u series - chromalox · 2016-07-25 · uas ambient-sensing thermostat* pcn 394038 nema 4x rated...
TRANSCRIPT
Heating Cable
G-65
acce
sso
rie
san
d c
on
tro
ls
U SeriesHeat Trace ConnectionSystem Accessories
SingleEntryConnectionBox• NEMA4X• Entryfor1Cable• 3/4”ConduitHubOpening
MultipleEntryConnectionBox• NEMA4X• Entryforupto3Cables• PowerorTeeConnection• 3/4”ConduitHubOpening
EndSealFitting• NEMA4X• FitsAllPipeSizes• MountsAbovetheInsulationforEasyAccess
• LightedorNon-Lighted
PipeStandoffKit• BringsCableOutsideInsulationtoCustomerSuppliedJunctionBox
UnderInsulationEndSealKit• 3”Dia.CurvedMountingSurface• StainlessSteelHardware• 1”WideStrappingChannelforSecureMounting
SmallPipeAdapterforPipesUnder1-1/2”Diameter
Features• MoldedofDurablePolyphenyleneSulphidePlasticMaterial*
• MaximumPipeTemperature482˚F(250˚C)
• CorrosionResistant
• ThermalStability
• Non-Flammable
• HighStrengthandRigidity
• CaptiveHardware
• StainlessSteelHardwaretoEnsuretheIntegrity of the System
• LiquidTightDesignPreventsMoisturefromReachingtheElectricalConnections
• AllModelsareRatedNEMA4X.
DescriptionThe U-Series Connection System represents cutting edge design in heat tracing acces-sories. Each model in this series is designed to satisfy the unique demands of a particular operation. These high-quality models combine a variety of functions in a convenient, easy-to-use and economical package.
ApplicationsThese accessories are designed to connect SRP,SRM/EandCWMheatingcablestocustomer-supplied wiring in any of the follow-ing applications:
• FreezeProtection
• PipingProcessTemperatureMaintenance
• FluidFlowandViscosityMaintenance
ApprovalsUL ListedOrdinary Areas
CSA Certified†
Ordinary AreasClass I, Div. 2, Groups A, B, C, and D Class II, Div. 2, Groups F, G
FM ApprovedOrdinary AreasClass I, Div. 2, Groups B, C, DClass II, Div. 2, Groups E, F, GClass III
ATeX Certified (SRL & SRM/e Cables Only)
IIG Exe IIIECEx CertifiedExe 11 Gb
†SSKtohavetheseapprovalswhenajunctionboxisusedthatisNEMA4Xratedandcertifiedbyappropriatethirdpartyagencyforuseforthatapplicationandhazardouslocations rating (Div. 2)
* This crystalline, high-performance engineering TP is characterizedbyoutstandinghigh-temperaturestability,inherent flame resistance and a broad range of chemical resistance. PPS plastics and compounds provide various combinations of high mechanical strength, impact resis-tance and electrical insulation, with its high arc resistance and low arc tracking.
203312
Heating Cable
G-66
U SeriesHeat Trace ConnectionSystem Accessories(cont’d.)
Accessories
UPC Power Connection Box PCN 393553
NEMA4XratedjunctionboxdesignedtoconnectSRL,SRP,SRM/EandCWMcablestocustomersuppliedpowerwiring.This kit provides water-resistant cable entry for one cable, enclosure support, terminal block, and a water-resistant corrosion-resistant wiring enclosure with a 3/4” opening toacceptaconduithub(CCH-2orequal).Apipestrap(PSSeries) is required to attach this model to a pipe. Small pipe adapterisavailableforpipesizelessthan1-1/2".
Kit Dimensions:9.78"Hx4.78"Wx3.6"D
Kit Includes:1 Junction box with DIN rail & terminal block1 Compression fitting1 Locknut1 Silicone termination boot1 Pipe standoff1 O-ring1 Self-regulating cable grommet1 Constant wattage cable grommet
UMC Multiple Entry Connection BoxPCN 393561NEMA4XratedjunctionboxdesignedtoconnecttwoorthreeSRL,SRP,SRM/EandCWMcablestocustomersuppliedpowerwiring. This kit provides water-resistant cable entry, enclosure support, terminal block and a water-resistant, corrosion-resistant wiring enclosure. In addition to splicing or teeing cables, this model can be used to provide power connection to up to three ca-bles from one connection kit. A pipe strap (PS series) is required to attach this model to a pipe. Small pipe adapter is available for pipesizelessthan1-1/2”.
