types - circuit breaker sales instructions...tvppical outline &onduits or cables. ... gain front...

9
GEK-73020 GEK-73020 Superseder GEH-2021 D Superseder GEH-2021 D TYPES AK-2/3/2A/3A-15 AKT-2/3/50/50S AK-2/3/2A/3A-25 AKU-2/3/2Aj3A-25 AK-2/3/4/5/2A/3A/4A/SA-SO/SOS AKU-2/3/4/5/2A/3A/4A/SA-SO/SOS AK-2/3/2A/3A-75/75S AKF-2/2A-25 AK-2/3/2A/3AdOO/lOOS AKF-2C/2D/2E

Upload: trinhdung

Post on 10-Jun-2018

221 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

GEK-73020 GEK-73020 Superseder GEH-2021 D Superseder GEH-2021 D

TYPES

AK-2/3/2A/3A-15 AKT-2/3/50/50S

AK-2/3/2A/3A-25 AKU-2/3/2Aj3A-25

AK-2/3/4/5/2A/3A/4A/SA-SO/SOS AKU-2/3/4/5/2A/3A/4A/SA-SO/SOS

AK-2/3/2A/3A-75/75S AKF-2/2A-25

AK-2/3/2A/3AdOO/lOOS AKF-2C/2D/2E

Page 2: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

U.&cl r5.J V.0” Magnet ’ \,

250 DC 210-280 1 1.75 0:s 0.15 I I ,\* .- ,,,

I 75 - 85% Lagging

j I600AC

30 - 35% c ‘,, :: ,‘,

I Lagging t Al c: KnQ t i3n I v n I inn I

? 14, I.U I”.”

600 AC 520-635 __ ’ 8.0 5.0 1 :t:

-

.:,,~:’

, ,b . . ( , y,; __ , , ” I : .’

‘* *+ __ , , ~~ : “ ; ~~a.

* Limited to 5.OA continuous &ting of $16 GA. wire on Drawout Breakers, ;z: :‘, : I, :” _\ _. _. ** Adequate for use with AR.Break& Shunt Trip Coils of the voltage :r%ngs listed in above table. (Maximum current of 12.3A for the 120V. A? coil)

\\ : <‘\ .’ :< ‘.

,,+,-- : ,, ‘5, , ‘. ‘1, _’ _. ‘_ _‘, ,’ .‘“;., ,*\ .\ ..+>;p \.

: I’ :A -‘ ,, ‘, *. ‘,;, * __:_ ‘b:: : .,:, ,,: j;,, ,:, ‘.:,,,i,: : ,.,:,:‘ : ,.. ~.‘_ _ ::s;,,:, i_ ::‘

:.; \ : : ,“ _: ; I ,,,,. ; s -\,...‘ *e.. ;,

,, :, ‘:** ,,<” _ \ ,,“: “;‘. _, \’

,, ::: I ,,, :y” : ,c;, ,<, :, ,,, _._ .i;. : y,\ ; .;

,) ,h ; , .,t, 1

Page 3: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

- ?,_ Breaker

Tvppical Outline &onduits or cables. Steps in the prdcedure LJ

c lrawine No. for installing enclosed breakers follow: - ‘\\

In choosing a location for the installa- AK-2-15 and 25 tion offan AK Circuit Breaker, there are AK-3-15 and 25 two factors to be considered. The first AK-2-50 Man. Opera ~” of these is the effect of the location on AK-2-50 Elec. Oper.

_L the breaker itself. Much better oer- AK-s-5’) Fan. QPer* 1dlL 133.3 .-- ^ ,> 3oer. _ 121C7555

695C116 1. If the breaker is an AK-15, AK-25

‘ 12lC7570 or an AK-50, remove it fromthe enclosure.

845C281 With AK-50 breakers, a handle and cam 238C123 arrangement is used for that part of the

.nfmCCrn breaker movement that involves the dis- +

formance and longer life may be expected AK-Y-50 E1ec’* ( - if the area is clean, dry, dust-free, and AKT-2-50 Mm- OP@r. ‘%zzY well ventilated, than if the opposites to

nvm ? Ch:rz.^^ ,-L^._

these conditions exist, The second con- xk‘LL-.J-r)” Nlilll. “paI-.

engagement or engagement of the primary disconnect. AK-75 and AK-100 breakers are bolted solidly to the enclosure frame

sideration is convenience for operation and maintenance. The breaker should be easily accessible to the operator, and there should be sufficient space allowed for maintenance work to be aone if this becomes necessary.

102C3650 rnnrrnnr. IV‘LJDDI 121C7589 121c7590

845C284 269C225

121C7583 121C7557

845C290 ‘-‘269C227 121C7585 121C7559 19*r=?mn

AKT-3-50 Elec. dper. AK-2-75 Man. Oper. AK-2-75 Elec. Oper AK-3-75 Man. Opes AK-3-75 Elec. Oper AK-2-100 Man, Opel AK-Z-100 Elec. Ope: AK-3-100 Man. Oper _ AK-3-100 Elec. Oper. AK-4-50 Man. Oper: l”IVY”“” AK-4-50 Elec. Oper. 134C2601 AK-5-50 Man. Oper. ,_ 134C2610 AK-5-50 Elec, Oper. 134C2611

I : The .surfaee on which the breaker is

mounted must be flat throughout in order not to impose any 1./..~~..1 1.^1. ..I2 .~~ -..

“the breaker unit. Tl must be rigid enough io avoid any pos- ,$ sibility of the breaker studs supporting the - weight of the breaker. Minimum cutom dimensions, as giv outline drawing, must ne n provide adequate electrical clc

and need not be removed from the en- closure.

2. Remove cover plates of enclosure and prepare them to accommodate whatever power entrance means is used.

3, Mount enclosing case to supporting structure,

A K Circuit Breakers are designed to be mounted in any one of three ways.

