. System design,

    product selection, installation and service: it has all got to come together. Thats where Leviton service and supportoptions come in. Well help you design your system and make the right product selections so you can create a lightingcontrol system that does exactly what you want it to do while saving electricity, meeting codes and standards, and evengarnering rebates.

    It all starts with the Leviton sales representative. Our lighting control specialists are here to support you every step ofthe way. They can perform on-site facility audits and suggest specific products and strategies for improving lightingenergy efficiency.

    Exclusive Wealth of Resources Exclusive Training - contact your local Leviton representative to have a Title 24 expert provide training in person or

    online exclusively for your team

    Title 24 App - simplifies Title 24 lighting control requirements and provides examples for common applications

    - available for Android and Apple devices Dollars & SensorsOnline Energy Audit Tool - makes energy audits easier than ever - use your smart device

    (Android, Apple, Windows or Blackberry) to enter audit information and your desktop to generate ROI reports,analyses, Bill of Materials, and a submittal package - go to www.leviton.com/dollarsandsensors

    Occupancy sensor layout services have a team of experts create occupancy sensor layouts directly on yourCAD drawings, complete with a List of Equipment at no cost go to portal.leviton.com

    LightLoggerProgram get an accurate estimate of your energy-savings potential with this exclusive payback analysistool go to www.leviton.com/logger

    ez-Learn get Leviton smart from the comfort of your home or office with this exclusive 24/7 online training go to www.leviton.com/ezlearn

    ASAP Lighting Design software point-and-click software allows you to quickly and simply design, specify andenter orders go to www.leviton.com/asap

    Find more exclusive no cost design tools at www.leviton.com/lesdesign

    Lighting control specialists at your disposal Field service engineers for top-level support

    Factory commissioning service

    Dedicated technical support via phone at 800 959-6004

    Contact your local Leviton Lighting Control Specialistfor Title 24 compliant design assistance.

  • 7/18/2019 UTF-8'en-us'Title 24 Design Guide 2015

    44/44

    Leviton Manufacturing Co., Inc. Lighting & Energy Solutions20497 SW Teton Avenue, Tualatin, OR 97062tel 503-404-5500 fax 503-404-5594

    tech line (6:00am4:00pm PST Monday-Friday) 800-959-6004

    Leviton Manufacturing Co., Inc. Global Headquarters201 N. Service Rd., Melville, NY 11747-3138tech line 1-800-824-3005 fax 1-800-832-9538

    G-9327BA/C15-tb

    REV MAR 2015

    Visit our Website at: www.leviton.com/title24