user instructions for toptronic rs-10ersatzteilkatalog.hoval.com/dvsfiles/0308020232drw... · if...

27
User Instructions For TopTronic ® RS-10 430293ENG-Dec01 Hoval Ltd Northgate Newark Nottinghamshire NG24 1JN Phone 01636 672711 Fax 01636 673532

Upload: duongdat

Post on 03-Sep-2018

247 views

Category:

Documents


7 download

TRANSCRIPT

User Instructions For TopTronic® RS-10 430293ENG-Dec01

Hoval Ltd Northgate Newark Nottinghamshire NG24 1JN Phone 01636 672711 Fax 01636 673532

2 Index 430293ENG-Dec01 Introduction Introduction ....................................................................................................................................... 3 Controls............................................................................................................................................. 3 Display .............................................................................................................................................. 3 User instructions Key function table.............................................................................................................................. 4 Switching on the room station ........................................................................................................... 4 Additional information........................................................................................................................ 5 Automatic program selection ............................................................................................................. 6 Room temperature ............................................................................................................................ 7 Heating program ............................................................................................................................... 8 Calorifier charging ............................................................................................................................. 10 Advanced user instructions Language .......................................................................................................................................... 11 Clock setting...................................................................................................................................... 11 Time clock level................................................................................................................................. 11 Time clock programming ................................................................................................................... 12 Block programming ........................................................................................................................... 14 Table program 1 settings................................................................................................................... 17 Table program 2 settings................................................................................................................... 18 Table program 3 settings................................................................................................................... 19 Room level ........................................................................................................................................ 20 Parameter tables Room level parameters table............................................................................................................. 23 Advanced parameter table ............................................................................................................... 24 Installation / technical Installation......................................................................................................................................... 27 Technical data................................................................................................................................... 27

430293ENG-Dec01 Introduction 3 The TopTronic RS-10 room station serves as a decentralized information center with remote interrogation and remote operating functions and can be used with all equipment versions of the TopTronic system. With the most up to date micro electronics exclusive functions can be activated which guarantee the highest level of comfort with the minimum energy usage. This is achieved with adaption and optimization functions which match heating energy to the exact building requirements. As well as these room temperature related functions a variety of equipment specific information is available which can be read within the living room and when necessary adapted to individual circumstances. This encompasses dates, on/off switching of the heating cycle with differently regulated room temperatures, actual values and diagnostic fault messages of the boiler. Operation of the unit is easy to understand and is limited to a minimum of operating elements which are separated for user and advanced user levels. The instructions are separated into two parts. Part 1 (user instructions) delivers all immediately important operating stages which are necessary for use and are selected with directly accessible operating keys. Part 2 (advanced instructions) these should only be used by the advanced user or service engineer and relate to specific settings / heating parameters and are accessible by the covered operating keys. Controls 1 4 2 5 3 6 7 10 12 11 13 8 9 1 � LCD Display 2 � Key (increase value) 3 � Key (decrease value) 4 � Key for heating program 5 � Key for reduced (night time) program 6 � Information 7 � Program key (time/date) 8 � Program key (automatic programs) 9 � Program key (house level) 10 � Program key (service level) 11 � Forward key 12 � Backward key 13 � Cover

Symbol Display Heating Night setback Clock signal Room temperature

4 User Instructions 430293ENG-Dec01

Key Function table (User Level)

Function Enter with keys Adjust with keys / range Page No.

Room temperature correction

or

or

5�30oC 7

Heating (day) room temperature

or with

or

5�30oC 7

Reduced (night) room temperature

or with

or

5�30oC 7

Information 5

Party function

press and hold or

0.5�10h 8

Continuous heating

press and hold

or

5�30oC 8

Absent function

press and hold or

0.5�10h 9

Continuous reduced

press and hold or

5�30oC 9

Automatic

or 8-9

Calorifier charging

and

simultaneously

ON or

OFF 10

Automatic programs 1-3 and

simultaneously

or

1, 2, 3 6

Switching on the Room station When the room station is first switched on the following display will show for 5 seconds: Room Station Software version Central unit s Software version The default display will then appear. The symbol indicates that the room station is in heating operation and the symbol indicates the room station is in reduced (night time) operation.

Information: Monday 10th March 1997 Time 20.15 Room temperature 20.5oC Clock synchronisation

Attention:

• During summer switch off the following symbols are not shown and .

• Blinking symbols or indicate that the unit is not operating under a normal program eg. party.

• The symbol indicates that a radio clock synchronisation has been connected.

i

430293ENG-Dec01 User Instructions 5

Additional Information The following additional information on the central TopTronic can be obtained by pressing the button (only if the relevant sensors are fitted):

Default display.

External sensor 1 temperature.

External sensor 2 temperature.

Boiler temperature.

Mixed circuit 1 temperature.

Mixed circuit 2 temperature.

Domestic hot water temperature.

If the calorifier is fitted with a thermostat instead of a sensor the following will be displayed:

Calorifier on/off.

Boiler flue gas temperature.

Boiler return temperature.

External heat source temperature.

Default display.

Additional information with TopTronic 1B or 133B connected

Switch off operation: switch off at outside sensor (short circuit) or no signal for

outside temp. When the unit is switched off the information below shows instead of the default display.

System off � system switched off completely with no frost protection.

