user’s manual - yokogawa electric im 01c20h01-01e 1. introduction 1. introduction thank you for...

70
User’s Manual Yokogawa Electric Corporation Model EJ118W, EJ118N and EJ118Y Diaphragm Sealed Differential Pressure Transmitter [Style: S2] IM 01C20H01-01E IM 01C20H01-01E 9th Edition

Upload: duongdien

Post on 30-Jun-2018

239 views

Category:

Documents


0 download

TRANSCRIPT

User’sManual

Yokogawa Electric Corporation

Model EJ118W, EJ118N andEJ118Y Diaphragm SealedDifferential Pressure Transmitter[Style: S2]

IM 01C20H01-01E

IM 01C20H01-01E9th Edition

i

CONTENTS

IM 01C20H01-01EFD No. IM 01C20H01-01E9th Edition: June 2006(KP)All Rights Reserved, Copyright © 1993, Yokogawa Electric Corporation

CONTENTS

1. INTRODUCTION............................................................................................ 1-1

1.1 Safe Use of This Product .................................................................... 1-11.2 Warranty .............................................................................................. 1-2

2. HANDLING CAUTIONS ................................................................................ 2-1

2.1 Model and Specifications Check ......................................................... 2-12.2 Unpacking ........................................................................................... 2-12.3 Storage ................................................................................................ 2-12.4 Selecting the Installation Location ...................................................... 2-22.5 Pressure Connection ........................................................................... 2-22.6 Waterproofing of Cable Conduit Connections .................................... 2-22.7 Restrictions on Use of Radio Transceivers ........................................ 2-22.8 Insulation Resistance Test and Dielectric Strength Test .................... 2-32.9 Installation of Intrinsically Safe Type Transmitters ............................. 2-3

2.9.1 TIIS Intrinsically Safe Type .......................................................... 2-32.9.2 FM Intrinsically Safe Type ............................................................ 2-4

2.10 Installation of Flameproof Type Transmitters ..................................... 2-42.10.1 TIIS Flameproof Type .................................................................. 2-42.10.2 FM Explosionproof Type .............................................................. 2-5

2.11 EMC Conformity Standards ................................................................ 2-5

3. COMPONENT NAMES.................................................................................. 3-1

4. INSTALLATION ............................................................................................. 4-1

4.1 Precautions ......................................................................................... 4-14.2 Mounting the Diaphragm Seals .......................................................... 4-14.3 Transmitter Mounting .......................................................................... 4-24.4 Affixing the Teflon Film ....................................................................... 4-3

5. WIRING.......................................................................................................... 5-1

5.1 Wiring Precautions .............................................................................. 5-15.2 Selecting the Wiring Materials ............................................................ 5-15.3 Connections of External Wiring to Terminal Box ................................ 5-1

5.3.1 Power Supply Wiring Connection ................................................ 5-15.3.2 External Indicator Connection ...................................................... 5-15.3.3 BRAIN TERMINAL BT200 Connection ........................................ 5-25.3.4 Check Meter Connection.............................................................. 5-2

5.4 Wiring .................................................................................................. 5-25.4.1 Loop Configuration ....................................................................... 5-2

(1) General-use Type and Flameproof Type ..................................... 5-2(2) Intrinsically Safe Type ................................................................. 5-3

5.4.2 Wiring Installation ......................................................................... 5-3(1) General-use Type and TIIS Intrinsically Safe Type ...................... 5-3(2) TIIS Flameproof Type .................................................................. 5-3

5.5 Grounding ............................................................................................ 5-45.6 Power Supply Voltage and Load Resistance ..................................... 5-4

ii

CONTENTS

IM 01C20H01-01E

6. OPERATION.................................................................................................. 6-1

6.1 Liquid Level Measurement in a Closed Tank ..................................... 6-16.1.1 Preparation for Operation ............................................................. 6-16.1.2 Zero Adjustments ......................................................................... 6-26.1.3 Starting Operation ........................................................................ 6-36.1.4 Shutting Down Operation ............................................................. 6-3

6.2 Measurement Range for Liquid Level Measurement(Determination of Differential Pressure Range) .................................. 6-3

7. BRAIN TERMINAL BT200 OPERATION ..................................................... 7-1

7.1 BT200 Operation Precautions ............................................................. 7-17.1.1 Connecting the BT200 ................................................................. 7-17.1.2 Conditions of Communication Line .............................................. 7-1

7.2 BT200 Operating Procedures ............................................................. 7-27.2.1 Key Layout ................................................................................... 7-27.2.2 Operating Key Functions.............................................................. 7-2

(1) Alphanumeric Keys and SHIFT Keys .......................................... 7-2(2) Function Keys ............................................................................. 7-3

7.2.3 Calling Up Menu Addresses Using the Operating Keys.............. 7-47.3 Setting Parameters Using the BT200 ................................................. 7-5

7.3.1 Parameter Usage and Selection .................................................. 7-57.3.2 Setting Parameters ....................................................................... 7-6

(1) Tag No. Setup .............................................................................. 7-7(2) Calibration Range Setup ............................................................. 7-7(3) Damping Time Constant Setup ................................................... 7-8(4) Output Mode and Integral Indicator Display Mode Setup ........... 7-8(5) Output Signal Low Cut Mode Setup ............................................ 7-9(6) Integral Indicator Scale Setup ................................................... 7-10(7) Unit Setup for Displayed Temperature....................................... 7-11(8) Unit Setup for Displayed Static Pressure .................................. 7-11(9) Operation Mode Setup .............................................................. 7-11(10) Impulse Line Connection Orientation setup .............................. 7-11(11) Output Status Display/Setup when a CPU Failure .................... 7-12(12) Output Status Setup when a Hardware Error Occurs ............... 7-12(13) Bi-directional Flow Measurement Setup ................................... 7-12(14) Range Change while applying Actual Inputs ............................ 7-13(15) Zero Point Adjustment ............................................................... 7-13(16) Test Output Setup ..................................................................... 7-15(17) Ambient Temperature Zero Shift Compensation ....................... 7-15(18) User Memo Fields ..................................................................... 7-16

7.4 Displaying Data Using the BT200..................................................... 7-167.4.1 Displaying Measured Data ......................................................... 7-167.4.2 Display Transmitter Model and Specifications ........................... 7-17

7.5 Self-Diagnostics ................................................................................ 7-177.5.1 Checking for Problems ............................................................... 7-17

(1) Identifying Problems with BT200 .............................................. 7-17(2) Checking with Integral Indicator ................................................ 7-18

7.5.2 Errors and Countermeasures ..................................................... 7-19

8. MAINTENANCE............................................................................................. 8-1

8.1 Overview ............................................................................................. 8-18.2 Calibration Instrument Selection ......................................................... 8-18.3 Calibration ........................................................................................... 8-18.4 Disassembly and Reassembly ............................................................ 8-3

iii

CONTENTS

IM 01C20H01-01E

8.4.1 Replacing the Integral Indicator ................................................... 8-38.4.2 Replacing the CPU Board Assembly ........................................... 8-4

8.5 Troubleshooting ................................................................................... 8-58.5.1 Basic Troubleshooting .................................................................. 8-58.5.2 Troubleshooting Flow Charts ....................................................... 8-5

9. PARAMETER SUMMARY............................................................................. 9-1

10. GENERAL SPECIFICATIONS .................................................................... 10-1

10.1 Standard Specifications .................................................................... 10-110.2 Model and Suffix Codes .................................................................... 10-310.3 Optional Specifications ...................................................................... 10-510.4 Dimensions ........................................................................................ 10-6

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS INTRINSICALLYSAFE EQUIPMENT ............................................................................. EX-A03E

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOFEQUIPMENT........................................................................................ EX-B03E

Customer Maintenance Parts List

DPharp EJ Series Transmitter Section ...........................CMPL 01C20A01-01EModel EJ118W, EJ118N and EJ118Y Diaphragm Sealed

Differential Pressure Transmitter ......................... CMPL 01C20H01-01E

REVISION RECORD

IM 01C20H01-01E1-1

1. INTRODUCTION

1. INTRODUCTION

Thank you for purchasing the DPharp EJ differentialpressure transmitter.

Your DPharp Pressure Transmitter was preciselycalibrated at the factory before shipment. To ensureboth safety and efficiency, please read this manualcarefully before you operate the instrument.

Regarding This Manual• This manual should be provided to the end user.

• The contents of this manual are subject to changewithout prior notice.

• All rights reserved. No part of this manual may bereproduced in any form without Yokogawa’s writtenpermission.

• Yokogawa makes no warranty of any kind withregard to this manual, including, but not limited to,implied warranty of merchantability and fitness for aparticular purpose.

• If any question arises or errors are found, or if anyinformation is missing from this manual, pleaseinform the nearest Yokogawa sales office.

• The specifications covered by this manual arelimited to those for the standard type under thespecified model number break-down and do notcover custom-made instruments.

• Please note that changes in the specifications,construction, or component parts of the instrumentmay not immediately be reflected in this manual atthe time of change, provided that postponement ofrevisions will not cause difficulty to the user from afunctional or performance standpoint.

• Yokogawa assumes no responsibilities for thisproduct except as stated in the warranty.

• If the customer or any third party is harmed by theuse of this product, Yokogawa assumes no responsi-bility for any such harm owing to any defects in theproduct which were not predictable, or for anyindirect damages.

• The following safety symbols are used in thismanual:

WARNING

Indicates a potentially hazardous situation which,if not avoided, could result in death or seriousinjury.

CAUTION

Indicates a potentially hazardous situation which,if not avoided, may result in minor or moderateinjury. It may also be used to alert againstunsafe practices.

IMPORTANT

Indicates that operating the hardware or softwarein this manner may damage it or lead to systemfailure.

NOTE

Draws attention to information essential forunderstanding the operation and features.

1.1 Safe Use of This ProductFor the safety of the operator and to protect theinstrument and the system, please be sure to follow thismanual’s safety instructions when handling thisinstrument. If these instructions are not heeded, theprotection provided by this instrument may be im-paired. In this case, Yokogawa cannot guarantee thatthe instrument can be safely operated. Please payspecial attention to the following points:

(a) Installation• This instrument may only be installed by an engi-

neer or technician who has an expert knowledge ofthis device. Operators are not allowed to carry outinstallation unless they meet this condition.

IM 01C20H01-01E1-2

1. INTRODUCTION

• With high process temperatures, care must be takennot to burn yourself by touching the instrument orits casing.

• Never loosen the process connector nuts when theinstrument is installed in a process. This can lead toa sudden, explosive release of process fluids.

• When draining condensate from the pressuredetector section, take appropriate precautions toprevent the inhalation of harmful vapors and thecontact of toxic process fluids with the skin or eyes.

• When removing the instrument from a hazardousprocess, avoid contact with the fluid and the interiorof the meter.

• All installation shall comply with local installationrequirements and the local electrical code.

(b) Wiring• The instrument must be installed by an engineer or

technician who has an expert knowledge of thisinstrument. Operators are not permitted to carry outwiring unless they meet this condition.

• Before connecting the power cables, please confirmthat there is no current flowing through the cablesand that the power supply to the instrument isswitched off.

(c) Operation• Wait 5 min. after the power is turned off, before

opening the covers.

(d) Maintenance• Please carry out only the maintenance procedures

described in this manual. If you require furtherassistance, please contact the nearest Yokogawaoffice.

• Care should be taken to prevent the build up of dustor other materials on the display glass and the nameplate. To clean these surfaces, use a soft, dry cloth.

(e) Explosion Protected Type Instrument• Users of explosion proof instruments should refer

first to section 2.9 and 2.10 (Installation of anExplosion Protected Instrument) of this manual.

• The use of this instrument is restricted to those whohave received appropriate training in the device.

• Take care not to create sparks when accessing theinstrument or peripheral devices in a hazardouslocation.

(f) Modification• Yokogawa will not be liable for malfunctions or

damage resulting from any modification made to thisinstrument by the customer.

1.2 Warranty• The warranty shall cover the period noted on the

quotation presented to the purchaser at the time ofpurchase. Problems occurring during the warrantyperiod shall basically be repaired free of charge.

• If any problems are experienced with this instru-ment, the customer should contact the Yokogawarepresentative from which this instrument waspurchased or the nearest Yokogawa office.

• If a problem arises with this instrument, pleaseinform us of the nature of the problem and thecircumstances under which it developed, includingthe model specification and serial number. Anydiagrams, data and other information you caninclude in your communication will also be helpful.

• The party responsible for the cost of fixing theproblem shall be determined by Yokogawa follow-ing an investigation conducted by Yokogawa.

• The purchaser shall bear the responsibility for repaircosts, even during the warranty period, if themalfunction is due to:

- Improper and/or inadequate maintenance by thepurchaser.

- Malfunction or damage due to a failure to handle,use, or store the instrument in accordance with thedesign specifications.

- Use of the product in question in a location notconforming to the standards specified byYokogawa, or due to improper maintenance of theinstallation location.

- Failure or damage due to modification or repair byany party except Yokogawa or an approvedrepresentative of Yokogawa.

- Malfunction or damage from improper relocationof the product in question after delivery.

- Reason of force majeure such as fires, earthquakes,storms/floods, thunder/lightening, or other naturaldisasters, or disturbances, riots, warfare, orradioactive contamination.

IM 01C20H01-01E2-1

2. HANDLING CAUTIONS

2. HANDLING CAUTIONS

The EJ118W, EJ118N and EJ118Y DifferentialPressure Transmitters are thoroughly tested at thefactory before shipment. When the transmitters aredelivered, visually check them to make sure that nodamage occurred during shipment. Also check that alltransmitter mounting hardware shown in Figure 2.1was received. If the instrument was ordered without themounting bracket, the transmitter mounting hardwarewill not be included. After checking the transmitter,repack it in its original packaging in the way it wasdelivered, then keep it like this until installation.

This chapter describes important cautions regardinghow to handle the transmitter. Read carefully beforeusing the transmitter. As for the cautions other thandescribed in this chapter, please read the cautions inthe relative chapters. If you have any problems orquestions, contact your nearest Yokogawa servicestation or sales representative.

Mounting bracket

U-bolt

U-bolt nuts

Transmitter mounting bolts

F0201E.EPS

Figure 2.1 Transmitter Mounting Hardware

2.1 Model and SpecificationsCheck

The model name and specifications are indicated on thename plate attached to the case.

This information should be included in all correspon-dence.

If the reverse operating mode was ordered (reversesignal), ‘REVERSE’ will be inscribed in field *1; ifsquare root display mode was ordered, ‘SQRT’ isinscribed in field *2; if square root output mode wasordered, ‘SQRT’ is inscribed in field *3.

F0202E.EPS

Figure 2.2 Name Plate Example of TIIS Flameproof Type

2.2 UnpackingWhen moving the transmitter to the installation site,keep it in its original packaging. Then, unpack thetransmitter there to avoid damage on the way.

2.3 StorageThe following precautions must be observed whenstoring the instrument, especially for a long period.

(1) Select a storage area which meets the followingconditions:• It is not exposed to rain or water,• It suffers minimum vibration and shock,• It has an ambient temperature and relative

humidity within the following ranges:Ambient temperature:

–40 to 85°C for a transmitter without integralindicator–30 to 80°C for a transmitter with integralindicator

Relative humidity:5% to 100% R.H. (at 40°C)

IM 01C20H01-01E2-2

2. HANDLING CAUTIONS

However, it is preferable at normal temperature andhumidity (approx. 25°C and 65% R.H.).

(2) When storing the transmitter, repack it as nearly aspossible to the way it was packed when deliveredfrom the factory.

(3) If storing a transmitter that has been used, thor-oughly clean diaphragm surfaces (the pressure-detector sections) of the diaphragm seals, so that nomeasured fluid remains on them.In addition, make sure before storing that thepressure-detector and transmitter assemblies aresecurely mounted.

2.4 Selecting the InstallationLocation

The transmitter is designed to withstand severeenvironmental conditions. However, to ensure stableand accurate operation for many years, the followingprecautions must be observed when selecting aninstallation location.

(1) Ambient TemperatureAvoid locations subject to wide temperature variationsor a significant temperature gradient. If the location isexposed to radiant heat from plant equipment, provideadequate thermal insulation and/or ventilation.

(2) Ambient AtmosphereAvoid installing the transmitter in a corrosive atmo-sphere. If the transmitter must be installed in a corro-sive atmosphere, there must be adequate ventilation aswell as measures to prevent intrusion or stagnation ofrain water in conduits.

(3) Shock and VibrationSelect an installation site suffering minimum shock andvibration (although the transmitter is designed to berelatively resistant to shock and vibration).

(4) Installation of Explosion-protected Trans-mitters

Explosion-protected transmitters can be installed inhazardous areas according to the types of gases forwhich they are certified. Important precautions regard-ing such use are included at the end of this manualunder “Installation and Operating Precautions forIntrinsically Safe Explosion-Protected Instruments” and“Installation and Operating Precautions for FlameproofExplosion-Protected Instruments.” Read these thor-oughly and carefully.

2.5 Pressure Connection

WARNING

(1) Instrument installed in the process is underpressure. Never loosen or tighten the flangebolts as it may cause dangerous spouting ofprocess fluid.

(2) If the accumulated process fluid may be toxicor otherwise harmful, take appropriate careto avoid contact with the body, or inhalationof vapors even after dismounting the instru-ment from process line for maintenance.

The following precautions must be observed in order tosafely operate the transmitter under pressure.

• Never apply a pressure higher than the specifiedmaximum working pressure.

2.6 Waterproofing of CableConduit Connections

Apply a non-hardening sealant to the threads towaterproof the transmitter cable conduit connections.(See Figure 5.4.2a, 5.4.2b, 5.4.2c and 5.4.2d.)

2.7 Restrictions on Use of RadioTransceivers

IMPORTANT

Although the transmitter has been designed toresist high frequency electrical noise, if a radiotransceiver is used near the transmitter or itsexternal wiring, the transmitter may be affectedby high frequency noise pickup. To test for sucheffects, bring the transceiver in use slowly from adistance of several meters from the transmitter,and observe the measurement loop for noiseeffects. Thereafter, always use the transceiveroutside the area affected by noise.

IM 01C20H01-01E2-3

2. HANDLING CAUTIONS

2.8 Insulation Resistance Testand Dielectric Strength Test

Since the transmitter has undergone insulation resis-tance and dielectric strength tests at the factory beforeshipment, normally these tests are not required.However, if required, observe the following precau-tions in the test procedures.

(1) Do not perform such tests more frequently than isabsolutely necessary. Even test voltages that do notcause visible damage to the insulation may degradethe insulation and reduce safety margins.

(2) Never apply a voltage exceeding 500V DC (100VDC with an internal lightning protector) for theinsulation resistance test, nor a voltage exceeding500V AC (100V AC with an internal lightningprotector) for the dielectric strength test.

(3) Before conducting these tests, disconnect all signallines from the transmitter terminals. Perform thetests in the following procedure:

• Insulation Resistance Test(1) Short-circuit the + and – SUPPLY/BT terminals in

the terminal box.(2) Turn OFF the insulation tester. Then connect the

insulation tester plus (+) lead wire to the shortedSUPPLY/BT terminals and the minus (–) leadwireto the grounding terminal.

(3) Turn ON the insulation tester power and measurethe insulation resistance. The voltage should beapplied short as possible to verify that the insula-tion resistance is at least 20 MΩ.

(4) After completing the test and being very careful notto touch exposed conductors disconnect theinsulation tester and connect a 100 kΩ resistorbetween the grounding terminal and the short-circuiting SUPPLY/BT terminals. Leave thisresistor connected at least one second to dischargeany static potential. Do not touch the terminalswhile it is discharging.

• Dielectric Strength Test(1) Short-circuit the + and – SUPPLY/BT terminals in

the terminal box.(2) Turn OFF the dielectric strength tester. Then

connect the tester between the shorted SUPPLY/BTterminals and the grounding terminal. Be sure toconnect the grounding lead of the dielectric strengthtester to the ground terminal.

(3) Set the current limit on the dielectric strength testerto 10 mA, then turn ON the power and graduallyincrease the test voltage from ‘0’ to the specifiedvoltage.

(4) When the specified voltage is reached, hold it forone minute.

(5) After completing this test, slowly decrease thevoltage to avoid any voltage surges.

2.9 Installation of IntrinsicallySafe Type Transmitters

WARNING

To pressure the safety of explosionproof equip-ment requires great care during mounting,wiring, and piping. Safety requirements alsoplace restrictions on maintenance and repairactivities. Please read the following sections verycarefully.

2.9.1 TIIS Intrinsically Safe Type

The TIIS intrinsically safe type differential pressuretransmitter is designed for hazardous areas whereexplosive or inflammable gases or vapors may bepresent as specified in the Recommended Practice forExplosion-Protected Electrical Installations in GeneralIndustries (1979), established by the Research Instituteof Industrial Safety, Ministry of Labor (Japan). (Thesetransmitters can be installed in Division 0, 1 and 2areas.)

To preserve the safety of intrinsically safe typeequipment requires great care during mounting, wiring,and piping and conduit installation.

The safety requirements also place restrictions onmaintenance and repair activities. Users absolutelymust read the “Installation and Operating Precautionsfor Intrinsically Safe Explosion-Protected Instruments”at the end of this manual.

Confirming the certification markA certification mark with the certification number isapplied on the instrument’s body.There is a fixed correspondence between certificationnumber and the safety barrier to be used as shownbelow. Please cross out the unnecessary certificationmark depending on a barrier.

For connecting with BARD-800 safety barrier;Certification No.: 56212 (without lightning

protector)56213 (with lightning protector)

For connecting with BARD-400 safety barrier;Certification No.: 54512

Please also cross out the unnecessary rating data on thedata plate accordingly.

IM 01C20H01-01E2-4

2. HANDLING CAUTIONS

If there is no label with the number corresponding tothe barrier to be used, you cannot use that barrier.Please use the correct barrier corresponding to thecertification number on the instrument.

