  • 7/30/2019 Upright and Pendent Intermediate Level Sprinkler, Quick Response

    1/6

    GeneralDescriptionThe Series TY-FRB, 5.6 and 8.0 K-fac-tor Upright and Pendent Intermediate

    Level Sprinklers described in this datasheet are automatic sprinklers of thequick response 3 mm frangible bulbtype. They are standard spray sprin-klers intended for use in fire sprinklersystems designed in accordance withthe standard installation rules recog-nized by the applicable Listing or Ap-proval agency (e.g., UL Listing isbased on NFPA requirements). Boththe Pendent and Upright Sprinklersproduce a hemispherical water distri-bution pattern below the deflector.

    Intermediate Level Sprinklers are pri-marily designed for use in rack storagesprinkler systems where their ther-mally sensitive elements must beshielded from the water spray of higherelevation sprinklers that could operateearlier during a fire. Intermediate LevelSprinklers are also used in other appli-cations such as beneath open griddedcatwalks.

    Corrosion resistant coatings, whereapplicable, are utilized to extend thelife of copper alloy sprinklers beyondthat which would otherwise be ob-tained when exposed to corrosive at-mospheres. Although corrosion resis-tant coated sprinklers have passed the

    standard corrosion tests of the appli-cable approval agencies, the testing isnot representative of all possible cor-rosive atmospheres. Consequently, itis recommended that the end user beconsulted with respect to the suitabilityof these coatings for any given corro-

    sive environment. The effects of ambi-ent temperature, concentration ofchemicals, and gas/chemical velocity,should be considered, as a minimum,along with the corrosive nature of thechemical to which the sprinklers will beexposed.

    WARNINGSThe Series TY-FRB Sprinklers de-scribed herein must be installed andmaintained in compliance with thisdocument, as well as with the applica-ble standards of the National Fire Pro-tection Association, in addition to thestandards of any other authorities hav-ing jurisdiction. Failure to do so mayimpair the performance of these de-vices.

    The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition.The installing contractor or sprinklermanufacturer should be contactedwith any questions.

    Model/Sprinkler

    IdentificationNumbersTY3133 - Upright 5.6K, 1/2"NPTTY3231 - Pendent 5.6K, 1/2"NPTTY4133 - Upright 8.0K, 3/4"NPTTY4231 - Pendent 8.0K, 3/4"NPT

    TechnicalDataApprovalsUL and C-UL Listed.FM and NYC Approved.

    (Refer to Table A forcomplete approvalinformation including corrosion resis-tant status.)

    Maximum Working Pressure175 psi (12,1 bar)

    Discharge CoefficientK = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2)

    Temperature RatingsRefer to Table A

    FinishesSprinkler: Refer to Table A

    Series TY-FRB 5.6 and 8.0 K-factorUpright and Pendent Intermediate Level SprinklersQuick Response

    Page 1 of 6 TFP356JANUARY, 2005

    Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

    IMPORTANTAlways refer to Technical DataSheet TFP700 for the INSTALLERWARNING that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.

  • 7/30/2019 Upright and Pendent Intermediate Level Sprinkler, Quick Response

    2/6

    Page 2 of 6 TFP356

    FIGURE 1QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3133) AND PENDENT (TY3231) SPRINKLERS

    INTERMEDIATE LEVEL SPRINKLERS, 5.6 K-FACTOR, 1/2 INCH NPT

    * Temperature rating is indicated on the deflector, shield, or adjacent to orifice seat on frame.**Pipe thread connections per ISO 7/1 can be provided on special request.

    * Temperature rating is indicated on the deflector, shield, or adjacent to orifice seat on frame.**Pipe thread connections per ISO 7/1 can be provided on special request.