Further automatic information also appears:

Indication of forced standby operation by telephone modem. Indication of common fault (when outside sensor 2 is in short circuit in central unit)

Fault Indications The RS-10 room station has a comprehensive fault indication system which has priority over all other indications and remain active until the fault is rectified.

i

i

i

i

i

i

i

i

i

i

i

6 User Instructions 430293ENG-Dec01 If the room station is connected to a TopTronic 1B or 133B faults concerning the firing unit must be rectified in accordance with operating manual instructions. If any of the following fault displays are shown (Fault � System Off, Fault � warm water temperature, Fault � boiler temperature, Fault � room temperature ) you must notify the heating engineer. Operating Indication For the heating programs to operate automatically according to the information stored within the room station the operating switch on the central unit must be in automatic 1, 2 or 3. In all other positions the central unit has priority and the room station only serves as a room sensor, remote temperature correction and information unit. The deviation from automatic setting is indicated on the room station as shown below: <<selection switch setting standby>> <<selection switch setting sun>> <<selection switch setting moon>> <<selection switch setting hand>> <<selection switch setting warm water>> Notes 1. The information remains active until the

central unit switch is set to one of the three automatic settings 1, 2 or 3.

2. During an indication the information key can be used to display actual values.

Automatic Program Selection In automatic there are three different time programs to switch between for each heating circuit. As a general rule these can be used without the need for adjustment but if individual programs are required customised cycles can be entered (see the advanced user section ). 1 – Program 1

Circuit Day Time

Boiler Circuit

Mo � Fr Sa, Su

6.00 - 8.00 16.00 - 22.00 7.00 - 23.00

Mixed circuit 1

Mo � Fr Sa, Su

6.00 - 8.00 16.00 - 22.00 7.00 - 23.00

Mixed Circuit 2

Mo � Fr Sa, Su

6.00 - 8.00 16.00 - 22.00 7.00 - 23.00

2 – Program 2

Circuit Day Time Boiler Circuit Mo � Su 6.00 - 22.00 Mixed circuit 1 Mo � Su 6.00 - 22.00 Mixed Circuit 2 Mo � Su 6.00 - 22.00

3 – Program 3

Circuit Day Time

Boiler Circuit Mo � Su 6.00 - 23.00 Mixed circuit 1 Mo � Su 6.00 - 23.00 Mixed Circuit 2 Mo � Su 6.00 - 23.00

Changing between Automatic Programs By using the and keys and following procedure it is possible to change between the automatic programs for the heating circuit which the room station is controlling. This can be the boiler circuit, mixed circuit 1 or mixed circuit 2.

Press Simultaneously The following will be displayed for the default setting of program 2:

Room Station for Boiler circuit

or Room station for Mixed circuit 1

or

Room station for Mixed circuit 2

Use the and keys to change between programs 1, 2 or 3. After 4 secs the default display will be restored.

i

430293ENG-Dec01 User Instructions 7

Room Temperature By using the program keys and the increase / decrease value keys the room temperature can be changed for heating and reduced (night time). A – Heating (day room temperature) If in heating operation as indicated by on the display follow the procedure below: press or

Display for heating operation.

Works setting: 20oC Adjustment range: 5oC�30oC press to increase to decrease

Default screen automatically returns after 4 seconds.

If in reduced operation as indicated by on the display follow the procedure below: press or

Display for reduced operation.

press

Display for heating temperature.

Works setting: 20oC Adjustment range: 5oC�30oC press to increase to decrease

Default screen automatically returns after 4 seconds.

B – Reduced (night room temperature) If in reduced operation as indicated by on the display follow the procedure below: press or

Display for reduced operation.

Works setting: 16oC Adjustment range: 5oC�30 oC press to increase to decrease

Default screen automatically returns after 4 seconds.

If in heating operation as indicated by on the display follow the procedure below: press or

Display for heating operation.

press

Display for reduced operation.

Works setting: 16oC Adjustment range: 5oC�30oC press to increase to decrease

Default screen automatically returns after 4 seconds.

8 User Instructions 430293ENG-Dec01 C – Holiday (room minimum temperature) When in holiday mode follow the procedure below to set the minimum room temperature:

Holiday program display.

press or Works setting: 10oC Adjustment range: 5oC�20oC press to increase to decrease Heating Program With the two program keys and the following changes can be made to the programs:

A - Party B - Heating C - Absent D - Reduced

A – Party This program is used to switch on or extend the heating automatic program to a certain time for a one off event press and hold

Display for party program.

For example: At 20.15 the heating needs to be extended by 3 hours (to 23.15). press to increase to decrease Adjustment range 0.5�10h

It should be noted that the adjustment is from the time of alteration and not an extension of the automatic program 1, 2 or 3. The default display will return after 4 seconds. To cancel party program The party program can be cancelled and put back into automatic by the following procedure: press and hold

The default display returns after 4 seconds. B - Heating This program is used to switch on the heating continuously. press and hold

The default display returns after 4 seconds.

430293ENG-Dec01 User Instructions 9 To cancel heating program The continuous heating program can be cancelled using the following procedure: press and hold

The default display will return after 4 seconds. C – Absent This program is used to switch to reduced or extend the reduced automatic program to a certain time for a one off event press and hold

Display for absent program.

For example: At 13.00 the heating is switched to reduced for the next 6 hours (to 19.00). press to increase to decrease Adjustment range 0.5�10h It should be noted that the adjustment is from the time of alteration and not an extension of the automatic program 1, 2 or 3. The default display will return after 4 seconds. To cancel absent program The absent program can be cancelled and put back into automatic by the following procedure: press and hold

The default display will return after 4 seconds. D - Reduced This program is used to switch to reduced continuously. press and hold

The default display returns after 4 seconds. To cancel reduced program The continuous reduced program can be cancelled using the following procedure: press and hold

The default display will return after 4 seconds.

