ultraflow circulator pumps & systemsgeneralpumps.com.au/wp-content/...spec-booklet.pdf ·...
TRANSCRIPT
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
Ultraflow CirculatorPumps & Systems
TECHNICALMANUAL
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 1
UCV15-15B UCV15-15BTU UCF15-40B-130 UCF20-60B-150 UCV20-60B-150 UCF20-70B-150
UCV20-80B-150 UCF25-60B-180 UCV25-60B-180 UCF25-60CI-130 UCF32-80B-180 UCF32-80CI-180
Warmth –Efficiency –SatisfactionThe ‘ULTRAFLOW’UCF & UCV range ofcirculator pumpsrepresent quality,reliability andefficiency. Thesepumps are installed innumerous countries all over theworld. The ‘ULTRAFLOW’ circulatorpumps are the culmination of morethan 60 years of manufacturingexperience with productioncommencing in 1947. They areproduced with precision, in atechnologically advancedmanufacturing plant in the heart ofEurope. So you can be assured thatwhen you purchase and install an‘ULTRAFLOW’ circulator pump it is aproduct that has been tried andproven many, many times over!
Applications‘ULTRAFLOW’ circulator pumps areinstalled in closed loop pipelines orcircuits. These pumps circulate hotwater around the circuit minimisingany decrease in temperature at anypoint on the circuit. Commonapplications include:-
• Potable hot water in residential &commercial buildings.
• Underfloor closed loop heating
• Solar heating systems,
• Boiler shunt pumps
• Heat pump systems
• Geothermal heating systems
• Heat recovery systems
Features• Bronze or cast iron pump casings• Standard 3 speed electric motors
or variable speed high efficiencymotors
• Low noise• Maintenance free• Complete range
High Efficiency MotorsThe ‘ULTRAFLOW’ ‘UCV’ seriescirculator pumps are fitted with highefficiency variable speed electricmotors reducing energyconsumption to a minimum. Thesepumps have an ‘A’ energy efficiencyrating. The electric motor varies inspeed depending on the circulationrequired. When used in place of acirculator pump with a 3 speedstandard electric motor, energysavings of up to 60% can beachieved. This translates intosignificant cost savings for theconsumer.
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected] www.generalpumps.com.au P 1300 662 787 E [email protected]
Circulator Pumps
MADE INEUROPE
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 2
Max Max Full Port Connection Head Flow Casing Load to Port Temperature Max operating
Model Size (m) (L/min) Material Amps Dimension Range Pressure Weight
UCV15-15B 15mm (no union) 1.1 15 Bronze 0.1 65mm -5°C - 70°C 10 Bar 0.9 kg
UCV15-15BTU 15mm (no union) 1.1 15 Bronze 0.1 65mm -5°C - 70°C 10 Bar 1.0 kg
UCF15-40B-130 15mm 4.6 47 Bronze 0.33 130mm -10°C - 110°C 10 Bar 2.3 kg
UCF20-60B-150 20mm 5.8 55 Bronze 0.39 150mm -10°C - 110°C 10 Bar 2.3 kg
UCV20-60B-150 20mm 5.8 55 Bronze 0.4 150mm -10°C - 110°C 10 Bar 2.3 kg
UCF20-70B-150 20mm 7.7 96 Bronze 0.62 150mm -10°C - 110°C 10 Bar 2.8 kg
UCV20-80B-150 20mm 8.5 84 Bronze 0.6 150mm -10°C - 110°C 10 Bar 2.3 kg
UCF25-60B-180 25mm 5.8 55 Bronze 0.39 180mm -10°C - 110°C 10 Bar 2.8 kg
UCV25-60B-180 25mm 5.8 55 Bronze 0.4 180mm -10°C - 110°C 10 Bar 3.1 kg
UCF25-60CI-130 25mm 5.8 55 Cast Iron 0.39 130mm -10°C - 110°C 10 Bar 2.8 kg
UCF32-80B-180 32mm 7.8 138 Bronze 0.95 180mm -10°C - 110°C 10 Bar 5.2 kg
UCF32-80CI-180 32mm 7.8 138 Cast Iron 0.95 180mm -10°C - 110°C 10 Bar 5.2 kg
DNModel D2 L b1 b2 (Connection Size) a I
UCF15-40B-130 25 130 80 44 15mm 28 108