2.9.2 FM Intrinsically Safe Type

Caution for FM Intrinsically safe type.

Note 1. Hazardous locations*Intrinsically Safe for Class I, Division 1,

Groups A, B, C & D.Class II, Division 1, Groups E, F & G and ClassIII, Division 1 Hazardous Locations.

*Outdoor hazardous locations, NEMA 4.*Temperature Class : T4*Ambient temperature : –20 to 60°C

Note 2. Entity Parameters*Vmax = 31.5V DC, Imax = 93 mA, Pmax = 1.1 W,

Ci = 2 nF, Li = 1.04 mH*Entity Installation Requirements

Vmax ≥ Voc or Vt, Imax ≥ Isc or It,Ca ≥ Ci + Ccable, La ≥ Li + Lcable

Note 3. Installation*Barrier must be installed in an enclosure that

meets the requirements of ANSI/ISA S82.01.*Resistance between lnt. Safe Gnd and earth

ground must be less than 1 ohm.*Control equipment connected to barrier must not

use or generate more than 250 Vrms or Vdc.*Installation should be in accordance with ANSI/

ISA RP12.6 “Installation of Intrinsically SafeSystems for Hazardous (Classified) Locations”and the National Electric Code (ANSI/NFPA 70).

*The configuration of associated apparatus must beFMRC Approved.

*Dust-tight conduit seal must be used wheninstalled in a Class II, III, Group E, F and Genvironments.

*No revision to drawing without prior FMRCApproved.

*Associated apparatus manufacturer’s installationdrawing must be followed when installing thisapparatus.

*The maximum power delivered from the barriermust not exceed 1.1 W.

F0203E.EPS

Class I, II, III, Division 1,Groups A, B, C, D, E, F, G

Transmitters Safety Barrier

Supply

Hazardous Location Nonhazardous Location

General PurposeEquipment

+

+

+

+

2.10 Installation of FlameproofType Transmitters

WARNING

To pressure the safety of explosionproof equip-ment requires great care during mounting,wiring, and piping. Safety requirements alsoplace restrictions on maintenance and repairactivities. Please read the following sections verycarefully.

2.10.1 TIIS Flameproof Type

The TIIS flameproof type differential pressure trans-mitter is designed for hazardous areas where inflam-mable gases or vapors may be present as specified inthe Recommended Practice for Explosion-ProtectedElectrical Installations in General Industries (1985),established by the Research Institute of IndustrialSafety, Ministry of Labor (Japan). (These transmitterscan be installed in Division 1 and 2 areas.)

To preserve the safety of flameproof type equipmentrequires great care during mounting, wiring, and pipingand conduit installation.

The safety requirements also place restrictions onmaintenance and repair activities. Users absolutelymust read “Installation and Operating Precautions forFlameproof Explosion-Protected Instruments” at theend of this manual.

CAUTION (For instruments without integral indicator)

When the fill fluid near the sensor part movesfrom within, the instrument outputs a failuresignal either high or low of the specific signal. Inthat case, generate the alarm to identify that thefailure signal is output since the event mayinvalidate the flameproof approval.If the optional integral indicator is equipped, theindicator identifies the alarm on its display.Therefore, no other alarm generation is neces-sary.

Transmitter

Hazardous Location Nonhazardous Location

PowerSupply

DCSDisplay

4 to 20 mA DC 1 to 5V DC

F0205E.EPS

Figure 2.3 Example of Using DCS (Distributed ControlSystem)

IM 01C20H01-01E2-5

2. HANDLING CAUTIONS

2.10.2 FM Explosionproof Type

Caution for FM Explosionproof type

Note 1. Hazardous locations:*Applicable standard: FM3600, FM3615, FM3810,

NEMA 250, ANSI/NFPA 70.*Explosionproof for Class I, Division 1, Groups B,

C and D.*Dust-ignitionproof for Class II, Division 1, Groups

E, F and G.*Suitable for Class III, Division 1.*Outdoor hazardous locations, NEMA 4.

Note 2. Wiring*All wiring shall comply with National Electrical

Code ANSI/NEPA70 and Local Electrical Codes.*In hazardous location, wiring to be in conduit as

shown in the figure.Note 3. Operation

*WARNING:DO NOT OPEN COVER WHILE CIRCUIT ISALIVE.

*Take care not to generate mechanical spark whenaccess to the instrument and peripheral devices inhazardous location.

Note 4. Maintenance and Repair*The instrument modification or parts replacement

by other than authorized representative ofYokogawa Electric Corporation is prohibited andwill void Factory Mutual Explosionproof Certifi-cation.

Nonhazardous Location Equipment

42V DC Max. 4 to 20 mA DC Signal

Nonhazardous Locations

Hazardous Locations

18'' (457 mm) Max.

Sealing FittingConduit

EJ Series

F0206E.EPS

2.11 EMC Conformity StandardsAS/NZS CISPR11

IM 01C20H01-01E3-1

3. COMPONENT NAMES

3. COMPONENT NAMES

Figure 3.1 Component Names (Model EJ118W External View)

*For details, refer to Figure 3.1.2

F0301E.EPS

Cover flange

Diaphragm seal(high pressure side)

Diaphragm seal(low pressure side)

Allen screw (for securing cover flange)

Capillary

Pressure-detector section

Transmitter section*

IM 01C20H01-01E3-2

3. COMPONENT NAMES

Integral indicator

CPU board assembly

Terminal box cover

Terminal box

Case cover

Mounting screw

Setting pin (CN6) (Optional)

Zero-adjustment screw

Note : Integral indicator is optional

Transmitter section

Setting pin(CN6) position (Note 1)

Burn-out direction

Output at burn-out

H

L

H

L

HIGH

LOW

110% or higher (21.6mA DC)

–5% or lower(3.2mA DC)

Note 1 : • Insert the pin (CN6) as shown in the above figure into the H or L side (set to the L side for delivery).

• The setting can be confirmed by calling up parameter D52 using the BRAIN TERMINAL. Refer to Subsection. 7. 3. 2(11).

Display Symbol

E.ZERO

Meaning of Display Symbol

Output mode is “square root”. (Display is not lit when “proportional” mode.)

The output signal being zero-adjusted is increasing.

The output signal being zero-adjusted is decreasing.

Display mode is “square root”. (Display is not lit when “proportional” mode.)

The zero-adjustment screw is “enabled”. (Display is not lit when the screw is “disabled.”)

F0302E.EPS

Figure 3.1.2 Component Names (Tranmitter Section Details)

IM 01C20H01-01E4-1

4. INSTALLATION

4. INSTALLATION

4.1 PrecautionsBefore installing the transmitter, read the cautionarynotes in Section 2.4, “Selecting the InstallationLocation.” For additional information on the ambientconditions allowed at the installation location, see the“Standard Specifications” later in this manual.

IMPORTANT

• When welding piping during construction, takecare not to allow welding currents to flowthrough the transmitter.

• Do not step on this instrument after installation.

4.2 Mounting the DiaphragmSeals

Mount the diaphragm seals using the flanges as shownin Figure 4.1. Figure 4.2 shows how to mount thediaphragm seals on a tank. The customer shouldprepare the mating flange, gasket, bolts and nuts.

Nuts

Flange

Diaphragm

ød

Gasket

Bolts

The product is shipped with these parts assembled.

Correctly install the diaphragm seals on the high and low pressure sides of the process, checking the label on each seal.

F0401E.EPS

Figure 4.1 Mounting the Diaphragm Seals

IMPORTANT

Please use a gasket which has a bigger insidediameter than that of gasket facing (d) ondiaphragm seal. In case a gsket which has asmaller inside diameter than that of gasketfacing is used, it may cause an error as thegasket prevents diaphragm from workingcorrectly. (Refer to ‘Dimensions’ later in thismanual)

IMPORTANT

• When measuring the liquid level of the tank, theminimum liquid level (zero point) must be set toa level at least 50 mm above the center of thehigh pressure side diaphragm seal (see Figure4.2).

• Correctly install the diaphragm seals on thehigh and low pressure sides of the process,checking the label on each seal.

• To avoid measuring error duets temperaturedifference between the two diaphragm seals,capillaries must be bound together. The capil-laries must be securely fixed to the tank wall toprevent movement by wind or vibration. If thecapillaries are too long, loosely coil the excessand secure using suitable clamps.

• During the diaphragm seal installation, ensureas far as possible that no seal liquid head isapplied to the diaphragm seals.

• Excercise care so as not to damage diaphragmsurface. Since the diaphragm protrudes ap-proximately 1 mm from the flange surface,placing the diaphragm seals with their dia-phragm surfaces facing downward may dam-age the diaphragm surfaces.

• Do not sharply bend or twist capillaries or applyexcessive stress to them.

IM 01C20H01-01E4-2

4. INSTALLATION

The transmitter should be installed as low as possible below the position where the high pressure side diaphragm seal is installed.

IMPORTANTInstall the sealed diaphragm so that the shank positions downward.

F0402E.EPS

P

Low pressure

side

High pressure

side50mm minimum

Minimum liquid level

Figure 4.2 Installing the Diaphragm Seals to a Tank

4.3 Transmitter MountingThe transmitter can be mounted on a nominal 50 mm(2-inch) pipe using the mounting bracket supplied, asshown in Figure 4.3. The transmitter can be mountedon either a horizontal or a vertical pipe.

IMPORTANT

1. The transmitter should be installed at least600 mm below the high pressure sidediaphragm seal to ensure a positive headpressure of fill fluid.Use caution for vacuum applications.If the transmitter can not be installed at least600 mm, please refer to the IMPORTANT 3.

2. Never loosen the four Allen screws securingthe cover flange or the screws at the jointsbetween the capillaries and cover flanges (ifthe seal liquid leaks, the transmitter cannotbe used).

F0403E.EPS

Horizontal pipe mounting

Vertical pipe mounting

U-bolt

U-bolt nuts50 mm (2-inch) pipe

U-bolt

Transmitter mounting bolts

U-bolt nuts

Bracket

Bracket

50 mm (2-inch) pipe

Transmitter mounting bolts

Figure 4.3 Transmitter Mounting

IMPORTANT

3. The transmitter should be installed at least600 mm below the high pressure (HP)process connection to ensure a positive headpressure of fill fluid. If it can not be installedat least 600 mm below the HP processconnection, please use the equation below:

h = × 7.5 × 10 [mm](P–P0) × dHg

ds–3

Where:h : Vertical height between the HP process

connection and the transmitter (mm)Note:

h≤0 : Install the transmitter at most h(mm) above the HP process con-nection

h>0 : Install the transmitter at least h(mm) below the HP process con-nection

P : Pressure in the tank (Pa abs)P0 : Minimum working pressure limit of the

transmitter

IM 01C20H01-01E4-3

4. INSTALLATION

Note : To determine minimum workingpressure refer to one of the following:1) If the ambient temperature range

is -10 to 50°C.3229 (The model code of thematerial of the wetted part is S)3690 (The model code of thematerial of the wetted part is T)6419 (The model code of thematerial of the wetted part is H)4918 (The model code of thematerial of the wetted part is U)

2) 5733 (If the ambient temperaturerange is 50 to 60°C)

ds : Specific gravity of fill fluid (at 25°C), referto GS 1C20H1-E.

dHg : Specific gravity of the Mercury 13.6 (at25°C)

F0404E.EPS

Ph

0

(+)

(–)

ds: Specific gravity of the seal liquid

Low pressure

side

High pressure

side

Figure 4.4 Example of Installation to Tank (Caution onInstallation)

4.4 Affixing the Teflon FilmThe FEP Teflon option includes a Teflon film andfluorinated oil.

Before mounting the diaphragm seal to the processflange, affix the Teflon film as follows:

IMPORTANT

(1) Position the diaphragm seal so that thediaphragm is in a upward position.

(2) Pour the fluorinated oil on the diaphragm andgasket area covering it completely andevenly. Be careful not to scratch the dia-phragm or change its shape.

(3) Affix the Teflon film over the diaphragm andgasket area.

(4) Next, carefully inspect the cover and try toidentify any entrapped air between thediaphragm and the Teflon film. The air mustbe removed to ensure accuracy. If airpockets are present, use your fingers toremove the air by starting at the center of thediaphragm and work your way out.

(5) Place the gasket with the teflon film and affixto the process flange.

Diaphraqm sealF0405E.EPS

Diaphragm

Fluorinated oil[PART No. : F9145YN]

Gasket area

Teflon film[PART No. : F9149CY for 3 inch (80mm) flange]

Figure 4.5 Affixing the Teflon Film

IM 01C20H01-01E5-1

5. WIRING

5. WIRING

5.1 Wiring Precautions

IMPORTANT

1.Lay wiring as far as possible from electricalnoise sources such as large capacity trans-formers, motors, and power supplies.

2.Remove electrical connection dust cap beforewiring.

3.All threaded parts must be treated with water-proofing sealant. (A non-hardening siliconegroup sealant is recommended.)

4.To prevent noise pickup, do not pass signaland power cables through the same ducts.

5.Explosion-protected instruments must be wiredin accordance with specific requirements (and,in certain countries, legal regulations) in orderto preserve the effectiveness of their explo-sion-protected features.

Refer to the “Installation and OperatingPrecautions for TIIS Flameproof Equipment”and “Installation and Operating Precautionsfor TIIS Intrinsically Safe Equipment” at theend of this manual for correct wiring.

5.2 Selecting the Wiring Materi-als

1. Use stranded leadwires or cables which are the sameas or better than 600V grade PVC insulated wire(JIS C3307) or equivalent for wiring.

2. Use shielded wires in areas that are susceptible toelectrical noise.

3. In areas with higher or lower ambient temperatures,use wires or cables appropriate for such tempera-tures.

CAUTION

If the transmitter is flameproof and the ambienttemperature is 50°C or more, use cables havinga maximum allowable heat resistance of least75°C in consideration of the instrument’s genera-tion of heat or the cables’ self-heating.

4. In environments where oils, solvents, corrosive gasesor liquids may be present, use wires or cables thatare resistant to such substances.

5. It is recommended that crimp-on solderless terminallugs (for 4 mm screws) with insulating sleeves beused for leadwire ends.

5.3 Connections of ExternalWiring to Terminal Box

5.3.1 Power Supply Wiring Connection

Connect the power supply wiring to the SUPPLY/BT +and – terminals.

Power supply–

+F0501E.EPS

Terminal box

Figure 5.3.1 Power Supply Wiring Connection

5.3.2 External Indicator Connection

Connect wiring for external indicators to the METER +and – terminals.

(Note) Use a external indicator whose internalresistance is 10 Ω or less.

– +

F0502E.EPS

Terminal box

External indicator Jumper

(Remove jumper)

Power supply

+

Figure 5.3.2 External Indicator Connection

IM 01C20H01-01E5-2

5. WIRING

5.3.3 BRAIN TERMINAL BT200 Connec-tion

Connect the BT200 to the SUPPLY/BT + and –terminals (Use hooks).

BT200

Jumper (should be attached if the external indicator is not connected)

F0503E.EPS

+

Terminal box

Power supply

Since the BT200 is AC-coupled to the terminal box, polarity does not matter.

Figure 5.3.3 BT200 Connection

5.3.4 Check Meter Connection

Connect the check meter to the CHECK + and –terminals (use hooks).

• A 10 to 50 mV DC signal is output corresponding to4 to 20 mA DC output signal from the CHECK +and – terminals.

F0504E.EPS

Check meter –

+

Terminal boxPower supply

Figure 5.3.4 Check Meter Connection

5.4 Wiring

CAUTION

For the intrinsically safe equipment and flame-proof equipment, wiring materials and wiringwork for these equipment including peripheralsare strictly restricted.Users absolutely must read “Installation andOperating Precautions for TIIS Intrinsically SafeEquipment” and “Installation and OperatingPrecautions for TIIS Flameproof Equipment” atthe end of this manual prior to the work.

5.4.1 Loop Configuration

Since the DPharp uses a two-wire transmission system,signal wiring is also used as power wiring.

DC power is required for the transmitter loop. Thetransmitter and distributor are connected as shownbelow.

For details of the power supply voltage and loadresistance, see Section 5.6; for communications linerequirements, see Subsection 7.1.2.

(1) General-use Type and Flameproof Type

F0505E.EPS

Distributor (Power supply unit)

Receiver instrument

Transmitter terminal box

Figure 5.4.1a Connection between Transmitter andDistributor

IM 01C20H01-01E5-3

5. WIRING

(2) Intrinsically Safe TypeFor intrinsically safe type, a safety barrier must beincluded in the loop.

F0506E.EPS

Distributor (Power supply unit)

Receiver instrument

Safety barrier

Transmitter terminal box

Figure 5.4.1b Connection between Transmitter andDistributor

5.4.2 Wiring Installation

NOTE

For installation of intrinsically safe type andflameproof type, see section 2.9 and 2.10.

(1) General-use Type and TIIS IntrinsicallySafe Type

Make cable wiring using metallic conduit or water-proof glands (marine watertight cable glands forelectric appliances, JIS F8801).

• Apply a non-hardening sealant to the terminal boxconnection port and to the threads on the flexiblemetal conduit for waterproofing.

F0507E.EPS

Flexible metal conduit

Wiring metal conduit

Tee

Drain plug

Apply a non-hardening sealant to the threads for waterproofing.

Figure 5.4.2a Typical Wiring Using Flexible Metal Conduit

(2) TIIS Flameproof TypeWire cables through a flameproof packing adapter, orusing a flameproof metal conduit.

Wiring cable through flameproof packing adapterfor only TIIS flameproof type(see Figure 5.4.2b)• Use only flameproof packing adapters approved

by Yokogawa.• Apply a non-hardening sealant to the terminal box

connection port and to the threads on the flame-proof packing adapter for waterproofing.

Flameproof packing adapter

Flexible metal conduitWiring metal conduit

Tee

Drain plug

Apply a non-hardening sealant to the threads for waterproofing.

F0508E.EPS

Figure 5.4.2b Typical Cable Wiring Using FlameproofPacking Adapter

• Measure the cable outer diameter in two directionsto within 1mm.

• Calculate the average of the two diameters, and usepacking with an internal diameter nearest to thisvalue (see Table 5.4.2).

Table 5.4.2 Flameproof Packings and Applicable CableOuter Diameters

Optional Code

Wiring Port Thread Diameter

Applicable Cable OD (mm)

Identifying Mark

Part Number

T0501E.EPS

G9601AM8 to 10

10.1 to1216 8-1016 10-12

22 10-1222 12-1422 14-16

G 1/2(PF 1/2)

G11

G12

G9601AN10 to12

12.1 to1414.1 to16

G 3/4(PF 3/4)

G21

G22

• Mounting flameproof packing adapter body toconduit connection (see Figure 6.4.2c)

1. Screw the flameproof packing adapter into theterminal box until the O-ring touches the wiring port(at least 6 full turns), and firmly tighten the lock nutwith a wrench.

2. Insert the cable through the union cover, the unioncoupling, the clamp nut, the clamp ring, the gland,the washer, the rubber packing, and the packing box,in that order.

3. Insert the end of the cable into the terminal box.

IM 01C20H01-01E5-4

5. WIRING

4. Tighten the union cover to grip the cable. Whentightening the union cover, tighten approximatelyone turn past the point where the cable will nolonger move up and down.Proper tightening is important. If it is too tight, acircuit break in the cable may occur; if not tightenough, the flameproof effectiveness will becompromised.

5. Fasten the cable by tightening the clamp nut.6. Tighten the lock nut on the union cover.7. Connect the cable wires to each terminal.

F0509.EPS

Apply a non-hardning sealant to the threads of these fittings for waterproofing.

Lock nut

Packing

Washer

Gland

Clamp ring

Clamp nut

Union coupling

Lock nut

Adapter body

O-ring

Packing box

Union cover

Cable

Figure 5.4.2c Installing Flameproof Packing Adapter

Flameproof metal conduit wiring• A seal fitting must be installed near the terminal

box connection port for a sealed construction.• Apply a non-hardening sealant to the threads of

the terminal box connection port, flexible metalconduit and seal fitting for waterproofing.

F0510E.EPS

Non-hazardous area

Hazardous area

Flameproof heavy-gauge steel conduit

Tee

Drain plug

Seal fitting

Gas sealing device

Apply a non-hardening sealant to the threads of these fittings for waterproofing.

Flameproof flexible metal conduit

(After wiring, impregnate the fitting with a compound to seal tubing.)

Figure 5.4.2d Typical Wiring Using Flameproof MetalConduit

5.5 Grounding1. Grounding should satisfy Class D requirements

(grounding resistance, 100 Ω or less). Grounding isrequired for TIIS flameproof type and intrinsicallysafe type.

(Note) In case of with Built-in Lightning Protector,grounding should satisfy Class C require-ments (grounding resistance, 10 Ω or less).

2. There are ground terminals on the inside and outsideof the terminal box. Either of these terminals may beused.

3. Use 600 V grade PVC insulated wires for grounding.

Ground terminal

Terminal box

F0511E.EPS

Figure 5.5 Ground Terminals

5.6 Power Supply Voltage andLoad Resistance

When configuring the loop, make sure that the externalload resistance is within the range in the figure below.

600

250

0 12 17.9

R = 42.3 (E12) (General-use type and flameproof type)

R = 42.3 (E16.5) (Intrinsically safe type)

26.216.5 22.4 31.5

42

Power supply voltage E (V DC)F0512E.EPS

Operating region

Ext

erna

l loa

d re

sist

ance

R (

Ω)

Figure 5.6 Relationship between Power Supply Voltageand External Load Resistance

IM 01C20H01-01E6-1

6. OPERATION

6. OPERATION

6.1 Liquid Level Measurement ina Closed Tank

This section describes the operating procedures for thepiping configuration shown in Figure 6.1.

6.1.1 Preparation for Operation

Closed tank

F0601E.EPS

Transmitter mounting pipe 50 mm (2 inches)

Capillaries

Diaphragm seal (high pressure side)

Diaphragm seal (low pressure side)

DP transmitter

Figure 6.1 Liquid Level Measurement in a Closed Tank

(1) Leak checkConfirm that there is no leak in the connecting part ofthe transmitter mounting flange.