    FIGURE 1QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4133) AND PENDENT (TY4231) SPRINKLERS

    INTERMEDIATE LEVEL SPRINKLERS, 8.0 K-FACTOR, 3/4 INCH NPT

    SCREWSHIELD

    UPRIGHTSHIELD

    MODEL S2SHIELD

    (FIELD ASSEMBLED - SEE INSTALLATION SECTION)

    2-3/16"(55,6 mm)

    PENDENT

    WRENCHINGFLATS

    NOMINAL MAKE-IN7/16" (11,1 mm) 1/2"

    NPT

    O-RING

    (60,3 mm)

    (FACTORY ASSEMBLED)

    UPRIGHT

    1/2"NPT

    (11,1 mm)

    MAKE-INNOMINAL

    7/16"

    2-3/8"

    3-1/2" (88,9 mm) DIA,

    FLATSWRENCHING

    **

    3-1/2" (88,9 mm) DIA, **

    *

    3/4"NPT

    **

    SHIELDUPRIGHT

    NOMINAL MAKE-IN1/2" (12,7 mm)

    WRENCHINGFLATS

    3/4"NPT

    O-RING

    (61,9 mm)

    1/2"

    NOMINALMAKE-IN

    (12,7 mm) 2-7/16"(58,7 mm)2-5/16"

    WRENCHINGFLATS

    SHIELDSCREW

    3-1/2" (88,9 mm) DIA,

    3-1/2" (88,9 mm) DIA,

    SHIELDMODEL S2

    **

    *

    (FIELD ASSEMBLED - SEE INSTALLATION SECTION)PENDENT

    (FACTORY ASSEMBLED)UPRIGHT

  • 7/30/2019 Upright and Pendent Intermediate Level Sprinkler, Quick Response

    3/6

    TFP356 Page 3 of 6

    TYPE TEMP. BULB

    LIQUID

    NATURAL

    BRASS***

    135F/57C

    286F/141C

    UPRIGHT

    (TY3133)

    SPRINKLER FINISH (See Note 5)

    1, 2, 3, 4

    Orange

    Red

    Yellow

    Green

    Blue

    155F/68C

    175F/79C

    200F/93C

    NOTES:1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response.2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response.3. Approved by Factory Mutual Research Corporation (FM) as Quick Response.4. Approved by the City of New York under MEA 354-01-E.5. Where Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as a Corrosion Resistant

    Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion ResistantSprinklers.

    *** With Zinc Plated Shield.N/A: Not Available

    TABLE ALABORATORY LISTINGS AND APPROVALS

    LEAD

    COATED

    1, 2, 3, 4

    K

    5.6

    1/2"

    NPT

    PENDENT

    (TY3231)

    135F/57C Orange

    155F/68C Red

    175F/79C Yellow

    200F/93C Green

    286F/141C Blue

    1, 2, 3, 4 N/A

    8.0

    3/4"

    NPT

    UPRIGHT

    (TY4133)

    PENDENT

    (TY4231)

    135F/57C

    155F/68C

    175F/79C

    200F/93C

    286F/141C

    135F/57C

    155F/68C

    175F/79C

    200F/93C

    286F/141C Blue

    Green

    Yellow

    Red

    Orange

    Blue

    Green

    Yellow

    Red

    Orange

    1, 2, 3, 4 1, 2, 3, 4

    N/A1, 2, 3, 4

  • 7/30/2019 Upright and Pendent Intermediate Level Sprinkler, Quick Response

    4/6

    Physical CharacteristicsFrame . . . . . . . . . . . . . BronzeButton . . . . . . . . . Brass/CopperSealing Assembly . . . . . . . . . .

    . . . . . Beryllium Nickel w/TeflonBulb . . . . . . . . . . . . . . . GlassCompression Screw . . . . . BronzeDeflector . . . . . . . . . . . CopperShield . . . . . . . . . . Plated Steel

    OperationThe glass Bulb contains a fluid whichexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatter theglass Bulb, allowing the sprinkler toactivate and water to flow.

