REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
GENERALSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
A.000
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
COVER SHEET
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
SHEET INDEX
GENERAL
PLANS
MECHANICAL
PLUMBING
ELECTRICAL
FIRE PROTECTION
ID
A.000A.001A.002
A.100A.101A.102G.100G.101
M-001M-100M-200
P-001P-100P-200
ED-101E.101
FP-100FP-200
DESCRIPTION
COVER SHEETARCHITECTURAL SPECIFICATIONSARCHITECTURAL SPECIFICATIONS
SITE/DEMO PLANFLOOR PLANSREFLECTED CEILING PLANSECTIONS AND DETAILSDETAILS
LEGEND, NOTES, & DETAILSFLOOR PLANSSPECIFICATIONS
LEGEND, NOTES, DETEAILS, DIAGRAMS & S...FLOOR AND PLANSSPECIFICATIONS
DEMOLITION PLANSNEW FLOOR PLANS
FLOOR PLANSSPECIFICATIONS
REV #
010101
0101010101
010101
010101
0101
0101
DATE
CODE ICC NFPA 101 IPC
YEAR 2015 2012 2015 2010
BUILDING STATISTICS
TOTAL AREA 3,180 SF
IBC SEC. BASIS OF DESIGN
302 OCCUPANCY CLASSIFICATION B
602 CONSTRUCTION CLASSIFICATION 2B
705 - 711 RATED CONSTRUCTION
FIRE WALLS N/A
FIRE BARRIERS 1 HR (UL# 419)
SHAFT WALLS EXISTING NOT TO BE PENETRATED
FIRE PARTITIONS N/A
ROOF - CLG N/A
FLOOR - CLG N/A
NSPC SEC. BASIS OF DESIGN
7.21.1 MIN. NUMBER OF REQUIRED PLUMBING FIXTURES
B BUSINESS BASED ON 25 OCCUPANTS
MALE FEMALE MALE FEMALE
WC 1 1 1 1
LAV 1 1 1 1
-MIN REQ. MET INCLUDED TOILETS IN PUBLIC
CORRIDOR.
DRINKING FOUNTAINS 1 REQUIRED LOCATED IN ADJOINING SUITE
SHOWER NONE N/A
SERVICE SINKS 1 REQUIRED 1 PROVIDED
-MOP SINK LOCATED IN SHARED J.C. IN
ADJOINING SUITE
NFPA CODE DESCRIPTION BASIS OF DESIGN
EMERGENCY LIGHTS AND SIGNS YES
FIRE ALARM AND DETECTION SYSTEM NO
PANIC HARDWARE YES
EXIT SIGNS YES
EXIT ILLUMINATION YES
SMOKE DETECTION SYSTEMS NA
EGRESS WINDOWS N/A
ANSUL SUPPRESSION (RANGE HOOD) N/ALIF
E S
AF
ET
Y S
YS
TE
MS
CODE DESCRIPTION
CH
. 3&
6
CH
AP
TE
R 7
- F
IRE
RE
SIS
TIV
E
CO
NS
TR
UC
TIO
N
CODE DESCRIPTION
CH
AP
TE
R 7
- P
LU
MB
ING
FIX
TU
RE
S
ADA - FED GUIDELINES FOR ACCESS.
BUILDING CODE SUMMARY
THIS PROJECT HAS BEEN PREPARED BY CDG IN ACCORDANCE WITH THE FOLLOWING CODES AS ADOPTED AND AMENDED BY
THE TOWN OF ELKTON, MARYLAND. (THE AUTHORITY HAVING JURISDICTION)
PROJECT DESCRIPTION:
THIS PROJECT IS A RELOCATION OF AN EXISTING SPACE ONTO THE ADJACENT SPACE WITH MINOR CHANGES TO INTERIOR
PARTITIONS.
THIS PROJECT PRESENTS NO INCREASE IN HAZARD OR CHANGE IN OCCUPANCY.
CLASSROOM100
CP RB P1 AC
N
C
B
A
D
E
F
G
H
I
J
L
M
W
V
U
T
S
R
Q
P
O
N
RUBBERHARDENED CONCRETE
BULKHEAD
FIBERGLAS
HANDICAP DRINKING FOUNTAIN
DRINKING FOUNTAIN
ALUMINUM STOREFRONT
HORIZONTAL LOUVER BLINDS
JOIST
INTERIOR
HOLLOW CORE FINISH VENEER
YIELD STRESS
FACE OF MASONRYFACE OF CONCRETEFLOOR
FINISH
ANGLE
ATAMPERESANCHOR BOLTABOVEAIR CONDITIONING
ACOUSTICAL PANEL CEILING
ADMINISTRATIVE
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
ALUMINUMALTERNATE
ANODIZEDACCESS PANEL
APPROXIMATELYARCHITECTURALASSEMBLYAUXILIARY
BOARD
BLOCKING
BUILDING
BOTTOM OF STEELBOTTOM
BRITISH THERMAL UNITBUILT-UP ROOF
CENTIGRADECABINET
CHALK BOARDCAST IRONCONTROL JOINTCENTER LINECEILINGCLOSETCLEARCONCRETE MASONRY UNIT
COAT HOOK
COLUMNCONCRETECONNECTION
CORRIDORCONTINUOUS
CURTAIN TRACK
CUSTODIAN
CERAMIC TILE
CUBIC
DAMPPROOFING
DIMENSION
DOUBLEDEFORMED
DRAWER
DIAGRAM
DIVISIONDOWN
DOORDOWNSPOUT
DRAWINGDOWELS
ELECTRICALEACH
EXPANSION JOINT
EXHAUST FLUE
ELEVATION
EXTERIOR GYPSUM SOFFIT BOARD
EQUALEQUIPMENTET CETERAEACH WAYELECTRIC WATER COOLEREXISTING GRADEEXHAUSTEXISTINGEXPANSIONEXPOSEDEXTERIOR
FAHRENHEITFIRE ALARMFIRE CODEFLOOR DRAIN
FINISH GRADE
FIRE EXTINGUISHER CABINETFINISH FLOOR
FLASHING
FIRE HOSE CABINET
FOLDING PARTITION
FOOT SCRAPER
FEET
FIBER REINFORCED PLASTIC
FURRING
GASGAUGEGALVANIZED
GYPSUM DRYWALLGENERAL
GENERAL CONTRACTOR
GLASS
GROUND
GRAB BAR
HOSE BIBBHOLLOW CORE
HEAD, HEADED, HEAVY DUTY
HOT-DIPPED GALVANIZEDHARDWARE
HOLLOW METALHORIZONTAL
HEIGHTHOUR, HOURS
HARD WOOD
IN ACCORDANCE WITH
INSULATING GLASSINCH, INCHESINCANDESCENT
INSULATION
JANITOR
JOINT
ANGLE SHAPE
LOUVER
LAMINATE
POUNDLINEAR FOOTLENGTHLIBRARYLONG LEG HORIZONTALLONG LEG VERTICAL
LAVATORY
LIGHTWEIGHT
LIQUID SOAP DISPENSER
PAPER TOWEL DISPENSERPARTITION
PRESSURE TREATED
POLYVINYL CHLORIDEPAVEMENT
COURSE
DETAIL
DIAMETER
FIRE EXTINGUISHER
ADJUSTABLE
CONSTRUCTION
INCLUDING
ARCHITECTURAL WOODWORK INSTITUTE
ACOUSTICAL
AGGREGATE
BRONZE
FIRE-RETARDANT TREATED WOOD
GRADE
GLAZED STRUCTURAL FACING TILE
INSIDE DIAMETER, DIMENSION
CEMENTITIOUS WOOD FIBER PLANK
COLD-FORMED METAL FRAMING
DISPENSER
GYPSUM
EXTERIOR INSULATED FINISH SYSTEM
ABOVE FINISHED CEILING
HANDICAP ELECTRIC WATER COOLER
GLASS MESH MORTAR UNITS
RESILIANT ATHLETIC FLOORING
RESILIANT WOOD ATHLETIC FLOORING
TEXTILE WALL COVERING
WINDOW
SPLIT FACED
WELDED-WIRE FABRIC
WATER-RESISTIVE TREATED WOOD
WEIGHT
WASTE RECEPTICLE
WATER HEATER
TEACHER CABINET
TOP OF CURBTOILET
TOILET TISSUE DISPENSER
TYPICAL
QUARRY TILE
VINYL WALL COVERING
SAWN CONTROL JOINT
TOP OF MASONRY
WEATHER-STRIP
WATER RESISTANT GYPSUM BACKER BOARD
WATERPROOFINGWEATHERPROOFWOMENWITHOUT
WIND BRACE BASEPLATE
WOODWATER CLOSET
WIND BRACEWITHWATTS
VENT THROUGH ROOF
VESTIBULEVENDINGVINYL COMPOSITION TILEVERTICALVOLTS
UTILITYURINAL SCREENUNLESS OTHERWISE NOTED
TACK SURFACETACK STRIPTACKBOARD
TOILET PARTITIONTOP OF STEEL
TEMPERATURETECHNICAL
TELEPHONE
SUSPENDEDSTRUCTURE, STRUCTURALSTORAGESTEELSTANDARD
SEALED
SEALANT
SOLID SURFACESHOWER RODSQUARE
SANITARY NAPKIN VENDOR
SANITARY NAPKIN DISPOSAL UNIT
SHOWERSHEETSINGLE
SQUARE FEETSECONDARYSMOKE DETECTORSCHEDULESOLID CORE FLUSH VENEER
SUSPENDED ACOUSTICAL CEILING
SERVICE SINK
ROOF VENT
ROOMROUGH OPENING
REQUIRED
REINFORCED, REINFORCEMENTROOF DRAIN
RADIUS
QUALITY ASSURANCE
REFER, REFERENCE
SIMILAR
SPACES
SOLID CORE
TOP OF DRAIN
TOP
CEMENTITIOUS BACKER BOARD
SOUND ABSORBING CONCRETE BLOCK
IMPACT-RESISTANT WALL COVERING
MOUNTED
MINERAL FIBER CEMENT SHINGLES
MASONRY EXPANSION JOINT
OVERHEAD COILING DOOROVERHEAD COILING GRILL
MULTI-TONE COLOR SYSTEM
OVERFLOW ROOF DRAIN
PLASTIC LAMINATE
PLASTIC
MULLION
MIRROR
PLASTER
PAINT GRADEPAINT, PAINTEDPREFINISHEDPREFABRICATEDPAIRPOSITIVE
PANELPLYWOOD
PLATE
PERPENDICULARPENETRATIONPARALLELPUBLIC ADDRESS
PLATE GLASS
OPPOSITE HAND
OPPOSITEOPENING
OVERHEAD
OUTSIDE DIAMETER/DIMENSION
ON CENTER
NUMBERNOT IN CONTRACT
NOT TO SCALE
NEGATIVENOT APPLICABLE
MARKER BOARD
METAL
MILES PER HOUR
MILLIMETERMEMBRANE
MISCELLANEOUS
MINIMUMMIDDLEMANHOLEMANAGERMANUFACTURER
MECHANICAL
MAXIMUM
MEDICINE CABINET
MASONRYMAINTENANCE
MOP BASIN
MASONRY OPENING
REINFORCED CONCRETEREINFORCED CONCRETE PIPE
ROUGH IN
HANDICAPPED
GLASS MESH CONCRETE PANEL
GROUND FACED
STAINLESS STEEL
VERIFY IN FIELD
FIBER REINFORCED GYPSUM BOARD
CENTER TO CENTER
MECHANICAL, ELECTRICAL & PLUMBING
EXISTINGEXISTING RELOCATED
FINISH FLOOR ELEVATION
MEANS ACTUAL FINISHED SIZEMEANS NOMINAL SIZE
RBRH-CONC
BLKHD
FG
HDF
DF
AL.ST.
HLB
JST
INT
HCFV
Fy
FOMFOCFLR
FIN
@A, AMPABABVA/C
APC
ADMIN
AFF
AHJ
ALUMALT
ANODAP
APPROXARCH, ARCHLASS'YAUX
BD
BLKG
BM
BLDG
BOSB, BOTT
BTUBUR
CCAB
CHBDCICJCL, ÇCLGCLOCLRCMU
CH
COLCONCCONNX
CRDRCONT
CTK
CUST
CT
CU
DP
DIM
DBLDEF
DWR
DIAG
DIVDN
DRDS
DWGDWLS
ELECEA
EJ
EF
EL, ELEV
EGSB
EQEQUIPETCEWEWCEXGREXHEXIST, EXGEXPEXPDEXT
FFAFCFD
FGD
FECFF
FLASH
FHC
FOLD PART
FS
FT
FRP
FUR
GGAGALV
GYP.BD.GEN
GC
GL
GND
GB
HBHC
HD
HDGHDWR
HMHORIZ, H
HTHR, HRS
HWD
IAW
IGININC
INSUL
JAN
JT
LLAM
LBLFLGLIBLLHLLV
LAV
LW
LSD
PTDPTN
PT
PVCPVMT
BLK
CRS
DTL
DIA, ø
FE
ADJ.
CONST.
INCL
AWI
ACOU
AGG
BRZ
FR-WD
GD
GSFT
ID
CWFP
LVR
CFMF
DISP
GYP
EIFS
AFC
HEWC
GMMU
RAF
RWAF
TWC
WNDW
SFC
WWF
WR-WD
WT
WR
WH
TC
TOCTLT
TTD
TYP
SNV
QT
SJ
TOM
WSTRIP
WRGBB
WPGWPWOMWO
WBBP
WDWC
WBW/W
VTR
VESTVENDVCTV, VERTV
UTILURS
TKSFTKSTKBD
TPTOS
TEMPTECH
T, TEL
SUSSTRUCT,STRCTSTORSTLSTD
SLD
SNT
SSSRSQ
SND
SIMSHRSH, SHTSGL
SFSECSDSCHEDSCFV
SAC
SSK
RV
RMRO
REQD
REINFRD
R
QA
REF
SPA
SC
TOD
T
CBB
SACB
IRWC
MTD
MFCS
MJ
OCDOCG
MTCS
ORD
PLT
MULL
MIR
PLAS
PNTGRPNTPREFIN, PFPREFABPRPOS
PNLPLYWD
PL, ¶
PERPPENPARPA
PG
OPH
OPPOPNG
OHOFOD
OC
NO, #NIC
NTS
NEGNA
MKBD
MTL,MET
MPH
MMMMB
MISC
MINMIDMHMGRMFR
MECH, MECH'L
MAX
MC
MASMAINT
MB
MO
R.C.