(2) Connecting to BRAIN TERMINALTurn ON power and connect the BRAIN TERMINAL.Open the terminal box cover and connect the BRAINTERMINAL to the SUPPLY/BT and termianls.

(3) Confirming that transmitter is operatingproperly

Using the BRAIN TERMINAL, confirm that thetransmitter is operating properly. Check parametervalues or change the setpoints as necessary.

For BRAIN TERMINAL operating procedures, seeChapter 7. If the transmitter is equipped with anintegral indicator, its indication can be used to confirmthat the transmitter is operating properly.

Using the BRAIN TERMINAL• If the wiring system is faulty, ‘communication

error’ appears on the display.• If the transmitter is faulty, ‘SELF CHECK ER-

ROR’ appears on the display.

communication error

PARAM C60:SELF CHECK ERROR

DATA DIAG PRNT ESC

Communication error (Faulty wiring)

Self-diagnostic error (Faulty transmitter)

F0602E.EPS

Using the integral indicator• If the wiring system is faulty, the display is blank.• If the transmitter is faulty, an error number will

appear on the display according to the nature of theerror.

F0603E.EPS

NOTE

If any of the error indications above appears onthe display of the integral indicator or BRAINTERMINAL, refer to Subsection 7.5.2 for correc-tive action.

Verify and change transmitter parametersetting and values

The following parameters are the minimum settingsrequired for operation. The transmitter has beenshipped with these parameters. To confirm or changethe values, see Subsection 7.3.2.

• Measuring range (measuring range low limit,high limit and unit) ............See Subsection 7.3.2 (2)

• Operation mode (direct/reverse output) ............See Subsection 7.3.2 (9)

IM 01C20H01-01E6-2

6. OPERATION

6.1.2 Zero Adjustments

IMPORTANT

Do not turn off the power to the transmitterimmediately after a zero adjustment. Poweringoff within 30 seconds after a zero adjustment willreturn the adjustment back to the previoussettings.

Zero adjustment of the transmitter can be set in twoways: uing the zero-adjustment screw of the transmit-ter, and through the operation of the BRAIN TERMI-NAL.

For output signal checking, display the parameter‘A10: OUTPUT(%)’ in the BRAIN TERMINAL.

Output signal (%) display

PARAM A10:OUTPUT(%) 0.0 % A11:ENGR OUTPUT

A20:AMP TEMP

DATA DIAG PRNT ESC

F0604E.EPS

After operating preparation is completed, adjust thezero point.

When adjusting the transmitter zero point, the liquidlevel in a tank does not have to be set to the low limit(0%) of the measuring range. In such case, match thetransmitter output signal with the actual measuredvalue using, for example, a glass gauge.

(1) When the liquid level in a tank can be setto the low limit of the measuring range(0%):

Using the transmitter zero-adjustmentscrew

Before using the zero-adjustment screw outside thetransmitter case, confirm the following.

• Parameter ‘J20: EXT ZERO ADJ’ display must be‘ENABLE’. See Subsection 7.3.2 (14) for the settingprocedure.

• If the transmitter is equipped with an integralindicator, ‘E.ZERO’ must be displayed.

Use a slotted screwdriver to turn the zero-adjustmentscrew. Turn the screw clockwise to increase the outputor counterclockwise to decrease the output, the zeropoint adjustment can be adjusted with a resolution of0.01% of the setting range.

The degree of zero adjustments varies with the screwturning speed. Therefore, turn the screw slowly for fineadjustment and quickly for coarse adjustment.

Zero-adjustment screw

F0605E.EPS

Using the BRAIN TERMINALZero point can be adjusted by simple key operation ofthe BRAIN TERMINAL.

Select parameter ‘J10: ZERO ADJ’, and press theENTER key twice. The zero point will be adjustedautomatically to the output signal 0% (4 mA DC).Confirm that the setting value displayed for theparameter is ‘0.0%’ before pressing the ENTER key.See Subsection 7.3.2 (14) for BRAIN TERMINALoperating procedures.

SET J10:ZERO ADJ –0.0 % + 000.0

CLR ESCF0606E.EPS

Display when parameter J10 is selected.

Press key twice for 0% output 4 mA DC.

IM 01C20H01-01E6-3

6. OPERATION

(2) When the liquid level in a tank cannot beset to the low limit (0%) of the measuringrange:

Convert the actual measured value obtained from thesight glass, etc. in %.

[Example] For the measurement range: 0 to 2 m, and actual measured value: 0.8 m

Actual measured value = 0.82

× 100 = 40%

Using the transmitter zero-adjustmentscrew(Match the output signal with the actual measuredvalue by turning the zero-adjustment screw.)

Using the BRAIN TERMINALSelect the parameter ‘J10: ZERO ADJ.’ Change theset point (%) displayed for the parameter to the actualmeasured value (%), and press the ENTER key twice.For operation details, see Subsection 7.3.2 (14).

SET J10:ZERO ADJ 0.0 % + 040.0

CLR ESC

F0607E.EPS

Display when parameter J10 is selectedChange setting to the actually measured value (40.0%).

Press the key twice for 40% output 10.4 mA DC.

6.1.3 Starting Operation

When the operation described in Subsection 6.1.2 iscompleted, the transmitter is already in operation.Perform the following:

1. Confirm the operating status.The output signal may widely fluctuate (huntingstate) due to process pressure periodic variation.In such case, BRAIN TERMINAL operationcan dampen the transmitter output signal.Confirm the hunting state using a receivinginstrument or the integral indicator and set theoptimum damping time constant. See Subsection7.3.2 (3) “Damping time constant setup.”

2. After confirming the operating status, performthe following:

IMPORTANT

• Remove the BRAIN TERMINAL from theterminal box, and confirm that none of theterminal screws are loosened.

• Close the terminal box cover and the (amplifier)case cover. Securely screw each cover untilthey cannot be turned.

• For TIIS flameproof type, hook the shroudingclamps to the cover edge and tighten themounting screws using an Allen wrench.

• Tighten the zero-adjustment cover mountingscrew to fix the cover in position.

6.1.4 Shutting Down Operation

Turn OFF power.

NOTE

If the transmitter is to be shut down for a pro-longed period, detach the transmitter (diaphragmseals) from the tank.

6.2 Measurement Range forLiquid Level Measurement(Determination of DifferentialPressure Range)

The following describes the procedure for calculatingthe differential pressure range for liquid level measure-ment.

Parameters Required for CalculationGL: Specific gravity of liquid inside tank (assumed not

to vary during liquid level measurement)

GC: Specific gravity of capillary seal liquid (assumednot to vary during liquid level measurement)

Density of gas or steam in tank:Omitted from calculation

Conversion factor in pressure unit:1 Pa = 1.01972 × 10–1 mmH2O

IM 01C20H01-01E6-4

6. OPERATION

(1) For a Closed TankSince the pressure inside the tank is introduced into thelow pressure side of the transmitter (the same pressureis also applied to the high pressure side), the pressureinside the tank is not required to be considered in thecalculation.

Span = xGL Zero elevation = yGL – dGCDifferential pressure range:

(yGL – dGC) to (xGL + yGL – dGC)Example: If x = 2 m, y = 0.1 m, d = 2.5 m, GL = 0.8,

GS = 1,then:Span = 2 × 0.8 × 9.80665 = 15.69 kPaZero elevation = (0.1 × 0.8 – 2.5 × 1) ×9.80665 = –23.73 kPaDifferential pressure range:

–23.73 to –8.04 kPa

F0608E.EPS

Highest liquid level

Lowest liquid level

y

x

z

d

Low pressure side

High pressure side

Figure 6.2.1 Closed Tank

7-1

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

7. BRAIN TERMINAL BT200OPERATION

The DPharp is equipped with BRAIN communicationscapabilities, so that range changes, Tag No. setup,monitoring of self-diagnostic results, and zero pointadjustment can be handled by remote control viacommunications from a BT200 BRAIN TERMINALor CENTUM CS console. This section describesprocedures for settings and changing parameters usingthe BT200. For details concerning the BT200, see IM01C00A11-01E, “BT200 User Manual.”

7.1 BT200 Operation Precautions

7.1.1 Connecting the BT200

The transmitter and the BT200 can be connected eitherby connecting the BT200 to the BT200 connectionhooks provided in the transmitter terminal box, or byconnecting it to a relaying terminal board.

DPharp

BT200

BT200

BT200BT200

Relaying terminals

Distributor

Control room

Terminal board

F0701E.EPS

Figure 7.1.1 Connecting the BT200

7.1.2 Conditions of Communication Line

DPharp

BT200

Cable resistance Rc

Cable resistance Rc

Load resistance R

ccPower supply

Loop resistance = R+2Rc = 250 to 600Ω Loop capacitance = 0.22µF max.

F0702E.EPS

Figure 7.1.2 Conditions of Communication Line

7-2

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

7.2 BT200 Operating Procedures

7.2.1 Key Layout

Figure 7.2.1 shows the arrangement of the operatingkeys on the BT200 keypad.

F0703E.EPS

Alphanumeric keys•Enter digits.•Enter letters in combination with the shift keys.

LCD(21 character × 8 lines)

Movement keys •Select items. •Move the cursor. •Change pages.

Power ON/OFF key

Function keys Use to execute the commands displayed at the bottom of the screen.

ENTER key •Enters selected items. •Sets up input data on the connected instrument.•Runs BT200 functions.

Shift keys

Figure 7.2.1 BT200 Key Layout

PARAM A10:OUTPUT 100.0 % A11:ENGR. OUTPUT 100 kPa A20:AMP TEMP 23 deg C

MENU A:DISPLAY B:SENSOR TYPE

BATTERY

HOME SET ADJ ESC

DATA DI AG PRNT

F0704E.EPS

Menu choices(up to six displayed)

MessagesMENU PANEL

Panel title Function commands

PARAMETER PANEL

Parameters (up to three displayed)

Function commands

7.2.2 Operating Key Functions

(1) Alphanumeric Keys and SHIFT KeysYou can use the alphanumeric keys in conjunction withthe shift keys to enter symbols, as well as alphanu-meric keys.

Shift keys

Alphanumeric keys

F0705E.EPS

a. Entering Digits, Symbols, and Spaces(0 to 9 ... )Simply press the alphanumeric keys.

Entry Key-in Sequence

–4

0.3

F0706E.EPS

1 –9

b. Entering Letters (A through Z)Press an alphanumeric key following a shift key toenter the letter shown on that side which the shiftkey represents. You must press the shift key beforeentering each letter.

Left-side letter on the alphanumeric key

F0707E.EPS

Right-side letter on the alphanumeric key

Entry Key-in Sequence

W

IC

J. BF0708E.EPS

7-3

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

Use the function key [F2] CAPS to select betweenuppercase and lowercase (for letters only). The casetoggles between uppercase and lowercase each timeyou press [F2] CAPS.

CODE CAPS CLR ESC CODE caps CLR ESC

Entry

Boy

Key-Sequence

Entering uppercase Entering lowercase

( B ) ( y )( o )

(Lower case)

F0709E.EPS

Use the function key [F1] CODE to enter symbols.

The following symbols will appear in sequence, one ata time, at the coursor each time you press [F1] CODE:

/ . – , + * ) ( ‘ & % $ # ” !

To enter characters next to these symbols, press [>]to move the cursor first.

Entry

l/m

Key-in Sequence

T0710E.EPS

( / ) ( m )( I )

(Lower case)

(2) Function KeysThe functions of the function keys depend on thefunction commands on display.

MENU A:DISPLAY B:SENSOR TYPE

HOME SET ADJ ESC Function commands

Function keysF0711E.EPS

Function Command List

ADJ

CAPS / caps

CODE

CLR

DATA

DEL

DIAG

ESC

HOME

NO

OK

PARM

SET

SLOT

UTIL

*COPY

*FEED

*LIST

*PON / POFF

*PRNT

*GO

*STOP

Displays the ADJ menu

Selects the case between uppercase and lowercase

Selects symbols

Erases input data or deletes all data

Updates parameter data

Deletes one character

Calls the self-check panel

Returns to the most recent display

Displays the menu panel

Quits setup and returns to the previous display

Proceeds to the next panel

Enters the parameter number setup mode

Displays the SET menu

Returns to the slot selection panel

Calls the utility panel

Prints out parameters on display

Paper feed

Lists all parameters in the menu

Turns the setup change data printout mode on or off

Changes to the print mode

Starts printing

Cancels printing

Parameters marked * are indicated only by the BT200-P00 (equipped with printer).

Command Function

T0701E.EPS

7-4

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

7.2.3 Calling Up Menu Addresses Using the Operating Keys

DATA DIAG PRNT ESC

PARAM A60:SELF CHECK GOOD

CODE CAPS CLR ESC

––WELCOME––BRAIN TERMINAL ID: BT200

check connection push ENTER key

UTIL FEED esc

PARAM 01:MODEL EJxxx-xx 02:TAG NO. YOKOGAWA 03:SELF CHECK GOOD

OK

HOME SET ADJ ESC

FUNC 1.MENU 2.UPLOAD TO BT200 3.DOWNLOAD TO INST 4.PRINT ALL DATA

HOME SET ADJ ESC

MENU A.DISPLAY B.SENSOR TYPE

HOME SET ADJ ESC

MENU C.SETTING D.AUX SET 1 E.AUX SET 2 H:AUTO SET

HOME SET ADJ ESC

MENU J.ADJUST K.TEST M.MEMO P:RECORD

DATA DIAG PRNT ESC

DATA DIAG PRNT ESCDATA DIAG PRNT ESC DATA DIAG PRNT ESC

PARAM C60:SELF CHECK GOOD

PARAM C22:HIGH RANGE 100 kPa

DATA DIAG PRNT ESC

PARAM J60:SELF CHECK GOOD

PARAM J10:ZERO ADJ 0.0 % J11:ZERO DEV 22.2 % J20:EXT. ZERO ADJ ENABLE

SET C10:TAG NO. YOKOGAWA YOKOGAWA

DATA DIAG PRNT ESC

PARAM A10:OUTPUT(%) 50.0 % A11:ENGR, OUTPUT 20.0 M A20:AMP TEMP 24.5 deg C

DATA DIAG PRNT ESC

PARAM C10:TAG NO. YOKOGAWA C20:PRESS UNIT kPa C21:LOW RANGE 0 kPa

PARAM A21:CAPSULE TEMP 26.5 deg C

UTILITY 1.ID 2.SECURITY CODE 3.LANGUAGE SELECT 4.LCD CONTRAST 5.PRINTER ADJUST

(HOME MENU SCREEN) (SET MENU SCREEN) (ADJ MENU SCREEN)

(UTIL)

(SET)

(ESC)

(ADJ)

The utility panel contain the following items.1. BT200 ID settings.2. Security code settings.3. Switching language of messages (Japanese or English).4. LCD contrast setting.5. Adjusting printout tone (BT200-P00 only).

F0712E.EPS

STARTUPSCREEN

INITIALDATASCREEN

MENUSCREEN

PARA-METERSCREEN

SETUPSCREEN

See, “BT200 Instruction Manual” for details concerninguploading and downloading parameters, and makingprintouts (BT200-P00).

7-5

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

7.3 Setting Parameters Using theBT200

IMPORTANT

Do not turn off the transmitter as soon as BRAINTERMINAL settings have been made. If thetransmitter is turned off less than 30 secondsafter parameters have been set, the set data willnot be stored and the terminal returns to previ-ous settings.

Table 7.3.1 Parameter Usage and Selection

7.3.1 Parameter Usage and Selection

Before describing the procedure for setting parameters,we present the following table showing how theparameters are used in what case.

Setup Item Description

Sets the integral indicator scale to a % scale or user-set engineering units scale.For engineering units scale, 4 data are set: user-set engineering scale designation unit (for BT200 display), display value at 4 mA DC, and display value at 20 mA DC.

Used mainly to stabilize output near 0% if output signal is the square root mode.Two modes are available: forcing output to 0% for input below a specific value, or changing to proportional output for input below a specific value.

Reverses the direction for 4 to 20 mA DC output relative to input.Reverse mode is used for applications in which safety requires that output be driven toward 20 mA if input is lost.

Sets a unit for static pressure displayed on the BT200.

Sets a unit for temperatures displayed on the BT200.

Sets modes for output signal and integral indicator to “Linear mode” (proportional to input differential pressure) or to “Square root mode” (proportional to flow).

Adjusts the output response speed for 4 to 20 mA DC.Can be set in 9 increments from 0.2 to 64 s.

Sets the Tag No. (using 16 alphanumeric characters).Note: Up to 8 alphanumerics (upper case

letters) can be used in the BT100.

Sets the calibration range for 4 to 20 mA DC.Sets three data items : range unit, input value at 4 mA DC (LRV), and input value at 20 mA DC (HRV).Note: LRV and HRV can be specified with

range value specifications up to 5 digits (excluding any decimal point) within the range of –32000 to 32000.

Integral indicator scale range and unit setupP.7-10

Output signal low cut mode setupP.7-9

Operation mode (normal/ reverse signal) setupP.7-11

Unit setup for displayed static pressure P.7-11

Unit setup for displayed temperatureP.8-11

Damping time constant setup P.7-8

Tag No. setupP.7-7

Calibration range setupP.7-7

Output and integral indicator display mode setupP.7-8

Setup Item Description

Used to measure bi-directional flows.Output at zero flow is 12 mA DC, with output range equally divided between forward and reverse flow.Can be used with square root mode.

Allows user to enter up to 5 items of any desired text in up to 8 uppercase alphanumeric characters per item.

Adjusts zero point.This can be done either using the external zero-adjustment screw on the transmitter or using the BT200.

Range for 4 to 20 mA DC signal is set with actual input applied.Sets 20 mA DC output precisely with respect to user’s reference instrument output.Note that DPharp is calibrated with high accuracy before shipment, so span should be set using the normal range setup.

Used where installation conditions make it imperative to connect high pressure side impulse line to low pressure side of transmitter. Reversal of orientation should be dealt with by reversing impulse line wherever possible. Use this function only where there is no alternative.

Displays the status of 4 to 20 mA DC output when a CPU failure. The parameter of the standard unit is fixed to the high limit value (a change to the low limit value is not possible).Specify the optional code /C1 when selection of a HIGH/LOW limit is necessary.

Bi-directional flow measurementP.7-12

Sets the status of the 4 to 20 mA DC output when an abnormal status is detected with the capsule or the amplifier as the result of self-diagnosis. One of the following statuses; last held, high limit, and low limit values, can be selected.

Output status setup when a hardware error occursP.7-12

User memo fieldsP.7-16

Used for loop checks.Output can be set freely from –2.5% to 110% in 1% steps.

Test output (fixed current output) setupP.7-15

Zero point adjustmentP.7-13 to 7-14

Range change (while applying actual inputs)P.7-13

Impulse line connection orientation (higher pressure on right/left side) setup P.7-11

Output status display/setup when a CPU failureP.7-12

T0702E.EPS

Allows user to compensate the zero shift by ambient temperature effect on capillary tubes.

Ambienttemperature zero shift compensationP.7-15

7-6

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

7.3.2 Setting Parameters

Table 7.3.2 shows a summary of parameters and theirdefault values (set values on delivery). Set or changethe parameters as necessary. After completing these, donot fail to use the “DIAG” key to confirm that“GOOD” is displayed for the self-diagnostic result“ 60: SELF CHECK”.

Table 7.3.2 Parameter Summary

No. Description Default ValueData Setting RangeItem

C10

C20

C21

C22

C30

C40

D10

D11

D20

D21

D22

D23

D30

D31

D40

D45

D52

D53

E10

E14

E15

E30

H10

H11

TAG NO.

PRESS UNIT

LOW RANGE

HIGH RANGE

AMP DAMPING

OUTPUT MODE

LOW CUT

LOW CUT MODE

DISP SELECT

DISP UNIT

DISP LRV

DISP HRV

TEMP UNIT

STAT. P. UNIT

REV OUTPUT

H/L SWAP

BURN OUT

ERROR OUT

DFS MODE

TEMP SELECT

TEMP ZERO

BI DIRE MODE

AUTO LRV

AUTO HRV

Tag number

Differential pressure units

Lower range value (LRV)

Higher range value (HRV)

Damping time constant

Output mode

Low cut value

Low cut mode

Display selection

Engineering unit to be displayed

Display LRV

Display HRV

Temperature unit

Static pressure unit

Operation mode

Impulse line connection orientation

The output when a CPU failure

The output when a hardware error occurs

DFS mode

Reference temperature sensor

Zero shift compensation setup

Normal / reverse mode

Automatic LRV setup

Automatic HRV setup

As specified when ordered.

As specified when ordered.

As specified when ordered.

As specified when ordered.

2 s

As specified when ordered.If not specified, OUT : LIN DSP : LIN.

10.0%

LINEAR

NORMAL (%)

As specified when ordered.

As specified when ordered.

deg C

As specified when ordered.If not specified, kPa or MPa.

As specified when ordered.If not specified, NORMAL.

NORMAL

HIGH

HIGH

ON

CAP.TEMP

0.00

OFF

Displays the same data as C21.

Displays the same data as C22.

16 alphanumeric characters

Selected from mmH2O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa, MPa, mbar, bar, gf/cm2, kgf/cm2,in H2O, inHg, ftH2O, psi, or atm.

–32000 to 32000But within measurement range

–32000 to 32000But within measurement range

Selected from 0.2, 0.5, 1.0, 2.0, 4.0, 8.0, 16.0, 32.0, or 64.0 s.

OUT : LIN DSP : LINOUT : LIN DSP : SQROUT : SQR DSP : SQR

0.0 to 20.0%

LINEAR, ZERO

NORMAL (%), USER SET

–19999 to 19999

–19999 to 19999

deg C, deg F

Selected from mmH2O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa, MPa, mbar, bar, gf/cm2, kgf/cm2, in H2O, inHg, ftH2O, psi, or atm.