Kit Dimensions:9.78"Hx8.69"Wx3.6"D
Kit Includes:1 Junction box with din rail and terminal block1 Compression fitting1 Locknut3 Silicone termination boots1 Pipe standoff1 O-ring1 Self-regulating cable grommet1 Constant wattage cable grommet1 Self-regulating cable grommet insert1 Constant wattage cable grommet insert
Kit Includes:1 Small pipe adapter
SPA Small Pipe Adapter*PCN 393609
*Pipeadaptertobeusedwhenpipesizeislessthan 1-1/2" diameter.
Heating Cable
G-67
acce
sso
rie
san
d c
on
tro
ls
UES Above Insulation End Seal Kit PCN 393570NEMA4XratedendsealdesignedoftoterminateSRL,SRP,SRM/EandCWMcables.Thiskitprovideswater-resistant cable entry for one cable, water-resistant and corrosion-resistant pipe support to bring the cable end outside the insulation for easy access. A pipe strap (PS Series) is required to attach this model to a pipe. Small pipeadapterisavailableforpipesizelessthan1-1/2”.
Kit Dimensions:5.5"Hx2.75"Wx2.25"D
Kit Includes:1 End cap1 Pipe standoff1 Self-regulating cable grommet1 Constant wattage cable grommet
RTES Under Insulation End Seal KitPCN 389570NEMA4XratedenclosureisdesignedtoterminateSRL,SRP,SRM/EandCWMcables.Thiskitprovideswater-resistant cable entry for one cable, enclosure support and a water-resistant corrosion-resistant en-closure. The fitting has two different curved mounting surfaces. One side has a 1-1/2” radius curved surface that provides stable support on pipes with a diameter of 3” or more. The other side has a 1/2” radius curved surface which permits a better fit on smaller pipes. A pipe strap (PS Series) is required to attach this model to a pipe. In addition, this side also has four “feet” for installation on flat surfaces.
Kit Dimensions:1.25"Hx1.75"Wx2"D
Kit Includes:1 End Cap1 Pressure Plate1GRSRSelf-RegulatingCableSealingGrommet1GRCWConstantWattageCableSealingGrommet
U SeriesHeat Trace ConnectionSystem Accessories(cont’d.)
SSK Single Entry Sealing Kit†
PCN 393617
This kit provides water resistant cable entry for one cable, water-resistant and corrosion-re-sistant pipe support to bring the cable outside the insulation for easy connection to power. A pipe strap (PS Series) is required to attach this model to a pipe. A small pipe adapter is avail-ableforpipesizeslessthan1-1/2".Customersuppliedjunctionboxrequired.
† Approved for CSA Class I, Div. 2 groups A, B, C & D and Class II, Div. 2, Groups F, GwhenjunctionboxthatisusedisNEMA4Xratedandcertifiedbyappropriatethirdparty agency for use for that application and hazardouslocationsrating(Div.2)
Kit Includes:1 Compression fitting1 Locknut3 Silicone termination boots1 Pipe standoff1 O-ring1 Self-regulating cable grommet1 Constant wattage cable grommet1 Insulated butt splice 10-12 AWG2 Insulated butt splice 14-16 AWG
Heating Cable
G-68
U SeriesHeat Trace ConnectionSystem Accessories(cont’d.)
UESL Signal Light Kit PCN 394257NEMA4Xratedendsealdesignedtopowerorsealonecableandindicatepoweronwithuni-versalvoltage120-277LEDindicatorlightkitdesignedforusewithSRL,SRP,SRM/EandCWMcables. This model provides water-resistant cable entry and corrosion-resistant wiring enclosure. A pipe strap (PS Series) is required to attach this model to a pipe. Small pipe adapter is available forpipesizelessthan1-1/2".
