As a covered entity under Title II of the Americans with Disabilities Act, the City of Los Angeles does not discriminate on the basis of disability and, upon request, will providereasonable accommodation to ensure equal access to its programs, services and activities. For efficient handling of information internally and in the internet, conversion to thisnew format of code related and administrative information bulletins including MGD and RGA that were previously issued will also allow flexibility and timely distribution ofinformation to the public.
Page 1 of 7
TYPE V SHEETONE STORY CONSTRUCTION ONLY
Type V construction is a classification of builidings by construction materials and methods. It is theleast restrictive permitted by the Uniform Building Code and includes light, wood-frameconstruction. This sheet is for information and reference only and is not a substitute for accuratedrawings prepared for each proposed construction project. LA City’s Type V-sheet is the same asthe attached Type V sheet by LARUCP except hereby clarified with respect to note 5 on “Footingson Expansive Soils”.
FOOTINGS ON EXPANSIVE SOILS
Footing systems on expansive soil shall be constructed in a manner that will minimize damageto the structure from movement of the soil.
1. Depth of footings below the natural and finished grades shall not be less than 24 inchesfor exterior and 18 inches for interior footings.
2. Exterior walls and interior bearing walls shall be supported on continuous footings.3. Footings shall be reinforced with four 1/2-inch diameter deformed reinforcing bars. Two
bars shall be placed 4 inches from the bottom of the footing and two bars within 4 inchesfrom the top of the footing.
4. Concrete floor slabs on grade shall be placed on a 4-inch fill of coarse aggregate or on amoisture barrier membrane. The slabs shall be at least 3-1/2 inches thick and shall bereinforced with ½" diameter deformed reinforcing bars. Reinforcing bars shall be spacedat intervals not exceeding 16 inches each way.
5. The soil below an interior concrete slab shall be saturated with a moisture to a depth of 18inches prior to placing the concrete.
INFORMATION BULLETIN / PUBLIC - BUILDING CODEREFERENCE NO.: LABC 91.2320 Effective: 1-20-00DOCUMENT NO. P/BC 2002-004 Revised: 6-11-02 Previously Issued As: IB ST- 9
Notes:1. Anchor bolts: 5/8"x10" embedded 7" and spaced 6'-0"oc with 2-1/2"x2-1/2"x1/4" plate washers, with minimum 2 anchor bolts per piece, located not more than12" or less than 7 bolt diameters from each end of the piece.2. All foundation plates or sills and sleepers on a concrete or masonry slab, which is in direct contact with earth, and sills that rest on concrete or masonry foundations, shall be pressure treated wood. 3. Minimum Concrete Strength: 2500 psi.4. Bearing walls and braced wall panels require continuous footings.5. FOR EXPANSIVE SOIL: Refer to local jurisdiction requirements.6. Where interior walls are shear wall panels, wall framing and sheathing shall extend to the roof sheathing.7. Under floor areas shall be ventilated by approved mechanical means or by openings into the under-floor area walls. Such openings shall have a net area of not less than 1 square foot for each 150 square feet of under-floor area.
Openings shall be located as close as possible to corners and provide cross ventilation. the openings shall be approximately equally distributed along the length of at least two sides. Corrosion resistant mesh w/ Minimum 1/4" openings.8. Enclosed attics and enclosed rafter spaces shall have cross ventilation for each separate space . The net free ventilating area shall not be less than 1/150 of the area of the space ventilated.
The openings may be 1/300 of the area provided 50% of the opening area is provided with ventilators in the upper portion at least 3' above the eave or cornice with the balance of the ventilators provided by eave or cornice vents. Provide baffles to prevent attic insulation from blocking eave vents. (CBC 1505.3)
9. For stem walls greater than 24" high: Refer to local jurisdiction requirements.
SEE NOTE 'A'
TYPE V CONSTRUCTION IS A CLASSIFICATION OF BUILDINGS BY CONSTRUCTION MATERIALS AND METHODS. IT IS THE LEAST RESTRICTIVE PERMITTED BY THE UNIFORM BUILDING CODE AND INCLUDES LIGHT, WOOD-FRAME CONSTRUCTION. THIS SHEET IS FOR INFORMATION AND REFERENCE ONLY AND IS NOT A SUBSTITUTE FOR ACCURATE DRAWINGS PREPARED FOR EACH PROPOSED CONSTRUCTION PROJECT.