10 User Instructions 430293ENG-Dec01 Calorifier Charging With this program it is possible to switch the calorifier on for a fixed three hour period. press simultaneously

The default display will return after 4 seconds. To Cancel program: press simultaneously

The default display will return after 4 seconds. Attention: The calorifier will be heated up to its

maximum permissible temperature.

430293ENG-Dec01 Advanced User Instructions 11

Language The room station is programmed in three languages English, German and French. To change the language press or key for 5 seconds. Once the language appears the keys can be used to change languages. or Works setting: ENGLISH The previous display will return in a few seconds. 1 - Clock setting The following functions can be set:

- Time (minutes, hours) - Day - Month - Year

The clock can be set to automatically change over from summer to winter time by a parameter in the service level of the central unit. Changing clock settings The clock can be changed by using key and then the and keys to increase or decrease the values. - Time

Change with: to increase to decrease Setting Range:

00:00 � 23:59 - Date

Change with: to increase to decrease Setting Range:

1 � 31

- Month

Change with: to increase to decrease Setting Range:

1 � 12 - Year

Change with: to increase to decrease Setting Range:

1995 � 2030 - Return to default display If the key is not pressed the default display will return after 2 minutes. It is possible to return to the default display at any time using the information key. 2 - Time clock level In the time clock level the individual program times can be customized. Standard heating programs 1, 2 and 3 can be called up as desired and overwritten with different switch times and temperatures. Each standard program can thus be configured individually and stored under the same program number so that three different programs are available on demand. These can then simply be called up in the user operating level see page 6 for setting of the automatic program. Note: Programming of room temperatures is only

possible if the relevant parameter has been enabled in the service level by an engineer.

If this has not been done it is only possible to change the on / off times. In this case the room temperature will be the works setting of 20ºC or the corrected value which has been set in the user level. The standard programs are lost when overwritten by customized programs. These are cancelled after a reset and replaced by the standard programs and therefore have to be recreated if needed.

12 Advanced User Instructions 430293ENG-Dec01 Room temperature correction for PARTY and HEATING with variable temperature parameter enabled. For operating types:

- PARTY - HEATING

The room temperature is set to automatic works setting of 20ºC or the corrected value which has been set in the user level. The actual room temperature values for each of these two operating types can be set independently to the automatic program if the relevant parameter has been enabled in the service level by an engineer. The value is set separately when calling up the operating type PARTY or HEATING by using the and keys. These values remain stored for each further call of this operating type. Room temperature correction during automatic with variable temperature parameter enabled. During automatic operation the room temperature can be corrected using the and keys. The value can also be corrected for PARTY or HEATING operation by pressing the key and for REDUCED operation by pressing the key. Entering the time clock level Entering this level is achieved by simply pressing the key. Initially the heating cycle which the room station has been set to is shown. The three programs 1, 2 or 3 can be selected using the and keys. Press key

Boiler circuit Works setting: 2 Change with and keys

or (if present)

Mixer circuit 1 Works setting: 2 Change with and keys

or (if present)

Mixer circuit 2 Works setting: 2 Change with and keys

With the and keys all of the heating circuits together with the hot water circuit can be called up and are available for programming. Time Clock Programming It is possible to program up to three cycles periods for each desired weekday. Each of these cycles has an on / off as well as a temperature indication for this time span. The temperature can only be adjusted if the relevant parameter is enabled in the service level. The temperature indication refers to the heating cycle. The temperature between heating cycles is controlled according to the setting at the central unit. For the hot water programs the temperature indication refers to the hot water temperature. Calling up of heating cycles With a further pressing of the key the first heating cycle of the selected program shows complete with indication of weekday, cycle number, on time, off time and temperature. Each value is called up with the key in series

- On time - Off time - Temperature

The key can be used to step backwards. The current value which can be changed with the and keys is shown blinking. Switch times can be altered in 5 minute intervals and temperatures in 0.5K increments in the range of 5-30ºC. The next heating cycle can be called up by pressing the key and the process repeated. Note: The on/off times of not used heating cycles

should be set to 00:00 by simultaneously pressing the and keys. The 00:00 value does not refer to a clock time but only shows an undefined switch time.

430293ENG-Dec01 Advanced User Instructions 13 After programming the last heating cycle (Sunday � cycle 3) the first heating cycle (Monday � cycle 1) will follow. By pressing the key in quick succession the programmed cycles can be called up in series the values noted and corrected if necessary. Time clock level can be exited by pressing the key. Press to enter Cycle program Cycle 1 Monday

ON

Change with Next setting

OFF

Change with Next setting

TEMP (only when set in service level parameters)

Change with Next cycle Cycle 2 Monday

ON

Change with Next setting

OFF

Change with Next setting

TEMP (only when set in service level parameters)

Change with Next cycle Cycle 3 Monday

ON

Change with Next setting

OFF

Change with Next setting

TEMP (only when set in service level parameters)

Change with Next cycle Remaining days in week Program as Monday

Tuesday ON cycle 1

Sunday OFF cycle 3

Time clock program The tables shown on pages 17-19 give an overview of the works programmed standard programs together with temperature settings which cannot be lost. When creating customized programs note the appropriate values in the tables.