,These are dead front mounting, individual mounting with the enclosure beingprovided, and drawout mounting in which the breaker is designed for insertion into a cubicle in drawout equipment such as a substation or control board.

4, Replace cover plate and make power connections to stationary terminals in mrlnsure.

DEADFRONTBREAKERS

These breakers are designed for mount- ing in a switchboard or enclosing case of the customer’s design and construction. Mounting in this instance consists of bolting the breaker frame to a supporting structure within the switchboard or enclosure, con netting the power buses or. ‘cables, and making any necessary control cdnnections. The front cover of the breaker enclosure may be a hinged door or a plate bolted to the panel. In either case, it should have a section cut out, through which the front escutcheon of the breake%‘may protrude. Outline drawing numbers giving the dimen- sions needed for preparing .a+~suitable enclosure or cubicle for the various types of A breakers are given below. These

INDIVIDUALLY ENCLOSED BKILAKBKY

en by the appropriate

-.

.

_- _- .__- __ _ supplied with several types of enclosures,

mintaine’d to

most common is the wnx~..nl ,.I,---,. L-a e- the weather resista

earance.

used for favorable

,:a w... . __---

Individu&lv enr&sed hreaknrs RPP

cuit, operate the breaker several times to be sure that it IS functioning properly. (See OPERATION).

AK-4/5-50 breakers which are individ- ually enclosed will have enclosures of the AKD5 drawout type. These breakers will be straight drawout breakers, types AK-4A- 50 and AK-5A-50. (See instructions in this: book nnder the heading. “Drawout Breakers _--__ -..-- AKD5 Equipment”) I’

the latter for outdo~ ~~~..~~.~~~ .~ ..__. ;,;,,locations that may be subject tounfavorable

conditions. All of the enclosures are pi vided with suitable means for mounting wails or supporting framework nemfivll

~‘“‘,czL”‘pu’I;““c ryyc “I

nt type. The former is DRAWOUT BREAKERS AKD EQUlPMENT indoor locations and

or locations or incinor Mounting drawout breakers consists of simnlv olacing the breaker in the proper

=o- pi&ion with respect to its enclosure, sliding or rolling it to a stop position and

. . _“_..*“. ,bfi by means of a racking handle and mechl cover plates are- supplied I.-... I..1 . vith the 411..

are for standard 2 or 3 pole breakers. closures which mm hP Arilld nr marhir ------ --^-a -_ ______- __ ...IY..-. led

anism, racking it through the last part of its

to accommodate the entrance of bus duets, movement during which the stationary and movable halves of the disconnects engage.

\ \ f ‘..

mrernai custorrion on he sunoortine structure 6, Before energi&ng the power cir-

Page 4: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

GEK-7302 Installation and operation of Type AK Power Circuit Breakers

L -- -___-- -~ ,$e~~~~ing‘~~ay which extends out fromthe \ enclosure to receive the breaker, Small

“+ breakers have guides on their side plates which slide in channels in the enclosures. Both large and small breakers have a test

..~ \1 ,’ “:@ ,. nrd+ rlrm~~mtt hriXake*s are fastened to a the breaker carriage. This 1s the safety cause the breaker to be trip free. Tighten

position stop where both the primar and 1

the 3/8 inch hex head screws inserted in the secondary contacts are disengaged. gain front holes of the drawout tray during step lift the position stop handle. Slide the 5 of this operation, The breaker is now in breaker slightly forward to remove it from the operating position. the enclosure. ‘__*_. --. . . w itnarawing Breaker AKi50, 75 %id”i%O Inserting Breaker AK-50, 75 and 100

elease the

I_ position in which the I are engaged, but the are not. In this posi Ln r\snrn+nA n,n”+rinQ

secondary disconnects primary disconnects

tion, the breaker may VG uprr a-L== zi&GCL1 IU dly without energizing the load cable or bus.

IT ncn.TAn ‘--“-icant on the disconnect the force required to

leerz me VredKC1.

1. Trip-:the breaker to r positiverackihg interlock.

2. Lift the’ racking handle as use uwn4 1 iuw I

terminals to reduce ir I II._ LL_^_l_^..

II .-“_ __.. D -. b=fir+in(l. Breaker AK-15 and 25

1. Lift the breaker to a position ap- proximately six inches above the height of the compartment tray. far as it

2. Pull the drawout tray out under the breaker as far as the tray will travel. NOTE - When installing an individual skeleton housing for a drawout AK-500r 75, locate a bolt head over the two front bottom mounting holes of the housing to provide a limit stop for the drawout tray.

Q ‘I ,T.,,PV the, h,.~a~~,. ahnu+ l/2” abc,ve

,.\\ will go. ,, ThiP‘operation w

interlock to the remaind Note that he +A#-

il l re-engage the trip hold the breaker trip-free for

ler of the racking operation. re the cam is rotated by lifting

e handle, whereas in racking the breaker ‘- in, tile operation is p

>‘- 1 erformer, as’s result

of pushing tl- ’ Le nancue down. ‘. _, _,

0, YYWbI -.I- u__I..__ ----_- il.” An7.rnl nine nn the +I-SV and oush the 3. Reset the handle to ‘its lowered ULG U”WLI pL”LY . , . . _.. I I - _j - - -

breaker back into its compartmeit so that position and lift it aa This operation the rear bottom angle of the breaker is .formed 5at&es to completely must be per against the guides on the tray directly back disengage t he cams from their racking of the dowel pins. pins, After the fi fth lifting stroke let the

4. Slowly lower the breaker onto the handle drop to its normal position. tray and at the same time guide it so that the holes in the rear angle of the breaker 4. Pull the breaker out of its com- fit over the two dowel pins on the tray. If ?a rfment until the test position stop engages the breaker is correctlv positioned 01 lthe co hold the breaker in the “test” posit,ion. ; ” -._ -- .._~~ dowels, its rear and side bottom frame i’ angles will all *sit firmly on the tray. 5. Depress the test position stop han- ‘, >:+

5. Insert two 3/8 inch hex, head screws dle and pull the breaker out of its corn-

through the holes in the front of the side partment as far as the drawout ,tray will ~nalae fin the hrnaker and thread them part travel.