Page 2 of 7
FOUNDATION DIMENSIONS SHOWN BASED ONNON-EXPANSIVE SOILS
LOS ANGELES REGIONAL UNIFORM CODE PROGRAMTYPE V CONSTRUCTION- WOOD FRAME RESIDENTIAL BUILDINGS (CBC CHAPTER 23, DIV IV, SEC. 2320) ONE-STORY CONSTRUCTION
NOTES: A. STUCCO SHALL BE PROVIDED WITH A CORROSION-RESISTANT WEEP SCREED.
12"
1/2" CDX PLY SHEATHINGW/ 8d @ 6"/ 6"/ 12" oc (COMMON NAILS)
2x ROOF RAFTERS W/ R-30 BATT. INSUL.
2X CEILING JOISTS
2X SOLID BLOCKINGW/ FRAMING ANCHOR EA. BLOCK
DOUBLE TOP PLATE
WALL SECTION: SLAB-ON-GRADE CONSTRUCTION
WHERE STUCCO IS APPLIED OVER PLY SHEATHING- PROVIDE 2-LAYERSGRADE 'D' PAPER UNDER LATH
3" C
LEAR
12"
6"
7'-6"
MIN
. (HAB
ITABL
E ROO
MS)
2X4 STUD WALL @ 16"oc(DF STUD GRADE- MINIMUM)R-13 BATT INSUL.1/2" STRUCT I PLY, OSB, OR STUCCO SHEAR PANEL (SEE PAGE #4)
2X P.T. SILL W/ 5/8"¯ X10" A.B. @ 6'oc, 2-1/2"x2-1/2"x1/4" PLATE WASHERS
3-1/2" CONC. SLAB, 6X6-10/10 WWM(SEE NOTE #5 FOR EXPANSIVE SOILS)2" SAND BED, 6 MIL VAPOR BARRIER
#3 DOWELS @ 24"OC, EXTEND 36" INTO SLAB(FOR TWO POUR)
#4 BAR, TOP/ #4 BAR, BOTTOM(SEE NOTE #5 FOR EXPANSIVE SOILS)
NAT. GRADE
4" C
LEAR
FOR
EXPA
NSIV
E SOI
L
SEE N
OTE #
5
E.N. 8d@6"oc
CONC. PAD
6" Min.12"
FOUNDATION DIMENSIONS SHOWN BASED ON NON-EXPANSIVE SOILS
3" MI
N.
6"6"
Min.
12" M
IN.
12" SQ.
5/8" T&G PLY W/ 10d @ 6"/ 6"/ 12" oc(COMMON NAILS)
2X SOLID BLOCKING
2X FLOOR JOISTS @ 16"oc
6"12
" MIN
.
6"
6"
18" M
IN.
12"
2X P.T. SILL W/ ANCHOR BOLTS ANDPLATE WASHERS
#4 BAR, BOTTOM
#4 BAR, TOP
2X RIM JOIST
2X4 STUD WALL @ 16"oc (STUD GRADE)
R-13 BATT INSUL.1/2" STRUCT I PLY, OSB, OR STUCCO SHEAR PANEL (SEE PAGE #4)
2X CEILING JOISTS @ 16" OC
2x SOLID BLOCKING2X DOUBLE TOP PLATE
1/2" CDX PLY W/ 8d @ 6"/ 6"/ 12"
2x ROOF RAFTERS @ 16"OC W/ R-30 BATT. INSUL.
R-19 BATT INSUL.
CEILING JOIST- LAP@ BEARING WALL
WALL SECTION: RAISED FLOOR CONSTRUCTION
2X BLOCKING@ 8'-0" OC FORJOIST SPANSOVER 8'-0"
POURED CONC.PIER W/POST BASE
4X4 P.T.POST W/ POST CAP
4X GIRDER
6"
6"
12"
AT JOIST SPLICELAP 3" MIN. W/ 3-16d
2X P.T. SILL & ANCHOR BOLT
INTE
RIOR
BEA
RING
WAL
L
3'-0" MIN.