NORMAL, REVERSE

NORMAL, REVERSE

HIGH (Note)

HOLD, HIGH, LOW

OFF, ON

AMP.TEMP/CAP.TEMP

±10.00

OFFON

–32000 to 32000

–32000 to 32000

T0703E.EPS

Note: Specify the optional code /C1 when selection of a HIGH/LOW limit is necessary.

7-7

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

(1) Tag No. Setup (C10: TAG NO)The Tag No. is set as specified in the order before theinstrument is shipped. Use the procedure below tochange the Tag No.

Up to 16 alphanumeric characters can be entered forthe Tag No.

• Example: Set a Tag No. to FIC-1a.

PARAM 01:MODEL EJ118W-DM 02:TAG NO. YOKOGAWA 03:SELF CHECK GOOD

OK

MENU A:DISPLAY B:SENSOR TYPE

HOME SET ADJ ESC

MENU C:SETTING D:AUX SET 1 E:AUX SET 2 H:AUTO SET

HOME SET ADJ ESC

MENU C10:TAG NO. YOKOGAWA C20:PRESS UNIT kPa C21:LOW RANGE 0 kPaDATA DIAG PRNT ESC

<When power is off>

––WELCOME––BRAIN TERMINAL ID: BT200

check connection push ENTER key

UTIL FEED

SET C10:TAG NO. YOKOGAWA YOKOGAWA

CODE CAPS CLR ESC

(caps)

FOKOGAWA

FIKOGAWA

FICOGAWA

FIC-GAWA

FIC-1AWA

FIC-1aWA

FIC-1a

Press the key to turn on

the BT200.

Connect DPharp and BT200 using a communication cable

and press the key.

Select C: SETTING and press

the key.

Select C10: TAG NO. and

press the key.

Displays the name of connected DPharp model, TAG NO. and diagnostics

information. Press the (OK)

key after confirmation.

Press the (SET) key to

display the SET menu panel.

Set the new TAG NO. (FIC-1A).

When you have made an entry mistake,

return the cursor using the key,

then reenter.F0713E.EPS

Display Description

SET C10:TAG NO. FIC-1a

FEED NO OK

DATA DIAG PRNT ESC

SET C10:TAG NO. YOKOGAWA FIC-1a

PRINTER OFF F2:PRINTER ON

PARAM C10:TAG NO. FIC-1a C20:PRESS UNIT kPa C21:LOW RANGE 0 kPa

FEED POFF NO

F0714E.EPS

SET C10:TAG NO. YOKOGAWA FIC-1a _

CODE caps CLE ESC

This is the panel for confirming set data. The set data itemsflash. When all items have been confirmed, press the

again. (To go back

to the setting panel, press the

(NO) key).

The DPharp TAG NO. was overwritten.

Press the (OK) key to

return to the parameter panel.

Press the (NO) key to

return to the setting panel.

Set TAG NO. and press the

key.

(2) Calibration Range Setup a. Setting Calibration Range Unit

(C20: PRESS UNIT)The unit is set at the factory before shipment ifspecified at the time of order.Follow the procedure at the below to change theunit.

mmH2OmmAqmmWGmmHgTorrkPaMPambarbargf/cm2

kgf/cm2

inH2OinHgftH2OpsiatmPahPa

ESC

SET C20:PRESS UNIT kPa

FEED NO OK

SET C20:PRESS UNIT kPa < kPa > < MPa > < mbar > < bar >

•Example: Change the unit from “kPa” to “MPa”.

Use the or

key to select “MPa”.

Press the key twice

to enter the setting.

Press the (OK) key.

F0715E.EPS

7-8

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

b. Setting Calibration Range Lower RangeValue and Higher Range Value(C21: LOW RANGE, C22: HIGH RANGE)These range values are set as specified in theorder before the instrument is shipped.Follow the procedure below to change the range.The measurement span is determined by the highand low range limit values.In this instrument, changing the low range valuealso automatically changes the high range value,keeping the span constant.

Span = Higher range value – Lower range value

FEED NO OK

SET C21:LOW RANGE 0.5 kPa

DATA DIAG PRNT ESC

SET C20:PRESS UNIT kPa C21:LOW RANGE 0.5 kPa C22:HIGH RANGE 30.5 kPa

DEL CLR ESC

SET C21:LOW RANGE 0 kPa + 0.5

•Example 1: With present settings of 0 to 30 kPa, set the lower range value to 0.5 kPa.

The higher range value ischanged with the span held constant.

Set “0.5”.

Press the key twice

to enter the setting.

F0716E.EPS

Press the (OK) key.

Note, however, that changing the higher rangevalue does not cause the lower range value tochange.Thus, changing the higher range value alsochanges the span.

FEED NO OK

SET C22:HIGH RANGE 10 kPa

DATA DIAG PRNT ESC

PARAM C20:PRESS UNIT kPa C21:LOW RANGE 0 kPa C22:HIGH RANGE 10 kPa

DEL CLR ESC

SET C22:HIGH RANGE 30 kPa + 10

•Example 2: With present settings of 0 to 30 kPa, set the higher range value to 10 kPa.

The low range value is notchanged, so the span changes.

Set “10”.

Press the key twice

to enter the setting.

F0717E.EPS

Press the (OK) key.

(3) Damping Time Constant Setup(C30: AMP DAMPING)

When the instrument is shipped, the damping timeconstant is set at 2.0 seconds.

Follow the procedure below to change the timeconstant (Note).

ESC

SET C30:AMP DAMPING 4.0 sec

FEED NO OK

SET C30:AMP DAMPING 2.0 sec < 2.0 sec > < 4.0 sec > < 8.0 sec > < 16.0 sec >

0.2sec0.5sec1.0sec2.0sec4.0sec8.0sec16.0sec32.0sec64.0sec

•Example: Change from 2.0 sec to 4.0 sec.

Use the or

key to select “4.0 sec”.

Press the key twice

to enter the setting.

F0718E.EPS

Press the (OK) key.

Note : The damping time constant set here is the damping timeconstant for the amplifier assembly. The damping timeconstant for the entire transmitter is the sum of the valuesfor the amplifier assembly and for the capsule assembly.For the capsule assembly damping time constant (fixed),see the “General Specifications” found at the end of thismanual.

(4) Output Mode and Integral IndicatorDisplay Mode Setup (C40: OUTPUTMODE)

The mode setting for the output signal and the integralindicator coordinate as shown in the table below.

BT200 Display Output ModeIntegral Indicator

Display Mode

OUT: LIN DSP: LIN

OUT: LIN DSP: SQR

OUT: SQR DSP: SQR

Linear

Linear

Square root

Linear

Square root

Square rootT0704E.EPS

7-9

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

This mode is set as specified in the order when theinstrument is shipped. Follow the procedure below tochange the mode.

If the instrument is equipped with an integral indicatorand the output mode is “square root,” “OUT ” isdisplayed on the integral indicator; if the display modeis “square root,” “DSP ” is displayed on the integralindicator.

For display details, see Chapter 3.

ESC

SET C40:OUTPUT MODE OUT:LIN DSP:SQR

FEED NO ESC

SET C40:OUTPUT MODE OUT:LIN DSP:LIN <OUT:LIN DSP:LIN > <OUT:LIN DSP:SQR.> <OUT:SQR DSP:SQR >

•Example: Set outout mode to “Linear” and displaymode to “Square root”.

F0719E.EPS

Use the or

key to select “OUT: LIN, DSP: SQR”.

Press the key twice

to enter the setting.

Press the (OK) key.

(5) Output Signal Low Cut Mode Setup(D10: LOW CUT, D11: LOW CUT MODE)

Low cut can be used on the output signal to stabilizethe output near the zero point.

The low cut point can be set in a range from 0 to 20%of output. (Hysteresis: ±1%)

Either “LINEAR” or “ZERO” can be selected as thelow cut mode.

Low cut mode “LINEAR” Low cut mode “ZERO”

LOW CUT at 20%

Input

LOW CUT at 20%

Input

Out

put

Out

put

Low cut mode “LINEAR”

• SQRT output signal

• LINEAR output signal

LOW CUT at 20%

Input

Out

put

LOW CUT at 20%

Input

Out

put

(mA)12

(50%)

7.2(20%)

04

(0%) 50 (%) 50 (%)

F0720E.EPS

50 (%)

Low cut mode “ZERO”

50 (%)

(mA)12

(50%)

7.2(20%)

04

(0%)

(mA)12

(50%)

7.2(20%)

04

(0%)

(mA)12

(50%)

7.2(20%)

04

(0%)

FEED NO OK

SET D10:LOW CUT 20.0 %

ESC

SET D11:LOW CUT MODE LINEAR < LINEAR > < ZERO >

DATA DIAG PRNT ESC

PARAM D10:LOW CUT 20.0 % D11:LOW CUT MODE ZERO D20:DISP SELECT NORMAL %

CLR ESC

SET D10:LOW CUT 10.0 % + 20.0

•Example: Change the low cut setting range from10% to 20%, and the low cut mode from “LINEAR” to “ZERO”.

Use the or

key to select “ZERO”.

Press the key twice

to enter the setting.

Press the (OK) key.

F0721E.EPS

Set “20”.

Press the key twice

to enter the setting.

Press the (OK) key.

Next, the [D11: LOW CUT MODE] setting panel is displayed.

• The output signal when the output mode is “linear”and the integral indicator display mode is “squareroot”

In a low cut range, the output signal depends on thelow cut set point value corresponding to the readingvalue on the integral indicator display in %. Forexample shown in the figure below, when D10:LOW CUT is set as 20%, the signal low cut func-tions at the 20% of reading value on the displaywhile the transmitter outputs 4% matching to thereading value.

Low cut mode “LINEAR” Low cut mode “ZERO”

Out

put

Out

put

F0755E.EPS

Input Input0

4

50 (%) 50 (%)0

4

20 20

(%)50

(%)50

Display value Display value

Output signal Output signal

7-10

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

(6) Integral Indicator Scale SetupThe following 2 integral scale indicators can beselected.

F0722E.EPS

D20: DISP SELECT Display/Description Related Parameters

NORMAL %

USER SET

A10: OUTOUT (%)45.6%

A11: ENGR. OUTPUT20.0M

* The number of lines displayed on the LCD is determined by the number of LRV and HRV lines set on the brain terminal.

Indicates -2.5 to 110% range depending on the set range (C21, C22).

Displays values depending on DSP LRV (D22) and DSP HRV.Units set using D21 are not indicated.

See a. through c. for each setting procedure.

% indication and input pressure indication

Transmitter is set

for “% display” when

shipped.

D20: DISP SELECT NORMAL %

User-set engineering unit display

D20: DISP SELECT USER SET

D21: DISP UNIT

D22: DISP LRV

D23: DISP HRV

Set for user-set engineering unit display.

Set a unit to be displayed on the BT200.

Set a numeric value for engineering unit for 4 mA output (LRV).

Set a numeric value for engineering unit for 20 mA output (HRV).

F0723E.EPS

a. Display Selection (D20: DISP SELECT)Follow the instructions given below to change therange of integral indication scales.When USER SET is selected, the user set valuesof integral indication and [A11: ENGR.OUTPUT] are indicated.

•Example: Set the integral indicator scale to engineering units display.

The “%” disappears from the integral indicator display.

ESC

SET D20:DISP SELECT USER SET

FEED NO OK

SET D20:DISP SELECT NORMAL % <NORMAL %> <USER SET>

Use the or

key to select “USER SET”.

Press the key twice

to enter the setting.

Press the (OK) key.

F0724E.EPS

b. Setting User-set Engineering Unit(D21: DISP UNIT)This parameter allows entry of the engineeringunits to be displayed on the BT200. When theinstrument is shipped, this is set as specified inthe order.Follow the procedure below to change thissetting.Since these units are not displayed on the integralindicator, use the adhesive labels provided. Thisparameter need not be set for % display.

CODE CAPS CLR ESC

SET D21:DISP UNIT M

FEED NO OK

SET D21:DISP UNIT M_

•Example: Set an engineering unit “M”.

Set “M”.

Press the key twice

to enter the setting.

Press the (OK) key.

F0725E.EPS

c. Lower and Higher Range Value Setup inEngineering Unit(D22: DISP LRV, D23: DISP HRV)These parameter items are used to set the lowerand higher range values for the engineering unitdisplay.When the instrument is shipped, these are set asspecified in the order.Follow the procedure below to change thesesettings.Note that these parameters need not be set for %display.

7-11

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

DEL CLR ESC

DATA DIAG PRNT ESC

PARAM D21:DISP UNT M D22:DISP LRV – 50M D23:DISP HRV 50M

DEL CLR ESC

SET D22:DISP LRV 0M - 50

SET D23:DISP HRV 100M + 50

•Example: Set lower range value (LRV) to “-50”and higher range value (HRV) to “50”.

Press the (OK) key.

F0726E.EPS

Set “-50”.

Press the key twice

to enter the setting.

Setting LRV

Setting HRV

Set “50”.

Press the key twice

to enter the setting.

(7) Unit Setup for Displayed Temperature(D30: TEMP UNIT)

When the instrument is shipped, the temperature unitsare set to “degC”.

Follow the procedure below to change this setting.Changing the unit here changes the unit for “A20:AMP TEMP” (amplifier temperature), and “A21:CAPSULE TEMP” (capsule temperature) is changed.

ESC

SET D30:TEMP UNIT deg C < deg C > < deg F >

•Example: Change the unit for the temperature display.

F0727E.EPS

Use the or

key to select “deg F”.

Press the key twice

to enter the setting.

(8) Unit Setup for Displayed Static Pressure(D31: STAT.P.UNIT)

Follow the procedure below to change the staticpressure units.

Changing this parameter changes the unit for the“30: STATIC PRESS” (static pressure) display.

ESC

SET C31:STAT.P.UNIT kPa < kPa > < MPa > < mbar > < bar >

mmH2OmmAqmmWGmmHgTorrkPaMPambarbargf/cm2

kgf/cm2

inH2OinHgftH2OpsiatmPahPa

•Example: Change the static pressure unit from “kgf/cm2” to “MPa”.

Use the or

key to select “MPa”.

Press the key twice

to enter the setting.

F0728E.EPS

(9) Operation Mode Setup (D40: REV OUTPUT)

This parameter allows the direction of the 4 to 20mAoutput to be reversed with respect to input.

Follow the procedure below to make this change.

ESC

SET D40:REV OUTPUT NORMAL < NORMAL > < REVERSE>

•Example: Change 4 to 20 mA output to 20 to 4 mA output.

Use the or

key to select “REVERSE”.

Press the key twice

to enter the setting.

F0729E.EPS

(10) Impulse Line Connection Orientationsetup (D45: H/L SWAP)

This parameter allows the impulse line connections tobe reversed at the transmitter.

Follow the figure below to make this change.

Note that this parameter is available for M capsule.

ESC

SET D45:H/L SWAP NORMAL < NORMAL > < REVERSE>

•Example: Change the impulse line connection from high pressure on right to high pressure on left.

Use the or

key to select “REVERSE”.

Press the key twice

to enter the setting.

F0730E.EPS

7-12

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

(11) Output Status Display/Setup when a CPUFailure (D52: BURN OUT)

This parameter displays the status of 4 to 20 mA DCoutput when a CPU failure. If a failure, communicationis disabled.

D52: BURN OUT HIGH

D52: BURN OUT LOW

•Example: Standard specifications

F0731E.EPS

•Example: Optional code /C1

Pin (CN6) position: H

Standard specificationsThe parameter is fixed to HIGH (a change to LOWis not possible). If a failure, output which is 110%or higher is generated.

Optional code /C1Setting of HIGH and LOW is enabled. This is donewith the pin (CN6) on the CPU board assembly.<1> If “HIGH” is generated, output which is 110%

or higher is generated. The parameter “D53:ERROR OUT” is set to HIGH for delivery.

<2> If “LOW” is generated, output which is –5%or lower is generated. The parameter “D53:ERROR OUT” is set to LOW for delivery.

(12) Output Status Setup when a HardwareError Occurs (D53: ERROR OUT)

This parameter allows the setting of the output statuswhen a hardware error occurs. The following threestatuses are available.

(a) HOLD; Outputs the last value held before theerror has occured.

(b) HIGH; Outputs an output of 110% when an errorhas occurred.

(c) LOW; Outputs an output of –2.5% when an errorhas occurred.(In the case of optional code /C1, output at erroroccurrence is –5% or equivalent.)

Note: A hardware error means CAP MODULE FAULT ofEr.01 or AMP MODULE FAULT of Er.02 which areshown in 7.5.2 “Errors and Countermeasures.”

ESC

SET D53:ERROR OUT HIGH < HIGH> < LOW> < HOLD>

•Example: Set the output status to LOW when a hardware error occurs.

Use the or

key to select “LOW”.

Press the key twice

to enter the setting.

F0732E.EPS

(13) Bi-directional Flow Measurement Setup(E30: BI DIRE MODE)

(a) This parameter enables selection of 50% output atan input of 0 kPa.Procedure is shown in the figure below.

(b) Combining this with “C40: OUTPUT MODE”provides a square root output computed indepen-dently for 0% to 50% output and for 50% to100% output.

ESC

SET E30:BI DIRE MODE OFF < OFF > < ON >

•Example: If measurement range is 0 to 10 kPa (LRV = 0 kPa, HRV = 10 kPa).

The measurement range changes to -10 to 0 to 10 kPa (output 0% to 50% to 100).Note that “C21: LOW RANGE” and “C22: HIGH RANGE” are not changed.

Use the or

key to select “ON”.

Press the key twice

to enter the setting.

F0733E.EPS

20mA (100% display)

4mA(-100% display)

Output mode “LINEAR”

LRV HRV

F0734E.EPS

20mA (100% display)Low Cut

4mA (-100% display)

Output mode “SQUARE ROOT”

LRV HRV

7-13

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

(14) Range Change while applying ActualInputs (H10: AUTO LRV, H11: AUTO HRV)

This feature allows the lower and higher range valuesto be set up automatically with the actual input applied.If the lower and higher range values are set, “C21:LOW RANGE” and “C22: HIGH RANGE” arechanged at the same time.

Follow the procedure in the figure below.

The measurement span is determined by the higher andlower range values.

Changing the lower range value results in the higherrange value changing automatically, keeping the spanconstant.

FEED NO OK

SET H10:AUTO LRV 0.5000 kPa

DATA DIAG PRNT ESC

PARAM H10:AUTO LRV 0.5000 kPa H11:AUTO HRV 30.500 kPa H60:SELF CHEC GOOD

ESC

SET H10:AUTO LRV 0 kPa + 0

•Example 1: When changing the lower range value to 0.5 kPa for the present setting of 0 to 30 kPa, take the following action with input pressure of 0.5 kPa applied.

F0735E.EPS

The higher range value is changed keeping the span constant.

Parameters C21 and C22 are changed at the same time.

Press the key twice.

The lower range value is changed to 0.5 kPa.

Press the (OK) key.

Note that changing the higher range value does notcause the lower range value to change but also changesthe span.

FEED NO OK

SET H11:AUTO HRV 10.000 kPa

DATA DIAG PRNT ESC

PARAM H10:AUTO LRV 0 kPa H11:AUTO HRV 10.000 kPa H60:SELF CHECK GOOD

ESC

SET H11:AUTO HRV 30 kPa + 30

•Example 2: When the higher range value is to be changed to 10 kPa with the present setting of 0 to 30 kPa, take the following action with an input pressure of 10 kPa applied.

The lower range value is not changed, so the span changes.

Parameter C22 is changed at the same time.

Press the key twice.

The higher range value is changed to 10 kPa.

Press the (OK) key.

F0736E.EPS

(15) Zero Point Adjustment (J10: ZERO ADJ,J11: ZERO DEV, J20: EXT ZERO ADJ)

The DPharp supports several adjustment methods.

Select the method best suited for conditions matchingthe state of the site.

Note that output signal can be checked by displayingparameter “A10: OUTPUT(%)” on the BT200.

Adjustment Method Description

Zero adjustment using the BT200.

Zero adjustment using the external zero-adjustment screw. P.7-14

Set the present input to 0%. P.7-14Adjust for 0% output at input level of 0%.

Adjust output to the reference value obtained using other means. P.7-14If the input level cannot easily be made 0% (because of tank level, etc.), adjust output to the reference value obtained using other means, such as a sight glass.

Adjust zero point using the zero-adjustment screw on the transmitter.This permits zero adjustment without using the BT200.Accurately adjust the output current to 4 mA DC or other target output value using an ammeter that accuratly reads output currents.

T0704E.EPS

7-14

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

(a) Follow the procedure below when setting thepresent output to 0% (4 mA).

FEED NO OK

SET J10:ZERO ADJ 0.0 %

CLR ESC

SET J10:ZERO ADJ 0.0 % + 000.0

A10:OUTPUT (%) 0.5 %

A10:OUTPUT (%) 0.0 %

Press the key twice.

Zero adjustment is completed.

Press the (OK) key.

F0737E.EPS

Output is 0.5%.

Output is 0%.

(b) In tank level measurement, if the actual levelcannot be brought to zero for zero adjustment,then the output can be adjusted to correspond tothe actual level obtained using another measuringinstrument such as a sight glass.

100%

0%

Present level 45%

Present level : 45%Present output : 41%

DPharp

F0738E.EPS

(b)-1Follow the procedure below to use“J10: ZERO ADJ”.

CLR ESC

SET J10:ZERO ADJ 0.0 % + 045.0

F0739E.EPS

A10:OUTPUT (%) 41.0 %

A10:OUTPUT (%) 45.0 %

Enter the present actual level, 45%.

Press the key twice.

The output is changed to 45%.

Present output is 41.0%.

(b)-2Follow the procedure below to use“J11: ZERO DEV.”.