1. Trip the breaker.

baker until the guides 2. Raise the bre

,,

,. ‘,

on the sides of the breaker are level with their mating supporting chant iels in the enclosure, and slide the break er part way‘ into its enclosure. (Note - ‘I ‘he breaker will be obstructed by a positior I stop at the bottom of the enclosr ure after the breaker __ has traveled only a E ;hort distance into the cubicle. Lift the J position stop handle, located at the bottom right of the enclosure, which will release * the position stop and

&+^..^I F....+Lnr intr. ikn allow the breaker to navel 1111 Lll=jl I_IIcv Lllr ““,, cubicle). Y \ 3. Raise the rackout handle forward

and up as far as its travel will permit and push the breaker into the enclosure until irt.^ .,- nlrn.l+ mine am thn h~nrllcz aqsmnhlv “Cdl asaruuc CLIb “““r”‘b , --__ “-_ _-___- __. ..-J ----- “~_- -rr--- the side of the enclosmg case. tighten screws fjrmly. This ‘prx . - -. -A../ _-_^- _.

4. Push downward on the I . ’ . .

6. Remove the two 3/8 hex. head screws which hold the breaker on the tray. better alignment 01 me primary s~ailolldl Y

gamut nan- studs and the urimarv disconnects for the : ,‘,a .:. j

a S

- _ . - . . 1 - _ . - _ - - - . - . . -

novement into the en- to prevent further tra;el. (Note f Refler to _ e operator to provide section describing “Test Position” in t to make the primary instructions.) then pull the breake ie stationary studs in orming this operation, 7. Release the test position stop by

primary contacts clea

itc: lever and nush the breaker . . : wards as far as its free travel will permit back>

and then pull the racking handle down to,X,bc-t:,zar,, be sure the trip interlock i-h --,^--^-1P\\ (Note - When the racking handle LL LIL rib position other than completely down, tl breaker cannot be c ..--- L-J ^^-I i^ L,.IA ,peraLeu a‘lu I D I I C I U

trip-free by the trip interlock.- This ap- olies to the “fullv in” and “test” positions.)

n+ rackme cam.

‘Y ----“I

le :“,“,,on the cam” which allows the racnk%E TEST POSITION +r. kn liF+nri nnmrah in o,,nw thp nawl . . __- _--.

to engage the first notch on the cam.

,’ ‘_’ *eaker open. If the . . . ,

8. When the paw1 engages the first notch on the cam, push the handle down again to its normal position. This causes’ the cam to rotate about.the racking pin. Repeat this operation five times to rack the hTr=csko? into its *‘Final noeratin@ nosition.

‘i’he “Test Positio n”, as referred to in the previous mstructn ,ns, is that breaker position where the pri..a-., =-..-- ma7v ~OWPT dincon- -_-_ _. nect contacts are safely disengaged but the secondary control disconnects are engaged. In this position, the breaker may be tested or operated manually or electrically with- ’ out enereiv;“m tho nrimarv newer circuit. se 1. Trip the br

*breaker is not open, the interlocK lever OX ,,* .,y.IA _..-- __I __._ -_ _).

the drawout mechanism will not permit Interlocks hold the breaker trip” free until provided”;hYe”;l”aEi;inerhandit: hss been move6

to the completely down position, thus re- operation of the rackout handle.

it is racked into the fully contactedposition. The fifth stroke of the handle is only a leasing the trip interlock.

up and for- partial stroke and does not result in any further movement of the breaker. It does

disengaging serve three usefulpurposes: itpositions the Foramorecon‘ 1 I” * y disconnects. cam so that it cannot rotate and allow the drawout me

AW3 DRAW 3. Slide the br eaker out until the

breaker to back out under short circuit TI^.-” stresses: the oartial stroke signals that the

2. Pull the racking handle ward as far as it will travel, the primar:

position stop engages in the front slot m the bottom of the breaker carriage. The breaker is now in the “test where its primary disconnects disconnected from tl minals of the enclosure. (Nott section describing “Test Positic instructions.)

--- -----, racking operation is complete; and it re- Innroo +ko twin intnrlnrli which wr,=cnrncrpd

qlete aescrlprlon or chanisms and enclosures see OUT EQUIPMENT INSTRUC-

VIYS, GEH-1830andAKD5DrawoutEquip- ment Instructions GEI-90890.

” position, ITLIYG.3 CIlr CA .p LILLIA * “ - . . , . . . - % . . . 1.11 -“.D-D--

are safely by the racking pin during the previous four pumps of the racking arm, NOTE: Once a DRAWOUT BREAKERS AKD5 EQUIPMENT

le line and load ter- . . ..a. . . ? - Refer to

racking operation has been started, it must NOTE: AKD )n” in these

be completed as the breaker cannot be rn.rnrn~A nn+il the ezickinn oDeration is letter “A” ap .

4. To remove the breaker from its enclosure, lift the position stop handle and slide the breaker forward until the position stop engages the rear slot in the bottom of

9. After completing the fifth racking stroke, lift the handle as high as it will go and allow it to drop to its normal position. NOTE: Any strokes beyond this point will

5 breakers are identlfleo Oy $ :\~ lpearingafter breaker number - *’

example, “AK-2A-15”. ,\ \.,; “V

Drawout Mechanism Operation - There are four positions of the drawout mechanism:

Page 5: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

,,, ‘\ : ‘.