    Design

    CriteriaThe Series TY-FRB Pendent and Up-right Intermediate Level Sprinklers areintended for fire protection systemsdesigned in accordance with thestandard installation rules recognizedby the applicable Listing or Approvalagency (e.g., UL Listing is based onthe requirements of NFPA 13, and FMApproval is based on the requirementsof FMs Loss Prevention Data Sheets).

    InstallationThe Series TY-FRB Sprinklers must beinstalled in accordance with the follow-ing instructions:

    NOTESDo not install any bulb type sprinkler ifthe bulb is cracked or there is a loss ofliquid from the bulb. With the sprinklerheld horizontally, a small air bubbleshould be present. The diameter of theair bubble is approximately 1/16 inch(1,6 mm) for the 135F/57C to 3/32inch (2,4 mm) for the 286F/141Ctemperature ratings.

    A leak tight 1/2 inch NPT sprinkler jointshould be obtained with a torque of 7to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-mum of 21 ft. lbs. (28,5 Nm) of torquemay be used to install sprinklers with1/2 NPT connections. A leak tight 3/4inch NPT sprinkler joint should be ob-tained with a torque of 10 to 20 ft.lbs.(13,4 to 26,8 Nm). A maximum of 30ft.lbs. (40,7 Nm) of torque is to be usedto install sprinklers with 3/4 NPT con-nections. Higher levels of torque maydistort the sprinkler inlet and causeleakage or impairment of the sprinkler.

    Upright Sprinklers The Series TY-FRB Intermediate LevelUpright Sprinklers must be installed inaccordance with the following instruc-tions.

    Step 1. With pipe thread sealant ap-plied to the pipe threads, hand tighten

    the sprinkler into the sprinkler fitting.Step 2. Tighten the sprinkler into thesprinkler fitting using only the W-Type6 Sprinkler Wrench (Ref. Figure 3).With reference to Figure 1 or 2, theW-Type 6 Sprinkler Wrench is to beapplied to the wrench flats.

    Pendent Sprinklers The Series TY-FRB Intermediate LevelPendent Sprinklers must be installedin accordance with the following in-structions.

    Step 1. Thread the S2 Shield onto thesprinkler threads with the stamped

    markings toward the deflector and just

  • 7/30/2019 Upright and Pendent Intermediate Level Sprinkler, Quick Response

    5/6

    specting from the floor level, a randomsampling of close-up visual inspec-tions should be made, so as to betterdetermine the exact sprinkler condi-tion and the long term integrity of thecorrosion resistant coating, as it maybe affected by the corrosive conditionspresent.

    The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association (e.g., NFPA 25), inaddition to the standards of any otherauthorities having jurisdiction. The in-stalling contractor or sprinkler manu-facturer should be contacted relative toany questions.

    It is recommended that automaticsprinkler systems be inspected,

    tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcode.

    LimitedWarrantyProducts manufactured by Tyco FireProducts are warranted solely to theoriginal Buyer for ten (10) years

    against defects in material and work-manship when paid for and properlyinstalled and maintained under normaluse and service. This warranty will ex-pire ten (10) years from date of ship-ment by Tyco Fire Products. No war-ran ty i s g iven for p roducts orcomponents manufactured by compa-nies not affiliated by ownership withTyco Fire Products or for products andcomponents which have been subjectto misuse, improper installation, corro-sion, or which have not been installed,maintained, modified or repaired in ac-cordance with applicable Standards ofthe National Fire Protection Associa-

    tion, and/or the standards of any otherAuthorities Having Jurisdiction. Mate-rials found by Tyco Fire Products to bedefective shall be either repaired orreplaced, at Tyco Fire Products soleoption. Tyco Fire Products neither as-sumes, nor authorizes any person toassume for it, any other obligation inconnection with the sale of products orparts of products. Tyco Fire Productsshall not be responsible for sprinklersystem design errors or inaccurate orincomplete information supplied byBuyer or Buyers representatives.

