types ssv-t and ssc-t relays for class ie ......westinghouse i.l. 41-766.5a types ssv-t and ssc-t...

12
Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during ship- ment. Make sure that all moving parts operate freely. Inspect the contacts to see that they are clean and close properly, and operate the relay to check the settings and electrical connections. APPLICATION These relays have been specially designed and tested to establish their suitability for Class IE applications. Materials have been selected and tested to insure that the relays will perform their intended function for their design life when operated in a normal environment as defined by ANSI standard C37. 90 - 197 1, when exposed to radiation levels up to 104 rads, and when sub- jected to seismic events producing a Shock Response Spectrum within the limits of the relay rating. "Class IE" is the safety classification of the electric equipment and systems in nuclear power generating stations that are essential to emergency shutdown of the reactor, containment isolation, cooling of the reactor, and heat removal from the containment and reactor, or otherwise are essential in preventing significant release of radioactive material to the environment. The solid state types SSC-T current relay and SSV-T voltage relay are high seismic relays and suitable for nuclear power staion relaying protection. They are adjustable over a wide range of current and voltage and have a calibrated scale plate which indicates the pick-up setting. The output unit is a telephone relay and an ICS (Indicating Contactor Switch) seal-in device. The type SSC-T and SSY-T relays have a high ratio of drop-out and are particularly suitable for use in applications requiring an accurate current or voltage level detector. CONSTRUCTION The type SSC-T or SSV-T relay consists of a printed circuit board with a transformer, a scale plate, an output telephone relay, and several associated components. The relay is mounted in the semi-flush FT- 1 1 Flexitest case. The relay also includes one ICS (Indicating Contactor Switch) for indication and seal-in purposes. The relay chassis is draw-out construction for easy of test and maintenance. The components are connected as shown m Fig. 4, 5, and 6. Input Transformer - The input transformer is a two winding type with a center tapped secondary winding. The secondary is connected to two full wave rectifiers. Rectifiers and DC Power Supply - There are two full wave rectifiers. One with two zener diodes and a capacitor is used as an input signal and connected to a level detector (setting) circuit. The zener diodes are also used as surge protec- tions. The other full wave rectifier is used as de power supply. For type SSC-T overcurrent relay, a resistor-zener diode is needed in order to keep the current transformer's linearity. Setting Circuit - The setting circuit is con- nected between zener-rectifier and sensing circuit. All possible contingencies which may arise during installation, operation, or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of his equipment, the local Westinghouse Electric Corporation representative should be contacted. SUPERSEDES I.L. 41-766.5 DATED NOVEMBER 1977 EFFECTIVE FEBRUARY 1984 www . ElectricalPartManuals . com www . ElectricalPartManuals . com

Upload: others

Post on 11-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

Westinghouse I.L. 41-766.5A

TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION

CAUTION: Before putting relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during ship­ment. Make sure that all moving parts operate freely. Inspect the contacts to see that they are clean and close properly, and operate the relay to check the settings and electrical connections.

APPLICATION These relays have been specially designed and

tested to establish their suitability for Class IE applications. Materials have been selected and tested to insure that the relays will perform their intended function for their design life when operated in a normal environment as defined by ANSI standard C37. 90 - 197 1, when exposed to radiation levels up to 104 rads, and when sub­jected to seismic events producing a Shock Response Spectrum within the limits of the relay rating.

"Class IE" is the safety classification of the electric equipment and systems in nuclear power generating stations that are essential to emergency shutdown of the reactor, containment isolation, cooling of the reactor, and heat removal from the containment and reactor, or otherwise are essential in preventing significant release of radioactive material to the environment.

The solid state types SSC-T current relay and SSV-T voltage relay are high seismic relays and suitable for nuclear power staion relaying protection. They are adjustable over a wide range of current and voltage and have a calibrated scale plate which indicates the pick-up setting. The output unit is a telephone relay and an ICS (Indicating Contactor Switch) seal-in device.

