uchc+marb+bldg+vfd+pm+2013
DESCRIPTION
UCHC MARB BLDG PMTRANSCRIPT
![Page 1: Uchc+Marb+Bldg+Vfd+Pm+2013](https://reader036.vdocuments.us/reader036/viewer/2022082401/5455c65db1af9f68038b497a/html5/thumbnails/1.jpg)
UCHC263 Farmington Ave, Farmington,CT 06030
VFD PM Checklist / Worksheet www.flowtechinc.com
Equipment TAG CHWP_1 DATE 2/132013
VFD Manufacturer ABB Location MARB BLDG 4th FLR
VFD Model ACH550UH08A84 VFD S/N 2052301486
Bypass Model ACH550VD08A84F267 Bypass S/N 2044000450
VFD SW/FW 203B HEX Operating Hours 44.57kh
Fault History: 6 0 0
VFD Fuses: N/A Main Fuses:
VFD O.L. Config: 1050s/110% VFD I-Limit Setting: 9.7
Bypass O.L. Config: 00010000
VFD U.V. Config: VFD Freq Limits: 12 TO 58 Hz
System Check System Check
Set / Confirm VFD Date/Time X Check Cooling Fan Operation X
Back-up Parameters to Panel X Record Fan Capacitor Rating N/A
Ambient Temp 22 C Record Fan Capacitor Actual N/A
VFD Temp at Check-out (Display) 34.2 C Motor / Wire Insulation Check X
IR Scan of VFD / Panel X Check Speed Control Signal X
Inspect / Tighten all Elec. Conn. X Check Other I/O Signals X
Clean VFD & Bypass Panel X Perform Static Diode / IGBT Test X
Check all Panel Indicator Lamps X Reset VFD Fault History X
DYNAMIC SYSTEM POWER CHECKS OPERATING SPEED 54.6 HZ
Input Voltage A-B: 480 Vac B-C: 480 Vac C-A: 481 Vac Display
Output Voltage A-B: 348 Vac B-C: 348 Vac C-A: 348 Vac 354 Vac
Input Current A: 2.2 Amps B: 2.4 Amps C: 2.3 Amps Display
Output Current A: 3.8 Amps B: 3.9 Amps C: 3.9 Amps 3.9 Amps
DC Bus Voltage DC Level: 641 Vdc AC Level: 15 Vac 642 Vdc
STATIC SYSTEM VOLTAGE CHECKS OPERATING SPEED 0 Hz
DC Bus Voltage DC Level: 657 Vdc AC Level: 1 Vac 660
+10vdc VFD Supply DC Level: 10 Vdc AC Level: 12 mVac N/A
+24vdc VFD Supply DC Level: 24 Vdc AC Level: 60 mVac N/A
Control TX Voltage AC Level: N/A
+7vdc E-Bypass V DC Level: 7 Vdc AC Level: 12 N/A
+24vdc E-Bypass V DC Level: 25 Vdc AC Level: 9 N/A
ü / Data ü / Data
![Page 2: Uchc+Marb+Bldg+Vfd+Pm+2013](https://reader036.vdocuments.us/reader036/viewer/2022082401/5455c65db1af9f68038b497a/html5/thumbnails/2.jpg)
UCHC263 Farmington Ave, Farmington,CT 06030
VFD PM Checklist / Worksheet www.flowtechinc.com
Equipment TAG CHWP_2 DATE 2/13/13
VFD Manufacturer ABB Location MARB BLDG 4th FLR
VFD Model ACH550UH08A84 VFD S/N 2053700714
Bypass Model ACH550VO08A84F267 Bypass S/N 2044000701
VFD SW/FW 206B HEX Operating Hours 42.47kh
Fault History: 0 0 0
VFD Fuses: N/A Main Fuses:
VFD O.L. Config: 1050s/110% VFD I-Limit Setting: 9.7
Bypass O.L. Config: 00010000
VFD U.V. Config: VFD Freq Limits: 12 TO 58 Hz
System Check System Check
Set / Confirm VFD Date/Time X Check Cooling Fan Operation X
Back-up Parameters to Panel x Record Fan Capacitor Rating N/A
Ambient Temp 22 C Record Fan Capacitor Actual N/A
VFD Temp at Check-out (Display) 33.7 C Motor / Wire Insulation Check X
IR Scan of VFD / Panel X Check Speed Control Signal X
Inspect / Tighten all Elec. Conn. X Check Other I/O Signals X
Clean VFD & Bypass Panel X Perform Static Diode / IGBT Test X
Check all Panel Indicator Lamps X Reset VFD Fault History X
DYNAMIC SYSTEM POWER CHECKS OPERATING SPEED 58 HZ
Input Voltage A-B: 482 Vac B-C: 483 Vac C-A: 479 Vac Display
Output Voltage A-B: 393 Vac B-C: 394 Vac C-A: 394 Vac 396 Vac
Input Current A: 2.4 Amps B: 2.9 Amps C: 2.6 Amps Display
Output Current A: 4.2 Amps B: 4 Amps C: 4.1 Amps 4.2 Amps
DC Bus Voltage DC Level: 643 Vdc AC Level: 14 Vac 641 Vdc
STATIC SYSTEM VOLTAGE CHECKS OPERATING SPEED Hz
DC Bus Voltage DC Level: 658 Vdc AC Level: 1.5 Vac 658
+10vdc VFD Supply DC Level: 10 Vdc AC Level: mVac N/A
+24vdc VFD Supply DC Level: 25 Vdc AC Level: mVac N/A
Control TX Voltage AC Level: N/A
+7vdc E-Bypass V DC Level: 7.74 Vdc AC Level: 12 N/A
+24vdc E-Bypass V DC Level: 25 Vdc AC Level: 18 N/A
ü / Data ü / Data