ECS

ESC

SET J11:ZERO DEV. 2.50 % 0

A10:OUTPUT (%) 41.0 %

A10:OUTPUT (%) 45.0 %

SET J11:ZERO DEV. 2.50 % 6.50

Output error = 45.0–41.0 = 4.0%

Correction = previous correction+ output error = 2.50+4.0 = 6.50%

“J11: ZERO DEV.” contains the previous correction.

Set the correction value to 6.50.

Press the key twice.

F0740E.EPS

Present output is 41.0%.

The output is changed to 45%.

(c) Zero Point Adjustment Using the External ZeroAdjustment Screw• Enabling/inhibiting zero point adjustment

using the external zero-adjustment screw onthe transmitter (J20:EXT ZERO ADJ)Follow the procedure below to enable orinhibit zero point adjustment from the zero-adjustment screw on the transmitter.This is set to “ENABLE” when the instrumentis shipped.When zero adjustment from the external zeroadjustment screw is enabled, “E. ZERO” isdisplayed on the integral indicator.

ESC

SET J20:EXIT ZERO ADJ ENABLE < ENABLE > < INHIBIT>

•Example: Inhibiting zero adjustment by the external zero-adjustment screw.

Use the or

key to select “INHIBIT”.

Press the key twice

to enter the setting.

F0741E.EPS

7-15

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

• Zero point adjustment using external zero-adjustment screw on the transmitterTurn the zero-adjustment screw on the outsideof the transmitter case using a slotted screw-driver. Turn the screw to the right to increasethe zero point or to the left to decrease thezero output; the zero adjusts in increments of0.01% of the range setting.Note that the amount of adjustment to the zeropoint changes according to the speed at whichthe screw is turned. To make fine adjustments,turn the screw slowly; to make coarse adjust-ments, turn the screw quickly.

Note : When a zero point adjustment has been made, do not turnoff the transmitter less than 30 seconds after adjustment.

Zero-adjustment screwF0742.EPS

(16) Test Output Setup (K10: OUTPUT X%)This feature can be used to output a fixed current from3.6 mA (–2.5%) to 21.6 mA (110%) for loop checks.

ESC

SET K10:OUTPUT X % 50.0 % ACTIVE

FEED NO OK

SET K10:OUTPUT X % 0.0 % + 050.0

•Example: Output 12 mA (50%) fixed current.

Set “50.0%”.

Press the key twice

to output a fixed current at 50%.

“Active” is displayed while this is being executed.

Press the (OK) key to

cancel the fixed current output.

F0743E.EPS

IMPORTANT

1. Test output is held for approximately 10minutes, and then released automaticallyafter the time has elapsed. Even if the BT200power supply is turned off or the communica-tion cable is disconnected during test output,it is held for approximately 10 minutes.

2. Press the (OK) key to release test output

immediately.

(17) Ambient Temperature Zero Shift Compen-sation

This function is used to compensate the zero shift bythe ambient temperature effect on the capillary tubes.

<1> DFS Mode Setup (E10: DFS MODE)When using the function, set the DFS MODE to“ON” to enable or “OFF” to disable.To set to “ON”, follow the procedure below.

ESC

SET E10:DFS MODE OFF < OFF > < ON >

F0744E.EPS

<1> Set the DFS mode to “ON”.

Use the or

key to select “ON”.

Press the key twice

to enter the setting.

Press the (OK) key.

<2> Reference Temperature Sensor Setup (E14:TEMP SELECT)“CAP. TEMP” is selected for use.Follow the procedure below.

ESC

SET E14:TEMP SELECT AMP.TEMP < AMP.TEMP > < CAP.TEMP >

F0745E.EPS

<2> Set the TEMP SELECT to “CAP.TEMP”.

Use the or

key to select “CAP.TEMP”.

Press the key twice

to enter the setting.

Press the (OK) key.

<3> Zero Shift Compenation Setup (E15: TEMPZERO)Obtain the compensation value of K from theequation (1) below. Then enter the value toexecute. The value can be rounded off to twodecimal places.

K= – × 100 • • • • • • (1)h × BSpan

7-16

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

Where,h: Distance from high side of diaphragm seal tolow side of diaphragm seal(m).B: Constant value of fill fluid (see Table A.below)span: |HRV–LRV|Example: When h = 3 m, fill fluid code A, andspan = 15 kPa,

K = – × 100 = – 0.15(3) × 0.0074515

ESC

F0746E.EPS

CLR

SET E15:TEMP ZERO 0.00 -0.15

<3> Enter the value of K obtained from the equation (1).

Enter “-0.15”.

Press the key twice

to enter the setting.

Press the (OK) key.

F0747E.EPS

Low side

High side

Transmitter body

h

Note1: The function is engaged in a built-in temperature sensorin the transmitter body. The temperature deviationbetween the transmitter body and capillaries should beminimized to achieve optimal performance of thefunction.

Note2: When the span changes, reenter the newly obtained valueof K to E15: TEMP ZERO.

Table A. Constant Value [B] of Fill Fluid

Fill fluid code

Co

nst

ant

valu

e [B

]

A, C, 1, 2 B D E, P

mmH2O

kgf/cm2

kPa

mBar

atm

inH2O

psi

mmHg

0.76

0.000076

0.00745

0.07453

0.000074

0.02992

0.00108

0.05592

0.87

0.000087

0.00853

0.08532

0.000084

0.03425

0.00124

0.06401

1.45

0.000145

0.01422

0.14220

0.000140

0.05709

0.00206

0.10669

0.75

0.000075

0.00736

0.07355

0.000073

0.02953

0.00167

0.05518

T0706E.EPS

Note : Select the constant value of [B] from the actual unit used shown in the table.

(18) User Memo Fields (M: MEMO)This feature provides 5 user memo fields, each holdingup to 8 alphanumeric characters. Up to 5 items such asinspection date, inspector, and other information can besaved in these fields.

DATA DIAG PRNT ESC

SET M10:MEMO 1

00.4.1_

ESC

PARAM M10:MEMO 1

M20:MEMO 2

M30:MEMO 3

•Example: Save an inspection date of April 1, 2000.

Set “00.4.1” in the order of year, month, and day.

Press the key twice

to enter the setting.

F0748E.EPS

7.4 Displaying Data Using theBT200

7.4.1 Displaying Measured Data

The BT200 can be used to display measured data.

The measured data is updated automatically every 7seconds.

In addition, the display can be updated to the present

data value at any time by pressing the (DATA)

key. For parameters associated with the display ofmeasured data, see the Parameter Summary later in thismanua1.

DATA DIAG PRNT ESC

PARAM A10:OUTPUT (%) A11:ENGR.OUTPUT A20:AMP TEMP

HOME SET ADJ ESC

MENU A:DISPLAY B:SENSOR TYPE

PARAM A10:OUTPUT (%) XX.X % A11:ENGR.OUTPUT YY.Y % A20:AMP TEMP ZZ deg C

communi

•Example: Display output.

F0749E.EPS

Data is updated automatically at 7-secondintervals.

display “A10 : OUTPUT (%)”.

7-17

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

7.4.2 Display Transmitter Model andSpecifications

The BT200 can be used to display the model andspecifications of the transmitter.

HOME SET ADJ ESC

MENU A:DISPLAY B:SENSOR TYPE

DATA DIAG PRNT ESC

PARAM B10:MODEL EJ118W-DM B11:STYLE NO. S2.XX B20:LRL – 98.07 kPa

•Example: View transmitter model name.

For the associated parameters, see the Parameter Summary later in this manual.

F0750E.EPS

7.5 Self-Diagnostics

7.5.1 Checking for Problems

(1) Identifying Problems with BT200The following four areas can be checked.

(a) Whether connections are good. (b) Whether BT200 was properly operated. (c) Whether settings were properly entered. (d) History of the errors.Refer to the following examples.

ESC

communication error

––WELCOME––BRAIN TERMINAL ID: BT200

check connection push ENTER key

UTIL FEED

•Example 1: Connection errors

Connect the BT200 to the transmitter.

Press the key.

When the panel shown on the left

appears, press the key.

Since communications will be unsuccessful if there is a problem in the connection to the BT200, the display at the left will appear.

Recheck the connection.

Press the (ESC) key.

F0751E.EPS

DATA DIAG PRNT ESC

PARAM C20:PRESS UNIT kPa C21:LOW RANGE 600 kPa C22:HIGH RANGE 600 kPa

FEED PRNT ESC

DIAG C60:SELF CHECK ERROR < ERROR > < ILLEGAL LRV >

OK

PARAM 01:MODEL EJ118W-DM 02:TAG NO. YOKOGAWA 03:SELF CHECK ERROR

•Example 2: Setting entry errors

F0752E.EPS

The initial data panel shows the result of current DPharp diagnostics.

Press the (DIAG) key in the

parameter panel to go to the diagnostics panel (C60: SELF CHECK).

An error message is displayed when an error occurs in the diagnostics panel.

7-18

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

HOME SET ADJ ESC

MENU J:ADJUST K:TEST M:MEMO P:RECORD

DATA DIAG PRNT ESC

PARAM P10:ERROR REC 1 ERROR P11:ERROR REC 2 ERROR P12:ERROR REC 3 GOOD

ESC

SET P10:ERROR REC 1 ERROR < ERROR > < ILLEGAL LRV > < ILLEGAL HRV >

•Example 3: Checking the history of the errors

Connect the BT200 to the transmitter, and call item “P”.

Setting P10: “ERROR REC 1” displays the last error.P11: “ERROR REC 2” displays the error one time

before the last error occurred.P12: “ERROR REC 3” displays the error two times

before the last error occurred.P13: “ERROR REC 4” displays the error three

times before the last error occurred.The history of up to four errors can be stored.When the 5th error has occurred, it is stored in “P10”. The error stored in “P13” will be deleted, and then, the error in “P12” will be copied to “P13”.In this sequence, the history of the most previously occurred error will be removed from memory.“GOOD” will be displayed if there was no previous error.

Select P10: ERROR REC 1 and press the key to displsy error information.

F0753E.EPS

The display and the contents of the error messages are those shown in 8.5.2 “Error and Countermeasures”.

<1> SETUP PANEL

Note 1: Press the key twice in the setting panel (panel 1) to clear all error message (P10 to P13) information.

Note 2: After two hours from when an error occurs, the error message of that error will be recorded.Therefore, if you switch off the transmitter within two hours from when the error occurs, there is no history of that error stored in the transmitter, and this function is meaningless.

CAP MODULE FAULTAMP MODULE FAULTOUT OF RANGEOUT OF SP RANGEOVER TEMP (CAP)OVER TEMP (AMP)

OVER OUTPUTOVER DISPLAYILLEGAL LRVILLEGAL HRVILLEGAL SPANZERO ADJ OVER

(2) Checking with Integral Indicator

NOTE

If an error is detected in the self-diagnostic, anerror number is displayed on the integral indica-tor. If there is more than one error, the errornumber changes at two-second intervals.See Table 7.5.2 regarding the error numbers.

F0754E.EPS

Figure 7.5.1 Identifying Problems Using the IntegralIndicator

7-19

7. BRAIN TERMINAL BT200 OPERATION

IM 01C20H01-01E

7.5.2 Errors and Countermeasures

The table below shows a summary of error messages.

Table 7.5.1 Error Message Summary

Integral Indicator Display

BT200 Display Cause CountermeasureOutput Operation

during Error

None

– – – –

Er. 01

Er. 02

Er. 03

Er. 04

Er. 05

Er. 06

Er. 07

Er. 08

Er. 09

Er. 10

Er. 11

Er. 12

GOOD

ERROR

CAP MODULE FAULT

AMP MODULE FAULT

OUT OF RANGE

OUT OF SP RANGE

OVER TEMP (CAP)

OVER TEMP (AMP)

OVER OUTPUT

OVER DISPLAY

ILLEGAL LRV

ILLEGAL HRV

ILLEGAL SPAN

ZERO ADJ OVER

Capsule problem

Amplifier problem

Input is outside measurement range limit of capsule.

Static pressure exceeds specified range.

Capsule temperature is outside range (–50 to 130°C).

Amplifier temperature is outside range (–50 to 95°C).

Output is outside high or low range limit value.

Displayed value is outside high or low range limit value.

LRV is outside setting range.

HRV is outside setting range.

SPAN is outside setting range.

Zero adjustment is too large.

Outputs the signal (Hold, High, or Low) set with parameter D53.

Outputs the signal (Hold, High, or Low) set with parameter D53.

Outputs high range limit value or low range limit value.

Displays present output.

Displays present output.

Displays present output.

Outputs high or low range limit value.

Displays high or low range limit value.

Holds output immediately before error occurrence.

Holds output immediately before error occurrence.

Holds output immediately before error occurrence.

Displays present output.

Replace capsule.

Replace amplifier.

Check input.

Check line pressure (static pressure).

Use heat insulation or make lagging to keep temperature within range.

Use heat insulation or make lagging to keep temperature within range.

Check input and range setting, and change them as needed.

Check input and display conditions and modify them as needed.

Check LRV and modify as needed.

Check HRV and modify as needed.

Check SPAN and change as needed.

Readjust zero point.

T0707E .EPS

IM 01C20H01-01E8-1

8. MAINTENANCE

8. MAINTENANCE

8.1 Overview

WARNING

Since the accumulated process fluid may betoxic or otherwise harmful, take appropriate careto avoid contact with the body, or inhalation ofvapors during draining condensate or ventinggas in transmitter pressure-detector section andeven after dismounting the instrument from theprocess line for maintenance.

Maintenance of the transmitter is easy due to itsmodular construction. This chapter describes theprocedures for calibration, adjustment, and the disas-sembly and reassembly procedures required forcomponent replacement.

Since the transmitters are precision instruments,carefully and thoroughly read the following sectionsfor proper handling during maintenance.

IMPORTANT

• As a rule, maintenance of this transmittershould be implemented in a maintenanceservice shop where the necessary tools areprovided.

• The CPU assembly contains sensitive partsthat may be damaged by static electricity.Exercise care so as not to directly touch theelectronic parts or circuit patterns on the board,for example, by preventing static electrificationby using grounded wrist straps when handlingthe assembly.Also take precautions such as placing a re-moved CPU assembly into a bag with anantistatic coating.

8.2 Calibration Instrument Selec-tion

Table 8.2.1 shows the instruments required for calibra-tion. Select instruments that will enable the transmitterto be calibrated or adjusted to the required accuracy.

The calibration instruments should be handled carefullyso as to maintain the specified accuracy.

8.3 CalibrationUse the procedure below to check instrument operationand accuracy during periodic maintenance or trouble-shooting.

<1> Connect the instruments as shown in Figure 8.3.1and warm up the instruments for at least fiveminutes.

IMPORTANT

1. To adjust the transmitter for highest accuracy,make adjustments with the power supplyvoltage and load resistance including leadwireresistance set close to the conditions underwhich the transmitter is installed.

2. If the measurement range 0% point is 0 kPa0 mmH2O or shifted in the positive direction(suppressed zero), the positive referencepressure should be applied on the highpressure side, as shown in the figure. If themeasurement range 0% point is shifted in thenegative direction (elevated zero), the positivereference pressure should be applied on thelow pressure side.

<2> Apply reference pressures of 0%, 25%, 50%,75%, and 100% of the measurement range to thetransmitter. Calculate the errors (differencesbetween digital voltmeter readings and referencepressures) as the pressure is increased from 0% to100% and is decreased from 100% to 0%, andconfirm that the errors are within the requiredaccuracy.

IM 01C20H01-01E8-2

8. MAINTENANCE

Table 8.2.1 Instruments Required for Calibration

Name RemarksYokogawa-recommended Instrument

Power supply Model SDBT or SDBS distributor

Load resistor

Model 2792 standard resistor [250 Ω ±0.005%, 3 W]

Load adjustment resistor [100 Ω ±1%, 1 W]

VoltmeterModel 2501 A digital multimeter Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)

Digital manometer

Model MT220 precision digital manometer1) For 10 kPa class

Accuracy: ±(0.015% of rdg + 0.015% of F.S.)±(0.2% of rdg + 0.1% of F.S.)

2) For 130 kPa classAccuracy: ±0.02% of rdg

±5digits±(0.2% of rdg + 0.1% of F.S.)

3) For 700 kPa classAccuracy: ±(0.02% of rdg + 3digits)

±5 digits ±(0.2% of rdg + 0.1% of F.S.)

4) For 3000 kPa classAccuracy: ±(0.02% of rdg + 10 digits)

±(0.2% of rdg + 0.1% of F.S.) 5) For 130 kPa abs class

Accuracy: ±(0.03% of rdg + 6 digits)

4 to 20 mA DC signal

Select a manometer having a pressure range close to that of the transmitter.

Pressure generator

Model 7674 pneumatic pressure standard for 200 kPa 2 kgf/cm2, 25 kPa 2500 mmH2OAccuracy: ±0.05% of F.S.

Requires air pressure supply.

Pressure source

Model 6919 pressure regulator (pressure pump)Pressure range: 0 to 133 kPa 1000 mmHg

Prepare the vacuum pump for negative pressure ranges.

Dead weight gauge tester 25 kPa 2500mmH2O Accuracy: ±0.03% of setting

Select the one having a pressure range close to that of the transmitter.

T0801E.EPS

for 0 to 10 kPafor -10 to 0 kPa

for 25 to 130 kPafor 0 to 25 kPafor -80 to 0 kPa

for 100 to 700 kPafor 0 to 100 kPafor -80 to 0 kPa

for 0 to 3000 kPafor -80 to 0 kPa

for 0 to 130 kPa abs

. . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . .

. . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . .

Note 1: The above table contains the instrumentscapable of performing calibration to the 0.2%level. Since special maintenance and manage-ment procedures involving traceability of eachinstrument to higher-level standards arerequired for calibration to the 0.1% level,there are difficulties in calibration to this levelin the field.For calibration to the 0.1% level, contactYokogawa representatives from which theinstrument was purchased or the nearestYokogawa office.

Note 2: If a liquid column manometer is to be usedfor calibration as a calibration manometer, itsreadings must be corrected to achieve propercalibration as shown below.

The formula below is for the case of a mercurymanometer with a brass scale.

Ls=L1–0.000163 (t–t0) – 0.00026cos2∅ – 2h×10–7

where

∅ : Latitudet : Working temperature, °Ct0 : Manometer reference temperature, °Ch : Altitude, mL : Liquid column reading, mLs : Liquid column (m) reading converted to h=0m,

∅ =45°Example :

• Correction for altitude and latitude in Tokyo isapproximately –0.09%.

• Correction at 23°C for a manometer with referencetemperature of 20°C is approximately –0.05%.

IM 01C20H01-01E8-3

8. MAINTENANCE

P

P

VRc R

F0801E.EPS

– +

Pressure source

If a pressure source and a manometer are combined:

Supply pressure

If a pressure generator is used:

Load adjustment resistor, 100Ω

Power supply E

Load resistor, 250Ω

Digital voltmeter

Mating calibration flange

High pressure side diaphragm seal

Low pressure side diaphragm seal

Precision digital manometer

Pneumatic pressure generator

Figure 8.3.1 Instrument Connections

8.4 Disassembly and Reassem-bly

CAUTION

Cautions for Flameproof Type Transmitters1. Flameproof type transmitters must be, as a

rule, removed to a non-hazardous area formaintenance and be disassembled andreassembled to the original state. For details,see “Installation and Operating Precautionsfor Intrinsically Safe Explosion-ProtectedInstruments” and “Instllation and OperatingPrecautions for Flameproof Explosion-Protected Instruments” at the end of thismanual.

2. When servicing a flameproof type transmitter,always detach the shrouding washers beforeremoving the cover, and never fail to re-tighten them after replacing the cover.

This section describes procedures for disassembly andreassembly for maintenance and component replace-ment.

Always turn OFF power and shut off and releasepressures before disassembly and reassembly. Useproper tools for all operations. Table 8.4.1 shows thetools required.

Table 8.4.1 Tools for Disassembly and Reassembly

Tool RemarksQuantity

Phillips screwdriver

Slotted screwdriver

Allen wrenches

Wrench

Torque wrench

Adjustable wrench

Socket wrench

Tweezers

1

1

3

1

1

1

1

1

JIS B4633, No. 2

JIS B4648One each, nominal 2, 4, and 5mm Allen wrenches

Width across flats, 19mm

Width across flats, 6mm

T0802E.EPS

8.4.1 Replacing the Integral Indicator

This subsection describes the procedure for replacingan integral indicator.

CAUTION

Cautions for Flameproof Type TransmittersUsers are prohibited by law from modifying theconstruction of a flameproof type transmitter.Thus the user is prohibited from using a flame-proof type transmitter with its integral indicatorremoved, or from adding an integral indicator toa transmitter. If such modification is absolutelyrequired, contact Yokogawa.

Removing the Integral Indicator<1> Remove the cover.<2> Supporting the integral indicator by hand, loosen

its two mounting screws.<3> Dismount the LCD board assembly from the CPU

board assembly.When doing this, carefully pull the LCD boardassembly straight forward so as not to damage theconnector between it and the CPU board assem-bly.

IM 01C20H01-01E8-4

8. MAINTENANCE

Attaching the Integral Indicator<1> Align both the LCD board assembly and CPU

board assembly connectors and engage them.<2> Insert and tighten the two mounting screws.<3> Replace the cover. (See Figure 8.4.1.)

F0802E.EPS

Cover

Integral indicator

Mounting screw

LCD board assembly

Connectors

Figure 8.4.1 Removing and Attaching Integral Indicator

8.4.2 Replacing the CPU Board Assembly

This subsection describes the procedure for replacingthe CPU board assembly.

Removing the CPU Board Assembly<1> Remove the cover.

If an integral indicator is mounted, refer toSubsection 8.4.1 and remove the indicator.

<2> Turn the zero-adjustment screw to the position(where the screw head slot is horizontal) shownin Figure 8.4.2.

<3> Disconnect the output terminal cable (cable withbrown connector at the end).When doing this, lightly press the side of theCPU board assembly connector and pull the cableconnector to disengage. (See Figure 8.4.3.)