14 Advanced User Instructions 430293ENG-Dec01 Canceling of individual heating cycles If necessary individually created cycles can be cancelled. After selecting the required cycle by pressing the key several times the cycle can be cancelled by pressing the and keys simultaneously. Enter the time program

or mixer circuit 1 or mixer circuit 2 or hot water

Press several times until the desired cycle appears

Press Simultaneously

Cycle cancelled

Block programming In order to simplify the programming of the time clocks it is possible to copy the time clock settings in various ways. A – Complete automatic programs It is possible to copy complete programs to other programs for example boiler circuit program 1 to mixed circuit 2 program 2. This can be achieved by using the key to enter the time clock and then the keys to select the program to use as the source. The key is used to select the target program to which it is to be copied. The key is used to complete the copy. The procedure is shown in further detail by the illustration on page 15. Note: It is not possible to copy heating circuit

programs to hot water programs or vice versa.

Restore standard program To restore a customized program to a works standard program select the program as described on page 12 (entering time clock level). Enter the time program

or mixer circuit 1 or mixer circuit 2 or hot water

Press Simultaneously

standard program restored

or mixer circuit 1 or mixer circuit 2 or hot water

Time clock level can be exited by pressing the key. The default display will then be restored.

B – Day to day or week Time programs can also be copied from day to the whole week or from day to day for example Tuesday to Wednesday. Day to week While in the time clock see page 13 the key followed by the key can be used to copy the current day to the whole week. The procedure is shown in further detail by the illustration on page 16. Day to day While in the time clock see page 13 the current day can be copied to another day by using the key two or more times to select the target day. The key is used to complete the copy of the current day to the target day. The procedure is shown in further detail by the illustration on page 16.

i

430293ENG-Dec01 Advanced User Instructions 15

Program 1

Program 2

Hot Water

Program 1

Program 2

Program 3

Mixed Circuit 2

Program 1

Program 2

Program 3

Mixed Circuit 1

Program 1

Program 2

Program 3

Boiler Circuit

Use or to change program no.

use to enter program to be copied to

Copy will appear

Press key to confirm copy

OK appears to confirm program copied

New source program for further copying

Program will blink

* * *

* only if present

Source program Source program Boiler circuit program 1 Target program mixer circuit 2 program 2 Program copied Target program = Source program

Copy Mixer 2 prog. 2 from boiler circuit prog. 1

Copy hot water prog. 3 from hot water prog. 2

Press to enter clock program

Program will blink

Heating circuit

16 Advanced User Instructions 430293ENG-Dec01 Room temperature corrections with individual temperature cycle programs (heating cycle only) When individual temperatures have been entered for each heating cycle, the desired room temperature can be altered via the correction keys or for one of the cycles. This change will then effect all other heating cycles as shown in the below example: Original cycle temperatures New cycle temperatures As the temperature was increased by 2K during cycle 2 the desired value has been increased by 2K in the other cycles.

Enter from heating cycle program Day copying

Day to copy (source day) Week Copying

Press

Target day to Copy to Press to copy Source day copied To target day Target day = Source for next copy

Press again to select target day

Copy again

Day copied to whole week Beginning of week now displayed

Press to copy

Cycle 2 20ºC + 2K = 22ºC

Cycle 1 18ºC + 2K = 20ºC

Cycle 3 22ºC + 2K = 24ºC Etc.