The type SSC-T and SSY-T relays have a high ratio of drop-out and are particularly suitable for use in applications requiring an accurate current or voltage level detector.

CONSTRUCTION

The type SSC-T or SSV-T relay consists of a printed circuit board with a transformer, a scale plate, an output telephone relay, and several associated components. The relay is mounted in the semi-flush FT- 1 1 Flexitest case. The relay also includes one ICS (Indicating Contactor Switch) for indication and seal-in purposes. The relay chassis is draw-out construction for easy of test and maintenance.

The components are connected as shown m Fig. 4, 5, and 6.

Input Transformer - The input transformer is a two winding type with a center tapped secondary winding. The secondary is connected to two full wave rectifiers.

Rectifiers and DC Power Supply - There are two full wave rectifiers. One with two zener diodes and a capacitor is used as an input signal and connected to a level detector (setting) circuit. The zener diodes are also used as surge protec­tions. The other full wave rectifier is used as de power supply. For type SSC-T overcurrent relay, a resistor-zener diode is needed in order to keep the current transformer's linearity.

Setting Circuit - The setting circuit is con­nected between zener-rectifier and sensing circuit.

All possible contingencies which may arise during installation, operation, or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of

his equipment, the local Westinghouse Electric Corporation representative should be contacted.

SUPERSEDES I.L. 41-766.5 DATED NOVEMBER 1977 EFFECTIVE FEBRUARY 1984 www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 2: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

I.L. 41-766.5A

It consists of two resistors and a potentiometer with a scale plate. The potentiometer has a locking feature to minimize accidential change of setting.

Sensing Circuit - The sensing circuit consists of a transistor, a zener diode, and several associ­ated components. It is actually a level detector. If the input voltage from the rectifier is high enough to break down the zener diode, the output transistor will be turned on.

Output Circuit - The output circuit consists of a transistor driver and a telephone relay. The overcurrent relay (SSC-T) has a telephone relay equipped with 2-A type contacts. The over or under voltage relay (SSV-T) has a telephone relay equipped with 1-A and 1-B t ype contacts.

Indicating Contactor Switch ( ICS) - The In­dicating contactor switch is a small de operated clapper type device. A magnetic armature to which leaf-spring mounted contacts are attached. It is attracted to the magnetic core upon energiz­ation of the switch. When the switch closes the moving contracts bridge two stationary contacts completing the trip circuit. Also during this operation, two fingers on the armature deflect a spring located on the front of the switch which allows the target to drop. The target is reset from the outside of the case by a push rod located at the bottom of the cover.

OPERATION

The block diagrams of the SSV-T and SSC-T are shown in Fig. I, 2, and 3 and the internal schematic are shown in Fig. 4, 5, and 6. For overvoltage and overcurrent application, the transistor Q2 is normally not conducting and the telephone relay is deenergized. The transistor Q I is used as an emitter follower. When ac voltage or current is applied to the primary of the trans­former (T) a voltage is produced on the secondary side that is proportional to the input. The potentiometer ( R2) is for the pick-up setting. If the voltage from rectifier (Z I, Z2, and C2) is large enough to exceed the breakdown voltage of zener diode Z5, the zener diode conducts to turn on the transistor Q2 and operate the telephone relay.

2

For undervoltage application, the transistors Q I and Q2 are normally conducting and the telephone relay is pulled in. As soon as the input voltage drops below the setting, the transistor Q2 is turned off and the telephone relay is re­leased.

CHARACTERISTICS

1. Overcurrent Relay SSC-T

Range

0.5- 2 amps 2.0- 8 amps 4.0- 16 amps 10- 40 amps

Continuous Rating

2 amps 8 amps

10 amps 10 amps

1 Second Rating . . . . . . 28 times the continuous rating

Operating Frequency ... 50/60Hz

Temperature Error . ... 2% between- 20°C and 65%C.

