USER’S OPERATING MANUAL FOR DIGITAL COUNTER
(Models: KCN - 448/778/998/668/888 )
SAFETY INSTRUCTIONThis controller is meant for counter applications. It is important to
read the manual prior to installing or commissioning of controller.
All safety related instruction appearing in this manual must be
followed to ensure safety of the operating personnel as well as
the instrument.
GENERALv The controller must be configured correctly for intended
operation. Incorrect configuration could result in damage to
the equipment or the process under control or it may lead
personnel injury.v The controller is generally part of control panel and in such a
case the terminals should not remain accessible to the user
after installation.
MECHANICALv The Controller in its installed state must not come in close
proximity to any corrosive/combustible gases, caustic
vapors, oils, steam or any other process by products.v The Controller in its installed state should not be exposed to
carbon dust, salt air, direct sunlight or radiant heat.v Ambient temperature and relative humidity surrounding the
controller must not exceed the maximum specified limit for
proper operation of the controller.v The controller in its installed state must be protected against
excessive electrostatic or electromagnetic interferences.
Ventilation holes provided on the chassis of the instrument
are meant for thermal dissipation hence should not be
obstructed in the panel.
ELECTRICALv The controller must be wired as per wiring diagram & it must
comply with local electrical regulation.v Care must be taken not to connect AC supplies to low voltage
sensor input.v Circuit breaker or mains s/w with fuse (275V/1A) must be
installed between power supply and supply terminals to
protect the controller from any possible damage due to high
voltage surges of extended duration.v Circuit breaker and appropriate fuses must be used for
driving high voltage loads to protect the controller from any
possible damage due to short circuit on loads.v To minimize pickup of electrical noise, the wiring for low
voltage DC and sensor input must be routed away from high
current power cables. Where it is impractical to do this, use
shielded ground at both ends.v The controller should not be wired to a 3-Phase supply with
unearthed star connection. Under fault condition such supply
could rise above 264 VAC which will damage the controller.v The Electrical noise generated by switching inductive loads
might create momentary Fluctuation in display, alarm latch
up, data loss or permanent damage to the instrument. To
reduce this use snubber circuit across the load.
SPECIFICATIONS: Display : 4 digit, height 0.56" 4 digit, height 0.39"
LED Indications : a] Output (OP1 & OP2)
b] Batch
c] Auto Reset time
No. of Set points : 1
settings : Through Keyboard
Range : 1 to 9999 counts 1 to 9999 Batch
Reset : a) Front Switch (Programmable)
b) Remote Reset (Via Rear terminals)
Timing Accuracy : 0.05% Full Scale
Repeat Accuracy : 0.01%
Outputs : 5 Amp @ 230VAC Relay (1C/O) x 2
Reset : a] Front switch (Programmable) b] Remote Reset (via rear terminals) C] On power interruption(Programmable)
2 Memory : Non-Volatile (E prom)
Memory Retention : Up to 10 years
Relay Outputs : 5 Amp @230VAC Relay (1C/O) x 2
Sensor Supply : 12 VDC (+10%) @ 50mA
Supply : 90 to 270 VAC
Mounting : Panel
Housing : ABS PlasticO OP. Temperature : O~55 C
Humidity : 95% RN (Non Condensing) CONFIGURABLE PARAMETERS:
Maximum I/P freq. : (a) Low
(For DC I/P) (b) Medium
(C) High
Count Direction : Up / Down
Function : On delay / Off delay
Counter Operating : (a) Latch O/P
Mode (b) Auto Reset
(c) Time Pulse Repeat (TPR)
Over Run : Enable / Disable
Front Reset : Enable / Disable
Hold I/P : Enable / Disable
Memory Back up : Enable / Disable
Scaler (settable ) : 0.001 to 999
Output 2 Function : a) Auxiliary Contact
B) Batch Mode
1 Document Name : OIM KCN-XX8(Ver 2.0) Page 1 of 6
MODEL:-KCN-448/KCN-778/KCN-998/ KCN-888/KCN-668
OVER ALL DIMENSIONS & PANEL CUT OUT (IN MM)
TABLE : 1
ModelDim
48
72
96
48
96
48
72
96
96
48
8
10
10
10
10
85
65
65
65
65
44
68
92
92
44
44
68
92
44
92
9
9
9
9
9
A B HC D F GE
43
66
89
43
89
KCN-448
KCN-778
KCN-998
KCN-888
KCN-668
MECHANICAL INSTALLATIONThe label on the controller identifies the serial number, wiring connections and batch number.
