upright and pendent sprinkler, quick response

Upload: ahrian-bena

Post on 04-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Upright and Pendent Sprinkler, Quick Response

    1/6

    GeneralDescriptionThe Series TY-FRL, 5.6 and 8.0 K-fac-tor Upright and Pendent Intermediate

    Level Sprinklers described in this datasheet are automatic sprinklers of thequick response solder type. They arestandard spray sprinklers intendedfor use in fire sprinkler systems de-signed in accordance with the stand-ard installation rules recognized by theapplicable Listing or Approval agency(e.g., UL Listing is based on NFPArequirements). Both the Pendent andUpright Sprinklers produce a hemi-spherical water distribution pattern be-low the deflector.

    Intermediate Level Sprinklers are pri-marily designed for use in rack storagesprinkler systems where their ther-mally sensitive elements must beshielded from the water spray of higherelevation sprinklers that could operateearlier during a fire. Intermediate LevelSprinklers are also used in other appli-cations such as beneath open griddedcatwalks.

    WARNINGSThe Series TY-FRL Sprinklers de-scribed herein must be installed andmaintained in compliance with thisdocument, as well as with the applica-

    ble standards of the National Fire Pro-tection Association, in addition to thestandards of any other authorities hav-ing jurisdiction. Failure to do so mayimpair the performance of these de-vices.

    The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition.The installing contractor or sprinklermanufacturer should be contactedwith any questions.

    Model/SprinklerIdentificationNumbersTY3123 - Upright 5.6K, 1/2"NPT

    TY3221 - Pendent 5.6K, 1/2"NPTTY4123 - Upright 8.0K, 3/4"NPTTY4221 - Pendent 8.0K, 3/4"NPT

    TY3123 is a redesignation for S1991and G8986.

    TY3221 is a redesignation for S1865and G8972.

    TY4123 is a redesignation for S1993and G8153.

    TY4221 is a redesignation for S1867and G8172.

    TechnicalDataApprovalsUL and C-UL Listed.FM and NYC Approved.(Refer to Table A for complete ap-proval information.)

    Maximum Working Pressure175 psi (12,1 bar)

    Discharge CoefficientK = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2)

    Temperature RatingsRefer to Table A

    Finishes

    Natural Brass, Chrome PlatedPhysical CharacteristicsFrame . . . . . . . . . . . . BronzeStrut . . . . . . . . . . . . . . MonelDeflector . . . . . . . . . . . B ronzeHook . . . . . . . . . . . . . . M onelLink Assembly . . . . . . . . . NickelEjection Spring . . . . . . . InconelButton . . . . . . . . . . . . BronzeSeal . . . . . . . . . . . . . TeflonShield . . . . . . . . . . . . . Brass DuPont Registered Trademark

    Series TY-FRL 5.6 and 8.0 K-factorUpright and Pendent Intermediate Level SprinklersQuick Response

    Page 1 of 6 TFP355JULY, 2005

    Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

    IMPORTANTA lways refer t o Technical DataSheet TFP700 for the INSTALLERWARNING that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.

  • 7/30/2019 Upright and Pendent Sprinkler, Quick Response

    2/6

    Page 2 of 6 TFP355

    FIGURE 1QUICK RESPONSE SERIES TY-FRL UPRIGHT (TY3123) AND PENDENT (TY3221) SPRINKLERS

    INTERMEDIATE LEVEL SPRINKLERS, 5.6 K-FACTOR, 1/2 INCH NPT

    * Temperature rating is indicated on the deflector or shield.** Pipe thread connections per ISO 7/1 can be provided on special request.

    * Temperature rating is indicated on the deflector or shield.** Pipe thread connections per ISO 7/1 can be provided on special request.

    FIGURE 2QUICK RESPONSE SERIES TY-FRL UPRIGHT (TY4123) AND PENDENT (TY4221) SPRINKLERS

    INTERMEDIATE LEVEL SPRINKLERS, 8.0 K-FACTOR, 3/4 INCH NPT

    2-3/4"(69,9 mm)

    (11,1 mm)NOMINALMAKE-IN

    7/16"

    FACTORY ASSEMBLED UPRIGHT

    FACTORY

    SHIELDUPRIGHT

    ASSEMBLED

    FLANGESWRENCH

    WRENCHAREA

    4-1/8" (104,8 mm) DIA.

