www.flowtechsystems.com 8669640072 5594 North Hollywood Avenue, Suite 202, Whitefish Bay, WI 53217 [email protected] University of California Santa Barbara FlowTech Test Report Installed: January 2014 Duration: 1 year Application: Cooling Tower Cooling Capacity: 400 tons Scale: Under chemical treatment, hard scale accumulated on the fill on the cooling tower. During the test, FlowTech prevented hard scale from forming on the cooling tower and even softened the existing scale to the point that it could be removed with a garden hose. Bacteria: Bacteria counts have historically been around 10,000 CFU/mL, but after FlowTech was installed, heterotrophic plate counts totaled only 2,337 CFU/mL. The bacteria tests were performed independently by FGL Environmental using Standard Method 9215. The formal report is included below. Corrosion: The LarsonSkold Corrosion Index of 2.5 indicates that the water in the system was extremely aggressive. Anything over .8 is a concern, and anything above 1.2 is considered very aggressive. Without any chemical assistance, FlowTech kept the corrosion rates low in a very harsh environment. Both of the results, .2 MPY copper and 2.4 MPY mild steel, are considered "mild or very good". The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below. Water Savings: By increasing the water reuse in the system from 2.2 to 3.8 cycles of concentration, FlowTech saved 57% of the blowdown water and 26% of all of the water used in the system – or approximately 3,003,429 gallons of water. At a rate of $6.53 per HCF for potable water and $3.26 per HCF for sewer, the university would save approximately $26,220 and $13,095 respectively each year. Other Savings: FlowTech also reduced the maintenance that had previously been required every month to remove scale from the fill on the cooling tower, improved the heat transfer efficiency, and eliminated chemicals and their associated costs and maintenance.

Upload: hacong

Post on 23-Apr-2018

216 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

 

  

www.flowtechsystems.com 

866‐964‐0072 • 5594 North Hollywood Avenue, Suite 202, Whitefish Bay, WI 53217 • [email protected] 

University of California Santa Barbara Flow‐Tech Test Report 

  Installed: January 2014 Duration: 1 year Application: Cooling Tower Cooling Capacity: 400 tons   Scale: Under chemical treatment, hard scale accumulated on the fill on the cooling tower.  During the test, Flow‐Tech prevented hard scale from forming on the cooling tower and even softened the existing scale to the point that it could be removed with a garden hose.  Bacteria: Bacteria counts have historically been around 10,000 CFU/mL, but after Flow‐Tech was installed, heterotrophic plate counts totaled only 2,337 CFU/mL.  The bacteria tests were performed independently by FGL Environmental using Standard Method 9215.  The formal report is included below.  Corrosion: The Larson‐Skold Corrosion Index of 2.5 indicates that the water in the system was extremely aggressive.  Anything over .8 is a concern, and anything above 1.2 is considered very aggressive.  Without any chemical assistance, Flow‐Tech kept the corrosion rates low in a very harsh environment.  Both of the results, .2 MPY copper and 2.4 MPY mild steel, are considered "mild or very good".  The corrosion tests were performed independently by Nalco, An Ecolab Company.  The formal report is included below.  Water Savings: By increasing the water reuse in the system from 2.2 to 3.8 cycles of concentration, Flow‐Tech saved 57% of the blow‐down water and 26% of all of the water used in the system – or approximately 3,003,429 gallons of water.  At a rate of $6.53 per HCF for potable water and $3.26 per HCF for sewer, the university would save approximately $26,220 and $13,095 respectively each year.  Other Savings: Flow‐Tech also reduced the maintenance that had previously been required every month to remove scale from the fill on the cooling tower, improved the heat transfer efficiency, and eliminated chemicals and their associated costs and maintenance.   