UCF20-60B-150 32 150 80 44 20mm 28 108
UCV20-60B-150 32 150 80 48 20mm 28 108
UCF20-70B-150 32 150 80 44 20mm 28 108
UCV20-80B-150 32 150 80 48 20mm 28 108
UCF25-60B-180 38 180 80 44 25mm 32 108
UCV25-60B-180 38 180 80 48 25mm 32 108
UCF25-60CI-130 38 180 80 44 25mm 32 108
UCF32-80B-180 50 180 80 57 32mm 39 150
UCF32-80CI-180 50 180 80 57 32mm 39 150
DNModel A1 A2 B1 B2 C1 C2 (Connection Size) L M N
UCV15-15B 76 - 118 - 105 - 15mm 65/80* 35 72
UCV15-15BTU - 110 - 163 - 150 15mm 65/80* 35 72
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
Circulator Pumps
*If an Ultraflow pump is replacing an alternative brand, an optional adapter can be ordered and fitted to the pump. This will increase the port to port domension (L) to 80mm.
3
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 3
Dual Circulator Pump UnitsWarmth – Continuity – Efficiency – Satisfaction
The ‘ULTRAFLOW’ DUCF & DUCV series dualcirculator pump units incorporate two (2)‘ULTRAFLOW’ UCF or UCV circulator pumpsmounted on a wall mount frame with suction anddischarge pipework manifolds, valves & fittingsalong with an ‘ULTRAFLOW’ DPTC dual pump timeclock controller which alternates the pumps every 4 / 6 / 12 hours – whatever time period isprogrammed. Dual pump systems ensure increasedpump life – operating the pumps for shorter intervalsincreases bearing and pump life. Having an additionalpump provides back-up in the event that one pump istaken off line for maintenance, repair or replacement.
Features• Compact design.
• Multiple connectionpoints
• 20mm, 25mm,32mm connectionsavailable,
• Factory pressuretested
• Fast delivery
• Many optionalextras available
Easy Time Saving InstallationThe installer simply mounts thecomplete ‘ULTRAFLOW’ dual pumpunit on to a wall, plumbs pipeworkto the suction and dischargeconnections, bleeds the air from thepumps/ system, and plugs thepower cord into a nearby 240 voltpower point – installation complete!Installation time is reduced to anabsolute minimum by having thepipework manifolds and valves pre-plumbed, electrical wiring fittedand the time clock programmed.
Standard System• Two (2) ‘Ultraflow’ circulator pumps • Stainless steel suction and discharge manifolds• Brass isolation valves• Brass non-return valves• Standard twin pump control, including
- Poly enclosure- Programmable 24 hour 7 day time clock for pump
alternation- Pump Run indication light for each pump
• Pumps, pipework and control mounted on a galvanisedsteel base plate with pre-drilled mounting holes
• 240 volt plug
Premium System• Two (2) ‘Ultraflow’ circulator
pumps • Stainless steel suction and
discharge manifolds• Brass isolation valves• Brass non-return valves• Premium twin pump control,
including- Weatherproof, powder coated
steel enclosure- Visual & audible alarms- Main isolator- Programmable 24 hour 7 day
time clock for pump alternation- Circuit breakers for motors and control circuit- Indication lights for Power On - Pump Run - Pump Fault- Manual - Off - Auto selector switches for each pump- Volt free contacts for motor faults- Auto changeover from duty pump to standby pump on
duty pump failure- Motor overload protection
• Pumps, pipework and control mounted on a galvanisedsteel base plate with pre-drilled mounting holes
• 240 volt plug
Circulator Pumps
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
Information subject to change without notice.