    FIELDASSEMBLED PENDENT

    2-11/16"(68,3 mm)

    DEFLECTOR*

    *

    SERIESPENDENT

    TY-FRL

    SPEEDNUT

    MODEL S4 SHIELD PACKAGEPENDENT SERIES TY-FRL &

    SEPERATELY ORDERED

    COMPRISE PENDENT ASSEMBLY(SEE ODERING PROCEDURE)

    O-RING

    SECTION)(SEE INSTALLATIONMODEL S4 SHIELDFIELD ASSEMBLED

    **NPT1/2"

    NOMINALMAKE-IN

    FACTORY ASSEMBLED UPRIGHT

    FACTORY

    SHIELDUPRIGHT

    ASSEMBLED

    FLANGESWRENCH

    WRENCHAREA

    4-1/8" (104,8 mm) DIA.

    FIELD ASSEMBLED PENDENT

    DEFLECTOR*

    *

    SERIESPENDENT

    TY-FRL

    SPEEDNUT

    MODEL S4 SHIELD PACKAGE

    PENDENT SERIES TY-FRL &SEPERATELY ORDERED

    COMPRISE PENDENTASSEMBLY(SEE ODERING PROCEDURE)

    O-RING

    SECTION)(SEE INSTALLATIONMODEL S4 SHIELDFIELDASSEMBLED

    **NPT3/4"

    2-13/16"(71,4 mm)

    (12,7 mm)1/2"

    (74,6 mm)2-15/16"

  • 7/30/2019 Upright and Pendent Sprinkler, Quick Response

    3/6

    Operation

    The fusible link (heat collector) assem-bly is comprised of two halves that are

    joined together by a thin layer of sol-der. When the rated temperature isreached, the solder melts and the twolink halves separate, allowing thesprinkler to operate.

    DesignCriteriaThe Series TY-FRL Pendent and Up-right Intermediate Level Sprinklers are

    intended for fire protection systemsdesigned in accordance wit h t hestandard installation rules recognizedby the applicable Listing or Approvalagency (e.g., UL Listing is based onthe requirements of NFPA 13, and FMApproval is based on the requirementsof FMs Loss Prevention Data Sheets).

    Installation

    The Series TY-FRL Sprinklers must beinstalled in accordance with the follow-ing instructions:

    NOTEA leak tight 1/2 inch NPT sprinkler jointshould be obtained with a torque of 7to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-mum of 21 ft. lbs. (28,5 Nm) of torquemay be used to install sprinklers with1/2 NPT connections. A leak tight 3/4inch NPT sprinkler joint should be ob-tained with a torque of 10 to 20 ft.lbs.(13,4 to 26,8 Nm). A maximum of 30ft.lbs. (40,7 Nm) of torque is to be usedto install sprinklers with 3/4 NPT con-

    nections. Higher levels of torque maydistort the sprinkler inlet and causeleakage or impairment of the sprinkler.

    Upright Sprinklers The Series TY-FRL Intermediate LevelUpright Sprinklers must be installed inaccordance with the following instruc-tions.

    Step 1. With pipe thread sealant ap-plied to the pipe threads, hand tightenthe sprinkler into the sprinkler fitting.

    Step 2. Tighten the sprinkler into thesprinkler fitting using only the W-Type9 Sprinkler Wrench (Ref. Figure 3).

    With reference to Figure 1 or 2, theW-Type 9 Sprinkler Wrench is to beapplied to the wrenching area.

    Pendent Sprinklers The Series TY-FRL Intermediate LevelPendent Sprinklers must be installedin accordance with the following in-structions.

    Step 1. Install the Speed-nut over thesprinkler threads until it seats againstthe sprinkler wrenching area flange asshown in Figure 1 or 2, as applicable.