FASCIA BOARD
2X BLOCKING W/ FRAMING CLIPS@ EACH BLOCK
EXTE
RIOR
BEA
RING
WAL
LNAT. GRADE
NAT. GRADE SEE N
OTE #
9
PRO
PERT
Y LI
NE
E.N. 8d@6"oc
12" MAX. AT 3'-0" SETBACK(CBC 503.2.1)
30" MIN. ATWALL WITHWINDOWS(CBC 1204)
EAVES EXTENDING CLOSER THAN 3'-0" TOPROPERTY LINE SHALL BEOF 1-HR CONSTRUCTIONOR HEAVY-TIMBER(CBC 705)
LARUCP/TYPEV1.2 12/2001
ALLOWABLE SPANS FOR DF #2 ROOF RAFTERS (DF-LARCH) Light Dead Load (up to 15 psf)/
Max. Roofing Load: 6 psf (Asphalt Shingles)Live Load: 20 psf
24" 8'-8"2x6 16" 10'-8"
12" 12'-4"24" 11'-0"
2x8 16" 13'-5"12" 15'-6"24" 14'-0"
2x10 16" 17'-2"12" 19'-10"24" 17'-0"
2x12 16" 20'-10"12" 24'-1"
ALLOWABLE SPANS FOR DF #2 CEILING JOISTS (DF-LARCH)Dead Load: 5 psf/ Live Load: 10 psf
JOIST SIZE SPACING ALLOWABLE SPAN24" 9'-10"
2x4 16" 11'-3"12" 12'-5"24" 14'-9"
2x6 16" 17'-8"12" 19'-6"24" 19'-0"
2x8 16" 23'-4"12" 25'-8"
2x10 12" 26'-0"
Live Load: 40 psfJOIST SIZE SPACING ALLOWABLE SPAN
2x6
2x8
2x10
2x12
ALLOWABLE SPANS FOR DF #2 FLOOR JOISTS (DF-LARCH) Light Dead Load (up to 10 psf)
Max. Flooring Load: 1.5 psf (Carpet orVinyl)
24"* 8'-2"16" 9'-9"12" 10'-9"24"* 10'-2"16" 12'-7"12" 14'-2"24"* 12'-8"16" 15'-0"12" 17'-4"24"* 14'-4"16" 18'-0"12" 20'-6"
ALLOWABLE SPANS FOR DF #1 FLOOR GIRDERS (DF-LARCH)Max. Floor Dead Load: 15 psf Max. Tributary Width: 8'-0"
SPAN GIRDER SIZE
5'-8" 4x6
7'-4" 4x8
PARTITIONS NO PARTITIONS
5'-3"
6'-10"
ALLOWABLE SPANS FOR DF#1 HEADERS (DF-LARCH)
Maximum span of tributary load: 20'-0"
SPAN BEAM SIZEUp to 4'-0" 4x4
4'-1" to 6'-0" 4x6
6'-1" to 8'-0" 4x8
8'-1" to 10'-0" 4x10
10'-1" to 12'-0" 4x12*
RAFTER SIZE SPACING ALLOWABLE SPAN
ALLOWABLE SPANS FOR PLYWOOD OR OSB FLOOR AND ROOF SHEATHING CONTINUOUS OVER TWO OR MORE SPANS-PERPENDICULAR TO SUPPORTS
24/0
24/16
32/16
40/20
48/24
7/16, 1/2
7/16, 1/2
15/32, 1/2, 5/8
19/32, 5/8, 3/4, 7/8
23/32, 3/4, 7/8
24
24
32
40
48
20
24
28
32
36
4050
40
40
45
30
40
30
30
35
16
16
20
24
* 4x12 DF No.1 may be used over a 16'-0" garage door in one-story garages without ceilings or open patio or carport structures.
