With a large installed base and proven track record, the PMRI breaker offers unequalled performance and reliability.
ABB Advantage• Compact, lightweight design reduces foundation requirements and saves construction costs• High performance interrupters in a definite purpose breaker reduce potential for overvoltages caused by restrikes during capacitor bank switching • One-piece interrupter assembly simplifies field change-out whenever end of life is reached by eliminating need for internal tank mounting of separate parts and alignment• Fully-integrated spring-hydraulic operating mechanism is self- lubricating and self-damping. It is also hermetically sealed to the atmosphere, which eliminates corrosion and helps provide maintenance-free performance with long term stability • Externally accessible current transformers enable simple field change-out without degassing breaker and bushing removal• Extensive range of available field services, from technical assistance to turn-key installation, can dramatically reduce construction costs and speed time to commercial operation
Type PMRI, 242 kV, up to 40 kAPower Circuit Breaker
Standard Features• Dead tank design, with one 3-cycle 40-kA self blast interrupter per tank on a galvanized steel frame• National Board certification of interrupter tanks per the ASME Pressure Vessel and Boiler Code• All tanks factory leak tested in a hard-vacuum chamber with a helium mass spectrometer• Certified per ANSI C37.04, C37.06, and C37.09 Standards• Three maintenance-free HMB-1 spring-hydraulic mechanisms• Frame mounted NEMA-3R steel control cabinet protected with TGIC polyester powdercoat finish• Density monitor and temperature-compensated pressure gauge directly-mounted on each tank• Porcelain bushings• Continuous current ratings through 4000 A• Ships fully assembled and factory tested with 5 psig SF6
gas
(bushings removed for export transit)
Options and Accessories• Switching Control Sentinel (SCS) for reduction of switching transients• Condition monitoring with the Circuit Breaker Sentinel (CBS)• Extra creep and/or extra strike bushings for special applications• Silicone rubber composite bushings• Tank heaters for operation in ambient temperatures below -30º C• High seismic designs
3xHMB-1.0 Mechanism Three type HMB-1 spring-hydraulic mechanisms are located within the 242PMRI breaker control cabinet. Each mechanism drives a separate interrupter to provide independent pole operation. A stack of disk springs within each unit stores mechanical energy. That energy is hydraulically translated through an operating shaft to open and close the contacts of its respective interrupter. Spring charge is automatically maintained by a universal motor and pump. Each fully-integrated mechanism is self lubricating and hermetically sealed, affording excellent reliability and long term stability.
Doc
umen
t N
umb
er -
2G
NM
11
00
09
/ M
arch
20
10
For more information please contact: ABB Inc. High Voltage ProductsWestmoreland Distribution Park East100 Distribution Circle Mount Pleasant, Pennsylvania, USA Phone: +1 (724) 696-1500 Fax: +1 (724) 696-1502 www.abb.com
Rated Capabilities
Circuit Breaker Type
Rated Maximum Voltage (kV, rms)
Short Circuit and Short Time
Current (kA, rms)
Maximum Continuous
Current (A, rms)
Rated Interrupting Time
(Cycles)
Full Wave Withstand Voltage
(kV, Peak)
Power Frequency Insulation
Withstand Voltage (kV, rms)
2 µ-sec Chopped Wave Impulse
Voltage (kV, Peak)
Closing and Latching Current
(kA, Peak)
242PMRI40-20 242 40 2000 3 900§ 425§ 1160 104
242PMRI40-30 242 40 3000 3 900§ 425§ 1160 104
242PMRI40-40 242 40 4000 3 900§ 425§ 1160 104
§ 1050 kV full wave withstand voltage with 460 kV power frequency withstand rating optionally available
171” (4348)SHIPPING AND INSTALLED WIDTH
94 1/2” (2400)MAX. DIM. FOR BUSHING REMOVAL
83 1/2” (2119)PHASE SPACING
83 1/2” (2119)PHASE SPACING
70” (1784)METAL TO METAL
74 1/8”(1883)HGT. OF
BREAKERCOUNTER
AND POSITIONINDICATOR
68 5/8”(1743)SPRINGCHARGE
INDICATOR
CONDUIT ENTRANCE 83 5/8”(981)
82 7/8”(2105)MOTOR
COUNTER
122”(3099)
MINIMUMBUSHINGHEIGHT
179”(4547)
LIVEPARTS
190 1/4”(4832)TOP OF
TERMINALPAD
198”(5029)
INSTALLEDHEIGHT
23”(584)
ADDITIONAL HEIGHTREQUIRED FORBUSHING REMOVAL
106” (2692)MAX. DIM. FOR BUSHING REMOVAL
101” (2565)SHIPPING LENGTH
68” (1728)METAL TO METAL
64”(1625)
BUSHINGSTRIKE
153”(3870)
SHIPPINGHEIGHT
220”(5588)
MIN. DIM.FOR
BUSHINGREMOVAL
45 1/4”(1149)
LEGEXTENSIONS
96 1/2”(2451)
HEIGHT TOCENTER
OF BREAKER
102 1/2” (2604)CLEARANCE TO REMOVE INTERRUPTER
RUPTURE DISC
MINI MONITOR
2KVA XFMR
12”(305)