PLAM
RCP
R/I
H/C
GMCP
GFC
S/S
UON
VIF
FRGB
C/C
MEP
(E)(ER)
FFE
1x1 WD1 1/2"x 2 3/4" WD
MISCELLANEOUS ABBREVIATIONS
AIR HANDLING UNITAHU
FOR FIELD FINISHFFF
ABBREVIATIONS PLAN SYMBOLS
3
3A-5
3A-5
3A-5
W1
BA-4
EXISTING CONTOURS
NEW CONTOURS
NEW OR REQUIRED POINT ELEVATION
EXISTING POINT ELEVATION
SECTION
DETAIL
ELEVATION
COLUMN REFERENCE GRID (LETTER, NUMBER)
PARTITION TYPE
WINDOW TYPE
ELEVATION OR WORKING POINT
INDICATES BID ALT. NUMBERSEE SPEC. SECT. NO. 01030
DEMOLITION/CONSTRUCTION NOTE
EXISTING WALL/ ITEM TO REMAIN
NEW WALL/ITEM
WALL/ ITEM TO BE REMOVED
A
1
+ 445
+ 223.4
334
233
METAL (SMALL SCALE)
TERRAZZO
PARTICLE BOARD
PLYWOOD
ROUGH WOOD (CONTINUOUS)
RIGID INSULATION
PLASTER, SAND, CEMENT, GROUT
RESILIENT FLOORING
STONE
POROUS FILL (STONE OR GRAVEL, ETC.)
MATERIAL LEGENDACOUSTICAL CEILING TILE
CUT OR CAST STONE
EARTH / SOIL
GLAZED STRUCTURAL FACING TILE (GSFT)
FINISH WOOD
BATT INSULATION
GLASS
CERAMIC TILE
GYPSUM DRYWALL
METAL (LARGE SCALE)
CONCRETE
CONCRETE MASONRY UNITS (CMU)
BRICK (COMMON OR FACE)
WEATHER RESISTIVE BARRIERWRB
PARALLEL STRAND LUMBERPSL
LAMINATED VENEER LUMBERLVL
ROOF RAFTERRR
SELF ADHERED MEMBRANE FLASHINGSAMF
OVERFRAMING
STOREFRONTSF
TYPICAL ROOM TAG W/ FINISH CODES
FLOORINGBASEWALLCEILING
D-01
UCCC AMEDISYSALTERATION
12/16/201612/16/201612/16/2016
12/16/201612/16/201612/16/201612/16/201612/16/2016
12/16/2016
12/16/2016
12/16/201612/16/201612/16/2016
12/16/201612/16/2016
12/16/201612/16/2016
REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
GENERALSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
A.001
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
ARCHITECTURALSPECIFICATIONS
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
DIVISION 01 - GENERAL REQUIREMENTS DRAWINGS & SPECIFICATIONS
THESE DRAWINGS AND SPECIFICATIONS ARE INTENDED SOLELY FOR USE AS
INSTRUMENTS OF SERVICE TO THE CLIENT RETAINING CDG (CLARK DESIGN GROUP,
PC). ANY USE OR REPRODUCTION WITHOUT CDG’S CONSENT IS PROHIBITED. CDG
ASSUMES NO LIABILITY FOR UNAUTHORIZED USE OF THE DRAWINGS AND
SPECIFICATIONS NOR UNAUTHORIZED MODIFICATIONS OR SUBSTITUTIONS FOR THE
SPECIFIED PRODUCTS WHICH FORM THE DESIGN BASIS OF QUALITY AND
PERFORMANCE.
THESE DOCUMENTS ARE A DIAGRAMMATIC EXPRESSION OF THE DESIGN INTENT TO
PROVIDE COMPLETE AND OPERATIONAL BUILDING SYSTEMS, AND DO NOT PURPORT TO
DEPICT ALL INCIDENTAL ITEMS OR ACCESSORIES NECESSARY FOR ASSEMBLY OR
INSTALLATION. SUFFICIENT INFORMATION IS SUPPLIED FOR EXPERIENCED TRADESMEN
TO ANTICIPATE CRITICAL CONDITIONS AND, IN CONJUNCTION WITH ON-SITE
MEASUREMENTS, ESTIMATE AND LAY-OUT COMPLETED SYSTEMS.
WHERE A CONFLICT IS FOUND BETWEEN THE REQUIREMENTS OF THE ARCHITECT’S
DRAWINGS/SPECS AND THOSE OF HIS CONSULTING ENGINEERS, THE CONTRACTOR
WILL ASSUME THE MORE STRINGENT REQUIREMENT APPLIES FOR THE PURPOSES OF
BIDDING. CONTRACTOR WILL THEN SEEK FROM CDG A DETERMINATION FOR THE
CORRECT INTERPRETATION OF THE DESIGN INTENT.
THE GENERAL CONTRACTOR IS NOT RELIEVED OF HIS RESPONSIBILITY TO ACQUIRE AN
UNDERSTANDING OF DESIGN INTENT FOR THE COMPLETED PROJECT AND ASSURE HIS
SUBCONTRACTORS PROPERLY ADDRESS THE FULL REQUIREMENTS OF THE CONTRACT
DOCUMENTS.
IF DOUBT EXISTS AS TO THE DESIGN INTENT, THE GENERAL CONTRACTOR & HIS
AFFECTED SUBCONTRACTORS SHALL CONFER TO EXAMINE AND ARRIVE AT AN
ASSESSMENT. IF DESIGN INTENT REMAINS UNCLEAR, THE GC WILL PREPARE A
WRITTEN REQUEST FOR DETERMINATION BY CDG WHICH INCLUDES EACH OF THE
FOLLOWING ACTIONS.
1. SUBMIT A DETAILED WRITTEN RECOMMENDATION TO SATISFY THE CONDITION IN QUESTION.
2. ROUTE IT PROMPTLY TO THE OWNER OR HIS REPRESENTATIVE FOR REVIEW AND DETERMINATION.
INTERPRETATION OF THE BID DOCUMENTS
IF THERE IS ANY DOUBT ABOUT THE TRUE MEANING AND INTENT OF THE BID DOCUMENTS, OR IF DISCREPANCIES OR OMISSIONS ARE DISCOVERED WHICH WILL SIGNIFICANTLY ALTER THE PRICE, PERFORMANCE, CODE COMPLIANCE, OR COMPLETION OF THE WORK, THE BIDDER SHALL REQUEST A WRITTEN INTERPRETATION IN WRITING FROM THE ARCHITECT, NO LATER THAN 7 DAYS BEFORE THE BID DATE. SHOULD ANY CONFLICT OR INCONSISTENCY OCCURE IN OR BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, THE CONTRACTOR IS DEEMED TO HAVE ESTIMATED ON THE GREATER QUANTITY OF WORK, THE HIGHEST PRICED MATERIAL OR EQUIPMENT INDICATED, AND ON THE MOST SATISFACTORY WAY OF DOING WORK, UNLESS IT SHALL HAVE ASKED FOR AND OBTAINED WRITTEN DECISION BEFORE SUBMISSION OF ITS BID AS TO WHICH METHODS OR MATERIALS WILL BE REQUIRED. SUBMISSION OF A BID SHALL INDICATE TO THE OWNER THAT THE CONTRACTOR HAS COMPLETELY REVIEWED THE BID DOCUMENTS AND IS SUFFICENTLY FAMILIAR WITH THE PROJECT TO SUBMIT A PROPER BID. THE SUBMISSION OF A BID INDICATES THAT THE CONTRACTOR IS PREPARED TO PROVIDE ALL MATERIALS, LABOR, AND SUPERVISION NECESSARY TO COMPLETE THE PROJECT. BARRING ANY UNFORESEEABLE CONDITIONS, THE CONTRACTOR CAN BUILD THE PROJECT AS PRESENTED IN THE DOCUMENTS AND CAN OBTAIN THE REQUIRED OCCUPANCY AND USE PERMITS REQUIRED FOR THE OWNER’S USE OF THE BUILDING.
REQUIREMENTS OF THE GENERAL CONTRACTOR
SHALL BE LICENSED AND IN GOOD STANDING FOR THE LAWFUL EXECUTION OF THE
CONTRACT FOR CONSTRUCTION WITHIN THE JURISDICTION(S) GOVERNING THE
PROJECT.
SHALL LET SUBCONTRACTS FOR THIS PROJECT ONLY TO ENTITIES WHO COMPLY WITH
THE SAME LICENSE & STANDING REQUIREMENT.
SHALL RETAIN ONLY EXPERIENCED TRADESMEN WITH A RECORD OF NOT LESS THAN 5
YRS EXPERIENCE IN MEETING OR EXCEEDING THE INDUSTRY STANDARDS FOR
PERFORMANCE AND WORKMANSHIP CITED IN THESE CONTRACT DOCUMENTS. WHERE
NO STANDARD HAS BEEN CITED, THE WORKMANSHIP SHALL CONFORM TO THE
STANDARD FO CARE APPROPRIATE TO THE TRADE IN THE REGION WHERE THE
PROJECT IN LOCATED.
PROVIDE ALL WORK IN FULL COMPLIANCE WITH FEDERAL, STATE, AND LOCAL
AUTHORITIES HAVING JURISDICTION OVER THE PROJECT.
SHALL NOTIFY THE OWNER’S REPRESENTATIVE OF ANY OMISSIONS OR DISCREPANCIES
UPON DISCOVERY, AND SHALL SUBMIT HIS RECOMMENDATIONS FOR MATERIALS &
METHODS FOR CORRECTION OR REMEDY WITH REPORT OF DISCOVERY.
SHALL PROVIDE ALL MATERIAL, EQUIPMENT, LABOR, TOOLS, AND SERVICES
NECESSARY TO COMPLETE THE WORK IN CONFORMANCE WITH THE CONTRACT
DOCUMENTS.
SHALL PROVIDE ONLY NEW AND SOUND MATERIALS FOR THE WORK DESCRIBED IN AND
BY THE CONTRACT DOCUMENTS. USE OR REUSE OF OLD OR SALVAGED COMPONENTS
IS AT THE SOLE DISCRETION OF THE OWNER OR AS DESCRIBED IN THE CONTRACT
DOCUMENTS. IF THE CONTRACTOR WANTS TO OFFER A SUBSTITUTE FOR A PRODUCT
CITED IN THE CONTRACT DOCUMENTS, HE SHALL SUBMIT A WRITTEN PROPOSAL
IDENTIFYING BOTH SUBSTITUTE & BASE-BID PRODUCT FOR REVIEW AND
DETERMINATION. UNREVIEWED, UNAUTHORIZED SUBSTITUTES ARE NOT PERMITTED.
ALL CONSEQUENCES OF REMOVAL, CORRECTION OR REPLACEMENT WILL BE THE
EXPENSE OF THE GC.
UNLESS OTHERWISE INDICATED, THE GENERAL CONTRACTOR WILL INCLUDE AS A PART
OF HIS SCOPE OF WORK AND EXPENSE:
1. ACQUIRING ALL BUILDING PERMITS, LANDFILL TAXES, USE TAXES, SALES TAX, INSPECTION FEES AND OTHER CHARGES ASSOCIATED WITH THE LAWFUL EXECUTION OF THE PROJECT.
2. BUILDER’S RISK (“ALL RISK”) INSURANCE TO COVER THE COST OF THIS WORK AND ALL COVERAGE AS DEFINED IN ARTICLE II OF GENERAL CONDITIONS (A201). PROVIDE THE OWNER WITH A CERTIFICATE OF CONTRACTOR’S INSURANCE.
3. PROVIDE LICENSE ENGINEERING SERVICES FOR: ROUGH CONSTRUCTION “STAKE-OUT” (FOR OWNER APPROVAL). FINAL CONSTRUCTION STAKING (APPROVED BUILDING
POSITION). 4. THE SERVICES OF AN INDEPENDENT TESTING FIRM, MUTUALLY
ACCEPTABLE TO CDG, FOR QUALITY ASSURANCE REPORTING ON SOLI CONDITIONS & COMPACTION, ROCK REMOVAL, & COMPLIANCE WITH SPECIFIED CONCRETE PERFORMANCE.
THE GENERAL CONTRACTOR IS RESPONSIBLE FOR WORKER & PUBLIC SAFETY
ASSOCIATED WITH THE EXECUTION OF WORK AT THE SITE. GC WILL COORDINATE THE
WORK OF THE TRADES AND COOPERATE WITH THE OWNER TO OBTAIN A SAFE SITE
WITH LEAST INTERFERENCE TO THE OWNER’S FACILITIES AND ON-GOING OPERATION.
COMPLY WITH SAFETY REQUIREMENTS & DIRECTIVES OF ALL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT.
MAINTAIN A CLEAN & ORDERLY CONSTRUCTION SITE AT ALL TIMES. CLEAR SITE OF
WASTE & DEBRIS AT THE CLOSE OF EACH WORK DAY. CONTINUE SITE MAINTENANCE
AND CLEAN-UP ROUTINES THROUGH SUBSTANTIAL COMPLETION TO ACCEPTANCE FOR
FINAL PAYMENT.
SUBMIT AT A MINIMUM THE FOLLOWING SHOP DRAWING INFORMATION (3 COPIES EACH)
TOGETHER WITH SUBMITTALS REQUIRED BY ANY OTHER SECTION OF THE ARCHITECT’S
OR ENGINEER’S SPECIFICATIONS.