SHEATHING GRADESSPAN RATING
Floor/Roof Span
MAX. SPAN (IN)
EDGE SUPPORTNO EDGE SUPPORT
LOADS (PSF)FLOORROOF
SPAN THICKNESS
TOTAL LOAD LIVE LOADMAX. SPAN (IN)
NOTE: APPLIES TO PANELS 24" OR WIDER (UBC SEC. 2312)
Panel edges with tongue and groove joints or with blocking
FOR 1/2", MAX. SPAN +24"(2X BLOCKING)
JOIST TO SILL OR GIRDER, TOE NAILBRIDGING TO JOIST, TOENAIL EACH ENDSOLE PLATE TO JOIST OR BLOCKING, TYPICAL FACE NAILSOLE PLATE TO JOIST OR BLOCKING, AT BRACED WALL PANELSTOP PLATE TO STUD, END NAILSTUD TO SOLE PLATEDOUBLE STUDS, FACE NAILDOUBLE TOP PLATES, TYPICAL FACE NAILDOUBLE TOP PLATES, LAP SPLICEBLOCKING BETWEEN JOISTS OT RAFTERS TO TOP PLATE, TOENAILRIM JOIST TO TOP PLATE, TOENAILTOP PLATES, LAPS AND INTERSECTIONS, FACE NAILCEILING JOISTS TO PLATE, TOENAILCONTINUOUS HEADER TO STUD, TOENAILCEILING JOISTS, LAPS OVER PARTITIONS, FACE NAILCEILING JOISTS TO PARALLEL RAFTERS,FACE NAILRAFTER TO PLATE, FACE NAILBUILT-UP CORNER STUDS2" PLANKS
3-8d2-8d16d @ 16"oc3-16d per 16"2-16d4-8d, TOENAIL, OR 2-16d, END NAIL16d @ 24" oc16d @ 16" oc8-16d3-8d8d @ 6" oc2-16d3-8d4-8d3-16d3-16d3-8d16d @ 24" oc2-16d @ EACH BEARING
NAILING SCHEDULE (CBC TABLE 23-II-B-1)
3 LARUCP/TYPEV1.2 12/2001
STUDS
TOP PLATE
SILL PLATE
HEADER- FULL STUD WIDTH BEARING
TRIMMER- USE 2 TRIMMERSWHEN SPAN IS 8'-0"OR MORE @ BEARING WALL
KING STUD- USE 2 KINGSTUDS WHEN SPAN IS5'-11" OR MORE @ BEARING WALL
HEADER/ LINTEL (CBC 2320.11.6)
4
(FOR ROOF PITCH NOT LESS THAN 4 VERTICAL TO 12 HORIZONTAL)
4 MIN. SLOPE
12
4 MIN. SLOPE
122X RIDGE BOARD2X ROOF RAFTERS
2X SOLID BLOCKING2X DOUBLE TOP PLATE2X STUDS
1X RAFTER TIE @ 4'-0" OC
RAFTER TIES (CBC 2320.12.6)
PURLINS (CBC 2320.12.7)
2X PURLIN- SAME SIZE AS RAFTER2X4 BRACE @ 4'-0" OC4X4 BRACE FOR LENGTHS OVER 6'-0"
2X RIDGE BOARD2X ROOF RAFTERS
2X SOLID BLOCKING2X DOUBLE TOP PLATE2X STUDS
2X CEILING JOISTS
INTERIOR BEARING WALL
45°MIN.
25'-0" MAX. BETWEEN BEARING WALLS WITHOUT ENGINEERING
NOTCHING & BORING: WALL STUDS (CBC 2320.11.9/ 2320.11.10),RAFTERS/CEILING JOISTS (CBC 2320.12.4) FLOOR JOISTS (CBC 2320.8.3)RIDGE (CBC 2320.12.3)
ROOF SLOPE- COMP SHINGLES (CBC TABLE 15-B-1)
NOTCHING & BORING RAFTERS & CEILING JOISTS(NOTCHING NOT PERMITTED IN MIDDLE 1/3 OF RAFTER OR JOIST SPAN)
ROOF SHEATHING
2X RIDGE BOARD- 2" LARGER THAN ROOF RAFTER
2X ROOF RAFTER
4:12 MIN. SLOPE W/ 1-LAYER TYPE 15 FELT2:12 TO 4:12 MIN. SLOPE WITH SELF-SEALING OR HAND-SEALEDCOMP. SHINGLES W/ 2-LAYERS TYPE 15 FELT
'D'
2" MI
N.2"
MIN. 'D'
NOTCHING & BORING FLOOR JOISTS(NOTCHING NOT PERMITTED IN MIDDLE 1/3 OF JOIST SPAN)
D/6 M
AX.
