UDC1000 & UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 11/98 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1000 & UDC 1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers which combine a high degree of functionality and reliability at low cost. They are fully dedicated to monitor and control temperatures, pressures and levels in a wide range of applications such as the plastics and food industries, furnaces, packaging and environmental chambers. The large and easy-to-read dual 4-digit display and tactile keypad make the UDC 1000 and UDC 1500 easy to configure and use. Their outstanding flexibility enables you to configure any unit for any application and change it if required. FEATURES Dual Display Two 4-digit displays with 7 LED segments, each configurable for : PV & SP (non adjutable) PV & SP (adjutable) PV & Ramping SP PV only Easy to configure Two different configuration levels (configuration mode and set-up mode) provide easy access to parameters. A 4-digit security code prevents unauthorized changes. Moisture resistant front-face Meets NEMA 3 / IP65 front-face protection against dust and water. Universal input Accepts seven different types of thermocouples, RTD’s, current and volt linear inputs. All inputs are configurable as standard. Universal power supply The UDC 1000 & UDC 1500 can operate on any line voltage from 90 Vac to 264 Vac at 50/60 Hz continuously. A 24/48 Vac/dc model is available as an option. Easy output selection and upgrade With only two basic modules (current and relay output) and plug-in options, you can configure the controller as you want for a wide range of applications. Up to three outputs The UDC 1000 & UDC 1500 provide up to three outputs for time and current proportioning, duplex mode (heat/cool), PV or SP retransmission, and alarms. Alarm strategy Two soft alarms on PV, deviation high/low/absolute. A special loop alarm is also provided to detect faults in the control loop by continuously analyzing the PV response to the control output. Alarm inhibit is available on power up and setpoint switching. Manual/Automatic mode Manual control (via bumpless transfer) is enabled by simply pressing the front-face AUTO/MAN key. The “SET” LED flashes and the output power is displayed on the lower display. Output can be adjusted with the upper and lower keys. Pre-tuning and self-tuning strategy Pre-tuning is used to set up the PID paramaters close to the optimum values which might be used by the self-tuning algorithm to subsequently optimize the tuning parameters. Limit Controller Packaged in 1/16DIN, the UDC 1000 limit controller is designed to provide a safety cut-out and optional alarms for use in a wide variety of applications.

Upload: lethu

Post on 11-May-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

UDC1000 & UDC 1500MICRO-PRO SERIES

UNIVERSAL DIGITAL CONTROLLERSEN0I-6041 11/98 PRODUCT SPECIFICATION SHEET

OVERVIEWThe UDC1000 & UDC 1500 aremicroprocessor-based 1/16 DIN and1/8 DIN controllers which combine ahigh degree of functionality andreliability at low cost.They are fully dedicated to monitor andcontrol temperatures, pressures andlevels in a wide range of applicationssuch as the plastics and foodindustries, furnaces, packaging andenvironmental chambers. The largeand easy-to-read dual 4-digit displayand tactile keypad make the UDC1000 and UDC 1500 easy to configureand use. Their outstanding flexibilityenables you to configure any unit forany application and change it ifrequired.

FEATURESDual DisplayTwo 4-digit displays with 7 LEDsegments, each configurable for :� PV & SP (non adjutable)� PV & SP (adjutable)� PV & Ramping SP� PV only

Easy to configureTwo different configuration levels(configuration mode and set-up mode)provide easy access to parameters. A4-digit security code preventsunauthorized changes.

Moisture resistant front-faceMeets NEMA 3 / IP65 front-faceprotection against dust and water.

Universal inputAccepts seven different types ofthermocouples, RTD’s, current andvolt linear inputs. All inputs areconfigurable as standard.

Universal power supplyThe UDC 1000 & UDC 1500 canoperate on any line voltage from 90Vac to 264 Vac at 50/60 Hzcontinuously. A 24/48 Vac/dc model isavailable as an option.

Easy output selection andupgradeWith only two basic modules (currentand relay output) and plug-in options,you can configure the controller as youwant for a wide range of applications.