 

 

 

Page 2: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

 

  

www.flowtechsystems.com 

866‐964‐0072 • 5594 North Hollywood Avenue, Suite 202, Whitefish Bay, WI 53217 • [email protected] 

 

                    

Flow‐Tech Panel                     

Flow‐Tech Signal Tag   

Page 3: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

 

  

www.flowtechsystems.com 

866‐964‐0072 • 5594 North Hollywood Avenue, Suite 202, Whitefish Bay, WI 53217 • [email protected] 

                       

Cooling Tower                   

   

Cooling Tower Location 

Page 4: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

 

  

www.flowtechsystems.com 

866‐964‐0072 • 5594 North Hollywood Avenue, Suite 202, Whitefish Bay, WI 53217 • [email protected] 

                                           

 Scale Removed With Garden Hose 

Page 5: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

Sub Project:

Project Manager:

Bennett, Kevin

1321 Palm Ave

Kevin BennettSan Mateo CA, 94402

Project: Routine

University SB

Work Order:

05/09/14 12:00

14E0787

Reported:

Received:

05/27/14

Clinical Laboratory of San Bernardino, Inc.

ResultAnalyte BatchPrepared AnalyzedMethod Units

@ engineering & sci bldg 14E0787-01 (Water) 05/09/14 9:15 Kevin BennettSample Date: Sampler:

MCLRep. Limit Qualifier

Field Analyses

930 142002705/09/14 Spec Conduct / E.C. (Field) Field umhos/cm 05/09/14

7.4 142003005/09/14 pH (Field) Field pH Units 05/09/14

General Chemical Analyses

170 142033705/19/14 Alkalinity, Total (as CaCO3) SM 2320 B mg/L 05/19/14 5.0

210 142033705/19/14 Bicarbonate (HCO3) SM 2320 B mg/L 05/19/14 5.0

05/19/14 1420337Carbonate (CO3) NDSM 2320B mg/L 05/19/14 5.0

25 142039305/16/14 Chloride (Cl) EPA 300.0 mg/L 05/15/14 1.0 500

390 [CALC]05/23/14 Hardness, Total (as CaCO3) Calculated mg/L 05/23/14 6.6

05/19/14 1420337Hydroxide (OH) NDSM 2320B mg/L 05/19/14 5.0

0.31 142003705/15/14 Phosphorus (Total as PO4) HACH 8190 mg/L 05/12/14 0.020

300 142039305/16/14 Sulfate (SO4) EPA 300.0 mg/L 05/15/14 0.50 500

Metals

78 142144405/23/14 Calcium (Ca) EPA 200.7 mg/L 05/23/14 1.0

47 142144405/23/14 Magnesium (Mg) EPA 200.7 mg/L 05/23/14 1.0

12 142033105/14/14 Silica (SiO2) EPA 200.7 mg/L 05/14/14 0.50

Analyte NOT DETECTED at or above the reporting limitND

Robin Glenney

Project Manager

Page 1 of 1

Post Office Box 329 San Bernardino, CA 92402 (909) 825-7693 Fax (909) 825-7696 ELAP Number 1088

Page 6: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

TURrU effi#Uru*TfnfiH

rul

l-

il

F,*aIJ.I:i*t

m"r2&*

s.?.

>-UJtrs

t

UJL*kl'*mxuloJ*r,5

il

cclJ.i.Lh*

":

:i

:7,(ai'bl

{ts{t7*tf*: i{sli#rl,*t i

i1

II

I

57

,1-

UJ

sIt

bJ

}{mUJTJ*

il

(n

hC:{,}z.g6G3U'{oIrlrf,,roLucg-xTIJ

uttr{{(n(nrxz:[Ohsu€hd

orEO{oTJ-

Ehrxjg<Lr

3ou,Etr

IZft, uJ3u!cEO>:c53(\r<or*

CEt!ozoJ

r lllgxEi>eNg;ffiGa--asoa9ru^=38

ui

=troz:)()c{Z,fit*

UIxtrUJtuqn

\t-t

.}rrib

\LJ\$€:\hC

ty27!,

r{1\u-t

aJ()$(f,

{q(}t{(D

t\lrtz.