D/6 M
AX.
D/4 M
AX. 'D'
'D'
2" MI
N.2"
MIN. 'D'
D/6 M
AX.
D/6 M
AX.
D/4 M
AX. 'D'
D/3 M
AX.
'D' MAX.
BEARING PARTITIONS NON-BEARING PARTITIONS
25% MAX. 40% MAX.40% MAX.
5/8" MIN.5/8" MIN.
60% MAX. OR EACHBORED STUD DOUBLED.NOT PERMITTED IN MORETHAN 2 DOUBLE D STUDS
1/3 'D
'1/3
'D'
LARUCP/TYPEV1.1 12/2001
2'-8" MIN. 2'-8" MIN.
CONT. DOUBLE TOP PLATE
HEADER
STRUCTURAL PANEL SHEATHING:1/2" STRUCT I PLY OR OSB W/ 8d @ 6"/ 6"/ 12"(COMMON NAILS)
SOLID BLK.- ALL UNSUPPORTEDPLYWOOD EDGES
P.T.D.F. SILL PLATEMIN. 2 ANCHOR BOLTS PER PANELMAX. 12" & MIN. 5" FROM BREAKIN SILL PLATE
10'-0
" MAX
.
ALTERNATE BRACED WALL PANEL (CBC 2320.11.4 AS AMENDED BY LARUCP )- 1-STORY, 'U' OCCUPANCY ONLY (PRIVATE GARAGES, SHEDS, & AGRICULTURAL BUILDINGS)
3"
BOLT
DEP
TH
1/4 OF PANEL WIDTH
FOOTING
1/4 OF PANEL WIDTH
4X4 EACH SIDE OF PANEL
HOLD DOWN EACH SIDE OF PANEL (1800# MIN. CAPACITY)-THICKEN FOOTING AS REQUIRED FOR BOLT EMBEDMENT DEPTH(NO HOLD DOWN REQUIRED FOR PANELS EXCEEDING 48" IN WIDTH
#4 TOP & BOTTOM
5
25'-0" MAX'H
' (HEIG
HT O
F PAN
EL)
'H' FOR STUCCO BRACED WALL PANEL
BRACED WALL PANEL'H'/2 FOR WOOD
SHEAR WALL OPTIONS:1/2" STRUCT I PLY W/ 8d@ 6"/ 6"/ 12" OC OR OSB (COMMON NAILS)7/8" STUCCO O/ WOVEN WIRE OR EXPANDED METAL LATH W/ NO.11 GA. NAILS, 1-1/2"X7/16" HEADS W/ 1/4" FURRING; APPLIES TO NAILING AT ALL STUDS, TOP & BOTTOM PLATES, & BLOCKING.
STANDARD BRACED WALL PANELS (CBC 2320.11.3)
8'-0" MAX. FROM END OF WALL
NO PENETRATIONSPERMITTED INBRACED WALL PANELS
NOTES:SHEAR WALLS SHALL NOT BE OFFSET MORE THAN 4'-0" FROMEACH OTHERSHEAR PANEL TYPES SHALL NOT BECOMBINED IN THE SAME LINE OF RESISTANCE
96" MIN.
48" MIN.
MINIMUM PANEL LENGTHS:PLYWOOD PANELS: NOT LESSTHAN 25% OF BLDG. LENGTHSTUCCO PANELS: NOT LESSTHAN 50% OF BLDG. LENGTH
25'-0" MAX.
25'-0
" MAX
.
25'-0" MAX. BETWEEN BRACED WALL PANELS IN EACH DIRECTION
LARUCP/TYPEV.1.1 12/2001
CONC.FOUND. WALL
FLOOR GIRDER
P.T. SILL
1/2" CLEAR- ALL SIDES,END, AND TOP
3" MIN. BEARING
GIRDER (CBC 2320.7/ 2306.6)TRENCHES AT FOOTINGS
24" MIN.