Up to three outputsThe UDC 1000 & UDC 1500 provideup to three outputs for time and currentproportioning, duplex mode(heat/cool), PV or SP retransmission,and alarms.

Alarm strategyTwo soft alarms on PV, deviationhigh/low/absolute. A special loop alarmis also provided to detect faults in thecontrol loop by continuously analyzingthe PV response to the control output.Alarm inhibit is available on power upand setpoint switching.

Manual/Automatic modeManual control (via bumpless transfer)is enabled by simply pressing thefront-face AUTO/MAN key. The “SET”LED flashes and the output power isdisplayed on the lower display. Outputcan be adjusted with the upper andlower keys.

Pre-tuning and self-tuningstrategyPre-tuning is used to set up the PIDparamaters close to the optimumvalues which might be used by theself-tuning algorithm to subsequentlyoptimize the tuning parameters.

Limit ControllerPackaged in 1/16DIN, the UDC 1000limit controller is designed to provide asafety cut-out and optional alarms foruse in a wide variety of applications.

Page 2: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

EN0I-6041 11/982

Setpoint rampAccording to a defined ramp rate, theSP ramps the current setpoint to thenew targeted setpoint.

Dual SetpointDual setpoint option is available on theUDC 1000 & UDC 1500. The currentsetpoint is selected by a digital input.This option is exclusive with UDC 1000limit model remote alarm reset.

CommunicationAn optional RS485 communicationsinterface is available on the UDC 1000& UDC 1500. It provides a link betweenup to 32 units and a host computerthrough ASCII or Modbus RTU protocolat up to 9600 baud.

Highly secureA non-volatile memory based onEEPROM technology ensures dataintegrity during loss of power supply,with retention of more than 100 years.The design is centered around a batteryconcept. A 4-digit security codeprevents unauthorized or accidentalchange.

OPTIONAL FEATURESThe following can be selected via theModel selection Guide (see page 7) :� RS485 ASCII communication� RS485 Modbus RTU

communication� Dual setpoint� Output 2� Output 3

PHYSICAL DESCRIPTIONThe UDC 1000 controller is housed in a110 mm (4.33 inches) deep case withthe standard UDC grey bezel. It can bemounted in a 1/16 DIN panel cutout.The UDC 1500 controller is housed in a100 mm (3.94 inches) deep case andcan be mounted in a 1/8 DIN panelcutout.By using the pre-assembledmounting fixture delivered with the unit,you can easily and securely install thecontroller into the panel cutout. Modularplug-in construction allows rapid accessand saves time. All inputs and outputsare connected on the rear terminalblock by screws.

OPERATOR INTERFACEFour display combinations are offeredto the operator. The upper 4-digit 7-segment display is always dedicated tomonitor the PV. The lower display canshow :� SETPOINT (read only)� SETPOINT (adjustable)� RAMPING setpoint (ramp mode)� BLANK

Page 3: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

EN0I-6041 11/98 3

UNIVERSAL INPUTSAll input types are available on anyunit. By positioning a jumper on theCPU board, the thermocouples, RTD’sor linear input families can be fieldselected. Selection among the varioustypes of inputs is made by promptconfiguration. As soon as the ProcessVariables reaches a value of the inputrange limits, the controller displays amessage. A sensor break indication isalso provided. A configurable digitalfilter is available from 0.5 sec. to 100.0sec.

OUTPUTSThree types of outputs (RELAY, SSRdriver or DC linear) are selectable forthree outputs, through the modelselection guide or by adding a plug-inmodule for outputs 2 and 3.

OUTPUTS ALGORITHMSThe UDC 1000 & UDC 1500 areavailable with the following outputalgorithms :� Time proportional :

ON/OFF or time proportional withelectromechanical relay SPDT 2Aor SSR driver (open collector).

� Current proportional :Supply directly proportionalcurrent or volt signal to the finalcontrol elements which require 0-20 mA, 4-20 mA, 0-10 V or 0-5 V.

� Time proportional duplex :Three duplex modes can beselected, either ON/OFF duplex ortime proportional duplex(heat/coolwith two proportional bands, twocycle times and deadband) orTPSC.