*

dduIet*'dEtu{ntlJI*,

F{0&J

{p$t.,E

{f,

}}ntuE.*xnn

iri(f;

ffiT}IJ

4(

r*Lt{fr\d

fvt,t{flqulfr\t+-**

F\t.Ih* C)..:&F'uhl t,.-

.,

tsq o,ffiLYP*-".]]*. \ ---tW*.t'Uhsk\IFi\U

3q*stu

@s\e

FT\_.Ht\

lq)UE)\La)

saffi&ffi

Wt*%

rqL {ikd{$*L

@\*stuSqred.&*}Hm&N&ear-kd&Hld

Pqae

ffi#r.wrlSGTh

.i kDeee

U

Page 7: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

Bacteriological Results Page: 1

SP 1406318:1 HETEROTROPHIC BACTERIA ANALYSISJune 17, 2014

Customer ID : 2-24705Flow Tech Systems5594 N. Hollywood Ave #202White Fish Bay, WI 53217

System Number :Project Name : UCSB Water Sample

Sample Handling Information

IDSample

NumberSample Description

SampleType/Reason

Sampled By Employed By Sampled Started Finished

1 SP 1406318-001 FSB Tower System-Routine George Rihousky Not Available 06/03/2014 13:20 06/03/2014 17:11 RRH 06/05/2014 LM

Analytical Results

ID Sample DescriptionChlorineTotal/Free

Temp°C

Method UnitsHeterotrophic

Plate CountMCL Person Notified‡

Date ‡Notified

Time ‡Notified

FootNote

1 FSB Tower --- --- SM 9215 CFU/ml 2300 * 500 Mark Meyer 06/06/2014 08:14

N/R Not Required. MPN Most Probable Number A/P Absence/Presence ‡ Client Notification details.

The samples listed below had failures for Heterotrophic Bacteria as Listed:

FSB Tower - Failure MCL

Analyses were performed using Standard Methods 20th edition. If you have any questions regarding your results, please call.

* Note: Per SM 9215-8.a, any results above 300 CFU/mL are considered estimated.

RRH:SMH

Corporate Offices & Laboratory853 Corporation StreetSanta Paula, CA 93060TEL: (805)392-2000Env FAX: (805)525-4172 / Ag FAX: (805)392-2063CA ELAP Certification No. 1573

Office & Laboratory2500 Stagecoach RoadStockton, CA 95215TEL: (209)942-0182FAX: (209)942-0423CA ELAP Certification No. 1563

Office & Laboratory563 E. Lindo AvenueChico, CA 95926TEL: (530)343-5818FAX: (530)343-3807CA ELAP Certification No. 2670

Office & Laboratory3442 Empresa Drive, Suite DSan Luis Obispo, CA 93401TEL: (805)783-2940FAX: (805)783-2912CA ELAP Certification No. 2775

Office & Laboratory9415 W. Goshen AvenueVisalia, CA 93291TEL: (559)734-9473FAX: (559)734-8435CA ELAP Certification No. 2810

ENVIRONMENTAL AGRICULTURALAnalytical Chemists

Reviewed andApproved By  Kelly A. Dunnahoo, B.S. 

Digitally signed by Kelly A. Dunnahoo, B.S.Title: Laboratory DirectorDate: 2014-06-17

Page 8: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below
Page 9: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

Customer Analytical Services1601 West Diehl Road Naperville IL 60563-1198

Phone: 630-305-1000 Fax: 630-305-2921 Email: [email protected]

Final - Report Number: 1214622

Sample number: NC171582

Date received: 11-Aug-2014

Date completed: 11-Aug-2014

Date Authorized: 11-Aug-2014

UCSB CAMPUS MCCARTHY TRAILER ATTN SMITH ELECTRIC

SERVICE

EL COLEGIO & OCEAN RD

SANTA BARBARA - CA - 93106 - USA

Sample taken from: 225, Condenser Water

Sold To: 0500060908 Ship To: 0150173817Representative: Mark Belanger

Analytical Report - Test Method CM18001

This sample was analyzed as received, the results being as follows:

SYSTEM INFORMATIONSample taken from 225, Condenser Water

Not GivenTreatment Program

COUPON INFORMATIONMild SteelCoupon Metallurgy

bar-style 3 x 3/8 x 1/16 inch (76 x 9.5 x 1.6 mm)Coupon Type

Q20084Serial number

PERIOD OF EXPOSURE26-Mar-2014Date inserted

01-Aug-2014Date removed

128Total days of exposure

WEIGHT LOSS7.9507Initial Weight g7.6589Final Weight g0.2918Weight Loss (Total) g0.2918Weight Loss (Corrected) g

CORROSION RESULTLocalized Corrosion - metal loss occurring at discrete sites on the

surface, such as pits, depressions or confined areas.