PER MANF.RECOMMENDATION
PER
MAN
F.RE
COM
MEN
DAT
ION
44" M
AX
44" M
AX.
EMERGENCY ESCAPE/ EXIT WINDOW (CBC 310.4)EMERGENCY ESCAPE/ EXIT WINDOW (CBC 310.4)
SINGLE CASEMENT: 2-4 x 4-0 2-6 x 3-6 DOUBLE CASEMENT: 4-8 x 4-0CASEMENT/ FIXED COMBO: 7-0 x 4-0
SINGLE/ DOUBLE HUNG: 3-0 x 5-0 3-0 x 5-6 3-4 x 5-0 3-8 x 5-0 4-0 x 5-0 SINGLE/ FIXED COMBO: NONE W/O MANF. DATA
SLIDER: 4-0 x 4-0 5-0 x 3-6 6-0 x 3-0SLIDER/ FIXED COMBO: 8-0 x 4-0 10-0 X 4-0 12-0 X 3-0
NOTE: SIZES ARE TAKEN FROM DATA SUPPLIED BYWINDOW MANUFACTURERS, HOWEVER THESE AREGENERAL DIMENSIONS. IT IS THE OWNERS RESPONSIBILITY TO VERIFY THAT THE ACTUAL WINDOWS INSTALLED MEETTHE MINIMUM EGRESS REQUIREMENTS.
OTHER WINDOW TYPESAWNING: NONE W/O MANF. DATABAY W/ FIXED CENTER: NONE W/O MANF. DATA
STANDARD 6'-8" HEADER HEIGHT
THE FOLLOWING WINDOW SIZES WILL BE THE MINIMUM ALLOWED FOR EGRESS UNLESS MANF. DATA IS SUPPLIED
1'-6" MIN.
45°
8"6"
WIDTH OF FOOTING xWIDTH OF TRENCH(MIN. SLEEVE + 18")
PIPE D
IA. +
2"
6" MI
N.
NO P
IPES
THIS
ARE
A
PIPE
DEP
THS
TO 3
'-0" M
AX.
BELO
W F
OO
TING
BOTT
OM 1
/3TO
P 1/3
4"
SEISMIC STRAPS: TWO MIN.DSA APPROVED SEISMIC STRAPSAPPLIED PER MANF. SPECS
GARAGE FLOOR
WATER HEATERS
NOTE:NO GAS-FIRED WATER HEATERALLOWED IN BEDROOMS, BATHROOMS, CLOTHES CLOSETS,OR ANY SPACE OPENING INTOA BEDROOM OR BATHROOM.
RAISE
18"
INGA
RAGE
EXTE
RIO
RW
ALL
T&P VALVE PIPED TO EXTERIOR3/4" MIN. PIPE. NO THREADS ALLOWED IN BOTTOM OF PIPING
6" M
IN/.
24" M
AX.
6
20" CLEAR
41" C
LEAR
24" C
LEAR
34-1/8" CLEAR
44" M
AX.
1. 20" MIN. CLEAR WIDTH
2. 24" MIN. CLEAR HEIGHT
3. 5.7 SF MIN. OPENABLE AREA
FLOOR LEVEL
OPENABLE
AREA
OPENABLE
AREA
MIN. SIZE WINDOW
FOR 20" CLEAR WIDTH
MIN. SIZE WINDOW
FOR 24" CLEAR HEIGHT
12" M
IN.
ROOF SLOPE: FLAT TO <6:12
PRO
PERT
YLI
NE
4'-0" MIN.