� Current proportional duplex :In addition to the first current/voltoutput, provides a second similaroutput with its own proportionalband.

� Current/Time or Time/Currentduplex :Provides a variation of traditionaltime or current duplex mode bymixing current and timeproportioning together.

CONTROL ALGORITHMSFour control algorithms can be set upthrough the configuration menu :� On/Off � PID� PD + MR � TPSCThe TPSC (Three Position StepControl) control algorithm isdedicated to control valve positioningwithout slidewire feedback from themotor shaft.

CONFIGURATIONThere are two levels of configuration.The SET-UP mode allows modificationof current parameters such as tuningparameters, alarm values, setpointlimit, ramp enable, auto-manual modeenable; auto-pretune enable.The CONFIGURATION mode is moreoriented to unit personality : inputselection, output 2 & 3 usage, alarmtype, communication address, lockoutcode, hardware definition coding.

CONTROL MODEManual or automatic mode withbumpless transfer is standard feature.In manual mode, the operator candirectly control the output through thetwo front face keys (raise and lowerkeys). The output value is monitoredon the lower display.

ALARMSOutputs 2 and 3 can be used asalarms. Two electromechanical singlepole double throw relays can activateexternal equipment when alarmsetpoints are reached. An LED is alsoactivated on the front-face. A direct orreverse acting alarm output can beconfigured. A logical combination ofthe two alarms : OR, AND orhysteresis (active when both alarmsare active, becomes inactive whenboth alarms are inactive) can be setwhich associates the two alarms statusbefore energizing the relay. In order todetect a defective control loop, thecontroller can supply a special loopalarm control by continually monitoringthe PV response to output demand. Atimer is automatically set up when anyoutput is on saturation mode. Whenthe timer reaches twice the reset timewith no PV response, then the loopalarm is activated. With this soft alarm,there is no need for a heater breaker,saving wiring time and costs.

DISPLAYDual, four digit LED display withdecimal point location configurable upto three places for linear ranges only.

LIMIT CONTROLLERThe UDC 1000 1/16 DIN limitcontroller provides a latched relayoutput which is activated whenprocess parameters either exceed orfall bellow the desired value, providinga fail safe cut-off which has to bemanually re-set before the process cancontinue.

The UDC 1000 limit controller can beconfigured to be either a “high limit”unit where the delay will de-energizewhen the PV is above the limitsetpoint, or a “low limit” where therelay will drop out when the PV fallsbelow the setpoint.

LED indication shows when limits havebeen exceeded, and when the relay islatched out.

Page 4: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

EN0I-6041 11/984

SPECIFICATIONS (Apply to both UDC 1000 and UDC 1500)

Technical data

Accuracy 0.25% of span ± 1 LSD

Temperature Stability 0.01% of span per ºC

Input Signal Failure Fail-safe output value : Achieved when burnout is detectedValue depends on configurationFor thermocouple and mV input detected by any lead break :Upscale burnoutFor RTD: burnout detected by any lead breakCurrent or volt input : Burnout set by open circuit detection

Input Impedance Volt impedance : 47 KohmsCurrent input : 4.7 ohmsAll others : 100 Mohms

Input Sampling Rate Four samples per second

Input Filter Digital filter configurable from front panel0.0 (Off), from 0.5s to 100.0 seconds in 0.5s increment

Input Resolution 14 bits approximately, always four times better than display resolution

Input Isolation Universal input isolated at 2500 V from all outputs except SSR and frompower supply

Stray Rejection Common mode rejection : > 120 dB at 50/60 HzSerial mode rejection : > 500% of span at 50/60 Hz

Approvals UL pendingFM approval pending on the UDC 1000 limit modelProduct design to meet CE MARK requirement