., : :, ‘_ ,,,. ._ _,, ._’ - ,~,’

,. “

GEK-7302 Installation a&‘Operation of Type AK Power Circuit Breakers !., : _\ _’ ;.,<.. “’

3. Rota& the two track lock links, and 2. Move the breaker and inn@? housing to ” b&zker is in the racked in (connected pull the right track all the way forward. the fully withdrawn position. (See position). This interlock, when requested, ,~~‘~~~ ,\ Breaker Insertion. Stems 1, 2 ami 3). will be orovided with both AKD and AKD5

k 4. * Using a lifting device and the spreader ‘\\ provided for these breakers, raise the

breaker and position it SO that the mounting pins on the side of the breaker line up with the slots in the track and are about 2 inches above the track.

, -

i \ \ I \ equipment that require quick close breakers

5. Pull the left track out and lower the breaker so that the mounting pins 1 engage the slots in the tracks.

6.

3. Rotate the two - * . -. track 1OCK mxs and CONNECTIGNS pull the breaker out to the limit of

-. the track travel. Attach; lifting device All electrical connections should %e arid-, lift breakt 3 up and away from made to assure good conductivtty. Mating compartment untilprimar y disconnects surfaces should be parallel and firmly clear the compartment. bolted or clamped together. Contact sur-

faces should be clean and have a smooth I”---- the inner housing to the connected 4. IvI”“t: finish, The bus or cable connecting to the __^^I&< pvaallon by pushing the tracks back breaker should have adequate current- against the track stops and then follow Steps 7 and 8 under Breaker Insertion.

carrying capacity to prevent excessive heating. Control circuit connections should

The inner housing is now in the con- be made according to the wiring diagram . . .,. necrea position and the breaker IS free from its comp;o rtment.

which applies to each breaker specifically. Depending on the breaker type, those con- ,

Breaker Removal A &4A/5A nections are made either to a terminal board on the breaker or to the stationary

Engage the racking handle. This is done by pushing the trip button in the breaker escutcheon. sliding the cover below it __

‘:: to the right, and inserting the handle ,;I#< on the jackshaft. ,.. >‘<. ,, 2,

“‘7, Turn the handle counterclockwise as far as it will go, (if it will move in 1. Trip the breaker. parts of the secondary disconnects. that direction) and remove the handle.

,2, :‘Engage the handle and rotate itcounter- ~D~IDUALLY ENCLOSED AKD 8. Push the breaker in against the track clockwise. If thebreaker closing Spring STATIONARY BREAKERS

stops, and lock the track links. _, ,_ is fully charged, it will be discharged automatically : - 3 - ^.? A....-* Ir^Cr. ‘PC?% nr,~thmorct evtmnsl m-mnections

9. Close the compartment door. Apain the end of the 5 __ ._.~. ~~~~

engage the ha& .¶----a

.e as in step 6, and -l-.r-...l-- ^^ 0,.

3. COUPON uL 1u1115 usluie I,,0 Lu~I”lllr~” .,a*-* .-1 _____- __._..

action. for operation of breakev flnn+roI romnonent! *a -.,‘..a __ --__ _r ______. 9 __- ___- .- and accessories are shown in Fig. 1.

rotate the handle \ CIOCKW~SV ds rar as ^ - . . . 3. .,_^,_ it- I-,.*3. lhnir upen me aoor, umook me ~idti;h HULAS, it will go. Towards the end, a high and pull the breaker all the wa,y forward. DRAWOUT BREAKERS :;i. __.-

’ ,-“force reauirement will be felt as the The breaker may now be lifted from

disconnect fingers on the breaker en- the tracks. _ The customers external con 9 gage the stationary studs. A couple of nections to these breakers are .

turns later, and the stop will be en- NOTE: The installation of AK- ..A,+-3”3, ray me srar~onary Y+~LUIIUL+I y uI.7bvLlllrrc- -... countered. .The position indicator will lOOS/AKF2C/2D andbreakers equippedwith cated in the breaker compartment as shown . .T-_ n ..--I 0 _ _ __ _ ̂ . now show “CONK ” . the q - . ‘- ” li vn Equiprn~~~~~~d Fr:gs+.h% AC,“+

1

uick-closing mecnanlsm 1s me same dS m I ags. L anu Q, A~)U the other breakers descrrbed m this book. and 5 AKD5 Equipn,sJ,b. ls.V’Iu I _... The only difference occurs with drawout breaker is used in a GeneralElectric Corn. breakers. The compartments that house the pany, Drawout Switchgear Equipment, al.. quick-close breakers will be equipped with external connections must be made to an interlock that prevents the manual dis- terminal blocks located in the rear vertical nL~rninrr n$ +kn pjncinc qnylnvq whilp +)a wirin* trnngh nf the eauioment.)

FURNI&ED <3< ONLY WHEN >5> <4 < c /‘- REQUWD \D > 4$ <5<-- -> 3>

,_, ” >2>

WHEN H~WUIKLLJ ‘, : d”,>

-RONT VIEW AK-2A-50,75,100 FRONT VIEW AK - IA+,25 8, AK-Z/4+, 25 ‘: F

BREAKER COMFAHTMENP‘ BREAKER COMPARTMENT ::y

;

6 : \‘.

.>.: \ ” TYPICAL WIRING DIAGRAMS ;\ Fig.‘& __ i5.g. 5

,.,. ..I?

,' I

Page 6: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

Installation and Operation of Type AK Power Circuit Breakers GEK-7302

OPERATIO MANUAL CLOSING

AK-15f25 manually operated breakers breakers are closed by a solenoidcoil. The are closed by turning the handle 90 degrees armature of the solenoid is linked to the

\;;: counterclo&wise anil +hnn nlrwhxrinn CUT breaker mechanism and its movement. L&U _, ,%?