4
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 4
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCV15-15B - DIMENSIONS - mmA1 B1 C1 DN L M N
(Connection Size)
76 118 105 15 *65 35 72
UCV15-15BTU - DIMENSIONS - mmA2 B2 C2 DN L M N
(Connection Size)
110 163 150 15 *65 35 72
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
V ‘V’ indicates variable speed high efficiency motor
15 Indicates nominal outlet size
15 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
T ‘T’ indicates 24 hour timer controllable
U ‘U’ indicates thermostatically controllable (20°C - 70°C)
DIMENSIONS
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) 2 - 8 W
Frequency 50Hz
Connection Size 15mm / ½ inch female BSP
Weight 0.9Kg – UCV15-15B1Kg – UCV15-15BTU
Phase 1ø
Voltage 240
Full Load Ampere 0.10
Liquid Temperature Range -5°C - 70°C**
Max Operating Pressure 10 Bar
Motor Insulation Class F
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Timer Increments (BTU Model) 30 minutes
Thermostat Range (BTU Model) 20°C - 70°C
ENERGY RATING GUIDE
UCV15-15BTU
UCV15-15B
Models: UCV15-15BUCV15-15BTU
5
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 5
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCF15-40B-130 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
25 130 80 44 15 28 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
F ‘F’ indicates standard motor
15 Indicates nominal outlet size
40 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
130 Port to port length in mm
DIMENSIONS
L/sec0.10.0 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
L/sec0.10.0 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
UCF15-40B-130
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 40 W
Power (Watts) Speed 2 58 W
Power (Watts) Speed 3 75 W
Frequency 50Hz
Union Connection Size 15mm / ½ inch female BSP
Pump Outlet Flange Thread 25mm / 1 inch male BSP
Weight 2.3Kg
Phase 1ø
Voltage 240
Full Load Ampere – Speed 1 0.17
Full Load Ampere – Speed 2 0.25
Full Load Ampere – Speed 3 0.33
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class H
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
Models: UCF15-40B-130
6
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 6
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCF20-60B-150 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
32 150 80 44 20 28 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
F ‘F’ indicates standard motor
20 Indicates nominal outlet size
60 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
150 Port to port length in mm
DIMENSIONS
UCF20-60B-150
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 40 W
Power (Watts) Speed 2 67 W
Power (Watts) Speed 3 90 W
Frequency 50Hz
Union Connection Size 20mm / ¾ inch female BSP
Pump Outlet Flange Thread 32mm / 1¼ inch female BSP
Weight 2.3Kg
Phase 1ø
Voltage 240
Full Load Ampere – Speed 1 0.17
Full Load Ampere – Speed 2 0.29
Full Load Ampere – Speed 3 0.39
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class H
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
Models: UCF20-60B-150
7
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 7
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCV20-60B-150 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
32 150 80 44 20 28 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
V ‘V’ indicates high efficiency variable speed motor
20 Indicates nominal outlet size
60 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
150 Port to port length in mm
DIMENSIONS
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 7-50 W
Power (Watts) Speed 2 16 W
Power (Watts) Speed 3 34 W
Frequency 50Hz
Union Connection Size 20mm / ¾ inch female BSP
Pump Outlet Flange Thread 32mm / 1¼ inch male BSP
Weight 2.3Kg
Phase 1ø
Voltage 240
Full Load Ampere – Variable Speed 0.05 – 0.4
Full Load Ampere – Speed 1 0.16
Full Load Ampere – Speed 2 0.3
Full Load Ampere – Speed 3 0.4
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class F
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
UCV20-60B-150
ENERGY RATING GUIDE
Models: UCV20-60B-150
8
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 8
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCF20-70B-150 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
32 150 80 44 20 28 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
F ‘F’ indicates standard motor
20 Indicates nominal outlet size
70 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
150 Port to port length in mm
DIMENSIONS
UCF20-70B-150
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 81 W
Power (Watts) Speed 2 123 W
Power (Watts) Speed 3 140 W
Frequency 50Hz
Union Connection Size 20mm / ¾ inch female BSP
Pump Outlet Flange Thread 32mm / 1¼ inch male BSP
Weight 2.7Kg
Phase 1ø
Voltage 240
Full Load Ampere – Speed 1 0.39
Full Load Ampere – Speed 2 0.57
Full Load Ampere – Speed 3 0.62
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class H
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
Models: UCF20-70B-150
9
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 9
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCV20-80B-150 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
32 150 80 48 20 28 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
V ‘V’ indicates high efficiency variable speed motor
20 Indicates nominal outlet size