5. STRUCTURAL STEEL LAYOUT AND DETAILS. 6. PREFABRICATED STRUCTURAL WOOD COMPONENTS &
ASSEMBLIES INCLUDING LAYOUT, ANCHORS, & TECH SHEETS. 7. SOIL & CONCRETE TESTS AND REPORTS. 8. MECHANICAL/ELECTRICAL/PLUMBING EQUIPMENT AND
FIXTURES. 9. DOORS/WINDOWS/FINISHED HARDWARE. 10. OTHER ITEMS INDICATED ON THE DRAWINGS OR
SPECIFICATIONS. 11. FIRE DETECTION & SUPPRESSION DESIGN LAYOUT,
COMPUTATIONS AND EQUIPMENT INCLUDING NICET-CERTIFIED DESIGNER’S SEAL.
END OF SECTION
DIVISION 02 – EXISTING CONDITIONS SECTION 024116 DEMOLITION
PART 1 GENERAL 1. SUMMARY
A. THIS SECTION INCLUDES THE FOLLOWING: 1) DEMOLITION AND REMOVAL OF BUILDINGS SUB SYSTEM. 2) ABANDONING IN PLACE/REMOVING BELOW-GRADE CONSTRUCTION. 3) DISCONNECTING, CAPPING OR SEALING, AND ABANDONING IN-PLACE OR
REMOVING SITE UTILITIES. 4) SALVAGING ITEMS FOR REUSE BY OWNER.
2. DEFINITIONS A. DEMOLISH: COMPLETELY REMOVE AND LEGALLY DISPOSE OF
OFF-SITE. B. RECYCLE: RECOVERY OF DEMOLITION WASTE FOR SUBSEQUENT
PROCESSING IN PREPARATION FOR REUSE. C. SALVAGE: CAREFULLY DETACH FROM EXISTING CONSTRUCTION,
IN A MANNER TO PREVENT DAMAGE, AND DELIVER TO OWNER READY FOR REUSE. INCLUDE FASTENERS OR BRACKETS NEEDED FOR REATTACHMENT ELSEWHERE.
3. MATERIALS OWNERSHIP A. UNLESS OTHERWISE INDICATED, DEMOLITION WASTE BECOMES
PROPERTY OF CONTRACTOR. B. HISTORIC ITEMS, RELICS, ANTIQUES, AND SIMILAR OBJECTS
INCLUDING, BUT NOT LIMITED TO, CORNERSTONES AND THEIR CONTENTS, COMMEMORATIVE PLAQUES AND TABLETS, AND OTHER ITEMS OF INTEREST OR VALUE TO OWNER THAT MAY BE UNCOVERED DURING DEMOLITION REMAIN THE PROPERTY OF OWNER.
1) CAREFULLY SALVAGE IN A MANNER TO PREVENT DAMAGE AND PROMPTLY RETURN TO OWNER.
4. SUBMITTALS A. QUALIFICATION DATA: FOR REFRIGERANT RECOVERY
TECHNICIAN. B. INVENTORY: SUBMIT A LIST OF ITEMS TO BE REMOVED AND
SALVAGED AND DELIVER TO OWNER PRIOR TO START OF DEMOLITION.
5. QUALITY ASSURANCE A. REGULATORY REQUIREMENTS: COMPLY WITH GOVERNING EPA
NOTIFICATION REGULATIONS BEFORE BEGINNING DEMOLITION. COMPLY WITH HAULING AND DISPOSAL REGULATIONS OF AUTHORITIES HAVING JURISDICTION.
B. STANDARDS: COMPLY WITH ANSI A10.6 AND NFPA 241. 6. PROJECT CONDITIONS
A. BUILDINGS TO BE DEMOLISHED WILL BE VACATED AND THEIR USE DISCONTINUED BEFORE START OF THE WORK.
B. OWNER ASSUMES NO RESPONSIBILITY FOR BUILDINGS AND STRUCTURES TO BE DEMOLISHED.
1) CONDITIONS EXISTING AT TIME OF INSPECTION FOR BIDDING PURPOSE WILL BE MAINTAINED BY OWNER AS FAR AS PRACTICAL.
2) BEFORE BUILDING DEMOLITION, OWNER WILL REMOVE THE FOLLOWING ITEMS: A) ALL EXISTING FURNITURE AND BUILDING EQUIPMENT
C. HAZARDOUS MATERIALS: IT IS NOT EXPECTED THAT HAZARDOUS MATERIALS WILL BE ENCOUNTERED IN THE WORK.
1) HAZARDOUS MATERIALS WILL BE REMOVED BY OWNER BEFORE START OF THE WORK.
2) IF MATERIALS SUSPECTED OF CONTAINING HAZARDOUS MATERIALS ARE ENCOUNTERED, DO NOT DISTURB; IMMEDIATELY NOTIFY ARCHITECT AND OWNER. HAZARDOUS MATERIALS WILL BE REMOVED BY OWNER UNDER A SEPARATE CONTRACT.
D. ON-SITE STORAGE OR SALE OF REMOVED ITEMS OR MATERIALS IS NOT PERMITTED.
PART 1 EXECUTION 1. EXAMINATION
A. VERIFY THAT UTILITIES HAVE BEEN DISCONNECTED AND CAPPED BEFORE STARTING DEMOLITION OPERATIONS.
B. REVIEW PROJECT RECORD DOCUMENTS OF EXISTING CONSTRUCTION PROVIDED BY OWNER. OWNER DOES NOT GUARANTEE THAT EXISTING CONDITIONS ARE SAME AS THOSE INDICATED IN PROJECT RECORD DOCUMENTS.
C. INVENTORY AND RECORD THE CONDITION OF ITEMS TO BE REMOVED AND SALVAGED.
D. VERIFY THAT HAZARDOUS MATERIALS HAVE BEEN REMEDIATED BEFORE PROCEEDING WITH BUILDING DEMOLITION OPERATIONS.
2. PREPARATION A. REFRIGERANT: REMOVE REFRIGERANT FROM MECHANICAL
EQUIPMENT ACCORDING TO 40 CFR 82 AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION BEFORE STARTING DEMOLITION.
B. EXISTING UTILITIES: LOCATE, IDENTIFY, DISCONNECT, AND SEAL OR CAP OFF INDICATED UTILITIES SERVING BUILDINGS AND STRUCTURES TO BE DEMOLISHED.
1) OWNER WILL ARRANGE TO SHUT OFF INDICATED UTILITIES WHEN REQUESTED BY CONTRACTOR.
2) ARRANGE TO SHUT OFF INDICATED UTILITIES WITH UTILITY COMPANIES. 3) IF REMOVAL, RELOCATION, OR ABANDONMENT OF UTILITY SERVICES WILL
AFFECT ADJACENT OCCUPIED BUILDINGS, THEN PROVIDE TEMPORARY UTILITIES THAT BYPASS BUILDINGS AND STRUCTURES TO BE DEMOLISHED AND THAT MAINTAIN CONTINUITY OF SERVICE TO OTHER BUILDINGS AND STRUCTURES.
4) CUT OFF PIPE OR CONDUIT A MINIMUM OF 24 INCHES (610 MM) BELOW GRADE. CAP, VALVE, OR PLUG AND SEAL REMAINING PORTION OF PIPE OR CONDUIT AFTER BYPASSING ACCORDING TO REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
C. EXISTING UTILITIES: REFER TO MEP SPECIFICATIONS FOR SHUTTING OFF, DISCONNECTING, REMOVING, AND SEALING OR CAPPING UTILITIES. DO NOT START DEMOLITION WORK UNTIL UTILITY DISCONNECTING AND SEALING HAVE BEEN COMPLETED AND VERIFIED IN WRITING.
D. TEMPORARY SHORING: PROVIDE AND MAINTAIN INTERIOR AND EXTERIOR SHORING, BRACING, OR STRUCTURAL SUPPORT TO PRESERVE STABILITY AND PREVENT UNEXPECTED MOVEMENT OR COLLAPSE OF CONSTRUCTION BEING DEMOLISHED.
5) STRENGTHEN OR ADD NEW SUPPORTS WHEN REQUIRED DURING PROGRESS OF DEMOLITION.
E. SALVAGED ITEMS: COMPLY WITH THE FOLLOWING: 6) CLEAN SALVAGED ITEMS OF DIRT AND DEMOLITION DEBRIS. 7) PACK OR CRATE ITEMS AFTER CLEANING. IDENTIFY CONTENTS OF
CONTAINERS. 8) STORE ITEMS IN A SECURE AREA UNTIL DELIVERY TO OWNER. 9) TRANSPORT ITEMS TO STORAGE AREA DESIGNATED BY OWNER. 10) PROTECT ITEMS FROM DAMAGE DURING TRANSPORT AND STORAGE.
3. PROTECTION A. EXISTING FACILITIES: PROTECT ADJACENT WALKWAYS, LOADING
DOCKS, BUILDING ENTRIES, AND OTHER BUILDING FACILITIES DURING DEMOLITION OPERATIONS. MAINTAIN EXITS FROM EXISTING BUILDINGS.
B. EXISTING UTILITIES: MAINTAIN UTILITY SERVICES TO REMAIN AND PROTECT FROM DAMAGE DURING DEMOLITION OPERATIONS.
1) DO NOT INTERRUPT EXISTING UTILITIES SERVING ADJACENT OCCUPIED OR OPERATING FACILITIES UNLESS AUTHORIZED IN WRITING BY OWNER AND AUTHORITIES HAVING JURISDICTION.
2) PROVIDE TEMPORARY SERVICES DURING INTERRUPTIONS TO EXISTING UTILITIES, AS ACCEPTABLE TO OWNER AND AUTHORITIES HAVING JURISDICTION. A) PROVIDE AT LEAST 72 HOURS' NOTICE TO OCCUPANTS OF AFFECTED
BUILDINGS IF SHUTDOWN OF SERVICE IS REQUIRED DURING CHANGEOVER.
C. TEMPORARY PROTECTION: ERECT TEMPORARY PROTECTION, SUCH AS WALKS, FENCES, RAILINGS, CANOPIES, AND COVERED PASSAGEWAYS, WHERE REQUIRED BY AUTHORITIES HAVING JURISDICTION, AND AS INDICATED. COMPLY WITH REQUIREMENTS IN DIVISION 01 SECTION "TEMPORARY FACILITIES AND CONTROLS."
3) PROTECT ADJACENT BUILDINGS AND FACILITIES FROM DAMAGE DUE TO DEMOLITION ACTIVITIES.
4) PROTECT EXISTING SITE IMPROVEMENTS, APPURTENANCES, AND LANDSCAPING TO REMAIN.
5) PROVIDE TEMPORARY BARRICADES AND OTHER PROTECTION REQUIRED TO PREVENT INJURY TO PEOPLE AND DAMAGE TO ADJACENT BUILDINGS AND FACILITIES TO REMAIN.
6) PROVIDE PROTECTION TO ENSURE SAFE PASSAGE OF PEOPLE AROUND BUILDING DEMOLITION AREA AND TO AND FROM OCCUPIED PORTIONS OF ADJACENT BUILDINGS AND STRUCTURES.
7) PROTECT WALLS, WINDOWS, ROOFS, AND OTHER ADJACENT EXTERIOR CONSTRUCTION THAT ARE TO REMAIN AND THAT ARE EXPOSED TO BUILDING DEMOLITION OPERATIONS.
D. REMOVE TEMPORARY BARRIERS AND PROTECTIONS WHERE HAZARDS NO LONGER EXIST. WHERE OPEN EXCAVATIONS OR
OTHER HAZARDOUS CONDITIONS REMAIN, LEAVE TEMPORARY BARRIERS AND PROTECTIONS IN PLACE.
4. DEMOLITION, GENERAL A. GENERAL: DEMOLISH INDICATED EXISTING BUILDINGS
COMPLETELY. USE METHODS REQUIRED TO COMPLETE THE WORK WITHIN LIMITATIONS OF GOVERNING REGULATIONS AND AS FOLLOWS:
1) DO NOT USE CUTTING TORCHES UNTIL WORK AREA IS CLEARED OF FLAMMABLE MATERIALS. MAINTAIN PORTABLE FIRE-SUPPRESSION DEVICES DURING FLAME-CUTTING OPERATIONS.
2) MAINTAIN FIRE WATCH DURING AND FOR AT LEAST 2 HOURS AFTER FLAME CUTTING OPERATIONS.
3) MAINTAIN ADEQUATE VENTILATION WHEN USING CUTTING TORCHES. 4) LOCATE BUILDING DEMOLITION EQUIPMENT AND REMOVE DEBRIS AND
MATERIALS SO AS NOT TO IMPOSE EXCESSIVE LOADS ON SUPPORTING WALLS, FLOORS, OR FRAMING.
B. ENGINEERING SURVEYS: DURING DEMOLITION, PERFORM SURVEYS TO DETECT HAZARDS THAT MAY RESULT FROM BUILDING DEMOLITION ACTIVITIES.
C. SITE ACCESS AND TEMPORARY CONTROLS: CONDUCT BUILDING DEMOLITION AND DEBRIS-REMOVAL OPERATIONS TO ENSURE MINIMUM INTERFERENCE WITH ROADS, STREETS, WALKS, WALKWAYS, AND OTHER ADJACENT OCCUPIED AND USED FACILITIES.
5) DO NOT CLOSE OR OBSTRUCT STREETS, WALKS, WALKWAYS, OR OTHER ADJACENT OCCUPIED OR USED FACILITIES WITHOUT PERMISSION FROM OWNER AND AUTHORITIES HAVING JURISDICTION. PROVIDE ALTERNATE ROUTES AROUND CLOSED OR OBSTRUCTED TRAFFIC WAYS IF REQUIRED BY AUTHORITIES HAVING JURISDICTION.
USE WATER MIST AND OTHER SUITABLE METHODS TO LIMIT SPREAD OF DUST AND DIRT.
COMPLY WITH GOVERNING ENVIRONMENTAL-PROTECTION
1) REGULATIONS. DO NOT USE WATER WHEN IT MAY DAMAGE ADJACENT CONSTRUCTION OR CREATE HAZARDOUS OR OBJECTIONABLE CONDITIONS, SUCH AS ICE, FLOODING, AND POLLUTION.