Dropout Ratio . . .. .... 90% to 98%

Response Time . . . . . . . Pickup Time =

10-13 ms Dropout Time =

10-16 ms For 2 to 15 times pickup setting value (Fig. 1 0)

Transient Overreach 5%

Burden . . . . . . . . . . . . . Table I

Frequency Response ... Fig. 12

2. Over/Undervoltage Relay SSV -T

Range . . . . . . . . . . . . . . 60- 140 Volts 140- 320 Volts 280- 640 Volts

www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 3: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

Continuous Rating . .. . Highest voltage of range setting.

Operating Frequency .. . 50/60Hz.

Temperature Error ... . 2% between -20°C and +65°C

Dropout Ratio . . . . .. . . 92% to 9 9%

Response Time . . . . . . . Pickup Time -7-10 ms Dropout Time -14-40 ms (Fig. 9)

Burden .. . . . . . . . .. . . 1 VA at 120 volts 60 hertz

TABLE I (60 hertz)

Pickup Current Setting

Range (Amps) Lowest Setting Highest Setting

VA P.F. Angle'/ VA P.F. Angle_i

0.5- 2.0 0.5 8.5° 4.0 12.SO

2.0- 8.0 0.5 8.5° 5.0 12.5°

4.0- 16.0 0.5 8.5° 5.0 12.SO

10.0- 40.0 0.8 10.0° 8.0 10.7°

Trip Circuit The main contacts will safely close 30 am­

peres at 250 volts de and the seal in contacts of the indicating contactor switch (when supplied) will safely carry this current long enough to trip a circuit breaker. The indicating contactor switch (when supplied) has a pickup of approximately 1 ampere. Its de resistance is 0. 37 ohms.

SETTINGS

The relay must be set for the desired levels of voltage or current. The pickup of the relay is made by adjusting the potentiometer in the front of the relay. Setting in between the scale marking can be made by applying the desired voltage or current and adjusting the potentiometer until the tele­phone relay operates.

I.L. 41-766.5A

INSTALLATION

The relays should be mounted on switchboard panels or their equivalent in a location free from dirt, moisture, excessive vibration and heat. Mount the relay vertically by means of the four mounting holes on the flange for the semi-flush type FT case. The mounting screws may be uti­lized for grounding the relay. External toothed washers are provided for use in the locations shown on the outline and drilling plan to facilitate making a good electrical connection betweer the relay case, its mounting screws and the relay panel. Ground Wires are affixed to the mounting screws as required for poorly grounded or insula­ting panels. Other electrical connections may be made directly to the terminals by means of screws for steel panel mounting.

For detail information on the FT case refer to I. L. 41-076 for semi-flush mounting.

ADJUSTMENT AND MAINTENANCE

The proper adjustments to insure correct operation of this relay have been made at the factory and should not be disturbed after receipt by the customer.

Acceptance Tests

The following check is recommended to insure that the relay is in proper working order. Refer to the internal schematics and apply volt­age or current to the proper terminals.

1. Minimum Trip Current - Check pickup at minimum and maximum settings. This is accomplished by applying the specified voltage or current and checking the pickup of the output telephone relay when the ac input is within ±5% of the settings.

2. Dropout Ratio - After checking pickup, gradually reduce the input. The dropout should be greater than 92% and 90% of the pickup for SSV-T and SSC-T relays respectively.

3 www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 4: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

I.L. 41-766.5A

Indicating Contactor Switch (ICS)

Close the main relay contacts and pass suffi­cient de current through the trip circuit to close the contacts of the ICS. This value of current should be not greater than ICS's rated current. The operation indicator target should drop freely.

The contact wipe should be approximately 0.016 inches. The bridging moving contact should touch both stationary contacts simultaneously.

ROUTINE MAINTENANCE

All relays' calibration should be checked and contacts should be cleaned at least once every year. A contact burnisher S#I82A836HO I is recommended for cleaning purpose. It is recom­mended to change the potentiomenter R2 every ten years.