80 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
150 Port to port length in mm
DIMENSIONS
UCV20-80B-150
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Variable Speed Mode 7-75 W
Power (Watts) Speed 1 25 W
Power (Watts) Speed 2 50 W
Power (Watts) Speed 3 75 W
Frequency 50Hz
Union Connection Size 20mm / ¾ inch female BSP
Pump Outlet Flange Thread 32mm / 1¼ inch male BSP
Weight 2.3Kg
Phase 1ø
Voltage 240
Full Load Ampere – Variable Speed 0.05 – 0.6
Full Load Ampere – Speed 1 0.24
Full Load Ampere – Speed 2 0.45
Full Load Ampere – Speed 3 0.60
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class F
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
ENERGY RATING GUIDE
Models: UCV20-80B-150
10
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 10
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCF25-60B-180 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
30 180 80 44 25 32 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
F ‘F’ indicates standard motor
25 Indicates nominal outlet size
60 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
180 Port to port length in mm
DIMENSIONS
UCF25-60B-180
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 40 W
Power (Watts) Speed 2 67 W
Power (Watts) Speed 3 90 W
Energy Label B
Frequency 50Hz
Union Connection Size 25mm / 1 inch female BSP
Pump Outlet Flange Thread 38mm / 1½ inch female BSP
Weight 2.8Kg
Phase 1ø
Voltage 240
Full Load Ampere – Speed 1 0.17
Full Load Ampere – Speed 2 0.29
Full Load Ampere – Speed 3 0.39
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class H
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
Models: UCF25-60B-180
11
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 11
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCV25-60B-180 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
38 180 80 48 25 32 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
V ‘V’ indicates high efficiency variable speed motor
25 Indicates nominal outlet size
60 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
180 Port to port length in mm
DIMENSIONS
UCV25-60B-180
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Variable Speed Mode 7-50 W
Power (Watts) Speed 1 16 W
Power (Watts) Speed 2 34 W
Power (Watts) Speed 3 50 W
Frequency 50Hz
Union Connection Size 25mm / ¾ inch female BSP
Pump Outlet Flange Thread 38mm / 1¼ inch male BSP
Weight 3.1Kg
Phase 1ø
Voltage 240
Full Load Ampere – Variable Speed 0.05 – 0.4
Full Load Ampere – Speed 1 0.16
Full Load Ampere – Speed 2 0.3
Full Load Ampere – Speed 3 0.4
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class F
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
ENERGY RATING GUIDE
Models: UCV25-60B-180
12
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 12
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCF25-60CI-130 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
38 130 80 44 25 32 108
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
F ‘F’ indicates standard motor
25 Indicates nominal outlet size
60 Indicates max pressure in kpa
CI ‘CI’ indicates cast iron pump casing
130 Port to port length in mm
DIMENSIONS
UCF25-60CI-130
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 40 W
Power (Watts) Speed 2 67 W
Power (Watts) Speed 3 90 W
Frequency 50Hz
Union Connection Size 25mm / 1 inch female BSP
Pump Outlet Flange Thread 38mm / 1½ inch female BSP
Weight 2.8Kg
Phase 1ø
Voltage 240
Full Load Ampere – Speed 1 0.17
Full Load Ampere – Speed 2 0.29
Full Load Ampere – Speed 3 0.39
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class H
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Cast Iron
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
Models: UCF25-60CI-130
13
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 13
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCF32-80B-180 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
50 180 80 57 32 39 150
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
F ‘F’ indicates standard motor
32 Indicates nominal outlet size
80 Indicates max pressure in kpa
B ‘B’ indicates bronze pump casing
180 Port to port length in mm
DIMENSIONS
UCF32-80B-180
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 107 W
Power (Watts) Speed 2 176 W
Power (Watts) Speed 3 210 W
Frequency 50Hz
Union Connection Size 32mm / 1¼ inch female BSP
Pump Outlet Flange Thread 50mm / 2 inch female BSP
Weight 5.2Kg
Phase 1ø
Voltage 240
Full Load Ampere – Speed 1 0.49
Full Load Ampere – Speed 2 0.80
Full Load Ampere – Speed 3 0.95
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class H
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Bronze
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
Models: UCF32-80B-180
14
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 14
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
UCF32-80CI-180 - DIMENSIONS - mmD2 L b1 b2 DN a l
(Connection Size)
50 180 80 57 32 39 150
PERFORMANCE CURVES
MODEL NUMBER STRUCTUREU Ultraflow
C Circulation pump
F ‘F’ indicates standard motor
32 Indicates nominal outlet size
80 Indicates max pressure in kpa
CI ‘CI’ indicates cast iron pump casing
180 Port to port length in mm
DIMENSIONS
UCF32-80CI-180
**It is suggested to keep the operating temperature as low as possible (e.g. 65°C)to avoid lime precipitation (calcium build-up). Information subject to change without notice.