VENT
FOR
ROOF
SLOP
E:
FLAT
TO
<6:1
2
6 LARUCP/TYPEV1.2 12/2001
7
LIVING
BEDROOM
HALL
DINING
KITCHEN
GARAGE
SD
SD
SD
SD
SMOKE DETECTORS: (CBC 310.9)IN SINGLE FAMILY DWELLING UNITS SMOKE DETECTORS ARE REQUIRED WHEN THE VALUATION OF AN ADDITION, ALTERATION, OR REPAIR EXCEEDS $1000.00.IN NEW CONSTRUCTION, 120V WITHBATTERY-BACK-UP SMOKE DETECTORS ARE REQUIREDIN EXISTING CONSTRUCTIONBATTERY-OPERATED DETECTORS ARE PERMITTED LOCATE SMOKE DETECTORS IN BEDROOMS,AND HALLWAYS OR ADJACENT ROOMS LEADING TO BEDROOMS
WHERE GARAGES ARE ATTACHED TO THE RESIDENCE,THE WALL ON THE GARGE SIDE SHALL BE PROTECTEDWITH 5/8" TYPE 'X' GYP. BD.
THE DOOR SHALL BE A SELF-CLOSING, TIGHT-FITTING1-3/8" SOLID CORE DOOR. (CBC 302.4)NOTE: THE GARAGE SHALL NOT OPEN INTO A SLEEPING ROOM.
BEDROOM
LIGHT : (CBC 1203.2)ALL HABITABLE ROOMS, EXCEPT BATHROOMS, KITCHENS, ANDLAUNDRIES REQUIRE NATURAL LIGHT BY MEANS OF EXTERIORWINDOWS OR SKYLIGHTS @ 1/10 THE FLOOR AREA OF THE ROOM, OR 10 SF MINIMUM, WHICHEVER IS GREATER.
VENTILATION: (CBC 1203.3)ALL HABITABLE ROOMS, EXCEPT BATHROMS, ANDLAUNDRIES REQUIRE NATURAL VENTILATION BY MEANS OFOPENABLE WINDOWS @ 1/20 THE FLOOR AREA OF THE ROOM, OR 5 SF MINIMUM. (NATURAL VENTILATION MAY BE SUBSTITUTEDWITH MECHANICAL VENTILATION).ALL BATHROOMS REQUIRE NATURAL VENTILATION BY MEANS OF OPENABLE WINDOWS @ 1/20 THE FLOOR AREA OF THE ROOM, OR 1-1/2 SF MINIMUM. (NATURAL VENTILATION MAY BE SUBSTITUTEDWITH MECHANICAL VENTILATION, AS NOTED IN EXAMPLE).
MINIMUM ROOM DIMENSIONS: (CBC 310.6)AT LEAST ONE ROOM 120 SFALL OTHER ROOMS EXCEPT KITCHEN 70 SF WITH A MIN.DIMENSION OF 7'-0"
12"X12"TUB ACCESS
70" HIGH NON-ABSORBENTFINISH @ SHOWER WALL (CBC 807.1.3)
24" MIN. CLEAR INFRONT OF TOILET (CBC 2904)
ALL WINDOWS WITHIN 24" OF DOOR SHALL BE TEMPERED(CBC 2406.4) SHOWER & TUB ENCLOSURES SHALL BE TEMPERED (CBC 2406.4)
WINDOWS AT SHOWERS & TUBS SHALL BE TEMPERED,IF LESS THAN 60" ABOVE A STANDING SURFACE AND DRAIN INLET (CBC 2406.4)
BATHROOMS MAY HAVE MECHANICALVENTILATION PROVIDING5 AIR CHANGES PER HOUR(CBC 1203.3)
18"X24"UNDERFLOORACCESS(UBC 2306.3)
22"X30" ATTIC ACCESS, OR 30"X30" IF FURNACE IS IN ATTICAND EQUIPMENT WILL NOT PASS THROUGH 22"X30" ACCESS.MIN. HEADROOM IS 30". (CBC 1505.1 & CMC)
RESIDENTIAL REQUIREMENTSLARUCP/TYPEV1.2 12/2001
PIPE BOLLARD OR OTHERPROTECTIVE MEASURE WHEN APPLIANCES ARESUBJECT TO DAMAGE.2" MIN. DIA.
WASHER & DRYER- DRYER VENT4"¯ MIN.; 14' MAX. W/ TWO 90° BENDSFOR METAL DUCT; 6' MAX. FORFLEX DUCT CONNECTOR
PER L
OCAL
ZON
ING
ORDI
NANC
E
30" MIN.
ALTERNATE 18"X24" UNDERFLOOR ACCESS FROM EXTERIOR