CALIBRATION

Use the following procedure for calibrating the relay if the relay adjustments have been dis­trubed. This procedure should not be used until it is apparent that the relay is not in proper working order. A new scale plate may be nec­essary when parts are changed.

Dial Calibration - I. Connect on ohmmeter across proper relay terminals which connect to the telephone relay contacts. 2. Apply the desired voltage or current to relay terminals 8 and 9. 3. Turn potentiometer on front of relay counter­clockwise from extreme clockwise position until the relay operates as indicated by the ohmmeter.

Indicating Contactor Switch (ICS) Initially adjust unit on the pedestal so that

armature fingers do not touch the yoke in the

4

reset position. This can be done by loosening the mounting screw in the molded pedestal and moving the ICS in the downward position.

I. Contact Wipe - Adjust the stationary contacts so that both stationary make with the moving contacts simultaneously and wipe I /64" to 3/64" when the armature is against the core.

For double trip ICS units, adjust the third contact so that it makes with its stationary con­tact at the same time as the two main contacts or up to I /64" ahead.

2. Target - Manually raise the moving contacts and check to see that the target drops at the same time as the contacts made or up to I/ 16" ahead. The cover may be removed and

the tab holding the target reformed slightly if necessary. However care should be exercised so that the target will not drop with a slight jar.

3. Pickup - Unit should pickup at 98% of rating and not pickup at 85% of rating. If nec­essary the cover leaf springs may be adjusted. To lower the pickup current use a tweezer or similar tool and squeeze each leaf spring approxi­mate equal by applying the tweezer between the leaf spring and the front surface of the cover at the bottom of the lower window.

If the pickup is low the front cover must be removed and the leaf spring bent outward equally.

RENEWAL PARTS

Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be furnished to customers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data.

www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 5: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

INDICATING CONTACTOR SWITCH

TELEPHONE RELAY

RED HANDLE

TERMINAL

(3516A 14).

Fig. 1. Block Diagram of the Type SSV-T Relay in the Type

FT-11 Case

INDICATING CONTACTOR SWITCH

INDICATING

CONTACTOR SWITCH

I.L. 41-766.SA

CURRENT TEST JACK

TERMINAl..

CHASSIS OPERATED SHOR'TlNG SWITQ-1

(3516A 15).

Fig. 2. Block Diagram of the Type SSG- T Relay in the Type

FT-11 Case

REO HANDLE

CURRENT TEST JACK

TERM IN�

(3517A80).

Fig. 3. Block Diagram of the Type SSG- T Relay (Double Trip)

5 www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 6: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

I.L. 41-766.5A

6

3 -------� r--l!------{:

.. +� ,----=---------1 I

� � Z2

l T

3 1;

CJ<o

.. "'

1

$ t--01

�----!4J -1...--{""' 02

I ��Z4

� C3 Z6t- I I I

-® ICS

1-----0

ICS

10

L ________________ �UIC82�d

Fig. 4. Internal Schematic of the Type SSV- T Relay

*ri4�5�17CB�2�G� 072.-�2 -�8�A7M�P7 S--� S�S �C�"� 1451C82G03 .5 2 AMPS SSC-T 1451C82GD4 4 16 AMPS SSC-T 1451CB2G05 10-40 AMPS SSC-T

® ®

liCS (i)