MArlA UIUII~l*I”(I U” degrees back to the original position. The operating through the mechanism closes

2 initial counterclockwise movement resets the breaker . The closing solenoid circuit

-s the closing mechanism. The clockwise may be operated by a push button closing movement closes the breaker, switch on the breaker or by a remote

‘*“’ switch or relav. deoendine on the individual

closes. A charge-indicator, tiumbered 1 to Large AK breakers (AK-50/~~~00) j’ 4, viewed through the breaker front es- are closed by the discharge of a. closing Fig. 8 c-

, ‘ r , ; ,

. ),icutcheon, moves with each complete handle spring. This rotates a crankshaft which, ,t”,i .ysi”“’ movement and indicates the number of ,: -_,_ ., .;b F by means of an attached roller, operates ,.

complete handle movements that have been a closing cam, forcing the movable breaker ” _, 88, ,._ <$ . ., ,~ 1.’ performed. contacts against the stationary contacts. i ‘. _‘:’ The closing spring is charged through the : q_/_ ,,, _a, AK..4/5-50 manual breakers are ~so~.~:~~~~~~atton of a motor and gear reduction

!nergy released through“ ,. energized, operating ‘ihe X contacts. This .

closing spring. The seals in the X relay and energizes the

IIP is dnne by a single The electrical control system is com- motor ohce again and the closing operation This involves prised of an X relay, two double contact takes place.

_...._. -_ _ :ountercbckwise from mechanically operated switches (F and G), : a until a stop is en- a push button closing switch and any means rt 14-i Afvrnec. rlf mta- for remote closing which the user mav

QUICK($LzP DDwAVFD* i ,e 0,

closed by means of e ihe discharge of a charging of the spri.., _- -__. stroke of the breaker handle. raising the handle ( the vertical positiol countered after abol-. _ __ --b- _ __ -_ _ _ __ tion. The spring is then extended to its fully charged position as the handle is re-

*turn&d to its normal vertical position. Release of the spring, and resultant closing of the breaker, occurs when the “close” button in the escutcheon is pushed. (The breaker will close only if the racking mech- anism is in the “CONN” or “TEST”nosition.)

The closing mechanism of the A&2/3 arrangements ” ‘desired. $f

-@hen a closing :’ 50/75/100 manual breakers is a spring signal is given, the X relay coil is ener- charged mechanism similar to the one gized and it in turn closes its contacts. One used on AK-2/3-50/75/105 electrically op- of these seals in the X coil circuit; the _ erated breakers. AK-2,‘3-50 ‘751100 manual other three, whtch are arranged tn.series,“’

<breakers are closed bv rorating the closing energize the solenoid closing coil: As the ,v$& ? handle counterclock&se ttirough approxi- ??$,, mately 120 degrees, and then clockwise

breaker closes, a mechanically operated LEGEND CC- CLOSING RELAY COlL

switch opens one pair of its contacts (bb) 0 - CLOS’NG RELAY CONTACTS .b, \.>>\,, back through 120 degrees to the normal and. closes another (aa). The contacts E - AhTl-PUMP RELAY CONTACTS

F d G- MECHASICALLY OPERATED SWITCHES “ye,> _

\’ which open cut out the X relay coil. The L -LCIIILIARY SWITCH CONTACTS __ _\ :, ‘: \<>i?,

handle position. Four such complete move- ‘- \” ments of the handle are required to close conhcts which close energize the Y relay f$ I Et,“,s!;q$~‘&~ CO,L

the breaker. During ?he four countercloek- coil, whose contacts now seal in the Y coil 1 -COhTRO: RELAY CONTACTS x - CONTW. RELAY CDlL wise movements and the iirst three clock- ‘and hold open the X relay coil circuit. Thts L - I*CRNkLY OPEN SWITCH CONTACTS T wise movements of the handle, the springs prevents another closing operation if one $2 - NORUALY CLOSED SWITCH CONTACTS

2.’ of the protective -devices operates to trip s?

are charged, After approximately 70 de- SIMPLIFIEC: “ELEMENTARY DV-GRAM

2

grees travel of the fourth clockwise handle the breaker before contact at the closing,,” “:,‘<\ %TERN&t WIRING OUICK CLOSE BREAKER movement, the spring charged mechanism switch is released. * - is driven over-center and the breaker z

incorporate into thhe system. When voltage is first applied to the breaker, (before any closing signal is given) the motor is ener- gized through two of the X relay contacts and the two G switch contacts, The motor then compresses the closing springs to the ‘pre-charged” position at which point the mechanically operated F and G switches

Functionally, the quick close mech- anism differs from the stand-- - lard electrical mechanism in that the pre-charge operat ’ ion is extended to completely charge the clos springs, At the end of the,charging ape] ing tion, which takes approxitiatelv 5 secon (2 seconds for -4/5-5(

:op roller to prevent n discharging.

a&a\ clostng of thk break&--When push button or remote switch signals for With

AK-15 and AK-25 electrically onesated a closing operatton, the X relay eoii is tllc - .._

ICAL CLOSING are operated. This opens Ihe G contacts, plate engages the pl

(Figures 6 and 7) stopping the motor, and closes the F con- closing springs fro1 &cts. which readies the svstem for the \

e _-I- the closir ? breaker is read7 . . -^1^...“^ ^f LL..”

Ig springs fully charged r for a closing operation

upVll Ie~c-d~c VI MC: prop roller. This mav

: EGENO

1 X * X RELAY COlL

P * X RELAY COWTACT

1% Y RELAY COIL

be accomplished either manually, by de- pressing the closing lever on the breaker, or electrically by closing the remote closing switch. Upon the release of the prop roller the closing springs discharge and close the breaker in the-same ma&&r as ;,,, on the standard electrical breaker. AK-4/5-

2: 50 breakers are closed through a remote d switch or the close button in the escutch-

eon, (if the breaker is equipped with a push button clos‘ing switch).

\ _\ \_ *‘+*, i_ _:_ ~, . .