Control Output type Type available :Output 1 : DC, Electromechanical relay, SSR drive (open collector)Output 2 : DC, Electromechanical relay, SSR drive (open collector)Output 3 : DC (transmission output only), Electromechanical relay, SSR drive (open collector)DC output :0-20 mA, 4-20 mA, 0-5 V, 0-10 VAccuracy : ± 0.5% (250 ohms for mA, 2 Kohms for volt)Resolution : 80bits in 250 ms (10 bits in 1 second typical > 10 bits in > 1second)Load impedance : 500 ohms max. for current output, 500 ohms min. forvolt outputIsolation : isolated 2500 V from all other inputs and outputsRange selection method : jumper positioning and front panel code settingTemperature stability : 0.01% / °CElectromechanical relay : SPDT contact Resistive load : 2A at 120 V or 240 V Life time : > 500000 operations at rated voltage/currentSSR drive/TTL :Drive capability : SSR > 4.3 V dc into 250 ohms min.Isolation : not isolated from input and other SSR output

Page 5: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

EN0I-6041 11/98 5

Alarms Maximum number of alarms : 2 soft alarms setpoint + 1 loop alarmAlarm inhibit available on power up and setpoint switchingAlarm output : up to two relays or SSR output on output 2 and 3Types : PV high or low, band, deviation high or low, loopCombination alarms : Logical “OR”, “AND” or hysteresis of alarms available toindividual hardware output

Loop control Automatic tuning type : Pre-tune & self-tuneProportional bands : 0 (inactive), 0.5 % to 999.9 % of input span with 0.1%increments. Two proportional bands available for duplex modeReset : Off or from 1s to 99 min.59sRate : from 0 to 99 min.59sManual reset : from 0 to 100 % of output (single output), from –100% to 100ùof output (dual output)Deadband : ± 20 of PB1+PB2ON/OFF hysteresis : 0.1% to 10.0% of input spanAuto/manual mode : Front key selectable with bumpless transfer betweenautomatic and manual modeCycle times : Up to two cycle times available for time duplex controlSelection : 0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256, or 512 secondsSetpoint ramp : From 1 to 9999 engineering units per hour

Retransmission Output Current and volt output of output 3 can be selected to retransmit the processvalue or setpoint

Communication Interface RS485 – ASCII or Modbus RTUBaud rate : 1200, 2400, 4800 or 9600 baudLink characteristics : 32 drops maximum, ASCII or Modbus protocols, twowires

Mounting Plug-in with pre-assembled mounting fixture

Wiring Connection Screw terminals on the rear of the case (combination head)

Power Consumption 4 WPhysical (UDC 1000) Weight : 210 grams max.

Height : 48 mm / 1.89 inchesWidth : 48 mm / 1.89 inchesDepth : 110 mm / 4.33 inchesCut out : 45 mm x 45 mm / 1.77 x 1.77 inches

Physical (UDC 1500) Weight : 250 grams max.Height : 96 mm / 3.78 inchesWidth : 48 mm / 1.89 inchesDepth : 100 mm / 3.94 inchesCut out : 45 mm x 92 mm / 1.77 x 3.62 inches

Environmental EMI Susceptibility : Designed to meet EN55101EMI Emission : Designed to meet EN55022Safety Considerations : Designed to comply with IEC1010-1as far asapplicable

Front Panel sealing NEMA 3 / IP65

Page 6: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

EN0I-6041 11/986

Input Actuations

Ranges

Thermocouple types °F °C(Fixed decimal) R 32 – 3002 0 – 1650

SJJJTTKK

32 – 300032.0 – 401.7

32 – 84232 – 1401-328 – 50332 – 501.0

-328 – 1399-328 – 2503

0 – 16490.0 – 205.4

0 – 4500 – 761

-200 – 2620.0 – 260.6–200 – 760-200 – 1373

LLL

32 – 402.232 – 84132 – 1403

0.0 - 205.70 – 4500 - 762

B 211 - 3315 100 – 1824N 32 - 2550 0 – 1399

RTD : (3 wires connection)PT100 (IEC) α = 0.00385 32 - 1471 0 – 800(Fixed decimal) 32 - 571 0 – 300

-149.7 – 211.932 – 213.6-328 – 402

-149.7 – 999.1

-100.9 – 100.00.0 – 100.9-200 – 206

-100.9 – 537.3

DC linear :10 - 50 mV 0 - 50 mV4 - 20 mA

1 - 5 V0 - 20 mA

0 – 5 V2 - 10 V 0 – 10 V

Operating Conditions

ReferenceConditions

OperativeLimits

Transportation andStorage

AmbientTemperature

20°C ± 2°C

(68°F ± 4°F)