    Step 2. Install the Shield over the

    sprinkler threads, and then roll the O-

    Ring over the sprinkler threads until itis seated firmly against the Shield.

    Step 3. With pipe thread sealant ap-plied, hand tighten the sprinkler intothe sprinkler fitting.

    Step 4. Tighten the sprinkler into thesprinkler fitting using only the W-Type9 Sprinkler Wrench (Ref. Figure 3).The wrench is to be applied to thesprinkler wrenching area shown in Fig-ure 1 or 2, as applicable.

    When installed correctly, the O-Ringwill be slightly compressed and theShield will be held firmly in place.

    TFP355 Page 3 of 6

    TEMP.

    RATING

    FRAME

    COLOR

    CODE

    NATURAL

    BRASS

    SPRINKLER FINISH

    1, 2, 3, 4Unpainted165F/74C

    NOTES:1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.4. Approved by the City of New York under MEA 112-04-E.

    TABLE ALABORATORY LISTINGS AND APPROVALS

    CHROME

    PLATED

    K = 5.6, UPRIGHT TY3123

    K = 5.6, PENDENT TY3221

    K = 8.0, UPRIGHT TY4123

    K = 8.0, PENDENT TY4221

    NATURAL

    BRASS

    CHROME

    PLATED

    FIGURE 3W-TYPE 9 SPRINKLER

    WRENCH

    WRENCH

    RECESS

  • 7/30/2019 Upright and Pendent Sprinkler, Quick Response

    4/6

    Care andMaintenanceThe Series TY-FRL Sprinklers must bemaintained and serviced in accord-ance with the following instructions:

    NOTESBefore closing a fire protection systemmain control valve for maintenancework on the fire protection system thatit controls, permission to shutdown theaffected fire protection system must beobtained from the proper authoritiesand all personnel who may be affectedby this action must be notified.

    Sprinklers that are found to be leakingor exhibiting visible signs of corrosionmust be replaced.

    Automatic sprinklers must never bepainted, plated, coated or otherwise

    altered after leaving the factory. Modi-fied or over-heated sprinklers must bereplaced.

    Care must be exercised to avoid dam-age to the sprinklers - before, during,and after installation. Sprinklers dam-aged by dropping, striking, wrenchtwist/slippage, or the like, must be re-placed.

    The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-

    tion Association (e.g., NFPA 25), inaddition to the standards of any otherauthorities having jurisdiction. The in-stalling contractor or sprinkler manu-facturer should be contacted relativeto any questions.

    It is recommended that automatics p r in k l er s y s te m s b e i n sp e ct e d,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcode.

    LimitedWarrantyProducts manufactured by Tyco Fire &Building Products are warranted solelyto the original Buyer for ten (10) years

    against defects in material and work-manship when paid for and properlyinstalled and maintained under normaluse and service. This warranty will ex-pire ten (10) years from date of ship-ment by Tyco Fire & Building Products.No warranty is given for products orcomponents manufactured by compa-nies not affiliated by ownership withTyco Fire & Building Products or forproducts and components which havebeen subject to misuse, improper in-stallation, corrosion, or which have notbeen installed, maintained, modifiedor repaired in accordance with applica-ble Standards of the National Fire Pro-

    tection Association, and/or the stand-ards of any other Authorities HavingJurisdiction. Materials found by TycoFire & Builing Products to be defectiveshall be either repaired or replaced, atTyco Fire & Building Products soleoption. Tyco Fire & Building Productsneither assumes, nor authorizes anyperson to assume for it, any other ob-ligation in connection with the sale ofproducts or parts of products. TycoFire & Building Products shall not beresponsible for sprinkler system de-sign errors or inaccurate or incompleteinf ormation suppl ied by B uyer orBuyers representatives.