INSTALLATION GUIDELINES
1. Prepare the cut-out with proper dimension as shown in figure. 2. Remove clamp from controller 3. Push the controller through panel cut-out and secure the
controller in its place by tightening the side clamp.
E
DC H
A
B
F
G
PANELCUTOUT
ELECTRICAL INSTALLATION
A
B DC H
E
G
FPANELCUTOUT
B
A E
DC H
G
FPANEL
CUTOUT
CAUTION: To prevent the risk of electrical shock, switch off the power before making/removing any connection or removing the controller from its enclosure.
SUPPLY
L
N
1 2 3 4 5 6
7 8 9 10 11 12
15
16
13
14
NO NCCM
RELAY1
SSR1
NO NCCM
RELAY2
1 2 3 4 5 6
10 11 12 13 14 15 16 17 18
7 8 9
NO NCCM
RELAY1
SSR1
NO NCCM
RELAY2SUPPLY
L N
1 2 3 4 5 6
109 11 12 13 14 15 16
7 8
NO NCCM
RELAY1
SSR1
SUPPLY
L N
KCN-778 KCN-998 KCN-668/KCN-888
FRONT PANEL LAYOUT
SSR2
BZR
NO NCCM
RELAY2
SSR2
BZRSSR2
BZR
PNPNPN
+12V +12VI/P1 I/P1I/P2 I/P2GND GNDRST RST +12V I/P1 I/P2 GND RST
NPN
2 Document Name : OIM KCN-XX8(Ver 2.0) Page 2 of 6
SUPPLY
L N
1 2 3 4 5
7 8 9 10
11
12 15
1613
14
NO1 NC1CM1
RELAY1
SSR1
KCN-444
NO
NC
CM
RE
LA
Y2
SS
R2
BZ
R
PNP
+12V I/P1 I/P2 GND RST
6
KCN-668
RL1 RL2 Rt Batch
RST
-counti KCN-94
1
2
43
86 75
KCN-448
RL1 RL2 Rt Batch
RST
KCN-44-Count
1
2
43
86 75
KCN-998
KCN-99-count
RL2
Rt
Batch
RL1
RST
1
2
43
86 75
KCN-888
RL2
Rt
Batch
RL1
-Counti KCN-49
RST
1
2
4
3
8
6
7
5
UpperDisplay
LowerDisplay
STATUSLED
SETKEY
UPKEY
DOWNKEY
SHIFTKEY
NO. NAME FUNCTION
(1) For count Setting. To access Configuration mode at power on. To scroll the parameter & to store its value.
(2) (3)
RL1 Glows when OP1 is ON & RL2 Glows when OP2 is ON. time running. Batch Led Glows when OP2 is configure in Batch mode & flashes while actual batch count display.
Rt Led flashes when Auto reset OR T.P.R
It will display Set count in run mode. Parameter in program mode.(1) (2)
It will display Actual set count in run mode. Sub Parameter in program mode.(1) (2)1
2
3 & 4
5
6
7
8
KCN-778
-count KCN-77
RL1
RL2
Rt
Batch
RST
1
2
43
86 75
(1) To decrease / alter parameter value in program mode. (2) To reset the counter
To increase/alter parameter value in program mode.
To select the particular digit for increment and decrement.
PARAMETER
DESCRIPTION DEFAULTLOWER
DISPLAYUPPER
DISPLAY
This option doesn't appear if the dot position for scale is at 4th position. User can set screen resolution for RUN Mode.
Resolution
If selected this by the user, In run mode the display will show the counting with out any Decimal Point.
This parameter occurs only if Auto Reset/TPR mode is selected, in Mode1. User can select from Bach/Auxiliary operation for 2nd o/p. In case of latched o/p Auxiliary mode is selected by default.