LEGEND

iii, = CLOSING MOT,-- v z = RELAY COIL ry * RELAY CONTl

FGG = MECHANICALLY vr~n.. I c

With control voltage applied, the motor is energized through the G switch contacts, and charges the closing springs. When the

eT _,,_ ,-$+:‘- springs reach the fully charged position, ----^-FO~SWIT&ES

the mechanically operated switches operate, -,...^r...:..” +l.^i- -,..-&(,ts . Upon operatton he motor-is stopped by G switch. The elostng spares the breaker for

y 8 1”6bA” C”r l IACI ” e. + = NORYALLY QPEhl SWITCH CONTACTS

IcYlT‘3LIIg LIICLI G”P ..-_..^ . ..-.. --ERILTED SW,PCHE* of these switches t ..-..---_. -. -.. iwlTCn : # ’ NORMALLY CLOSED SWITEH CONTACTS the opening of the

. NORMALLY Cl.@SED SWITCH CONl’A,XS :‘=?:, L - AUXILIARY SWlTCtf CONTACT of the F switch prl Fig. 6 Slnoll"ied~ Elem1tary Diagram

_: : Intmxai iirin~ M-1 j and ?j

kg. 7 Simplifieu Xlrmentary Diagram a closing operation.

Internal Wiring h-50, 75 and 100 ,,‘;, ,,., (_ __;, __ / ,* _’ _,.\. _’ ,+:, ‘vp2$ *’ ,‘ \ 7

: : ‘:.:\ ;: .’ ” ., _’ .: 1

Page 7: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

/_’ ‘:%/‘I

CEK-7302 -a Installation and Operation of Type AK Power Circuit Breakers ‘_

; ,.& ‘$9 “li \ ,”

,&, ,,h, i ‘%. ,ng signal:now given energizes relay X whose contacts close

.-. +s.n ni..n..i+ l I.r,-..,,dl tl-.n “,,-mi”” a> i’[email protected] -z L.l‘.z b&I GULL nnrvugu “&C ti.‘“Y...b j, relay coil. With the closing relay coil

energized the breaker closes as described above. At the same time the closing relay (.%A”+ “I#.^“,. 4” n..nrninn Chn -.n+,-nr,mn

,I ,,9,: position), due to mechanic%designed inter-’ breaker. All of the means provided icr ference between the enclosure and the tripping the breaker operate through striker cnrintr r?iar.hsrma lmwr’nn the breaker. If arms which disnlace th- -=nkn*+e- +*i* - - “ . . . . -~- - “ . - - “__ ____ __ _____ _ _

z&z closing is desired with the breaker __ -.._ . ._. - - . . . - -c-- . - . . -G ‘I‘~~-IILuIIU“I ** ‘p

latch by moving against trip paddlesfasteaed racked‘in, the interference feature must be on the trip shaft. Looking at the breaker removed, otherwise the breaker can be from the right, counterclockwise rotation mam~allv rlnaerl in thra tent nnsitinn nrfullv of the trio shaft causes tl== h-nobnr +A +-in. ,,,uILL ~~“cs.z~ C ” .z,‘r;L~LYF u1.z L”~.-y..“‘~ - - - . - - - - I -J -_-II_ -* . .._- - - - -

r-------- 4lav causing its contacts to reverse pro- racked out position only, nti-pump feature.

1.

_~.~. ~~ -llzi VIFMCL C” CA&p,

clockwise movement resets the mechanism latch, The manual trip button, overload devices, shunt trip, undervoltage tripping device, and reverse current trip all operate in this fashion to trip the breaker. The movement of the striker arms of all of these, when : l/32 to l/16 i

bctivated, should move from rich beyond the point at which

tripping occur ‘S. This is what is meant by the expressior L, “positive tripping”.

rt-, _---. viding the a

When the breaker closes, the mechani- With the ratchet type maintenance hand- le applied to the gearbox shaft, operate

cal operated G switches close to energize the handle until the springs are fully the motor again and the F switches open charged. The fully charged position is and de-energize the control relay. The indicated by the spring charge mdicator auxiliary switch contact opens preventing and by solid resistance to any further the control relay from being energizeduntil handle operation. the breaker is tripped open. With the G

$? switches closed, the motor charges the 2* Push down on the push to close lever to closing springs ready for the next closing release the energy stored in the closing operation. springs which closes the breaker’s con-

tacts.

NOTE: BEFORE MAKING ANY ADJUST- MENTS TO TRIP DEVICE SETTINGS, THE BREAKER SHOULD BE IN THE OPEN POSITION AND CONTROL POWER RE- MOVED,

Most AK-2 and AK-4 air cil: ers are equipped witi . .

ecuit break- n series overcurrent

trip devices eltner of the dual magnetic type (instantaneous and time delay tripping) or instantaneous alone. Breakers are designed to carry up to 100% of the con- , ,. of their tripdevices.

higher currents for :, ’

,ill cause overheating * j /

MANUAL OR MAINTENANCE CLOSING OF ELECTRICAL BREAKERS To close AK-4/5-50 breakers:

iy be closed NOTE: ‘AK-4A and AK- 5A drawout breakers will kn ~~Crin-Croc? “if+h~~~~FG-in~*m~chlnicm All electrical breakers in: manually by means of the maintenance handle furnished with the breaker or switch- gear. .:

To*%lor

“ill vc c’*p-‘Auu aa b..” ‘Ly”*yL.6 I . . \ I ” . . I . . - I . . .

is in anv nosition other than the “TEST” or “CONN” position. If the breaker is on a workbench or on the extended rails, and i+ in +n kn mlnnarl mrith +hn maintansnro

se AK-15/25 breakers: IL I Y I ” WC b&“YIU -IL&s Cl,” illl~...“..~.--

handle, operate the drawout mechanism mwous current raring *v Place the two small hooks of the handle as far as it will go in a clockwise direction. Any attempt to carry

into the two slots located in the lower This will putthe mechanism in the “connect- a prolonged period w -,...+:,w. rre +ha PrnnC an”r.+nhnnn nrl” nncitinn anal thphrpalrpr,,,hpclnspri. and possible damage.