<4> Disconnect the flat cable (cable with blackconnector at the end) that connects the CPUboard assembly and the capsule.

<5> Use a socket wrench (width across flats, 6mm) toloosen the two bosses.

<6> Carefully pull the CPU board assembly straightforward to remove it.

NOTE

Be careful not to apply excessive force to theCPU board assembly when removing it.

F0803E.EPS

Figure 8.4.2 Zero-Adjustment Screw

Mounting the CPU Board Assembly<1> Connect the flat cable (with black connector)

between the CPU board assembly and thecapsule.

<2> Connect the output terminal cable (with brownconnector).There is a slit in the CPU board assembly intowhich this cable should be fitted during assembly.

NOTE

Do not fail to confirm that the cables are free ofpinching between the case and the CPU boardassembly edge.

<3> Align and engage the zero adjustment screw withthe bracket on the CPU board assembly.Insert the CPU board assembly straight onto thepost in the amplifier case.

<4> Tighten the two bosses.If the transmitter is equipped with an integralindicator, refer to Subsection 8.4.1 to mount theindicator.

<5> Replace the cover.

F0804E.EPS

Output terminal cable

Cover

Integral indicator

Mounting screw

Flat cable

Flat cable

Post

BossCPU board assembly

Press forward

Figure 8.4.3 Removing and Mounting the CPU BoardAssembly

IM 01C20H01-01E8-5

8. MAINTENANCE

8.5 TroubleshootingIf any abnormality appears in the measured values, usethe troubleshooting flow chart below to isolate andremedy the problem. Since some problems havecomplex causes, it will not be possible to identify allusing this flow chart. If you have difficulty isolating orcorrecting a problem, contact Yokogawa servicepersonnel.

8.5.1 Basic Troubleshooting

If abnormal indication is encountered in measuredvalues, first determine whether the process variable isactually abnormal or a problem exists in the measure-ment system. If it can be decided that the problem is inthe measurement system, next isolate the problem anddecide what remedial action to take.

This transmitter is equipped with a self-diagnosticfunction which will be useful in troubleshooting; seeSection 8.5 for information on using this function.

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variable itself abnormal?

Inspect the process system.

Isolate problem in measurement system.

Does problem exist in receiving instrument?

Check transmitter.

Inspect receiver.

Check / correct operating conditions.

Y

Y

N Measurement system problem

N

Operating conditions

Environmental conditions

F0805E.EPS

Check / correct environmental conditions.

Transmitter itself

Figure 8.5.1 Basic Flow and Self-Diagnostics

8.5.2 Troubleshooting Flow Charts

F0806E.EPS

Connect BRAIN TERMINAL and check self-diagnostics.

NO

YES

YES

YES

YES

NO

NO

NO

Contact Yokogawa service personnel.

Does the self-diagnostic indicate problem location?

Is power supply polarity correct?

Are power supply voltage and load

resistance correct?

Is there continuity through the

transmitter loop wiring? Do the loop numbers

match?

Refer to error message summary in Subsection 7.5.2 to take action.

Refer to Section 5.3 to check / correct polarity at each terminal from power supply to the terminal box.

Refer to Section 5.6 for rated voltage and load resistance.

Find / correct broken conductor or wiring error.

The following sorts of symptoms indicate that transmitter may not be operating properly.Example: •There is no output signal.

•Output signal does not change even though process variable is known to be varying.•Output value is inconsistent with value inferred for process variable.

IM 01C20H01-01E8-6

8. MAINTENANCE

F0807E.EPS

Connect BRAIN TERMINAL and check self-diagnostics.

NO

YES

YES

YES

YES

NO

NO

YES

NO

NO

Contact Yokogawa service personnel.

Does the self-diagnostic indicate problem location?

Are high and low pressure side

diaphragm seals correctly connected to the

process?

Is power supply polarity correct?

Is the liquid level as specified?

Is zero point adjusted correctly?

Refer to error message summary in Subsection 7.5.2 to take action.

Check / correct polarity at each terminal from power supply to the terminal box.

Use the transmitter within the measurementrange shown onthe data plate.

Adjust the zero point.

Check the connections.

Output travels beyond 0% or 100%.

F0808E.EPS

Connect BRAIN TERMINAL and check self-diagnostics.

NO

YES

NO

YES

YES

NO

YES

NO

YES

NO

YES

Does the self-diagnostic indicate the

problem location?

Is external noise contained in the

output?

Are power supply voltage

and load resistance correct?

Are excess capillaries secured?

Does the ambient temperature

significantly differ between the high and low pressure

side capillaries?

Is transmitter installed where there is

marked variation in temperature?

Refer to error message summary in Subsection 7.5.2 to take action.

Refer to Section 5.6 to obtain the rated voltage and load resistance.

Avoid noise by providing complete grounding, or using shielded wires.

Secure them so that they are not moved by wind or vibration.

Provide lagging and / or neat insulation, or allow adequate ventilation.

Refer to Section 8.2 when selecting instruments for calibration.

NO

YES

NO

Contact Yokogawa service personnel.

Were appropriate instruments used for

calibration?

YES

NOIs output adjusted correctly?

Adjust the output.

Large output error.

Bind capillaries together as far as possible or provide lagging.

IM 01C20H01-01E9-1

9. PARAMETER SUMMARY

9. PARAMETER SUMMARY

Instruments to which applicable:F : Differentil pressure transmitters ..... EJ110, EJ120, EJ130, EJ118W, EJ118N, EJ118Y, EJ115, EJ135P : Pressure transmitters ..................... EJ310, EJ318W, EJ318N, EJ430, EJ440, EJ438W, EJ438NL : Liqyid level transmitters ................. EJ210, EJ220

T0901E.EPS

No.P LF

DescriptionApplicability

Display Setting RemarksItem

01

02

03

A

A10

A11

A20

A21

A30

A40

A60

B

B10

B11

B20

B21

B30

B40

B60

C

C10

C20

C21

C22

C30

C40

C60

MODEL

TAG NO.

SELF CHECK

DISPLAY

OUTPUT (%)

ENGR. OUTPUT

AMP TEMP

CAPSULE TEMP

STATIC PRESS

INPUT

SELF CHECK

SENSOR TYPE

MODEL

STYLE NO.

LRL

URL

MIN SPAN

MAX STAT.P.

SELF CHECK

SETTING

TAG. NO.

PRESS UNIT

LOW RANGE

HIGH RANGE

AMP DAMPING

OUTPUT MODE

SELF CHECK

Model + capsule type

Tag number

Self-diagnostic result

Measured data display

Output (in %)

Output (in engineering units)

Amplifier temperature

Capsule temperature

Static pressure

Input (indicated in engineering DP unit)

Self-diagnostic messages

Sensor type

Model + span

Style number

Lower range-limit

Upper range-limit

Minimum span

Maximum static pressure

Self-diagnostic messages

Setting data

Tag number

Measurement range units

Measurement range, lower limit value

Measurement range, upper limit value

Damping time constant

Output mode and integral indicator mode

Self-diagnostic messages

16 alphanumerics

GOOD / ERROR

Menu name

–2.5 to 110.0%

–19999 to 19999

Unit specified in D30

Unit specified in D30

Unit specified in D31*

–32000 to 32000

GOOD / ERROR, CAP MODULE FAULT, AMP MODULE FAULT, OUT OF RANGE, OUT OF SP RANGE*, OVER TEMP (CAP), OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY, ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, ZERO ADJ OVER

Menu name

8 uppercase alphanumerics

–32000 to 32000

–32000 to 32000

–32000 to 32000

Same as A60

Menu name

16 alphanumerics

Selected from mmH2O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa, MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O, inHg, ftH2O, psi, or atm

–32000 to 32000(but within measurement range)

–32000 to 32000(but within measurement range)

Selected from 0.2, 0.5, 1.0, 2.0, 4.0, 8.0, 16.0, 32.0, or 64.0 sec

Selected fromOUT: LIN, DSP: LIN, OUT: LIN, DSP: SQR, OUT: SQR, DSP: SQR

Same as A60

*: In case of type EJ120, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.

IM 01C20H01-01E9-2

9. PARAMETER SUMMARY

T0902E.EPS

No.P LF

DescriptionApplicability

Display Setting RemarksItem

D

D10

D11

D20

D21

D22

D23

D30

D31

D40

D45

D52

D53

D60

E

E10

E14

E15

E30

E60

H

H10

H11

H60

J

J10

J11

J20

J60

K

K10

K60

M

M10

M20

M30

M40

M50

M60

AUX SET 1

LOW CUT

LOW CUT MODE

DISP SELECT

DISP UNIT

DISP LRV

DISP HRV

TEMP UNIT

STAT. P. UNIT

REV OUTPUT

H/L SWAP

BURN OUT

ERROR OUT

SELF CHECK

AUX SET 2

DFS MODE

TEMP SELECT

TEMP ZERO

BI DIRE MODE

SELF CHECK

AUTO SET

AUTO LRV

AUTO HRV

SELF CHECK

ADJUST

ZERO ADJ

ZERO DEV.

EXT. ZERO ADJ

SELF CHECK

TEST

OUTPUT × %

SELF CHECK

MEMO

MEMO 1

MEMO 2

MEMO 3

MEMO 4

MEMO 5

SELF CHECK

Auxiliary setting data 1

Low cut

Low cut mode

Display selection

Engineering unit for display

Engineering unit display, low range limit

Engineering unit display, high range limit

Temperature setting units

Static pressure setting units

Output reversal

Impulse piping accessing direction

CPU failure

Hardware error

Self-diagnostic messages

Auxiliary setting data 2

DFS mode

Reference temperature sensor

Zero shift compensation setup

Bidirectional mode

Self-diagnostic messages

Automatic setup

Automatic measurement range low range limit setup

Automatic measurement range high range limit setup

Self-diagnostic messages

Adjustment data

Automatic zero adjustment

Manual zero adjustment

External zero-adjustment screw permission

Self-diagnostic messages

Tests

Tes output % setting

Self-diagnostic messages

Memo

Memo

Memo

Memo

Memo

Memo

Self-diagnostic messages

Menu name

0.0 to 20.0%

LINEAR / ZERO

NORMAL% / USER SET

8 uppercase alphanumerics

–19999 to 19999

–19999 to 19999

deg C/deg F

Selected from mmH2O, mmAq, mmWG, mmHg, Torr, Pa, hPa, kPa, MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O, inHg, ftH2O, psi, or atm

NORMAL / REVERSE

NORMAL / REVERSE*

HIGH

HOLD / HIGH / LOW

Same as A60

Menu name

OFF, ON**

AMP. TEMP / CAP. TEMP**

±10.00**

OFF / ON

Same as A60

Menu name

–32000 to 32000

–32000 to 32000

Same as A60

Menu name

–2.5 to 110.0%

ENABLE / INHIBIT

Same as A60

Menu name

–2.5 to 110.0%Displays “ACTIVE” while executing

Same as A60

Menu name

8 uppercase alphanumerics

8 uppercase alphanumerics

8 uppercase alphanumerics

8 uppercase alphanumerics

8 uppercase alphanumerics

Same as A60

* : Parameter D45 is not applicable for EJ115 and EJ135.**: Parameter E10, E14, and E15 are applicable for EJ118W, EJ118N, EJ118Y, EJ318W, EJ318N, EJ438W and EJ438N

diaphragm sealed pressure transmitters only.

IM 01C20H01-01E10-1

10. GENERAL SPECIFICATIONS

10. GENERAL SPECIFICATIONS

10.1 Standard Specifications

Performance SpecificationsSee General Specifications sheet, GS 01C20H01-00E (Forwetted parts material code H, T, or U, refer toGS 01C20V01-00E).

Functional Specifications

Span and Range Limits:Capsule Measurement Span Measurement Range

V

2.5 to 130 kPa250 to 13000 mmH2O

14 to 700 kPa0.14 to 7 kgf/cm2

0.28 to 13.7 MPa2.8 to 140 kgf/cm2

130 to 130 kPa13000 to 13000 mmH2O

100 to 700 kPa1 to 7.0 kgf/cm2

0.1 to 13.7 MPa1 to 140 kgf/cm2

H

M

T1101E.EPS

Output Signal: 4 to 20 mA DC, 2-wire system

Failure Alarm:Output status at CPU failure;

Up-scale: 110%, 21.6 mA DC or more (fixed)Output status at Hardware error;

Up-scale: 110%, 21.6 mA DC (standard)Down-scale: –2.5%, 3.6 mA DC

Conditions of Communication Line:Power supply voltage;

18 to 42 V DC *Load resistance;

See Figure 10.1.Note: In case of an intrinsically safe transmitter, external load

resistance includes safety barrier resistance.Communication distance;

2 km *, when polyethylene-insulated PVC-sheathedcontrol (CEV) cables are used.

Load capacitance;0.22 F * or less.

Load inductance;3.3 mH * or less.

Spacing from power line;15 cm or more.* For general type and flameproof type.

Ambient Temperature Limits:–40 to 60C (–40 to 140F) (general-use type)–30 to 60C (–22 to 140F) (with integral indicator)

(See ‘Optional Specifications’ for Explosion-protectedtypes)Note: The ambient temperature limits must be within the fill

fluid operating temperature range, see Table 10.1.

Process Temperature Limits:See Table 10.1.

Ambient Humidity Limits:5 to 100% R.H. (at 40C)

Working Pressure Limits:2.7 kPa abs 20 mmHg abs to flange rating pressure.For atmospheric pressure or below, see Figure 10.2

Power Supply Effect:0.005%/V (21.6 to 32 V DC, 350 )

Mounting:Transmitter; 2-inch pipe mountingDiaphragm seals; flange mounting

Mounting Flange Rating:See ‘Model and Suffix Code.’Flanges conforming to ANSI are serrated on their gasketsurfaces (ANSI B16.5).Note: For model EJ118W with wetted parts material code H,

T, or U, no serration is done.

Explosion-protected Construction:See ‘Optional Specifications.’

Integral Indicator:LCD digital indicator (optional)

EMC Conformity Standards: AS/NZS CISPR11

Damping Time Constant:(Sum of time constants for amplifier assembly and capsuleassembly)

• Amplifier assembly time constant; Can be set in 9increments from 0.2 to 64 sec.

• Approximate capsule assembly damping time constantvalues obtained at normal temperature when thecapillary length is 3 m and the fill fluid code is A;

Capsule M

Time Constant(sec)

Approx.0.9

H

Approx.0.7

V

Approx.0.7

T1102E.EPS

External Zero Adjustment:Continuously adjustable

Resolution; 0.01% of span

Zero Adjustment Limits:Zero can be fully elevated or suppressed as long as low andhigh range values are within the measurement range limitsof the capsule.

Physical SpecificationsWetted Parts Materials:

Diaphragm and other wetted parts;See ‘Model and Suffix Codes’

Capillaries;JIS SUS316

Protection tubes;JIS SUS304, PVC-sheathed [Max. operating temperatureof PVC, 100C (212F)]

Fill fluid;See Table 10.1.

IM 01C20H01-01E10-2

10. GENERAL SPECIFICATIONS

Non-wetted Parts Materials:Transmitter cover flange;

JIS SUS316Transmitter cover flange bolts;

See ‘Model and Suffix Codes’

Degrees of Protection:IP67, NEMA4, JIS C0920

Painting:Polyurethane resin baked finish.

For case; frosty white (Munsell 2.5Y8.4/1.2)For cover: deep sea moss green (Munsell 0.6GY3.l /2.0)

Weight:[EJ118 with JIS 10K flange]

24.0 kg (52.9 lb) (with mounting bracket)Connections:

Refer to the ‘Model and Suffix Codes’ to specify the processand electrical connection type.

R=

250

600

12 17.9 42

Power supply voltage E (V DC)

Communicationapplicable

range

F1101E.EPS

26.2

E–120.0236External

load resistanceR ()

Figure 10.1 Relationship Between Power Supply Voltageand External Load Resistance

F1102E.EPS

Process temperaturefor fill fluid code B

Process temperaturefor fill fluid code A

Process temperaturefor fill fluid code C

Flange max.working pressure

Atmo-sphericpressure

Transmitter ambienttemperature range(For fill fluid code A, B)

2.7 20

Process Temperature (C)

Working pressurekPa abs

mmHg abs

100 750

0.1 0.75

1 7.5

10 75

50 0 50 100 150 200 250 300

Figure 10.2 Working Pressure and Process Temperature

Table 10.1 Process Temperature and Ambient Temperature

Silicone Oil Fluorinated Oil Ethylene Glycol

Fill FluidCode ‘A’

Fill FluidCode ‘B’

Fill FluidCode ‘C’

Fill FluidCode ‘D’

Fill FluidCode ‘E’

Processtemperature

-10 to 250 C(14 to 482 F)

-30 to 180 C(-22 to 356 F)

10 to 300 C(50 to 572 F)

-20 to 120 C(-4 to 248 F)

-50 to 100 C(-58 to 212 F)

Ambienttemperature

-10 to 60 C(14 to 140 F)

-15 to 60 C(5 to 140 F)

10 to 60 C(50 to 140 F)

-20 to 60 C(-4 to 140 F)

-40 to 60 C(-40 to 140 F)

Working pressure See Figure 10.251 kPa abs or more380 mmHg abs

Vacuum pressure notallowed

Specific gravity 1.07 0.94 1.09 1.90 to 1.92 1.09

T1103E.EPS

Table 10.2 Calibration Units

MeasurementSpan and

Range

Optional code

EJ1

18W

EJ1

18N

, Y

D1 (psi Unit) D3 (bar Unit) D4 (kgf/cm2 Unit)

MSpan 10 to 520 inH2O 25 to 1300 mbar 250 to 13000 mmH2O

Range -520 to 520 inH2O -1300 to 1300 mbar -13000 to 13000 mmH2O

HSpan 56 to 2800 inH 2O 140 to 7000 mbar 0.14 to 7 kgf/cm 2

Range -400 to 2800 inH 2O -1000 to 7000 mbar -1 to 7 kgf/cm 2

VSpan 40 to 2000 psi 2.8 to 137 bar 2.8 to 140 kgf/cm 2

Range -15 to 2000 psi -1 to 137 bar -1 to 140 kgf/cm 2

MSpan 10 to 520 inH2O 25 to 1300 mbar 250 to 13000 mmH2O

Range -520 to 520 inH2O -1300 to 1300 mbar -13000 to 13000 mmH2O

HSpan 56 to 2800 inH 2O 140 to 7000 mbar 0.14 to 7 kgf/cm 2

Range -400 to 2800 inH 2O -1000 to 7000 mbar -1 to 7 kgf/cm 2

T1108E.EPS

IM 01C20H01-01E10-3

10. GENERAL SPECIFICATIONS

10.2 Model and Suffix Codes

Model EJ118W

Model Suffix codes Description

EJ118W · · · · · · · · · · · · · · · · · · · · · · · · · · · · Diaphragm sealed differential pressure transmitter (Flush diaphragm type)

Output signal -D · · · · · · · · · · · · · · · · · · · · · · · · · · 4 to 20 mA DC with digital communication (BRAIN protocol)

Measurement span(capsule)

M · · · · · · · · · · · · · · · · · · · · · · · · · · H · · · · · · · · · · · · · · · · · · · · · · · · · · V · · · · · · · · · · · · · · · · · · · · · · · · · ·

2.5 to 130 kPa 250 to 13000 mmH2O14 to 700 kPa 0.14 to 7 kgf/cm20.28 to 13.7 MPa 2.8 to 140 kgf/cm2

Wetted parts material S · · · · · · · · · · · · · · · · · · · · · · ·

H · · · · · · · · · · · · · · · · · · · · · · ·T · · · · · · · · · · · · · · · · · · · · · · · U · · · · · · · · · · · · · · · · · · · · · · ·

Process flange rating J1 · · · · · · · · · · · · · · · · · · · · ·J2 · · · · · · · · · · · · · · · · · · · · · J4 · · · · · · · · · · · · · · · · · · · · · A1 · · · · · · · · · · · · · · · · · · · · · A2 · · · · · · · · · · · · · · · · · · · · ·A4 · · · · · · · · · · · · · · · · · · · · ·

JIS 10KJIS 20KJIS 40KANSI class 150ANSI class 300ANSI class 600

Process flange size/material

D · · · · · · · · · · · · · · · · · · · · E · · · · · · · · · · · · · · · · · · · ·

Installation -0 · · · · · · · · · · · -2 · · · · · · · · · · ·

Vertical impulse piping type, left side terminal boxVertical impulse piping type, right side terminal box

Electrical connection 0 · · · · · · · · · · 1 · · · · · · · · · · 2 · · · · · · · · · · 5 · · · · · · · · · · 6 · · · · · · · · · · 7 · · · · · · · · · ·

G 1/2 femaleG 3/4 female1/2 NPT female G 1/2 female, with external indicator connectionG 3/4 female, with external indicator connection1/2 NPT female, with external indicator connection

Integral indicator D · · · · · · · · N · · · · · · · ·

Digital indicator(None)

Mounting bracket A · · · · · B · · · · · N · · · · ·

T1104E.EPS

3-inch (80 mm)/ JIS S25C3-inch (80 mm)/ JIS SUS304

JIS SECC 2-inch pipe mounting (flat type)JIS SUS304 2-inch pipe mounting (flat type)(None)

[Diaphragm] [Others]JIS SUS316L JIS SUS316LHastelloy C-276 Hastelloy C-276Tantalum TantalumTitanium Titanium

Cover flange bolts material A · · · · · · · · · · · · · · · · · · B · · · · · · · · · · · · · · · · · ·

JIS SCM435JIS SUS630

Fill fluid

-A *1 · · · · · · · · · · · · · · · -B · · · · · · · · · · · · · · · · -C *2 · · · · · · · · · · · · · · ·-D *3 · · · · · · · · · · · · · · · -E · · · · · · · · · · · · · · · ·

––– A · · · · · · · · · · · · · · · Always A

Optional codes / Optional specification

Capillary length (m) · · · · · · · · · · · · Specify capillary length from 1 to 5 m in . (Example for 2 m: 02)

[Process [Ambienttemperature] temperature]

For general use (silicone oil) 10 to 250 C 10 to 60 CFor general use (silicone oil) 30 to 180 C 15 to 60 CFor high temperature use (silicone oil) 10 to 300 C 10 to 60 CFor oil-prohibited use (fluorinated oil) 20 to 120 C 10 to 60 CFor low temperature use (ethylene glycol) 50 to 100 C 40 to 60 C

Example: EJ118W-DMSJ1DA-AA02-02NA/

*1: In case of wetted parts material code T (Tantalum), the process temperature limit is -10 to 200 C.*2: Wetted parts material code T (Tantalum) cannot be applied.*3: Even in case where fill fluid code D (fluorinated oil) is selected, if degrease cleansing treatment for the wetted parts is required, specify

optional code K1.