Cycle 2 20ºC

Cycle 1 18ºC

Cycle 3 22ºC

New Cycle 2 22ºC

Room temp + 2K

430293ENG-Dec01 Advanced User Instructions 17

Program 1 settings

Standard Program 1 Custom Program 1

Day Setting 1 Setting

2 Setting 3 Day Setting

1 Setting 2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To Temp

Mon 6.00 8.00 20oC 16.00 22.00 20oC - - - Mon

Tue 6.00 8.00 20oC 16.00 22.00 20oC - - - Tue

Wed 6.00 8.00 20oC 16.00 22.00 20oC - - - Wed

Thur 6.00 8.00 20oC 16.00 22.00 20oC - - - Thur

Fri 6.00 8.00 20oC 16.00 22.00 20oC - - - Fri

Sat 7.00 23.00 20oC - - - - - - Sat

Sun 7.00 23.00 20oC - - - - - -

Boi

ler C

ircui

t

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To Temp

Mon 6.00 8.00 20oC 16.00 22.00 20oC - - - Mon

Tue 6.00 8.00 20oC 16.00 22.00 20oC - - - Tue

Wed 6.00 8.00 20oC 16.00 22.00 20oC - - - Wed

Thur 6.00 8.00 20oC 16.00 22.00 20oC - - - Thur

Fri 6.00 8.00 20oC 16.00 22.00 20oC - - - Fri

Sat 7.00 23.00 20oC - - - - - - Sat

Sun 7.00 23.00 20oC - - - - - -

Mix

ed C

ircui

t 1

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To Temp

Mon 6.00 8.00 20oC 16.00 22.00 20oC - - - Mon

Tue 6.00 8.00 20oC 16.00 22.00 20oC - - - Tue

Wed 6.00 8.00 20oC 16.00 22.00 20oC - - - Wed

Thur 6.00 8.00 20oC 16.00 22.00 20oC - - - Thur

Fri 6.00 8.00 20oC 16.00 22.00 20oC - - - Fri

Sat 7.00 23.00 20oC - - - - - - Sat

Sun 7.00 23.00 20oC - - - - - -

Mix

ed C

ircui

t 2

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To Temp

Mon 6.00 8.00 60oC 16.00 22.00 60oC - - - Mon

Tue 6.00 8.00 60oC 16.00 22.00 60oC - - - Tue

Wed 6.00 8.00 60oC 16.00 22.00 60oC - - - Wed

Thur 6.00 8.00 60oC 16.00 22.00 60oC - - - Thur

Fri 6.00 8.00 60oC 16.00 22.00 60oC - - - Fri

Sat 6.00 22.00 60oC - - - - - - Sat

Sun 6.00 22.00 60oC - - - - - -

Hot

Wat

er

Sun

18 Advanced User Instructions 430293ENG-Dec01

Program 2 settings

Standard Program 2 Custom Program 2

Day Setting 1 Setting

2 Setting 3 Day Setting

1 Setting 2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To Temp

Mon 6.00 22.00 20oC - - - - - - Mon

Tue 6.00 22.00 20oC - - - - - - Tue

Wed 6.00 22.00 20oC - - - - - - Wed

Thur 6.00 22.00 20oC - - - - - - Thur

Fri 6.00 22.00 20oC - - - - - - Fri

Sat 7.00 22.00 20oC - - - - - - Sat

Sun 7.00 22.00 20oC - - - - - -

Boi

ler C

ircui

t Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To TempMon 6.00 22.00 20oC - - - - - - Mon Tue 6.00 22.00 20oC - - - - - - Tue Wed 6.00 22.00 20oC - - - - - - Wed Thur 6.00 22.00 20oC - - - - - - Thur Fri 6.00 22.00 20oC - - - - - - Fri Sat 7.00 22.00 20oC - - - - - - Sat Sun 7.00 22.00 20oC - - - - - -

Mix

ed C

ircui

t 1

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To TempMon 6.00 22.00 20oC - - - - - - Mon Tue 6.00 22.00 20oC - - - - - - Tue Wed 6.00 22.00 20oC - - - - - - Wed Thur 6.00 22.00 20oC - - - - - - Thur Fri 6.00 22.00 20oC - - - - - - Fri Sat 7.00 22.00 20oC - - - - - - Sat Sun 7.00 22.00 20oC - - - - - -

Mix

ed C

ircui

t 2

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To TempMon 6.00 22.00 60oC - - - - - - Mon Tue 6.00 22.00 60oC - - - - - - Tue Wed 6.00 22.00 60oC - - - - - - Wed Thur 6.00 22.00 60oC - - - - - - Thur Fri 6.00 22.00 60oC - - - - - - Fri Sat 6.00 22.00 60oC - - - - - - Sat Sun 6.00 22.00 60oC - - - - - -

Hot

Wat

er

Sun

430293ENG-Dec01 Advanced User Instructions 19

Program 3 settings

Standard Program 3 Custom Program 3

Day Setting 1 Setting

2 Setting 3 Day Setting

1 Setting 2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To Temp

Mon 6.00 23.00 20oC - - - - - - Mon

Tue 6.00 23.00 20oC - - - - - - Tue

Wed 6.00 23.00 20oC - - - - - - Wed

Thur 6.00 23.00 20oC - - - - - - Thur

Fri 6.00 23.00 20oC - - - - - - Fri

Sat 7.00 23.00 20oC - - - - - - Sat

Sun 7.00 22.00 20oC - - - - - -

Boi

ler C

ircui

t

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To TempMon 6.00 23.00 20oC - - - - - - Mon Tue 6.00 23.00 20oC - - - - - - Tue Wed 6.00 23.00 20oC - - - - - - Wed Thur 6.00 23.00 20oC - - - - - - Thur Fri 6.00 23.00 20oC - - - - - - Fri Sat 7.00 23.00 20oC - - - - - - Sat Sun 7.00 22.00 20oC - - - - - -

Mix

ed C

ircui

t 1

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To TempMon 6.00 23.00 20oC - - - - - - Mon Tue 6.00 23.00 20oC - - - - - - Tue Wed 6.00 23.00 20oC - - - - - - Wed Thur 6.00 23.00 20oC - - - - - - Thur Fri 6.00 23.00 20oC - - - - - - Fri Sat 7.00 23.00 20oC - - - - - - Sat Sun 7.00 22.00 20oC - - - - - -

Mix

ed C

ircui

t 2

Sun

Day Setting

1 Setting

2 Setting

3 Day Setting

1 Setting

2 Setting

3

From To Temp From To Temp From To Temp From To Temp From To Temp From To TempMon 6.00 23.00 60oC - - - - - - Mon Tue 6.00 23.00 60oC - - - - - - Tue Wed 6.00 23.00 60oC - - - - - - Wed Thur 6.00 23.00 60oC - - - - - - Thur Fri 6.00 23.00 60oC - - - - - - Fri Sat 6.00 23.00 60oC - - - - - - Sat Sun 6.00 22.00 60oC - - - - - -

Hot

Wat

er

Sun

20 Advanced User Instructions 430293ENG-Dec01 3 - Room Level At this level, the parameters relevant to the heating requirements of the building and its characteristics can be displayed and changed.

- Hot water temperature - Burner hours run - Burner starts - Holiday program - Clock programs - Heating curves - Room temperature correction - Reset function

Entering the Room Level Room level can be entered by using the key. Changes can be made using the , and keys. To exit the room level press the key at any time. Press and hold for 3 secs

Hot water temperature

Works setting: TopTronic 1B and 133B → 55ºC Other TopTronics → 60ºC Adjustment range 10ºC � Hot water maximum temperature press to increase to decrease The maximum temperature is set in the technical parameter level.

Burner hours run on 1ST stage

Works setting: 000000.00h Range: 0 � 99999999

Number of burner starts on 1st stage

Works setting: 00000000 Range: 0 � 99999999

Burner hours run on 2nd stage

Works setting: 000000.00h Range: 0 � 99999999

Number of burner starts on 2nd stage

Works setting: 00000000 Range: 0 � 99999999

Holiday program start

Adjust with to increase and to decrease Change between day and month with and This function is used to switch the heating to frost protection only while the building is unoccupied for example a holiday. The default display will be today�s date.