    IN NO EVENT SHALL TYCO FIREPRODUCTS BE LIABLE, IN CON-TRACT, TORT, STRICT LIABILITY ORUNDER ANY OTHER LEGAL THE-ORY, FOR INCIDENTAL, INDIRECT,SPECIAL OR CONSEQUENTIALDAMAGES, INCLUDING BUT NOTLIMITED TO LABOR CHARGES, RE-GARDLESS OF WHETHER TYCOFIRE PRODUCTS WAS INFORMEDABOUT THE POSSIBILITY OF SUCHDAMAGES, AND IN NO EVENTSHALL TYCO FIRE PRODUCTS LI-ABILITY EXCEED AN AMOUNTEQUAL TO THE SALES PRICE.

    THE FOREGOING WARRANTY ISMADE IN LIEU OF ANY AND ALL

    OTHER WARRANTIES EXPRESSORIMPLIED,INCLUDING WARRANTIESOF MERCHANTABILITY AND FIT-NESS FOR A PARTICULAR PUR-POSE.

    OrderingProcedureWhen placingan order, indicate the fullproduct name. Refer to the Price Listfor complete listing of Part Numbers.

    Contact your local distr ibutor for avail-ability.

    Upright Sprinkler Assemblies withShield and NPT ThreadConnections:Specify: (Specify Model/SIN), QuickResponse, (specify K-factor), (specifytemperature rating), Series TY-FRBUpright Intermediate Level Sprinklerwith (specify type of finish or coating),P/N (specify from Table B).

    Pendent Sprinkler Assemblies with(Shield Ordered Separately) and

    NPT Thread Connections:Specify: (Specify Model/SIN), QuickResponse, (specify K-factor), (specifytemperature rating), Series TY-FRBPendent Sprinkler with (specify type offinish or coating), P/N (specify fromTable C)

    Model S2 Pendent Shield & O-Ring:Specify: S2 Pendent Shield & O-Ringfoe use with (specify 1/2" NPT or 3/4"NPT) Series TY-B Pendent Sprinklers,P/N (specify).

    1/2" NPT S2Pendent Shield& O-Ring . . . . . . . . . . . . . . P/N 56-070-9-332

    3/4" NPT S2Pendent Shield

    & O-Riing . . . . . . . . . . . . . . P/N 56-070-9-342

    Sprinkler Wrench:Specify: W-Type 6 Sprinkler Wrench,P/N 56-000-6-387.

    TFP356 Page 5 of 6

  • 7/30/2019 Upright and Pendent Intermediate Level Sprinkler, Quick Response

    6/6

    Page 6 of 6 TFP356

    P/N 57 XXX X XXX

    155F/68C155

    TEMPERATURE

    RATING

    135F/57C135

    1

    SPRINKLER

    TABLE BPART NUMBER SELECTION

    SERIES TY-FRB UPRIGHT INTERMEDIATE LEVEL SPRINKLERS

    (UPRIGHT SHIELD INCLUDED WITH SPRINKLER)

    175F/79C

    286

    200F/93C200

    286F/141C

    175

    NATURAL BRASS

    MODEL/SIN

    7 LEAD COATED343 8.0K UPRIGHT (3/4"NPT)

    333 5.6K UPRIGHT (1/2"NPT) TY3133

    TY4133

    P/N 57 XXX X XXX

    155F/68C155

    TEMPERATURE

    RATING

    135F/57C135

    1

    SPRINKLER

    TABLE CPART NUMBER SELECTION

    SERIES TY-FRB PENDENT SPRINKLERS(MODEL S2 PENDENT SHIELD & O-RING MUST BE SEPARATELY ORDERED)

    175F/79C

    286

    200F/93C200

    286F/141C

    175

    NATURAL BRASS

    MODEL/SIN

    7 LEAD COATED391 8.0K PENDENT (3/4"NPT)

    371 5.6K PENDENT (1/2"NPT) TY3231

    TY4231

    TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446