0°C to 55°C

(32°F to 131°F)

-20°C to 80°C

(-4°F to 176°F)

RelativeHumidity

60 - 70 % 20 - 95 % non -condensing

Voltage 90–264 vac ± 1 % 90-264 Vac

Frequency 50 Hz 50 - 60 Hz

Source resistance < 10 ohms forthermocouple

1000 ohms max forthermocouple

Lead resistancefor RTD

< 0.1 ohm/lead(PT100)

50 ohms per leadmaximum balanced

Page 7: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

EN0I-6041 11/98 7

Model Selection Guide

Key NumberU D 1C

U

00

51CD 0

Table5

Table4

Table3

Table2

Table7

Table6

Table8

Table1

INPUT TYPE (Factory selected)

TABLE 1 : OUTPUT 1

TABLE 4 : OUTPUT 4

TABLE 3 : OUTPUT 3

1 RTD or linear mV2 Thermocouple3 Linear mA4 Linear VoltT TPSC modelL UDC 1000 limit model

1 Relay2 SSR driver3 Linear = 0-10 V4 Linear = 0-20 mA5 Linear = 0-5 V7 Linear = 4-20 mA

0 None1 Relay2 SSR driver3 Linear = 0-10 V4 Linear = 0-20 mA5 Linear = 0-5 V7 Linear = 4-20 mA

0 None1 Relay Alarm 1 only2 SSR driver3 Linear = 0-10 V4 Linear = 0-20 mA Retransmission5 Linear = 0-5 V only7 Linear = 4-20 mA

0 No selection1 RS485 ASCII serial communication2 Digital input (SP1/SP2 selection or UDC 1000 limit model remote reset)3 RS485 Modbus RTU communication

TABLE 6 : see price sheet

TABLE 8 : see price sheet

TABLE 7 : see price sheet

1 Power supply 90-264 Vac2 Power supply 24/48 Vac/dc

TABLE 5 : Option 2

TABLE 2 : OUTPUT 2

Page 8: UNIVERSAL DIGITAL CONTROLLERS - A. Hock MSR- …€¦ · UDC1000 & UDC 1500 MICRO-PRO SERIES ... Manual/Automatic mode ... Input Isolation Universal input isolated at 2500 V from

EN0I-6041 11/988

EXTERNAL DIMENSIONS, PANEL CUTOUT

HoneywellIndustrial Automation and ControlHoneywell Inc.http://europe.iac.honeywell.com

U.S.A. : Honeywell Industrial Automation and Control, 16404 North Black Canyon Hwy., Phoenix, AZ 85023Canada : The Honeywell Centre, 155 Gordon Baker Rd., North York, Ontario M2H 3N7Latin America : Honeywel Inc., 480 Sawgrass Corporate Parkway, Suite 200, Sunrise, Florida 33325Japan : Industrial Operations Tokyo, 4-28-1 Nishi-Rokugo Othu-ku, Tokyo 144, Japan,Asia : Honeywell Asia Pacific Inc., Room 3213-3225, Sun Hung Kai Centre, No. 30 Harbour Road, Wanchai, Hong KongPacific Division : Honeywell Pty Ltd., 5 Thomas Holt Drive, North Ryde NSW Australia 2113Northern Europe and Southern Africa : Honeywell Ltd., Honeywell House, Arlington Business Park, Bracknell, RG 12 1 EB, U.K.Central Europe : Honeywell A.G., Kaiserleistraße 39, 63067 Offenbach, GermanyWestern and Southern Europe : Honeywell S.A., Bourgetlann 1, 1140 Brussels, BelgiumEastern Europe : Honeywell Praha, s.r.o., Budejovicka1, 140 00 Prague 4, Czech RepublicMiddle East : Honeywell Middle East Ltd., Khalifa Street, Sheikh Faisal Building, Abu Dhabi, U.A.E.