D. EXPLOSIVES: USE OF EXPLOSIVES IS NOT PERMITTED. 5. DEMOLITION BY MECHANICAL MEANS
A. PROCEED WITH DEMOLITION OF STRUCTURAL FRAMING MEMBERS SYSTEMATICALLY, FROM HIGHER TO LOWER LEVEL. COMPLETE BUILDING DEMOLITION OPERATIONS ABOVE EACH FLOOR OR TIER BEFORE DISTURBING SUPPORTING MEMBERS ON THE NEXT LOWER LEVEL.
B. REMOVE DEBRIS FROM ELEVATED PORTIONS OF THE BUILDING BY CHUTE, HOIST, OR OTHER DEVICE THAT WILL CONVEY DEBRIS TO GRADE LEVEL IN A CONTROLLED DESCENT..
6. REPAIRS A. PROMPTLY REPAIR DAMAGE TO ADJACENT BUILDINGS CAUSED BY
DEMOLITION OPERATIONS. 7. DISPOSAL OF DEMOLISHED MATERIALS
A. REMOVE DEMOLITION WASTE MATERIALS FROM PROJECT SITE. B. REMOVE DEMOLITION WASTE MATERIALS FROM PROJECT SITE
AND LEGALLY DISPOSE OF THEM IN AN EPA-APPROVED LANDFILL ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION.
1) DO NOT ALLOW DEMOLISHED MATERIALS TO ACCUMULATE ON-SITE. 2) REMOVE AND TRANSPORT DEBRIS IN A MANNER THAT WILL PREVENT
SPILLAGE ON ADJACENT SURFACES AND AREAS. C. RECYCLE BUILDING MATERIALS TO THE MAXIMUM EXTENT
POSSIBLE. D. DO NOT BURN DEMOLISHED MATERIALS.
8. CLEANING A. CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS OF DUST,
DIRT, AND DEBRIS CAUSED BY BUILDING DEMOLITION OPERATIONS. RETURN ADJACENT AREAS TO CONDITION EXISTING BEFORE BUILDING DEMOLITION OPERATIONS BEGAN.
END OF SECTION
DIVISION 03 - CONCRETE SECTION 03300 CAST-IN-PLACE-CONCRETE PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE CAST-IN-PLACE CONCRETE PATCHING WHERE DEMOLISHED TO INSTALL PLUMBING AND REPAIR CRACKS.
B. VAPOR BARRIER, SEAM TAPE, AND MASTIC FOR INSTALLATION UNDER CONCRETE SLABS
1.2 SUBMITTALS A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION
INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED. B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS INDICATING MATERIAL
CHARACTERISTICS, DETAILS OF CONSTRUCTION, CONNECTIONS, AND RELATIONSHIP WITH ADJACENT CONSTRUCTION. (NOT REQUIRED THIS PROJECT) 1. SHOP DRAWINGS SHALL BE PREPARED AND STAMPED BY A QUALIFIED
ENGINEER LICENSED IN THE JURISDICTION OF THE PROJECT. C. MIX DESIGN: SUBMIT FOR APPROVAL MIX DESIGN PROPOSED FOR USE.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. STANDARDS: 1. ACI 301, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS. 2. ACI 318, BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE,
AND CRSI MANUAL OF STANDARD PRACTICE. C. FLOOR FLATNESS AND LEVELNESS TOLERANCES:
1. SUBFLOORS UNDER MATERIALS SUCH AS CONCRETE TOPPINGS, CERAMIC TILE, AND SAND BED TERRAZZO: ACI 302.1R AND ASTM E 1155, FLOOR FLATNESS (FF) OF 15, FLOOR LEVELNESS (FL) OF 13.
2. SUBFLOORS UNDER MATERIALS SUCH AS VINYL TILE, EPOXY TOPPINGS, PAINT, AND CARPET: ACI 302.1R AND ASTM E 1155, FLOOR FLATNESS (FF) OF 20, FLOOR LEVELNESS (FL) OF 17.
PART 1 PRODUCTS 1.1 MATERIALS
A. CAST-IN-PLACE CONCRETE: 1. APPLICATION: SLABS ON GRADE. 2. FINISH FOR SLAB: SMOOTH FINISH
B. VAPOR BARRIER PRODUCTS: 1. BASIS OF DESIGN: STEGO WRAP VAPOR BARRIER (15 MIL) BY STEGO
INDUSTRIES LLC, (887)464.7834 WWW.STEGOINDUSTRIES.COM INSTALL VAPOR BARRIER PRODUCT TO THE STRICT SPECIFICATIONS SET
FORTH BY THE MANUFACTURER. 2. ACCESSORIES
SEAM TAPE BY STEGO A. VAPOR PROOFING MASTIC BY STEGO
PART 1 EXECUTION 1.1 INSTALLATION
A. COMPLY WITH ASTM C 94. DO NOT CHANGE MIX DESIGN WITHOUT APPROVAL. CALCIUM CHLORIDE ADMIXTURES ARE NOT PERMITTED.
B. CHAMFER EXPOSED EDGES/CORNERS TO PROVIDE STRAIGHT LINES. C. TOLERANCE: PLUS 1/8" IN 10" FOR GRADE, ALIGNMENT, AND STRAIGHTNESS. D. CONSTRUCTION JOINTS: USE KEYWAYS, CONTINUE REINFORCEMENT THROUGH
JOINT. E. EXPANSION JOINTS: FOR EXTERIOR WORK LOCATE 30' O.C. AT APPROVED
LOCATIONS. PROVIDE SMOOTH DOWELS ACROSS JOINT WHICH PERMIT 1" HORIZONTAL MOVEMENT AND NO VERTICAL SHEAR MOVEMENT.
F. ISOLATION JOINTS: PROVIDE BETWEEN SLABS AND VERTICAL ELEMENTS SUCH AS COLUMNS AND STRUCTURAL WALLS.
G. CONTROL JOINTS: PROVIDE SAWN OR TOOLED JOINTS OR REMOVEABLE INSERT STRIPS; DEPTH EQUAL TO 1/4 SLAB THICKNESS. SPACING AS REQUIRED AND APPROVED.
H. WALL FINISHES: AS-CAST AND PATCHED FOR CONCEALED WORK; RUBBED SMOOTH, FILLED AND CEMENT PASTE COATED FOR EXPOSED WORK.
I. SLAB FINISHES: OBTAIN SAMPLE APPROVAL BEFORE BEGINNING WORK. 1. SCRATCH: FOR SURFACES TO RECEIVE MORTAR SETTING BEDS OR
CEMENTITIOUS FLOORING MATERIALS. 2. TROWEL: HARD, SMOOTH, UNIFORM SURFACE FOR AREAS TO RECEIVE
RESILIENT FLOORING, CARPET, OR OTHER THIN FINISH MATERIAL. 3. BROOM: AFTER TROWEL FINISHING, ROUGHEN SURFACE BY FINE
BROOMING PERPENDICULAR TO TRAFFIC DIRECTION FOR EXPOSED EXTERIOR WALKS, STEPS AND RAMPS.
4. NON-SLIP AGGREGATE: AFTER TROWEL FINISHING, UNIFORMLY TROWEL 25-LBS./100 S. F. OF DAMP NON-SLIP AGGREGATE INTO SURFACE. CURE, THEN RUB LIGHTLY TO EXPOSE AGGREGATE. USE FOR INTERIOR EXPOSED CONCRETE STAIRS AND RAMPS.
5. EXPOSED AGGREGATE: USE CHEMICAL RETARDER OR TAMP AGGREGATE
INTO WET CONCRETE AND EXPOSE BY BRUSHING WITH WATER. USE WHERE INDICATED.
6. HARDENER FINISH: FOR EXPOSED INTERIOR CONCRETE FLOORS. FOLLOW MANUFACTURER'S DIRECTIONS.
7. FORMED FINISH: SMOOTH FOR CONCRETE EXPOSED TO VIEW AND WHERE COATED, COVERED WITH WATER-PRFG OR OTHER DIRECT-APPLIED MATERIAL.
J. CURE AND PROTECT WORK. REPORT DEFECTIVE WORK IN WRITING.
K. INSTALL VAPOR BARRIER IN ACCORDANCE WITH MANUFACTURER’S INSTRUCTIONS AND ASTM E 1643. 1. UNROLL VAPOR BARRIER WITH THE LONGEST DIMENSION PARALLEL WITH
THE DIRECTION OF THE CONCRETE PLACEMENT. 2. LAP VAPOR BARRIER OVER FOOTINGS AND/OR SEAL TO FOUNDATION WALLS. 3. OVERLAP JOINTS 6 INCHES AND SEAL WITH MANUFACTURER’S TAPE. 4. SEAL ALL PENETRATIONS (INCLUDING PIPES) PER MANUFACTURER’S
INSTRUCTIONS. 5. NO PENETRATION OF THE VAPOR BARRIER IS ALLOWED EXCEPT FOR
REINFORCING STEEL AND PERMANENT UTILITIES. 6. REPAIR DAMAGED AREAS BY CUTTING PATCHES OF VAPOR BARRIER,
OVERLAPPING DAMAGED AREA 6 INCHES AND TAPING ALL SIDES WITH TAPE.
END OF SECTION
DIVISION 06 - WOOD AND PLASTICS REFER TO STRUCTURAL DRAWINGS BY THE ENGINEER OF RECORD FOR THIS PROJECT. THE REQUIREMENTS OF THE ENGINEER SUPERCEDE THE FOLLOWING IN THE EVENT OF CONFLICT; HOWEVER, IN THE ABSENCE OF GOVERNING REQUIREMENTS BY THE STRUCTURAL ENGINEER, THE FOLLOWING MINIMUM REQUIREMENTS APPLY FOR THE WORK OF THIS PROJECT. SECTION 06200 INTERIOR FINISH CARPENTRY PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE INTERIOR FINISH CARPENTRY, ARCHITECTURAL WOODWORK AND COUNTERTOPS.
B. SEE FINISH DRAWINGS AND NOTES FOR CASEWORK SPECIFICATIONS 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS INDICATING MATERIAL CHARACTERISTICS, DETAILS OF CONSTRUCTION, CONNECTIONS, AND RELATIONSHIP WITH ADJACENT CONSTRUCTION.
C. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. STANDARDS: ARCHITECTURAL WOODWORK INSTITUTE (AWI) 'ARCHITECTURAL WOODWORK STANDARDS.'
C. PRESERVATIVE TREATMENT: NONPRESSURE METHOD, EXTERIOR TYPE, AWPA N1 D. FIRE-RETARDANT TREATMENT:
1. LUMBER: AWPA C20, NON-CORROSIVE TYPE. 2. PLYWOOD: AWPA C27, NON-CORROSIVE TYPE. 3. PARTICLEBOARD: ASTM E 84, FLAME SPREAD 20 OR LESS.
E. WOOD PRODUCTS: COMPLY WITH THE FOLLOWING: 1. HARDBOARD: AHA A135.4. 2. MEDIUM-DENSITY FIBERBOARD: ANSI A208.2, GRADE MD-EXTERIOR GLUE. 3. PARTICLEBOARD: ANSI A208.1, GRADE M-2-EXTERIOR GLUE. 4. SOFTWOOD PLYWOOD: DOC PS 1, MEDIUM DENSITY OVERLAY. 5. HARDWOOD PLYWOOD AND FACE VENEERS: HPVA HP-1.
PART 1 PRODUCTS 1.1 MATERIALS
A. INTERIOR TRIMS AND MOULDINGS 1. SPECIES FOR TRANSPARENT FINISH: ANY CLOSED-GRAIN HARDWOOD. 2. SPECIES FOR OPAQUE FINISH: ANY CLOSED-GRAIN HARDWOOD.
B. INTERIOR SOLID SURFACING MATERIAL COUNTERTOPS: 1. MANUFACTURERS: FORMICA OR APPROVED EQUAL 2. TYPE: HOMOGENEOUS SOLID SHEETS ANSI Z124.3, FOR TYPE 5 OR TYPE
6, WITHOUT A PRECOATED FINISH. 3. EDGE: EASED 4. SPECIAL FABRICATION: DROPPED IN STAINLESS STEAL.
PART 1 EXECUTION 1.1 INSTALLATION
A. PROVIDE WORK TO SIZES, SHAPES, AND PROFILES INDICATED. INSTALL WORK TO COMPLY WITH QUALITY STANDARDS REFERENCED. BACK PRIME WORK AND INSTALL PLUMB, LEVEL AND STRAIGHT WITH TIGHT JOINTS; SCRIBE WORK TO FIT.
B. QUALITY STANDARD: INSTALL WOODWORK TO COMPLY WITH AWI STANDARDS FOR THE SAME GRADE SPECIFIED FOR TYPE OF WOODWORK INVOLVED.
C. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION. COORDINATE WITH WORK OF OTHER SECTIONS.
D. COMPLY WITH MANUFACTURER'S REQUIREMENTS FOR CUTTING, HANDLING, FASTENING AND WORKING TREATED MATERIALS.
E. REPAIR MINOR DAMAGE, CLEAN AND PROTECT. END OF SECTION
DIVISION 07 - THERMAL AND MOISTURE PROTECTION SECTION 07210 BUILDING INSULATION PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE THERMAL INSULATION AND VAPOR RETARDERS. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SUBMIT FOR APPROVAL TEST REPORTS. 1.3 QUALITY ASSURANCE
A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
PART 1 PRODUCTS 1.1 MATERIALS -
A. BOARD INSULATION: 1. MANUFACTURER: OWENS CORNING OR EQUAL. 2. APPLICATION: WALL INFILL. 3. TYPE: EXTRUDED POLYSTYRENE, RIGID.
STANDARD: ASTM C 578. 4. R-VALUE: 10 MINIMUM
PART 1 EXECUTION 1.1 INSTALLATION
A. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION. COORDINATE WITH WORK OF OTHER SECTIONS. PROVIDE FULL THICKNESS IN ONE LAYER OVER ENTIRE AREA, TIGHTLY FITTING AROUND PENETRATIONS.