Holiday program finish

Adjust with to increase and to decrease Change between day and month with and This function is used to switch the heating back on when the building becomes occupied. Example of holiday program

The heating will be switched to frost protection only on the 29.3 at 24.00 hrs

i

430293ENG-Dec01 Advanced User Instructions 21

The heating will remain off from 30.3 00.00 hrs to 14.4 00.00 hrs. This will be

the default display until the heating is started again on 14.4.

Hot water clock program

Works setting: Program 2 Options: Program 1 Program 2 Program 3 Change with or With this parameter it is possible to change between the three clock programs for hot water, see pages 17 to 19 for settings.

Boiler circuit clock program

Works setting: Program 2 Options: Program 1 Program 2 Program 3 Change with or With this parameter it is possible to change between the three clock programs for the boiler circuit, see pages 17 to 19 for settings.

Mixed circuit 1 clock program

Works setting: Program 2 Options: Program 1 Program 2 Program 3 Change with or With this parameter it is possible to change between the three clock programs for mixed circuit 1, see pages 17 to 19 for settings.

Mixed circuit 2 clock program Works setting: Program 2

Options: Program 1 Program 2 Program 3 Change with or With this parameter it is possible to change between the three clock programs for mixed circuit 2, see pages 17 to 19 for settings.

Heating curve for boiler circuit

Works setting: 1.4 Range: 0.20 � 3.5 Change with or With this parameter it is possible to change the slope of the heating curve for the boiler circuit (see graph).

Heating curve for mixed circuit 1

Works setting: 1.4 Range: 0.20 � 3.5 Change with or With this parameter it is possible to change the slope of the heating curve for mixed circuit 1 (see graph).

Heating curve for mixed circuit 2

Blinks if auto adaption is set in service level parameters (do not change)

Blinks if auto adaption is set in service level parameters (do not change)

Blinks if auto adaption is set in service level parameters (do not change)

22 Advanced User Instructions 430293ENG-Dec01 Works setting: 1.4 Range: 0.20 � 3.5 Change with or With this parameter it is possible to change the slope of the heating curve for the boiler circuit (see graph). The heating curve gives the (boiler and / or mixed circuit) flow temperature / outdoor temperature ratio. The curve should only be reset with minimum changes spread out over a certain period of time to enable the regulator to react (by nature a heating installation is very slow to react). Corrections of 0.1 increments every 1 or 2 days is recommended. Note: The room station should be placed in the

room that most accurately represents the temperature of the building. Thermostatic radiator valves when fitted properly should only serve to deregulate foreign heat sources and therefore should be fully open. During the regulation phase all foreign heat source should be switch off and ventilation should be kept to a minimum so as not to disturb the regulation process.

When the heating curve is correctly set the room temperature should remain constant regardless of outside temperature. If automatic adaption is set in the service level the value will blink and is constantly corrected. In this case it must not be manually altered. Recommended values: Floor heating: 0.3 �.. 1.0 Radiator heating: 1.2 �.. 2.0 Convection heating: 1.5 �.. 2.0 Heating curve graph

Room temperature compensation

1 2 Works setting: 0.0K Range: -2.5K � +2.5K Change with or 1 � Room temperature 2 � Correction With this parameter it is possible to calibration the room temperature by ± 2.5K.

Reset function

With this function it is possible to reset all the room level parameters back to their factory settings with the exception of burner hours run and burner starts. To reset room level parameters hold and Simultaneously until the following display appears

Parameters reset

Default display

Max temp

Min temp

Outside temperature ºC

Boiler Flow Temp ºC

430293ENG-Dec01 Room Level Parameters 23

Parameter Function With TopTronic Range Factory Setting

Current Setting

1. Burner hours run 1B, 133B 2B, 23B, 233B 223B, 2233B 203B

000000.00 � 999999.59

000000.00

2. Burner starts 1B, 133B 2B, 23B, 233B 223B, 2233B 203B

00000000 � 99999999

00000000

3. Burner hours run on 2nd stage

223B, 2233B 000000.00 � 999999.59

000000.00

4. Burner starts on 2nd stage 223B, 2233B 00000000 � 99999999

00000000

5. Holiday program start 1B, 133B 2B, 23B, 233B 223B, 2233B 203B 3

01/01 � 31/12 Not set

6. Holiday program finish 1B, 133B 2B, 23B, 233B 223B, 2233B 203B 3

01/01 � 31/12 Not set

7. Clock program for HWS 1B, 133B 2B, 23B, 233B 223B, 2233B 203B

1 � 2 � 3

2

8. Clock program for boiler circuit

1B, 133B 2B, 23B, 233B 223B, 2233B 203B

1 � 2 � 3

2

9. Clock program for mixed circuit 1

1B, 133B 2B, 23B, 233B 223B, 2233B 203B

1 � 2 � 3

2

10. Clock program for mixed circuit 2

1B, 133B 2B, 23B, 233B 223B, 2233B 203B

1 � 2 � 3

2

1B, 133B 55oC 11. HWS temp (only with greater access program) 2B, 23B, 233B

223B, 2233B 203B

10oC

60oC

12. Heating curve � boiler circuit 1B, 133B 2B, 23B, 233B 223B, 2233B 203B

0.20�3.50 1.4

13. Heating curve � mixed circuit 1

1B, 133B 2B, 23B, 233B 223B, 2233B 203B

0.20�3.50 1.4

14. Heating circuit � mixed circuit 2

133B 233B 2233B

0.20�3.50 1.4

15. Room temperature compensation

1B, 133B 2B, 23B, 233B 223B, 2233B 203B 3

16. Reset to factory settings

24 Advanced Parameter Table 430293ENG-Dec01

Factory settings No. Parameter Function Adj. Range 133B 1B 2B 23B 233B 2233B 223B 3 203B Current Setting