rig 5. Internal Schematic of the Type SSG- T Relay

CAPAC I TOR

C3 Cl-2

l>10DE

01-2

.JUMPER

JI,J2 TRANS! ST0R

QJ-2

RESl ST0R

R9 R>

R7 •• ••

ZENER

Z4 zs Zl-2 Z6

TEL£ RELAY ssv

POT R2

CAPAC I T0R

C3

Cl-2

UI0DE

DJ-4-5

UJ-2

POT R2

QJ-2

RESI ST0R

R3

R5 R7 RB

•• .. Rl

ZENER

Z3 zs z 1-2

Z6

TELE. RELAY

sse

DESCRIPTION STYLE Nl1o o<470UF >OV 762A680H04

J.QOOUf' 200V 876A<409HIO

DESCRI PT 10N STYLE N0o

IN4821 188A342HI6

DESCRI PTI0N STYLE N8o

0 0HM RESI ST0R 862A478HOI

DESCHIPT10N STYLE N0• 2Nl711 762A58SH08

DESCR1PTI 0N STYLE Nlih

saoo.o �sow 2% 629�53JH49 620QoQ 0 sow 2% 629A53JHSI

JO.QK • sow 22 629ASJIHS6. 36o OK 0 sow 21 629AS31H69

IOQ.QK 0 50\11 21 629A53tH80

DESCHIPT10N STYLE N8o

IN9658 24 v 186A797 HOB IN52J5B 6o8V 862A288H07

L5K£200 200o OV 878A619HOI INJOJSB 4J.OV 188A302H08

541D514H33

15K 763A560H21 CuM . LO�AT ON __ ---- -�"I<>AI

BLOCK DIAGRAM _______ 3516AI4

UESCRI PTI0N

• 470UF 50V

I • OOOUF 200V

DESCRIPT10N

IN914

IN4B21

IOK

DESCIUPTI0N

2N l71 1 DESCRI PT10N

JOOOoO • 501W 2%

6200· 0 • sow 2%

10. OK 0 sow 21

4JoQK • sow 2% IOO.QK • sow 21 470 .Q • sow 2%

620oQ SoOQW .. DESCRIPTION

IN2986B 24 V 1N523SB 6o8V

I,SKE200 200 • OV IN3036A 47.QV

(7758589).

STYLE NO.

762A6BOH04 I:J76A409HIO

STYLE N0o

I:JJ6A928HOt

188AJ42H16

763A560H20

STYLE N0. 762A585H08

STYLE N0o 629AS31H.43 629A531HSI

629A531HS6 629A531H71 629AS31H80 629A531 H24 837A23JH03

STYLE NBo

629A79BH03 862A288H07

878A619HO/ 184A449HOS

54t0514H24

COMP LOCATION ____ 3516AI8 BLOCK OIAGRAM ____ 3516AI5

(7758590).

www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 7: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

I.L. 41-766.5A

Ut::>Cr<I<"TIO:II

•470Ui ':>OV

I·OOOUF 200V

OESCRI PTI _, .... IN9141

P�4821

STYlE N'-1� 762A680H04 tl76A409HIO

ST (Lf.: NQ,. 6 Jo;M�2HHOI l:::ldAJ42Hl6 r-��--+---------+------- -

IOK VLSCrH PTI (}N

2:'111711

Ot:SCrHPTI�N

3000· 0 ·SO\. 2%

6200 • 0 • ::.0:0. 2I

10-0r< • so .. 2%

43.Qt'( • SJ\.' 2t 100-01( • su .. 2%

47Q.Q -SO ... 2I

6£o.a s.oo• 11

Dt::SCtd PTI ON

IN2966B 24V IN52356 6·�V

1.51<£200 200· ov IN3036A 47.QV

763A560H20

STYLE ,..,0,. 762AS'ISH08

STYLE N0. 62?:r.SJIH43

6�'.>ASJIH51

62H.:.JII-IS6

6?-:; �5311"171

62YA')JJHSO

629AS31 H24

037A2JJ.-10J

STYLE :'�!So 629A798H03

862A2ddrl07

878A619HOI

164A449H05

541DSI4H24

COMP LOCATION . __ 3516A18 BLOCK DIAGRAM_ ... 3517ABO

(7758758).

Fig. 6. Internal Schematic of the Type SSG- T Relay (Double Trip)

0

N "'

"' u u

0

(3516A 17).

Fig. 7. Component Location on SSV- T Module

(3516A18).