    IN NO EVENT SHALL TYCO FIRE &BUILDING PRODUCTS BE LIABLE,IN CONTRACT, TORT, STRICT LI-ABILITY OR UNDER ANY OTHER LE-GAL THEORY, FOR INCIDENTAL,INDIRECT, SPECIAL OR CONSE-QUENTIAL DAMAGES, INCLUDINGB UT N OT L IM IT ED T O L AB ORC H AR GE S, R EG AR DL ES S O FWHETHER TYCO FIRE & BUILDINGP RO DU CT S W AS I NF OR MEDABOUT THE POSSIBILITY OF SUCHD A MA G ES , A N D I N N O E V EN TS HA LL TY CO FI RE & B UI LDI NGPRODUCTS LIABILITY EXCEED ANAMOUNT EQUAL TO THE SALESPRICE.

    THE FOREGOING WARRANTY ISMADE IN LIEU OF ANY AND ALLOTHER WARRANTIES EXPRESSOR IMPLIED, INCLUDING WARRAN-TIES OF MERCHANTABILITY ANDFITNESS FOR A PARTICULAR PUR-POSE.

    Page 4 of 6 TFP355

  • 7/30/2019 Upright and Pendent Sprinkler, Quick Response

    5/6

    OrderingProcedureWhen placing an order, indicate the fullproduct name. Refer to the Price Listfor complete listing of Part Numbers.

    Contact your local distributor for avail-ability.

    Upright Sprinkler Assemblies withShield and NPT ThreadConnections:Specify: (Specify Model/SIN), QuickResponse, (specify K-factor), (specifytemperature rating), Series TY-FRLUpright Intermediate Level Sprinklerwith (specify finish), P/N (specify fromTable B).

    Pendent Sprinkler Assemblies with(Shield Ordered Separately) andNPT Thread Connections:Specify: (Specify Model/SIN), QuickResponse, (specify K-factor), (specify

    temperature rating), Series TY-FRLPendent Sprinkler with (specify finish),P/N (specify from Table C)

    Model S4 Pendent Shield Package:Specify: S4 Pendent Shield Package(one shield / one o-ring/ one speed-nut) with (specify finish) for use with(specify 1/2" NPT or 3/4" NPT) SeriesTY -FRL P endent S prinklers, P / N(specify).

    1/2" NPT S4Plain BrassPendent ShieldPackage . . . . . . . . . . . . . . P/N 56-952-1-001

    1/2" NPT S4Chrome PlatedPendent ShieldPackage . . . . . . . . . . . . . . P/N 56-951-9-001

    3/4" NPT S4Plain BrassPendent ShieldPackage . . . . . . . . . . . . . . P/N 56-152-1-001

    3/4" NPT S4Chrome PlatedPendent ShieldPackage . . . . . . . . . . . . . . P/N 56-152-9-001

    Sprinkler Wrench:Specify: W-Type 9 Sprinkler Wrench,P/N 56-000-1-849.

    TFP355 Page 5 of 6

    P/N 58 XXX X XXX

    165F/74C165

    TEMPERATURE

    RATING

    1

    SPRINKLER

    TABLE BPART NUMBER SELECTION

    SERIES TY-FRL UPRIGHT INTERMEDIATE LEVEL SPRINKLERS(UPRIGHT SHIELD INCLUDED WITH SPRINKLER)

    NATURAL BRASS

    MODEL/SIN

    153 8.0K UPRIGHT (3/4"NPT)

    986 5.6K UPRIGHT (1/2"NPT) TY3123

    TY4123 9 CHROME PLATED

    P/N 58 XXX X XXX

    TEMPERATURE

    RATING

    1

    SPRINKLER

    TABLE CPART NUMBER SELECTION

    SERIES TY-FRL PENDENT SPRINKLERS(MODEL S4 PENDENT SHIELD, SPEED-NUT & O-RING MUST BE SEPARATELY ORDERED)

    NATURAL BRASS

    MODEL/SIN

    172 8.0K PENDENT (3/4"NPT)

    982 5.6K PENDENT (1/2"NPT) TY3221

    TY4221

    165 165F/74C

    9 CHROME PLATED

  • 7/30/2019 Upright and Pendent Sprinkler, Quick Response

    6/6

    Page 6 of 6 TFP355

    TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446