SPECIFICATIONSPower (Watts) Speed 1 107 W
Power (Watts) Speed 2 176 W
Power (Watts) Speed 3 210 W
Frequency 50Hz
Union Connection Size 32mm / 1¼ inch female BSP
Pump Outlet Flange Thread 50mm / 2 inch female BSP
Weight 5.2Kg
Phase 1ø
Voltage 240
Full Load Ampere – Speed 1 0.49
Full Load Ampere – Speed 2 0.80
Full Load Ampere – Speed 3 0.95
Liquid Temperature Range -10°C - 110°C**
Max Operating Pressure 10 Bar
Motor Insulation Class H
Motor Protection IP44
Impeller Construction Noryl GFN 1630V
Pump Casing Construction Cast Iron
Temp of media in system °C 110 100 90 80
Max Temp surrounding pump °C 35 50 50 70
Models: UCF32-80CI-180
15
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 15
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
DIMENSIONS
Drawings are not to scale and measurements are approximate. Information subject to change without notice.
DUAL PUMP SYSTEM SPECIFICATIONSDischarge Connections 20mm BSP female
Suction Connections 20mm BSP female
No. of Discharge Connections 2 (connect to left or right)
No. of Suction Connections 2 (connect to left or right)
No. of Circulation Pumps 2
No. of Discharge Isolation Valves 2 (ball type)
No. of Suction Isolation Valves 2 (ball valve union type)
No. of Non-return Valves 2 (swing type)
Pipework Mountings Anti vibration standoff clamps
Ball valve material Brass
Non-return Valve Material Brass
Union Material Brass
Suction/Discharge manifolds 304 stainless steel
Base Plate Material Galvanised steel
Approximate Weight 16Kg62Kg (enclosure mounted units)
Controller & time clock function:
- Polypropylene enclosure- 24 hour/7 day programmable timer, 12 hour alternation default- 100 hour battery back up- Manual override- Indication lights for each pump run- Alternating duty pump via timeclock
DUAL CIRCULATOR SYSTEM
Enclosure mounted systems
UFS-2F206B
UFS-2V206B
UFS-2F207B
UFS-2V208B
Models: UFS-2F206B UFS-2F207BUFS-2V206B UFS-2V208B
16
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 16
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
Models: UFP-2F206B UFP-2F207BUFP-2V206B UFP-2V208B
DIMENSIONS
DUAL PUMP SYSTEM SPECIFICATIONSDischarge Connections 20mm BSP female
Suction Connections 20mm BSP female
No. of Discharge Connections 2 (connect to left or right)
No. of Suction Connections 2 (connect to left or right)
No. of Circulation Pumps 2
No. of Discharge Isolation Valves 2 (ball type)
No. of Suction Isolation Valves 2 (ball valve union type)
No. of Non-return Valves 2 (swing type)
Pipework Mountings Anti vibration standoff clamps
Ball valve material Brass
Non-return Valve Material Brass
Union Material Brass
Suction/Discharge manifolds 304 stainless steel
Base Plate Material Galvanised steel
Approximate Weight 28Kg79Kg (enclosure mounted units)
Controller & time clock function:
- Powder coated steel enclosure- 24 hour/7 day programmable timer, 12 hour alternation default- 100 hour battery back up- Manual/Off/Auto switches for each pump- Indication lights for ‘Power On’ and each pump ‘Run’ & ‘Fault’- Main isolator- Thermal overload protection- Alarm light and buzzer with mute- Provision for thermostat operation - optional- Alternating duty pump via timeclock- Auto changeover from duty pump to standby pump on duty pump failure
DUAL CIRCULATOR SYSTEM
Enclosure mounted systems
UFP-2F206B
UFP-2V206B
UFP-2F207B
UFP-2V208B
Drawings are not to scale and measurements are approximate. Information subject to change without notice.
