ul864 9th edition web presentation

48
UL Code 864 9 th Edition An Overview of the Foremost Code Updates

Upload: elias-macotela

Post on 13-Apr-2015

67 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ul864 9th Edition Web Presentation

UL Code 864 9 th Edition

An Overview of the Foremost Code Updates

Page 2: Ul864 9th Edition Web Presentation

2 HONEYWELL ­ CONFIDENTIAL File Number

9 th Edition of UL 864, ANSI/UL 864

•Note that UL 864 is an ANSI standard. •ANSI is national Norm. •ANY NRTL can certify. •FM and UL are equivalent

Latest incarnation of a standard first published in 1948

Page 3: Ul864 9th Edition Web Presentation

3 HONEYWELL ­ CONFIDENTIAL File Number

UL 864 9 th Edition

• When published in October 2003 the 9th edition had an effective date of October 31, 2005

• Three subsequent extensions by UL has moved the effective date to June 30, 2007

• UL no longer accepts products for certification to the 8th edition

Page 4: Ul864 9th Edition Web Presentation

4 HONEYWELL ­ CONFIDENTIAL File Number

Ground Fault Supervision

• Ground faults are no longer just a short to ground

• Manufacturer specifies the amount of leakage to ground and UL tests to verify the trip point

• Wiring installation workmanship is very important!

December 31, 2007 December 31, 2007 June 30, 2007

Page 5: Ul864 9th Edition Web Presentation

5 HONEYWELL ­ CONFIDENTIAL File Number

Products installed in Air­handling Spaces

June 30, 2007

• This is an issue particularly for speakers and associated wiring

Page 6: Ul864 9th Edition Web Presentation

6 HONEYWELL ­ CONFIDENTIAL File Number

Devices Installed in an Outlet Box

• You can not just lay a device in an outlet box!

June 30, 2007

Page 7: Ul864 9th Edition Web Presentation

7 HONEYWELL ­ CONFIDENTIAL File Number

Wiring the Fire Alarm

June 30, 2007

• It is vital that the installer follow minimum wire gage size specified in the installation wiring diagram

Page 8: Ul864 9th Edition Web Presentation

8 HONEYWELL ­ CONFIDENTIAL File Number

Alarm Signal Processing Time

• This is a major change from 90 seconds that has been the requirement for fire for more than 30 years

Page 9: Ul864 9th Edition Web Presentation

9 HONEYWELL ­ CONFIDENTIAL File Number

Trouble Signal Processing Time

• Trouble signal process time remains essentially unchanged

• Provision is now made to delay transmission of a battery trouble to avoid overloading the central station when an area loses power

Page 10: Ul864 9th Edition Web Presentation

10 HONEYWELL ­ CONFIDENTIAL File Number

Alarm and Trouble Signals Annunciation

• Voice systems must have a command center and this location must indicate all alarm and trouble signals for the system.

Page 11: Ul864 9th Edition Web Presentation

11 HONEYWELL ­ CONFIDENTIAL File Number

Visual Signal Annunciation at the Control

Can be a hold­up alarm!

Page 12: Ul864 9th Edition Web Presentation

12 HONEYWELL ­ CONFIDENTIAL File Number

Alarm Signaling

• This is the “Temporal Three”

• Synchronization introduces new complexities in the 9 th edition ­ Compatibility is a critical issue ­ Current calculations and wire size are critical ­ Power supply loading

• Note the exception – The whole alarm system does not need to be synchronized!

Page 13: Ul864 9th Edition Web Presentation

13 HONEYWELL ­ CONFIDENTIAL File Number

Supervisory Signals

• Supervisory Signals must be distinctly different than trouble signals. This calls for a separate device to be used unless the sounder can make different sounds.

• Note supervisory signals generally do not latch

Page 14: Ul864 9th Edition Web Presentation

14 HONEYWELL ­ CONFIDENTIAL File Number

Voice Alarm Command Center

• Controls Active LED on all ONYX panels

Page 15: Ul864 9th Edition Web Presentation

15 HONEYWELL ­ CONFIDENTIAL File Number

Emergency Voice/Alarm Function Sequence

• This is consistent with NFPA 72

• Some major communities (i.e. Chicago) follow a different sequence

• It is vital to be familiar with the local “High Rise Code”

Page 16: Ul864 9th Edition Web Presentation

16 HONEYWELL ­ CONFIDENTIAL File Number

Fire Warden Telephone Circuit

• The Telephone circuit must be supervised for opens, shorts and grounds.

• In today’s environment, communications for the fire service personnel is a vital function.

Page 17: Ul864 9th Edition Web Presentation

17 HONEYWELL ­ CONFIDENTIAL File Number

Operation Time Requirements

• Operating time requirements are greatly changed from the 8 th Edition of UL’s 864 Code.