Fig. 8. Component Location on SSG- T Module

7 www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 8: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

I.L. 41-766.5A

en 0 z 0 0 1&1 en ...J ...J ::IE z 1&1 ::IE t=

8

50

45

40

35

30

25

20

� 15 -

10

5

0 0

I I(

J

I !/ �

� V'

20

TYPICAL T IME CURVES OF THE

/

/ �

/ / �

40

TYPE SSV- T RELAY

( R A NGE 60-140V .)

� lL"

/ .... v

� v /

I --.

60

VOLTS

v

J z

� ....

v

/

I I I

v I -

80

• I

,

L..,...

CURVE NO 619506

80 V. DROPOUT SETTING

(INITIAL VOLTAGE= 120V)

IOOV. DROPOUT SETTING

(INITIAL VOLTAGE= 120V)

80V. PICKUP SETTING

(FINAL VOLT AGE = 120 V. )

IOOV. PICKUP SETTING

(FINAL VOLTAGE =120V.)

100 120

(619506)

Fig. 9. Typical Operating and Reset Time Curves of the Type SSV- T Relay

www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 9: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

(/) 0 z

26

25

24

23

22

2 I

20

19

18

17

0 16 0 w (/) ...J 15 ...J :I; � 14 w :I; I- 13

12

I

10

9

8

0 1: 0

I.L. 41-766.SA

CURVE NO. 619507

, �

/ v

I I " -

TYPICAL O PERATING AND RESET

I TIME CURVES OF THE T YPE

SS C-T RELAY

(RANGE 2-8 AMPS)

r r- RESET TIME • *

NO TE : CURRENT REDUCED T O ,. 0% OF PICKUP AND INTER-

RUP TED AT CURRENT ZER O.

\I/ t-- OPERATING TIME

""

2 3 4 5 6 7 8 9 10 II 12 13 14 15 MULTIPLES OF PICKUP VALUE

(619507).

Fig. 10. Typical operating and Reset Time Curves of the Type SSG- T Relay

9 www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 10: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

I.L. 41-766.SA

10

v 0 I() en iD 0 z ..... > a: ::> (.)

.

I 9

: I ' I ! !

II I II I I i ; I i! II I I I\ l i I i : l i > ..... 0 > Q a:

::> II (.) t!l 0 z

� c::i 1-1- .....

VI I > ::i VI � VI

i I: I I j' i 'cj' i ��' !'-! i i

·· · IHI �fH+

i • I! I i

I i

. . - -. 1- -- - - - � -

I! I

I ! I

VI ..... > 0:: ::> (.) ..... (.) z 0 0.. VI ..... 0:: >-(.) z ..... ::> 0 ..... 0:: LL

> 0 ! I

0 <D >-<( ...J ..... 0:: 1-I >

VI VI

0:: 0 LL

. I' '\.''. � l :

I : · i'-' 1 � - t : : i --_!_:_ f . i

i l

li 'i I i

l t 1 I i! I;, .

i . ,.:-;

H H \H+J-++-'\. I II: ! I! i '\." '-i '·' "i !!·'! · i i· '· i '-i '

I I . ·� ·'-, I i i-i ' ' • i i • \. • � . . . . . i·i.i I .L'�c' ! LLLI\, :\.: . ' ' . •. . u i

I ' if t t; I ! I ! 1 i :! � L ! i j-f:[! ! I i:

I i 1 ':"" i ! i : : : ! i; \-\ i l-1 I ·� I, tr l 1 ;.c -� · §= ::t' ·

']�[fl1tlllJJJJilllttll1lJJJJJilllllllJlJJ!llll11lllJJJlllllll�ll-J+lJilll111lil � Q dn>l:lld Z.1ij3H 09 � 0 0 o o 0 .:10 .1N3:lij3d Nl dn>l:lld N - Q en fD

N 1-0:: ..... X

(619504).