B. POUR LOOSE INSULATION INTO CAVITIES INDICATED; PROVIDE UNIFORM COVERAGE AT CORRECT DENSITY AND THICKNESS.
C. INSTALL VAPOR RETARDER OVER ENTIRE AREA OF INSIDE FACE OF EXTERIOR WALLS AND ELSEWHERE AS INDICATED. SEAL ALL SEAMS AND AROUND PERIMETER AND PENETRATIONS WITH DUCT TAPE TO FORM A CONTINUOUS VAPOR RETARDER FREE OF HOLES.
D. PROTECT INSTALLED INSULATION AND VAPOR RETARDER.
END OF SECTION SECTION 07900 JOINT SEALERS
PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE JOINT SEALERS AND FILLERS. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED. B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
1. INCLUDE MANUFACTURERS FULL RANGE OF COLOR AND FINISH OPTIONS IF ADDITIONAL SELECTION IS REQUIRED.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. B. FIELD-CONSTRUCTED MOCK-UPS: EACH JOINT TYPE.
PART 2 PRODUCTS 2.1 MATERIALS
A. INTERIOR JOINTS, LIMITED MOVEMENT, ACRYLIC: 1. MANUFACTURERS: LIQUID NAILS BRAND; PABCO GYPSUM; TOP GUN BRAND. 2. MATERIALS: ACRYLIC-EMULSION, ASTM C 834.
B. INTERIOR JOINTS, SANITARY SILICONE: 1. MANUFACTURERS: MOMENTIVE PERFORMANCE MATERIALS - GE EXCLUSIVE LICENSEE. 2. MATERIALS: ONE-PART MILDEW-RESISTANT SILICONE SEALANT, ASTM C 920.
PART 3 EXECUTION 3.1 INSTALLATION
A. EXAMINE SUBSTRATE; REPORT UNSATISFACTORY CONDITIONS IN WRITING. BEGINNING WORK MEANS ACCEPTANCE OF SUBSTRATES. B. PROVIDE SEALANTS IN COLORS AS SELECTED FROM MANUFACTURER'S STANDARDS. C. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS. CLEAN AND PRIME JOINTS, AND INSTALL BOND BREAKERS, BACKER RODS AND SEALANT AS RECOMMENDED BY MANUFACTURERS. D. DEPTH SHALL EQUAL WIDTH UP TO 1/2 INCH WIDE; DEPTH SHALL EQUAL 1/2 WIDTH FOR JOINTS OVER 1/2 INCH WIDE. E. CURE AND PROTECT SEALANTS AS DIRECTED BY MANUFACTURERS. REPLACE OR RESTORE DAMAGED SEALANTS. CLEAN ADJACENT SURFACES TO REMOVE SPILLAGE.
END OF SECTION
DIVISION 08 - OPENINGS
SECTION 08110 STEEL FRAMES PART 1 GENERAL 1.2 SUMMARY
A. PROVIDE STEEL DOORS AND FRAMES. 1.3 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS INDICATING MATERIAL CHARACTERISTICS, DETAILS OF CONSTRUCTION, CONNECTIONS, AND RELATIONSHIP WITH ADJACENT CONSTRUCTION.
1.4 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. STANDARDS: ANSI/SDI-100, RECOMMENDED SPECIFICATIONS FOR STANDARD STEEL DOORS AND FRAMES.
C. PERFORMANCE STANDARDS: 1. FIRE-RATED ASSEMBLIES: NFPA 80, AND ACCEPTABLE TESTING AGENCY
LISTING. 2. THERMAL-RATED ASSEMBLIES AT EXTERIOR: ASTM C 236 OR ASTM C 976. 3. SOUND-RATED ASSEMBLIES AT MECHANICAL ROOMS: ASTM E 1408, AND
ASTM E 413. PART 1 PRODUCTS 1.1 MATERIALS
A. INTERIOR STEEL FRAMES: 1. MANUFACTURERS: PHILLIP MANUF., CO.; CURRIES, CO.; CECO CORP.;
PIONEER INDUSTRIES. 2. MATERIAL: MINIMUM 16 GAUGE STEEL SHEET. 3. CORNERS: MITERED OR COPED. 4. TYPE: STD KNOCKDOWN FRAME 5. FINISH: FACTORY PRIMED AND FIELD PAINTED.
PART 1 EXECUTION 1.1 INSTALLATION
A. FABRICATE WORK TO BE RIGID, NEAT AND FREE FROM SEAMS, DEFECTS, DENTS, WARP, BUCKLE, AND EXPOSED FASTENERS. INSTALL DOORS AND FRAMES IN COMPLIANCE WITH SDI-100, NFPA 80, AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
B. PROVIDE THERMALLY IMPROVED DOORS WITH MAXIMUM U-VALUE OF 0.24 BTU/HR./SQ. FT. DEGREE F (ASTM C 236) FOR ALL EXTERIOR DOORS AND ELSEWHERE AS NOTED.
C. PROVIDE ACOUSTICALLY IMPROVED DOORS WITH MINIMUM STC OF 33 (ASTM E 90 AND ASTM E 413) WHERE INDICATED.
D. HARDWARE: PREPARE DOORS AND FRAMES TO RECEIVE HARDWARE ON FINAL SCHEDULE. PROVIDE FOR 3 SILENCERS ON SINGLE DOORFRAMES; 2 ON DOUBLE DOORFRAMES.
E. SHOP FINISH: CLEAN, TREAT AND PRIME PAINT ALL WORK WITH RUST-INHIBITING PRIMER COMPARABLE WITH FINISH PAINT SPECIFIED IN DIVISION 9 SECTION. PROVIDE ASPHALT EMULSION SOUND DEADENING COATING ON CONCEALED FRAME INTERIORS.
F. TOUCH-UP DAMAGED COATINGS READY TO RECEIVE FINISH PAINTING. END OF SECTION SECTION 08210 FLUSH WOOD DOORS PART 1 GENERAL 1.2 SUMMARY
A. PROVIDE FLUSH WOOD DOORS. 1.3 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
C. WARRANTY: SUBMIT MANUFACTURERS STANDARD WARRANTY. INCLUDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE MATERIALS. 1. SOLID-CORE EXTERIOR DOORS: 5 YEARS. 2. SOLID-CORE INTERIOR DOORS: LIFE OF INSTALLATION. 3. HOLLOW-CORE INTERIOR DOORS: 2 YEARS.
1.4 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. QUALITY STANDARDS: [NWWDA I.S.1-A, 'ARCHITECTURAL WOOD FLUSH DOORS.'] [AWI'S 'ARCHITECTURAL WOODWORK STANDARDS.'].
C. FIRE RATED WOOD DOORS: MEET NFPA 80 REQUIREMENTS. PART 1 PRODUCTS 1.1 MATERIALS
A. INTERIOR FLUSH WOOD DOORS: 1. MANUFACTURERS: VT INDUSTRIES, INC.; OSHKOSH ARCHITECTURAL
DOOR CO.; GRAHAM. 2. TYPE: SOLID CORE. 3. THICKNESS: 1-3/4 INCHES THICK. 4. FRAMES: HOLLOW METAL. 5. SPECIESWHITE SELECT BIRCH INTERIOR DOORS 6. FINISH: MATCH SUITE: 134 7. CUT: MATCH EXISTING 8. MATCHING: MATCH EXISTING
PART 1 EXECUTION 1.1 INSTALLATION
A. COMPLY WITH NWMA I.S. 1A AND SPECIFIED QUALITY STANDARD. B. PREFIT DOORS TO FRAMES. PREMACHINE DOORS FOR HARDWARE LISTED ON
FINAL SCHEDULES. FACTORY BEVEL DOORS. C. INSTALL DOORS WITH NOT MORE THAN 1/8 INCH CLEARANCE AT TOP AND SIDES,
1/4 INCH AT BOTTOM. COMPLY WITH NFPA 80 FOR RATED ASSEMBLIES. D. ADJUST, CLEAN, AND PROTECT.
END OF SECTION SECTION 08710 DOOR HARDWARE
PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE DOOR HARDWARE. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
C. SUBMIT FOR APPROVAL HARDWARE SCHEDULE PROPOSED FOR USE BASED ON OWNER'S REQUIREMENTS.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. HARDWARE FOR FIRE-RATED OPENINGS: NFPA 80, AND LOCAL REQUIREMENTS. C. MATERIALS AND APPLICATION: ANSI A156 SERIES STANDARDS.
PART 2 PRODUCTS 2.1 MATERIALS
A. DOOR HARDWARE: 1. MANUFACTURERS: PROVIDE HARDWARE BY MANUFACTURERS FOUND BELOW
OR AN ACCEPTABLE EQUAL TO BE APPROVED BY THE ARCHITECT. LOCKSETS – CORBIN RUSSWIN HINGES
1) STANDARD - MCKINNEY 2) CONTINUOUS - PEMKO
CLOSERS – CORBIN RUSSWIN PARALLEL ARM ELEC. STRIKES – HES (HANCHETT ENTRY SYSTEMS) FLUSH BOLTS - ROCKWOOD COORDINATORS - ROCKWOOD KICKPLATES – ROCKWOOD K1050 PULL PLATES – ROCKWOOD 111X70C PUSH PLATES – ROCKWOOD 70C RECESSED PULLS – ACCURATE FE5001 SLIDING DOOR HARDWARE –
3) BYPASS - HAGER 9886 OR PEMKO 4) SINGLE – PEMKO 200 SERIES OR EQUAL HAGER
POCKET DOOR KIT – HAGER 9630 OR PEMKO POCKET FRAME KIT SLIDING OR POCKET – LATCH/LOCKSETS – ACCURATE SLIDING/POCKET
HARDWARE (LOCKSETS FOR CYLINDERS AND FLUSH PULLS WITH CONCEALED SCREWS – CS TYPE)
CABINET LOCKS – BEST 5L SERIES LATCHBOLT - MORTISED WALL STOPS – ROCKWOOD 406 OVERHEAD STOPS - RIXON ELECTROMAG HOLD – RIXON 998 SILENCERS - ROCKWOOD SEALS AND SWEEPS – PEMKO AUTOMATIC DOOR BOTTOMS - PEMKO EXT. THRESHOLDS - PEMKO INT. THRESHOLDS
5) STANDARD – PEMKO 6) AT CERAMIC TILE – MARBLE
CARD/BADGE READERS 7) PROVIDE ALL REQUIRED INFRASTRUCTURE FOR
INSTALLATION AND COORDINATE WITH THE HOSPITAL FOR EXACT MODEL DEVICE. GC TO INSTALL OWNER TO PROVIDE.
2. QUALITY LEVEL: HEAVY DUTY COMMERCIAL. 3. INTERIOR LOCKSETS AND LATCHSETS: MORTISE TYPE. 4. EXTERIOR LOCKSETS AND LATCHSETS: RIM TYPE W/ PANIC DEVICE. 5. LOCK CYLINDERS: INTERCHANGEABLE. 6. KEYING: OWNER'S REQUIREMENTS – GC TO COORDINATE 7. HINGES AND BUTTS: FULL-MORTISE TYPE AT INTERIOR, WITH
CONTINUOUS TYPE AT EXTERIOR DOORS. 8. CLOSERS, DOOR CONTROL, AND EXIT DEVICES: HIGH FREQUENCY. 9. CLOSERS, DOOR CONTROL, AND EXIT DEVICES: BARRIER-FREE. 10. PIVOTS: OFFSET OR CENTER-HUNG TYPE. 11. PUSH/PULL UNITS: THROUGH-BOLTED TYPE. 12. HARDWARE FINISHES: US26D
PART 3 EXECUTION 3.1 INSTALLATION
A. FOLLOW GUIDELINES OF DHI 'RECOMMENDED LOCATIONS FOR BUILDER'S HARDWARE AND HARDWARE MANUFACTURERS' INSTRUCTIONS.
B. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS.
C. KET TO AMEDISYS SUITE134 MASTER. D. ADJUST OPERATION, CLEAN AND PROTECT.
3.2 SCHEDULE A. HARDWARE SCHEDULE: SEE ARCHITECTURAL DWGS.
END OF SECTION
DIVISION 09 - FINISHES SECTION 09110 NON-STRUCTURAL METAL FRAMING PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE NON-STRUCTURAL METAL FRAMING FOR GYPSUM BOARD ASSEMBLIES. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. TOLERANCES: NOT MORE THAN 1/8 INCH IN 10 FEET DEVIATION FROM TRUE PLANE, PLUMB, LEVEL AND PROPER RELATION TO ADJACENT SURFACES IN FINISHED WORK.
C. FIRE RESISTANCE FOR FIRE-RATED ASSEMBLIES: ASTM E 119. D. PERFORMANCE: FIRE, STRUCTURAL, AND SEISMIC PERFORMANCE MEETING
REQUIREMENTS OF BUILDING CODE AND LOCAL AUTHORITIES. PART 1 PRODUCTS 1.1 MATERIALS
A. STEEL FRAMING FOR SUSPENDED AND FURRED CEILINGS: 1. MANUFACTURERS: CLARKDIETRICH BUILDING SYSTEMS; MARINO/WARE
OR APPROVED EQUAL. 2. MATERIAL STANDARD: ASTM C645. 3. ATTACHMENT: STANDARD. 4. ACCESSORIES: FURRING CHANNELS, HANGERS AND INSERTS.
B. STEEL FRAMING FOR WALLS AND PARTITIONS: 1. MANUFACTURERS: CLARK DIETRICH; MARINOWARE 2. MATERIAL STANDARD: ASTM C645. 3. STUD THICKNESS: 20 GAUGE (.0329 INCH). 4. STUD DEPTH, TYPICAL: 3-5/8 INCHES. 5. FURRING CHANNEL THICKNESS: 20 GAUGE (.0329 INCH). 6. AUXILIARY FRAMING COMPONENTS: FURRING BRACKETS, RESILIENT
FURRING CHANNELS, Z-FURRING MEMBERS, AND NON-CORROSIVE FASTENERS.
PART 1 EXECUTION 1.1 INSTALLATION
A. PROVIDE FIRE-RATED SYSTEMS WHERE INDICATED AND WHERE REQUIRED BY AUTHORITIES HAVING JURISDICTION.
B. WHERE NEW PARTITIONS MEET EXISTING CONSTRUCTION, REMOVE EXISTING CORNERBEADS TO PROVIDE A SMOOTH TRANSITION.
C. PROVIDE ACOUSTICAL SEALANT AT BOTH FACES AT TOP AND BOTTOM RUNNER TRACKS, WALL PERIMETERS, OPENINGS, EXPANSION AND CONTROL JOINTS.