AUXILIARY: If selected , OP2 can be used as Auxiliary contact. Both the relay output will
ON/OFF together as per the ON/OFF Delay.
nd 2 Output
ModeBatch
NONE
nd 2 Output
BatchEnable
BatchReset
Enable
ENABLE: If selected; when in view mode, user can reset the bach count by pressing down key located at front panel for 3sec.
This feature is useful to avoid unauthorized attempt to reset the bach count during run mode.
This parameter occurs only if bach operation is selected for 2nd o/p. This parameter lets the user enable/disable the bach count reset from down/reset key.
DISABLE: If selected ; user can not reset the bach count by pressing down key located at front panel.
BATCH: If selected , Output2 used as a Batch mod. When Batch count EQUAL S.Bch output2
will on & the output of second relay will remain ON until user press the reset key for 3second
when Batch count displyed.
ENABLE: If selected; when in set mode, user can set the Bach count by using UP/DOWN/SHIFT Key
This feature is useful to avoid unauthorized attempt to change the Bach count during run mode.
This parameter occurs only if bach operation is selected for 2nd o/p. This parameter lets the user enable/disable the Bach count setting in 'set mode'.
DISABLE: If selected; In set mode user can only view the Bach count setting but cannot change the value.
5 Document Name : OIM KCN-XX8(Ver 2.0) Page 5 of 6
By pressing set key in Run Mode display shows batch count. while a showing batch if reset key is pressed than only batch count will reset to zero
Batch ResetCount Reset
If front Reset is enable then after set count by pressing the RST Key count reset to zero & Relay change its status. If reset key is press before set count then only count reset to zero RLY status not changed.
Reset function
UP Counting Down Counting
On reset display shows 0000. At each count pulse Counter increment count upwards towards the set point. At set point display shows TW value. (If non over run selected)
SET
O
Count Value
On Reset display shows TW Value At each count pluse counter decrement count downwards from the set point to Zero.
SET
O
Count Value
The O/P is energised at the end of the counting cycle. (When the number of pulses received equal to set value) Relay remain on till the unit is reset
UP Counting
SET
O
Count Value
RLY 1
RST
The O/P is energised at the start of the counting cycle and de-energizedat its completion. (When the number of pulses received equal to set count)Relay remain off till the unit is reset.
Up Counting
SET
O
Count Value
RLY 1
RST
ON Delay OFF Delay
Count Direction
Delay Mode
O/P Mode
Over Run mode
In overrun mode the counter continued counting after the set value has been crossed.
2nd O/P Mode
2nd RLY can be configuring as an o/p for a batch counter. In Autoreset or TPR mode,whenever the number of pulses received equal to set value batch counter increments by one. when batch count equals to the set Batch count 2nd RLY energizes & remain on till the unit is reset.
O
RLY 1
SET
a) Auxiliary :- 2nd RLY can be used as a Auxiliary contact.
b) Batch :
After set count display shows TW Value (if UP Counting) or 0000 (if down counting) & Relay changes its status accordingly ON & OFF delay & remain in this condition, until reset key or rear reset pressed. (NOTE : Batch counting is not valid in this mode)
SET
O
Count Value
RLY 1
Latch O/P Mode(up counting & on delay)
Auto Reset Mode
The O/P (relay) changes state (according to the on delay or off delay mode selected) at the end of the count cycle, for the auto reset time after which the counter automatically reset and begins the next count cycle. The unit remains reset for the programmed auto reset time duration and resumes operation after this period has elapsed
SET
O
Count Value
RLY 1AR AR = Auto Reset Time
(up counting & on delay)
After set count RLY changes its status accordingly ON or OFF delay. For a programed pulse time(t) at the end of the count cycle, the count automatically reset & count cycle repeats. Process counting continues uninterrupted during pulse time.
Time Pulse Repeat Mode
(up counting & on delay)
SET
O
Count Value
RLY 1TPRTPR = Time Pulse Repeat
O
RLY 1
SET
RLY 2
6 Document Name : OIM KCN-XX8(Ver 2.0) Page 6 of 6
USER GUIDE
338, New Sonal Link Service Ind. Est. no.2 , Link Road, Malad (W), Mumbai - 400064. Tel: 022-66939916/17. Fax: 022-66939918 E-mail:[email protected] ; Website: innovativeinstruments.co.in
Mfgd by: Innovative InstrumentsPrecision unrivalled
DelayMode
ON
User can select among ON Delay / OFF Delay Mode described as follows,
ON DELAY: During Counter is in run mode; both Relay O/Ps still remain de-energised(OFF). At the completion of count ; both O/Ps change its state(ON) & remain in that state until user press RESET or next cycle begins(in auto reset mode & TPR mode).