G ” “V S”“ “ . b” I ^ ” -*“““____““_“_ =-- ____._

before it can be reinserted into the breaker compartment in the enclosure. Sensor* ereaKe’* ,,“,“,‘,,,“~,,~

time current band a

All AK-3 and AK-5 type air circuit T...__ 7 _^_.^ -..111 L- -quipped with Power trip devices. The

s well as the pickup e are adjustable. A

“e ullllllu screw adjusts all three 1--r ---+‘-,llar characteristic or

1.: Place the maintenance handle on settings of this devic the end of the camshaft below the motor. single cap&p- *L*,-1-. c

phases for ally pai LL~;L 2. Operate the handle until the closing setting, Should a ‘...--...- - --

spring goes over center and the breaker advertently left loose the Power closes. If the breaker is a “quick-close” will revert to the “minimum” pickup breaker, type AK-4/5-50S, the spring will or “maximum” time delay bands nnt FC~~PQCL ~mnn cmina nv~r center. hut inrrlv. Tf after installatior -**ir-rr*fi

Sensor* setting- accord- +,GV.*i,,m

r ”

q& ~‘:,~‘~,: pJ~U”,l UI u,r llVllL CYIIL.CI..\I”..O

“i 2. -: ._ Rotation of the long end of the handle ‘_____ downwards forcf ?s the shorter end of

the handle upwal rds against the bottom of the -_,_.._Ii soienolo armature, and closes the bre !aker’s contacts,

To close AK-2/3-50/751100 breakers: Place the ratchet “‘type maintenance handle on the shaft that protrudes from the gear reduction unit. ‘&^^^1^ L^‘.rll^ ..-a.;, ‘I.” o,.&mrs nln..nn

1.

0 A‘ILuL.*b”I 1 c!aua LU‘al scuo ..--* -” ..--- --- -., - -- ” - ---. _ D ------ __.. . “rl‘Y”I L”I &!‘Ly”a i

rate handle until the can be released by pulling forward on the se%,gs as required for the specific appli- nlndno* canlcnnirl armatllre lncnted beneath ration and tighten all the +h-ymh a*raw~ nn

, , , ; /g* - “perarc l‘aL,uAF “LlUl U & C uy’rllg bA‘alCjr ‘A”. A ” * “ . . - ” My”.. D”-.bD 1. - - - - - - - - - I --~~

8, i i..Ai^,.*^.. . . ^ “A” “%.“ . .? . “A will ho hnlrl nff hv ‘II .hlnrkinv link. This

Pi “/ I,,, i~3. ?‘, Continue to ope

“--‘-*‘e I”_“..“__ _____ -_-__ ___-. -.. ..~~~~ 5 : -\ closing springs discharge and close the the mechanism. This can be done safely, “\ contacts. ,,,<,since no moving parts are located in this _ . . ‘,:space.

To close AK-50S/75S/lOOS, AKF2Ci. ,‘I_ 2D breakers and brr-‘---- ^e...;-.e^rl .,,:*L. TRIPPING the mzirk rlnsinp rn~r1

the Power Sezsor*.

For a more detailed discussion of the construction, operation, and application of nvarmlrrcd tri* rimriroa --o--L- LL^l^“^*...

:aKeI-L) cqupyI;u WlLIl “ . . . - - . . “>.. .--= - - . _““L zT:1er L” L&It2 IU I IUW-

- . - ~--“*- “ - - - - - -D . ..--.mnism. I’ * The breaker is tripped open by the &snlawrncwt of a mechanism latch. which

ing publications:

1. Maintenance manual for specific breaker mvolved (see “Rlmin+nn”nn.P”\ I . “ I U . & X I & rl’u.2, “a -ALA. , - ” “‘.““““’ ‘Jy- l‘l”“LI”LG L.“IICLIULY A/‘ U S I . . A ” I ” . . r ” I - - - “ - - _- - - - - - - - - \ Lal‘lCFllcLllrr ,.

breakers equipped with the quick closing collapse. This trip latch is fastened mechanism cannot normally be closed man- rigidly to a trip shaft which runs hori- 2. “Selection and Application of Pow- uallv when in the racked in (connected zontallv from left to right through the er Circuit Breakers” GET-1113.

,

_ ~!n Fuse Lockout Device , , , : , . ‘,~

*” left hand side of the breaker (looking from latched in the closed air cay --- m-r r------- -G- J---1-- ---_ be fureghedwif$ my front). The purpose of this device is to allowing the reset butt< m to extend forward

akers. The open fuse trip the breaker upon the blowing of anyone indicating which fuse hi 1s blown, and simul- icIe Lollalurs of 3 separately oper- of the breaker fuses. This energizes the taneouslv ho1 iding the breaker in the trip- !S (one per breaker pole) each coil of the device causing the armature to fre e position until the latch closed armature

_II FU 111 ,,rallel to corresponding breaker engage the trip paddle, thereby tripping the is released by the operating of the manual ” ;‘fuses.’ These devices are mounted on the breaker, Once operated, the armature is reset button. ‘;,

TYPE AKU

Ooe 1‘11t3 LievIce rrray

of the above type bre lockout devj-- I.---~-+ ated device ~X,i,.,s4 in Y.”

:AKER CO

Page 8: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

, , , , ,

‘j __,

‘, __ : __ ‘” , \

: ‘_ \_ __ , , ,c : ; . , .s , “

‘~~ - \ _, \ ;*e,

, ,

Installation and Operation of Type AK Power Circuit Breakers GEK-7302 ,,+ ,::.@ _ :. ‘% j ;,, ,,t> ‘. ” I”“.%

“‘. ‘:‘ .._ t>\ .,.><$.~ l_l_ MAINTENANCC. ~INiT IONS ?,j ,),_ - ,,’

; ‘.‘;: ,, ., ._ ; ‘,

& j ‘\‘ ,, .,*,r‘.