END OF SECTION SECTION 09260 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE GYPSUM BOARD ASSEMBLIES. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
GENERALSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
A.002
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
ARCHITECTURALSPECIFICATIONS
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
B. TOLERANCES: NOT MORE THAN 1/16-INCH DIFFERENCE IN TRUE PLANE AT JOINTS BETWEEN ADJACENT BOARDS BEFORE FINISHING. AFTER FINISHING, JOINTS SHALL BE NOT BE VISIBLE. NOT MORE THAN 1/8 INCH IN 10 FEET DEVIATION FROM TRUE PLANE, PLUMB, LEVEL AND PROPER RELATION TO ADJACENT SURFACES IN FINISHED WORK.
C. FIRE RESISTANCE FOR FIRE-RATED ASSEMBLIES: ASTM E 119. D. PERFORMANCE: FIRE, STRUCTURAL, AND SEISMIC PERFORMANCE MEETING
REQUIREMENTS OF BUILDING CODE AND LOCAL AUTHORITIES. PART 1 PRODUCTS 1.1 MATERIALS
A. GYPSUM BOARD: 1. APPLICATION: INTERIOR WALLS, PARTITIONS, AND CEILINGS WITH TAPE
AND JOINT COMPOUND FINISH. PART 1 EXECUTION 1.1 INSTALLATION
A. INSTALL GYPSUM BOARD FOR TAPE AND 3-COAT JOINT COMPOUND FINISH IN COMPLIANCE WITH ASTM C 840 AND GA 216, LEVEL 4 FINISH. INSTALL GYPSUM BOARD ASSEMBLIES TRUE, PLUMB, LEVEL AND IN PROPER RELATION TO ADJACENT SURFACES.
B. PROVIDE FIRE-RATED SYSTEMS WHERE INDICATED AND WHERE REQUIRED BY AUTHORITIES HAVING JURISDICTION.
C. INSTALL BOARDS VERTICALLY. DO NOT ALLOW BUTT-TO-BUTT JOINTS AND JOINTS THAT DO NOT FALL OVER FRAMING MEMBERS.
D. WHERE NEW PARTITIONS MEET EXISTING CONSTRUCTION, REMOVE EXISTING CORNERBEADS TO PROVIDE A SMOOTH TRANSITION.
E. PROVIDE INSULATION FULL HEIGHT AND THICKNESS IN PARTITIONS AT CONFERENCE ROOMS, TOILET ROOMS, BETWEEN DIFFERENT OCCUPANCIES, AND WHERE REQUIRED.
F. PROVIDE ACOUSTICAL SEALANT AT BOTH FACES AT TOP AND BOTTOM RUNNER TRACKS, WALL PERIMETERS, OPENINGS, EXPANSION AND CONTROL JOINTS.
G. INSTALL TRIM IN STRICT COMPLIANCE WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
H. REPAIR SURFACE DEFECTS. LEAVE READY FOR FINISH PAINTING OR WALL TREATMENT.
END OF SECTION SECTION 09510 ACOUSTICAL CEILINGS PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE ACOUSTICAL CEILINGS AND SUSPENSION SYSTEMS. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
C. EXTRA STOCK: SUBMIT EXTRA STOCK EQUAL TO 5 PERCENT OF AMOUNT INSTALLED.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. PERFORMANCE: FIRE, STRUCTURAL, AND SEISMIC PERFORMANCE MEETING REQUIREMENTS OF BUILDING CODE AND LOCAL AUTHORITIES. ACOUSTICAL PERFORMANCE BASED ON PROJECT REQUIREMENTS.
PART 1 PRODUCTS 1.1 MATERIALS
A. MINERAL FIBER ACOUSTICAL CEILINGS: 1. MANUFACTURERS: ARMSTRONG OR APPROVED EQUAL 2. PANEL SIZE: AS SHOWN ON DRAWINGS 3. PANEL EDGE: FLAT LAYIN. BOD .755B 4. GRID: EXPOSED FLUSH GRID. 5. SUSPENSION SYSTEM: MATCH EXISTING 6. AUXILIARY MATERIALS:
-EDGE MOLDING AND TRIM. -HOLD-DOWN CLIPS AND IMPACT CLIPS. -CONCEALED ACOUSTICAL SEALANT.
PART 1 EXECUTION 1.1 INSTALLATION
A. INSTALL MATERIALS AND SUSPENSION SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS, AND ASTM C 636. COORDINATE INSTALLATION WITH LOCATION OF MECHANICAL AND ELECTRICAL WORK TO ENSURE PROPER LOCATIONS AND ANCHORAGE.
B. LEVEL CEILING TO WITHIN 1/8 INCH IN 10 FEET IN BOTH DIRECTIONS. SCRIBE AND CUT PANELS TO FIT ACCURATELY. MEASURE AND LAYOUT TO AVOID LESS THAN HALF PANEL UNITS.
C. REMOVAL AND REINSTALLATION AT EXISTING CEILINGS: REMOVE AND STORE MATERIALS FOR REUSE WHEN ALLOWED. HANDLE WITH WHITE GLOVES AND AVOID DAMAGING CORNERS AND EDGES. CLEAN TILES AND GRID SYSTEM, WHICH HAVE BEEN REMOVED. PROVIDE ADDITIONAL MATERIALS TO COMPLETE THE WORK AND TO REPLACE DAMAGED EXISTING MATERIALS. NEW MATERIALS SHALL MATCH EXISTING MATERIALS AS APPROVED.
D. ADJUST, CLEAN, AND TOUCH-UP ALL SYSTEM COMPONENTS. END OF SECTION
SECTION 09650 RESILIENT FLOORING
PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE RESILIENT FLOORING AND FLOOR PREPARATION. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
C. EXTRA STOCK: SUBMIT EXTRA STOCK EQUAL TO 2% OF TOTAL USED. 1.3 QUALITY ASSURANCE
A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. PERFORMANCE: FIRE PERFORMANCE MEETING REQUIREMENTS OF BUILDING CODE AND LOCAL AUTHORITIES.
PART 1 PRODUCTS 1.1 MATERIALS
A. VINYL COMPOSITION TILE FLOORING: 1. MANUFACTURERS: ARMSTRONG OR APPROVED EQUAL. 2. TYPE: VINYL COMPOSITION TILE: ASTM F 1066, CLASS 2 THROUGH-
PATTERN. 3. SIZE: 12 BY 12 INCHES. 4. THICKNESS: 1/8 INCH. 5. AUXILIARY MATERIALS:
EDGE STRIPS AND TERMINATIONS. LEVELING COMPOUND.
PART 1 EXECUTION 1.1 INSTALLATION
A. COMPLY WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. INSTALL IN PROPER RELATION TO ADJACENT WORK.
B. PREPARE SURFACES BY CLEANING, LEVELING AND PRIMING AS REQUIRED. TEST ADHESIVE FOR BOND BEFORE GENERAL INSTALLATION. LEVEL TO 1/8' IN 10' TOLERANCE.
C. TILE FLOORING: INSTALL TILE WITH TIGHT JOINTS AND WITH ONE-WAY PATTERN. LAYOUT TO PREVENT LESS THAN 1/2 TILE UNITS.
D. SHEET FLOORING: INSTALL SHEETS WITH TIGHT JOINTS AND PATTERN IN ADJOINING AREAS RUNNING IN THE SAME DIRECTION. LAYOUT TO MINIMIZE SEAMS AS APPROVED.
E. CLEAN, POLISH, AND PROTECT. F. PROVIDE 2% EXTRA STOCK
PART 1 END OF SECTION SECTION 09653 RESILIENT BASE AND ACCESSORIES PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE RESILIENT WALL BASE AND ACCESSORIES. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
C. SUBMIT EXTRA STOCK EQUAL TO 2% OF TOTAL USED. 1.3 QUALITY ASSURANCE
A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. PERFORMANCE: FIRE PERFORMANCE MEETING REQUIREMENTS OF BUILDING CODE AND LOCAL AUTHORITIES.
PART 1 PRODUCTS 1.1 MATERIALS
A. RESILIENT WALL BASE: 1. MANUFACTURERS: JOHNSONITE, ROPPE OR APPROVED EQUAL 2. STANDARD: ASTM F 1861. 3. TYPE: TV (VINYL). 4. TYPE: TS (RUBBER, VULCANIZED THERMOSET). 5. GROUP: I (SOLID, HOMOGENEOUS) 6. GROUP: II (LAYERED) 7. STYLE: COVE. 8. STYLE: STRAIGHT. 9. THICKNESS: 0.125 INCH 10. THICKNESS: 0.080 INCH 11. HEIGHT: 4 INCHES.
PART 1 EXECUTION 1.1 INSTALLATION
A. COMPLY WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. INSTALL IN PROPER RELATION TO ADJACENT WORK.
B. INSTALL BASE AND ACCESSORIES TO MINIMIZE JOINTS. INSTALL BASE WITH JOINTS AS FAR FROM CORNERS AS PRACTICAL.
C. CLEAN, POLISH, AND PROTECT. END OF SECTION SECTION 09684 CARPETING PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE BROAD LOOM CARPET AND FLOOR PREPARATION. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED.
C. EXTRA STOCK: SUBMIT EXTRA STOCK EQUAL TO 2% OF TOTAL USED.
PART 1 PRODUCTS 1.1 MATERIALS
A. CARPET : 1. MANUFACTURERS: SEE AMEDISYS SPEC 2. COLOR AND STYLE: SEE AMEDISYS FINISH SCHEDULE 3. MATERIAL: HIGH-PERFORMANCE NYLON BONDED TO RESILIENT BACKING. 4. INSTALLATION METHOD: GLUE-DOWN. 5. AUXILIARY MATERIALS:
EDGE GUARDS. ADHESIVES, CEMENTS AND FASTENERS. LEVELING COMPOUND.
PART 1 EXECUTION 1.1 INSTALLATION
A. COMPLY WITH RECOMMENDATIONS OF CARPET AND RUG INSTITUTE "SPECIFIER'S HANDBOOK".
B. PREPARE SURFACES AND INSTALL MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SUBMITTALS. CLEAN, PATCH, AND LEVEL SUBSTRATE. INSTALL MATERIALS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS.
C. INSTALL EDGE GUARDS AND REDUCER STRIPS AS REQUIRED; CLEAN AND PROTECT.
END OF SECTION SECTION 09910 PAINTS PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE PAINTING AND SURFACE PREPARATION. 1.2 SUBMITTALS
A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED.
B. SAMPLES: SUBMIT TWO REPRESENTATIVE SAMPLES OF EACH MATERIAL SPECIFIED INDICATING VISUAL CHARACTERISTICS AND FINISH. INCLUDE RANGE SAMPLES IF VARIATION OF FINISH IS ANTICIPATED. 1. INCLUDE MANUFACTURERS FULL RANGE OF COLOR AND FINISH OPTIONS
IF ADDITIONAL SELECTION IS REQUIRED. C. EXTRA STOCK: SUBMIT 2 UNOPENED GALLONS OF EACH PAINT AND COLOR USED
IN THE PROJECT. 1.3 QUALITY ASSURANCE
A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
B. REGULATIONS: COMPLIANCE WITH VOC AND ENVIRONMENTAL REGULATIONS. PART 1 PRODUCTS 1.1 MATERIALS
A. PAINTING: 1. MANUFACTURERS: SHERWIN-WILLIAMS AND BENJAMIN MOORE. 2. APPLICATION: INTERIOR UNFINISHED SURFACES. 3. PRIMARY COATING TYPE: LATEX ZERO VOC BASED PAINTS. 4. PRIMARY PAINT SYSTEMS: PRIMER PLUS TWO FINISH COATS.
PART 1 EXECUTION 1.1 INSTALLATION
A. INSPECT SURFACES, REPORT UNSATISFACTORY CONDITIONS IN WRITING; BEGINNING WORK MEANS ACCEPTANCE OF SUBSTRATE.
B. COMPLY WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS FOR PREPARATION, PRIMING AND COATING WORK. COORDINATE WITH WORK OF OTHER SECTIONS.
C. AT EXISTING AREAS TO BE REPAINTED, REMOVE BLISTERED OR PEELING PAINT TO SOUND SUBSTRATES. REMOVE CHALK DEPOSITS AND MILDEW AND WASH ALL SURFACES WITH MILD DETERGENT. PERFORM RELATED MINOR PREPARATION INCLUDING CAULK AND GLAZING COMPOUNDS. SPOT PRIME BARE AREAS BEFORE PRIMING AND PAINTING AS SPECIFIED.
END OF SECTION
DIVISION 10 – SPECIALTIES SECTION 10520 FIRE PROTECTION SPECIALTIES PART 1 GENERAL 1.1 SUMMARY
A. RELOCATE EXISTING FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES. PROVIDE NEW IF NEEDED.
1.2 SUBMITTALS A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED. B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS INDICATING MATERIAL CHARACTERISTICS, DETAILS OF CONSTRUCTION, CONNECTIONS, AND RELATIONSHIP WITH ADJACENT CONSTRUCTION.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. B. STANDARDS: UL AND FM LISTED PRODUCTS, NFPA 10. C. REGULATIONS: ADAAG.
PART 2 PRODUCTS 2.1 MATERIALS
A. FIRE EXTINGUISHERS: 1. MANUFACTURERS: JL INDUSTRIES OR EQUAL 2. TYPE: MULTIPURPOSE DRY CHEMICAL TYPE. 3. TYPE: STORED-PRESSURE WATER TYPE. 4. RATING: SIZED FOR PROJECT REQUIREMENTS. 5. PUBLIC AREA MOUNTING: CABINET MOUNTED. 6. SERVICE AREA MOUNTING: METAL BRACKETS.