OFF DELAY: During Counter is in run mode; Both Relay O/Ps get energized (ON). At the completion of count ; both relay O/Ps change its state (OFF) & remain in that state until user press RESET or next cycle begins(in auto reset mode & TPR mode).
PROGRAMMINGUSER LIST : To access the user list press SET key once.(All following selected parameter’s code as shown in shaded will be displayed for01 sec. followed by their values / options)
CONFIGURATION MODE: 1. TO ENTER IN THIS MODE: PRESS AND HOLD DOWN "SET" KEY FOR 3 SEC. AT POWER ON.2."CNFG", "LIST" MESSAGE WILL BE DISPLAYED ON UPPER & LOWER DISPLAY RESPECTIVELY AND IT WILL REMAIN STEADY FOR 3 SEC. NOW UNIT WILL ALLOW THE USER TO CONFIGURE DIFFERENT PARAMETERS WITH OPTIONS AS DESCRIBED BELOW. 3. PRESS UP OR DOWN KEY TO SCROLL BETWEEN THE PARAMETER OPTIONS. 4. USE Up/Down/Shift KEY TO SET NUMERIC VALUES OF THE PARAMETERS.ALL FOLLOWING SELECTED PARAMETER CODE AS SHOWN IN SHADED WILL BE ON THE LOWER DISPLAY AND THEIR OPTIONS VALUE WILL BE DISPLAYED ON THE UPPER DISPLAY.
In normal mode, The lower display shows the value of 'set count' while the upper display shows the actual value of count (in accordance with the scale) given at the input terminal. If 'Front reset' is enable than the value of count can be reset by pressing reset/dn key.
In normal mode, Press the 'up' key to view the present value of Bach count. 'B.CNT' will be displayed on the lower display & the present value of 'Bach count' will be displayed on the upper display. The Bach led flashes every 500ms to indicate' view mode'. If batch reset is enabled than the Bach count can be reset by pressing the reset/dn key for 3 sec. Press the 'set' key or wait for 3sec to exit this mode.
Count Direction
UP
Input Frequency
User can select an option from Very Low/Low/Med/High according to the frequency of count pulse at the input terminal. This feature is useful in avoiding noise signal.
PARAMETER
DESCRIPTION DEFAULTLOWER
DISPLAYUPPER
DISPLAY
THIS PARAMETER ALLOWS USER TO SET COUNTING DIRECTION FOR RUN MODE AS FOLLOWS:
UP COUNTING: If selected; counting starts from 0000 up to set count in ascending order.
DOWN COUNTING: If selected; counting starts from set count to 0000 in descending order.
CAUTION: The stored value of count (if any) resets on changing the direction off counting.
SET MODE
RUN MODE
VIEW MODE
PARAMETER
RANGE DESCRIPTION DEFAULT
In RUN mode, Press the 'set' key to set the desired count value. 'S.CNT' will be displayed on the lower display & last stored/default value of 'set count' will be displayed on the upper display. User can change this value by using Up/Down/Shift key. Press the 'set' key to store the desired value & move to next parameter (in case of auto reset ot TPR mode) or the RUN mode. 'Set count' decimal value will be set depending on the screen resolution.
Set Batch
Set Count
0 - 9999
1
This parameter occurs after the above parameter, if 'Auto reset' or 'TPR' is selected as output mode. 'S.BCH' will be displayed on the lower display while the last stored/default value of 'Bach' will be displayed on the upper display. This value can be changed by using Up/Down/Shift key. Press the 'set' key to store the desired value and enters the 'run' mode again.
LOWERDISPLAY
UPPERDISPLAY
D e p e n d s on screen resolution
1
0
0
Count
Bachcount
Dependson screenresolution
LOW
Dependson screenresolution
LOW FREQUENCY: If selected; COUNT INPUT FREQUENCY UP TO 10Hz.
VERY LOW FREQUENCY: If selected; COUNT INPUT FREQUENCY UP TO 3Hz.
