1
USE:GENERALCUSTOMER INFORMATION FOR GROUNDING AND BONDING CONCRETE ENCASED ELECTRODE (UFER GROUND) EXTERIOR FOUNDATION {TOP VIEW) (END VIEW) 2" MIN. CONNECTION TO ELECTRODE. CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUNDING ELECTRODE WITH APPROVED GROUNDING CLAMP. SEE NEC ARTICLE 250 GROUNDING ELECTRODE SHALL BE TERMINATED IN A DRY LOCATION IF RE-BAR IS USED SERVICE DISCONNECT IF THE NEUTRAL BUS IS INSULATED FROM THE ENCLOSURE INSTALL A MAIN BONDING JUMPER OR SCREW PER NEC ARTICLE 250. SEE NEC ARTICLE 250 FOR TYPE AND SIZE OF MATERIAL AND PROTECTION OF THE GROUNDING ELECTRODE CONDUCTOR. BOND TO INTERIOR METALLIC WATER PIPING SYSTEMS PER NEC ARTICLE 250. EXTERIOR CONCRETE FOUNDATION 1-----GROUND ELECTRODE NEC 250 3" MIN . (SIDE VIEW) NOTE: 20 FT. OR MORE ENCASED OF #4 REINFORCING STEEL, OR #4 BARE COPPER WIRE (OR LARGER). SEE NEC ARTICLE 250 . FORMALLY: SR-453 Page 5 -- ....... INITIATED BY DM REVISION NO. 0 UniSouroeEnergy a-------+-----11-------+------1 SR-602 Pg. 1 of 1 Tucson Electric Power SERVl:ES i--ES_R_C_O_M_M_ . ---+-----1 SUTACRUZCOUNTY ESR COMM . 7-17 EFFECTIVE DATE 7-17

Upload: others

Post on 21-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: USE:GENERALCUSTOMER CONCRETE ENCASED ELECTRODE INFORMATION FOR (UFER GROUND… · 2019. 5. 20. · ground electrode nec 250 initiated by esr comm. sleeves holes, etc. (end view) connection

USE:GENERALCUSTOMER INFORMATION FOR GROUNDING AND BONDING

CONCRETE ENCASED ELECTRODE (UFER GROUND)

EXTERIOR FOUNDATION {TOP VIEW)

(END VIEW)

2" MIN.

CONNECTION TO ELECTRODE. CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUNDING ELECTRODE WITH APPROVED GROUNDING CLAMP. SEE NEC ARTICLE 250

GROUNDING ELECTRODE SHALL BE TERMINATED IN A DRY LOCATION IF RE-BAR IS USED

SERVICE DISCONNECT

IF THE NEUTRAL BUS IS INSULATED FROM THE ENCLOSURE INSTALL A MAIN BONDING JUMPER OR SCREW PER NEC ARTICLE 250.

SEE NEC ARTICLE 250 FOR TYPE AND SIZE OF MATERIAL AND PROTECTION OF THE GROUNDING ELECTRODE CONDUCTOR.

BOND TO INTERIOR METALLIC WATER PIPING SYSTEMS PER NEC ARTICLE 250.

EXTERIOR CONCRETE FOUNDATION

1-----GROUND ELECTRODE NEC 250

3" MIN. (SIDE VIEW)

NOTE: 20 FT. OR MORE ENCASED OF #4 REINFORCING STEEL, OR #4 BARE COPPER WIRE (OR LARGER). SEE NEC ARTICLE 250.

FORMALLY: SR-453 Page 5

--....... INITIATED BY DM REVISION NO. 0 UniSouroeEnergy a-------+-----11-------+------1 SR-602 Pg. 1 of 1 Tucson Electric Power

SERVl:ES i--ES_R_C_O_M_M_. ---+-----1 SUTACRUZCOUNTY ESR COMM . 7-17 EFFECTIVE DATE 7-17