B. CABINETS: 1. MANUFACTURERS: JL INDUSTRIES OR EQUAL 2. MODEL: COSMOPOLITAN SERIES 3. MOUNTING: SURFACE-MOUNTED/SEMI RECESSED 4. DOORS: STEEL, BAKED ENAMEL FINISH. 5. DOORS: ACRYLIC. 6. DOOR STYLE: DUO-PANEL. 7. ACCESSORIES:
A. GLASS BREAKER OR FIRE HANDLE. B. SIGNAGE. C. OPERATION INSTRUCTIONS
PART 3 EXECUTION 3.1 INSTALLATION
A. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS. B. INSTALL FIRE EXTINGUISHERS IN MECHANICAL AND SERVICE AREAS WITH WALL-HUNG BRACKETS AT LOCATIONS AND HEIGHTS INDICATED AND ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. C. INSTALL FIRE EXTINGUISHERS IN CABINETS IN PUBLIC AREAS PLUMB AND LEVEL AT HEIGHTS ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. D. RESTORE DAMAGED FINISHES. CLEAN AND PROTECT WORK FROM DAMAGE.
END OF SECTION SECTION 10800 TOILET ACCESSORIES PART 1 GENERAL 1.1 SUMMARY
A. PROVIDE TOILET, BATH, AND LAUNDRY ACCESSORIES. B. SEE PLUMBING DWGS AND SPECS FOR SPECIFIC PLUMBING FIXTURE
INFORMATION. IN THE ABSENCE OF SUCH REQUIREMENTS, THE FOLLOWING MINIMUM REQUIREMENTS APPLY FOR THE WORK OF THIS PROJECT.
1.2 SUBMITTALS A. PRODUCT DATA: SUBMIT MANUFACTURER'S PRODUCT DATA AND INSTALLATION
INSTRUCTIONS FOR EACH MATERIAL AND PRODUCT USED. B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS INDICATING MATERIAL
CHARACTERISTICS, DETAILS OF CONSTRUCTION, CONNECTIONS, AND RELATIONSHIP WITH ADJACENT CONSTRUCTION.
1.3 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF
ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
PART 2 PRODUCTS 2.1 MATERIALS
B. TOILET AND BATH ACCESSORIES: SEE PLUMBING FIXTURE SCHEDULE. PART 3 EXECUTION 3.1 INSTALLATION
C. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPROVED SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS.
D. RESTORE DAMAGED FINISHES AND TEST FOR PROPER OPERATION. CLEAN AND PROTECT WORK FROM DAMAGE.
END OF SECTION
DIVISION 12 - FURNISHINGS SECTION 12490 WINDOW TREATMENTS PART 1 GENERAL 1.1 SUMMARY
A. EXISTING TO REMAIN. B. NEW AT NEW WINDOW LOCATION.
PART 3 EXECUTION 3.1 INSTALLATION
A. CLEAN, ADJUST, AND VERIFY PROPER OPEREATION. B. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS AND APPROVED SUBMITTALS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS.
C. RESTORE DAMAGED FINISHES AND TEST FOR PROPER OPERATION. CLEAN AND PROTECT WORK FROM DAMAGE.
END OF SECTION
REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
PLANSSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
A.100
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
SITE/DEMO PLAN
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
LEE ANNPHYS. THERAPY
McCRONE
PRO AUTOMATED
CHES
APEA
KE B
LVD
KONICA DR.
AMEDISYS
SHERRIF'S OFFICE/EOC WAWA CORP. OFFICESEMPTY
F F
FE
FE
EXISTING ELECTRICALPANEL TO REMAIN
EXISTING AMEDISYS
SUITE: 134 SUITE: 124
ROOM101
ROOM101
REL-100
DEMOLITION NOTES:
LEGEND
SCALE: 1" =100'
1 KEY PLANA.100
SCALE: 1/8" = 1'-0"
3 GROUND FLOOR DEMOA.100
D-01
D-02
D-03
D-04
D-01
D-01
D-05
D-01
D-02
D-03
D-03
D-03 D-03
D-05
D-04
D-04
D-06
D-06
D-07
D-07
D-08
D-09
D-08
D-01
D-09
D-10 D-10
EXISITNG
DEMOL
NOTE TAG
ROOM TAG
ROOM TAG(CHANGINGFUNCTION)
INDICATES DOOR TO BE RELOCATED.NUMBER INDICATES NEW ROOM LOCATION
DEMO EXISTING INTERIOR WALLS WHERE INDICATED.
DEMO EXISTING INTERIOR DOOR. INFILL AND RE-FINISH TO MATCH EXISTING WALLS.RE-FINISH FLOORING.
PATCH FLOOR WHERE EXISTING VERTICAL CONDUIT WAS LOCATED.
REMOVE AND/OR RELOCATE EXISTING EQUIPMENT AND PIPING.EXISTING ELECTRICAL PANEL TO REMAINCOORDINATE WITH M.E.P. ENGINEERS.PATCH AND REFINISH WALLS TO MATCH EXISTING.
DEMO EXISTING DOOR AND PREPEARE FOR NEW OPENING. PATCH AND RE-FINISHTO MATCH EXISTING AND RE-FINISH FLOORING.COORDINATE WITH ARCH. DWGS.
REMOVE EXISTING OVERHEAD DOOR. INFILL WALL TO MATCH EXISTING CMU WALLPREPARE FOR NEW WINDOW. COORDINATE WITH ARCH DWGS.
PATCH/REPAIR ANY CRACKS IN EXISTING SLAB.
- RELOCATE ANY EXISTING EXIT SIGNS AND EMERGENCY LIGHTS.COORDINATE WITH ELECT. ENGINEERS.
- EXISTING BLINDS TO BE MAINTAINED AND RE-USED.
PROJECT PERIMETER
DEMO SLAB WHERE INDICATED FOR NEW PLUMBING FIXTURES.
DEMO AND PEPARE WALL FOR NEW OPENING. COORDINATE WITH ARCH. DWGS.
GENERAL NOTES
WALL TO BE STAGGERED STUD WALL. BUILD PARTITION IN PHASES- TO BECOMPLETED AFTER TENANT IS MOVED IN.
- EXISTING LIGHT FIXTURES TO BE MAINTAINED AND RE-USED.
REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
PLANSSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
A.101
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
FLOOR PLANS
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
F F
EXISTING ELECTRICALPANEL TO REMIAN
4'-3"4'-3"
SUITE: 134 SUITE: 124
OFFICE101
CP RB P1 AC
OFFICE102
CP RB P1 AC
SERVER ROOM105
CP RB P1 AC
OFFICE103
CP RB P1 AC
MULTI PURPOSE100
CP RB P1 AC
TOILET106
FT CB WT AC
MULTI PURPOSE104
CP RB P1 AC
WAITING ??100
CP RB P1 AC
FE
FE
TOILET106
FT CB WT AC
F F
EXISTING ELECTRICALPANEL TO REMIAN
107
105
11'-7"
7'-7"
7'-6"
25'-6
"15
'-1"
19'-10"+/-
2G.100
2G.100
3G.100
4G
.100
2
SUITE: 134 SUITE: 124
OFFICE101
CP RB P1 AC
OFFICE102
CP RB P1 AC
SERVER ROOM105
CP RB P1 AC
OFFICE103
CP RB P1 AC
MULTI PURPOSE100
CP RB P1 AC
TOILET106
FT CB WT AC
MULTI PURPOSE104
CP RB P1 AC
WAITING ??100
CP RB P1 AC
2
2
2
FE
FE
103
102
W1
101
105
106
24'-4
"
12'-6
"7'-
6"
11'-0" 12'-10"+/-
12'-6
"
1G.100
1G.100
5
4
TOILET106
FT CB WT AC
CLASSROOM100
CP RB P1 AC
FE
100
PARTITION LEGEND
EXISTING WALL/ITEM TO REMAIN
PLAN LEGEND
PROPOSED WALLS / ITEMS
WALL TAG
DOOR TAG
STOREFRONT TAGSF1
SPECIFIC NOTE
SPECIFIC NOTES:
FIRE EXTINGUISHER CABINET
TYPICAL ROOM TAG W/ FINISH CODES
SCALE: 1/8" = 1'-0"
1 SPACE PLANA.101
SCALE: 1/8" = 1'-0"
2 GROUND FLOOR ARCHITECTURAL PLANA.101
FLOORINGBASEWALLCEILING
N-04
N-02
N-01
1
1
2
3
N-01
N-02
N-01
N-02
4
5
N-02
N-03 N-03
N-04
DEMO GWB
3 5/8" MTL STUD
WRAP 5 1/2" ACCOUSTICINSULATION THRU/AROUNDSTUDS
BLOCK OUT GAP
BLOCK OUT GAP
5 1/2" ACCOUSTICINSULATION THRU/AROUNDSTUDS
N-05
N-05
N-06
N-06
3 5/8" MTL STUDS
EXISTING DECKING
BEAM BEYOND
NEW STAGGERED STUDWALL. TO EXISTING DECKING
PARTITION NOTES:METAL STUD PARTITIONS TO BE INSTALLED W/ BRACING AND BRIDGINGPER MFG'S SPECIFICATIONS.
ALL PARTITIONS ARE NEW U.N.O.
ALL EXISTING INTERIOR PLASTER WALLS IN PROJECT AREA TO BE REPAIREDW/ PLASTER MATERIALS WHERE DAMAGED BY DEMOLITION ANDWHERE WARRANTED BY EXISTING MATERIAL DEGRADATION.PATCH AND MAKE APPEARANCE LIKE ADJACENT WALLS. PROVIDE ACOUSTIC CAULKING/SEALANT WHERE ADJOININGTO ADJACENT MATERIAL.
ALL DIMENSIONS ARE MEASURED FROM FINISHED FACE OF WALL TO FINISHEDFACE OF WALL UNLESS NOTED OTHERWISE. CONTRACTOR SHALL NOT ADJUSTANY DIMENSIONS DESIGNATED AS "HOLD" OR "HLD" WITHOUT WRITTENINSTRUCTIONS FROM ARCHITECT.
VERIFY LOCATION OF ALL COLUMNS BEFORE LAYING OUT INTERIOR STUD WALLS.IF CONTRACTOR NOTICES ANY DISCREPANCY THEY ARE TO CONTACTARCHITECT IMMEDIATELY.
PROVIDE SLEEVES FOR CABLING IN WALLS THAT EXTEND TO STRUCTURE ABOVE.
PROVIDE SLEEVES FOR HVAC DUCTWORK IN WALLS THAT EXTEND TO STRUCTUREABOVE.
INSTALL HILTI ANCHORS WHERE NEW METAL STUDS BUTT EXISTING BLOCK WALLS.
INTERIOR PARTITIONS 6" ABOVE CEILING U.N.O.
TYP. TOILET RM WALL5/8" GYP WB3 5/8" MTL STUD W/ 6" SOUND BATTSTILE & BACKER UP TO WAINSCOT (APPROX 3'-4" IN TOILETS)5/8" GYP WB MOISTURE RESISTANT
MOISTURESIDE
TYP. TOILET PLUMBING WALL5/8" GYP WB MOISTURE RESISTANTTILE & BACKER (WAINSCOT - APPROX 3'-4" IN TOILETS)6" MTL STUDTILE & BACKER (WAINSCOT)5/8" GYP WB MOISTURE RESISTANT
TYP. INTERIOR WALL5/8" GYP WB3 5/8" MTL STUD5/8" GYP WB
INFILL OVER HEAD DOOR OPENING. TO MATCH EXISTING EXTERIOR CMU WALL.ADD WINDOW, TO MATCH EXISITNG IN BUILDING. SEE INTERIOR ELEVATION.
PATCH AND RE-FINISH FLOORING TO MATCH EXISTING.
ALL EXTERIOR WALL TYPES TYP.ALL INTERIOR WALL TYPES TYP.
EXISTING AMEDISYS
PROJECT PERIMETERPROJECT PERIMETER
MOISTURESIDE
STAGGERED STUD WALL- ALTERATION TO EXISTING PARTITION.UP TO DECK- COMPLETE AFTER TENENT MOVE-IN.5/8" GYP WB3 5/8" MTL STUD W/ SOUND BATTS-FILL STUD CAVITY- UP TO DECK3 5/8" MTL STUD W/ SOUND BATTS-FILL STUD CAVITY- UP TO DECK5/8" GYP WB
STAGGEREDSTUDS
CMU EXTERIOR INFILL WALLINFILL OH DOOR8"/12"CMU2" GALV. CLIPS2" RIGID INSULATION5/8" GYP. WB
EXISTING ELECTRICAL PANEL TO REMAIN.
INFILL DEMO'D DOOR OPENING. TO MATCH EXISTING.
EXISTING STUDSTO REMAIN
WALL TO BE BUILT IN PHASES.SUITE 114 TO BE COMPLETED AFTERTENANT IS MOVED INTO SUITE 124
BASE
DECK
STAGGERED STUD PARTITION.
NEW STUDS
EXISTING AMEDISYS
PROVIDE NEEDED ELECTRICAL FOR SERVER. COORDINATE WITH ELECTRICAL DRAWINGS.
PROVIDE PLUMBING AND ELECTRICAL NEEDED FOR NEW KITCHEN SINK AND REFRIGERATOR
STAGGERED STUD PARTITION @ DECK.
SUITE 114SUITE 124
CLIP OPENING
INFILL AT BEAM
REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
PLANSSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
A.102
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
REFLECTED CEILING PLAN
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
LEGEND
EQUQL EQUAL
EQUA
LEQ
UAL
EQUQL EQUAL
EQUA
LEQ
UAL
WORKING POINT
TYPICAL CEILING LAYOUT
CEILINGGRID
ALTERNATE CEILING LAYOUT
TYPICAL SUSPENDED ACOUSTICAL (SAC) CEILING
19'-4
"
14'-4"14
'-9"
17'-3
1/2"
35'-0
"
31'-3
3/4"
EXISTING ELECTRICALPANEL TO REMIAN
2A.102
9'-0"AC48
7'-10"GYPSOFFIT
BULKHEAD
BULKHEAD
BULKHEAD
9'-0"AC48
9'-0"AC48
9'-0"AC48
9'-0"AC48
9'-0"AC48
9'-0"AC48
9'-0"AC48
CEILING TILE CEILING TILE
V.I.F
NEW 2x4 FIXTURE
NEW 2x2 FIXTURE
NEW EMERGENCYLIGHTING (BATTERY PACK)
NEW EXIT LIGHTSOLID INDICATESEGRESS DIRECTION
NEW SWITCH
NEW 3 WAY SWITCH
NEW 2x4 NIGHT LIGHTFIXTURE
SCALE: 1/8" = 1'-0"
1 REFLECTED CEILING PLANA.102
2 BULKHEAD STLA.102
S3
S
ALL CEILINGS TO BE CENTERED IN SPACE & CORRIDOR.