1 Frost Protection -20°C...10°C 0 0 0 0 0 0 0 0 0 2 Summer switch-off Aus, 10°C...30°C 17°C 17°C 17°C 17°C 17°C 17°C 17°C 17°C 17°C 3 Minimum outdoor temperature -20...0 -10 -10 -10 -10 -10 -10 -10 -10 -10 4 Maximum flue gas temperature 70°C...250°C 250°C 250°C 250°C 250°C 250°C 250°C 250°C 5 Maximum boiler temperature 10°C...95°C (90°C Gas) 80°C 80°C 85°C 85°C 85°C 85°C 85°C 85°C 6 Boiler return temperature 0...70°C 0 38°C 38°C 38°C 38°C 38°C 7 Blr circ Temp rise (Above mix circ) 0(-5K 133B,3)...20K) 0K 8 K 8 K 12 K 12 K 8K 8 K 8 Pump overrun 0...15 min 5 min 5 min 5 min 5 min 5 min 5 min 5 min 5 min 5 min 9 Boiler minimum temperature 10°C(0°C 203B)...95°C 48°C 48°C 48°C 48°C 48°C 0 °C

Type of hot water priority 1,2,3 3 2 2 3 3 3 3 3 1: None X X X X X X X X 2: Priority X X X X X X X X

10

3: Priority with reservation X X X X X X 11 Maximum hot water temperature 40°C...80°C 60°C 60°C 60°C 60°C 60°C 60°C 60°C 60°C

Type of calorifier sensor 1,2 2 2 2 2 2 2 2 2 1: Thermostat X X X X X X X X 12

2: Sensor X X X X X X X X 13 Protection against Legionella 0...8 8 8 0 0 0 0 0 0 14 Night water load 0.1...1.0 0.3 0.3 15 Dom H/water installation load temp 0...50K 20 K 20 K 25 K 25 K 25 K 25 K 25 K 25 K 20 Influence room temp on blr circ KK 0...2.5 0.5 0.5 1.0 1.0 1.0 1.0 1.0 1.0

Blr circ automatic adaption KK 0,1 0 1 1 0 0 0 0 0 0: Off X X X X X X X X 21

1: On X X X X X X X X Boiler circuit user index KK 1,2,3 2 2 2 2 2 2 2 2 1: 1.00 X X X X X X X X 2: 1.31 X X X X X X X X

22

3: 2.00 X X X X X X X X 23 Blr circ derivative action time KK 0...6h 2h 2h 1h 1h 1h 1h 1h 1h

Blr circ ext sensor detection KK 0,1,2 0 0 0 0 0 0 0 0 0: Average value X X X X X X X X 1: External sensor 1 X X X X X X X X

24

2: External sensor 2 X X X X X X X X 27 Boiler circ constant temp reg KK 0..95 (90°C Gas) °C 0 0 0 0 0 0 30 Influence room temp blr circ MK1 0...2.5 0.5 1.0 1.0 1.0 1.0 1.0 1.0

Mixed circ 1 auto adaption MK1 0,1 1 1 1 1 1 1 1 0: Off X X X X X X X 31

1: On X X X X X X X 32 Mixed circuit minimum temp MK1 0...95°C (90°C Gas) 0 0 0 0 0 0 0 33 Mixed circuit maximum temp MK1 10°C...95°C (90°C Gas) 80°C 80°C 80°C 80°C 80°C 80°C 80°C

Mixed circuit 1 user index MK1 1,2,3 2 2 2 2 2 2 2 1: 1.00 X X X X X X X 2: 1.31 X X X X X X X

34

3: 2.00 X X X X X X X 35 Mix circ1 derivative action time MK1 0...6h 2h 1h 1h 1h 1h 1h 1h

Mix circ 1 ext sens. detection MK1 0,1,2 0 0 0 0 0 0 0 0: Average value X X X X X X X 1: External sensor 1 X X X X X X X

36

2: External sensor 2 X X X X X X X 40 Influence room temp mix circ 2MK2 0...2.5 0.5 1.0 1.0

X = Possible settings

430293ENG-Dec01 Advanced Parameter Table 25

Factory settings No. Parameter Function Adj. Range 133B 1B 2B 23B 233B 2233B 223B 3 203B Current Setting

Mixed circ 2 auto adaption 2MK2 0,1 1 1 1 0: Off X X X 41

1: On X X X 42 Mixed circ 2 minimum temp MK2 0...95°C (90°C Gas) 0 0 0 43 Mixed circ 2 maximum temp MK2 10°C...95°C (90°C Gas) 80°C 80°C 80°C

Mixed circuit 2 user index MK2 1,2,3 2 2 2 1: 1.00 X X X 2: 1.31 X X X

44

3: 2.00 X X X 45 Mix circ2 derivative actiontimeMK2 0...6h 2h 1h 1h

Mix circ2 ext sensor detect MK2 0,1,2 0 0 0 0: Average value X X X 1: External sensor 1 X X X