17
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 17
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
DIMENSIONS
Drawings are not to scale and measurements are approximate. Information subject to change without notice.
DUAL PUMP SYSTEM SPECIFICATIONSDischarge Connections 25mm BSP female
Suction Connections 25mm BSP female
No. of Discharge Connections 2 (connect to left or right)
No. of Suction Connections 2 (connect to left or right)
No. of Circulation Pumps 2
No. of Discharge Isolation Valves 2 (ball type)
No. of Suction Isolation Valves 2 (ball valve union type)
No. of Non-return Valves 2 (swing type)
Pipework Mountings Anti vibration standoff clamps
Ball valve material Brass
Non-return Valve Material Brass
Union Material Brass
Suction/Discharge manifolds 304 stainless steel
Base Plate Material Galvanised steel
Approximate Weight 21Kg67Kg (enclosure mounted units)
Controller & time clock function:
- Polypropylene enclosure- 24 hour/7 day programmable timer, 12 hour alternation default- 100 hour battery back up- Manual override- Indication lights for each pump run- Alternating duty pump via timeclock
DUAL CIRCULATOR SYSTEM
Enclosure mounted systems
UFS-2F256B
UFS-2V256B
Models: UFS-2F256BUFS-2V256B
18
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 18
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
DIMENSIONS
DUAL PUMP SYSTEM SPECIFICATIONSDischarge Connections 25mm BSP female
Suction Connections 25mm BSP female
No. of Discharge Connections 2 (connect to left or right)
No. of Suction Connections 2 (connect to left or right)
No. of Circulation Pumps 2
No. of Discharge Isolation Valves 2 (ball type)
No. of Suction Isolation Valves 2 (ball valve union type)
No. of Non-return Valves 2 (swing type)
Pipework Mountings Anti vibration standoff clamps
Ball valve material Brass
Non-return Valve Material Brass
Union Material Brass
Suction/Discharge manifolds 304 stainless steel
Base Plate Material Galvanised steel
Approximate Weight 31Kg74Kg (enclosure mounted units)
Controller & time clock function:
- Powder coated steel enclosure- 24 hour/7 day programmable timer, 12 hour alternation default- 100 hour battery back up- Manual/Off/Auto switches for each pump- Indication lights for ‘Power On’ and each pump ‘Run’ & ‘Fault’- Main isolator- Thermal overload protection- Alarm light and buzzer with mute- Provision for thermostat operation - optional- Alternating duty pump via timeclock- Auto changeover from duty pump to standby pump on duty pump failure
DUAL CIRCULATOR SYSTEM
Enclosure mounted systems
UFP-2F256B
UFP-2V256B
Models: UFP-2F256BUFP-2V256B
Drawings are not to scale and measurements are approximate. Information subject to change without notice.
19
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 19
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
DIMENSIONS
Drawings are not to scale and measurements are approximate. Information subject to change without notice.