ALL AREAS TO HAVE NEW 2' x4' BLDG STD CEILING TILE AND GRID
EXISTING AMEDISYS
PROJECT PERIMETER ALL NEW CEILINGS TO BE 9'-0". ADJUST CEILING TO MATCH EXISTING.
SOFFIT DTL SIMILAR, BUT SOFFIT TO BE 13" WIDE
REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
PLANSSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
G.100
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
SECTIONS AND DETAILS
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
2A.102 D-05
S.A.C.S.A.C.
S.A.C.
EXISTINGEXTERIOR WALL
EXISTING WINDOW EXISTING WALL
INFILLED OPENING
NEW OPENING INTOEXISTING AMEDISYS
EXISTING PARTITIONWALL NEW WALL
EXISTING PARTITIONWALL
INFILLEDOPENING
NEW OPENINGTO EXISTING AMEDISYS
NEW WALL SOFFIT.
NEW OPENINGBEYOND EXISTING WALL
NEW OFFICEWALL
INFILLED OPENINGBEYOND 2
A.102
SOFFIT
7'-11/4
"
7'-7"
7'-11/4
"
7'-7"
WC
LAV
WC
LAV
GB36
MR
FS
TW
GB42
GB36
FS
GB42
TOILET106
FT CB WT AC
105
106
TW
TOILET106
FT CB WT AC
PLUMBING FIXTURE SCHEDULE
(TO BE USED FOR ARCH. COORDINATION. SEE PLUMBING DWGS & SPECS FOR SPECIFIC PLUMBING FIXTURE INFORM
IDFSGB36GB42LAVMRTWWC
Quantity2222222
ManufacturerSCA-TORKBOBRICKBOBRICKTOTOBOBRICKBOBRICKTOTO
Product NameFOAM SOAP DISPENSERGRAB BARGRAB BARWALL HUNG LAVFIXED POSITION TILT MIRRORCONTURA TOWEL/WASTE COMBOH/C FLOOR MTD TOILET
Product ID572020A00B-5806x36819388SEE MEPB-293 1836B-43944SEE MEP
Accessories
AUTOMATIC FLUSH
MFG.: SHERWIN WILLIAMS
PRIMER: 1 COAT REGAL PRIMERCOLOR:
FINISH: 2 COATS SATIN FINISH
FINISH CODES
MFG:
STYLE:COLOR:
SIZE:VCTFLOOR TILE
FLOORING
COLOR:STYLE: TRADITIONAL COVED TOE
RUBBER BASE MFG: ROPPESIZE: 4" HGT
PAINTTRIM
PAINTFIELD COLOR
BASE
PRIMER: 1 COAT REGAL PRIMERCOLOR:
FINISH: 2 COATS REGAL SEMI-GLOSS
WALLPR
OVI
DE
SEM
I-GLO
SS IN
LO
CAT
ION
SW
HIC
H R
EQU
IRE
REG
ULA
R C
LEAN
ING
.IE
TO
ILET
RO
OM
S, K
ITC
HEN
/BR
EAK
RO
OM
S, J
ANIT
OR
'S C
LOSE
TS E
TC.
MISC.
FT
RB1 P1
P2
CG
TS
MFG:
STYLE:COLOR:
SIZE:CARPET TILE
CP
4'-2" 8'-0"
5'-0"
EXISTING REAREXIT DOOR
NEW WINDOW
INFILLED OVERHEADDOOR OPENING
EXISTING EXTERIOR WALL
EXISTING ELECTICALPANEL TO REMAIN
3'-0"
2'-9" 2'-6" 2'-6"
4"2'-
6"4"
1'-8"
3'-0" 1'-
6"
END PANELPLAM SIDE SPLASH
AND BACK PANEL
F
HEAD
INFILLED OPENINGTO MATCH EXISTING CMU.PAINT TO MATCH.
KAWNEER 450.SEE MANUFACTURERFOR DETAILS.
PLAM SILL
5/8" GYP.
S.A.C.
EXISTING LINTEL
EXISTINGEXTERIOR WALL
INFILLEDOPENING
1" RIGID INSULATION
5/8" GYP.
1" RIGID INSULATION
SCHEDULED BASE & FLOORING EXISTING WALL/FOUNDATIONBELOW
FLASHING
MATCHING PRECASTSILL
FLASHING
NEW PRECAST LINTEL
BLOCKING
EXISTING CMU
KILIM BEIGE SW 6106
MFG.: SHERWIN WILLIAMS
PURE WHITE SW7005
MOHAWK GROUPBROAD LOOMPURE GENIUS IIDOCTOR II COMPOSER 859 BLACK-BROWN P193
ARMSTRONG12"x12"STANDARD EXCELONCOASTER GREIGE
PL-1PLASTIC LAMINATE
NO DESCRIPTION MFR. STYLE/COLOR NOTES:
PL-2 PLASTIC LAMINATE
PL-3 PLASTIC LAMINATE
MILLWORK FINISH SCHEDULE
FORMICA
WILSONART
COLOR: TUSCAN MARBLENO: 7736-42
COLOR: BRUNE SLATENO: 1763-60
COLOR: GRAPHITE MATTE
COUNTERTOPOPTION 1
OPTION 2
CABINETRYFORMICA
NO: 837-58 OPTION 1
PL-4 PLASTIC LAMINATE WILSONART COLOR: SLATE GREYNO: D91-60 OPTION 2
COUNTERTOP
CABINETRY
3'-33/4
"2'-
6"
2'-6"
2'-10
"3'-
8" S
OAP
DISP
.
2'-9"
- 3'-
0"
15"
17"-1
9"
1'-10
" 39" -
41"
1'-6"
1'-0" 3'-6"4'-6"
39" - 41"
2'-9"
- 3'-
0"
3'-0" 6"
1'-6"
4'-0"
MAX
. FOR
WAR
D RE
ACH
1'-3"
MIN
.
4'-21/2
" MTG
HEI
GHT
MR
FS
LAV
30" WIDE x 48" DEEP CLEARFLOOR SPACE W/ MAX 19"PROJECTING UNDER SINK
WC
GB24
GB42
SN
TTGB(V)
STD HEIGHTHC HEIGHT
GB24
GB42
GB(V)
SN
TT
WC
HANDLE TOFACEACCESSIBLESIDE
TW
PIPE INSULATION(TYP.)
4'-6"
MAX
. SID
E RE
ACH
SCALE: 1/4" = 1'-0"
1 SECTIONG.100
SCALE: 1/4" = 1'-0"
2 SECTIONG.100
SCALE: 1/2" = 1'-0"
6 TOILET ROOMSG.100
SCALE: 1/4" = 1'-0"
3 NEW WINDOW ELEVATIONG.100
SCALE: 1/4" = 1'-0"
4 KITCHENETTEG.100
SCALE: 1" = 1'-0"
5 SECTION THROUGH NEW WINDOWG.100
SCALE: 1/2" = 1'-0"
7 TYP FIXTURE MOUNTING HEIGHTG.100
FURNITURE N.I.C.
FURNITURE N.I.C.
PI 2 LAVATORY PIPE AND P-TRAP INSULATIONEVERBILT
REVISIONSID01
DESCRIPTIONBID SET
DATE12/22/2016 12:23 PM
NGINEERING
HILADELPHIA
PIKE
DE. 19809ILMINGTON,
ORPORATIONCE
PFAX 302.762.0653TEL 302.762.6010
WWW.PARAGON-ENG.COM
708 P
CE W
PARAGON
PLANSSHEET:
REV #:
ISSUE FOR BID SETISSUE DATE 12/22/2016
PROJECT NO. 2016.16
DRAWN GM
CHECKED MEC
I AM A DULY LICENSED ARCHITECT UNDER THEPREPARED OR APPROVED BY ME, AND THAT
LAWS OF THE STATE OF:
LICENSE NUMBER:
136 WEST HIGH STREET
(410) 398-8866
MECHANICAL and ELECTRICAL ENGINEERING:
CIVIL ENGINEERING:
ALT
ERA
TION
G.101
8078-R
01
UCC
C A
MED
ISYS
107
CH
ESA
PEA
K BL
VD
ELKT
ON
, M
D
I CERTIFY THAT THESE DOCUMENTS WERE
MD
DETAILS
C
ELKTON, MARYLAND 21921
CO
PYR
IGH
T 2
016
CLA
RK
Des
ign
Gro
up,
pcPR
INT
DAT
E: T
hurs
day,
Dec
embe
r 22,
201
6 L:
\_Pr
ojec
ts\2
016\
2016
-26
CC
UC
CC
AM
EDIS
YS 2
016\
3. P
RO
JEC
T C
ADD
FIL
ES\2
. AR
CH
ITEC
TUR
AL\U
CC
C A
MED
ISYS
.pln
ISSUE FORREVIEW ONLYNOT FORCONSTRUCTION
WWW.CDGARCHITECTURE.COM
12/16/2016
FF(2)
= FLUSH= DOUBLE FLUSH
G = HALF GLASS= DOUBLE HALF GLASSG(2)
3'-7"
6"
6" GLAZING ASSCHEDULED
N(2)
GLAZING ASSCHEDULED
3'-7"
3"
= NARROW LITEN= DOUBLE NARROW LITE
6"
2'-9"
6"
NOMI
NAL D
OOR
HEIG
HT
NOMINAL DOOR WIDTH
NOMI
NAL D
OOR
HEIG
HT
NOMINAL DOOR WIDTHNOMINAL DOOR WIDTH
V(2)
GLAZING ASSCHEDULED
3'-4"
6"
= VISION PANELV= DOUBLE VISION PANEL
3'-0"
6"
NOMI
NAL D
OOR
HEIG
HT
NOMINAL DOOR WIDTH
WHERE SCHEDULEDDOUBLE DOOR
WHERE SCHEDULEDDOUBLE DOOR
WHERE SCHEDULEDDOUBLE DOOR
WHERE SCHEDULEDDOUBLE DOOR
NOMI
NAL D
OOR
HEIG
HT
2" 2"
DOOR
HEIG
HTDOOR WIDTH
FRAMETYPES
2"*
*PROVIDE 4" HEAD AT 7'-0"HIGH DOORS IN CMU WALLS
A = STD KNOCKDOWN
5" 5"2"
2" 2"
SEE
PLAN
SEE PLAN
SEE PLAN
GYP WB, EA SIDE (TYP.)
DBL MTL STUD
PNT HM FRAME
FRAME ANCHOR
DOOR LEAFPERIMETER SEALANT(EA SIDE)LINE OF GWB @CORNER CONDITION
PERIMTER SEALANT(EA SIDE)
PNT HM DOOR FRAME(SIZED PER PARTITION)
DOOR LEAF
PNT HM DOOR FRAME(SIZED PER PARTITION)
DOOR LEAF
JAMB - J1 HEAD - H1
DOOR SCHEDULE
MARK
101102103105105106107
DOOR LEAFElevation
FFFFFFF
W3'3'3'3'3'3'4'
HT7'7'7'7'7'7'
6'-8"
THK0'-1 3/4"0'-1 3/4"0'-1 3/4"0'-1 3/4"0'-1 3/4"0'-1 3/4"0'-1 3/4"
MATLWDWDWDWDWDWDWD
LOUVERW---------------
HT---------------
FRAMETYPE
KDKDKDKDKDKD---
MATLHMHMHMHMHMHM---
GLZ---------------
FIRE RATING
-------
SET NO
OFF.1OFF.1OFF.1OFF.1TR.1TR.1
OFF.1
SIGN TYPE
-----
0101
NOTES
03/4" T
EXT
8"
8"
R 01/2"RESTROOM
2'-0"
1'-11/4"
3'-2"
9"
111/2"
8'-9"
(REF
ER T
O RC
P PL
AN)
2'-0"
2'-10
"
3"
4"1'-
83/4"
7/8"
6"7/8
"
SCHEDULED BASE
PLAM COUNTERTOP.SOFTEN EDGES
PLAM 4" HIGH BACKSPLASH
LIGHT FIXTURE
STD WIRE PULLS (TYP.)
3/4" PLAM ADJ. SHELF ON PINS
PROVIDE FIRE-RETARDANT WOODBLOCKING INSIDE WALL FORATTACHMENT, TYP.
1" THK. PLAM W/ WHITE MEL.INTERIOR, LINE BORING AT1-1/4" O.C., TYP.
1" THK. PLAM PANEL ATFRONT & EXPOSED SIDES (TYP)
SCHEDULED ACT CLG
STD WIRE PULLS (TYP.)
1" THK. PLAM W/ WHITE MEL.INTERIOR, LINE BORING AT1-1/4" O.C., TYP.
3/4" PLAM ADJ. SHELF ON PINS
DRAWER
SCALE: 1/4" = 1'-0"
2 DOOR TYPESG.101
SCALE: 1/4" = 1'-0"
3 FRAME TYPESG.101
SCALE: 1 1/2"= 1'-0"
1 TYP. FRAME DETAILSG.101
SCALE: 1" = 1'-0"
4 COUNTERSG.101
OFF.1 - TYPICAL OFFICE DOOR
(3) HINGEOFFICE LOCKSETDOOR STOP(3) SILENCER
HARDWARE SETS
TR.1 - SGL TOILET ROOM DOOR
(3) HINGEPRIVACY SETDOOR CLOSERKICKPLATEMOP PLATEDOOR STOP(3) SILENCER
OFF.3 - TYPICAL OFFICE CLOSET DOOR
(3) HINGESTOREROOM LOCKSETDOOR STOP(3) SILENCER
SIGN TYPE
01