unsymmetrical faults in power system

75
POWER SYSTEM ENGINEERING CE00603-3 UNIT- II Unbalanced System Analysis

Upload: erramansaini1947

Post on 14-Apr-2017

533 views

Category:

Engineering


57 download

TRANSCRIPT

Page 1: UNSYMMETRICAL FAULTS IN POWER SYSTEM

POWER SYSTEM ENGINEERING

CE00603-3

UNIT- IIUnbalanced System Analysis

Page 2: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Contents

• Introduction• Symmetrical Faults on 3-Phase System• Percentage Reactance and Base KVA• Steps for Symmetrical Fault Calculations• Unsymmetrical Faults on 3-Phase system• Significance of Positive, Negative and Zero sequence

components• Average three phase power in terms of symmetrical

components• Sequence impedances• Single Line-to-Ground Fault• Line-to-Line Faults • Double Line-to-Ground Faults

Slide 2 of 11

Page 3: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Introduction

Short-Circuit “Whenever a fault occurs on a network such that a

large current flows in one or more phases, a short circuit is said to have occurred”.

Causes of short-circuit (i) Internal effects are caused by breakdown of

equipment or transmission lines, from deterioration of insulation in a generator, transformer etc. Such troubles may be due to ageing of insulation, inadequate design or improper installation.

(ii) External effects causing short circuit include insulation failure due to lightning surges, overloading of equipment causing excessive heating; mechanical damage by public etc.

Slide 3 of 11

Page 4: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Effects of short-circuit

• When a short-circuit occurs, the current in the system increases to an abnormally high value while the system voltage decreases to a low value.

• Short-circuit causes excessive heating which may result in fire or explosion. Sometimes short-circuit takes the form of an arc and causes considerable damage to the system

• Low voltage created by the fault has a very harmful effect on the service rendered by the power system. If the voltage remains low for even a few seconds, the consumers’ motors may be shut down and generators on the power system may become unstable.

Slide 4 of 11

Page 5: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Short-Circuit Current Calculations

The calculations of the short-circuit currents are important for the following reasons:

(i) A short-circuit on the power system is cleared by a circuit breaker or a fuse. It is necessary, therefore, to know the maximum possible values of short-circuit current so that switchgear of suitable rating may be installed to interrupt them.

(ii) The magnitude of short-circuit current determines the setting and sometimes the types and location of protective system.

(iii) The magnitude of short-circuit current determines the size of the protective reactors which must be inserted in the system so that the circuit breaker is able to withstand the fault current.

(iv) The calculation of short-circuit currents enables us to make proper selection of the associated apparatus (e.g. bus-bars, current transformers etc.) so that they can withstand the forces that arise due to the occurrence of short circuits.

Slide 5 of 11

Page 6: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Faults in a Power System

• Symmetrical faults : That fault which gives rise to symmetrical fault currents (i.e. equal faults currents with 120o displacement) is called a symmetrical fault.

Example: when all the three conductors of a 3-phase line are brought together simultaneously into a short-circuit condition.

• Unsymmetrical faults: Those faults which give rise to unsymmetrical currents (i.e. unequal line currents with unequal displacement) are called unsymmetrical faults.

• Single line-to-ground fault • Line-to-line fault • Double line-to-ground fault

Common: a short-circuit from one line to ground

Slide 6 of 11

Page 7: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Symmetrical Faults on 3-Phase System

“That fault on the power system which gives rise to symmetrical fault currents (i.e. equal fault currents in the lines with 120o

displacement) is called a symmetrical fault”

• symmetrical fault rarely occurs in practice

• The symmetrical fault is the most severe and imposes more heavy duty on the circuit breaker

Slide 7 of 11

Page 8: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Limitation of Fault Current

• When a short circuit occurs at any point in a system, the short-circuit current is limited by the impedance of the system up to the point of fault

• The knowledge of the impedances of various equipment and circuits in the line of the system is very important for the determination of short-circuit currents

Slide 8 of 11

Page 9: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Percentage Reactance

Slide 9 of 11

Page 10: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Conclusion

• For instance, if the percentage reactance of an element is 20% and the full-load current is 50 A, then short-circuit current will be 50 × 100/20 = 250 A when only that element is in the circuit.

• It may be worthwhile to mention here the advantage of using percentage reactance instead of ohmic reactance in short-circuit calculations. Percentage reactance values remain unchanged as they are referred through transformers, unlike ohmic reactances which become multiplied or divided by the square of transformation ratio. This makes the procedure simple and permits quick

calculations.

Slide 10 of 11

Page 11: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Percentage Reactance and Base kVA

Slide 11 of 11

Page 12: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 12 of 11

Page 13: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 13 of 11

Page 14: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 14 of 11

Page 15: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Short-Circuit kVA

Slide 15 of 11

Page 16: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Reactor Control of Short-Circuit Currents

• With the fast expanding power system, the fault level (i.e. the power available to flow into a fault) is also rising

• The circuit breakers connected in the power system must be capable of dealing with maximum possible short-circuit currents that can occur at their points of connection

• Generally, the reactance of the system under fault conditions is low and fault currents may rise to a dangerously high value

• If no steps are taken to limit the value of these short-circuit currents, not only will the duty required of circuit breakers be excessively heavy, but also damage to lines and other equipment will almost certainly occur

• Solution: additional reactance's known as reactors are connected in series with the system at suitable points

• A reactor is a coil of number of turns designed to have a large inductance as compared to its ohmic resistance

Slide 16 of 11

Page 17: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 17 of 11

Page 18: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Steps for Symmetrical Fault Calculations

Slide 18 of 11

Page 19: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 1

• Fig. shows the single line diagram of a 3-phase system. The percentage reactance of each alternator is based on its own capacity. Find the short-circuit current that will flow into a complete 3-phase short-circuit at F

Slide 19 of 11

Page 20: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Slide 20 of 11

Page 21: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 2

• A 3-phase, 20 MVA, 10 kV alternator has internal reactance of 5% and negligible resistance. Find the external reactance per phase to be connected in series with the alternator so that steady current on short-circuit does not exceed 8 times the full load current.