IM 01C20H01-01E10-4

10. GENERAL SPECIFICATIONS

Model EJ118N and EJ118YModel Suffix codes Description

EJ118NEJ118Y

· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·

Diaphragm sealed differential pressure transmitter (Extended diaphragm type)Diaphragm sealed differential pressure transmitter(Combination of Extended diaphragm and flush diaphragm type)

Output signal -D · · · · · · · · · · · · · · · · · · · · · · · · 4 to 20 mA DC with digital communication (BRAIN protocol)

Measurement span(capsule)

M · · · · · · · · · · · · · · · · · · · · · · · H · · · · · · · · · · · · · · · · · · · · · · ·

2.5 to 130 kPa 250 to 13000 mmH2O14 to 700 kPa 0.14 to 7 kgf/cm2

Wetted parts material *1

Process flange rating J1 · · · · · · · · · · · · · · · · · · · ·J2 · · · · · · · · · · · · · · · · · · · ·A1 · · · · · · · · · · · · · · · · · · ·A2 · · · · · · · · · · · · · · · · · · · ·

Process flange size/material

G · · · · · · · · · · · · · · · · ·H · · · · · · · · · · · · · · · · ·P · · · · · · · · · · · · · · · · ·Q · · · · · · · · · · · · · · · · ·

Installation -0 · · · · · · · · · · -2 · · · · · · · · · ·

Vertical impulse piping type, left side terminal boxVertical impulse piping type, right side terminal box

Electrical connection 0 · · · · · · · · · 1 · · · · · · · · · 2 · · · · · · · · ·5 · · · · · · · · · 6 · · · · · · · · ·7 · · · · · · · · ·

G 1/2 femaleG 3/4 female1/2 NPT female G 1/2 female, with external indicator connectionG 3/4 female, with external indicator connection1/2 NPT female, with external indicator connection

Integral indicator D · · · · · · N · · · · · ·

Digital indicator(None)

Mounting bracket A · · · · B · · · · N · · · ·

4-inch (100 mm)/ JIS S25C4-inch (100 mm)/ JIS SUS304High side 4-inch (100 mm) and Low side 3-inch (80 mm)/JIS S25CHigh side 4-inch (100 mm) and Low side 3-inch (80 mm)/JIS SUS304

JIS SECC 2-inch pipe mounting (flat type)JIS SUS304 2-inch pipe mounting (flat type)(None)

Cover flange bolts material A · · · · · · · · · · · · · · · · B · · · · · · · · · · · · · · · ·

JIS SCM435JIS SUS630

Fill fluid

-A · · · · · · · · · · · · · · -B · · · · · · · · · · · · · ·-C · · · · · · · · · · · · · ·-D *2 · · · · · · · · · · · -E · · · · · · · · · · · · · ·

– B · · · · · · · · · · · · · Always B

Capillary length (m) · · · · · · · · · · Specify capillary length from 1 to 5 m in . (Example for 2 m: 02)

Diaphragm extension length

2 · · · · · · · · · · · · · · · · · · · ·4 · · · · · · · · · · · · · · · · · · · ·6 · · · · · · · · · · · · · · · · · · · ·

X2= 50.8 mmX2=101.6 mmX2=152.4 mm

T1105E.EPS

[Process [Ambienttemperature] temperature]

For general use (silicone oil) 10 to 250C 10 to 60CFor general use (silicone oil) 30 to 180C 15 to 60CFor high temperature use (silicone oil) 10 to 300C 10 to 60CFor oil-prohibited use (fluorinated oil) 20 to 120C 10 to 60CFor low temperature use (ethylene glycol) 50 to 100C 40 to 60C

Optional codes / Optional specification

[Diaphragm] [Pipe] [Others]JIS SUS316L JIS SUS316 JIS SUS316

JIS 10KJIS 20KANSI class 150ANSI class 300

S · · · · · · · · · · · · · · · · · · · · · ·

Example: EJ118Y-DMSJ12PA-AC02-02NA/

*1: For wetted parts material of EJ118Y low pressure side (Flush diaphragm): Diaphragm; SUS3l6L, Others; SUS316L.*2: Even in case where fill fluid code D (fluorinated oil) is selected, if degrease cleansing treatment for the wetted parts is required, specify

optional code K1.

IM 01C20H01-01E10-5

10. GENERAL SPECIFICATIONS

10.3 Optional Specifications

T1106E.EPS

Explosionproof type

JF3

FF1

Intrinsically safe type

JS11

FM Intrinsically Safe Approval Class I Division 1 groups A, B, C and D Class II Division 1 groups E, F and G, Class III Division 1 Vmax : 31.5 VDC Imax : 93 mA Pmax : 1.1 W Ci=2 nF Li=1.04 mH Temperature Class : T4 Outdoor hazardous locations (NEMA 4) Amb. Temp. : –20 to 60 C

FS1

Attached flameproof packingadapter *7

Electrical connection : G1/2 femaleApplicable cable O.D. : 8 to 12 mm

1 pc. G11

2 pcs. G12

Electrical connection : G3/4 femaleApplicable cable O.D. : 10 to 16 mm

1 pc. G21

2 pcs. G22

Item

Color change

Coating change

Lightning protector

Oil-prohibited use

Calibration units

No serration *1

Teflon film *2

Operating temperature correction *3

Capillary without PVC sheaths

CPU failure alarm down-scale *4

Gold-plate *5

Description

Amplifier cover only

Epoxy resin-baked coating

Transmitter power supply voltage: 12.5 to 32 V DC

Allowable current: Max. 6000 A (140 µs), Repeating 1000 A (140 µs) 100 times

Degrease cleaning treatment

P calibration (psi unit)

bar calibration (bar unit)

M calibration (kgf/cm2 unit)

No serration work on the flange gasket surface (for ANSI flange only)

With FEP film and flourinated oil

Working range: 20 to 150 °C, 0 to 2 MPa0 to 20 kgf/cm2 (Not usable under vaccum)

Adjusting range: 80 to Maximum temperature of specified fill fluid

When ambient temperature exceeds 100 °C, or use of PVC is prohibited

Output status at CPU failure and hardware error for –5%, 3.2 mA DC or less with attached user selectable high-low jumper switch.

Gold-plated Diaphragm

Code

P

X1

A

K1

D1

D3

D4

Q

T

R

V

C1

A1

(See Table 10.2)

Painting

TIIS Flameproof Approval, Ex do IIC T4X *6

Certificate: TC13810 (Without integral indicator) TC13811 (With integral indicator) Amb. Temp. : –20 to 60°C, Max. Process Temp. : 120°C

FM Explosionproof Approval Applicable standard: FM3600, FM3615, FM3810, NEMA 250, ANSI/NFPA 70 Class I, II and III, Division 1, Groups B, C, D, E, F and G. Outdoor hazardous locations (NEMA 4), Temperature class : T6 Electrical connection : 1/2 NPT female, Amb. Temp. : –40 to 60°C

TIIS Intrinsically Safe Approval, i3aG4 *8 *9

(Using Model BARD-800 safety barrier : Model BARD-400 can also be used.) Amb. Temp. : –10 to 60°C, Max. Process Temp. : 80°C

*1: Not applicable for model EJ118W with Wetted part material code H, T, or U.*2: Teflon film can only be specified for model EJ118W.*3: Specify the process operating temperature for zero correction.

Example: Zero correction by process temperature 90 C.*4: The direction of hardware error alarm is user selectable by BT200.*5: Applicable for wetted parts material code S.*6: In case the ambient temperature exceeds 50°C, use heat-resistant cables with maximum allowable temperature of 75°C or above.*7: If cable wiring is to be used to a TIIS flameproof type transmitter, do not fail to add the YOKOGAWA-assured flameproof packing

adapter.*8: The communication distance is about 800 m when using polyethylene-insulated PVC sheathed control (CEV) cables.*9: See certificate list of TIIS intrinsically safe approval below.

Without lightning protector(option code /A)

With lightning protector(option code /A)

Connection to BARD-800 Connection to BARD-400

T1109E.EPS

T56212T54512

T56213

IM 01C20H01-01E10-6

10. GENERAL SPECIFICATIONS

10.4 Dimensions

T1107E.EPS

Flange Rating

JIS 10K

JIS 20K

JIS 40K

ANSI Class 150

ANSI Class 300

ANSI Class 600

øD

185(7.28)

200(7.87)

210(8.27)

190.5(7.5)

209.6(8.2)

209.6(8.25)

t

18(0.71)

22(0.87)

32(1.26)

23.9(0.94)

28.5(1.12)

38.2(1.50)

øC

150(5.91)

160(6.30)

170(6.69)

152.4(6)

168.1(6.62)

168.1(6.62)

n

8

8

8

4

8

8

øh

19(0.75)

23(0.91)

23(0.91)

19.1(0.75)

22.4(0.88)

22.4(0.88)

f*2

0

0

0

1.6(0.06)

1.6(0.06)

0

*2: In case where process flange material is JIS S25C, value of f is 0.

90*1

(3.54)

D

C

13

4 (5

.28)

225

(8.8

6)15(0.59)

t

31 (1.22)

n-h f

Unit: mm(approx. inch)

125(4.92)

193(7.60)

70(2.76)

112 (4.41) 48(1.89)

170 (6.69) 97(3.82)

224

(8.8

2)

124

(4.8

8)47

(1.8

5)

11

1 (4

.37)

68(2

.68)

53(

2.09

)

External indicatorconduit connection (Optional)

Groundterminal

2-inch pipe mounting bracket(Optional)

Conduitconnection

Zeroadjustment

2-inch pipe(O.D. 60.5mm)

Shrouding bolts(Only for TIIS Flameproof type)

*1: Indicates inside diameter of gasket contact surface.

Flange Rating

JIS 10K

JIS 20K

ANSI Class 150

ANSI Class 300

øD

210(8.72)

225(8.86)

228.6(9.00)

254(10.00)

t

18(0.71)

24(0.94)

23.9(0.94)

31.8(1.25)

øC

175(6.89)

185(7.28)

190.5(7.50)

200.2(7.88)

n

8

8

8

8

øh

19(0.75)

23(0.91)

19.1(0.75)

22.4(0.88)

f*1

0

0

1.6(0.06)

1.6(0.06)

Diaphragm extension length code2: X2 = 50.8 mm (2-inch)4: X2 = 101.6 mm (4-inch)6: X2 = 152.4 mm (6-inch)

120

(4.7

2)

t

96

D

C

154.5

X2

14.3

(0.

52)

n-h

HIGHfLOW

30(1.18)

120

(4.7

2)

t

96

D

C

154.5

X2

14.3

(0.

52)

n-h

HIGHf

30(1.18)

Model EJ118W Diaphragm seal part (Flush diaphragm type)

Model EJ118N Diaphragm seal part (Extended diaphragm type)

Model EJ118Y Diaphragm seal part (Combination of extended and flush diaphragm type)

Model EJ118W, EJ118N, EJ118Y Transmitter part and pressure detector section

Low pressure side

Flange Rating

JIS 10K

JIS 20K

ANSI Class 150

ANSI Class 300

øD

185(7.28)

200(7.87)

190.5(7.50)

209.6(8.25)

t

18(0.71)

22(0.87)

23.9(0.94)

28.5(1.12)

øC

150(5.91)

160(6.30)

152.4(6)

168.1(6.62)

n

8

8

4

8

øh

19(0.75)

23(0.91)

19.1(0.75)

22.4(0.88)

f*2

0

0

1.6(0.06)

1.6(0.06)

High pressure side

Flange Rating

JIS 10K

JIS 20K

ANSI Class 150

ANSI Class 300

øD

210(8.72)

225(8.86)

228.6(9.00)

254(10.00)

t

18(0.71)

24(0.94)

23.9(0.94)

31.8(1.25)

øC

175(6.89)

185(7.28)

190.5(7.50)

200.2(7.88)

n

8

8

8

8

øh

19(0.75)

23(0.91)

19.1(0.75)

22.4(0.88)

f*2

0

0

1.6(0.06)

1.6(0.06)

tf

Lowpressureside

Highpressureside

D

C

13

4 (5

.28)

225

(8.8

6)

15(0.59)

31 (1.22)

EX-A03E1

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS INTRINSICALLY SAFE EQUIPMENT

INSTALLATION AND OPERATING PRECAUTIONS FORTIIS INTRINSICALLY SAFE EQUIPMENT

Apparatus Certified Under Technical Criteria (IEC-compatible Standards)and from “RECOMMENDED PRACTICES for Explosion-Protected Electri-cal Installations in General Industries,” published in 1979

1. GeneralThe following describes precautions on electrical apparatusof intrinsically safe construction (hereinafter referred to asintrinsically safe apparatus).

Following the Labor Safety and Health Laws of Japan, anintrinsically safe apparatus must undergo type tests in orderto be certified by the Technical Institute of Industrial Safety,Inc. These tests are required to satisfy either the technicalcriteria for electrical machinery and equipment in compliancewith explosionproof standards involving inflammable gasesor vapors and for machinery and equipment havingexplosionproof performance (standards notification no. 556

from the Japanese Ministry of Labor) (hereinafter referred toas technical criteria), in conformity with IEC Standards, orthe “Recommended Practice for Explosion-ProtectedElectrical Installations in General Industries,” published in1979. Such a certified apparatus can be used in hazardouslocations where inflammable gases or vapors may be present.

Certified apparatus includes a certification label and anequipment nameplate with the specifications necessary forexplosion requirements as well as precautions on explosionprotection. Please confirm these precautionary items and usethem to meet specification requirements.

For electrical wiring and maintenance servicing, please referto “Internal Wiring Rules” in the Electrical InstallationTechnical Standards as well as “USER’S GUIDELINES forElectrical Installations for Explosive Gas Atmospheres inGeneral Industry,” published in 1994.

To meet intrinsically safe requirements, equipment that canbe termed an “intrinsically safe apparatus” must:

(1) be certified by the Technical Institute of IndustrialSafety, Inc. in accordance with the Labor Safety andHealth Laws of Japan and have the appropriate mark ofcertification labeled on its case, and

(2) be used in compliance with the specifications marked onits certification label, equipment nameplate and

precautionary information furnished.

Note: Intrinsically safe apparatus satisfy their performance underspecific conditions. They are not always absolutely safe underevery operational and environmental condition. In other

words, they are not safe products involved with factors suchas chemical reactions, geographical changes or the like otherthan affected by electric energy from the equipment itself.

2. Electrical Apparatus of IntrinsicSafety Type of Explosion-Pro-tected Construction

The intrinsic safety type of explosion-protected constructionis a method of protection applicable to a circuit or part of acircuit in which, under prescribed test conditions, no spark orthermal effect, whether produced normally or accidentally, iscapable of causing a prescribed explosive gas to ignite. Inother words, electrical apparatus of this construction isintended to suppress electrical energy thereby preventingignition of a given explosive gas atmosphere even though

spark or high thermal effect occurs in the electric circuitry.

Intrinsically safe electrical apparatus generally compriseintrinsically safe apparatus installed in a hazardous location

and a safety barrier (associated apparatus), installed in a non-hazardous location, aimed at preventing electrical energyfrom flowing into the electric circuitry of intrinsically safeapparatus.

However, battery-operated, portable intrinsically safeapparatus or the like may be used alone.

3. Terminology(1) Intrinsically safe apparatus: Electrical apparatus in which

all the circuits are intrinsically safe circuits.(2) Associated apparatus: Electrical apparatus in which there

are both intrinsically safe circuits and non-intrinsicallysafe circuits that can affect the safety of intrinsically safecircuits.

(3) Safety barrier: A specific type of associated apparatus,which consists mainly of safety barrier elements, andserves to limit the flow of excessive electrical energy,which is capable of causing ignition of a given explosivegas or vapour of a non-intrinsically safe circuit intoconcerned intrinsically safe circuits.

(4) Apparatus of category “ia”: Intrinsically safe electricalapparatus and associated apparatus which are incapableof causing ignition of a given explosive gas or vapourwith the appropriate safety factors such as:

EX-A03E2

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS INTRINSICALLY SAFE EQUIPMENT

— when up to two countable faults are applied and, inaddition,

— when non-countable faults produce an onerouscondition.

(5) Apparatus of category “ib”: Intrinsically safe electrical

apparatus and associated apparatus which are incapableof causing ignition of a given explosive gas or vapour,with the appropriate safety factors such as:— when up to one countable fault is applied and, in

addition,— when non-countable faults produce an onerous

condition.(6) Safety rating: A rating to be designated to intrinsically

safe apparatus as well as associated apparatus and is themaximum rating allowable for maintaining intrinsicsafety of concerned intrinsically safe circuits.

4. Caution on Combining Intrinsi-cally Safe Apparatus andSafety Barriers

(1) A combination of certified intrinsically safe apparatusand safety barriers needs to satisfy combinationrequirements. If intrinsically safe apparatus specifysafety barriers for combination, safety barriers other thanspecified cannot be used (see Note 1 for more details).

(2) Certified intrinsically safe systems specify specific safetybarriers in combination with intrinsically safe apparatus.So safety barriers other than specified cannot be used(see Note 2 for more details).

(3) Other than limitations of combining intrinsically safe

apparatus and safety barriers as given in (1) and (2)above, two or more pieces of apparatus certified underdifferent standards cannot be combined with each other(see Note 3 for more details). In addition, bear in mindthat classifications of explosion protection such as “IIA,”“IIB” and “IIC” and category “ia” and “ib” limit acombination of intrinsically safe apparatus and safetybarriers.For more details, see the “Type Certificate Guide forExplosion-Protected Constructionfor ElectricalMachinery and Equipment,” issued by the JapaneseMinistry of Labour, the Research Institute of Industrial

Safety.

Note 1: Testing ApparatusIntrinsically safe apparatus and safety barriers are assessedindividually to ensure that their safety requirements aresatisfied. Tested and certified intrinsically safe apparatus andsafety barriers incorporate individual certification numbers.A combination of intrinsically safe apparatus and safetybarriers involves the following two limitations:(1) A safety barrier which meets the combination require-

ments by referring to its safety rating and combinationparameters shall be selected.

(2) For pressure transmitters, pH transmitters, temperaturedetectors and the like, safety barriers that can becombined are already specified. Other safety barrierscannot be used.

Note 2: Testing Intrinsically Safe SystemAn assembly (as a system) in which intrinsically safeapparatus and safety barriers are combined is assessed toensure that its safety requirements are satisfied. A tested andcertified system incorporates a certification number(intrinsically safe apparatus and safety barriers have the samecertification number).

Note 3: Impossible Combinations of Apparatus Certified UnderDifferent StandardsIntrinsically safe apparatus certified under technical criteriaand safety barriers certified under the “RecommendedPractice for Explosion-Protected Electrical Installations inGeneral Industries” (1979) and vice versa cannot becombined even if their combination requirements aresatisfied.

5. Installation of Intrinsically SafeApparatus and Safety Barriers

(1) Classification of installation locationIntrinsically safe apparatus may be installed, depending uponapplicable gases, in a hazardous area in Zone 0, 1 or 2 (Note4 below), where the specified gases are present. However,note that apparatus certified under Technical Criteria, incategory “ib” shall be installed only in Zone 1 or 2. Safetybarriers (associated apparatus) that are combined with theseintrinsically safe apparatus shall be installed only in a non-

hazardous area. In cases where safety barriers are installed ina hazardous area, they shall be enclosed, for example, in aflameproof enclosure.

Note 4: Hazardous areas are classified in zones based upon thefrequency of the appearance and the duration of an explosivegas atmosphere as follows:Zone 0: An area in which an explosive gas atmosphere is

present continuously or is present for long periods.Zone 1: An area in which an explosive gas atmosphere is

likely to occur in normal operation.Zone 2: An area in which an explosive gas atmosphere is not

likely to occur in normal operation and if it doesoccur it will exist for a short period only.

(2) Ambient temperature limits for intrinsicallysafe apparatus

Intrinsically safe apparatus shall be installed in a location

where the ambient temperature ranges from –20° to +40°C(for those certified under Technical Criteria) or –10° to+40°C (for those certified under the “Recommended Practicefor Explosion-Protected Electrical Installations in GeneralIndustries” (1979). However, some field-mounted

EX-A03E3

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS INTRINSICALLY SAFE EQUIPMENT

intrinsically safe apparatus may be used at an ambienttemperature up to 60°C. So, specifications should be checkedbefore installing intrinsically safe apparatus.

If the intrinsically safe apparatus are exposed to directsunshine or radiant heat from plant facilities, appropriatethermal protection measures shall be taken.

6. Wiring for Intrinsically SafeCircuits

In intrinsically safe construction, safety shall be maintainedas an intrinsically safe system involving intrinsically safeapparatus and safety barriers connected thereto, and electricalwiring (through intrinsically safe circuits) interconnectedbetween them. In other words, even when safety

requirements are maintained individually by intrinsically safeapparatus and safety barriers, they shall not be affected byelectrical or magnetic energy caused by electrical wiring.