• Operating time for alarm and supervisory annunciation reduced to 10 seconds from 90.

• Trouble signals remain at 200 seconds.

Page 18: Ul864 9th Edition Web Presentation

18 HONEYWELL ­ CONFIDENTIAL File Number

Releasing Device Service

• False tripping of a releasing device circuit, besides being an expensive mishap, can be very dangerous.

• This requirement specifically addresses a situation when the alarm panel is being serviced.

Page 19: Ul864 9th Edition Web Presentation

19 HONEYWELL ­ CONFIDENTIAL File Number

Networked Releasing Device Panels

• Concern for false dumps carries over to networked systems.

• If multiple systems can trigger a dump in the same system, the status of any panel on the system must be annunciated at the other panels connected to the system.

Page 20: Ul864 9th Edition Web Presentation

20 HONEYWELL ­ CONFIDENTIAL File Number

Pre­Discharge Notification

• Releasing device control panels must provide a predischarge warning to alert the building occupants.

Page 21: Ul864 9th Edition Web Presentation

21 HONEYWELL ­ CONFIDENTIAL File Number

Temporal Three

• Note the panel must have the capability of Temporal Three

• Some municipalities do not permit the Temporal Three; therefore, the requirement is one must have the capacity.

Page 22: Ul864 9th Edition Web Presentation

22 HONEYWELL ­ CONFIDENTIAL File Number

Deactivating Alarm and Discharge

Page 23: Ul864 9th Edition Web Presentation

23 HONEYWELL ­ CONFIDENTIAL File Number

Abort Switches

• Abort Switches must be manually­operated.

• Abort Switches must be self­restoring.

• Abort Switches must NOT be used with pre­action or deluge water systems.

Page 24: Ul864 9th Edition Web Presentation

24 HONEYWELL ­ CONFIDENTIAL File Number

Abort Switch Circuit Supervision

• The abort switch circuit must meet the supervision and style requirements applicable to initiating circuits.

Page 25: Ul864 9th Edition Web Presentation

25 HONEYWELL ­ CONFIDENTIAL File Number

Abort Switch Operation

• Operation of the abort switch during a fire alarm requires a distinctive visual and audible trouble signal.

• The visual indicator must be dedicated to the abort function.

• The audible may be the control panel common trouble sounder or a dedicated audible

Page 26: Ul864 9th Edition Web Presentation

26 HONEYWELL ­ CONFIDENTIAL File Number

Manual Release Switch

• Manual release switch must override all delays except manual release delay period

• Release must occur within 30 seconds

• The manual abort switch is not required to override the manual release switch. This can be a programming function.

• Operator’s manual must specify if manual override is provided.

Page 27: Ul864 9th Edition Web Presentation

27 HONEYWELL ­ CONFIDENTIAL File Number

Protected Premise Controls Timing # 1

Page 28: Ul864 9th Edition Web Presentation

28 HONEYWELL ­ CONFIDENTIAL File Number

Protected Premise Controls Timing # 2

• Report time can be 1 minute to 4 hours based on FCC regulations.

• Battery trouble signal shall be transmitted within 4 hours. • Battery trouble signal shall be transmitted for 7 days.

• Immediate local annunciation. • Transmission of signal within 60 to 180 minute delay.

• Immediate local annunciation. • Transmission over working path within 4 minutes.

Page 29: Ul864 9th Edition Web Presentation

29 HONEYWELL ­ CONFIDENTIAL File Number

Protected Premise Signal Annunciation

• If the signals sent to a remote supervisory station do not include zone information for a multi­zone panel, zone information must be indicated at the panel.

• If indication is not lamp per zone, it must include: ­ Signal prioritization ­ Indication by type ­ Indication by zone

Page 30: Ul864 9th Edition Web Presentation

30 HONEYWELL ­ CONFIDENTIAL File Number

Digital Radio Alarm Transmitters

• “Mechanically protected” means conduit

• If the transmitting antenna of transmitter/antenna combination are remote, conduit is required

Page 31: Ul864 9th Edition Web Presentation

31 HONEYWELL ­ CONFIDENTIAL File Number

DACT Dual Line Requirement

• Requirement includes: ­ Indication of fault subscriber location ­ Can not inhibit other subscriber ­ Faults include single open, ground, wire­to­wire short & noise ­ Signal restoration of service ­ Fault condition and restorations must be annunciated at the supervising station within 200 seconds

Page 32: Ul864 9th Edition Web Presentation

32 HONEYWELL ­ CONFIDENTIAL File Number

New Transmission Technologies

• NFPA 72, including the 2007 edition, is basically a prescriptive standard

• Each technology is treated differently ­ There is no correlation between technologies ­ Technologies are not rated as to their strength

• NFPA technical committee recognized this limitation and created the Other Technologies Transmission section

• This is where Internet based requirements originated

Page 33: Ul864 9th Edition Web Presentation

33 HONEYWELL ­ CONFIDENTIAL File Number

Time to transmit an alarm signal

• The “10 seconds” applies to all signal processing at the protected premise.