Slide 21 of 11

Page 22: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Slide 22 of 11

Page 23: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 23 of 11

Page 24: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 24 of 11

Page 25: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 25 of 11

Page 26: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 26 of 11

Page 27: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Operator ‘a’

Slide 27 of 11

Page 28: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 28 of 11

Page 29: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Symmetrical Components in Terms of Phase Currents

Slide 29 of 11

Page 30: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 30 of 11

Page 31: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 31 of 11

Page 32: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 32 of 11

Page 33: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 1

In a 3-phase, 4-wire system, the currents in R, Y and B lines under abnormal conditions of loading are as under:

IR = 100 ∠30º A ; IY = 50 ∠300º A ; IB = 30 ∠180º A Calculate the positive, negative and zero sequence

currents in the R-line and return current in the neutral wire.

Page 34: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 35: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 2

The currents in a 3-phase unbalanced system are :IR = (12 + j 6) A ; IY = (12 − j 12) A ; IB = (−15 + j 10) AThe phase sequence is RYB. Calculate the zero, positive

and negative sequence components of the currents.

Slide 35 of 11

Page 36: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Slide 36 of 11

Page 37: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 37 of 11

Page 38: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 3

The sequence voltages in the red phase are as under :ER0 = 100 V ; ER1 = (200 − j 100) V ; ER2 = − 100 VFind the phase voltages ER ,EY and EB .

Slide 38 of 11

Page 39: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Slide 39 of 11

Page 40: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 4

A balanced star connected load takes 90 A from a balanced 3-phase, 4-wire supply. If the fuses in the Y and B phases are removed, find the symmetrical components of the line currents

(i) before the fuses are removed (ii) after the fuses are removed

Slide 40 of 11

Page 41: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Slide 41 of 11

Page 42: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 42 of 11

Page 43: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 43 of 11

Page 44: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 44 of 11

Page 45: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 5

Slide 45 of 11

Page 46: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Slide 46 of 11

Page 47: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2Slide 47 of 11

Page 48: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Sequence Impedances

Each element of power system will offer impedance to different phase sequence components of current which may not be the same. Therefore, in unsymmetrical fault calculations, each piece of equipment will have three values of impedance—one corresponding to each sequence current viz.

 (i) Positive sequence impedance (Z1)(ii) Negative sequence impedance (Z2)(iii) Zero sequence impedance (Z0)

Slide 48 of 11

Page 49: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 49 of 11

Page 50: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Analysis of Unsymmetrical Faults

In the analysis of unsymmetrical faults, the following assumptions will be made :

(i) The generated e.m.f. system is of positive sequence only.

(ii) No current flows in the network other than due to fault i.e. load currents are neglected.

(iii) The impedance of the fault is zero.(iv) Phase R shall be taken as the reference phase.

In each case of unsymmetrical fault, e.m.fs’ per phase are denoted by ER, EY and EB and the terminal p.d. per phase by VR, VY and VB.

Slide 50 of 11

Page 51: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Single Line-to-Ground Fault

Page 52: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 53: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 54: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 55: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Line-to-Line Fault

Slide 55 of 11

Page 56: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 57: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 58: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 59: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Double Line-to-Ground Fault

Page 60: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 61: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 62: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Observations on Faults

• Positive sequence currents are present in all type of faults

• Negative sequence currents are present in all unsymmetrical faults

• Zero sequence currents are present when the neutral of the system is grounded and faults also involves the ground and magnitude of the neutral current is equal to 3IR0

Slide 62 of 11

Page 63: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 1

A 3-phase, 10 MVA, 11 kV generator with a solidly earthed neutral point supplies a feeder. The relevant impedances of the generator and feeder in ohms are as under :

Generator feederPositive sequence impedance j 1·2 j 1·0Negative sequence impedance j 0·9 j 1·0Zero sequence impedance j 0·4 j 3·0

If a fault from one phase to earth occurs on the far end of the feeder, calculate(i) the magnitude of fault current(ii) line to neutral voltage at the generator terminal

Page 64: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Page 65: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 66: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 2

A 3-phase, 11 kV, 25 MVA generator with X0 = 0·05 p.u., X1 = 0·2 p.u. and X2= 0·2 p.u. is grounded through a reactance of 0·3 Ω. Calculate the fault current for a single line to ground fault.

Page 67: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Page 68: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Page 69: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 3 Two 11 KV, 12 MVA, 3f, star connected generators operate in parallel. The positive, negative and zero sequence reactance's of each being j0.09, j0.05 and j0.04 pu respectively. A single line to ground fault occurs at the terminals of one of the generators. Estimate (i) the fault current (ii) current in grounding resistor (iii) voltage across grounding resistor.

Slide 69 of 11

Page 70: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 70 of 11

Page 71: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2 Slide 71 of 11

Page 72: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Example 4

• A 50 MVA, 11 kV three-phase alternator was subjected to different types of faults. The fault currents are as under :

3-phase fault = 2000 A ; Line-to-Line fault = 2600 A ; Line-to-ground fault = 4200 A

The generator neutral is solidly grounded. Find the values of the

three sequence reactance's of the alternator. Ignore resistances.

Slide 72 of 11

Page 73: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Solution

Slide 73 of 11

Page 74: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2Slide 74 of 11

Page 75: UNSYMMETRICAL FAULTS IN POWER SYSTEM

Signal Processing, CE00039-2

Any Queries?

Slide 75 of 11