To make electrical wiring for intrinsically safe circuits, youmust:

(a) refer to the equipment configuration diagram and makeelectrical wiring properly;

(b) prevent intrinsically safe wiring from being contactedwith non-intrinsically safe wiring, and separate theintrinsically safe circuit from other electrical circuits;

(c) prevent intrinsically safe wiring from beingelectrostatically and magnetically affected by non-intrinsically safe wiring;

(d) reduce wiring inductance and capacitance producedbetween the intrinsically safe apparatus and safetybarrier where possible, and use a shorter cable betweenthe intrinsically safe apparatus and safety barrier thanspecified if the maximum permissible inductance of the

cable is specified as operating conditions;(e) conform to conditions of installation such as wiring

method, earthing or the like, if any; and(f) protect the outer sheath of cables from damage with

appropriate measures.

7. Maintenance and Inspection ofIntrinsically Safe Apparatusand Safety Barriers

Maintenance and inspection of intrinsically safe apparatusand safety barriers shall be limited to within the instructionsdescribed in applicable instruction manuals. If other than this

is required, contact the manufacturers. For more information,refer to the “USER’S GUIDELINES for Electrical

Installations for Explosive Gas Atmospheres in GeneralIndustry” issued in 1994 by the Japanese Ministry of Labour,the Research Institute of Industrial Safety.

(1) Requirements for maintenance personnelMaintenance and inspection of intrinsically safe apparatusand safety barriers shall be conducted by maintenancepersonnel skilled in intrinsically safe construction and

installation of electrical devices as well as capable ofapplying associated rules.

(2) Maintenance and Inspection(a) Visual inspection

Visually inspect the external connections of intrinsicallysafe apparatus and safety barriers, and cables for damageor corrosion as well as other mechanical and structuraldefects.

(b) AdjustmentsZero, span and sensitivity adjustments shall be madewith applicable adjusting potentiometers and mechanicaladjustment screws.These maintenance adjustments shall be made in a non-hazardous location.

CAUTION

If intrinsically safe apparatus and safety barriersrequire maintenance service and checking, agas detector shall be used to ensure that thereis no explosive gas in the location (mainte-nance servicing shall be conducted in a non-hazardous location).

(3) RepairIntrinsically safe apparatus and safety barriers shall berepaired by manufacturers.

(4) Prohibition of modifications and specifica-tion changes

Do not attempt to make modifications or change specifica-tions which may affect safety.

EX-B03E1

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT

INSTALLATION AND OPERATING PRECAUTIONS FORTIIS FLAMEPROOF EQUIPMENT

Apparatus Certified Under Technical Criteria(IEC-compatible Standards)

1. GeneralThe following describes precautions on electrical apparatusof flameproof construction (hereinafter referred to asflameproof apparatus) in explosion-protected apparatus.

Following the Labour Safety and Health Laws of Japan,flameproof apparatus is subjected to type tests to meet eitherthe technical criteria for explosionproof electrical machineryand equipment (standards notification no. 556 from the

Japanese Ministry of Labour) (hereinafter referred to astechnical criteria), in conformity with the IEC Standards, orthe “Recommended Practice for Explosion-ProtectedElectrical Installations in General Industries,” published in1979. These certified apparatus can be used in hazardouslocations where explosive or inflammable gases or vapoursmay be present.

Certified apparatus includes a certification label and anequipment nameplate with the specifications necessary forexplosion requirements as well as precautions on explosionprotection. Please confirm these precautionary items and usethem to meet specification requirements.

For electrical wiring and maintenance servicing, please referto “Internal Wiring Rules” in the Electrical InstallationTechnical Standards as well as “USER’S GUIDELINES forElectrical Installations for Explosive Gas Atmospheres inGeneral Industry,” published in 1994.

To meet flameproof requirements, equipment that can betermed “flameproof” must:

(1) Be certified by a Japanese public authority in accordancewith the Labour Safety and Health Laws of Japan andhave a certification label in an appropriate location on itscase, and

(2) Be used in compliance with the specifications marked onits certification label, equipment nameplate andprecautionary information furnished.

2. Electrical Apparatus of Flame-proof Type of Explosion-Pro-tected Construction

Electrical apparatus which is of flameproof construction issubjected to a type test and certified by the Japanese Ministryof Labour aiming at preventing explosion caused by electricalapparatus in a factory or any location where inflammable

gases or vapours may be present. The flameproof

construction is of completely enclosed type and its enclosureshall endure explosive pressures in cases where explosivegases or vapours entering the enclosure cause explosion. Inaddition, the enclosure construction shall be such that flamecaused by explosion does not ignite gases or vapours outsidethe enclosure.

In this manual, the word "flameproof" is applied to theflameproof equipment combined with the types of protection"e", "o", "i", and "d" as well as flameproof equipment.

3. Terminology

(1) EnclosureAn outer shell of an electrical apparatus, which encloses liveparts and thus is needed to configure explosion-protected

construction.

(2) ShroudA component part which is so designed that the fastening ofjoint surfaces cannot be loosened unless a special tool isused.

(3) Enclosure internal volumeThis is indicated by:— the total internal volume of theflameproof enclosure minus the volume of the internalcomponents essential to equipment functions.

(4) Path length of joint surfaceOn a joint surface, the length of the shortest path throughwhich flame flows from the inside to outside of theflameproof enclosure. This definition cannot be applied tothreaded joints.

(5) Gaps between joint surfacesThe physical distance between two mating surfaces, ordifferences in diameters if the mating surfaces are cylindrical.

Note: The permissible sizes of gaps between joint surfaces, the pathlength of a joint surface and the number of joint threads aredetermined by such factors as the enclosure’s internalvolume, joint and mating surface construction, and theexplosion classification of the specified gases and vapours.

EX-B03E2

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT

4. Installation of Flameproof Ap-paratus

(1) Installation AreaFlameproof apparatus may be installed, in accordance withapplicable gases, in a hazardous area in Zone 1 or 2, wherethe specified gases are present. Those apparatus shall not beinstalled in a hazardous area in Zone 0.

Note: Hazardous areas are classified in zones based upon thefrequency of the appearance and the duration of an explosivegas atmosphere as follows:Zone 0: An area in which an explosive gas atmosphere is

present continuously or is present for long periods.Zone 1: An area in which an explosive gas atmosphere is

likely to occur in normal operation.Zone 2: An area in which an explosive gas atmosphere is not

likely to occur in normal operation and if it doesoccur it will exist for a short period only.

(2) Environmental ConditionsThe standard environmental condition for the installation offlameproof apparatus is limited to an ambient temperaturerange from –20°C to +40°C (for products certified under

Technical Criteria). However, some field-mountedinstruments may be certified at an ambient temperature up to+60°C as indicated on the instrument nameplates. If theflameproof apparatus are exposed to direct sunshine orradiant heat from plant facilities, appropriate thermalprotection measures shall be taken.

5. External Wiring for FlameproofApparatus

Flameproof apparatus require cable wiring or flameproofmetal conduits for their electrical connections. For cablewiring, cable glands (cable entry devices for flameproof type)to wiring connections shall be attached. For metal conduits,attach sealing fittings as close to wiring connections aspossible and completely seal the apparatus. All non-livemetal parts such as the enclosure shall be securely grounded.For details, see the “USER’S GUIDELINES for ElectricalInstallations for Explosive Gas Atmospheres in GeneralIndustry,” published in 1994.

(1) Cable Wiring• For cable wiring, cable glands (cable entry devices for

flameproof type) specified or supplied with the apparatusshall be directly attached to the wiring connections tocomplete sealing of the apparatus.

• Screws that connect cable glands to the apparatus are

those for G-type parallel pipe threads (TIIS B 0202) withno sealing property. To protect the apparatus fromcorrosive gases or moisture, apply nonhardening sealantsuch as liquid gaskets to those threads for waterproofing.

• Specific cables shall be used as recommended by the“USER’S GUIDELINES for Electrical Installations forExplosive Gas Atmospheres in General Industry,”published in 1994.

• In necessary, appropriate protective pipes (conduit or

flexible pipes), ducts or trays shall be used forpreventing the cable run (outside the cable glands) fromdamage.

• To prevent explosive atmosphere from being propagatedform Zone 1 or 2 hazardous location to any differentlocation or non-hazardous location through the protectivepipe or duct, apply sealing of the protective pipes in thevicinity of individual boundaries, or fill the ducts withsand appropriately.

• When branch connections of cables, or cable connectionswith insulated cables inside the conduit pipes are made,a flameproof or increased-safety connection box shall be

used. In this case, flameproof or increased-safety cableglands meeting the type of connection box must be usedfor cable connections to the box.

(2) Flameproof Metal Conduit Wiring• For the flameproof metal conduit wiring or insulated

wires shall be used as recommended by the USER’SGUIDELINES for Electrical Installations for ExplosiveGas Atmospheres in General Industry, published in1994.

• For conduit pipes, heavy-gauge steel conduitsconforming to TIIS C 8305 Standard shall be used.

• Flameproof sealing fittings shall be used in the vicinityof the wiring connections, and those fittings shall befilled with sealing compounds to complete sealing of theapparatus. In addition, to prevent explosive gases,moisture, or flame caused by explosion form being

propagated through the conduit, always provide sealingfittings to complete sealing of the conduit in thefollowing locations:

(a) In the boundaries between the hazardous and non-hazardous locations.

(b) In the boundaries where there is a differentclassification of hazardous location.

• For the connections of the apparatus with a conduit pipeor its associated accessories, G-type parallel pipe threads(TIIS B 0202) shall be used to provide a minimum offive-thread engagement to complete tightness. Inaddition, since these parallel threads do not have sealing

property, nonhardening sealant such as liquid gasketsshall thus be applied to those threads for ensuringwaterproofness.

• If metal conduits need flexibility, use flameproof flexiblefittings.

EX-B03E3

INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT

6. Maintenance of FlameproofApparatus

To maintain the flameproof apparatus, do the following. (Fordetails, see Chapter 10 “MAINTENANCE OF EXPLOSION-PROTECTED ELECTRICAL INSTALLATION” in theUSER’S GUIDELINES for Electrical Installations forExplosive Gas Atmospheres in General Industry.)

(1) Maintenance servicing with the power on.Flameproof apparatus shall not be maintenance-serviced withits power turned on. However, in cases where maintenanceservicing is to be conducted with the power turned on, withthe equipment cover removed, always use a gas detector tocheck that there is no explosive gas in that location. If itcannot be checked whether an explosive gas is present or not,maintenance servicing shall be limited to the following twoitems:

(a) Visual inspectionVisually inspect the flameproof apparatus, metal

conduits, and cables for damage or corrosion, and othermechanical and structural defects.

(b) Zero and span adjustmentsThese adjustments should be made only to the extentthat they can be conducted from the outside withoutopening the equipment cover. In doing this, great caremust be taken not to cause mechanical sparks with tools.

(2) RepairIf the flameproof apparatus requires repair, turn off the powerand transport it to a safety (non-hazardous) location. Observethe following points before attempting to repair theapparatus.

(a) Make only such electrical and mechanical repairs as willrestore the apparatus to its original condition. For theflameproof apparatus, the gaps and path lengths of jointsand mating surfaces, and mechanical strength ofenclosures are critical factors in explosion protection.Exercise great care not to damage the joints or shock theenclosure.

(b) If any damage occurs in threads, joints or matingsurfaces, inspection windows, connections between thetransmitter and terminal box, shrouds or clamps, orexternal wiring connections which are essential inflameproofness, contact Yokogawa Electric Corporation.

CAUTION

Do not attempt to re-process threaded connections orrefinish joints or mating surfaces.

(c) Unless otherwise specified, the electrical circuitry andinternal mechanisms may be repaired by componentreplacement, as this will not directly affect the

requirements for flameproof apparatus (however, bear inmind that the apparatus must always be restored to itsoriginal condition). If you attempt to repair theflameproof apparatus, company-specified componentsshall be used.

(d) Before starting to service the apparatus, be sure to checkall parts necessary for retaining the requirements forflameproof apparatus. For this, check that all screws,bolts, nuts, and threaded connections have properly beentightened.

(3) Prohibition of specification changes andmodifications

Do not attempt to change specifications or makemodifications involving addition of or changes in externalwiring connections.

7. Selection of Cable Entry De-vices for Flameproof Type

IMPORTANT

The cable glands (cable entry devices for flameprooftype) conforming to IEC Standards are certified incombination with the flameproof apparatus. So,Yokogawa-specified cable entry devices for flameprooftype shall be used to meet this demand.

References:(1) Type Certificate Guide for Explosion-Protected Con-

struction Electrical Machinery and Equipment (relatingto Technical Standards Conforming to InternationalStandards), issued by the Technical Institution ofIndustrial Safety, Japan

(2) USER’S GUIDELINES for Electrical Installations forExplosive Gas Atmospheres in General Industry (1994),issued by the Japanese Ministry of Labour, the ResearchInstitute of Industrial Safet

All Rights Reserved, Copyright © 1992, Yokogawa Electric Corporation.

Yokogawa Electric Corporation

[Style: S2*]

CMPL 01C20A01-01E 5th Edition: June 2006(KP)

DPharp EJ SeriesTransmitter Section

Left Side Terminal Box Right Side Terminal Box

Left Side Terminal Box Right Side Terminal Box

Vertical Piping Connection Type

Horizontal Piping Connection Type**

*: Style code for model EJ115 and EJ135 is S3.**: Not applicable for model EJ118W, EJ118N, EJ118Y, EJ318W, EJ318N, EJ438W, and EJ438N.

CustomerMaintenanceParts List

2

CMPL 01C20A01-01EJune 2006Subject to change without notice. Printed in Japan.

37

22 35

29

21

30

3433

36

38

26

2524

27

28

3635

31

32

23

1

3

2

4

5 7

6

7

2

8

13

12

911

10

3

CMPL 01C20A01-01EJune 2006Subject to change without notice. Printed in Japan.

CoverO-RingCoverO-RingTag No. Plate

Nameplate (Data Plate)Self-tapping Screw, M3×5LCD Board AssemblyB.H. Screw, M4×6Cover Assembly

Label (to be specified by user)Label (used for TIIS flameproof type and TIIS intrinsically safe type)Label (used only for TIIS intrinsically safe type)

12345

6789

10

111213

F9301DQG9303LKF9301DYG9303AMF9300NE

—F9300AGF9302DAY9406JBF9301MA

F9300PB——

11111

14121

211

Item Part No. DescriptionQty

For with Field Indicator*

Note *: In case of horizontal piping connection type, combination with field indicator is not available.

Case AssemblyTerminal Board Assembly

For General Use Type and Flameproof Type. (without lighting protector)For General Use Type and Flameproof Type. (with lighting protector)For Intrinsically Safe Type (without lightning protector)

For Intrinsically Safe Type (with lightning protector)HookJumperScrew

O-Ring

Hex Soc. H. Cap Screw with Spring WasherPan H. Screw, M4×18 with Spring Washer

PlugFor Electrical Connection Code: 5 (G1/2)For Electrical Connection Code: 6 (G3/4)

For Electrical Connection Code: 7 (1/2NPT)Hex. Soc. H. Cap Screw with Spring WasherCable AssemblyCPU Board Assembly

For General Use Type and Flameproof Type.

(without output selection switch for CPU fault)For General Use Type and Flameproof Type.

(with output selection switch for CPU fault, Option Code: /C1)For Intrinsically Safe Type

(without output selection switch for CPU fault)

Pan H. Screw, M4×6Lock WasherClampHex Soc. H. Cap ScrewCable Gland Assembly

Card

2122

23242526

272829

303132

3334353637

38

See Table 1Below

F9301FSF9301FYF9301FC

F9301FQF9301FFF9203CRF9270SJF9301FG

F9300AMY9418JH

BelowG9330DPG9330DQ

G9612ECF9300AHF9302KA

BelowF9302BA

F9302BC

F9302BS

F9340ALY9401WLG9339AAY9408ZUSee Table 2

G9339AB

11

3141

41

211

1122—

1

11

3141

411

211

1122—

1

Item Part No. Description

Qty

Typ

e

For Attached Flameproof Packing adapter (Option Code: /G)

For TIIS Flameproof Type

With

out C

onne

ctio

nfo

r R

emot

e In

dica

tor

With

Con

nect

ion

for

Rem

ote

Indi

cato

r

4

CMPL 01C20A01-01EJune 2006Subject to change without notice. Printed in Japan.

Table 1. Case Assembly Part Number (item 21)

*1: General Use Type, TIIS Flameproof Type and TIIS Intrinsically Safe Type.*2: Not applicable for model EJ118W, EJ118N, EJ118Y, EJ318W, EJ318N, EJ438W, and EJ438N.

*1

*2

*2

Case Assembly Part Number (item 21)G1/2 (PF1/2) G3/4 (PF3/4) 1/2NPT

Electrical ConnectionDescription

Description Qty Part No.

With

out C

onne

ctio

nfo

r R

emot

e In

dica

tor

With

Con

nect

ion

for

Rem

ote

Indi

cato

r

Vertical PipingConnection Type

Left SideTerminal Box

Connection forRemote Indicator

Suffix Code(Option)

Right SideTerminal BoxLeft SideTerminal BoxRight SideTerminal BoxLeft SideTerminal BoxRight SideTerminal BoxLeft SideTerminal BoxRight SideTerminal Box

Horizontal PipingConnection Type

Vertical PipingConnection Type

Horizontal PipingConnection Type

Electrical Connection: for G1/2Cable Size: ø8 to ø12

Without G11 1With G12 2Without G21 1With G22 2

Electrical Connection: for G3/4Cable Size: ø10 to ø16

F9301BA

F9301BL

F9301BF

F9301BR

F9301RA

F9301RL

F9301RF

F9301RR

F9301BB

F9301BM

F9301BG

F9301BS

F9301RB

F9301RM

F9301RG

F9301RS

F9301BC

F9301BN

F9301BH

F9301BT

F9301RC

F9301RN

F9301RH

F9301RT

G9601AM

G9601AN

Table 2. Cable Gland Assembly Part Number (option, item 37)

CustomerMaintenanceParts List

All Rights Reserved, Copyright © 1992, Yokogawa Electric Corporation.

Yokogawa Electric Corporation

CMPL 01C20H01-01E4th Edition: June 2006

Model EJ118W, EJ118N and EJ118YDiaphragm SealedDifferential Pressure Transmitter

4

5

4

54

5

8

6

7

22

3

3

2

3

9

1

Model EJ118W

Model EJ118N Model EJ118Y

[Style: S2]

2

CMPL 01C20H01-01EJune 2006Subject to change without notice. Printed in Japan.

O-RingFlange [see table 1]Screw [see table 1]Screw

For JIS10K

For JIS20K and ANSI Class 150For ANSI Class 300

Pan H. Screw, M612Bracket Assembly

SECC Carbon Steel

SUS304 Stainless SteelU-Bolt/Nut Assembly, SUS 304 Stainless SteelBracket

SECC Carbon SteelSUS 304 Stainless Steel

BoltS25C Carbon SteelSUS XM7 Stainless Steel

1234

56

78

9

F9300AJ——

BelowF9149WR

F9149WSF9149WTY9612HU

BelowF9270AW

F9300TAD0117XL-A

BelowF9270AXF9300TE

BelowF9270AYF9273CZ

124

1

11

4

1

8

81

11

4

Item Part No. Description

Qty

Mod

el

EJ1

18W

EJ1

18N

1124

41

11

4

EJ1

18Y

T01.EPS

Table 1. Flange and Screw Part Number (Item 2 and 3).

Pan H.Screw(item 3)

S25C Carbon Steel,80mm(3inch)

SUS304 Stainless Steel, 80mm(3inch)

Flange Rating

T02.EPS

Y9525ZU

Y9530ZU

Y9540ZU

Y9530ZU

Y9347VX

Y9540ZU

JIS 10K

JIS 20K

JIS 40K

ANSI Class 150

ANSI Class 300

ANSI Class 600

F9351KA

F9351KB

F9351KC

F9351KE

F9351KF

F9351KG

F9351GA

F9351GB

F9351GC

F9351GE

F9351GF

F9149LR

IM 01C20H01-01E

REVISION RECORDTitle: Model EJ118W, EJ118N, and EJ118Y Diaphragm Sealed Differential Pres-

sure TransmitterManual No.: IM 01C20H01-01E

Edition Date Page Revised Item

7th Oct. 2000 -

10-1

CMPL

Revised a book in a new format. (The location of contents and the associated page numbers may not coincide with the one in old editions.) • Add Chapter 10, General SpecificationsCMPL 1C20H1-01E 1st 2nd • Add Revision Record

REVISION RECORD.EPS

8th May 2002 -2-1

2-3 2-5

10-1CMPL

New coding system applied. • Delete CE marking from Figure 2.2. • Add "Confirming the certification mark." • Delete EMC Conformity number and the note for wire selection. • Delete CE marking and CE EMC Conformity number. CMPL 1C20A1-01E 2nd 01C20A01-01E 3rd • Add Part No. to item 5, Tag No. Plate (F9300NE).CMPL 1C20H1-01E 2nd 01C20H01-01E 3rd

9th June 2006 1-12-42-52-57-9

7-1610-5

-CMPL

1 • Revise layout of chapter 1 2.9.3 • Delete SAA Intrinsically safe type 2.10.2 • Add Caution of selecting cables 2.11 • Correct C-tick number 7.3.2 (5) • Add an example of low cut mode setting 7.3.2 (17) • Correct the definition of 'h' 10.3 • Delete option code /EF1 • JIS Certification TIIS Certification CMPL 01C20A01-01E 3rd 5th • Item22 F9301FT F9301FY • Item27, 28 Item27 Y9516ZU F9300AM Y9500SU Delete • Item29, 30 Item28 Y9418JB Y9418JH Y9400SP Delete • Item35 Item33 Y9406JU F9340AL • Item39, 41, 42 Delete parts • Item43 Item38 F9301FS G9339ABCMPL 01C20H01-01E 3rd 4th • Item9 F9270AX F9270AY F9300TE F9273CZ • Revise Table 1