Kit Dimensions:7"Hx3.25"Wx3.25"D
Kit Includes:1 Pipe standoff1 Self-regulating cable grommet1 Constant wattage cable grommet1 Universal voltage 120-277V LED light assembly2 Insulated parallel splices
UAS Ambient-Sensing Thermostat*PCN 394038NEMA4Xratedjunctionboxdesignedtocon-nectasingleSRL,SRP,SRM/EorCWMcablerun to power and control cable output via am-bientairtemperatureinnon-hazardousareas.This kit provides water-resistant cable entry for one cable, enclosure support, terminal block and a water resistant corrosion resistant wiring enclosure with a 3/4" opening to accept aconduithub(CCH-2orequal).Stainlesssteel sheath probe is 9/16" diameter x 3" long. Switchratedfor22ampsSPDT120-480volts.Operatingtemperaturerangeis-40°Fto160°F(-40°Cto71°C).Temperaturesetpoint0°to225°F(-81°Cto107°C)with10°Fscaledivisions.
* Only approved for ordinary areas.
Kit Dimensions:9.78"Hx8.69"Wx3.6"D
Kit Includes:1 Junction box with DIN rail & terminal block1 Compression fitting1 Locknut1 Silicone termination boot1 Pipe standoff1 O-ring1 Self-regulating cable grommet1 Constant wattage cable grommet
Heating Cable
G-69
acce
sso
rie
san
d c
on
tro
ls
Hea
t Out
put (
W/F
t.)
9
8
7
6
5
4
3
2
1
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150Pipe Temperature (°F)
Cable Output vs. Temperature
AT-1 Aluminum Tape Cable AttachmentsPCN 383355
180’rollaluminumfoilinstallationtapewithpressure sensitive acrylic adhesive. 2-mil thickness with high tensile strength; 2-1/2” wide.200°F(93°C)rating.Minimumap-plicationtemperatures40°F(5°C).
U SeriesHeat Trace ConnectionSystem Accessories(cont’d.)
UBC Line-Sensing Thermostat*PCN 394011NEMA4XratedjunctionboxdesignedtoconnectasingleSRL,SRP,SRM/EorCWMcableruntopowerandcontrolcableoutputviapipetemperatureinnon-hazardousareas.Thiskitprovideswater-resistant cable entry for one cable, enclosure support, terminal block and a water resistant corrosionresistantwiringenclosurewitha3/4"openingtoacceptaconduithub(CCH-2orequal). Stainless steel bulb is 1/4" diameter x 7-1/4" long with 3ft capillary. Switch rated for 22 ampsSPDT120-480volts.Operatingtemperaturerangeis-40°Fto160°F(-40°Cto71°C).Temperaturesetpoint0°to400°F(-81°Cto200°C)with10°F.
* Only approved for ordinary areas.
Kit Dimensions:9.78"Hx8.69"Wx3.6"D
Kit Includes:1 Junction box with DIN rail &terminal block1 Compression fitting1 Locknut1 Silicone termination boot1 Pipe standoff1 O-ring1 Self-regulating cable grommet1 Constant wattage cable grommet1 Line-sensing thermostat assembly
Thermal Output Ratings on Plastic Pipe with Aluminum Tape
Heating Cable
G-70
PS-1, PS-3, PS-10 Pipe StrapsPCN 382352, 382360, 382379
UsedforattachingUPCandUMCkitstopipe.PS-1 1/2”to3/4”pipes(PCN382352)PS-3 1”to3-1/2”pipes(PCN382360)PS-10 2-1/2”to9”pipes(PCN382379)
Stripping ToolPCN 393510
ForSRCables,BladesforHSRLandSRLCablesincluded
Replacement Blades
PCN 393529BladeSetforStrippingHSRMandSRM/ECables
PCN 393537BladeSetforStrippingHSRLandSRLCables
U SeriesHeat Trace ConnectionSystem Accessories(cont’d.)
FT-3 Fiberglass Tape Cable AttachmentsPCN 389941
66’ roll glass cloth installation tape with pressure sensi-tivethermosettingadhesive.3/8”wide.310°F(155°C)rating.Strapatonefootintervals.Minimumapplicationtemperature40°F(5°C).
Tape Type
Rolls Needed per 100' of Pipe
Pipe Dia. (In.)
1/2" 1 2 3 4 6 8
FT-3 0.6 1.2 4 4 6 8 10
AT-1 0.6 1.2 4 6 6 10 12
Use one foot of tape per foot of heated cable.
Conduit Hub w/Grounding LugCCH-2 (385650)
Corrision resistant hub for 3/4" conduit. Fits opening in PJB, DL, U Series and DTS. Includes ground connector.