Corrosion Type

Corrosion Rate by Weight Loss 2.4 Mils per year 0.062 mm/year

Measured Depth of Metal Loss 7 mils 0.17 mm

COMMENTSThe corrosion rate calculated by weight loss is predominantly a result of corrosion at the edge and/or attachment hardware. The

localized metal loss, however, was measured away from these regions and is representative.

Authorized by Brendan Kane

Laboratory Techncian II

Page 1 of 2

Page 10: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

Customer Analytical Services1601 West Diehl Road Naperville IL 60563-1198

Phone: 630-305-1000 Fax: 630-305-2921 Email: [email protected]

Final - Report Number: 1214622

Sample number: NC171582

Date received: 11-Aug-2014

Date completed: 11-Aug-2014

Date Authorized: 11-Aug-2014

UCSB CAMPUS MCCARTHY TRAILER ATTN SMITH ELECTRIC

SERVICE

EL COLEGIO & OCEAN RD

SANTA BARBARA - CA - 93106 - USA

Sample taken from: 225, Condenser Water

Sold To: 0500060908 Ship To: 0150173817Representative: Mark Belanger

Analytical Report - Test Method CM18001

Before Cleaning After Cleaning

Authorized by Brendan Kane

Laboratory Techncian II

Page 2 of 2

Page 11: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

Customer Analytical Services1601 West Diehl Road Naperville IL 60563-1198

Phone: 630-305-1000 Fax: 630-305-2921 Email: [email protected]

Final - Report Number: 1214622

Sample number: NC171583

Date received: 11-Aug-2014

Date completed: 11-Aug-2014

Date Authorized: 11-Aug-2014

UCSB CAMPUS MCCARTHY TRAILER ATTN SMITH ELECTRIC

SERVICE

EL COLEGIO & OCEAN RD

SANTA BARBARA - CA - 93106 - USA

Sample taken from: 225, Condenser Water

Sold To: 0500060908 Ship To: 0150173817Representative: Mark Belanger

Analytical Report - Test Method CM18001

This sample was analyzed as received, the results being as follows:

SYSTEM INFORMATIONSample taken from 225, Condenser Water

Not GivenTreatment Program

COUPON INFORMATIONCopperCoupon Metallurgy

bar-style 3 x 1/2 x 1/16 inch (76 x 12.7 x 1.6 mm)Coupon Type

CV6831Serial number

PERIOD OF EXPOSURE26-Mar-2014Date inserted

01-Aug-2014Date removed

128Total days of exposure

WEIGHT LOSS12.3504Initial Weight g12.3238Final Weight g

0.0266Weight Loss (Total) g0.0266Weight Loss (Corrected) g

CORROSION RESULTGeneral Corrosion - metal loss dominated by uniform thinning and

without appreciable localized attack.

Corrosion Type

Corrosion Rate by Weight Loss 0.2 Mils per year 0.004 mm/year

Authorized by Brendan Kane

Laboratory Techncian II

Page 1 of 2

Page 12: UCSB - Test Report - v1. The corrosion tests were performed independently by Nalco, An Ecolab Company. The formal report is included below

Customer Analytical Services1601 West Diehl Road Naperville IL 60563-1198

Phone: 630-305-1000 Fax: 630-305-2921 Email: [email protected]

Final - Report Number: 1214622

Sample number: NC171583

Date received: 11-Aug-2014

Date completed: 11-Aug-2014

Date Authorized: 11-Aug-2014

UCSB CAMPUS MCCARTHY TRAILER ATTN SMITH ELECTRIC

SERVICE

EL COLEGIO & OCEAN RD

SANTA BARBARA - CA - 93106 - USA

Sample taken from: 225, Condenser Water

Sold To: 0500060908 Ship To: 0150173817Representative: Mark Belanger

Analytical Report - Test Method CM18001

Before Cleaning After Cleaning

Authorized by Brendan Kane

Laboratory Techncian II

Page 2 of 2