MEDIUM FREQUENCY: If selected;; COUNT INPUT FREQUENCY UP TO 100HZ.
HIGH FREQUENCY: If selected; COUNT INPUT FREQUENCY UP TO 1KHz.
3 Document Name : OIM KCN-XX8(Ver 2.0) Page 3 of 6
OutputMode
User can select Output mode among LO/TPR/Auto Reset described as follows,
TOGGLE OUTPUT MODE: If selected ; when actual counts reaches its set value ,Relay O/Ps will get l changes its state.
AUTO RESET OUTPUT MODE : When relay contacts change its state after the set value of count has been reached; it will remain in same position & wait for end of auto reset time(it can be set by user). On completion of this time, counter will reset i.e. relay contact positions initialize depending on 'ON' or 'OFF' Delay mode selected &counter will start counting again. There are two different modes of operation in auto reset mode.
PARAMETER
DESCRIPTION DEFAULTLOWER
DISPLAYUPPER
DISPLAY
Mode 2Time
FrontReset
Enable
This parameter lets the user enable/disable the count reset from down/reset key.
DISABLE: If selected; user can not reset the counter by pressing down key located at front
panel. Only remote reset at back terminal is allowed. This feature is useful to avoid unauthorized
attempt to reset the counter during run mode.
ENABLE: If selected; user can reset the counter by pressing down key located at front panel.
Auto ResetTPR OUTPUT MODE: If selected; when relay contacts change its state after the set value of count has been reached; Relays will remain in this state for 'TPR' time (it can be set by user). On completion of this time, relay contact positions initialize depending on 'ON' or 'OFF' Delay mode selected. Unlike Auto reset mode, counting continues during the TPR time. There are two different modes of operation in TPR mode.
MOD1
MODE 2: In TPR Mode2, User ca set two different ON/OFF time for both relay output as per the ON/OFF Delay.
MODE 1: If selected; user can set 'Auto Reset/TPR' time. The On/OFF time for first relay output
is same as 'Auto Reset/TPR' time. In case of auxiliary operation, 2nd relay will have same on/off
time.(if used for Bach operation 2nd relay remains on after set Bach count has been reached)
This parameter occurs only if 'Auto Reset 'or 'TPR' mode is selected. User can select any one of
the two modes described below:
Mode ForTPR Time
OR
This parameter occurs only if Latch o/p mode is selected. User can enable/disable counting after set value of count is reached.
Enable: If selected; counting continues after the set value of count is reached. Only the o/p remains latched thereafter until count is reset.
Disable: If selected; counting stops after the set value of count is reached. The o/p & count remains latched thereafter until count is reset.
Over RunMode
Disable
This parameter appears only if mode 1 is selected. Last stored value of time appears on the upper display. User can set Auto Reset/TPR time by using Up/Down/Shift key. Time can be set to a precision of one decimal point.
Mode 1Time
000.1
This parameter appears only if mode 2 is selected. Last stored value of time1 appears on the upper display. User can set Auto Reset/TPR time1 by using Up/Down/Shift key. Time1 can be set to a precision of one decimal point.
000.1This parameter appears only if mode 2 is selected. Last stored value of time2 appears on the upper display. User can set Auto Reset/TPR time2 by using Up/Down/Shift key. Time2 can be set to a precision of one decimal point.
MemoryBackup EnableEnable
Set DPPoint
User can set position of decimal point for scale factor. The last set value of scale will appear on the upper display & the lower display will toggle b/w “SELt” & “DP” Position of decimal point can be shifted by using the shift key.
0001
ScaleFactor
User can set the value of scale factor. The last stored value of scale with decimal position as set above appears on the upper display. In run mode, on receiving a count pulse the counter will increment count value by the scale factor provided by the user.
0001
DISABLE: If selected; when power fails when counter is running; At the time when power is
restored ; counter will be re-set & counting will restart(depending on the output mode)
ENABLE: If selected ; when power fails during counter is running ; counter will continue
operation from the last count value & relay will be either ON or OFF (depending on mode
selected) at the time when power is restored.
This feature enables user to select memory back up facility at the time of power fail during timer is running.
4 Document Name : OIM KCN-XX8(Ver 2.0) Page 4 of 6