DUAL PUMP SYSTEM SPECIFICATIONSDischarge Connections 32mm BSP female
Suction Connections 32mm BSP female
No. of Discharge Connections 2 (connect to left or right)
No. of Suction Connections 2 (connect to left or right)
No. of Circulation Pumps 2
No. of Discharge Isolation Valves 2 (ball type)
No. of Suction Isolation Valves 2 (ball valve union type)
No. of Non-return Valves 2 (swing type)
Pipework Mountings Anti vibration standoff clamps
Ball valve material Brass
Non-return Valve Material Brass
Union Material Brass
Suction/Discharge manifolds 304 stainless steel
Base Plate Material Galvanised steel
Approximate Weight 29Kg61Kg (enclosure mounted units)
Controller & time clock function:
- Polypropylene enclosure- 24 hour/7 day programmable timer, 12 hour alternation default- 100 hour battery back up- Manual override- Indication lights for each pump run- Alternating duty pump via timeclock
DUAL CIRCULATOR SYSTEM
Enclosure mounted systems
UFS-2F328B
Models: UFS-2F328B
20
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 8:59 pm Page 20
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
DIMENSIONS
DUAL PUMP SYSTEM SPECIFICATIONSDischarge Connections 32mm BSP female
Suction Connections 32mm BSP female
No. of Discharge Connections 2 (connect to left or right)
No. of Suction Connections 2 (connect to left or right)
No. of Circulation Pumps 2
No. of Discharge Isolation Valves 2 (ball type)
No. of Suction Isolation Valves 2 (ball valve union type)
No. of Non-return Valves 2 (swing type)
Pipework Mountings Anti vibration standoff clamps
Ball valve material Brass
Non-return Valve Material Brass
Union Material Brass
Suction/Discharge manifolds 304 stainless steel
Base Plate Material Galvanised steel
Approximate Weight 41Kg84Kg (enclosure mounted units)
Controller & time clock function:
- Powder coated steel enclosure- 24 hour/7 day programmable timer, 12 hour alternation default- 100 hour battery back up- Manual/Off/Auto switches for each pump- Indication lights for ‘Power On’ and each pump ‘Run’ & ‘Fault’- Main isolator- Thermal overload protection- Alarm light and buzzer with mute- Provision for thermostat operation - optional- Alternating duty pump via timeclock- Auto changeover from duty pump to standby pump on duty pump failure
DUAL CIRCULATOR SYSTEM
Enclosure mounted systems
Models: UFP-2F328B
Drawings are not to scale and measurements are approximate. Information subject to change without notice.
UFP-2F328B
21
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 9:00 pm Page 21
ENCLOSURE MOUNTED SYSTEMS
OPTIONAL EXTRA FOR UCV15-15B AND UCV15-15BTU
TEMPERATURE GAUGE
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
Options
When circulator pumpsand systems are installedoutdoors, it is essentialthat they are protectedfrom the weather. AllUltraflow circulatorpumps and systems areavailable pre-mounted inan enclosure.
• 80mm diameter face• Stainless steel surround• 0-120°C temperature
gauge• 15mm connection• Rear entry
AIR RELEASE VALVE
• 15mm connection• Brass body• Bottom entry
• Optional outlet adapter allows the port to port dimensionto be extended to 80mm to suit existing alternative brands
• Request at the time of ordering• Supplied with pumps only. Available for purchase
individually upon request
LARGE CIRCULATOR PUMPS & SYSTEMS
22
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 9:00 pm Page 22
VISIT www.generalpumps.com.au P 1300 662 787 E [email protected]
Other Products
PACKAGED PUMPSTATIONS
SUBMERSIBLEPUMPS
PUMPS AND CONTROLLER KITS
UNDER SINK UNITS GREASE ARRESTORS
WATER SUPPLYPRESSURE AND
RAINWATERHARVESTING
SYSTEM
OIL / WATERSEPARATORS
CONTROL PANELS& SWITCH GEAR
FIRE PROTECTION PACKAGES WATER SUPPLY PRESSURE BOOSTER
23
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 9:00 pm Page 23
Phone 1300 662 787www.generalpumps.com.auF: 1300 662 717E: [email protected] & Factory: 22-24 Sommerville Cct, Emu Plains NSW 2750
CirculatorPumps&Systems-0916_Layout 1 6/09/2016 9:00 pm Page 24