Fig. 11. Typical Frequency Response Curve of the Type SSV- T Relay

www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 11: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

LO 0 LO 01 (j)

0 z LIJ > a: ;:) 0

I.L. 41-766.5A

��::::+r+l+l+J4J4����p:p:��----�++++++++44��=P,C·�· ����II:+=:I:�:JJl I I! I I I I I ! ! ! ! I :!

.

I 9

II 'i I I' I I I I I I iiI i I': 'i ''' i 11'1 II I I I I I I I I iI I iII i i ' I! i i i i I II I l !Ill I I I 1 I i I I I I l

*� -t++t I.L+ � +- � � - li-t-'- +c-t+ -t-1--i+ -H-t-t- -f-+·;-t

I • I , ,

: : : +:-I ':-·H-�Hi-HH a � 1+1--+-H-++++-1++++++. -�-· -+' +l-+:-H�_,:_,w + : : :- + : : ' - jcJ:I JJll I ;:) c;: - - - 'c:J -- : 1� �·J� + I I ' o.: (!) - - - - - - - - - - - !

z EEEEEtEE88��HHBHFH���������� 1;-i= - - - - - - -�=�= ·=.::·

1--+-H-H-++++++++++++++++-H� �� H-++�-���-+�+_+�+-�+_+=+:+.++++-H�-H�_l--+-_�_H-_l·_���-�:�:+_+_+_+=+_ 1

!I i I ! I I I I II I I ! I I

! I I 11 11 I I -:T'-i- .LL I I ' I i I

I I : ! I ' ' I ! I JJ.I ' ' i I I ! I ! i I i I I I I i I I : fi_l ! I i i I Ll

(/) - -- -i I ' I

I I i ' I i i 'i I ' ' ! i i ! ' I I 1

,, ' I �I I ' I J I I I '

I I i I I I·: -!

I I

: I I i I i!

I

i I I

! I. --J-

i • :I

-+++f·++-it+'-+-'-H-H-+'-+1-H-+-+..L.+:+I-1-l- Jti+-H-H-I+�if- I.JILi'i-!:Li:c-1 I I

II H- 'I ! I ll '' t! :iII I; II I I I 1 . 11 1 : 1· , : I , : , , ' , 1 r 1 1 1 r TT 1 1 1 11 .

-- -U -"' •1. -1-+' -i--J-f-+-T-+-,..,-J.;-H..L.ii-1L.L' L1 L.l 1-+--'--"-- c 1-l..i_-'--,-+-i I�' i i: I ;Ti '

_ 1-. _ II' 'lcj i -- -- - - - · -

� 2

----·0 dn>l:>ld ZJ.�3H 09 LO 0 LO

.:10 !N3:>�3d Nl dn>l:>ld � Q ,._

N 1-a: LIJ :J:

(619505).

Fig. 12. Typical Frequency Curve of the Type SSG-T Relay

11 www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com

Page 12: TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE ......Westinghouse I.L. 41-766.5A TYPES SSV-T AND SSC-T RELAYS FOR CLASS IE APPLICATION CAUTION: Before putting relays into service, remove

I.L. 41-766.5A

DIMENSIONS IN INCHES -i6.375 DIMENSIONS IN MM (161.93)

, . 3.188 ••

(80,98) I

PANEL LOCATION �

SEMI-FLUSH MTG. �

.563 (14.30)

tl��)OIA, 4 HOLES FOR ' ,190-32 MTG. SCREWS

PANEL CUTOUT 8 DRILUNG FOR SEMI- FLUSH t.ITG.

(3519A65).

Fig. 13. Outline and Drilling Plan for the Type SSV-T and SSG-T Relay in Semi-Flush FT-11 Case

WESTINGHOUSE RELAY- I NSTRUME NT DIV ISIO N

ELECTRIC CORPORATION CORAL SPRI NGS, FL 33065

Printed in U.S.A. www . El

ectric

alPar

tMan

uals

. com

www . El

ectric

alPar

tMan

uals

. com