* \ ‘a\\%~\, *\\ ,,> INSPECTION

i J : 4, Inspect arc quenchers and contacts .‘.

BEFORE INSPECTION OR ANY,,,,&ZAIN- shorting, or redacing p&s of the breaker,

for breakage or excessive burning. TENANCE WORK IS DONE, BE SURE THAT

refer to the complete instruction for the

THE BREAKER IS IN THE OPEN ‘~PGSI- Should arc quencher barriers or contacts particular breaker type involved. These

be eroded to half their original thickness are:-

;;?N&RAy”L ELECTRICAL POWER, BOTH AND CONTROL SOURCES they should be replaced. Maintenance Breaker Type

SHOULD ALSO BE DISCONNECTED. Manual LUBRICATION

\, ‘_ GEI-50299 AK-2/2A/3/3A-15125, AK Perioaie inspection of the circuit In general, the circ& breaker&e-” GEI-g3353 U-2/2A 3/3A-25

breaker is recommended at least once a quires moderate lumbrication. AKF-2 2A-25 / ‘year, Morefrequent inspections are recom-

Bearing points and sliding surfaces should be lub- GEK-7303 AK-2/2A/3 3A-50/75/103,

i ::;*, mended, if severe load conditions, dust, ricated at the regular inspection periods AKU-2/2A 3/3A-50 / 3::. ‘,’ moisture, or other unfavorable conditions with a thin film of GE Lubricant D50H15. AK-2/2A/3/3A-505/75S/

exist. Before lubricating remove any hardened lOChS, AKF-2C/2D/2E

Always inspect the breaker after a grease and dirt from latch and bearing GEK-7301 Power Sensor Solid State

short circuit current has been interrupt&, surfaces with kerosene. ALL EXCESS Test Instructions :

At the time of inspection, the following A CLEAN CLOTH TO AVOID ANY AC- LUBRICANT WHOULD BE REMOVED WITH GEK-7310 AK/AK&4/5-50/5OS checks should be made after,the breaker CUMULATION OF DORT OR DUST. GEK-7309’ I; has been de-energized.,

Test I&ructions for In- I ‘:‘,,-i,,

On drawout breakers, the contact sur- stallation or service of

1. Manually operrite the breaker Power Sensor Equipped several times, checking for obstructions face of the disconnect studs should, be ’ AK breakers or excessive friction, cleaned and greased with GE Grease Specifi-

cation D50H47. Renewal parts bulletins for the various ‘~2. Electrically operate the breaker -,~:rz:s types of breakers are:

several times (if breaker has electrical These instructions have as their purr- * i: .__

pose the imparting of information of a - Bulletin “*<::,

‘~3 control) to ascertain whether the electrical Breaker Type

,, ,‘~ : attachments are functioning properly. general nature concerning the installation

:s

:?\‘ .a( GEF-4149 AK-2-15/25 ’ _ ii,,: ” ” and operation of Type AK power circuit

breakers. GEF-4150 AK-2-50

,_’ 3. Remove the arc quenchers by re-

If more complete and specific GEF-4395 AK-2/2A/3/3A-75 ’ information is required, such as might be

moving the channel shaped retaining bar. GEF-4396 AK-2/2A/3/3A-109

: needed for overhauling the breaker, trouble GET-4527 AK-4/5-50

_ ;; ,, ,. j ’ :,

‘_ ,> . . .’ Ib. : _ .‘. : ,, .,,~ _’

.,, ,,,__ ,,,. :~’ ! .;,1,,,;. ~”

: “y ,+.

” “/ “,;,, ;,;.:z \

. . ., \. ,. :” ‘y;\~, ,\: __ ._ ze5~,;,~;>, \ ,, ,,‘; s: i, yy *~ ‘. “‘& .~, ““y;, \ i ___\ \ \\ ” /, ,, :; ,” ,:

..c ‘: ‘)‘,

‘“. ,, .j :‘ _”

:,< :

* .c, :.

.:!S .’ ‘; ,’ ‘_ _ ‘S;,. ‘?, ,,_ ..I j ‘. : .,, ‘: :

..‘,’ ‘*~:>..< ‘,’ ,’ \. : ,.. \ ..‘ ,,I

j ’ ‘// : .,. _ ‘:‘, ‘, ,? .“,:. i(,i- :;__ _‘:_ ‘**\ ;, j __,

.-:. -;,;;:, ” __ ‘X&J y;,,, ,_ &j,, ,: .’ : ‘, “,“::\:, ‘_ .‘\

,_, :.,,. :’ ,:,,,

,, y ,,, ~~ . . . . . . “\ ,:\, _ ,,

j: \_ ;:, \\a, .‘~ \ .,, ‘>‘, .*, ,,.::

: _I > ‘.:\ ,,’ ,,

\;;;* _/,3 : __ _.,

L ,-: ;,, 1. I % , ,,:

;;j,y ,, ., .,- ,j _c,, 8:: .~‘,

**\s ‘_, ” :‘:.~> ‘: __, y\-\, ~: ‘..

.A’ ‘. ., $7; ,~.;,‘~” ,,, ’

.\i -I.= .X8\ i. ‘ i

:I-., ,,, z ; _, r: ‘.-

\, ,. A”,,.,.;\ .,:,::.-.“ *’ ,.,. 9 ! 9

,.. .,“, .: ,,i

:\ I

Page 9: TYPES - Circuit Breaker Sales Instructions...Tvppical Outline &onduits or cables. ... gain front holes of the drawout tray during step ... the load cable or bus

This information is distributed for information purposes only and Group CBS does not warrant the accuracy or reliability of any informatian contained herein. Copyright to this information remains the property of the original manufacturer.

IEf vou need additional infor ation or service. dease call us at:

Email

Be sure to check out other resources at:

ox 1098, Gainwvik, TX 76240