46

2: External sensor 2 X X X 47 Mix circ 2 const. reg operat'n MK2 0...95°C (90°C Gas) 0 0 0 48 Mixed circ2 fixed point regulation 0...95°C (90°C Gas) 0 0 0

Summer/winter switchover 0,1 1 1 1 1 1 1 1 1 1 0: Off X X X X X X X X X 60

1: On X X X X X X X X X Control output programming X3-3 1 ... 7 4 1 1 4 4 5 5 5 1: Boiler circuit pump X X X X X X X X 2: Casc. Boil. Interm. Valve X X X X X X X X 3: Fault signal output X X X X X X 4: Boiler circuit lock X X X X X X 5: Primary pump X X X X X X 6: Low return temp protection pump X X X X X

61

7: Switch-on with external sensor X Control output programming X4-10 1,2,3,4 1 4 4 3 3 1: Heat pump/solar/wood X X X X X 2: Fault signal output X X X X X 3: Boiler circ. Clock X X X X X

62

4: Electrical battery X X X X Control output programming X4-11 1,2,3,4 1 1 1 1 1 1 1: Fault signal output X X X X X X 2: Pump minimum speed X X X X X X 3: Clock channel X X X X X

63

4: Heat pump/solar/wood X X X X X X 64 Bus address 1...5 1 1 1 1 1 1 1 1 1

Boiler cascade 0,1 0 0 0 0 0 0 0: Single boiler X X X X X X 65

1: Cascade X X X X X X Level lock up 0,1,2,3 0 0 0 0 0 0 0 0 0 0: No lock up X X X X X X X X X 1: Room level lock up X X X X X X X X X 2: Clock lock up X X X X X X X X X

66

3: Room level and clock lock up X X X X X X X X X Reduced operation 0,1 1 1 1 1 1 1 1 1 1 0: ECO - (Switch-off) X X X X X X X X X 67

1: Abs (Reduction) X X X X X X X X X 68 Minimum Room Temperature 5°C...20°C 5 °C 5 °C 5 °C 5 °C 5 °C 5 °C 5 °C 5 °C 5 °C

X = Possible settings

26 Advanced Parameter Table 430293ENG-Dec01

Factory settings No. Parameter Function Adj. Range 133B 1B 2B 23B 233B 2233B 223B 3 203B Current Setting

Pump seizure protection 0,1 1 1 1 1 1 1 1 1 1 0: Off X X X X X X X X X 69

1: On X X X X X X X X X C/return protect during Blr turnon 0,1 1 1 1 1 1 1 0: Off X X X X X X 70

1: On X X X X X X 71 Extended burner operation time 0...20 min 10 min 10 min 10 min 10 min 10 min 20 min 72 1st stage differential 2...30K 6 K 6 K 6 K 6 K 6 K 10 K 73 2nd stage differential 2...30K 12 K 12 K 74 2nd stage delay 0...60min 10 min 10 min 10 min 75 Lock 2stage with Outdoor temp Aus, -15°C...30°C 10°C 10°C 10°C

Hot water power select for 2stage 1...3 3 3 3 1: With outdoor temp and delay X X X 2: With outdoor temp without delay X X X

76

3: Without limitations X X X Control input programming X1-33 0,1,2 0 0 2 2 2 0: Dom water heat (auto/Blr/Elec) X X X X 1: Priority inversion X X X

80

2: Burner operation X X X X X Alarm logic signals 0,1 1 1 1 1 1 1 1 1 1 0: Off X X X X X X X X X 81

1: On X X X X X X X X X 82 RESET RESET X X X X X X X X X 83 Relay Test alle Relais / all relays X X X X X X X X X

X = Possible settings

430293ENG-Dec01 Installation / Technical Data 27

Installation

Positioning – without room sensor If there is no room sensor or the room sensor has not been activated the unit can be placed as desired.

Positioning – with room sensor When used with the unit sensor activated the unit must be placed at a height of approximately 1.20 to 1.50 m in a place representing the temperature of all rooms. It is advisable to choose an internal wall in the coolest room which is used in the day.

The unit may not be positioned: • In direct sunlight (take note of the position of the sun in winter) • Near any equipment which produces heat like televisions, wall lights, radiators etc. • On walls where hot water pipes or chimneys run. • On outside walls which are not insulated. • In corners, recesses, shelves or behind curtains (insufficient air circulation). • Near doors which lead to unheated rooms. • In rooms which are regulated with thermostatic valves.

Mounting Open the cover and loosen the screw inside. Lift the unit off the back plate. Secure the back plate with the screws provided. The data bus cable must be threaded through the lower part of the back plate. With a data bus cable of over 50m cable of types JY-(ST) 2x2x0.6 or LI YC T (TP) 2x2x0.75 must be used. The screening must be connected to the earth terminal of the boiler. Note: on new installations use a box behind the room station.

Electrical Connection Before connecting / wiring the power at the boiler must be off. The 4 core bus cable is connected to the 4 pole terminal on the back plate. After the wiring is complete the room station is slotted in from above and screwed to the back plate. Note: by incorrect wiring the remains in VERSION indication for approximately 1 minute and then goes to fault indication. Technical Data

Wiring: 4 pole screwed terminals on back plate for 1mm2 max wire cross section.

Bus Interface: RS485

Power supply: From central unit

Color: White RAL 9016

Fixing distance: 60mm (2 hole fixing) Wall Fixing: 2 x 3mm dia x 18 long

Weight: 170g

Operating Temperature: -10oC�.+50oC

Storage Temperature: -25oC�.+60oC

Indication: Alpha numeric text indication as well as symbols