• Trouble annunciation or signal retransmission remains at 200.

Page 34: Ul864 9th Edition Web Presentation

34 HONEYWELL ­ CONFIDENTIAL File Number

Multi Zone Systems

Note: A holdup alarm can have same priority as fire

Burglar Alarm

Page 35: Ul864 9th Edition Web Presentation

35 HONEYWELL ­ CONFIDENTIAL File Number

Component Reliability

• In 8 th edition, 50% derating was required.

• In 9 th edition, 864 adopts a process first introduced in UL217.

• This change permits more design flexibility.

Page 36: Ul864 9th Edition Web Presentation

36 HONEYWELL ­ CONFIDENTIAL File Number

Software

• Software has become a major concern.

• It is critical that the A&E and installer be familiar with the programming function.

• It is particularly critical that each of the programming options be understood with regard to standard compliance.

Page 37: Ul864 9th Edition Web Presentation

37 HONEYWELL ­ CONFIDENTIAL File Number

Software compliance with the standard

• Software has made possible the concept of a universal panel.

• All features and options may not be compliant with UL 864 or NFPA 72.

• It is vital that the A&E review the options selected to assure compliance.

Page 38: Ul864 9th Edition Web Presentation

38 HONEYWELL ­ CONFIDENTIAL File Number

Executive Software tracking

• Knowing the Rev. level of the software is very important particularly when a problem occurs.

Page 39: Ul864 9th Edition Web Presentation

39 HONEYWELL ­ CONFIDENTIAL File Number

User Access and Programming

• Mapping of output circuits is permitted.

• Mapping input circuits to supervising station is not permitted.

• The executive program does automatic mapping of critical functions.

Page 40: Ul864 9th Edition Web Presentation

40 HONEYWELL ­ CONFIDENTIAL File Number

Combination Systems

• Anything non­fire connected to a fire alarm system can not cause any degradation of supervision or alarm functions.

• Testing is conducted by placing opens, shorts, grounds on these circuits to verify NOTHING has been compromised.

Page 41: Ul864 9th Edition Web Presentation

41 HONEYWELL ­ CONFIDENTIAL File Number

Interconnected Fire Alarm Control Units

• This is a concern for A&E and Installer ­ how and where you install is very important.

• Unless you can see the displays on all of the alarm panels at the same time, ALL panels must concurrently display: ­ Alarm ­ Supervisory ­ Trouble ­ Reset ­ Alarm Silence ­ Trouble Silence

Page 42: Ul864 9th Edition Web Presentation

42 HONEYWELL ­ CONFIDENTIAL File Number

Power Supply Capacity

• The power supply shall be capable of operating the system under full load with supply voltage at 85% of rated with battery disconnected.

• The system must be capable of fully charging the battery when the supply voltage is reduced to 85% (or transfer voltage) of rated voltage.

Page 43: Ul864 9th Edition Web Presentation

43 HONEYWELL ­ CONFIDENTIAL File Number

Notification Appliance Circuits

• Compatibility of Notification Appliances with specific panels is now critical

• Voltage calculations are very important­one can’t add just one more device

• Synchronization is a critical factor as the steady­state load can be very much less then the peak load

• Great care must be taken in selecting notification appliances for use with a particular panel.

• The panel installation instructions and wiring diagrams are your primary guide.

Page 44: Ul864 9th Edition Web Presentation

44 HONEYWELL ­ CONFIDENTIAL File Number

Rating Designations

• All NAC circuits must be identified by one of these designations

• All NAC circuits must operate within the specified voltage range

• Note the special application category

Page 45: Ul864 9th Edition Web Presentation

45 HONEYWELL ­ CONFIDENTIAL File Number

Regulated NAC Circuits

Page 46: Ul864 9th Edition Web Presentation

46 HONEYWELL ­ CONFIDENTIAL File Number

Special Application NAC Circuits

Page 47: Ul864 9th Edition Web Presentation

47 HONEYWELL ­ CONFIDENTIAL File Number

Regulated NAC Surge Current Loading

• Loading for first surge is 10X steady state rating of circuit

• Loading for repetitive surges is 5X steady state rating

Page 48: Ul864 9th Edition Web Presentation

48 HONEYWELL ­ CONFIDENTIAL File Number

Special Application Surge Current Loading

• Only devices specified in the panel installation documentation are permitted!